nidec asi silcovert s
DESCRIPTION
about silcovert sTRANSCRIPT
www.nidec-asi.com
SilcovertSilcovert SS™™
PPT2013.01.01.15EN
2www.nidec-asi.com
Silcovert S™
SILCOVERT S is a medium voltage load-commutated current source inverter (LCI) forsynchronous motors that provides speed regularity, monitoring and braking torque
regulation, V/Hz law shaping.
The flexibility of this product means that construction meets with the exact requirements ofthe application. In 12 or 24 pulse configurations the SILCOVERT S gives precise power
control in applications requiring high power and/or speed ratings.
When necessary the same power converter can be used to brake the generator-turbine set,regenerating the breaking power back into the network.
PPT2013.01.01.15EN
3www.nidec-asi.com
Supplied as a soft starter or an inverter (forsynchronous motors) the SILCOVERT S ischaracterised by:
compact design; low weight; easy installation; minimum maintenance; high accuracy; air or water cooling system
Silcovert S™Medium Voltage Drive
PPT2013.01.01.15EN
4www.nidec-asi.com
65 MWOutput Power:
50/60 Hz ± 3%Input Frequency:
Air Cooling up to 4500 V
Water Cooling up to 11000 V
Main Supply Voltage(3phase):
LCI – Thyristor TechnologyInverter Type:
5 up to 95HzOutput Frequency:
Air Cooling up to 4500 V
Water Cooling up to 10000 V
Output Voltage:
Silcovert S™Medium Voltage Drive
PPT2013.01.01.15EN
5www.nidec-asi.com
MOTOR POWER vs CURRENT - VOLTAGE [2x]
PF = 0.9
0
10000
20000
30000
40000
50000
60000
70000
80000
90000
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
Current [Arms]
Po
wer
[kW
]
0
2000
4000
6000
8000
10000
12000
Vo
ltag
e[V
rsm
]
Power [kW] V=4.16kV Power [kW] V=5.6kV Power [kW] V=6.6kV Power [kW] V=10kV
4.16kV 5.6kV 6.6kV 10kV
WA
TE
RA
IR
Motor Power vs Motor Current
PPT2013.01.01.15EN
6www.nidec-asi.com
6 pulse / 6 pulse 12 pulse / 6 pulse
=
~
~= SM
~=
SM
=
~
~
=
=~=
~=
~=
SM
~=
=
~
=
~
SM
~=
~=
~=
~=
24 pulse / 12 pulse 12 pulse / 12 pulse
Silcovert S™Configuration
PPT2013.01.01.15EN
7www.nidec-asi.com
Silcovert S™Forced Air
PPT2013.01.01.15EN
8www.nidec-asi.com
External Water to Air Exchanger
Silcovert S™Water Cooling System
PPT2013.01.01.15EN
9www.nidec-asi.com
Internal Water to Water Exchanger
Silcovert S™Water Cooling System
PPT2013.01.01.15EN
10www.nidec-asi.com
The DC link reactor:
decouples the line bridge(rectifier) from the loadbridge (inverter). Theysmooth and reduce theripple in the direct currentflowing in the intermediatecircuit between the rectifierand the inverter bridges.
Thyristors:
grouped in an array called a stack (4 – 8thyristors), the number that are connectedin series is selected based on themagnitude of the prospective peakvoltage.Above is a typical 3-stacks 8-thyristorspower module. The stack auxiliarydevices include snubber capacitors &resistors, firing board, firing high insulationtransformer.
Power Converter:
the rectifier and inverteruse as a standard a 6-pulse three-phasethyristors controlled bridge,fitted in air-cooled orde-ionized water-cooledheat sinks.
Main System Components
PPT2013.01.01.15EN
11www.nidec-asi.com
Power Converter (Front) Power Converter (Rear)
Main System Components
PPT2013.01.01.15EN
12www.nidec-asi.com
Air Cooling for power up to 10000 kW
The air is drawn into the cubicle by the converter fan and ejected from the top or carried out by means of airducts. Air forced cooling system it’s a very reliable way of cooling semiconductors devices, with minimalmaintenance costs. NIDEC ASI mounts a special device called anemometer on the top of the converterpanel, the converter is tripped if the fan is faulted or the air is not circulating.
Water Cooling for power above 10000 kW
De-ionized water is used to remove the heat from the thyristors and snubber resistors to a heat exchanger(water-to-water or water-to-air). The converter’s primary cooling system is a closed-loop system with awater tank. The de-ionized water circulates from the pump through the heat exchanger to the converterbridge and returns to the pump. In most application also the DC link reactor is water-cooled. The watercooling system is made up of the following components:
• Pump-motor group• Tank• Deionization system• Conductivity measuring system• Filter• Exchanger• Instruments• Hydraulic Connections• Cooling System Control
Cooling SystemsAir Cooling & Water Cooling
PPT2013.01.01.15EN
13www.nidec-asi.com
DC Link ReactorThyristor Power
Converter Front View
Thyristor PowerConverter Rear View
Silcovert S™40ft Container Mounting
PPT2013.01.01.15EN
14www.nidec-asi.com
The operator interface (SSDTERM)enables the operator to perform quick andefficient analysis on the digital regulator
status.
Display – makes up of the principalelectrical quantities (line and motorcurrent/voltage, speed set-point, speedfeedback, etc.), these same quantities arealso displayed as digital values.
Scope – is an oscilloscope function thatenables the real time display of selectedanalog and digital variables.
Silcovert S HMIInstrumentation & Monitoring
PPT2013.01.01.15EN
15www.nidec-asi.com
Black Box: enables the operator toexamine the status of up to 8variables (selected parameters)before and after a certain event (ex.Trip).
Contents can be saved as ASCIIfile, and exported for furtherexamination and remotetransmission. (Also refer to theOscilloscope function)
Transformer and temperature monitoringVisual display of the motor and transformers windingstemperature.A traffic light for each motor and transformer displays thestatus of protection (green means normal operation,yellow – warning and red – trip).
HMIControl & Diagnostic Panels
PPT2013.01.01.15EN
16www.nidec-asi.com
Deionised cooling system – hydraulic circuitIt permits to display the motors status and thenumeric value of the water temperature, absolute anddifferential pressure, conductivity, flow.When the system is in local mode start/stop ofhydraulic pump is allowed from this page.
Thyristor Status Lay OutThe Lay -Out permits to display the Thyristor status(green means status Ok, yellow means warning andred means presence of trip).Also the status (RUN,ALARM,TRIP) of the devices(TC1,TC2, CONVERTER N.1, CONVERTER N.2,MOTOR) is displayed.
HMIControl & Diagnostic Panels
PPT2013.01.01.15EN
17www.nidec-asi.com
Event-Alarm - Trip ReportOne of the most important functions of HMI systems is the alarm'smanagement recall.
The basic goals of this function are as follows:1. Detect alarm conditions reported by basic automation PLCs2. Notify any new alarm condition to the operators3. Allow the operator to recognize (acknowledge) the new alarms.
The alarms' summary page shall allow following functions:1. Presentation of alarms in form of list in chronological order.2. Alarms are in different colours according to priorities.
All alarms are date and time summarised on the summary page.
Oscilloscope FunctionOperator settings can be viewed through this function allowing avisual assessment of drive functionality and status.
HMIControl & Diagnostic Panels
PPT2013.01.01.15EN
18www.nidec-asi.com
Starter for gas turbine generator
Starter for hydro turbine generator
Starter for synchronous compensator
Starter for large synchronous motor
VFD for synchronous motor up to 75 MW
Marine propulsion VFD motor
Gas compressor VFD motor
Silcovert S™Principal Applications
PPT2013.01.01.15EN