ringmaster nov07 se6251

92
Ringmaster range indoor/outdoor switchgear Installation, operation and maintenance instructions 07 November

Upload: george-asuncion

Post on 21-Oct-2015

277 views

Category:

Documents


23 download

DESCRIPTION

electrical

TRANSCRIPT

Ringmaster rangeindoor/outdoor switchgearInstallation, operation and maintenance instructions

07November

1SCHNEIDER ELECTRIC

page

Contents

Version 11 - Issue date November 2007Note: This manual covers ring main units produced from June 1999. Designation RN2c/RN6c/RE2c. For ring main units designated RN2/RN6 see earlier manual.Ref: Version 005/December 98.

Commissioning

Checks and tests

Tests

Commissioning Ringmaster

with VIP 300

Ringmaster operation

RN2c, RE2c, RN6c essential checks

Features

Switch and circuit breaker

Earth switch

Cable testing

Circuit breaker reset

Motorpack

Motorpack operation

Neon indication

Ringmaster range operation

Main features

Switch and circuit breaker

Earth switch

Cable testing and actuator control

Actuator control

Maintenance

Recommendations and conditions

Housing

Circuit breaker

54

54

55

65

69

69

70

71

72

73

75

76

77

78

79

80

81

82

83

84

85

85

86

87

General

Symbols and meanings

Schneider Electric at your service

General description

Handling, transportation and storage

Storage

Goods receiving

Characteristics

Civil engineering

Floor preparation

Internal arc

Cable trench

Installation

Transformer mounting

Connecting the HV cables

Erection / connection

Installation of pilot cables

Removal of VIP relay

Accessing VT’s

Earth fault flow indicator

Actuators

Accessories

Fitting REC2 to Ringmaster range

Protection

Time fuse link

Operation

VIP300

VAP6

2

2

3

4

5

6

7

8

9

9

10

12

13

14

15

20

22

23

24

25

26

27

28

43

43

44

46

52

page

2 SCHNEIDER ELECTRIC

GeneralSymbols and meanings

! DANGER

WARNING

CAUTION

The following symbols appear in this document to indicate the degree of hazard according to the situation.

Danger: Failure to follow this instruction will result in death, seriousinjury or equipment damage

Warning: Failure to follow this instruction can result in death, seriousinjury or equipment damage

Caution: Failure to follow this instruction can result in equipment damage

Information: We draw your attention to this particular point

3SCHNEIDER ELECTRIC

GeneralSchneider Electric at your service

Customer service and aftersales support

Services and projects

Document guidelines

Safety requirements

All operations described hereafter must be carried out by respecting the safetyrequirements in full, under the responsibility an authorised person.

Personnel undertaking installation and commissioning must be competent and understand local regulations and standards.

If the installation and operational team is unsure or not familiar with Ringmaster orRingmaster Range switchgear please contact Schneider Electric.

CAUTION

CAUTION

! DANGER

For technical support or advice current products please contact our customer service department:Tel: +44 (0) 113 290 3651Fax: +44 (0) 113 290 3710Email: [email protected]

For the following services please contact Services & Projects:

■ Spares and managed spares contracts■ Maintenance and service contracts■ Retrofit■ Installation■ Testing and commissioning■ System design■ Training

Tel: +44 (0) 113 290 3634Fax: +44 (0) 113 290 3777Email: [email protected]

This document is not a commercial document, but a technical document prepared bySchneider Electric.

The objective of this publication is to assist with the correct installation and operationof Ringmaster and Ringmaster Range.

Reproduction either in full or partial of this document is prohibited and can only beundertaken with permission of Schneider Electric.

4 SCHNEIDER ELECTRIC

GeneralGeneral description

These instructions cover all operations concerning handling, installation, operation

and maintenance of the Ringmaster Range of equipment.

Introduction

RN2c/RE2cRN6c

CN2 SN6 CE6 SE6 CE2 MU6+CE6/CE2/SE6

MU2 MU6

1510 1610hWI

average dimensions(mm) (packed)

unit(s)

approx. weight (kg)

771842350

1750520960280

1750520960280

1750520960280

1750520960280

1750520960280

175011001100520

1650520960240

1750520960240

When fully installed the equipment is suitable for outdoor use. It may therefore be necessary to protect the equipment from the environment duringerection/commissioning. Please check equipment specification for clarification ofindoor/outdoor use. Should the busbar chamber or cable box become exposed tothe elements, they should be thoroughly cleaned prior to energising.

The range comprises:-■ RN2c 630/200A non extensible compact ring main unit■ RN6c 630/630A non extensible compact ring main unit■ RE2c 630/200A extensible compact ring main unit■ CN2 200A non extensible circuit breaker ■ SN6 630A non extensible switch■ CE2 200A extensible circuit breaker ■ CE6 630A extensible circuit breaker ■ SE6 630A extensible switch■ MU2 200A feeder metering unit non-extensible units■ CE2/CE6/SE6 with metering unit

Compact non extensible composite ringmain unit ■ RN2c 630/200A■ RN6c 630/630A

Weights and dimensions

Extensible circuit breakers and switches ■ CE2 200A■ CE6 630A■ SE6 630A

Please refer to the appropriate pages in the Ringmaster selection guide Ref:MGMV5337 available from Schneider Electric or on line at www.schneider.co.uk

5SCHNEIDER ELECTRIC

GeneralHandling, transportation and storage instructions

Transport & handling

Storage

CAUTION

CAUTION

Ringmaster is only suitable for outdoor storage when packaged correctly or fullycommissioned.The type of gland supplied will vary in accordance with specific contract requirements.The style of packaging will vary in accordance with the method of transportationand specific contract requirements.Please consult your commercial documentation to see how this equipment ispacked.

Highcentre ofgravity

Use lifting lugsONLY to liftRingmaster

Use all four lifting points

Do not stand on Ringmaster

Do not put anything on Ringmaster

All units can be off loaded by fork lift truck using the transport pallet. They can also be off loaded using the lifting lugs fitted at the top of the unit.

Units can be carried on open topped trucks or stored outside for short periods provided that all apertures are covered. Units should not be considered weatherproof until the paint work has been inspected and, if necessary any damage should be re-touched. Please refer to paintwork on page 7 for repairingdamaged paintwork.If units are to be stored for long periods of time they should be stored in a warm,dry location and protected against dust and debris.

6 SCHNEIDER ELECTRIC

GeneralStorage

All units are delivered on pallets (secured by 4 x M8 screws and nuts) and fitted

with lifting eyes, suitable for off loading by forklift truck or overhead crane.

Ancillary kits containing busbar, dyscon boots, glands, screws etc. are supplied

loose with each unit or fastened to the panel leg or secured in the cable boxes.

Following transportation ensure circuit breaker mechanism is reset prior to

operation.

It is recommended that prior to energising the unit all protection device are

checked to ensure they are set correctly. For TFL units ensure fuses are fitted.

VIP units must be set in accordance with the results of a protection co-ordination

study.

Off loading

Ancillary kits

Prior to operation

Prior to energising

7SCHNEIDER ELECTRIC

GeneralGoods receiving

In the event of an anomaly, please contact the transport/shipping company.

The functional unit must remain on its base, in its original packing, during storage, and until installation.

In the event of any anomaly or apparent damage, do not install, please contact SCHNEIDER ELECTRIC.

Contact details: are detailed on page 3.

Check for any damaged paintwork. Damaged areas should be cleaned and re-coated as follows:

Rub down the area around the damage with medium glass paper. Clean the damaged area with emery paper ensuring the surface is clean and free of any corrosion. Apply one coat of zinc-rich epoxy primer (a two-pack system is recommended), the coating to be 35-45 microns thick. The recommended paintsystem is International Paints “Interzinc EPA 072 and EPA 073”.

Leave to cure for 24 hours, then apply two, 35-45 micron coats (ie 70-80 microns in total) of two-pack polyurethane, Interphane PFR 764 is recommended.

The standard colour employed is Dark Grey Code 632 to BS 381C:1996.

CAUTION

Goods receiving ■ Before any equipment is accepted it should be inspected carefully for damage or loss incurred during transit

■ Where possible check the presence of accessories against the packaging list

■ Where possible check the information on the nameplate(s) and compare against the order confirmation

■ The packing must be in place and in good condition at the time of receipt. Wherever possible, damage should be recorded, photographed and witnessed.It may be necessary to unpack the equipment to establish the full extent of the problem.

Paintwork

8 SCHNEIDER ELECTRIC

GeneralCharacteristics

Check that the information contained on the rating plate corresponds to the equipment ordered.

Typical rating plate for RN2c

Serial NO.Panel type no.Service voltageHighest system voltageImpulse voltage withstand levelFrequencyMass of unit (max)Mass of SF6 GasSF6 Gas filling pressure at 20°C

11kV12kV75kV

50/60HZ300 kg

0.516 kg0.35 bar G

Year

Normal current

Short time current 3 seconds

Peak making current

Earth switch short timecurrent 3 second

Ratings

RingmasterRN2C

123 Jack LaneLeeds LS10 1BS U.K.

A

kA

kA

6301640

kA

kA

6301640

2001640

16

40

16

40

busbars Switch CircuitBreaker

To Specification EATS 41-26 AND RELEVANT IEC & BS SPECIFICATIONS

Tel +44 113 290 3500Fax +44 113 290 3710

Earth switch peakmaking current

R N X C

Ringmaster Non extensible Circuit breaker rating Compact2 = 200A6 = 630A

Typical rating plate for CE2

Serial NO.Service voltageHighest system voltageImpulse voltage withstand levelFrequencyMass (max)SF6 Gas filling pressure at 20°C

12kV12kV75kV

50/60HZ350 kg

0.80 bar G

Year

Normal current

Short time current3 second

Peak makingcurrent

Earth switch short timecurrent 3 second

Earth switch peakmaking current

Testing standard

A

kA

kA

kA

kA

630

16

40

230

16

40

16

40B.S.5311IEC 56

Busbars Circuit breaker

Ratings

RingmasterCE2

200A circuit breaker To specification EA41-26Leeds LS10 1BS U.K.

X X X

S - Switch N - Non extensible ratingC - Circuit breaker E - Extensible

2 = 200A6 = 630A

9SCHNEIDER ELECTRIC

Civil engineeringFloor preparation

Floor preparation, equipment fixing dimensions and main cable position can befound in the Ringmaster selection guide reference MGMV5337. Or, if supplied the arrangement drawing for the switchboard or unit.

Where it is not possible to guarantee that the floor is within the specified tolerance,we strongly recommend the use of foundation channels, i.e. Unistrut P3270 or similar.

Note: The floor must be 1mm below the top of the Unistrut.

jigs supplied

channels grouted in

4170

position using setting

41

foot of unit

m10 channel fixing

in subfloorchannels made

channel nut

to + - 1mm with

spring loaded

foundation channel

note: floor level flush

Both non extensible units and switchboards can be directly bolted to the concretefloor by use of 4 x 10mm (supplied) UNI-FIX or similar rag bolt fixings - see diagram. The floor tolerance for extensible switchboards is ±1mm over 1metre.

10 SCHNEIDER ELECTRIC

Civil engineeringInternal arc

Ringmaster

Modular Ringmaster range

Internal arc

Kits to safely divert the flow of gassesoutside the substation are not part ofthe supply of equipment. If required,kits will need to be adapted to eachsituation.

Internal arc withstand

12.5kA, 16kA and 21kA for 1 second

Arrows indicate direction of exhaustgases

CAUTION

Where units are to be installed in anenclosed substation the following approximate free air volumes behindthe units must be observed.

11SCHNEIDER ELECTRIC

Civil engineeringInternal arc

CAUTION

If the unit is to be installed outdoors there are no special requirements for exhausting the arc gasses.

If the minimum free air space can notbe guaranteed then arc vent trunkingmust be used. Typical trunkingarrangements are detailed. ContactSchneider Electric for advice beforedesigning and installing internal arctrunking.

Note: Arc trunking is not part of ourscope of supply.

CAUTION

16kA equipment fault rating 21kA equipment fault rating

Minimum 112m Minimum 152m

5 degree angled trunking (to prevent moisture ingress)

External ventingpanel hinged onbottom edge

The elbow and side/rear trunking isthe same for both RN2c and CE/SE

12 SCHNEIDER ELECTRIC

Civil engineeringCable trench

16675

7

1320

trenchmaincable

45

16675

7

1320

trench maincable

45O

front entry rear entry

53313

20

max. trench width

56097 97

1630 20

42

223.

5

cabl

e bo

x ta

ll le

ngth

54.5

928 735

695

door

operatinghandle

Cable trench

Where the equipment is to sit over atrench, details of the maximum cabletrench width can be found in the selection guide.

Care must be exercised with the cablebend, refer to cable manufacturersspecification

CAUTION

Typical side view of a Ringmaster Range unit.

13SCHNEIDER ELECTRIC

Installation

CAUTION

Standard units can be installed in environments which meet ‘normalservice conditions’ as defined by IEC 60694 section 2.1:-

Ambient temperature: -25°C to +45°CAltitude: up to 1,000 meters above sea level

If the location is outside the certified parameters please refer to the selection guide,alternatively contact Schneider Electric for advice. Where the units are to beinstalled in environments where the above parameters are exceeded, this must bedeclared to Schneider Electric so the appropriate de-rating factors can be applied.

Failure to rate the equipment to the location may result in equipment failure.

CAUTIONUnits may be installed indoors or outdoors but must not be subjected to regularextremes of weather e.g. heavy rain storms, heavy snow and ice, flooding, temperature cycles not greater than 55°C and less than -25°C, dense coastal fogor acid rain.

14 SCHNEIDER ELECTRIC

InstallationTransformer mounting

771

30

771

600

973

537

510

40

1510

4 OFF M10*115RAWL THROUGHBOLTS

213 213

267

263

105

385.5

569

1955

516

1320

936

385.5

105

ES

I35-

1 tr

ansf

orm

er

470

86 86 86 86 86

89

89216370 116

Dimensions of the EA transformer flange

General arrangement of a transformer mounted RN2c.

14 x M12 clearance holes

Adjust RMU stand height to suit. Under workshop conditions remove transformer lidscrews. Pump oil out to below HV pocket height. (Pump into clean, dry drum).Remove blanking plate. Push units together. Insert bushing gasket and make firm connections on flanges and support brackets. Make off the 3 phase connectionschecking that these are tight and in the correct phase sequence, onto the M12 copper studs in the bushings. Pump clean oil back to the cold oil fill levelmarked on the transformer oil gauge. Re-fit tank cover ensuring that there is nodamage to the gasket. Touch up paint as necessary.

Perform primary winding resistance test in insulation resistance test.

WARNINGImportant when coupling transformerM12 transformer termination lug tightening torque - 25Nm

15SCHNEIDER ELECTRIC

InstallationConnecting the HV cables

The RN2c/RE2c/RN6c is suitable foraccepting 1 x 3 core or 3 x 1 corecable up to 240mm2 copper or aluminium approaching from below -top entry available on request. Fit the gland plate and accessories inaccordance with the instructions supplied with the ancillary kit.

Standard RN2c/RE2c/RN6c cable box

Angled gland plates can be provided on all units to the front or rear, in orderto simplify civil works.

Please refer to accessory kit instructionsfor details.

Standard CE, CN, SE & SN cable boxStandard cable entry directly from below

WARNING

Connecting the HV cablesForeward

Before connecting the cables, ensure that each unit is in the earthed switch position.

The cables MUST be connected with the equipment securely fixed to the ground.The operations described below apply to apply to all types.

The connections used should be made and used according to the manufacturersinstructions.

Connecting Ringmaster frame to the substation earthBefore connecting the HV cables you must connect the Ringmaster frame to themain earth bar.

Access to the HV connection bushingsCable box venting fixings arrangementEnsure cable box cover screws are configured correctly as detailed on cable boxcover label.

16 SCHNEIDER ELECTRIC

InstallationConnecting the HV cables

CE2, CE6, SE6, CN2, SN6 top cable entry

CE2, CE6, SE6, CN2, SN6 angled cable entry

16675

7

1320

trenchmaincable

45

16675

7

1320

trench maincable

45O

CE2, CE6, SE6, CN2, SN6 with top entry cable box.

front entry rear entry

Top entry cable boxes can be fitted forbasement substation applications.

17SCHNEIDER ELECTRIC

InstallationConnecting the HV cables

WARNING

! DANGER

Always clamp the cable with theappropriate glanding system beforeconnecting the cable to the bushing.Proceeding otherwise will put unacceptable stress on the bushingand could damage the bushing, leading to equipment failure. Theweight of the cable must always besupported by the cable gland.

WARNING

When using cable connectors usethose supplied with the equipment, ifothers are used the long term dielectric withstand cannot be guaranteed.

Ensure the bolt torque’s are adhered to, otherwise equipment failure may occur.

unit boot type cable socket lug torquefixing (Nm)

RN2c/RE2c main right angled M12 stud 54

RN6c tee off right angled M12 stud 54

RN6c tee off straight M12 clearance hole in palm 54

CE6/CE2/SE6 straight M12 clearance hole in palm 54

CE2/CE6 feeder metering right angled M12 tapped hole 54

CN2/SN6 main straight M12 clearance hole in palm 54

CN2/SN6 outgoing right angled M12 tapped hole 54

Installation noteThe most common cause of disruptive failure on this type of equipment is causedby incorrectly tightened cable connections ALWAYS double check cable connections with a calibrated torque wrench.

18 SCHNEIDER ELECTRIC

InstallationConnecting the HV cables

WARNINGWhen cabling please ensure that the correct phase rotation is followed for all medium voltage cable boxes.

When connecting two cables per phase on RN2c and RN6c on a single bushinguse the termination kit supplied by Schneider Electric. For all other units contactSchneider Electric for advice before proceeding.

CAUTION

✔✕

There are phase identification stickers in all accessible points throughout the equipment.

Double cable arrangement using the ECONcable termination kit

19SCHNEIDER ELECTRIC

InstallationConnecting the HV cables

✕ ✕ ✕

WARNINGThe cut cable length of the cable must be adjusted for each phase (in particular 3core cables).

Never use a bar to pull the and fit a connection lug to the bushing. The bushingand hence the complete cubicle could irreversibly damaged.

To prevent vermin entering cable boxes ensure that the correct gland is fitted andtightened, cable box covers are fitted correctly and all bolts are replaced. If thereare any visible spaces consult Schneider Electric on sealing advice.

Tighten nuts/bolts to the torque’s detailed on page 17.

Ensure all cable box fittings are replaced after installing cable.

20 SCHNEIDER ELECTRIC

InstallationErection/connection

Erection/connection CE6, CE2, SE6.

Remove the top cover on each unitand bolt each panel to the adjacentone. Use the 16 x M6 screws aroundthe busbar aperture and the 2 x M8screws by the cable test access/auxiliary compartment.

The busbar end cap is secured with 16screws. Before fitting the end cap apply a line of silicon compoundaround the busbar aperture.

Please refer to accessory kit instructionsfor full details.

Connect the busbars as shown below.Connect the earth bars at the back ofthe units. Connect the main substationearth to the equipment main earth bar.Fit the main gland plates (see ancillaryinstructions). Erect the first unit underclean, dry conditions either directly tothe floor, or on to the foundation channels.

Connection of busbars CE6, CE2, SE6.Refer to accessory kit instructions for full details

430 430

rain shieldpanel lid

sealing strip

rain shield

busb

ar e

nd c

ap

typical busbar run

Ensure that the environment is cleanand dry. Remove busbar chamber covers.

refer to accessory kit for full detailsRemove dyscon boots and clean bushings. Apply DC4 silicon grease toboots. Fit busbars into boots as shownabove.

21SCHNEIDER ELECTRIC

InstallationErection/connection

Feeder meteringEnsure that the environment is cleanand dry. Remove busbar covers asshown above. Remove dyscon boots and clean bushings. Apply DC4, Dow Corning silicon grease to boots. Fit busbarsinto boots as shown above.

Busbar meteringEnsure that the environment is cleanand dry. Remove busbar covers asshown above. Remove dyscon boots and clean bushings. Apply DC4, Dow Corning silicon grease to boots. Fit busbarsinto boots as shown above.

Connection of busbars metering

busbar collarbusbar busbar

Torque busbar screw to 54 Nm. Fitdyscon dust caps. Degrease and cleanusing a lint free cloth. Replace busbarchamber covers taking care not todamage nylon inserts. Ensure sealingstrip is correctly fitted.

Connection of busbars RE2cWhen supplied pre-assembled the RE2c to CE6/CE2/SE6 busbars require a final torque during on site commissioningPlease refer to the accessory kit instructions supplied with the product (ref: RMR-A369 "on site" busbar re-torquing procedure)

Note: It is recommended prior to refitting busbar chamber covers that the busbars are tested - see pages 39, 42 and54 for typical tests

busbarbusbar

CAUTION

22 SCHNEIDER ELECTRIC

InstallationInstallation of pilot cables

Installation of pilot cables RN2c, RE2c, RN6c

The universal gland plate at the rear ofthe LV compartment will accommodatepilot cable glands upto 25.5mm2.

To fit gland and cable remove 4 glandplate screws. Slide top section ofgland plate forward.

Insert gland and cable replace topgland plate and 4 fixing screws.

Installation of pilot cables CE2, CE6, CN2, CN6, SE6 and MU

on switch/circuit breaker.Remove VIP relay if fitted, knock outthe pre-punched gland plates from theinside as required. There is no need tore-touch with paint (the plates arestainless steel).

Note:20.5mm = 1x7 core / 1x9 core pilot gland25.5mm = 1x19 core pilot gland

on MU2Knock out the pre-punched glandplates from the inside as required.There is no need to re-touch with paint(the plates are stainless steel).

on feeder/busbar metering unitsKnock out the pre-punched glandplates from the inside as required.There is no need to re-touch with paint(the plates are stainless steel).

23SCHNEIDER ELECTRIC

InstallationRemoval of VIP relay

Removal of VIP relay RN2c, RE2c, RN6c

Open cabinet door. Move shorting links on terminal rail,short circuiting the CT Secondaries.Remove top cover 3 x M6 x 20 screws.

note: CT secondaries notshorted on aboveShort circuiting of the CTsecondaries.To short circuit the protectioncurrent transformers loosentest terminals A, and moveshorting link B upwards.

note: CT secondaries shortedon aboveSlide earthbar B to positionabove and tighten test terminals A.To isolate protection devicefrom CT’s loosen screw Cand slide link to lower position.

Open up relay cover. Loosen two retaining bracket screws attop of VIP facia.Withdraw relay and remove secondary wiring.

A

B

B

A C

Removal of VIP relay CN2, SN6, CE2, CE6, SE6

Remove the crimp terminals from thetop of the relay. Rotate the two faciascrews behind perspex window torelease clamps and withdraw relay.

Pull the relay cover forwards andremove.

Remove the 2 , M4 x 20mm pan headscrews and washers from the front ofthe relay cover and the M6 x 20 mmscrew from the top of the relay cover.

24 SCHNEIDER ELECTRIC

Accessing VT’s

Disconnection of solid link VT

Before accessing the VT enclosurethat you check the following:

RN2c/RN6c/CN the circuit breaker isin circuit earth and padlocked in itsposition.

Extensible CE/SE range ensure thatthe incoming supply breaker is padlocked in the open position.

Ensure that the VT secondary circuit isisolated and earthed.

See pages 71 to 83 for operationinstructions.

Remove the metering chamber H.V.access cover, as indicated.

Pull back the V.T. insulating boot, andloosen the top V.T. connection usingan 6mm allen key as indicated.Pull back the lower fuse link insulatingboot and disconnect the V.T. link.

InstallationAccessing VT's

WARNING

25SCHNEIDER ELECTRIC

InstallationEarth fault flow indicator

Earth fault flow indicator

Hand or self reset earth fault flow indicators can be fitted.Please refer to manufacturers instructions.

For C.T.'s mounted inside the cablebox, gland insulation is not required.For C.T.'s fitted outside the cable boxgland insulation must be fitted.

Split core C.T.'s can be installed afterthe main cable has been made off outside the cable box. Howeverplease note gland insulation must befitted if mounted outside the cable box.Installation instructions for the unitsare supplied with the ancillary kits.

26 SCHNEIDER ELECTRIC

InstallationActuators

Procedure for fitting and setting of actuators fitted to the Ringmaster range of switchgearCN2, SN6, CE2, CE6, SE6

1 Fix the actuator to the top mounting bracket ensuring that the distance from the top of the actuator to the top of the mounting bracket is approximately 9mm (as shown in the drawing below) and tighten the fixing screw. Note: this is only an approximate preliminary setting.

2 Also ensure there is approximately 3mm of clearance between the body of the actuator and the facia of the unit (as shown in the drawing below).

3 Rotate the bottom of the actuator in a clockwise direction (if looking from below as shown in the drawing) until resistance against the actuator motor can be felt.

4 Then rotate the actuator in an anticlockwise direction approximately one half of a full rotation making sure that the actuator motor is not rotating (this has the effect of lengthening actuator i.e. gap ‘a’ on the drawing should increase).

5 Fit the actuator operating bracket assembly to the bottom of the actuator locating the operating bracket spigot in the operating handle socket (as shown in the drawing below) and tighten up the fixing screw.

6 Connect the actuator plug and perform a few electrical operations.

7 Remove the plug and check that the actuator can be withdrawn and replaced with relative ease.

8 If not, adjust the positioning of the actuator by loosening either the mounting bracket or operating bracket and moving either part so that the actuator can be withdrawn easily. Repeat this process until it is possible to withdraw the actuator with relative ease.

IMPORTANTIn the event that the actuator failsto complete a closing or openingoperation, DO NOT attempt todisconnect the actuator operatingbracket spigot from the operatinghandle socket.Contact Schneider Electric, details onpage 3.

27SCHNEIDER ELECTRIC

InstallationAccessories

Accessories

Accessories will be despatched either:■ Fitted to the unit within the works, i.e. too bulky or need testing prior to despatch■ Loose boxed for assembly on site

Anti-vandal measuresPadlock points are provided to prevent un-authorised access to the unit, padlockscan be supplied with the unit if required at the time of enquiry or order.

Available accessories are detailed in the Ringmaster selection guide Ref: MGMV 5337.Accessories will be detailed with individual confirmation orders.

28 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Removal of blanking kit

Fig.1

Fig.2

Remove the extensible right hand topside sheet (Ref.4) by undoing the 7 offfully tightened M6 x 20 hex headscrews (Ref.102) and M6 nyltite seals(Ref.103). See Fig. 1

Remove the 13 off fully tightened M6 x 20 hex head screws (Ref.102)and nylite seals (Ref.103) from theextensible bushing cover top (Ref.2)then remove the extensible bushingcover top. See Fig. 1

Remove the 4 off M6 x 20 hex headscrews (Ref.102) from the supportplate (Ref.5) and remove the supportplate complete with the 3 off extensiblebushing sleeves and bushing sleevecovers (Ref.1). See Fig. 2

Remove the 2 off M6x20 hex headscrews (Ref.102) from the extensiblebushing cover bottom (Ref.3) andremove the extensible bushing coverbottom

Insert the cable socket studs into theL3, L2 and L1 bushings and tightenup.

5

3

1

102103

102103

4

2

102103

29SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Transition plate to RE2c unit

Disconnect circlip and pivot pinassembly (Ref.A) retaining 2 off gasstrut (Ref.B) to fascia. See Fig. 3

Loosen off hardware at the main doorhinge (Ref.C) and slide out the 2 offmain door hinge pivots (Ref.D) whichretain the main door. See Fig. 4

NOTE: This door is heavy! Caremust be taken when removing it.

Remove the M8 & M6 (Ref.E) hardware retaining the lid in positionand place lid to one side. See Fig. 5

Fig.3

Fig.4

Fig.5

A

B

C

D

E

CAUTION

30 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Transition plate to RE2c unit

Offer up the extensible transition platesub assembly (Ref.11) to the righthand side of the extensible unit ensuring the dimple is pointing outwards.

Secure in position with 2 off M6 x 20hex screws (Ref.103) with 1 off M6nyltite seal (Ref.105) placed over thethreads of each. See Fig. 6

Apply phase dots (Ref.122, 123, 124)to the extensible transition plate(Ref.11) just above the extensiblebushings. See Fig. 7

NOTE: To re-fit lid follow steps infirst three paragraphs of ‘blankingkit removal’ see page 28.

NOTE: When re-fitting lid it isimportant to replace the correctlength screws in each location.

Fig.6

Fig.7

122 123 12411

103105

11

Dimple

103105

31SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Sub assembled extensible busbar and housing to unit

Fasten a length of EPDM seal strip(Ref.106 A) along the outside of thebend at the rear of extensible trunkingbase (Ref.10). See Fig. 8

Fasten further lengths of EPDM sealstrip (Ref.106 B) around the inside ofextensible trunking base (Ref.10) asshown in Fig. 8

Offer trunking base assembly (Ref.10)up to the RHS of the extensible unitwith the short end flush with the rear ofthe unit. Secure with 3 off M6 x 25 hexscrews (Ref.104) with 1 off M6 nyltiteseals (Ref.105) under the heads ofeach. See Fig. 8

Smear approximately 1 mm thicknessof DC4 silicon compound (Ref.111)around the inside of 3 off bushing sleeves (Ref.23) before inserting theminto bushing sleeve securing plate(Ref.22). See Fig. 9

Slide bushing sleeve plate assemblyover phase bushings and secure inposition using 4 off M6 x 25 hex headscrews (Ref.104) with nyltite seals(Ref.105) under the heads and a stackof 7 off M6 form ‘C’ washers (Ref.119)over the threads of each M6 screwbetween the bushing sleeve plate andthe unit. See Fig. 10

Fig.8

Fig.9

Fig.10

104119

104105

10

106A

106B

111

2322

32 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Transition plate and lid sub assembly

Push 17 off M6 hexagonal inserts(Ref.101) through the hexagonal holesaround the outside edge of the extensible left hand side sheet(Ref.14) ensuring all Inserts are facinginwards.

Secure all inserts in position using thecorrect insert tool. See Fig. 11

Fasten lengths of EPDM seal strip(Ref.106) around extensible left handside Sheet (Ref.14) as shown in Fig. 11.

Fasten lengths of EPDM seal strip(Ref.106) around the bend of theextensible trunking lid (Ref.12) asshown in Fig.12

Lay sub assembled extensible lefthand side sheet (Ref.14) on one side.Offer sub assembled extensible trunking lid (Ref.12) so the bend isflush with the side sheet. See Fig.12

Secure using 7 off M6 x 20 hex Hdscrews (Ref.103) together with 1 offM6 nyltite seal (Ref.105) under theheads of each.

Fig.11

Fig.12

101

101

14

106

106

14

12

103105

106

33SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Transition plate and lid sub assembly

Offer up trunking light hand side sheetand trunking lid sub assembly to theside of the extensible unit with theshort side flush with the rear of theunit. See Fig. 13

Secure trunking left hand side sheet(Ref.14) and lid (Ref.12) sub assemblyto the transition plate (Ref.11) using 9off M6 x 25 hex screws (Ref.104)together with 1 off M6 nyltite seal(Ref.105) under the heads of each,fully tighten these screws. Fit theextensible trunking lid (Ref.12) usingthe "flanged" end, this is fitted with; 5 off M6 x 20 hex screws (Ref.103.)with a nylite seal (Ref.105) under thehead of each. Fully tighten thesescrews after fitting.

Secure trunking left hand side sheet(Ref.14) to the trunking base (Ref.10)using 2 off M6 x 20 hex screws(Ref.103) together with 1 off M6 nyltiteseal (Ref.105) under the heads ofeach, fully tighten these screws.

Extensible busbar sub assembly

Place 1 off M10 form ‘A’ washer (Ref.121) over the threads of 1 off M10 x 30 hex screw (Ref.108) followed by 1 off RE2c conductoradapter (Ref.3).

Screw the above assembly into thethreaded end of the extensible L3 busbar (Ref.4)

Follow steps 6.1 and 6.2 for extensibleL2 busbar (Ref.5) and for extensibleL1 busbar (Ref.6).

See Fig 14 for the assembled components – each busbar shouldlook like this.

NOTE: Leave these assembliesloose and tighten up before starting‘sub assembled housing to unit’ seepage 35.

Fig.13

Fig.14

10

103105

103105

12

3

4

121

108

103105

34 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Extensible busbar sub assembly

Slide 1 off 5mm silver plated copperwasher (Ref.107) over each of the 3off M12 cable studs. Offer up the busbars (Refs.4, 5 & 6),facing away from the unit, through theecon boots (Ref.15) over the M12cable studs. See Fig. 15

Position the three busbars so that thefree ends are in a horizontal line whenviewed form the side.of the unit.Secure each busbar with 1 off M12form ‘A’ washer (Ref.109) and 1 offM12 nut (Ref.110) torqued to 54 NM.

NOTE: Now FULLY tighten theassemblies mentioned in paragraphs 4 to 6 and shown in Fig. 14 on page 33

Push the econ boot caps (Ref.16) ontothe front of the econ boots (Ref.15).See Fig. 15

NOTE: Using a tyewrap or similar,insert tyewrap behind econ boot cap(Ref.16) to ensure air is expelled whilst fitting cap. See Fig.16

Fig.15

Fig.16

16

5

4

6

15

16

109

128

110

3

107

35SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Sub assembled housing to unit

Fasten lengths of EPDM seal strip(Ref.106) around the access hole ofthe Ringmaster range unit. See Fig. 17

Push 26 off M6 hexagonal inserts(Ref.101) through the hexagonal holesaround the top and bottom edges ofthe trunking main body (Ref.13) ensuring all inserts are facing inwards.

Secure all inserts in position using thecorrect insert tool. See Fig 18.

Fasten lengths of EPDM seal strip(Ref.106) around the top of the trunking main body (Ref.13). See Fig. 18

Offer trunking main body (Ref.13) tothe side of the Ringmaster range unit.Secure in position with 16 off M6 x 20 hex Hd screws (Ref.103) and16 off fully tightened M6 nuts (Ref.112)with 1 off M6 washers (Ref.113) underthe heads of each M6 screw andunder each M6 nut. See Fig.19

Secure left hand side sheet (Ref.14)and lid sub assembly to trunking mainbody(Ref.13) and trunking base(Ref.10) with 34 off M6 x 20 hex Hdscrews (Ref.103) together with 1 offM6 nyltite seal (Ref.105) under thehead of each screw. See Fig. 19

Fig.17

Fig.19

Fig.18

106

106

13

101

103105

36 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Final assembly

Offer up blanking plate (Ref.17) to theleft hand side (viewed from the front)of the Ringmaster range unit andsecure with 2 off 3/16” monobolt(Ref.118).

Smear approximately 1mm thicknessof DC4 silicon compound (Ref.111)around the stems and dyscon boots(Ref.18) of the Ringmaster rangebefore sliding them into position.

NOTE: The lower side of the dysconboot should face the left hand sideof the Ringmaster range unit whenviewed from the front.

Position the Ringmaster range unitand the extensible unit together so theholes in the main trunking body line upwith the holes in the left hand sidesheet on the Ringmaster range unit. See Fig 20

NOTE: At this stage the lid on theRingmaster range unit should beremoved to aid access for assembly.

Secure the main trunking body and lefthand side sheet on the Ringmasterrange unit in position with 16 off M6 x 20 hex screws (Ref.103) and 16off M6 nuts (Ref.112) with 1 off M6washers (Ref.113) under the heads ofeach M6 screw and under each M6nut. Fully tighten these componentsup.

NOTE: The orientation of thescrews – the top row should havethe heads facing outwards as in thephoto. See Fig. 21

Fig.21

Fig.20

118

17

Screw heads

37SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Earth bars to unit

Offer up the horizontal earth bar(Ref.20) to the rear of the extensibleunit. Secure the right hand side inposition behind the RE2c earth bar (Ref A) using 1 off M10 x 30 hex Hdscrew (Ref.127) with 1 off M10 form ‘A’washer (Ref.125) under the head anda further 1 off M10 form ‘A’ washer(Ref.125) under 1 off M10 hex full nut(Ref 126). See Fig. 22

Offer up the vertical earth bar (Ref.21) to the rear of the Ringmasterrange unit. Secure one end to theRingmaster range unit – in front of earth bar (Ref B) and the other endbehind the horizontal earth bar(Ref.20) using 1 off M10 x 30 hex Hdscrew (Ref.127) with 1 off M10 form ‘A’washer (Ref.125) under the head anda further 1 off M10 form ‘A’ washer(Ref.125) under 1 off M10 hex full nut(Ref.126). See Fig. 22

Fig.22

20

A

21

B

126

127

125

38 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Fitment of front and rear transit braces

NOTE: These parts do NOT requirefitting if the unit is fitted to a plinthassembly!

The left hand ends of the rear andfront transit braces (Ref 8 and 9 asshown in Fig.23 ), are fitted to theinside faces of the "L" shaped struts (Ref C). Place an M8 form A washer(Ref.115) over 2 off M8 x 25 setscrews (Ref.130). Push each screw through the two "L" shaped brackets(Ref C) and the transit braces (Ref.8 and 9). Place another M8 FormA washer (Ref.115) over each screwthread and fit an M8 full nut (Ref.117)to each one – leave loose.

The right hand end (as shown in Fig.23) of the front transit brace (Ref.9) goes to the inside of the "U"shaped strut (Ref D). Put an M10 formA washer (Ref.121) over an M10 x 30hex head screw (Ref.127). Push thisthrough the front transit brace (Ref.9)and through the "U" shaped strut (Ref.D). Place an M10 form A washer(Ref.121) over the screw threads ofthe M10 x 30 hex head screw (Ref 127) and then fit an M10 full nut (Ref.126) - leave loose.

The rear brace (Ref.8) goes to theinside of the supporting foot (Ref.E).Place an M10 form A washer (Ref.125)over an M10 x 30 hex head screw(Ref.127). Push the screw with thewasher on through the support foot(Ref.E) and through the rear transitbrace (Ref.8). Place a 1 off M10 formA washer (Ref.125) over the thread ofthe screw and fit an M10 full nut(Ref.126)

Once all the above is complete fullytighten all the M10 and M8 hardwarementioned above. See Fig. 23 for thecompleted assembly.

Fig.23

8

E

C

D

9

39SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Ducting, HV and discharge testing of the units

Prior to carrying out the electricaltests the operator should completethe following:-

Secure all 3 off busbars to the stems(Ref.D) of the Ringmaster range unitusing 1 off M12 x 40 hex head screw(Ref.114) with the M12 flat washer(Ref.109) and 1 off busbar spacer(Ref.120) under each of the heads.Tighten the 3 off M12 x 40 hex headset screws (Ref.114) To 54 Nm with acalibrated torque wrench.

Slide the 3 off extensible conductorCap up the busbars and locate in position in the rear of the boots. Thesecaps are not visible in Fig 24 and arepart of the bought in, L3, L2 and L1sub assemblies.

Push dyscon dust caps (Ref.19) in thefront and top of the dyscon boots(Ref.18). See Fig. 24

At this point perform the three following tests:

■ High voltage partial discharge test■ High voltage frequency test■ Resistance test

NOTE: For transportation purposeson completion of the above theRingmaster range side of the busbar assembly must be un-torqued as it is to be fullytorqued up when in position on site.

Fig.24

19

18

D

109

120

4A

114

40 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Securing of busbars and fitment of blanking plate

Fit the blanking plate (Ref.25) to theunit as shown in Fig. 25. This is fittedusing 10 off M6 x 20 screws with anyltite seal (Ref.105) under the headof each screw Insert these through theblanking plate (Ref.25) and the unit(Ref.A) and then fit an M6 form Awasher (Ref.113) followed by an M6full nut (Ref.112) fully tighten these up.See Fig. 25

Refit the previously removed lid to theRingmaster range unit plus lid edgestrips.(Ref.131) A lifting Lug willrequire fitting to the left hand side ofthe unit when viewed from the rear. Tofit the lid use; 12 off M6 x 20 screws(Ref.103) with an M6 nylite seal (Ref.105) under the head of each ofeach screw. These are followed by; 22 off M6 x 25hex head screws (Ref.104) with a andnylite seal (Ref.105) under the head ofeach. These 22 screws hold on the lidedge strips which are fitted using tessamol to make them weather tight.All the above hardware should now befully tightened up.

Fig.25

25

41SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Securing of busbars and fitment of blanking plate

Offer up RE2C - CE2/6 lid stiffeningplate (Ref.7) to the underside of therear of the Ringmaster range lid.Secure in position using 2 off M8 x 40screws (Ref.116) with 1 off M8 SSform ‘A’ washer under the head ofeach.Push the left hand screw (asviewed from the rear of the units as inthe figure left) through the lifting lug(Ref.D), through the lid edge strip(Ref.117) through the lid and throughthe lid stiffing plate (Ref.7) of the unit.

Next slide a further 1 off M8 form ‘A’washer (Ref.115) over the thread andfollowed by 2 off M8 hex full nuts(Ref.117) fully tighten the first nut andthen lock the second nut against eachthe first.

The right hand side is the sameassembly as the left with the exceptionthat the lifting lug (Ref.D) is not fitted.See Fig. 26

Fig.26

7

131D

131

116117

116117

Left hand viewed from rear of unitRight hand viewed from rear of unit

NOTE: This procedure only applieswhen the unit is on site.

When unit is in position on site removedyscon boot caps (Ref.19) from thetop of the dyscon boots (Ref.18). See Fig. 27

Fully secure each busbar assembly by torquing the M12 x 40 hex head set screw inside the dyscon boots to54Nm. See Fig. 27

Replace dyscon boot caps (Ref.19) inthe top of the dyscon boots (Ref.18).

Finally carry out ductor tests to the following ratings:

42 SCHNEIDER ELECTRIC

InstallationFitting RE2c to Ringmaster range

Final torque of busbars

Fig.27

Phase Resistance(micro ohms)

L1 196L2 198L3 200

19

18

114

120

4

A

109

43SCHNEIDER ELECTRIC

ProtectionTime fuse link

Protection systems

Time fuse link (TFL) protectionsummary

TFL selection

Recommended Time fuse Link (TFL) settings to ESI 12 - 6

All circuit breakers can be fitted with various forms of protection system -

1. VIP self powered IDMT protection - refer to VIP user guidesVIP 30 - provides protection against phase-to-phase faultsVIP 35 - provides protection against phase-to-phase faults and earth faultsVIP 300 - three phase overcurrent and earth fault protection

2. Time fuse link (TFL) protection system to EA 41-26 (time fuse links to EA 12-6).

Time fuse link protection provides a cost effective way of protecting a transformerof 1600kVA or less. It is a recognised method of protection and the fuses are covered by EA 12-6 (1973). The arrangements in the Ringmaster range is of 2 phase overcurrent and earth fault.

Schneider Electric recommend TFL sizes in accordance with the table below.

The table also includes our recommendations for the maximum LV fuse size toensure discrimination. Note that the size of this fuse is less than the full load current of the transformer, however, it would normally be expected to have a number of LV fuses fed from the LV side of the transformer.

Important note: Please ensure TFL fuses are fitted prior to energising the equipment.

3.3 10A - - - - - - TFL

(kV) 200 315 500 800 1000 1250 1600

150A - - - - - - LV fuse

6.6 5A 10A 15A - - - - TFL

150A 250A 400A - - - - LV fuse

11 3A 5A 10A 15A -

560A -

15A -

560A -

- -

- -

12.5A 15A

560A 560A

7.5A 10A 12.5A 15A

630A 630A

12.5A 15A

630A 630A

560A 630A

7.5A 10A

560A 630A

400A

10A

400A

15A

400A

7.5A

400A

- - TFL

200A 300A - - LV fuse

13.8 3A 5A - - TFL

200A 300A - - LV fuse

3.3 5A 10A - - TFL

150A 250A - - LV fuse

6.6 - 5A - - TFL

- 250A - - LV fuse

11 - - 5A TFL

- - 400A LV fuse

13.8 - - 5A TFL

- - 400A LV fuse

CT ratio = 50/5

voltage transformer rated power (kVA)

earth fault setting = 25A

(instantaneous trip)

CT ratio = 100/5

earth fault setting = 30A

(instantaneous trip)

WARNING

TLF protection will not work correctlyunless the recommended fuses are fitted.

44 SCHNEIDER ELECTRIC

ProtectionOperation

The circuit consists of 3 dual ratioC.T.'s, 2 Direct Acting Trip (DAT) solenoid type overcurrent coils connected in parallel with associatedTime Fuse Links (TFL's) and 1 instantaneous earthfault DATsolenoid Coil.

Under normal load conditions on, sayan 11000 volt 1000KVA transformer, 52amps will flow in the C.T. primaries(1000kVA(11kv/3). If the C.T. ratio isset on 50/5 Amp ratio, then approximately 5 Amps will flow in theC.T. Secondaries. As the overcurrentcoils are shorted out by the fuses, nocurrent will flow through the coils.Assuming that there was no earthleakage, the red, yellow and blue phases will balance, and no current willflow through the earth fault coil.

In the event of a phase to phase faultof, say, 500 Amps, 50Amps would flowthrough the C.T. secondaries. Thiswould blow the 15Amp fuse links shunting all of the current through theDAT coils, which would operate and trip the 3 phase circuit breaker. Thetripped on fault flag would operate, andthe CB would have to be re-set and thefuses replaced.

Two overcurrent coils are required tocover all phase fault combinations, i.e.for a R-Y phase fault, the CB will trip on the red phase coil. Under earth fault conditions, there will be an imbalance between the red, yellow andblue phases, and current will flow downthe residual path of the C.T.'s andthrough the earth fault coil. The unitwill trip instantaneously. If a TFL is fitted in parallel with the earthfault coilthen the tripping time will follow the TFL characteristics. Alternatively, thefuse can be removed.

Operation

Removable Earth Link

Circuit breakercontacts

Removable Earth Link

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Red phase TFL

Blue phase TFL

Earth fault TFL(if lifted)

Terminal block

C11

C31

C51

C70

C90

250

230

210

BREAKERCONTACTS

CIRCUIT

150

130

110

50/5A RATIO

C71

REMOVABLE TEST LINK

BLUE O/C COIL

RED O/C COIL

100/5A RATIO

RATIO CHANGEOVERLINK

C52

C32

C12(IF FITTED)

EARTH FAULT COIL

EARTH FAULT TFL

REMOVABLE EARTH LINK

P

PS

S

S2

70

31

11

51

C

C

C

C

C

C

C

C

C

C

11

32

R1

Y1

B1

Panel types CN/SN/CE/SE

Panel types RN2c/RE2c/RN6c

45SCHNEIDER ELECTRIC

ProtectionOperation

Close-up of C.T. links. Replacing the time fuse links.

Dual ratio 100/50/5Amp C.T.'s are fitted as standard, to the Ring MainUnits and 200 Amp circuit breakerswith TFL protection. Selection of theappropriate C.T. ratio can be easilyachieved by moving the auxiliary linkin the pilot cable box. Note that the circuit must be off load when changingratios.

WARNINGCurrent transformers not in use

Current transformers (T200E and earth fault flow indicator) that are not going to beused during commissioning or during service, they must be shorted out otherwiseirreversible damage may occur to current transformers and/or the unit.

46 SCHNEIDER ELECTRIC

ProtectionVIP 300

Phase overcurrent setting1. Phase setting area

(upper half of relay front panel).2. Red LED phase overcurrent

pick-up indicator.3. Phase overcurrent trip indicator.4. Phase overcurrent setting Is.5. Choice of low set curve type I>.6. Low set pick-up (DT only) I>.7. Low set time delay t>8. Multiplying factor (low set).9. High set pick-up I>>10. High set time delay t>>

Earth fault setting11. Earth fault setting area

(lower half of relay front panel).12. Red LED earth fault pick-up

indicator.13. Earth fault trip indicator.14. Earth fault setting current Ios.15. Choice of low set curve type Io>.16. Low set pick-up (DT only) Io>.17. Low set time delay to>.18. Multiplying factor (low set).19. High set pick-up Io>>.20. High set time delay to>>.

Other functionsA. Current setting scale label.B. Current transformer and

range information.C. Indicator reset button.D. Minimum operating current.E. VAP6 test plug socket.

VIP300

0.40.20.60.1

0.90.05

1.50.03

to>>(s)

129156

204

off3 (x Is)

0.20.150.30.1

0.40.07

0.60.05

0.40.20.60.1

0.90.05

1.50.03

t>>(s)

129156

204

off3 (x Ios)

2.11.82.41.5

2.71.2

31 (x Ios)

0.20.150.30.1

0.40.07

0.60.05

to>(s)

curve selection

DT onlyIo> Io>>

I>>

Is

4842 5636 64

30 7224 80

20 90100(A)

Ios

2416 3212 40

8 504 60

2 7080(A)

I>

I>

trip

reset

trip

Io>

earth fault

x10

sensors:200/1 4509996A0VIP300LH range: x2

minimum operatingphase current: 20A

phaseovercurrent

x1

EIVISI

offRI

DT

(s)

2.11.82.41.5

2.71.2

31 (x Is)

x10

x1

VAP6 test plug

EIVISI

offRI

DT

DT only

curve selection

t>

0.050.070.10.150.20.30.40.050.60.070.10.150.20.30.40.6

x1x1x1x1x1x1x1x10x1x10x10x10x10x10x10x10

0.020.020.030.050.070.100.130.170.200.240.340.500.671.011.352.02

0.030.050.070.100.130.200.270.330.400.470.671.001.332.02.674.00

0.060.090.120.190.250.370.500.620.740.871.241.862.483.714.957.43

t> to> SI VI EI

VIP 300Settings

Equivalent Time Multiplier

warning

not timemultiplier

see table

warning

not timemultiplier

see table

11 12 13 14

D

15 17 18 16 19 20

E

1 2 3

C B A

4 5 6 9 107 8

47SCHNEIDER ELECTRIC

ProtectionVIP 300

Phase overcurrent setting

The numbers indicated below are thoseof the setting switches (refer to the diagram of the front panel on page 4)The letters indicate the curve characteristic as shown opposite.

Phase overcurrent setting:F ■ Setting current Is (4)G ■ Type of low set I> curve (5)

IDMT: SI, VI, EI, RI.Definite time: DT

H ■ DT low set pick-up I> (6)This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI,VI, EI, low set pick-up is fixed at 1.2 Is.

J ■ Low set time delay t> (7) and multiplier (8)

K ■ High set I>>(9)L ■ High set time delay t>>(10)

Earth fault setting

The principle is the same as for phaseprotection.

Set:F ■ Setting current Ios (14)G ■ Type of low setting Io> curve (15)

IDMT: SI, VI, EI, RIDefinite time: DT

H ■ DT low set pick-up Io> (16)This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI, VI, EI low set pick-up is fixed at 1.2 Is.

J ■ Low set time delay to> (17) and multiplier (18)

K ■ High set Io>>(19)L ■ High set time delay to>>(20)

Operation

The high and low set elementsoperate separately. The tripping orderresults from the “ logical OR” betweenthe two settings.

Is

SI, VI, EI RIG

F

J

K

Lt>>

1.2 Is 10 Is I>>

t>

tIDMT curve selection

Is

DT G

Lt>>

t>

I>1.2 Is I>>

F

J

K

H

tDT curve selection

WARNING

VIP 300 relay will not work without the appropriate settings

48 SCHNEIDER ELECTRIC

ProtectionVIP 300

1 Phase overcurrent setting area

All information concerning the phaseovercurrent is grouped together in theupper half of the front panel. The section numbers below are related tothe numbering on the drawing shownon page 46.

2 Phase overcurrent pick-up indicator

When the red LED blinks, it indicatesthat the low set element has pickedup. If the current does not decreasebelow the pick-up level the relay willtrip.■ For IDMT curves (SI, VI, EI) the

LED blinks when the current is greater than 1.2 times the setting current Is.

■ For the IDMT curve (RI), the LED blinks when the current is greater than the setting.

■ For the DT curve, the LED blinks when the I> pick-up setting is exceeded.

Also refer to “indicator reset button”(page 51).

3 Phase overcurrent trip indicator

The indicator is normally black andturns yellow when the phase overcurrent has given a tripping order.It stays yellow, even when the relay isde-energised.

4 Setting current Is

The setting depends on the currenttransformer (CT) used, and the rangeselected via the connections made tothe back of the relay. The scale labelinserted should match the CT andrange selected. The switch can thenbe positioned to the primary current magnitude required in amperes.

Phase overcurrent 5 Choice of low set curve

SI : Standard inverse time.VI : Very inverse time.EI : Extremely inverse time.RI : Specific curve

- consult Schneider ElectricDT : Definite time.Off : Low set is disabled.

6 Low set pick-up (DT only) I>

The setting is a multiple of Is. It is onlyactive when the low set curve type DTis selected.

If the tripping curve is selected withIDMT (selector switch 5 set to SI, VI, EI, RI) the selector switch has no effect.

7 Low set time delay t>

■ If the DT curve is selected, the value shown is the low set time delay.

■ For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Is.

8 Multiplying factor (low set)

In the x10 position, the time delay displayed on switch 7 is multiplied by10.

9 High set pick-up I>>

The high set is chosen as a multiple ofthe current Is. In the “off” position, thehigh set is disabled.

10 High set time delay t>>

Time delay is set directly in seconds.

VIP300129

156

204

off3 (x Is)

0.20.150.30.1

0.40.07

0.60.05

0.40.20.60.1

0.90.05

1.50.03

t>>(s)

I>>

Is

4842 5636 64

30 7224 80

20 90100(A)

I>

I>

trip

reset

x10

sensors:200/1 4509996A0VIP300LH range: x2

phaseovercurrent

x1

EIVISI

offRI

DT

(s)

2.11.82.41.5

2.71.2

31 (x Is)

DT only

curve selection

t>

0.050.070.1

0.150.20.30.4

0.050.6

0.070.1

0.150.20.30.40.6

x1x1x1x1x1x1x1x10x1x10x10x10x10x10x10x10

0.020.020.030.050.070.100.130.170.200.240.340.500.671.011.352.02

0.030.050.070.100.130.200.270.330.400.470.671.001.332.0

2.674.00

0.060.090.120.190.250.370.500.620.740.871.241.862.483.714.957.43

t> to> SI VI EI

VIP 300Settings

Equivalent Time Multiplier

warning

not timemultiplier

see table

49SCHNEIDER ELECTRIC

The setting principle is the same asfor phase overcurrent.

11 Earth fault setting area

All information concerning earth faultsettings are grouped together in thelower half of the front panel. Sectionnumbers below are related to the numbering on the drawing shown onpage 46.

12 Earth fault pick-up indicator

When the red LED blinks, It indicatesthat the low set element has pickedup. If the current does not decreasebelow the pick-up level the relay willtrip.■ For IDMT curves (SI, VI, EI) the

LED blinks when the current is greater than 1.2 times the setting current Is.

■ For the IDMT curve (RI), the LED blinks when the current is greater than the setting.

■ For the DT curve, the LED blinkswhen the l> pick-up setting is exceeded.

N.B. The LED only blinks when thephase current is greater than the minimum operating current (refer tominimum operating current, page 51) Also refer to “indicator reset button”(page 51).

13 Earth fault trip indicator

The indicator is normally black andturns yellow when the earth fault element has given a tripping order. Itstays yellow, even when the relay is de-energised.

14 Setting current Ios

The setting depends on the currenttransformer (CT) used, and the rangeselected via the connections made tothe back of the relay. The scale labelinserted should match the CT andrange selected. The switch can thenbe positioned to the primary amp valuerequired.For earth fault relay operation: linkbetween contacts 2 and 9 (x2 range)and 1 and 9 (x4 range) must be madeat back of relay.

Earth fault 15 Choice of low set curve

SI :Standard inverse time.VI :Very inverse time.EI :Extremely inverse time.RI :Specific curve.DT :Definite time.Off :Low set is disabled.

16 Low set pick-up (DT only) Io>

The setting is a multiple of Ios. It isonly active when the low set curvetype DT is selected. If the trippingcurve is selected with IDMT (selectorswitch 15 set to SI, VI, EI, RI) theselector switch has no effect.

17 Low set time delay to>

■ If the DT curve is selected, the value shown is the low set time delay.

■ For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Ios.

18 Multiplying factor (low set)

In the x10 position, the time delay displayed on switch 17 is multiplied by 10.

19 High set pick-up Io>>

The high set is chosen as a multiple ofthe current Ios. In the “off” position, thehigh set is disabled.

20 High set time delay to>>

Time delay is set directly in seconds

0.40.20.60.1

0.90.05

1.50.03

to>>(s)

129156

204

off3 (x Ios)

2.11.82.41.5

2.71.2

31 (x Ios)

0.20.150.30.1

0.40.07

0.60.05

to>(s)

curve selection

DT onlyIo> Io>>

Ios

2416 3212 40

8 504 60

2 7080(A)

reset

trip

Io>

earth fault

minimum operatingphase current: 20A

x10

x1

VAP6 test plug

EIVISI

offRI

DT

warning

not timemultiplier

see table

ProtectionVIP 300

50 SCHNEIDER ELECTRIC

ProtectionVIP 300

Other functions A. Setting scale label

■ The label indicates the range for the phase overcurrent and earthfault primary amp settings. It isinserted from the top, behind thetransparent part of the front panel.

■ The label is reversible and is printed with the x2 range setting currents on one side, and the x4 range setting currents on the other. The scale label when inserted should match the CT and terminal positions on the rear of the relay, for the range required.

Also refer to “testing and commissioning”.

B. CT and range indication

The CT and range are given on eachside of the setting scale label. The labelwill match the appropriate CT for theRingmaster panel type supplied. Thisinformation is hidden when the label isinserted.

Choice of setting scale label

■ Make sure that the information given on the top of the label matches:1 - The current transformer used:

200/1A, 400/1A or 800/1A2 - The range used.

x2 or x4

This information is hidden when thelabel is in position.

■ For help with the choice of range to select, refer to the application section.

Installation

■ Slide the setting scale into position behind the transparent part of the front face.

■ Make sure the label is pushed right into the bottom of the slot. To remove the label, use the hole in the top, if necessary with the help of the tip of a pencil or a screwdriver.

VIP 300LH range: x2

(A)

sensor200/1: 4509996A0

Is4842 56

36 6430 7224 80

20 90100

sensor200/1: 4509996A0

VIP 300LHrange: x4

Is9684 112

72 12860 14448 160

40 180200

minimum operatingphase current: 20A

Ios2416 32

12 408 504 60

2 7080

minimum operatingphase current: 40A

(A)

(A)

x 2 range

Reversible scale label for Ringmaster fitted with 200/1A CT’s

Ios4832 64

24 8016 1008 120

4 140160(A)

x 4 range

x 2 range x 4 range

Reversible scale label for Ringmaster fitted with 400/1A CT’s

VIP 300LH range: x2

(A)

sensor400/1: 451101200

Is9684 112

72 12860 14448 160

40 180200

sensor400/1: 451101200

VIP 300LHrange: x4

Is192168 224

144 256120 28896 320

80 360400

minimum operatingphase current: 40A

Ios4832 64

24 8016 1008 120

4 140160

minimum operatingphase current: 80A

(A)

(A)

Ios9664 128

48 16032 20016 240

8 280320(A)

VIP 300LH range: x2

(A)

sensor800/1: 4509169A0

Is192168 224

144 256120 28896 320

80 360400

sensor800/1: 4509169A0

VIP 300LHrange: x4

Is384336 448

288 512240 576192 640

160 720800

minimum operatingphase current: 80A

Ios9664 128

48 16032 20016 240

8 280320

minimum operatingphase current: 160A

Ios192128 256

96 32064 40032 480

16 560640

(A)

(A)

(A)

x 2 range x 4 range

Reversible scale label for Ringmaster fitted with 800/1A CT’s

51SCHNEIDER ELECTRIC

ProtectionVIP 300

C. Indicator reset button

The reset button can be operated withthe sealable cover either open orclosed. When the button is pressed, thefollowing actions are initiated:■ It resets the phase overcurrent

and earth fault trip indicators. N.B. If reset is more than 48 hours after the relay has operated and is left without being energised, the VAP6 must be used to reset the trip indicators or the operator must wait for the relay to be re-energised.

■ The two red LED’s light up simultaneously for approximately three seconds to indicate the following:- The relay is energized and the minimum operating current level has been reached.-The relay self testing results are healthyN.B.If one of the two conditions is not met, the indicators do not light up.

This function may be used to carry outa basic relay operation test.

D. Minimum operating current

The minimum operating current is thephase current required for the relay tobe energized and operational. The setting depends on the CT used, andthe range selected via the connectionsmade to the back of the relay. Thevalue given on either side of the scalelabel is the single phase RMS minimum operating current.

N.B. Regarding minimum operatingcurrent:

The VIP 300 does not operate belowthe minimum operating current level.As a result, if the earth fault setting(Ios) is below the minimum operatingcurrent, it will only take effect whenthere is phase current greater than orequal to the minimum operating current.

E. VAP6 test plug

The test plug is exclusively designed forconnection of the VAP6 which is usedfor fast, simplified relay testing.The operation may be carried out whilethe relay is operating since the VAP6and VIP 300 provide the possibility oftesting with inhibition of circuit breakertripping.

Fitting of reversible scale label

52 SCHNEIDER ELECTRIC

ProtectionVAP6

The VAP6 is a portable unit which isconnected to the VIP 300 to carry outsimplified testing.The test can be carried out in the following two cases:

- the VIP 300 is already powered up by the sensors (CT’s).- The VIP 300 is not supplied. In this case, the VAP6 batteries supply power to the relay.

Push buttons:

1 ■ Battery test:If the batteries are healthy, the “on” indicator(A) lights up when the button is pressed.

2 ■ Phase overcurrent:Sends the phase overcurrent test stimulus, which is equivalent to 20 times the setting current Is.

3 ■ Earth fault:Sends the earth fault test stimulus, which is equivalent to20 times the earth setting current Ios.

4 ■ Trip inhibition:By pressing and holding this button down the relay can be tested with the VAP6 without tripping the circuit breaker. This facility will inhibit the circuit breaker tripping even if a real fault occurs during the test.

VAP6 front panel Indicators

A ■ On:Indicates that the batteries are operating. Also lights up when the battery test is carried out by pressing “battery test”.

B ■ Test in progress:Confirms sending of the test stimulus to the VIP 300.

C ■ Trip:Is used to test other relays in the VIP range. It is not to be considered for the VIP 300 test (it lights up for a transient period when the VIP 300 sends a tripping order; whether or not the circuit breaker is inhibited).

D ■ “External MITOP” output:This feature may be used to connect an external MITOP trip coil which could be used to operate a timer etc. The external coil is triggered at the same time as the circuit breaker MITOP. The trip inhibit button does not effect the external coil.

Batteries:

■ The batteries are normally deactivated and are automatically activated when the VAP6 is connected to the VIP 300. They are activated in the following cases:- Pressing the “battery test” button.- Direct connection to a VIP 300relay.

■ To install or change the batteries,open the unit by removing the 4 screws on the bottom of the unit. Be sure to use the correct polarities.

Technical characteristics:

Supply: 3 x 9V 6LR61 batteries

Weight: 0.45KGDimensions: 93 X 157 X 45mm

I>

on

external mitop

VAP6

+ -

test in progress

trip

tripinhibition

earth fault

phase overcurrent

battery test

circuit breakermitop

circuit breakermitop

earth fault VIP 30VIP 35VIP300VIP50VIP75

VIP 11, 11RVIP 12RVIP13VIP17VIP200, 201

test

phaseovercurrent

test

phaseovercurrent

trip tripinhibition

externalmitop

A

B

C

D

4

D

1

2

3

53SCHNEIDER ELECTRIC

ProtectionVAP6

The test may be carried out with orwithout the relay energised by theRingmaster current transformers, andall the relay settings are effective.During the test, the relay remains operational and will give a trippingorder in the event of a fault, unless the“trip inhibit” button is pressed and helddown.

Connect the VAP6 to the “VAP6 testplug”. The VAP6 batteries are activatedand the “on” indicator lights up.

Press the “trip inhibition” button if thetest should be carried out without tripping the circuit breaker.Be sure to continue pressing the “trip inhibition” button throughout thetime it takes to send the stimulus.

The test consists of:- Initiation of the VIP 300 self monitoring and diagnostic routine.- Injecting a stimulus to stimulate a phase fault. - Check trippingThe VAP6 is supplied by batteries. Therefore the parts of the VIP 300 that run on ACcurrent are not checked using this method (input and supply circuits).

Press the “phase overcurrent” button tosend the test stimulus.

- Continue pressing the button throughout the duration of the stimulus. The stimulus represents about 20 times the setting current Is.-The VAP6 “test in progress” indicator lights up to confirm the sending of the stimulus to the VIP300 relay.- The red “I>” indicator of the VIP300 blinks during the time relay delay period.- Then the VIP 300 phase “trip” indicator turns yellow.- The circuit breaker trips if it is not inhibited.

N.B. If the “phase overcurrent” button isheld down after tripping, the VIP300starts the time delay/tripping cycleagain; this is normal operation. In that case:

- The VAP6 red “trip” indicator lights up for a transient period each time there is a trip.- Depending on the time delay setting, the VIP 300 red “I>” indicator may be off or blink rapidly and/or in an irregular manner.

Press “earth fault” to test the relaysoperation. The stimulus injected is equalto 20 times the setting current Ios. Usethe procedure as for the phase overcurrent test.

Disconnect the VAP6. In order to savebatteries, do not leave the VAP6 connected to the relay unnecessarily.

54 SCHNEIDER ELECTRIC

CommissioningChecks and tests

Commissioning

Physical checks

Functional checks

High voltage withstand test toIEC60694 and IEC62271-200.

All equipment is subject to stringent quality and operational checks prior todespatch. However it is the owners responsibility to ensure that commissioning tests have been completed to IEC60694. The following is a resumeof those tests.

Remove all packaging and transit labels from the equipment. Check the data platedetails against the specification. Check the operation of the switches/circuit breaker, test access and various interlocks.

Check confirmation of auxiliary switch contacts and remote indication in accordance with the schematic diagram.Confirm the phase relationship of the neon indicator sockets.Check the pick up voltage of auxiliary coils if fitted, a.c. coils should operatebetween 85% and 110% of the rated voltage, d.c. coils should operate between70% and110% of the rated voltage.

Note: All voltages should be applied instantaneously unless otherwise specified.

Connect the H.V. test set as shown in the diagrams an carry out the withstand tests in accordance with the following tables.

FRONT

RN2c

RN2c/RE2c/RN6c

CE2/CE6/SE6 or SN6/CN2

(enclosed in busbar chamber)

B1Y1R1

B2Y2R2 B3Y3R3

R1Y1B1

R2Y2B2

55SCHNEIDER ELECTRIC

CommissioningTests

H.V. withstand - contd.

Test voltages

Test connection - circuit breaker/switch - CE2/CE6/SN6

3.6 8 50 1 (AC) 15 (DC) 7.5

7.2 16 50 1 (AC) 15 (DC) 15

12 23 50 1 (AC) 15 (DC) 25

13.8 32 50 1 (AC) 15 (DC) 32

test number

1

2

3

4

5

6

CB / switch

closed

closed

closed

closed

open

open

live terminals

R, Y, B

R, Y

Y, B

B, R

R1, Y1, B1

R2, Y2, B2

earthed terminals

frame

B, frame

R, frame

Y, frame

R2, Y2, B2, frame

R1, Y1, B1, frame

rated voltage(kV)

a.c. test voltage(kV)

frequency(Hz)

duration(minutes)

(d.c. test voltage - current practice)

Test connection - ring main unit - RN2c/RN6c

test number

1

2

3

4

5

6

ring switch 1 ring switch 2

closed closed closed

closed closed

closed open

closed open

open

open

closed

closed

closed

closed

closed

open

open

circuit breaker live terminals

R1, B1

Y1

R1, Y1 B1

R2, Y2, B2

R2, Y2, B2

R1, Y1, B1, R3, Y3, B3

earthed terminals

Y1, frame

R1, B1, frame

R2, Y2, B2, frame

R1, Y1, B1, frame

R1, Y1, B1, R3, Y3, B3 frame

R2, Y2, B2, frame

56 SCHNEIDER ELECTRIC

CommissioningTests

R1, Y1, B1

R2, Y2, B2

R3, Y3, B3

Diagram of connections - RN2

xR2, Y2, B2

R1, Y1, B1

Diagram of connections - circuit breaker / switch

o

Note: Ensure VT primary connections are isolated prior to HV pressure testing equipment.

When applying AC/DC test voltages greater than 12kV additional insulationmust be added to the bushing sleeve to prevent damage.The bushing sleeve is designed to be used in conjunction with some additionalmethod of insulation, such as econ boot or heatshrink termination boots.Due to the compact design of the bushing, permanent damage could result fromhigh voltage stress if additional insulation is not used during testing.

H.V. withstand - contd.

CAUTION

57SCHNEIDER ELECTRIC

CommissioningTests

Removable Earth Link

A

R1

Y1

B1

Circuit breakercontacts

50/100A a.c.

Selectphase

Removable Earth Link

0 - 5A

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Red phase TFL

Blue phase TFL

Earth fault TFL(if lifted)

R2 Y2 B2

Selectphase

Terminal block

C11

C31

C51

Selectphase

C70

Circuit breaker auxiliary tests

C.T. ratio test1 remove test link2 select required C.T. ratio at changeover

link3 connect ammeter (0-5A a.c.) as shown 4 select R, Y or B phase to be tested 5 connect primary injection test equipment

as shown6 operate the circuit breaker (and

respective ring switch if applicable)mechanism to "Main On"

7 inject C.T. rated primary current (100A or50A) in each phase in turn (R1-R2), (Y1-Y2), (B1-B2)

8 note indicated current on ammeter during each test, at C.T. rated primary current ammeter should indicate 5A

All secondary wiring has been 2kVinsulation tested at our works. Wetherefore recommend that testing onsite is done with a 1,000 volt meggerand not re-stressed at 2kV.

The following tests have been conducted during manufacturing(except CT insulation test, magnetisation curve), and are to beused as a guide for commissioningpurposes.

Remove all earth connections and testthe wiring to earth. For units fitted witha VIP relay please refer to the VIPuser guide.

Ringmaster circuit breakers

Panel types CN/CE

Ringmaster Cring main units

Panel types RN2c/RE2c/RN6c

58 SCHNEIDER ELECTRIC

CommissioningTests

Ringmaster Cring main units

Ringmaster circuit breakers

Removable Earth Link

mA

R1

Y1

B1

Circuit breakercontacts

Switch 'S'

Selectphase

Removable Earth Link

d.c. milliammeter

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Red phase TFL

Blue phase TFL

Earth fault TFL(if lifted)

R2 Y2 B2

Selectphase

Terminal block

C11

C31

C51

Selectphase

6V - 12Vd.c.+ve

-ve

+ve-ve

C70

Circuit breaker auxiliary tests

C.T. polarity test1 Remove test link2 Connect a d.c. analogue milliammeter

(centre scale "zero" preferred) as shown3 Select, R, Y or B phase to be tested4 Connect d.c. voltage source as shown

ensuring correct polarity5 Operate the circuit breaker (and

respective ring switch if applicable) mechanism to "Main On"

6 Close switch "S" and note positive direction of dc milliammeter movement. If negative direction is observed C.T.polarity is incorrect.

Panel types CN/CE

Panel types RN2c/RE2c/RN6c

59SCHNEIDER ELECTRIC

CommissioningTests

Removable Earth Link

mA

R1

Y1

B1

Circuit breakercontacts

Selectphase

Removable Earth Link

0 - 10mA a.c.

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Temporary TFL Shorting Link

Earth fault TFL(if lifted)

R2 Y2 B2

Terminal block

C11

C31

C51

Three phaseshorting link(100A rated)

C70

50/100A a.c.

Temporary TFL Shorting Link

C.T. spill test1 Remove test link2 Select required C.T. ratio at changeover

link3 Connect 3 phase short circuiting link

(100A rated) at R1, Y1 and B1 connections

4 Replace R and B.T.F.L.'s for temporary shorting links as shown Note: a shorting link in parallel withthe earth fault coil is not required

5 Connect an a.c. milliammeter as shown 6 Select R-Y, Y-B or R-B phases to be

tested7 Connect primary current injection test

equipment as shown 8 Operate the circuit breaker (and

respective ring switch if applicable) mechanism to "Main On"

9 Inject C.T. rated primary current and note spill current indicated on ammeter

10 Spill current to be less than 10mAduring the test

11 Repeat for remaining pairs of phases (and C.T. ratio if required)

Ringmaster circuit breakers

Ringmaster Cring main units

Panel types CN/CE

Panel types RN2c/RE2c/RN6c

60 SCHNEIDER ELECTRIC

CommissioningTests

Ringmaster circuit breakers

Ringmaster Cring main units

Removable Earth Link

R1

Y1

B1

Circuit breakercontacts

Selectphase

Removable Earth Link

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Temporary TFL Shorting Link

Earth fault TFL(if lifted)

R2 Y2 B2

Terminal block

C11

C31

C51

Three phaseshorting link(100A rated)

C70

50/100A a.c.

Temporary TFL Shorting Link

T.F.L. / D.A.T. overcurrent tests -primary current injection1 Ensure removable earth link is fitted2 Select required C.T. ratio at changeover

link3 Connect 3 phase short circuiting link

(100A rated) at R1, Y1 and B1 connections

4 Replace R and B.T.F.L.'s for temporary shorting links as shownNote: a shorting link in parallel withthe earth fault coil is not required

5 Select R-Y, Y-B or R-B phases to betested

6 Connect primary current injection test equipment as shown

7 Operate the circuit breaker (and respective ring switch if applicable) mechanism to "Main On"

8 Inject C.T. rated primary current and remove the T.F.L. shorting links in accordance with the table below ensuring the correct action results

9 Repeat for remaining parts of phases(and C.T. ratio if required)

10 Note - with both R & B T.F.L. shortinglinks in circuit, the circuit breaker shouldnot trip during overcurrent testsNote: ensure test current does notreduce signification due to circuit impedance changes during this test

R - YR - YY - BY - BR - BR - B

RBBRRB

BRRBBR

no triptrip

no triptriptriptrip

phasesundertest In cct Out cct

T.F.L shorting link circuitbreakeraction

Panel types CN/CE

Panel types RN2c/RE2c/RN6c

61SCHNEIDER ELECTRIC

CommissioningTests

R1

Y1

B1

Circuit breakercontacts

0-50A a.c.

Selectphase

Removable Earth Link

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Temporary TFL Shorting Link

Earth fault TFL(if lifted)

R2 Y2 B2

Terminal block

C11

C31

C51

Three phaseshorting link(100A rated)

C70

Temporary TFL Shorting Link

T.F.L. / D.A.T. earth fault tests - primary current injection1 Ensure removable test link is fitted2 Select required C.T. ratio at changeover

link3 Connect 3 phase short circuiting link

(100A rated) at R1, Y1, and B1 connections

4 Replace R and BT.F.L.'s for temporary shorting links as shownNote: a shorting link in parallel withthe earth fault coil is not to be fitted

5 Select R, Y or B phase to be tested6 Connect primary current injection test

equipment as shown7 Operate the circuit breaker (and

respective ring switch if applicable) mechanism to "Main On"

8 Inject a primary current instaneously(pulse) not gradually in accordancewith the table below ensuring the correct actions result and the tripping levels arewithin tolerance

9 Repeat for remaining pairs of phases (and C.T. ratio if required)

RYB

RYB

50/5A50/5A50/5A

100/5A100/5A100/5A

20 - 26.5 A20 - 26.5 A20 - 26.5 A

25 - 31 A25 - 31 A25 - 31 A

triptriptrip

triptriptrip

Rangephasesundertest

C.T. ratio trip levelscircuit

breakeraction

RYB

RYB

50/5A50/5A50/5A

100/5A100/5A100/5A

19 - 28 A19 - 28 A19 - 28 A

24 - 33 A24 - 33 A24 - 33 A

triptriptrip

triptriptrip

RN2cphasesundertest

C.T. ratio trip levelscircuit

breakeraction

Ringmaster circuit breakers and switches

Ringmaster Cring main units

Panel types CN/SN/CE/SE

Panel types RN2c/RE2c/RN6c

62 SCHNEIDER ELECTRIC

CommissioningTests

Removable Earth Link

R1

Y1

B1

Circuit breakercontacts

Removable Earth Link

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Temporary TFL Shorting Link

Earth fault TFL(if lifted)

R2 Y2 B2

Terminal block

C11

C31

C51

C70

Select pairsof phases

0 - 5A a.c.

Temporary TFL Shorting Link

R - YR - YY - BY - BR - BR - B

RBBRRB

BRRBBR

no triptrip

no triptriptriptrip

phasesundertest In cct Out cct

T.F.L shorting link circuitbreakeraction

T.F.L. / D.A.T. overcurrent tests - secondary current injection1 Ensure removable earth and test links

are fitted2 Select required C.T. ratio at changeover

link3 Replace R and BT.F.L.'s for temporary

shorting links as shownNote: a shorting link in parallel with the earth fault coil is not required

4 Select R-Y, Y-B or R-B phases to betested

5 Connect secondary current injection test equipment as shown

6 Operate the circuit breaker mechanism to "Main On"

7 Inject a secondary current of 5A andremove the T.F.L. shorting links in accordance with the table below ensuring the correct actions result

8 Repeat for remaining phases(and C.T. ratio if required)Note: ensure test current does not reduce significantly due to circuit impedance changes during this test

Ringmaster circuit breakers and switches

Ringmaster Cring main units

Panel types CN/SN/CE/SE

Panel types RN2c/RE2c/RN6c

63SCHNEIDER ELECTRIC

CommissioningTests

Removable Earth Link

R1

Y1

B1

Circuit breakercontacts

0 - 5A a.c.

Removable Test Link

50/5A Ratio

C250

C230

C210

C70

C150

C130

C110

100/5A Ratio

Rapid changeover link

Blue o/c coilS3

S2S1

Earth fault coil

Red o/c coil

Temporary TFL Shorting Link

Earth fault TFL(if lifted)

R2 Y2 B2

Selectphase

Terminal block

C11

C31

C51

C70

Temporary TFL Shorting Link

RYB

RYB

50/5A50/5A50/5A

100/5A100/5A100/5A

2.0 - 2.65 A2.0 - 2.65 A2.0 - 2.65 A

1.25 - 1.55 A1.25 - 1.55 A1.25 - 1.55 A

triptriptrip

triptriptrip

rangephasesundertest

C.T. ratio trip levelscircuit

breakeraction

RYB

RYB

50/5A50/5A50/5A

100/5A100/5A100/5A

1.7 - 2.8 A1.7 - 2.8 A1.7 - 2.8 A

1.1 - 1.65 A1.1 - 1.65 A1.1 - 1.65 A

triptriptrip

triptriptrip

RN2cphasesundertest

C.T. ratio trip levelscircuit

breakeraction

T.F.L. / D.A.T. earth fault tests - secondary current injection1 Ensure removable earth and test links

are fitted2 Select required C.T. ratio at changeover

link3 Replace R and BT.F.L.'s for temporary

shorting links as shownNote: a shorting link in parallel withthe earth fault coil is not to be fitted

4 Select R, Y or B phase to be tested5 Connect secondary current injection test

equipment as shown6 Operate the circuit breaker mechanism

to "Main On"7 Inject a secondary current instaneously

(pulse) not gradual increase in accordance with the table below ensuring the correct actions result andthe tripping levels are within tolerance

8 Repeat for remaining phases (and C.T.ratio if required)

Ringmaster circuit breakers

Ringmaster Cring main units

Panel types CN/CE

Panel types RN2c/RE2c/RN6c

64 SCHNEIDER ELECTRIC

CommissioningTests

Current transformer insulationtest (magnetisation curve singlepoint test)

1 Remove C70 test link.2 Remove ratio link.3 Increase test voltage to 1.3 x the

knee point voltage.4 Decrease voltage to the appropriate

knee point voltage (detailed below) for the respective CT ratio under test.

Ratio Knee point Typicalvoltage magnetisation

current100/5A 9v 470mA 10%50/5A 4.5v 940mA 10%

5 Replace both the test and ratio links.

Ringmaster circuit breakers

Ringmaster Cring main units

Panel types CN/CE

Panel types RN2c/RE2c/RN6c

+-+-

65SCHNEIDER ELECTRIC

CommissioningCommissioning Ringmaster with VIP 300

Since the system is fully tested it is only necessary to prove the relay on site at the servicesettings, therefore reducing commissioning time to a minimum.Once the switchgear has been installed and cabled up, it is impractical or sometimes impossible to carry out injection tests. It is suggested that for commissioning and maintenance purposes either of the following two methods can be used.1. Simple trip test using the VAP6 test unit (described previously).2. Secondary injection using standard equipment with an output filter.

Factory tests:

Testing using secondary injection is used to test the following parts of the protection system:■ The electronic circuit.

■ The integrity of the power supply of the VIP 300.■ The link to the mitop trip coil and also the circuit breaker mechanical tripping

mechanism.■ The integrity of the switches on the front panel to ensure they give the correct tripping times for the curves selected.

■ The “MITOP” trip coil must be used only in conjunction with the VIP relay.■ Voltage withstand testing of the aux i l ia ry and control circuits at 2000V AC for 1 minute

should never be carried out without disconnecting the MITOP trip coil or VIP relay.■ Secondary injection facilities are provided on the terminal rail in the pilot cable box.■ No external connections should be made to the VIP 300 or theMITOP trip coil.

All Ringmaster panel types are fully tested before leaving the factory. These tests include thewhole protection system including current transformers, wiring harness, relay, trip coil and thecircuit breaker itself using primary injection to energise the system. Tripping tests are carriedout using different settings for each of the IDMT and DT curves available on the relay. Thetripping times are measured with a chronometer and its accuracy is verified against the theoretical times calculated.

Note: When using a secondary injectionset with VIP 300 a filter (e.g. FosterSF30) should be used to improve thewave form. If a filter is not used theoperating time of the relay may not follow the theoretical operating times.

VIP 300 IDMT RELAY

P1

P2

S1

S2

C11

MITOP - ITC

S2

CT1

52

P1

P2

S1

S2

P1

P2

S1

S2

C114

5

6

7

8

9

10

C31 C31

C51 C51

C10 C70

C30

C50 C70

C90

8

7

6

5

4

3

2

1

x4 range

minimumoperatingcurrent

950/51

50N/51N10

11

12

13

14

1516

0v

YR B

K8 (-VE)

K7 (+VE)

C7

1

Injection test setwith filter

CB auxiliary contact(for timing purposes)

connect to terminal blocks above for secondary injection

N.B. - Always check against the relevantCB schematic diagram before carryingout tests

MITOP - CB trip coil

40A,80A or 160A

x2 range

minimumoperatingcurrent

20A,40A or 80A

CAUTION

Reduced commissioning

Secondary injection

Test set connections: The injection set is connected to the VIP 300 relay without disconnecting the CT’s. This isdone via the sockets on the terminal rail located in the pilot cable box, just above the relayitself.

Phase overcurrent connections: To test the overcurrent protection the connection should be made across two CT’s (terminalrails no’s 4 to 5, 5 to 6 or 6 to 4).

Earth fault connections: To test the earth fault protection, the connection should be made across one CT(terminal rail no’s 4 to 7, 5 to 7, or 6 to 7).These terminal numbers should be cross checked with the relevant circuit breaker schematicdiagram. Terminals 15 and 16 (not shown above - see Ringmaster selection guide) giveaccess to a normally open contact, which is normally open when the CB is in the open position. This can be used to connect a timing device to measure the opening time of therelay and circuit breaker.The type of test plug used to connect to the DIN rail connectors is a standard 2mm 19A testplug.

66 SCHNEIDER ELECTRIC

CommissioningCommissioning Ringmaster with VIP 300

1. Pick-up check- Increase the current slowly until the appropriate LED indicator starts to blink.

2. Setting check:- Set the current to be injected (a true RMS ammeter should be used to measure the current).- The CB should then be closed and the counter/timer reset. The current should then be applied.- When the CB has operated, the applied current should be turned off if not done automatically.- The time shown on the counter display includes the operating time of the circuit breaker >80ms or <100ms. The actual relay operating time can then be calculated by subtracting this time from the counter reading.

Recommended test procedure for secondary injection:

Note: No connection should be made to the MITOP trip coil from the secondary injection test set.

*Note. These values exceed the rating of the circuit breaker.

RN2c, RE2c, CE2, CN2CT ratio 200/1A

Range x 2 Range x 4Minimum Operating

Current=20ASecondary

injected currentEquivalent

primary current

100mA 20A

120mA 24A

150mA 30A

180mA 36A

210mA 42A

240mA 48A

280mA 56A

320mA 64A

360mA 72A

400mA 80A

450mA 90A

500mA 100A

Minimum OperatingCurrent=40A

Secondary

injected currentEquivalent

primary current

200mA 40A

240mA 48A

300mA 60A

360mA 72A

420mA 84A

480mA 96A

560mA 112A

640mA 128A

720mA 144A

800mA 160A

900mA 180A

1A 200A

RN6cCT ratio 400/1A

Range x 2 Range x 4Minimum Operating

Current=40ASecondary

injected currentEquivalent

primary current

100mA 40A

120mA 48A

150mA 60A

180mA 72A

210mA 84A

240mA 96A

280mA 112A

320mA 128A

360mA 144A

400mA 160A

450mA 180A

500mA 200A

Minimum OperatingCurrent=80A

Secondary

injected currentEquivalent

primary current

200mA 80A

240mA 96A

300mA 120A

360mA 144A

420mA 168A

480mA 192A

560mA 224A

640mA 256A

720mA 288A

800mA 320A

900mA 360A

1A 400A

CE6, RN6cCT ratio 800/1A

Range x 2 Range x 4Minimum Operating

Current=80ASecondary

injected currentEquivalent

primary current

100mA 80A

120mA 96A

150mA 120A

180mA 144A

210mA 168A

240mA 192A

280mA 224A

320mA 256A

360mA 288A

400mA 320A

450mA 360A

500mA 400A

Minimum OperatingCurrent=160A

Secondary

injected currentEquivalent

primary current

200mA 160A

240mA 192A

300mA 240A

360mA 288A

420mA 336A

480mA 384A

560mA 448A

640mA 512A

720mA 576A

800mA 640A *

900mA 720A *

1A 800A *

The test procedure outlined here is only a guide and may need modifying to suitthe different test sets available.

The manufacturers instructions should be read before attempting to secondaryinject the VIP 300 relay.

The VIP 300 relay can be secondary injected like any conventional 1A relay, therefore the output recommended for 1A relays should be used.

Calculate the secondary current to be injected from the equivalent primary current,taking into account the CT’s used and the range selected by connections to theterminals on the back of the relay.

With the VIP 300 connected so as to present the correct burden, the following testscan be carried out:

67SCHNEIDER ELECTRIC

CommissioningCommissioning Ringmaster with VIP 300

Customer Site

Contact ref. Panel

Relay type Relay serial no.

Current transformers Setting range, minimum operating current

200/1A x2, 20A

x4, 40A

400/1A x2, 40A

x4, 80A

800/1A x2, 80A

x4, 160A

Note: Ensure connections on the rear of the relay are made to the appropriate terminals for the x2 or x4 setting ranges and that the scale labelsare inserted correctly to match the range selected.

Indicate on the diagram below actual settings. Carry out tests and record theresults in the table provided.

Commissioning test record:

Secondary injection of Schneider Electric VIP 300 self powered overcurrent and earth faultrelay.

✔ tick as appropriate

Mark settings with an arrow e.g.

Setting scale label selection to belocated at point “A” for appropriate CTtype 200/1A, 400/1A & 800/1A

VIP 300LH range: x2

(A)

sensor200/1: 4509996A0

Is4842 56

36 6430 7224 80

20 90100

sensor200/1: 4509996A0

VIP 300LHrange: x4

Is9684 112

72 12860 14448 160

40 180200

minimum operatingphase current: 20A

Ios2416 32

12 408 504 60

2 7080

minimum operatingphase current: 40A

(A)

(A)

Ios4832 64

24 8016 1008 120

4 140160(A)

VIP 300LH range: x2

(A)

sensor400/1: 451101200

Is9684 112

72 12860 14448 160

40 180200

sensor400/1: 451101200

VIP 300LHrange: x4

Is192168 224

144 256120 28896 320

80 360400

minimum operatingphase current: 40A

Ios4832 64

24 8016 1008 120

4 140160

minimum operatingphase current: 80A

(A)

(A)

Ios9664 128

48 16032 20016 240

8 280320(A)

VIP 300LH range: x2

(A)

sensor800/1: 4509169A0

Is192168 224

144 256120 28896 320

80 360400

sensor800/1: 4509169A0

VIP 300LHrange: x4

Is384336 448

288 512240 576192 640

160 720800

minimum operatingphase current: 80A

Ios9664 128

48 16032 20016 240

8 280320

minimum operatingphase current: 160A

Ios192128 256

96 32064 40032 480

16 560640

(A)

(A)

(A)

200/1A 400/1A 800/1A

VIP 300

0.40.20.60.1

0.90.05

1.50.03

to>>(s)

129156

204

off3 (x Is)

0.20.150.30.1

0.40.07

0.60.05

0.40.20.60.1

0.90.05

1.50.03

t>>(s)

129156

204

off3 (x Ios)

2.11.82.41.5

2.71.2

31 (s)

0.20.150.30.1

0.40.07

0.60.05

to>(s)

curve selection

DT onlyIo> Io>>

I>>I>

I>

trip

reset

trip

Io>

earth fault

x10

phaseovercurrent

x1

EIVISI

offRI

DT (s)

2.11.82.41.5

2.71.2

31 (x Is)

x10

x1

VAP6 test plug

EIVISI

offRI

DT

DT only

curve selection

t>

0.050.070.1

0.150.20.30.4

0.050.6

0.070.1

0.150.20.30.40.6

x1x1x1x1x1x1x1x10x1x10x10x10x10x10x10x10

0.020.020.030.050.070.100.130.170.200.240.340.500.671.011.352.02

0.030.050.070.100.130.200.270.330.400.470.671.001.332.0

2.674.00

0.060.090.120.190.250.370.500.620.740.871.241.862.483.714.957.43

t> to> SI VI EI

VIP 300Settings

Equivalent Time Multiplier

warning

not timemultiplier

see table

warning

not timemultiplier

see table

68

68 SCHNEIDER ELECTRIC

CommissioningCommissioning Ringmaster with VIP 300

Commissioning test record

1. Pick up check.Inject the test current into the relay for each phase in turn and note the current required to flash the LED.

2. Operating time and curve check at final settings.Inject the test current into the relay for each phase in turn and note the operating times.

3. Instantaneous trip checkInject the appropriate test current into the relay and ensure the correct instantaneous response.

Curve............... T.............. Curve........... T..............

Phase A-B Phase B-C Phase C-A EF

1. Pick-up current at setting

2. Operating time and curve at finalselected setting

3. Current level to trip high set

Commissioning test record4. Check test facility using

VAP6

Commissioning engineer Date

Customer witness Date

69SCHNEIDER ELECTRIC

Ringmaster operationRN2c, RE2c, RN6c essential checks

WARNING

Do not operate this equipment if needle is in the red zone or at zero.Equipment must be isolated and earth before removing any external covers. Pleaserefer to your local Schneider Electric office or UK customer service team, contactdetails can be found atthe front of this document.The option of voltage presence indicator (VPIS) system must be used as indication only. It should not beused as absolute proof of isolation.Do not earth a live cable which is being fed from the remote end. Check voltageof the respective breaker/switch before any operation of a Ringmaster unit.Failure to follow these instructions may result in personal injury.

! DANGER

Prior to energisingIt is recommended that to energising the unit all protection devices are checked toensure they are set correctly. For TLF units ensure that fuses are fitted. VIP unitsmust be set in accordance with the results of a protection co-ordination study.

WARNINGCurrent transformers not in useCurrent transformers (T200E and earth fault flow indicator) that are not going to beused during commissioning or during service, they must be shorted out otherwiseirreversible damage may occur to current transformers and/or the unit.

Note: This manual covers ring main units produced from June 1999, designated RN2c/RN6c/RE6c.For ring main units designated RN2/RN6 see earlier manual Ref: version 005December

!DO NOT OPERATE THIS EQUIPMENTIF THE NEEDLE IS IN THE RED ZONEOR AT ZERO.

EQUIPMENT MUST BE EARTHEDBEFORE REMOVING ANY EXTERNALCOVERS.

FAILURE TO FOLLOW THESEINSTRUCTIONS MAY RESULT IN PERSONAL INJURY.

70 SCHNEIDER ELECTRIC

Ringmaster operationMain features

RN2c

facia MIMIC of RN2coperating handle

Key

1 facia

2 operating handle (padlockable)

3 auxiliary/Protection LV compartment

4 test access key

5 data plate

6 main circuit label

7 gas pressure indicator

8 tripped on fault flag

9 main earth selector lever

Note: The operating handle can be used in two positions:1. With the handle protruding outside the unit dimensions.2. With the handle within the constraints of the unit.

7

6

8

9

2

4

3

5

1

71SCHNEIDER ELECTRIC

Ringmaster operationSwitch and circuit breaker

Manual operation of main switch/circuit breaker RN2c, RE2c, RN6c

Lift up hinged door. Check that thegas indicator is in the green, "healthy condition". Check the facia diagramfor the service condition. Remove padlocks if fitted.

Move selector to "Main Switch/Circuitbreaker" position. To operate selectorslide padlock sleeve towards selectorpivot point and rotate selector torequired position.

Insert handle as shown, aligning handle profile and direction of operation (arrow) to unit operationalsocket, for direction of operation.Firmly operate, in a rotational movement, the operating handle untilthe circuit breaker/switch closes.

Padlock fitted to circuit breaker/mainswitch in the “close in service position”.To open, remove “closed in serviceposition” padlock, if fitted, rotate handlethrough 180° and reverse procedure.

The selector lever will be locked in the“main switch/circuit breaker” positionwhen in the “closed in service” position.

Padlock fitted to circuit breaker/mainswitch selector.

Note: To operate to the “main on’ position the operating handle must be rotated in a clockwise direction for the circuit breaker/righthand ring switch and in an anti-clock wise direction for the left hand ring switch (as marked on the unit facia).

Note: The fitting of padlocks does not affect the electrical tripping of the unit.

72 SCHNEIDER ELECTRIC

Ringmaster operationEarth switch

Manual operation of earth switch RN2c, RE2c, RN6c

Lift up hinged door. Check that thegas indicator is in the green, "healthy condition". Check the facia diagramfor the “off” service condition. Remove padlocks if fitted. Move selector to“Earth Switch” position. To operateselector slide padlock sleeve towardsselector pivot point and rotate selectorto required position.

Insert handle as shown, aligning handle profile and direction of operation (arrow), to unit operationalsocket for direction of operation. Firmlyoperate, in a rotational movement, theoperating handle until the earth switchcloses.

The selector lever will be locked in the“earth switch” position when in the“closed in earth” position.

Padlock fitted to earth switch selector. Padlock fitted to earth switch in the“closed in earth position”. To open,remove “closed in earth position” padlock, if fitted, rotate handle through180° and reverse procedure.

Note: To operate to the “earth on’ position the operating handle must be rotated in an anti-clockwise direction for the circuit breaker/right hand ring switch and clockwise direction for the left hand ring switch (as marked on the unit facia).

Note: The unit will not electrically trip if an earth is applied onto a fault.

73SCHNEIDER ELECTRIC

Ringmaster operationCable testing

Cable testing - ring cables RN2c

Open LV compartment by depressinglever on lower edge of LV compartment. Remove padlock if fitted,at this point.

Ensure that the main earth switch is inthe “earth on” position. This will openthe key way.

Key way Insert test key (located inside LV cabinet)into key way.

The test access key will be locked inposition until the cover is firmly closed.Reverse procedure to return to servicecondition. Note: ensure cables are discharged before touching bushingsafter testing.

Turn lever clockwise. Remove testaccess cover padlock if fitted.

Pull test access cover down, utilisingoperating handle, to remove cableearth and provide access to the testingbushings (marked with red, yellow andblue phase dots).

74 SCHNEIDER ELECTRIC

Ringmaster operationCable testing

Cable testing - circuit breaker RN6c

Ensure that the CB earth switch is inthe “earth on” position.This will open the key way for the testkey.

key waytest key

The test key is located on the RN6cfascia as shown above. To remove the key, turn the black lever 90° anti-clockwise.

Insert the test key as shown and turnthe black lever 90° in a clockwise direction to lock in position.

Remove test access padlock (if fitted).Whilst holding black lever of test keydown, raise the CB test access cover.Note that some resistance will beencountered.

Lift CB test access cover clear of testcontacts. Note that the test key is nowlocked in position until the accesscover is firmly closed.Reverse procedure to return CB to service.

75SCHNEIDER ELECTRIC

Ringmaster operationCircuit breaker reset

Circuit breaker reset - electrical trip/tripped on fault RN2c, RE2c, RN6c

Motorpack circuit breaker reset - electrical trip/tripped on fault

Following a circuit breaker electricaltrip/tripped on fault operation the tripping spring has to be reset prior toa close operation. The orange trippedon fault flag (indicated with arrow) willbe displayed following the electricaltrip.

Insert handle as shown, aligning handle profile and direction of operation (arrow) to unit operationalsocket, for direction of operation.Firmly operate, in an anti-clockwiserotational movement, the operatinghandle until the orange tripped on faultflag changes to the white normal service condition, and the handlereaches the end stop.

On the resetting of the flag to whiteallow the operating handle to returnclockwise to the off position.To close the circuit breaker to the service/earth condition, refer to relevant section regarding manualoperation.

When a trip operation has occured, themotor intelligence will automaticallyreset the circuit breaker.

Note: To manually reset circuit breaker remove motorpack and follow above procedure.

76 SCHNEIDER ELECTRIC

Ringmaster operationMotorpack

Motorpack control RN2c, RE2c RN6c

Prior to connecting the motorpackcheck the facia diagram for serviceconditions. The service selector padlock, if fitted, can remain fitted withthe application of the motorpack.Note: The motorpack can only be fittedwhen the main switch/circuit breaker position is selected and not when the earthposition is selected.

Align both the motorpack male driveshaft and the electrical connector withthe female switch operating socketand electrical connector on the unitfacia.Note: The motorpack can be removed andreplaced in both the “Main On” and “MainOff” service conditions.

Offer motorpack to unit until fullengagement of both the drive and electrical connection are achieved.

For electrical operation of the motorpack with Easergy T200E refer to the Easergy T200E manual.

The motorpack protection fuse is located at the bottom right hand corneras above when the motor is removed.

The motorpack is fitted with a manualdrive, to release mechanism springtension, should the motor fail duringelectrical operation. Remove allenscrews (indicated with arrows) onmotorpack cover to access manualdrive screw.

Note: Only manual operation of the earth switch can be undertaken. To operate earth switch remove motorpack and follow “manualoperation of earth switch instructions.

77SCHNEIDER ELECTRIC

Ringmaster operationMotorpack operation

Motorpack control - RN2c, RN6c and RE2c

Operating voltage, current and time

RN2c/RN6c/RE2c close 24V d.c. 4A 5 sec.

RN2c/RN6c/RE2c open 24V d.c. 4A 5 sec.

RN2c/RN6c/RE2c reset (CB only) 24V d.c. 3.5A 11 sec.

panel type operation voltage current time

Values given are typical and may vary slightly between units.

+ 30%- 10%

+ 30%- 10%

+ 30%- 10%

78 SCHNEIDER ELECTRIC

Ringmaster operationNeon indication

Neon indication

Neon indication can be fitted as an optional item on the ringswitches and circuit breaker on the RN2c. The test socketsare located in the pilot cable box.

A garter spring is fitted to the relevant cable bushing whichforms a capacitive coupling with the HV conductor, derivingthe neon voltage.

Note: Circuit breaker neons cannot be fitted to transformer mounted units.Note: To achieve correct reading when using a phase comparitor please use Pfisterer Electronic Phase Comparator

EPV LRM System No.827 189-007 (available as kit RMR-A25)

79SCHNEIDER ELECTRIC

Ringmaster range operationCN2, SN6, CE2, CE6, SE6, MU2 essential checks

WARNING

Do not operate this equipment if needle is in the red zone or at zero.

Equipment must be isolated and earth before removing any external covers. Pleaserefer to your local Schneider Electric office or UK customer service team, contactdetails can be found atthe front of this document.

The option of voltage presence indicator (VPIS) system must be used as indication only. It should not be used as absolute proof of isolation.

Do not earth a live cable which is being fed from the remote end. Check voltageof the respective breaker/switch before any operation of a Ringmaster unit.

Failure to follow these instructions may result in personal injury.

! DANGER

Prior to energisingIt is recommended that to energising the unit all protection devices are checked toensure they are set correctly. For TLF units ensure that fuses are fitted. VIP unitsmust be set in accordance with the results of a protection co-ordination study.

WARNINGCurrent transformers not in useCurrent transformers (T200E and earth fault flow indicator) are not going to beused during commissioning or during service, they must be shorted out otherwiseirreversible damage may occur to current transformers and/or the unit.

!DO NOT OPERATE THIS EQUIPMENTIF THE NEEDLE IS IN THE RED ZONEOR AT ZERO.

EQUIPMENT MUST BE EARTHEDBEFORE REMOVING ANY EXTERNALCOVERS.

FAILURE TO FOLLOW THESEINSTRUCTIONS MAY RESULT IN PERSONAL INJURY.

80 SCHNEIDER ELECTRIC

Ringmaster range operationMain features

CN2/SN6

CE2/CE6/SE6

8

8

7

10

9

10

1

2

5

1

3

4/6

Key

1 facia

2 operating handle (padlockable)

3 auxiliary/Protection compartment

4 test access key (within LV pilot

box)

5 data plate/pilot box

6 main circuit label on pilot box

7 transformer earth switch

8 gas pressure indicator

9 tripped on fault flag

10 main selector lever

81SCHNEIDER ELECTRIC

Ringmaster range operationSwitch and circuit breaker

Operation of main switch/circuit breaker CE6, CE2, SE6, CN2, SN6

Operation of main earth CE6, CE2, SE6, CN2, SN6

Lift up hinged door. Check that the gasindicator is in the green, "healthy condition". Check the facia diagram forthe service condition. Remove padlocks if fitted.

Move select to "Main Switch" position.Insert handle as shown and pull downfirmly until the circuit breaker/switchcloses. The selector lever will belocked into the "main switch" position.Fit padlock into "CB closed in service"position if required.

Note: That this does not affect electricaltripping of the unit.

To open, rotate the handle through 180° and reverse the procedure.

To open, rotate the handle through180° and reverse the procedure.

Lift up hinged door. Check that the gasindicator is in the green, "healthy condition". Check the facia diagram forthe service condition. Removepadlocks if fitted.

With the switch/circuit breaker in theopen position, move selector lever to"earth switch position". Insert handleas shown and pull down firmly until theswitch closes. The selector will belocked in the "earth switch" position.Fit padlock into "circuit breaker/switchmain cable earthed" if required.

Note: That the unit will not trip on fault.

82 SCHNEIDER ELECTRIC

Ringmaster range operationEarth switch

Transformer earth switch SN6 and CN2 only

Opening earth switch

Open the main switch/circuit breaker.Move the selector lever (see page 81)to earth position. Do not re-close themain earth switch unless incomingcable earth is required. Movetransformer earth selector lever asshown above.

Pull lever forwards as shown to closeearth switch. Push back to rest position. The main selector levershould be locked in the earth position.

The switch can be padlocked "on" asshown above.

The transformer earth can now be padlocked off as shown above. Themain selector lever is now free tomove.

Remove padlock if fitted. Move transformer earth selector lever asshown above.

Turn lever clockwise as shown aboveuntil flag show "off" and mechanism isreset. Turn lever back to the rest position.

Closing earth switch

83SCHNEIDER ELECTRIC

Ringmaster range operationCable testing and actuator control

Cable testing main cable - CE6, CE2, SE6, CN2, SN6 and ring cables

Actuator control

Ensure that the main earth switch is"earth on". This will open the key way.

Insert test key (located in pilot cablebox compartment) into key way andturn lever anti-clockwise. Remove testaccess cover padlock if fitted.

Pull test access cover down to removecable earth and provide access to thetesting bushings, (marked with red, yellow and blue phase spots). The testaccess key will be locked in positionuntil the cover is firmly closed.Reverse procedure to return to servicecondition.Note: Ensure cables are discharged

before touching bushings after testing.

Rotate actuator mechanism anti-clockwise away from the handlesocket. Manual operation can be performed as normal. Reverse theprocedure to fit the actuator.

For electrical operation of the actuatorsee page 84 (if using Easergy T200Erefer to the Easergy manual).To earth the main cable, the actuatormust be removed. With the switch/circuit breaker in the open position, disconnect the actuator supply.

Lift the lever on the connecting bracket.

84 SCHNEIDER ELECTRIC

Actuator control - CE2, CE6, SE6 and SN6

Operating voltage, current and time

CE2/CE6 close 24V d.c. 9A 7 sec.

CE2/CE6 open 24V d.c. 5A 7 sec.

SE6/SN6 close 24V d.c. 5A 7 sec.

panel type operation voltage current time

SE6/SN6 open 24V d.c. 5A 7 sec.

Ringmaster range operationActuator control

+ 30%- 10%

+ 30%- 10%

+ 30%- 10%

+ 30%- 10%

85SCHNEIDER ELECTRIC

MaintenanceRecommendations and conditions

Routine maintenance recommendations toBS6626:1985

Environmental conditionsUnit installed and commissioned in accordance with the manufacturers instructionsIndoors, completely protected from the weather. Humidity below 40% and no dripping water. Minimal dust and air circulation. Ambient temperature between -5oC and +40oC.No contact with any chemical agents (eg. salt). No infestation of any animal life (eg. insects). No contact with any plant life (eg. mould). No earth movements. No damage to the unit of any kind.

Operational conditionsNo mal-operation of any kind. No abnormally high number of operations - refer to the graph on page 87. No abnormally high number of faults - refer to the graph on page 87. No over-voltage or over-current (above rating).

Environmental conditionsUnit installed and commissioned in accordance with the manufacturer’s conditions. Humidity below 60%. Unit may be indoors or outdoors but must not be subjected to regular extremes of weather eg.heavy rain storms, dust storms, heavy snow and ice, flooding, temperature cycles greater than 40oC or less than -20oC, dense coastal fog or acid rain. No regular or thick covering of leaves or other debris. No contact with any chemical agents (eg. salt). No infestation of animal or plant life. No earth movements. No damage to the unit of any kind.

Operational conditionsNo mal-operation of any kind. No abnormally high number of operations - refer to the graph. No abnormally high number of faults - refer to the graph. No over-voltage or over-current (above rating).

Any environmental or operational conditions which do not satisfy either of the above twodescriptions must be deemed aggressive.

Ideal conditions

Standard conditions

Aggressive conditions

Routine maintenance will depend on the conditions to which the unit is subjectedand to the relevant codes and practice. Periodic inspection of the substation andequipment will be necessary to establish the conditions to which the units are subjected to.

ideal conditions

gas enclosure

housing interior(mechos, etc.)

housing

protection system

standard conditions aggressive conditions

no attention no attention no attention

no attention

periodic inspection

periodic inspection

every 5 years

every 5 years

every 2 years

every 5 years every 5 years every 5 years

Note: Local legislation may dictate maintenance be carried out with greater frequency, irrespective of site conditions. Please contactyour local Schneider Electric representative for further details.

We recommend that after 50% of its rated fault operations the following is checked:■ Gas pressure■ Trip opening time■ Contact resistanceThe maximum number of fault interruptions can be calculated from the interrupting capacitygraph on page 88.

Post fault maintenance

86 SCHNEIDER ELECTRIC

MaintenanceHousing

Housing exterior

‘O’ rings must be scrupulously clean and wellgreased with petroleum jelly

RN2c/RN6c/RE2c filler pointModular switch / CB filler point

Check all external fixings, labels and earth connections are present and tight.

Check inside the main door (if fitted) and pilot cable box for heavy deposits of dust,ingress of water or contamination by animal or plant life. Check that the gas indicator is reading in the green zone.

Clean the units thoroughly and touch up paint work as necessary.

Open the main and pilot cable box door. Check that the gas indicator is in thegreen zone and the protector cap is fitted over the gas filler valve.

For circuit breaker panels check the electrical protection system - refer to commissioning instructions.

Check the operation of the unit and all mechanical interlocks.

filler point filler point

Housing interior

87SCHNEIDER ELECTRIC

MaintenanceCircuit breaker

Leakage of SF6 gasIn the extremely unlikely event of a gas leak contact your local Schneider Electric officeor UK customer service team immediately. Contact details can be found in the front ofthis document.

New SF6 gas is nontoxic and non combustible. However when exposed to an electricarc SF6 breaks down and becomes toxic.

Service lifeIf correctly installed and maintained the Ringmaster range of switchgear has a servicelife expectancy of 25 years.

10000

1000

100

10

1

1 10 100 1000 10000 100000

current interrupted (amperes)

num

ber

of

op

erat

ions

Prospective interrupting capacity

16kA version21kA version

The above applies to: RE2c, RE6c, CE2, CE6 and CN2 circuit breakers. It is not applicable to the ring switches of the ring main units or the SE6.

88 SCHNEIDER ELECTRIC

Notes

Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems and is focused on the needs of both thecommercial and industrial sectors. The newly launched VDINetwork Solutions offer provides flexible, configurable ethernet systems for all communication needs.

Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltageelectrical distribution equipment, systems and services areused extensively in residential and commercial applications.

Telemecanique is a UK market leader and world expert inautomation and control. It provides complete solutions, withits range of components, Modicon range of high technologyprogrammable controllers (PLCs), multiple fieldbus and ethernet communication networks, HMI, motion control systems, variable speed drives and communications software. In addition, it offers power distribution through prefabricated busbar trunking.

Schneider Electric’s local supportSchneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largestdedicated sales force in the UK electrical industry, operate from 4 customer support centres.

Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.

To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includesfacilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.

www.schneider-electric.co.uk

ScotlandSchneider Electric LtdUnit 18 Claremont Centre112a Cornwall Street SouthKinning ParkGlasgow G41 1AA

South WestSchneider Electric LtdPO Box 41Langley RoadChippenhamWiltshire SN15 1JJ

North WestSchneider Electric LtdFirst Floor Market HouseChurch StreetWilmslowCheshire SK9 1AY

Industrial systems and solutions showroomSchneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ

Building systems and solutions showroomSchneider Electric Ltd, Stafford Park 5, Telford, Shropshire TF3 3BL

Energy and Infrastructure systems and solutions showroomSchneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS

Product showrooms

Local customer support centres

Fax 0870 608 8 6060870 608 8 608Nationwide support on one number - call the Customer Information Centre on

member of

.co.uk

SE6251 NOV 2007