SS-GASPT www.goodmanmfg.com 5/15 Supersedes 3/15 ASPT Series Multi-Position, Multi-Speed, ECM-Based Air Handler with Internal TXV 1½ to 5 Tons Contents Air Handler Nomenclature .................... 2 Heater Kit Nomenclature ...................... 2 Product Specificaons ........................... 3 Dimensions ............................................ 4 Airflow Data ........................................... 6 Heat Kit Data .......................................... 7 Wiring Diagram...................................... 9 Accessories .......................................... 12 Product Features Internal factory-installed thermal expansion valves for cooling and heat pump applicaons Direct drive, mul-speed ECM blower motor • All-aluminum evaporator coil Coil mounng track for quick reposioning Opmized for use with R-410A refrigerant Cabinet air leakage less than 2.0% at 1.0 inch H2O when tested in accordance with ASHRAE standard 193 Cabinet air leakage less than 1.4% at 0.5 inch H2O when tested in accordance with ASHRAE standard 193 3 kW – 25 kW electric heater kits Horizontal or vercal configuraon capabilies Rigid SmartFrame cabinet • 21” depth for easier ac access DecaBDE-free thermoplasc drain pan with secondary drain connecons Screw-less sides and back helps to reduce condensaon when installed in humid locaons Foil-faced insulaon covers the internal casing to reduce cabinet condensaon Galvanized, leather grain-embossed finish Glue-less cabinet insulaon retenon Tool-less filter access AHRI cerfied; ETL listed * Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registraon must be completed within 60 days of installaon. Online registraon is not required in California or Québec.

Upload: others

Post on 19-Jul-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 5/15Supersedes 3/15

ASPT SeriesMulti-Position, Multi-Speed,

ECM-Based Air Handler with Internal TXV

1½ to 5 TonsContentsAir Handler Nomenclature .................... 2Heater Kit Nomenclature ...................... 2Product Specifications ........................... 3Dimensions ............................................ 4Airflow Data ........................................... 6Heat Kit Data .......................................... 7Wiring Diagram ...................................... 9Accessories .......................................... 12

Product Features• Internal factory-installed thermal expansion

valves for cooling and heat pump applications• Direct drive, multi-speed ECM blower motor• All-aluminum evaporator coil• Coil mounting track for quick repositioning• Optimized for use with R-410A refrigerant• Cabinet air leakage less than 2.0%

at 1.0 inch H2O when tested in accordance with ASHRAE standard 193

• Cabinet air leakage less than 1.4% at 0.5 inch H2O when tested in accordance with ASHRAE standard 193

• 3 kW – 25 kW electric heater kits• Horizontal or vertical configuration

capabilities

• Rigid SmartFrame™ cabinet• 21” depth for easier attic access• DecaBDE-free thermoplastic drain

pan with secondary drain connections• Screw-less sides and back helps to

reduce condensation when installed in humid locations

• Foil-faced insulation covers the internal casing to reduce cabinet condensation

• Galvanized, leather grain-embossed finish• Glue-less cabinet insulation retention • Tool-less filter access• AHRI certified; ETL listed

* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Québec.

Page 2: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

2 www.goodmanmfg.com SS-GASPT

HKS X 03 X A AA

Unit  Type Major  &  Minor  RevisionsHKS  -­‐  AH  Heater  Kit

PhaseCircuit  Breaker A  -­‐-­‐  208  VAC  /  1  Ø D  -­‐-­‐  208  VAC  /  3  ØX  -­‐-­‐  No  circuit  breaker B  -­‐-­‐  240  VAC  /  1  Ø E  -­‐-­‐  240  VAC  /  3  ØC  -­‐-­‐  Circuit  Breaker C  -­‐-­‐  208/240  VAC  /  1  Ø F  -­‐-­‐  208/240  VAC  /  3  Ø

G  -­‐-­‐  460  VAC  /  3  ØkW03  -­‐-­‐  3.0  kW 15  -­‐-­‐  14.4  kW Cabinet  Size  (MAX)05  -­‐-­‐  4.8  kW 19  -­‐-­‐  19.2kW  w/150F  limit C  -­‐-­‐  C  Cabinet06  -­‐-­‐  6.0kW 20  -­‐-­‐  19.2kW  w/170F  limit D  -­‐-­‐  D  Cabinet08  -­‐-­‐  8.0kW 25  -­‐-­‐  25.0  kW X  -­‐-­‐  All  Cabinet  Sizes10  -­‐-­‐  9.6  kW

 

Brand Engineering  *A  -­‐  Single-­‐Piece  Air  Handler Major/  Minor  Revisions

*Not  used  for  inventory  management

Unit  ApplicationC  -­‐  Ceiling  Mount  PSC  Motor Refrigerant  CompatabilityR  -­‐  Multi-­‐Position  PSC  Motor 4  =  R-­‐410A  S  -­‐  Multi-­‐Position  EEM  MotorW  -­‐  Wall  Mount  PSC  Motor Electrical

1  -­‐  208/240  V,  1  Phase,  60  HzCabinet  FinishU  -­‐  Unpainted Nominal  WidthP  -­‐  Painted B  -­‐  17½”  WideN  -­‐  Uncased C  -­‐  21”  Wide

D  -­‐  24½”  WideExpansion  DeviceF  -­‐  Flowrator Nominal  Capacity  RangeT  -­‐  Expansion  Valve 24  =  2  Tons 42  =  3½  Tons

30  =  2½  Tons 48  =  4  Tons36  =  3  Tons 60  =  5  Tons

A S P T 24 C

1 2 3 4 5,6 7 9 10,11

61  =  5  Tons

1 4 AA

8

Nomenclature

Page 3: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 3

ASPT25B14*

ASPT29B14*

ASPT37B14*

ASPT37C14*

ASPT47C14*

ASPT59C14*

ASPT47D14*

ASPT49D14*

ASPT61D14*

Nominal Ratings

Cooling (Btu/h) 24,000 24,000 30,000 36,000 42,000 60,000 42,000 48,000 60,000

Blower

Diameter 9½" 9½" 9½" 10⅝" 10⅝" 10⅝" 10⅝" 11¹⁵⁄₁₆" 11¹⁵⁄₁₆"

Width 6" 6" 6" 8" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝"

Coil ConnectionsLiquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"

Suction ¾" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞"

Coil Drain Connect (FPT) ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"

Electrical Data

Voltage 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230

Minimum Circuit Ampacity 5.8 / 5.8 5.8 / 5.8 5.6 / 5.6 5.6 / 5.6 5.6 / 5.6 7.9 / 7.9 5.6 / 5.6 8.6 / 8.6 8.6 / 8.6

Max. Overcurrent Device (Amps) 15 / 15 15 / 15 15 / 15 15 / 15 15 / 15 15/15 15 / 15 15 / 15 15 / 15

Minimum VAC 197 197 197 197 197 197 197 197 197

Maximum VAC 253 253 253 253 253 253 253 253 253

Blower Motor

Full Load Amps (FLA) 4.6 4.6 4.5 4.5 4.5 6.3 4.5 6.9 6.9

Horsepower (HP) ¾ ¾ ¾ ¾ ¾ 1 ¾ 1 1

Ship Weight (Lbs.) 116 129 129 144 144 144 155 167 167

*Airflow rate @.3 static Note: Assumes dry coil; SCFM correction for wet coil = 4% (208V / 240V)

Product Specifications

Page 4: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

4 www.goodmanmfg.com SS-GASPT

Dimensions

-2_MIN-

-2_MIN--2_MIN-

CB

.55"(1.40 cm)

.55"(1.40 cm)

2.17"(5.51cm)

DE

21"

9.21"

11.3"(28.70 cm)

.55"(1.40 cm)

A

45.00

21.03

16.4117.63

9.21

14.97

.6 .6

11.5

58.00

21.0323.34

24.639.21

11 .5

28.7725.77

2.17

.6.6

1.63

17.97

1.67 1.67

17.66

FINLET

(FRONT VIEW)

1"(2.54 cm)

.55"(1.40 cm)

19.5" (49.5 cm)INLET

(RIGHT SIDE VIEW)

1.73

1.73"(4.39 cm)

1.73"(4.39 cm)

14.16 1.00.54

1.73 1.7321.16

.99.5419.52

19.52

2.17

1.45"(3.68 cm)

3.08"(7.82 cm)

1.63"(4.13 cm)

2.91"(7.39 cm)

2.93"(7.44 cm)

G

H

1.638.78

11.91

12.28

12.41

4.50"(11.43 cm)

4.50 4.502.91

2.91

2.93

2.93 3.07

1.453.08

1.45

1.4"(3.6 cm)

3.1"(7.9 cm)

5.2"(13.3 cm)

7.5"(19.1 cm)

1.8"(4.6 cm)

1.413.08

5.167.54

1.78

1.41

3.08

5.16

7.54

1.78

PLASTICBREAKER

COVER

LOGO LOCATION

SEE DRAIN PORT DETAIL

LIQUID LINESUCTION TUBE

INLETTUBE

0270AOO676

DRAIN PORT DETAIL

Model A" B" C" D" E" F" G" H"

ASPT25B14* 45 16⅜ 17½ 15¼ 12 143/16 9⅛ 12⅝

ASPT29B14* 537/16 16⅜ 17½ 2311/16 20½ 143/16 9⅛ 7⅝

ASPT37B14* 537/16 16⅜ 17½ 2311/16 20½ 143/16 9⅛ 7⅝

ASPT37C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 6⅞

ASPT47C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 6⅞

ASPT59C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 6⅞

ASPT47D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

ASPT49D14* 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 25⅛

ASPT61D14 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 25⅛

Page 5: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 5

Dimensions (Cont.)

Model A" B" C" D" E" F" G" H"

ASPT61D14 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 25⅛

Page 6: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

6 www.goodmanmfg.com SS-GASPT

Airflow Data

Model SpeedTap

Static Pressure (in w.c)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

ASPT 25B14AA

1 640 585 580 545 510 490 410 340 280

2 800 765 725 700 670 645 595 565 490

3 840 805 800 760 740 700 670 625 580

4 985 950 920 885 850 815 800 760 7255 1,475 1,440 1,400 1,375 1,335 1,305 1,270 1,240 1,150

ASPT 29B14AA

1 595 590 565 530 505 455 380 305 2602 790 775 745 705 665 625 585 515 445

3 865 820 790 770 735 695 645 595 530

4 1,015 980 955 925 880 840 795 770 7205 1,505 1,465 1,430 1,410 1,385 1,350 1,315 1,285 1,220

ASPT 37B14AA

1 1,025 985 945 910 875 830 795 735 690

2 1,150 1,105 1,065 1,025 995 950 915 870 825

3 1,240 1,200 1,160 1,120 1,085 1,050 1,010 970 925

4 1,425 1,400 1,355 1,320 1,290 1,250 1,215 1,180 1,1455 1,490 1,455 1,415 1,390 1,355 1,320 1,285 1,250 1,205

ASPT 37C14AA

1 980 935 895 860 825 800 755 710 665

2 1,125 1,075 1,045 1,000 965 930 880 845 820

3 1,235 1,190 1,155 1,120 1,085 1,045 1,005 965 920

4 1,485 1,450 1,425 1,390 1,355 1,315 1,275 1,230 1,1905 1,565 1,535 1,510 1,480 1,240 1,390 1,365 1,320 1,280

ASPT 47C14AA

1 955 895 855 840 780 735 675 615 5602 1,100 1,050 1,005 965 925 870 815 770 705

3 1,205 1,160 1,120 1,075 1,035 990 940 885 830

4 1,445 1,410 1,365 1,320 1,275 1,235 1,190 1,140 1,0955 1,525 1,480 1,435 1,400 1,360 1,320 1,275 1,230 1,180

ASPT 47D14AA

1 1,055 1,015 950 895 830 785 730 680 6202 1,210 1,165 1,110 1,070 1,015 960 900 840 785

3 1,335 1,290 1,250 1,205 1,145 1,100 1,050 980 910

4 1,625 1,580 1,530 1,495 1,455 1,405 1,350 1,295 1,2305 1,720 1,670 1,625 1,580 1,540 1,490 1,435 1,390 1,325

ASPT 49D14AA

1 1,485 1,435 1,380 1,320 1,265 1,200 1,230 1,015 930

2 1,570 1,525 1,480 1,430 1,370 1,315 1,235 1,155 1,035

3 1,680 1,600 1,570 1,555 1,475 1,430 1,360 1,280 1,185

4 1,800 1,765 1,715 1,670 1,625 1,590 1,510 1,465 1,3905 2,215 2,160 2,120 2,085 2,040 2,000 1,970 1,930 1,865

ASPT 59C14AA

1 1,370 1,330 1,295 1,255 1,215 1,180 1,140 1,100 1,0602 1,535 1,500 1,465 1,430 1,405 1,370 1,335 1,300 1,2103 1,680 1,645 1,615 1,575 1,545 1,510 1,440 1,330 1,2054 1,905 1,855 1,780 1,690 1,605 1,515 1,425 1,330 1,2055 1,940 1,855 1,775 1,700 1,605 1,505 1,420 1,320 1,205

ASPT 61D14AA

1 1,545 1,495 1,440 1,390 1,335 1,260 1,180 1,080 1,0302 1,745 1,695 1,625 1,575 1,525 1,475 1,400 1,360 1,275

3 1,905 1,855 1,815 1,770 1,725 1,670 1,635 1,575 1,500

4 2,155 2,105 2,090 2,045 2,000 1,970 1,935 1,890 1,8305 2,340 2,310 2,265 2,220 2,185 2,165 2,120 2,080 2,030

Notes• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. • Use the CFM adjustment factors of .98 for horizontal left, .95 for horizontal right & .96 for downflow orientations. • Assumes dry coil with filter in place.• All models are shipped from the factory with the speed tap set on T4.• Assumes dry coil; SCFM correction for wet coil = 4% • All ASPT models are shipped from the factory with the speed tap set on T4.

Page 7: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 7

Heat Kit Data

ModelCircuit 1 Circuit 2 Single-Point Kit

Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

ASPT25B14AA 0/0 5.8/5.8 15/15 --- --- --- --- ---

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20.0 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.6/25.0 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.8/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.6/40.0 49/56 50/60 --- --- --- -- --

ASPT29B14AA 0/0 5.8/5.8 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 49/56 50/60 --- --- --- -- --

HKS*15*#* 34.7/40 49/56 50/60 17/20 22/25 25/25 71/81 80/90

ASPT37B14AA 0/0 5.6/5.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 49/56 50/60 --- --- --- -- --

HKS*15*#* 34.7/40 49/56 50/60 17.3/20 22/25 25/25 71/81 80/90

ASPT37C14AA 0/0 5.6/5.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 49/56 50/60 --- --- --- -- --

HKS*15*#* 34.7/40 49/56 50/60 17.3/20 22/25 25/25 71/81 80/90

HKSC19C*#* 34.7/40 49/56 50/60 34.7/40 43/50 45/50 92/106 100/110

HKSC*15XF* 0/0 5.6/5.6 15/15 30/34.6 38/43 40/45 --- ---

ASPT47C14AA 0/0 5.6/5.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 49/56 50/60 --- --- --- -- --

HKS*15*#* 34.7/40 49/56 50/60 17.3/20 22/25 25/25 71/81 80/90

HKSC19C*#* 34.7/40 49/56 50/60 34.7/40 43/50 45/50 92/106 100/110

HKSC*15XF* 0/0 5.6/5.6 15/15 30/34.6 38/43 40/45 --- ---

Heating kW Correction Factor

Supply Voltage 240 230 220 210 208

Correction Factor 1.00 0.92 0.84 0.77 0.75

Multiply the 240-volt heating capacity by correction factors.

¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits

* Revision level that may or may not be designatedC = Circuit Breaker Option--- indicates Not Required

Page 8: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

8 www.goodmanmfg.com SS-GASPT

Heat Kit Data (cont.)

ModelCircuit 1 Circuit 2 Single-Point Kit

Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²

ASPT59C14AA 0.0/.0.0 7.9/7.9 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 21/24 25/25 --- --- --- -- --

HKS*05XC* 17.3/20 30/33 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 35/39 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 44/50 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 51/58 60/60 --- --- --- -- --

HKS*15*#* 34.7/40 51/58 60/60 17.3/20 22/25 25/25 73/83 80/90

HKSC19C*#* 34.7/40 51/58 60/60 34.7/40 43/50 45/50 95/108 100/110

HKSC*15XF* 0.0/0.0 7.9/7.9 15/15 30/34.6 38/43 40/45 --- ---

ASPT47D14AA 0/0 5.6/5.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 19/21 20/25 --- --- --- -- --

HKS*05XC* 17.3/20 27/31 30/35 --- --- --- -- --

HKS*06XC* 21.7/25 33/37 35/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 42/47 45/50 --- --- --- -- --

HKS*10XC* 34.7/40 49/56 50/60 --- --- --- -- --

HKS*15*#* 34.7/40 49/56 50/60 17.3/20 22/25 25/25 71/81 80/90

HKSC20D#C* 34.7/40 49/56 50/60 34.7/40 43/50 45/50 92/106 100/110

HKSC*15XF* 0/0 5.6/5.6 15/15 30/34.6 38/43 40/45 --- ---

HKS*20XF* 0/0 5.6/5.6 15/15 37.5/43.3 47/54 50/60 --- ---

ASPT49D14AA 0/0 8.6/8.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 22/24 25/25 --- --- --- -- --

HKS*05XC* 17.3/20 30.3/34 35/35 --- --- --- -- --

HKS*06XC* 21.7/25 36/40 40/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 45/50.3 45/60 --- --- --- -- --

HKS*10XC* 34.7/40 52/59 60/60 --- --- --- -- --

HKSC15*#* 34.7/40 52/59 60/60 17.3/20.0 22/25 25/25 74/84 80/90

HKSC20D#* 34.7/40 52/59 60/60 34.7/40.0 43/50 45/50 95/109 100/110

HKS*15XF* 0/0 8.6/8.6 15/15 30/34.6 38/43 40/45 --- ---

HKS*20XF* 0/0 8.6/8.6 15/15 37.5/43.3 47/54 50/60 --- ---

HKSC25DC* 52/60 74/84 80/90 35/40 43/50 45/50 117/134 125/150

ASPT61D14AA 0/0 8.6/8.6 15/15 --- --- --- -- --

HKS*03XC* 10.8/12.5 22/24 25/25 --- --- --- -- --

HKS*05XC* 17.3/20 30.3/34 35/35 --- --- --- -- --

HKS*06XC* 21.7/25 36/40 40/40 --- --- --- -- --

HKS*08XC* 28.9/33.3 45/50.3 45/60 --- --- --- -- --

HKS*10XC* 34.7/40 52/59 60/60 --- --- --- -- --

HKSC15*#* 34.7/40 52/59 60/60 17.3/20.0 22/25 25/25 74/84 80/90

HKSC20D#* 34.7/40 52/59 60/60 34.7/40.0 43/50 45/50 95/109 100/110

HKS*15XF* 0/0 8.6/8.6 15/15 30/34.6 38/43 40/45 --- ---

HKS*20XF* 0/0 8.6/8.6 15/15 37.5/43.3 47/54 50/60 --- ---

HKSC25DC* 52/60 74/84 80/90 35/40 43/50 45/50 117/134 125/150

Heating kW Correction Factor

Supply Voltage 240 230 220 210 208

Correction Factor 1.00 0.92 0.84 0.77 0.75

Multiply the 240-volt heating capacity by correction factors.

¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits

* Revision level that may or may not be designatedC = Circuit Breaker Option--- indicates Not Required

Page 9: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 9

Wiri

ng is

sub

ject

to c

hang

e. A

lway

s re

fer

to t

he w

iring

dia

gram

on

the

unit

for t

he m

ost u

p-to

-dat

e w

iring

.⚠

W

arni

ngHi

gh V

olta

ge:

Dis

conn

ect

all

pow

er b

efor

e se

rvic

ing

or i

nsta

lling

thi

s un

it. M

ultip

le p

ower

so

urce

s m

ay b

e pr

esen

t. F

ailu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r dea

th.⚡

BK BL

BK

L1L2

BK

BK

HTR

1TL

HTR

1

RD

987

R

WH

BLPU

TL

BK

5 63 4PLF

BK

RD

1 2

WH

RD

L2L1

BK

BK

RD

BKR

D

RHTR

2TL

L1

BK

6 8 972

RD

PU

4 53

BKR

D1PL

F

BK

L2L1

L2

RD

YL

M1

M2

BK

RD

YL

RD

R1

M4

RD

BK

M3

HTR

3TL

HTR

2

HTR

1TL TL

PU

M2

R2

YL

M1

BL

WH

BR

BL

RD

BK RD

BK

TLH

TR1

BKHTR

4

HTR

3

HTR

2

BKR

D

97 8

L2L1

L1L2

2 5 63 4PLF

1

RD

M1

YL

BK

M2

BL

WH

6

BL

RD

BK

YL8 97

M6

M5

M3 R

1

M4

RD

PU

M7 R2

M8BL

TL TLTL YL

BL

RDBK

RD BL B

R

4 532

BK

PLF

1

ON

E (1

) ELE

MEN

T R

OW

STW

O (2

) ELE

MEN

T R

OW

STH

REE

(3) E

LEM

EN

T R

OW

SFO

UR

(4) E

LEM

ENT

RO

WS

FL

M1

M2

FL FL

M1

M2

M3 M4

FL FL FL

FL FL FL FL

CO

PPER

PO

WER

SU

PPLY

(USE

RAT

ING

PLA

TE)

USE

MIN

. 75°

C F

IELD

WIR

E

0140

A000

63-B

PLM

PLF TRFAC

TOR

Y W

IRIN

G

FIE

LD W

IRIN

G

NO

TES:

1) R

ED W

IRES

TO

BE

ON

TR

ANSF

OR

MER

TE

RM

INAL

"3" F

OR

240

VO

LTS

AND

ON

TER

MIN

AL "2

" FO

R 2

08 V

OLT

S.2)

SEE

CO

MPL

ETE

WIR

ING

DIA

GR

AMS

IN IN

STAL

LATI

ON

INST

RU

CTI

ON

S FO

RPR

OPE

R L

OW

VO

LTAG

E W

IRIN

G C

ON

NEC

TIO

NS.

3) C

ON

FIR

M S

PEED

TAP

SEL

ECTI

ON

IS A

PPR

OPR

IATE

FO

R A

PPLI

CAT

ION

. IF

SPEE

D T

AP N

EED

S TO

BE

CHA

NG

ED, C

ON

NEC

T PU

RPL

E W

IRE

FRO

M T

ERM

INAL

4O

F C

R R

ELAY

TO

APP

RO

PR

IATE

TAP

AT

TB4)

BR

OW

N A

ND

WH

ITE

WIR

ES

ARE

USE

D F

OR

HEA

T KI

TS O

NLY

.5)

FUS

E: 3

A, 2

50V,

3AG

CAR

TRID

GE

FUSE

.

REL

AY

EVAP

OR

ATO

R M

OTO

R

TER

MIN

AL B

OAR

D REM TB

BK RD

BLYLBL

UE

BLAC

KR

EDYE

LLO

W

CO

MPO

NEN

T C

OD

E

BRO

WN

PUR

PLE

GR

EEN

PU BRGR

FEM

ALE

PLU

G C

ON

NEC

TOR

MAL

E P

LUG

CO

NN

ECTO

R

TRA

NSF

OR

ME

R

H

IGH

VO

LTA

GE

LO

W V

OLT

AGE

H

IGH

VO

LTA

GE

LO

W V

OLT

AGE

PLF

2

CO

LOR

CO

DE

TR

65

PLM

4

424

V5

12

3

EM

WIR

ING

CO

DE

208/

240

VOLT

S

11PL

F

PLM

L1

PLM

2L2

IF R

EPLA

CEM

ENT

OF

THE

OR

IGIN

AL W

IRES

SUPP

LIED

WIT

H T

HIS

ASS

EMBL

Y IS

NEC

ESSA

RY,

USE

WIR

E TH

AT C

ON

FOR

MS

TO T

HE

NAT

ION

ALEL

ECTR

IC C

OD

E.

FLFU

SE L

INK

TLTH

ER

MAL

LIM

IT

HTR

HEA

T EL

EME

NTS

CR

CO

NTR

OL

REL

AY

NO

TE: W

HEN

INST

ALLI

NG

HEA

TER

KIT,

EN

SUR

E SP

EED

TAP

DO

ES N

OT

EXCE

ED M

INIM

UM

BLO

WER

SPE

ED (M

BS) S

PEC

IFIE

D F

OR

THE

AIR

HAND

LER

/HEA

TER

KIT

CO

MBI

NATI

ON

ON

TH

ISU

NIT'

S S&

R PL

ATE.

AFT

ER IN

STAL

LIN

G O

PTIO

NAL

HEAT

KIT

, MAR

K A

"X" I

N TH

E BO

X PR

OVI

DED

ABO

VE.M

ARK

ACC

OR

DING

TO

NU

MBE

R O

F HE

ATER

ELE

MEN

T RO

WS

INST

ALLE

D. N

O M

ARK

IND

ICAT

ES N

O H

EAT

KIT

INST

ALLE

D.

WH

ITE

WH

LG

N

W2

RW

1C

G4

Y1O

Y21

DH

32

5

AB

1

C

EM2 43 5

47

CR

FUSE

HO

LDER

(OPT

ION

AL)

1

SEE

NO

TE 1

USE

CO

PPER

WIR

EEQ

UIPM

ENT

GRO

UND

BL

EM

YL

BL

5

BK

C

BK

PLF

BK1

RD23

240

24V

4

12

3

TR

RD

BLBR

45

WH6

78

9PL

M

GRD

12

34

56

78

9

AB17

4

CR

SEE

NOTE

2

21

43

5 NC

GL

RD

PU

BL

BR WH

BL

RD

GR

RD o

r BKBL

RD

BKRD

W2

RW

1C

G4

Y1O

Y21

DH

32

5

RD o

r BK

PU

BR

WH

OR

WH

WH

BL

GR

RD o

r BK

BLFU

SEHO

LDER

(OPT

IONA

L)

L2L1

SEE

NO

TE 1

SEE

NO

TE 4

1354

2

ALTE

RN

ATE

HEA

T R

ELAYPU

RD GR

WH

13

24

CR

5

ALTE

RN

ATE

HEA

T R

ELAY

Air Handler Wiring Diagram

NOTE: The five element, 25 kW heater kit is not shown above.

Page 10: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

10 www.goodmanmfg.com SS-GASPT

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡

M9

M10

TL

FLHTR1

HTR2

HTR3

HTR4

M6

M5

L2L2 L1

RD

BLBK

YL

RD

BK

BK

RD

M1 M3YL

BL

BK RD

M2

R1

M4

PU

9

8

WH

M8

7

6

BR 5

M7

R2

BLRD

BL 4

3

2

BL

YL

BK 1

PC

RD

BK

HTR5

L1L2L1

BL

R3

PU

PU

1L 2L

CB4

CB3 CB1 CB2

WH

PU

TL

FLTL

FL

TL

FL

TL

FL

COLOR CODE

BK = BLACK BL = BLUE BR = BROWN

PK = PINK

RD = RED WH = WHITE YL = YELLOW

WIRING CODE:HIGH VOLTAGELOWVOLTAGE

COMPONENT CODE

PC = 9 PIN CONNECTOR HTR = HEATER ELEMENT TL = THERMAL LMT RS = RELAY/SEQUENCER TB = TERMINAL BLOCK CB = CIRCUIT BREAKER CC = CONTACTOR FL = FUSE LINK

TR = TRANSFORMERSR = STRAIN RELIEF

EM = EVAPORATOR MOTOREBTDR = ELEC. BLOWER TIME DELAYRC = RUN CAPACITOR

GR = GREEN OR = ORANGE

PU = PURPLE

0140M00274-A

NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP MUST EXCEED OREQUAL THE MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER /HEATER KIT COMBINATION ON THIS UNIT'S SERIAL PLATE. AFTER INSTALLINGOPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED BELOW.NO MARK INDICATES NO HEAT KIT INSTALLED.

FIVE (5) ELEMENT ROWS

NOTE:-THIS LABEL MUST BE ATTACHED ON THEAIRHANDLER IN A PROMINENT LOCATION

BK RD BKRD

Five-Element Heater Kit Wiring Diagram

Page 11: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

SS-GASPT www.goodmanmfg.com 11

RC

BR

BREM

3 5

2

1 4

RD

TR

WH

BR

BK

L2

L1

RD

RDBL

BK

PU

BLPU

RELAY/SEQUENCER

THERMAL LIMITTRANSFORMER

RUN CAPACITOR

ELEC. BLOWER TIME DELAY RELAYEVAPORATOR MOTORHEAT ELEMENTHTR

EBTDREM

RS

TLTR

RC

COMPONENT CODE

24 VOLT

TR

RC EM

EBTDR

EBTDR

COM

NONC

208/240 VOLTS

0140M00273-A

WH

BK

GND

L3 T3

CC

L2

L1

BL

T2

T1

R

BL

RD

BR

M3

M4PU

M2

PUWH

M1

WH

WH

RSBL

WH

PU

BL

RD

1

2

3

5

7

8

9

6

4

WH

PC

EBTDR

TERMINAL BLOCKCONTACTOR9-PIN CONNECTORPC

CCTB

M2

RS

M1

M3M4

L1 L2

LOW

HIGH

CC

HEATER CONTROL

AR POWER SUPPLY

1

2

3

4

5

6

7

8

9

PC

(CIRCUIT 1)

NCSPEEDUP

GR

C

RDXFMR-RXFMR-C

M1

COMK1

NOK1

L1

RDGR

PKBL

PU

SR

STRAIN RELIEF

M1

YL YELLOW

BK BLACKBL BLUEBR BROWNGR GREENOR ORANGEPK PINKPU PURPLERD REDWH WHITE

COLOR CODE

(CIRCUIT 2)HKR POWER SUPPLY

L1 L2 L3

FLSR

FUSE LINK

W2 W1

WBRGRBLPK

GRCRD

T1 T2 T3

1 2 3

4 5

FL HTR3 TL

FL HTR2 TL

FL HTR1 TL

TLFL HTR3 TLFL HTR2

TLFL HTR1

CB CIRCUIT BREAKER

L1L2L3

BKBK BK

BK

BK

BK

BK BK

BK

BKBK

BK

BKBK

BK

BK

BK

BK

BK

WIRING CODEHIGH VOLTAGELOW VOLTAGE

BK

NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP MUST EXCEED OR EQUAL THE MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER KIT COMBINATION ON THIS UNIT'S SERIAL PLATE.AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED BELOW.

NO MARK INDICATES NO HEAT KIT INSTALLED.

NOTE:-THIS LABEL MUST BEATTACHED ON THEAIRHANDLER IN A PROMINENTLOCATION

BK RD

TB

L1 L2

CIRCUIT 11 PH 208-240V

CIRCUIT 23 PH. 208-240V

Three-Phase Heater Kit Wiring Diagram

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡

Page 12: ASPT Series - Interline Brands · SS-GASPT 3 ASPT 25B14* ASPT 29B14* ASPT 37B14* ASPT 37C14* ASPT 47C14* ASPT 59C14* ASPT 47D14* ASPT 49D14* ASPT 61D14* Nominal Ratings Cooling (Btu/h)

12 www.goodmanmfg.com SS-GASPT

Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2015 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.

Accessories

Downflow Insulation Kit

DFK-B DFK-C DFK-D

ASPT24B14** ASPT30C14** ASPT42D14**

ASPT36C14** ASPT48D14**

ASPT42C14** ASPT60D14**

ASPT48C14** ASPT61D14**

Filters

Chassis Part # Size

B ALFH16201E 16.0” x 20.0”

C ALFH1912201E 19.5” x 20.0”

D ALFH20231E 23.0” x 20.0”