Page 1: Nidec asi silcovert s

www.nidec-asi.com

SilcovertSilcovert SS™™

PPT2013.01.01.15EN

Page 2: Nidec asi silcovert s

2www.nidec-asi.com

Silcovert S™

SILCOVERT S is a medium voltage load-commutated current source inverter (LCI) forsynchronous motors that provides speed regularity, monitoring and braking torque

regulation, V/Hz law shaping.

The flexibility of this product means that construction meets with the exact requirements ofthe application. In 12 or 24 pulse configurations the SILCOVERT S gives precise power

control in applications requiring high power and/or speed ratings.

When necessary the same power converter can be used to brake the generator-turbine set,regenerating the breaking power back into the network.

PPT2013.01.01.15EN

Page 3: Nidec asi silcovert s

3www.nidec-asi.com

Supplied as a soft starter or an inverter (forsynchronous motors) the SILCOVERT S ischaracterised by:

compact design; low weight; easy installation; minimum maintenance; high accuracy; air or water cooling system

Silcovert S™Medium Voltage Drive

PPT2013.01.01.15EN

Page 4: Nidec asi silcovert s

4www.nidec-asi.com

65 MWOutput Power:

50/60 Hz ± 3%Input Frequency:

Air Cooling up to 4500 V

Water Cooling up to 11000 V

Main Supply Voltage(3phase):

LCI – Thyristor TechnologyInverter Type:

5 up to 95HzOutput Frequency:

Air Cooling up to 4500 V

Water Cooling up to 10000 V

Output Voltage:

Silcovert S™Medium Voltage Drive

PPT2013.01.01.15EN

Page 5: Nidec asi silcovert s

5www.nidec-asi.com

MOTOR POWER vs CURRENT - VOLTAGE [2x]

PF = 0.9

0

10000

20000

30000

40000

50000

60000

70000

80000

90000

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500

Current [Arms]

Po

wer

[kW

]

0

2000

4000

6000

8000

10000

12000

Vo

ltag

e[V

rsm

]

Power [kW] V=4.16kV Power [kW] V=5.6kV Power [kW] V=6.6kV Power [kW] V=10kV

4.16kV 5.6kV 6.6kV 10kV

WA

TE

RA

IR

Motor Power vs Motor Current

PPT2013.01.01.15EN

Page 6: Nidec asi silcovert s

6www.nidec-asi.com

6 pulse / 6 pulse 12 pulse / 6 pulse

=

~

~= SM

~=

SM

=

~

~

=

=~=

~=

~=

SM

~=

=

~

=

~

SM

~=

~=

~=

~=

24 pulse / 12 pulse 12 pulse / 12 pulse

Silcovert S™Configuration

PPT2013.01.01.15EN

Page 7: Nidec asi silcovert s

7www.nidec-asi.com

Silcovert S™Forced Air

PPT2013.01.01.15EN

Page 8: Nidec asi silcovert s

8www.nidec-asi.com

External Water to Air Exchanger

Silcovert S™Water Cooling System

PPT2013.01.01.15EN

Page 9: Nidec asi silcovert s

9www.nidec-asi.com

Internal Water to Water Exchanger

Silcovert S™Water Cooling System

PPT2013.01.01.15EN

Page 10: Nidec asi silcovert s

10www.nidec-asi.com

The DC link reactor:

decouples the line bridge(rectifier) from the loadbridge (inverter). Theysmooth and reduce theripple in the direct currentflowing in the intermediatecircuit between the rectifierand the inverter bridges.

Thyristors:

grouped in an array called a stack (4 – 8thyristors), the number that are connectedin series is selected based on themagnitude of the prospective peakvoltage.Above is a typical 3-stacks 8-thyristorspower module. The stack auxiliarydevices include snubber capacitors &resistors, firing board, firing high insulationtransformer.

Power Converter:

the rectifier and inverteruse as a standard a 6-pulse three-phasethyristors controlled bridge,fitted in air-cooled orde-ionized water-cooledheat sinks.

Main System Components

PPT2013.01.01.15EN

Page 11: Nidec asi silcovert s

11www.nidec-asi.com

Power Converter (Front) Power Converter (Rear)

Main System Components

PPT2013.01.01.15EN

Page 12: Nidec asi silcovert s

12www.nidec-asi.com

Air Cooling for power up to 10000 kW

The air is drawn into the cubicle by the converter fan and ejected from the top or carried out by means of airducts. Air forced cooling system it’s a very reliable way of cooling semiconductors devices, with minimalmaintenance costs. NIDEC ASI mounts a special device called anemometer on the top of the converterpanel, the converter is tripped if the fan is faulted or the air is not circulating.

Water Cooling for power above 10000 kW

De-ionized water is used to remove the heat from the thyristors and snubber resistors to a heat exchanger(water-to-water or water-to-air). The converter’s primary cooling system is a closed-loop system with awater tank. The de-ionized water circulates from the pump through the heat exchanger to the converterbridge and returns to the pump. In most application also the DC link reactor is water-cooled. The watercooling system is made up of the following components:

• Pump-motor group• Tank• Deionization system• Conductivity measuring system• Filter• Exchanger• Instruments• Hydraulic Connections• Cooling System Control

Cooling SystemsAir Cooling & Water Cooling

PPT2013.01.01.15EN

Page 13: Nidec asi silcovert s

13www.nidec-asi.com

DC Link ReactorThyristor Power

Converter Front View

Thyristor PowerConverter Rear View

Silcovert S™40ft Container Mounting

PPT2013.01.01.15EN

Page 14: Nidec asi silcovert s

14www.nidec-asi.com

The operator interface (SSDTERM)enables the operator to perform quick andefficient analysis on the digital regulator

status.

Display – makes up of the principalelectrical quantities (line and motorcurrent/voltage, speed set-point, speedfeedback, etc.), these same quantities arealso displayed as digital values.

Scope – is an oscilloscope function thatenables the real time display of selectedanalog and digital variables.

Silcovert S HMIInstrumentation & Monitoring

PPT2013.01.01.15EN

Page 15: Nidec asi silcovert s

15www.nidec-asi.com

Black Box: enables the operator toexamine the status of up to 8variables (selected parameters)before and after a certain event (ex.Trip).

Contents can be saved as ASCIIfile, and exported for furtherexamination and remotetransmission. (Also refer to theOscilloscope function)

Transformer and temperature monitoringVisual display of the motor and transformers windingstemperature.A traffic light for each motor and transformer displays thestatus of protection (green means normal operation,yellow – warning and red – trip).

HMIControl & Diagnostic Panels

PPT2013.01.01.15EN

Page 16: Nidec asi silcovert s

16www.nidec-asi.com

Deionised cooling system – hydraulic circuitIt permits to display the motors status and thenumeric value of the water temperature, absolute anddifferential pressure, conductivity, flow.When the system is in local mode start/stop ofhydraulic pump is allowed from this page.

Thyristor Status Lay OutThe Lay -Out permits to display the Thyristor status(green means status Ok, yellow means warning andred means presence of trip).Also the status (RUN,ALARM,TRIP) of the devices(TC1,TC2, CONVERTER N.1, CONVERTER N.2,MOTOR) is displayed.

HMIControl & Diagnostic Panels

PPT2013.01.01.15EN

Page 17: Nidec asi silcovert s

17www.nidec-asi.com

Event-Alarm - Trip ReportOne of the most important functions of HMI systems is the alarm'smanagement recall.

The basic goals of this function are as follows:1. Detect alarm conditions reported by basic automation PLCs2. Notify any new alarm condition to the operators3. Allow the operator to recognize (acknowledge) the new alarms.

The alarms' summary page shall allow following functions:1. Presentation of alarms in form of list in chronological order.2. Alarms are in different colours according to priorities.

All alarms are date and time summarised on the summary page.

Oscilloscope FunctionOperator settings can be viewed through this function allowing avisual assessment of drive functionality and status.

HMIControl & Diagnostic Panels

PPT2013.01.01.15EN

Page 18: Nidec asi silcovert s

18www.nidec-asi.com

Starter for gas turbine generator

Starter for hydro turbine generator

Starter for synchronous compensator

Starter for large synchronous motor

VFD for synchronous motor up to 75 MW

Marine propulsion VFD motor

Gas compressor VFD motor

Silcovert S™Principal Applications

PPT2013.01.01.15EN