www.nidec-asi.com
Medium Voltage Soft StartersMedium Voltage Soft Starters
3,3 KV3,3 KV -- 4,16 KV4,16 KV -- 5,5 KV5,5 KV6,6 KV6,6 KV -- 11 KV11 KV
PPT2013.01.01.16EN
2www.nidec-asi.com
HighlightsHighlights
. Designed to start induction motors in any fixed speedapplication
. Ensures smooth, step less control of acceleration.
. Designed to eliminate mechanical shocks and toreduce
inrush current to protect both motor and load.
. Designed for safety and power quality immunitywith high level insulation circuit via optical fibers.
NEW NIDEC ASI digital soft starters STAT:
PPT2013.01.01.16EN
3www.nidec-asi.com
Identification CodeSTAT X X X X X X X X X X X X X
Productseries
Current Design Supply voltage Motor protectionrelay option
Soft starter cabinet option Line cabinetoption 1
Line cabinetoption 2
ProfibusCommunication
Option
080 = 80 A
160 = 160A
260 = 260A
350 = 350A450 = 450A
600 = 600A
(1)
S =standard
M = marine
3K3 = 3300VAC
4K16 = 4160VAC
5K5 = 5500VAC
6K6 = 6600VAC
11K0 =11000VAC
(1)
A = not included
B = included0 = no bypass contactor
(2)
1 = bypass contactor (3)
0 = no linecontactor
1 = line contactor
0 = none
1 = MV fuses kit(4)
2 = MV switch +groundswitch
3 = MV switch +groundswitch +MV fuseskit
0 = no Profibusboard
P = Profibus board
(1) Other range consult factory(2) incoming and outgoing lines inside soft starter cabinet ( no line cabinet if no option 1 andno option 2 )(3) incoming and outgoing lines inside line cabinet ( line cabinet even if no option 1 and nooption 2)(4) available only for soft starter protection and not motor protection in case of bypasscontactor not integrated
For other options ask to the factory
Example : STAT350M6K6A113Soft starter 350 A, marine design, 6600VAC, motor protection relay not included, bypasscontactor included, line contactor included, MV switch + ground switch + MV fuses kitincluded ( soft starter cabinet + line cabinet with options 1 and 2 )
PPT2013.01.01.16EN
4www.nidec-asi.com
Power Ratings
Voltage Output ratings (KW)
80 A 160 A 260 A 350 A 450 A 600 A
3300 V 400 710 1250 1600 2000 2800
4160 V 500 900 1600 2000 2800 3550
5500 V 630 1250 2000 2800 3550 4500
6600 V 710 1600 2500 3150 4500 5600
11000 V 1250 2500 4000 5600 7100 9000
3,3 KV – 4,16 KV – 5,5 KV – 6,6 KV – 11 KV
*
= continuous current*
PPT2013.01.01.16EN
5www.nidec-asi.com
Voltage
(V)
SOFT STARTER CABINET
(Standard)
LINE CABINET(With optionalcomponents)
H (mm)W
(mm) D (mm) H (mm)W
(mm)D
(mm)
3300 V 2340 800 1000 2340 800 1000
4160 V 2340 800 1000 2340 800 1000
5500 V 2340 800 1200 2340 800 1200
6600 V 2340 800 1200 2340 800 1200
11000 V 2340 800 1400 2340 800 1400
3,3 KV – 4,16 KV – 5,5 KV – 6,6 KV – 11 KV
Size And Configurations
PPT2013.01.01.16EN
6www.nidec-asi.com
BYPASSCONTACTOR
S OFT STARTERM ODULES
LINE CON TACTOR
HV FUSES KIT H V SW ITCH +G ROU NDS W ITCH
HV SW ITCH +GRO UNDSW ITCH + HVFUSES KIT
INCO M ING
Soft StarterCabinet option
Standard Soft Starter
L ine Cabinetoption 1
L ine Cabinetoption 2
One Line Diagram
PPT2013.01.01.16EN
7www.nidec-asi.com
MV FUSESMV FUSES
MOTOR ANDMOTOR ANDLINELINE
TERMINALSTERMINALS
BYBY--PASSPASSCONTACTORCONTACTOR
POWERPOWERMODULESMODULES
EXAMPLE :EXAMPLE :STAT250M6K6A101STAT250M6K6A101
Technical Key Points
PPT2013.01.01.16EN
8www.nidec-asi.com
THYRISTORTHYRISTORINTERFACEINTERFACEFIRINGFIRINGBOARDBOARD
OPTICALOPTICALFIRINGFIRINGBOARDBOARD
PULSEPULSETRANSFORMETRANSFORME
RR
HEAT SINKHEAT SINK
STANDARDSTANDARDSOFTSTARTESOFTSTARTE
R CABINETR CABINET
POWER MODULE n THYRISTORSPOWER MODULE n THYRISTORS/ PHASE/ PHASE
SNUBBERSNUBBERBOARDBOARD
Technical Key Points
PPT2013.01.01.16EN
9www.nidec-asi.com
Motor and Soft starter Protections:. Line loss protection. External protection ( remote stop,… ). Over current. Watchdog protection. Stall protection
Programmable configuration :. Soft starter main data. Analog / digital inputs and outputs. Current limit and regulation. Protections and alarms. Monitoring
Technical Data
PPT2013.01.01.16EN
10www.nidec-asi.com
Communication : Profibus as option board
. Input voltage tolerance ± 10%
. Frequency 50/60 Hz ± 5%
. Control signals fiber-optically isolated from HV signals
. Remote control with dedicated digital inputs (24Vdc and 230Vac).
. Remote monitoring with dedicated digital outputs (dry contacts).
. Current limit: adjust. 100 – 3/400 % In ( ask to the factory )
. Ramp-up time: adjust. 1- 30 sec.
. Numbers of starts : 2/3 per hour at maximum conditionsaccording to the motor data
. Standard design ambient temperature : 0 to 40°C
. Degree of cabinet protection: IP32
. Cabinet color : RAL7035
. Cable entry : bottom – front side (other consult factory)
Technical Data
PPT2013.01.01.16EN
11www.nidec-asi.com 11
. Design ambient temperature : 45°C
. Tropicalized boards
. Tin copper bus bars
. Voltage tolerance: +6/-10% permanentand +/-20% transient (1,5s)
. Frequency tolerance: +/-5% permanent and +/-10% transient (5s)
. Main electrical components type approvedby marine registers (ABS, Lloyd’s, Rina, DNV…)
. Vibration and inclination testing
. Power supply variation testing
Marine Option: Technical Data
PPT2013.01.01.16EN
12www.nidec-asi.com
Maintenance :. Lifting eyebolts and handling truck. Door locking and padlocking facilities. Soft starter isolation capability by hand-removable bus bars(configuration with internal or external bypass contactor)
. Full voltage Direct On Line option(in case of soft starter failure, motor can be startedin direct on line mode bypassing soft starter)
Maintenance: Technical Data
PPT2013.01.01.16EN
13www.nidec-asi.com
Low Voltage Compartment
PPT2013.01.01.16EN
14www.nidec-asi.com
Standard:Standard:
1. Buttons:
• Emergency Stop. ( 1 )
• Lamp Test. ( 2 )
• Reset Fault. ( 3 )
2. Signal lights :
• Soft Starter Bypassed (green) - ( 4 )
• General fault (red) – ( 5 )
• Auxiliary voltage alive (white) – ( 6 )
• Bus Bar Alive Upstream MVCB – ( 7 )
Options:Options:
1. Buttons:
• “Direct On Line” Selector – ( 8 )
• Others in accordance with line cabinet options1 & 2.
2. Signal lights:
• “Direct On Line” Mode – ( 9 )
• Others in accordance with line cabinet options1 & 2.
1
2
3
9
456
7
86
Low Voltage Compartment
PPT2013.01.01.16EN
15www.nidec-asi.com
Dialog Interface
LED 7LED 7SegmentsSegments
Key to selectKey to selectgroups orgroups or
functions, or tofunctions, or toselect / changeselect / change
parametersparameters
LCD ScreenLCD Screen
2 lines2 lines
Key to confirmKey to confirmor to reach theor to reach themenu of downmenu of down
levellevel
Key to reachKey to reachthe menu of upthe menu of up
levellevel
Local monitoring :. Metering. Parameters setting. Fault display. Hardware status monitoring
Low Voltage Compartment
PPT2013.01.01.16EN
16www.nidec-asi.com
Marine Certification :
Since June 2007 we are ABS certified
CE, IEC compliant
Standards
PPT2013.01.01.16EN
17www.nidec-asi.com
First References :
2006 : Geostock (France) : 9 Soft starters 5,5 KV delivered end of 2006 year for OIL Pumping2007: ELSAG (Italy) : 3 x Soft starters 6,6 KV for marine application (Water injection pumps)2007: SAIPEM (Italy) : 2 x Soft starters 11 KV for marine application (Thruster for pipe layer vessel)2008 : DANIELI AUTOMATION (Italy) : 3 x Soft Starters 10kV for Melt shop Plant2009 : SCHNEIDER ELECTRIC (France) : 1 x Soft Starter 3,3kV2009: SAIPEM (Italy) : 1 x Soft starter 11 KV for marine application (Thruster for pipe layer vessel)2010: IPLOM (Italy) 2 x Soft starters 6.6 KV for compressor for OIL Pumping2010: FLOWSERVE (TOBRUK - Libya) 2 x Soft starters 3.3 KV for compressor for OIL Pumping2011 : SCHNEIDER ELECTRIC (France) : 2 x Soft Starters 5,5kV2012 : Engineering Steel Belgium (Belgium) : 2 x Soft Starters 6,6kV2012 : DRESSER RAND (APACHE – Australia) : 2 x Soft Starters 6,6kV2012 : INGERSOLL RAND (TASNEE - Saoudi Arabia) : 1 x Soft Starter 4,16kV