7/21/2019 Catalogue Ringmaster Part1
1/70
Ringmaster
Medium Voltage Distribution
Ring Main Unit
Catalogue2009
-
7/21/2019 Catalogue Ringmaster Part1
2/70
A new path for achieving your electrical installations
A comprehensive offer
The Ringmaster range is part of a comprehensive offer of products that are perfectlycoordinated to meet all medium and low voltage electrical distribution requirements.All of these products have been designed to work together: electrical, mechanicaland communication compatibility.The electrical installation is thus both optimised and has improved performance:@ better service continuity,@ increased personnel and equipment safety,@ guaranteed upgradeability,@ efficient monitoring and control.You therefore have all the advantages at hand in terms of know-how and creativityfor achieving optimised, safe, upgradeable and compliant installations.
Tools for facilitating the design and installation
With Schneider Electric, you have a complete range of tools to help you get to know andinstall the products whilst complying with current standards and good working practices.These tools, technical sheets and guides, design software, training courses, etc areregularly updated.
For a real partnership with you
A universal solution doesnt exist because each electrical installation is specific.The variety of combinations on offer allows you to truly customise the technical solutions.You are able to express your creativity and put your know-how to best advantagewhen designing, manufacturing and exploiting an electrical installation.
Schneider Electric is associating itself with
your know-how and your creativity to produce
optimised, safe, upgradeable and compliant
installations
-
7/21/2019 Catalogue Ringmaster Part1
3/701AMTED399086EN.indd
Presentation 2
Applications 2
Switchgear description 3
VIP protection relays 5
Network remote control 6
Ringmaster selection guide 8
Section 1 9
Ring main units 10 - 25
Circuit breaker, metering and switches 26 - 65
Remote control 66 - 68
Section 2 69
Installation drawings 70 - 80
Schematic diagrams 81 - 112
Section 3 113
Accessories 114 - 119
Section 4 121
Schneider Electric, an overview and order form 122 - 128
Ringmaster range General contents
-
7/21/2019 Catalogue Ringmaster Part1
4/702 AMTED399086EN.indd
Ringmaster range
PresentationApplications
Ringmaster is the ideal choice for all your MV applications.
From simple transformer protection, or sectionalising with remote
control, to multi-panel metered consumer switchboards,the Ringmaster range from Schneider Electric offers a solution.
Quality engineering for extreme climates enables Ringmaster
to provide flexibility for any location.
Covering a wide range of options with an indoor and outdoor IP54
design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster
has proved successful in markets around the world.
Product advantages
Simple, clear operation combined with compact size,
high functionality and reliability extends the applicationsof the Ringmaster range.
Safety to personnel
Fully certified internal arc design.
Indoor/outdoor design
No need for expensive switchrooms.
Self powered protection
Not reliant on costly battery chargers.
Compact
Reduced dimensions, gives reduced civil costs.
Virtually maintenance free
Low lifetime costs.
Modular design
Quick, simple & easy to install.
Proven design
Assured consistent quality.
ISO 9001 quality certification.
Environmental
Manufactured to ISO 14001 environmental standards.PE40438
-
7/21/2019 Catalogue Ringmaster Part1
5/703AMTED399086EN.indd
Ringmaster range
PresentationSwitchgear description
PE57061
A variety of different panel types are available for each unit within
the range, together with a number of optional accessories enabling
Ringmaster to satisfy the most complex system specification.
A multitude of configurations
Free standing,
non-extensible,
cable connected
ring main unit.
Transformer mounted,
non-extensible ring main unit,
incorporated in a packaged
substation.
Free standing,
extensible cable
connected ring main unit
Transformer mounted,
extensible ring main unit,
incorporated in a packaged
substation.
Free standing,
non-extensible
circuit breaker.
Cable connected
extensible switchboard.
PE57064
PE57062
PE57065
PE57063
PE57066
-
7/21/2019 Catalogue Ringmaster Part1
6/704 AMTED399086EN.indd
Ringmaster range
PresentationSwitchgear description
General characteristics
b Gas pressure indicator as standard
bAnti-reflex operating handle with facilities
for electrical operation
bInterlocked MV cable test access (no need to remove
cable terminations or use loose earthing devices)
bIntegral self-powered protection with TFL,
adjustable curve & relay options
bIP54 enclosure
bSimple to follow mimic providing user-friendly operation
bEarth screened cast-resin gas module
bRange of dry type metering units
bMechanical tripped on-fault indication
bResin encapsulated busbars in air bus chamber
for extensible version
bDirect coupling to transformers or cable connection.
Standard and quality assurance
Manufactured to BS EN ISO 9001.
Ringmaster meets the following standards and has obtained
approval from the UK Electricity Association: IEC 56, IEC 60265,
IEC 62271-200, BS EN 60265 and EATS 41-26.
PE57067
-
7/21/2019 Catalogue Ringmaster Part1
7/705AMTED399086EN.indd
Ringmaster range
PresentationVIP protection relaysSelf-powered reliability
PE57160
VIP 300
Pick-up current ranges: RN2c, RE2c, CN2, CE2Overcurrent: 20A-200A.Earth fault: 2A-160A.CE6 and RN6c Overcurrent: 80A-800A.Earth fault: 8A to 640A.Hardened electronics Certified EMC performance to IEC60255 and EN 50061, EN50082.
Separate overcurrent and earth fault trip indication.
Flashing LEDs indicate when the relay is operating underfault conditions.
b
b
b
PE57159
VIP 35
provides protection against phase-to-phase faultsand earth faults.
PE56826
VAP 6
VIP 300 - the leading protection relay providing a wide range of
selectivity and quality of supplyThe VIP 300 is a three phase overcurrent and earth fault protection device, providing
protection for networks and equipment. Being an integral part of the highly successful
Ringmaster range, its main function is to detect phase and earth faults within the
network and to trip the circuit breaker.
Flexibility
The relay provides for a wide range of protection settings for most applications.
The IDMT characteristics employed for both the overcurrent and earth fault elements
can be easily adjusted to provide discrimination with upstream MV and downstream
LV protective devices. Fast power-up of the VIP 300 also provides immediate
protection and can detect faults instructing the CB to trip in less than 40ms.
Reliability
The relay has a self monitoring device and diagnostic routine that constantly checks
the operation of the relay automatically.
Self-powered reliability
The VIP 300 protection relay is a self powered microprocessor based device which
requires no external DC power source or batteries, making it the ideal solution for
location in remote areas where auxiliary supplies are not readily available.
Ease of use
VIP 300 has improved operation and control with the relay settings being clearly
displayed on the front panel. Manual reset flags show separate tripped on fault for
either phase or earth fault conditions.
Testing
The VAP 6 hand held test unit, is available to provide a simple check of the integrity
of the relay and can also be used to perform trip tests on the circuit breaker.
The circuit breaker trip inhibit facility allows the relay to be tested without tripping
the circuit breaker. Secondary injection can be carried out using conventional testequipment.
The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power
source or batteries. They are designed for use in distribution networks providing
protection for transformers.
-
7/21/2019 Catalogue Ringmaster Part1
8/706 AMTED399086EN.indd
Ringmaster range
PresentationNetwork remote controlT200E telecontrol
Ringmaster and T200E
Control your Ringmaster from a remote position
The Schneider Electric Easergy T200E telecontrol cabinet, which
links the Ringmaster to a control centres automation system,
allows you to manage a secondary distribution network from
a remote point. Network faults can be identified and isolated
and the network reconfigured in seconds without manual
intervention, which substantially improves the quality of supply.
The small and compact Easergy T200E can be easily mounted
directly onto the Ringmaster, saving installation costs and valuable
floor space.
Telecontrol equipment can be added any time after installation.
This makes Ringmaster RMUs even more cost-effective to install,
since a control system can be bought separately if needed at a later
date. Other RTUs can also be integrated if required.
PE57069
PE57071
Internal viewof Easergy T200E
Ringmaster C with Easergy T200E
-
7/21/2019 Catalogue Ringmaster Part1
9/707AMTED399086EN.indd
Ringmaster range
PresentationNetwork remote controlEasergy L500
Continuity of service guaranteed by an overalltelecontrol offer
Schneider Electric offers you a complete solution, including:the Easergy T200 E telecontrol interface,
MT switchgear that is adapted for telecontrol.
b
b
PE56312
L500 network monitoring screen
DE40901EN
PE57073EN
RN2C RN2C RN2C
RN2CRN2C RN2C
Network control centre
HV/MV
Communication network
MV ring
Easergy L500, a low cost solution
to immediately improve your SAIDI ** SAIDI: system average interruption duration index
Easergy L500 is a SCADA providing all the functions needed to operate
the MV network in real time
Pre-configured with Easergy range products:
MV/LV substations equipped with T200 E or Flair 200C
overhead line equipped with Flite 116/G200
Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.
Advantages
Simple implementation:
one to two weeks only for 20 MV/LV substations
configuration, training and handling within a few daysShort return on investment
Simple and fast evolutions by operations managers
Service quality and operations rapidly improved.
b
v
v
b
b
v
v
b
b
b
-
7/21/2019 Catalogue Ringmaster Part1
10/708 AMTED399086EN.indd
Key to product references
Ringmaster is available as standard panel types, allowing easy
selection and specification. The product references are made up as
follows:
R Ring main unit 2 200 A
C Circuit breaker 6 600 A
S Switch 16 16 kA
N Non-Extensible 21 21 kA
E Extensible
MU Metering unit
Example: CN2-T1/16 = circuit breaker, non extensible, 200 A, 16 kA fault rating.
The Ringmaster catalogue allows easy selection and specification,
based on a broad range of worldwide applications.
Included in this publication is:
bpanel type specifications
bdetails of optional accessories
bschematic diagrams
bInstallation drawings.
Accessories
Accessories for the Ringmaster range are supplied either fitted or
loose, where stated enabling simple panel configuration on site.
Details of accessories are contained within the panel type pages.
General arrangement drawings
General arrangement drawings are given for each panel type.This allows you to quickly size up switchrooms and calculate
external connections at the pre-order stage.
Need more information?
If your requirements are not listed, please contact your local
Schneider Electric representative, or contact us on:
Tel: +44(0) 113 290 3500
Email: [email protected]
Electronic catalogue requests
Electronic copies of this selection guide are available free of charge
upon request. For this, and other MV literature, please email your
full contact details to Email:
RN2c RE2c RN6c MU2 CN2 SN6 CE2 CE6 SE6
200 Anon extensiblering main unit
200 Aextensiblering main unit
630 Anon extensiblering main unit
200 Afeedermetering unit
200 Anon extensiblecircuit breaker
630 Anon extensibleswitch
200 Aextensiblecircuit breaker
630 Aextensiblecircuit breaker
630 Aextensibleswitch
PE57072
Ringmaster range
PresentationRingmaster selection guide
-
7/21/2019 Catalogue Ringmaster Part1
11/709AMTED399086EN.indd
Ringmaster range
Section 1Contents
Ring main units
Non-extensible ring main unit 200A
RN2c-T1, RN2c-T2, RN2c-T3, RN2c-T4, RN2c-T5 10 -17Non-extensible ring main unit 630A
RN6c-T1 18
Extensible ring main unit 200A
RE2c-T1, RE2c-T2, RE2c-T3, RE2c-T4 19 - 25
Circuit breaker, metering and switches
Non-extensible circuit breaker - 200A
CN2-T1, CN2-T6 26 - 29
Non-extensible Switch 630A
SN6-S1, SN6-S2 30 - 33
Non-extensible metering unit - 200A
MU2-M1, MU2-M2, MU2-M3 34 - 38
Extensible circuit breaker - 200A
CE2-T2, CE2-T7, CE2-T*, CE2-T12, CE2-T**,
CE2-T13, CE2-T15, CE2-T16 39 - 49
Extensible circuit breaker - 630A
CE6-T4, CE6-T*, CE6-T8, CE6-T** 50 - 55
Extensible switch - 630A
SE6-S1, SE6-S2, SE6-E1 56 - 60
Extensible bus section - 630A
SE6-B1, CE6-B3, CE6-B5 61 - 65
Remote controlTelecontrol unit
Easergy T200-E01M, Easergy T200-E04M 66 - 68
-
7/21/2019 Catalogue Ringmaster Part1
12/7010 AMTED399086EN.indd
Ringmaster range
Section 1Ring main units non-extensibleSpecification
RN2c-T1
TFL
RN2c-T2
VIP 300
RN2c-T3
VIP 30
RN2c-T4
VIP 35
RN2c-T5
Glass TFL
RN6c-T1
VIP 300
Environment
Indoor / outdoor b b b b b b
IP54 b b b b b b
Transformer mounted b b b b b
Freestanding O O O O O b
Ratings
Busbars 630A b b b b b b
Circuit breaker normal rated current 200A b b b b b
Circuit breaker normal rated current 630A b
Switch normal rated current 630A b b b b b b
12kV 16kA 3 seconds 75kV BIL b b b b b b
13.8kV 21kA 3 seconds 95kV BIL O O O O O O
Ring switch cable earth switch 16kA 3 seconds b b b b b b
Ring switch cable earth switch 21kA 3 seconds O O O O O O
Circuit breaker earth switch 3.15kA b b b b b b
MechanismIndependent manual b b b b b b
Provision for motorised mechanism LH ring switch b b b b b b
Provision for motorised mechanism RH ring switch b b b b b b
Provision for motorised mechanism circuit breaker O O O O O O
Protection & control - circuit breaker
CTs dual ratio - 100/50/5A class X b b
CTs ratio - 200/1A class X b
CTs ratio - 500/200/1A class X b b
CTs ratio - 800/400/1A class X b
Overcurrent & earth fault CT operated trip coils - TFL b
Overcurrent & earth fault CT operated trip coils - glass TFL b
Overcurrent relay - VIP 30 b
Overcurrent & earth fault relay - VIP 35 b
IDMT overcurrent & earth fault relay - VIP 300 b b
Multi voltage shunt trip coil (see accessories page 11) O O O O O O
Indication
Mechanical ON/OFF b b b b b b
Mechanical EARTH/MAIN b b b b b b
Neon indication 3.3 - 13.8kV O O O O O O
Gas pressure indicator (-25C to +55C) b b b b b b
RSW aux contacts 1NO & 1NC O O O O O O
Test facility
Integral ring cable test facility b b b b b b
Integral circuit breaker test facility O O O O O b
Standard features
Operating handle b b b b b b
Cable (see available cable kit accessories)
Bottom entry up 1 x 3C 300mm2 b b b b b b
Bottom entry up 3 x 1C 630mm2 b b b b b b
Top entry cables (indoor only) O O O O O O
Order codes
12kV, 16kA, 75kV BIL, 0.35bG RN2c-T1/16 RN2c-T2/16 RN2c-T3/16 RN2c-T4/16 RN2c-T5/16 RN6c-T1/16
13.8kV, 21kA, 95kV BIL, 0.8bG RN2c-T1/21 RN2c-T2/21 RN2c-T3/21 RN2c-T4/21 RN2c-T5/21 RN6c-T1/21
General arrangement drawing - transformer mounted RMINST-06Page 77
RMINST-06Page 77
RMINST-06Page 77
RMINST-06Page 77
RMINST-06Page 77
RMINST-06Page 77
General arrangement drawing - freestanding RMINST-05Page 116
RMINST-05Page 116
RMINST-05Page 116
RMINST-05Page 116
RMINST-05Page 116
RMINST-05Page 116
Schematic diagram - TFL RMSCH-01Page 85
RMSCH-01Page 85
Schematic diagram - VIP 30 RMSCH-02Page 87
Schematic diagram - VIP 35 RMSCH-15Page 88
Schematic diagram - VIP 300 RMSCH-03Page 86
RMSCH-42Page 89
Key: bStandard feature OOptional feature
-
7/21/2019 Catalogue Ringmaster Part1
13/7011AMTED399086EN.indd
Ringmaster range
Section 1Ring main units non-extensibleAccessories
RN2c-T1
TFL
RN2c-T2
VIP 300
RN2c-T3
VIP 30
RN2c-T4
VIP 35
RN2c-T5
Glass TFL
RN6c-T1
VIP 300
Kit no.
Cable kits
Circuit breaker cable box v v v v v RMR-A/F47
Circuit breaker cable box with integral cable test facility v v v v v b RMR-F325
Gland plate 1 x 3C O O O O O O RMR-A316
Gland plate 3 x 1C O O O O O O RMR-A319
Small gland plate 1 x 3c O O O O O O RMR-A322
Blank aluminium gland plate O O O O O O RMR-A320
Brass wiping gland 1 x 3C O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O RMR-A11
Small brass wiping gland 1 x 3c O O O O O O RMR-A105
Tubular gland 1 x 3C O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O RMR-A13
Small tubular gland O O O O O O RMR-A106
CES5 gland O O O O O O RMR-A120
CES5 gland plate 1 x 3C O O O O O O RMR-A321
CES5 gland adaptor O O O O O O RMR-A525
6 x ECON cable termination kit O O O O O O RMR-A314
3 x STD ECON end cap O O O O O O RMR-A370
3 x ECON cable termination kit O O O O O O RMR-A315
Top entry cables RH cable box (indoor only) v v v v v v RMR-F303
Top entry cables LH cable box (indoor only) v v v v v v RMR-F302
Rsw extension box for 2 x 3C cables (left hand) v v v v v v RMR-F523
Rsw extension box for 2 x 3C (right hand) v v v v v v RMR-F522
Angled gland plate 1 x 3C O O O O O O RMR-A317
Split gland plate 1 x 3C O O O O O O RMR-A318
Installation items
Transformer mounting kit v v v v v v RMR-A/F323
Extension trunking (to clear transformer radiators) O O O O O O RMR-A20
Set of padlocks - 11 no O O O O O O RMR-A343
Anti-vandal fixings, including tool O O O O O O RMR-A344
Foundation bolts (not required for transformer mounting) O O O O O O RMR-A22Multicore pilot glands O O O O O O RMR-A342
Time limit fuses (set of 2 - specify rating as table page 115) O O O O O O RMR-A17
RN2c to MU2 installation kit v v v v v v RMR-A350
Ariel mounting bracket O O O O O O RMR-A201
Operational items
Operating handle b b b b b b RMR-F345
LH ring switch control auxiliary sw for motorisedmechanism provision
v v v v v v RMR-F328
LH ring switch termination block for motorisedmechanism provision (not Easergy)
v v v v v v RMR-F363
RH ring switch control auxiliary sw for motorisedmechanism provision
v v v v v v RMR-F329
RH ring switch termination block for motorisedmechanism provision (not Easergy)
v v v v v v RMR-F364
Provision for motorised mechanism circuit breaker v v v v v b RMR-F543
Motorised mechanism - specify voltage v v v v v v RMR-F507
CB Termination block for motorisedmechanism provision (not Easergy)
v v v v v v RMR-F365
Shunt trip coil (20-250V DC, 110-250V AC) TLF v v v v v v RMR-F581
Shunt trip coil (20-250V DC, 110-250V AC) VIP v v v v v v RMR-F582
Ring switch cable neon indication (11-13.8kV) v v v v v v RMR-F341
Ring switch cable neon indication (3.3-7.2kV) v v v v v v RMR-F348
Circuit breaker cable neon indication (11-13.8kV) v v v v v v RMR-F340
Circuit breaker cable neon indication (3.3-7.2kV) v v v v v v RMR-F347
Phase indication device O O O O O O RMR-A374
VAP 6 test unit for VIP 300/30/35 O O O O O O RMR-A202
Emergency trip push button v v v v v v RMR-F339
Gas pressure switch for remote indication only v v v v v v RMR-F368
Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
14/7012 AMTED399086EN.indd
Ringmaster range
Section 1Ring main units non-extensibleAccessories
RN2c-T1
TFL
RN2c-T2
VIP 300
RN2c-T3
VIP 30
RN2c-T4
VIP 35
RN2c-T5
Glass TFL
RN6c-T1
VIP 300
Kit no.
Mechanical interlocks
Circuit breaker - key free, EARTH ON v v v v v v RMR-F337
Circuit breaker - key free, MAIN OFF v v v v v v RMR-F338
Switch - key free, SWITCH OFF LH v v v v v v RMR-F335
Switch - key free, SWITCH OFF RH v v v v v v RMR-F336
N. B. specify lock symbol at time of ordering ( 3 digits max) notavailable with motor mechanisms
Earth fault passage indication (choose provision kit
and an EFPI required if not using Easergy T200E)
Phase & earth fault provision for Easergy T200E O O O O O O RMR-F310
EFPI provision kit, inside cable box O O O O O O RMR-A304
EFPI provision kit, CT outside cable box O O O O O O RMR-A305
EFPI provision kit, inside cable box, top entry O O O O O O RMR-A308
EFPI provision kit, outside cable box, top entry O O O O O O RMR-A309
Bowden RR EFPI and CT O O O O O O RMR-A422
Bowden STD EFPI type NB O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O RMR-A278
Bowden LV reset & alarm type NB2 O O O O O O RMR-A279
Fundamentals ER FIND EFPI and CT O O O O O O RMR-A57
N. B. above CTs are ring type for split core - please consultSchneider Electric
Key: v Factory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
15/7013AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible ring main unit200 ARN2c-T1
Transformer protection up to 1.6MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200ANormal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicatorCB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kitFreestanding tee-off cable box
Order information
Code Rating
RN2c-T1/16 16kA, 12kV, 75kV BIL
RN2c-T1/21 21kA, 13.8kV, 95kV BIL
DE60180
DE60181
-
7/21/2019 Catalogue Ringmaster Part1
16/7014 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible ring main unit200 ARN2c-T2
Transformer protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1A class X
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
RatingsBusbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V ACNeon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T2/16 16kA, 12kV, 75kV BIL
RN2c-T2/21 21kA, 13.8kV, 95kV BIL
b
v
v
DE60180
DE60185
-
7/21/2019 Catalogue Ringmaster Part1
17/7015AMTED399086EN.indd
MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1A class X
Setting range: 500/1A
Overcurrent: 20-200A
Setting range: 200/1A
Overcurrent: 8-80A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-02
Environment
Indoor/outdoor
IP54
RatingsBusbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V ACNeon indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T3/16 16kA, 12kV, 75kV BIL
RN2c-T3/21 21kA, 13.8kV, 95kV BIL
b
v
b
v
Ringmaster range
Section 1Non-extensible ring main unit200 ARN2c-T3
DE60180
DE60182
-
7/21/2019 Catalogue Ringmaster Part1
18/7016 AMTED399086EN.indd
MV transformer protection
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1A class X
CH30 core balance CT
Setting range: 500/1A
Overcurrent: 20-200A
Earth fault: 25-300A
Setting range: 200/1A
Overcurrent: 8-80A
Earth fault: 10-120A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-15
EnvironmentIndoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2c-T4/16 16kA, 12kV, 75kV BIL
RN2c-T4/21 21kA, 13.8kV, 95kV BIL
b
v
v
b
v
v
Ringmaster range
Section 1Non-extensible ring main unit200 ARN2c-T4
DE60180
DE60183
-
7/21/2019 Catalogue Ringmaster Part1
19/7017AMTED399086EN.indd
Transformer protection up to 1.6MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links (glass fuse link)
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200ANormal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicatorCB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kitFreestanding tee off cable box
Order information
Code Rating
RN2c-T5/16 16kA, 12kV, 75kV BIL
RN2c-T5/21 21kA, 13.8kV, 95kV BIL
Ringmaster range
Section 1Non-extensible ring main unit200 ARN2c-T5
DE60180
DE60184
-
7/21/2019 Catalogue Ringmaster Part1
20/7018 AMTED399086EN.indd
Network sectionalising up to 12MVA 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 800/400/1A class X
Setting range: 800/1A ratio
Overcurrent: 80-800A
Earth fault: 8-640A
Setting range: 400/1A
Overcurrent: 40-400A
Earth fault: 4-320A
Documents
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-42
Environment
Indoor/outdoor
IP54
RatingsBusbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Circuit breaker earth switch 16/21kA
Ring cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug
interface
Indication
Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch and circuit breaker test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Freestanding
Order information
Code Rating
RN6c-T1/16 16kA, 12kV, 75kV BIL
RN6c-T1/21 21kA, 13.8kV, 95kV BIL
b
v
v
b
v
v
Ringmaster range
Section 1Non-extensible ring main unit200 ARN6c-T1
DE60180
DE60186
-
7/21/2019 Catalogue Ringmaster Part1
21/7019AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unitsSpecification
RE2c-T1
TFL
RE2c-T2
VIP 300
RE2c-T3
VIP 30
RE2c-T4
VIP 35
Environment
Indoor / outdoor b b b b
IP54 b b b b
Transformer mounted b b b b
Freestanding b b b b
Extensible (RHS) O O O O
Ratings
Busbars 630A b b b b
Circuit breaker normal rated current 200A b b b b
Circuit breaker normal rated current 630A
Switch normal rated current 630A b b b b
12kV 16kA 3 seconds 75kV BIL b b b b
13.8kV 21kA 3 seconds 95kV BIL O O O O
Ring switch cable earth switch 16kA 3 seconds b b b b
Ring switch cable earth switch 21kA 3 seconds O O O O
Circuit breaker earth switch 3.15kA b b b b
Extensible rmu busbar chamber 630A O O O O
Mechanism
Independent manual b b b b
Provision for motorised mechanism LH ring switch b b b b
Provision for motorised mechanism RH ring switch b b b b
Provision for motorised mechanism circuit breaker O O O O
Protection & control - circuit breaker
CTs dual ratio - 100/50/5A class X b
CTs ratio - 200/1A class X b
CTs ratio - 500/200/1A class X b b
CTs ratio - 800/400/1A class X
Overcurrent & earth fault CT operated trip coils - TFL b
Overcurrent & earth fault CT operated trip coils - glass TFL
Overcurrent relay - VIP 30 b
Overcurrent & earth fault relay - VIP 35 bIDMT overcurrent & earth fault relay - VIP 300 b
Multi voltage shunt trip coil (see accessories) O O O O
Indication
Mechanical ON/OFF b b b b
Mechanical EARTH/MAIN b b b b
Neon indication 3.3 - 13.8kV O O O O
Gas pressure indicator (-25C to +55C) b b b b
RSW aux contacts 1NO & 1NC O O O O
Test facility
Integral ring cable test facility b b b b
Standard features
Operating handle b b b b
Cable (see available cable kit accessories)
Bottom entry up 1 x 3C 300mm2 b b b b
Bottom entry up 3 x 1C 630mm2 b b b b
Top entry cables* (indoor only) (left hand side only) O O O O
Order codes
12kV, 16kA, 75kV BIL, 0.35bG RE2c-T1/16 RE2c-T2/16 RE2c-T3/16 RE2c-T4/16
13.8kV, 21kA, 95kV BIL, 0.8bG RE2c-T1/21 RE2c-T2/21 RE2c-T3/21 RE2c-T4/21
General arrangement drawing - freestanding RMINST-22, Page 75 RMINST-22, Page 75 RMINST-22, Page 75 RMINST-22, Page 75
Schematic diagram - TFL RMSCH-01, Page 85
Schematic diagram - VIP 30 RMSCH-02, Page 87
Schematic diagram - VIP 35 RMSCH-15, Page 88
Schematic diagram - VIP 300 RMSCH-03, Page 86
Key: bStandard feature OOptional feature
-
7/21/2019 Catalogue Ringmaster Part1
22/7020 AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unitsAccessories
RE2c-T1
TFL
RE2c-T2
VIP 300
RE2c-T3
VIP 30
RE2c-T4
VIP 35
Kit no.
Cable kits
Extensible ring main units v v v v RMR-A/F47
Gland plate 1 x 3C O O O O RMR-A316
Gland plate 3 x 1C O O O O RMR-A319
Small gland plate 1 x 3C O O O O RMR-A322
Blank aluminium gland plate O O O O RMR-A320
Brass wiping gland 1 x 3C O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O RMR-A10
Small brass wiping gland 1 x 3C O O O O RMR-A105
Tubular gland 1 x 3C O O O O RMR-A12
Tubular gland 3 x 1C O O O O RMR-A13
Small tubular gland 1 x 3C O O O O RMR-A106
CES5 gland O O O O RMR-A120
CES5 gland plate 1 x 3C O O O O RMR-A321
CES5 gland plate adaptor O O O O RMR-A525
6 x ECON cable termination kit O O O O RMR-A314
3 x STD ECON end cap O O O O RMR-A370
3 x ECON cable termination kit O O O O RMR-A315
3 x ECON end cap capacitors O O O O RMR-A371
Top entry cables LH cable box (indoor only) v v v v RMR-F302
Angled gland plate 1 x 3C O O O O RMR-A317
Split gland plate 1 x 3C O O O O RMR-A318
Installation items
Transformer mounting kit v v v v RMR-A/F323
Extension trunking (to clear radiators) O O O O RMR-A20
Set of padlocks - 11 no O O O O RMR-A343
Anti-vandal fixings, including tool O O O O RMR-A344
Foundation bolts (not required for transformer mounting) O O O O RMR-A22
Multicore pilot glands O O O O RMR-A342
Time limit fuses (set of 2 - specify rating as table page 115) O O O O RMR-A17
RE2c to MU2 installation kit v v v v RMR-A350Extensible busbar chamber 630A O O O O RMR-F369
Ariel mounting bracket O O O O RMR-A201
Operational items
Operating handle b b b b RMR-F345
LH ring switch control auxiliary sw for motorised mechanismprovision
v v v v RMR-F328
LH ring switch termination block for motorised mechanismprovision (not Easergy)
v v v v RMR-F363
RH ring switch control auxiliary sw for motorised mechanismprovision
v v v v RMR-F329
RH ring switch termination block for motorised mechanismprovision (not Easergy)
v v v v RMR-F364
Provision for motorised mechanism circuit breaker v v v v RMR-F543
Motorised mechanism - specify voltage v v v v RMR-F507
Shunt trip coil (20-250V DC, 110-250V AC) TLF v v v v RMR-F581
Shunt trip coil (20-250V DC, 110-250V AC) VIP v v v v RMR-F582
Ring switch cable neon indication (11-13.8kV) v v v v RMR-F341
Ring switch cable neon indication (3.3-7.2kV) v v v v RMR-F348
Circuit breaker neon indication (11-13.8kV) v v v v RMR-F340
Circuit breaker neon indication (3.3-7.2kV) v v v v RMR-F347
VAP 6 test unit for VIP 300/30/35 v v v v RMR-A202
Emergency trip push button v v v v RMR-F339
Gas pressure switch for remote indication only v v v v RMR-F368
Key: bStandard feature vFactory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
23/7021AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unitsAccessories
RE2c-T1
TFL
RE2c-T2
VIP 300
RE2c-T3
VIP 30
RE2c-T4
VIP 35
Kit no.
Mechanical interlocks
Circuit breaker - key free, earth on v v v v RMR-F337
Circuit breaker - key free, main off v v v v RMR-F338
Switch - key free, switch off LH v v v v RMR-F335
Switch - key free, switch off RH v v v v RMR-F336
N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms
Earth fault passage indication (choose provision kit
and an EFPI required if not using Easergy T200E)
Phase & earth fault provision for Easergy T200E O O O O RMR-F310
EFPI provision kit, inside cable box O O O O RMR-A304
EFPI provision kit, CT outside cable box O O O O RMR-A305
EFPI provision kit, inside cable box, top entry O O O O RMR-A308
EFPI provision kit, outside cable box, top entry O O O O RMR-A309
Bowden RR EFPI and CT O O O O RMR-A422
Bowden STD EFPI type NB O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O RMR-A278
Bowden LV reset & alarm type NB O O O O RMR-A279
Fundamentals ER FIND EFPI and CT O O O O RMR-A57
N. B. above CTs are ring type for split core - please consultSchneider Electric
Key: v Factory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
24/7022 AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unit 200 ARE2c-T1
Multiple transformer feeders or network switching points
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Freestanding installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kVNormal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicatorCB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Integral circuit breaker test facility
Inverted cable boxes LH, CB (indoor only)Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T1/16 16kA, 12kV, 75kV BIL
RE2c-T1/21 21kA, 13.8kV, 95kV BIL
DE60211
DE60187
-
7/21/2019 Catalogue Ringmaster Part1
25/7023AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unit 200 ARE2c-T2
Multiple transformer feeders or network switching points
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS 142.
Protection CTs - 200/1A class X
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630AShort time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20V DC - 250V ACNeon indication
Inverted cable box LH CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T2/16 16kA, 12kV, 75kV BIL
RE2c-T2/21 21kA, 13.8kV, 95kV BIL
b
v
v
DE60211
DE60188
-
7/21/2019 Catalogue Ringmaster Part1
26/7024 AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unit 200 ARE2c-T3
MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1A class X
Setting range: 500/1A
Overcurrent: 20-200A
Setting range: 200/1A
Overcurrent: 8-80A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-02
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630AShort time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20V DC - 250V ACNeon indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T3/16 16kA, 12kV, 75kV BIL
RE2c-T3/21 21kA, 13.8kV, 95kV BIL
b
v
b
v
DE60211
DE60189
-
7/21/2019 Catalogue Ringmaster Part1
27/7025AMTED399086EN.indd
Ringmaster range
Section 1Extensible ring main unit 200 ARE2c-T4
MV transformer protection
Protection & control - CB
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1A class with CH30 core balance CT
Setting range: 500/1A
Overcurrent: 20-200A
Earth fault 25-300A
Setting range: 200/1A
Overcurrent: 8-80A
Earth fault 10-120A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-15
Environment
Indoor/outdoorIP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
Earth position selected 1NO
Earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table page 20CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil
Neon indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting
Freestanding tee-off cable box
Order information
Code Rating
RE2c-T4/16 16kA, 12kV, 75kV BIL
RE2c-T4/21 21kA, 13.8kV, 95kV BIL
b
v
v
b
v
v
DE60211
DE60190
-
7/21/2019 Catalogue Ringmaster Part1
28/7026 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible circuit breakers200 ASpecification
CN2-T1 CN2-T6
Environment
Indoor / outdoor b b
IP54 b b
Ratings
Normal rated current 200A b b
12kV 16kA 3 seconds 75kV BIL b b
13.8kV 21kA 3 seconds 95kV BIL O O
Cable earth switch 16kA 3 seconds b b
Cable earth switch 21kA 3 seconds O O
Transformer earth switch 3.15kA 3 seconds b b
Mechanism
Independent manual b b
Protection & control - circuit breaker
CTs dual ratio - 100/50/5A class X b
CTs ratio - 200/1A class X b
Overcurrent & earth fault CT operated trip coils b
Time fuse Link O
IDMT overcurrent & earth fault relay - VIP 300 b
20V-250shunt trip coil b b
Circuit breaker auxiliary switch 1NO 2NC b b
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
Neon indication (6.6 - 13.8kV) O O
Auxiliary switch contacts 1NO 2NC b b
Gas pressure indicator b b
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300mm21 x 3c b b
Bottom entry up 630mm23 x 1c b b
Key: bStandard feature OOptional feature
-
7/21/2019 Catalogue Ringmaster Part1
29/7027AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible circuit breakers200 AAccessories
CN2-T1 CN2-T6 Kit no.
Cable kits
Tee-off cable box v v
RMR-F47Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50 Blank
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Time limit fuses (set of 2 - specify rating as table page 115) O RMR-A17Operational items
Operating handle b b RMR-A23
Neon indication (6.6-13.8kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
VAP 6 test unit for VIP 300 O RMR-A202
Mechanical interlocks
Key free, earth on v v RMR-F85
Key free, unit off v v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms
Order codes
12kV, 16kA, 75kV BIL, 0.35bG CN2-T1/16 CN2-T6/16
13.8kV, 21kA, 95kV BIL, 0.8bG CN2-T1/21 CN2-T6/21
General arrangement drawing - transformer mounted RMINST-04 Page 76 RMINST-04 Page 76
General arrangement drawing - freestanding RMINST-09 Page 117 RMINST-09 Page 117
Schematic diagram RMSCH-26 Page 106 RMSCH-11 Page 96
Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
30/7028 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible circuit breaker200 ACN2-T1
Transformer protection up to 3.5MVA
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1A class X
Setting range:
Overcurrent: 20-200A
Earth fault: 2A-160A
Shunt trip coil, 20V DC-250V AC
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-26
Environment
Indoor/outdoor
IP54Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Tee-off earth switch, 3.15kA 3s
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicatorMechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 27 for details
Order information
Code Rating
CN2-T1/16 16kA, 12kV, 75kV BIL
CN2-T1/21 21kA, 13.8kV, 95kV BIL
b
v
v
DE60250
-
7/21/2019 Catalogue Ringmaster Part1
31/7029AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible circuit breaker200 ACN2-T6
Transformer protection up to 1.5MVA
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-11
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3sNormal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicatorCB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 27 for details
Order information
Code Rating
CN2-T6/16 16kA, 12kV, 75kV BILCN2-T6/21 21kA, 13.8kV, 95kV BIL
DE60192
-
7/21/2019 Catalogue Ringmaster Part1
32/7030 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible switch 630 ASpecification
SN6-S1 SN6-S2
Environment
Indoor / outdoor b b
IP54 b b
Ratings
Normal rated current 630A b b
13.8kV 21kA 3 seconds 95kV BIL b b
Cable earth switch 21kA 3 seconds b b
Transformer earth switch 3.15kA 3 seconds b b
Mechanism
Independent manual b b
Provision for actuator 24V DC b
Actuator 24V DC O
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
Neon indication (6.6 - 13.8kV) O O
Auxiliary switch contacts 1NO 2NC b
Phase and earth fault detection CTs for Easergy 200E O
Provision for EFPI O O
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300mm21 x 3c b b
Bottom entry up 630mm23 x 1c b b
Key: bStandard feature OOptional feature
-
7/21/2019 Catalogue Ringmaster Part1
33/7031AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible switch 630 AAccessories
SN6-S1 SN6-S2 Kit no.
Cable kits
Tee-off cable box v v
RMR-F47Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Operational itemsOperating handle b b RMR-A23
Neon indication (6.6-13.8kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
Actuator 24V DC v RMR-F67
Mechanical interlocks
Key free, earth on v RMR-F85
Key free, unit off v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits max) notavailable with motor mechanisms
Order codes
13.8kV, 21kA, 95kVBIL, 0.8bG SN6-S1/21 SN6-S2/21
General arrangement drawing - transformer mounted RMINST-04 Page 76 RMINST-04 Page 76
General arrangement drawing - freestanding RMINST-09 Page 117 RMINST-09 Page 117
Schematic diagram N/A RMSCH-28 Page 107
Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site
-
7/21/2019 Catalogue Ringmaster Part1
34/7032 AMTED399086EN.indd
Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
AccessoriesTee-off cable box
Neon indication
Glands and plates
Interlocks
See page 31 for details
Order information
Code Rating
SN6-S1/21 21kA, 13.8kV, 95kV BIL
Ringmaster range
Section 1Non-extensible switch 630 ASN6-S1
DE60193
-
7/21/2019 Catalogue Ringmaster Part1
35/7033AMTED399086EN.indd
Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-28
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manualProvision for actuator, 24V DC
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Auxiliary contacts 1NO 2NC
Earth selected auxiliary contact 1NO
Test facility
Integral cable test facilities
CableBottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Tee-off cable box
Actuator, 24V DC
Neon indication
Glands and plates
See page 31 for details
Order information
Code Rating
SN6-S2/21 21kA, 13.8kV, 95kV BIL
Ringmaster range
Section 1Non-extensible switch 630 ASN6-S2
DE60194
-
7/21/2019 Catalogue Ringmaster Part1
36/7034 AMTED399086EN.indd
MU2-M1 MU2-M2 MU2-M3
Environment
Indoor / outdoor b b b
IP54 b b b
Ratings
Normal rated current 200A b b b
12kV 16kA 1 second 75kV BIL b b b
Metering*
CTs -50/25/5A 0.5s 7.5VA b
CTs -100/50/5A 0.5s 10VA b
CTs -200/100/5A 0.5s 10VA b
VTs -11kV/110V 0.5 50VA b b b
*CTs - 2 phases (R & B), VTs phase to phase. 6.6kV VTs areavailable - contact Schneider Electric
Cable (see available cable kit accessories)
Bottom entry up 300mm21 x 3c O O O
Bottom entry up 630mm23 x 1c O O O
Key: bStandard feature OOptional feature
Ringmaster range
Section 1Non-extensible metering unit200 ASpecification
-
7/21/2019 Catalogue Ringmaster Part1
37/7035AMTED399086EN.indd
MU2-M1 MU2-M2 MU2-M3 Kit no.
Cable kits
Tee-off cable box v v v
RMR-F47Gland plate 1 x 3C O O O RMR-A48
Gland plate 3 x 1C O O O RMR-A49
Angled gland plates (RMU) O O O RMR-A51 Blank
Blank aluminium gland plate O O O RMR-A52
Brass wiping gland 1 x 3C O O O RMR-A10
Brass wiping gland 3 x 1C O O O RMR-A11
Tubular gland 1 x 3C O O O RMR-A12
Tubular gland 3 x 1C O O O RMR-A13
CES5 gland plate 1 x 3C O O O RMR-A132
Installation items
Set of padlocks - XX no O O O RMR-A18/6
Foundation bolts (not required for transformer mounting) O O O RMR-A22
Multicore pilot glands O O O RMR-A16
RMU - MU2 installation kit O O O RMR-A350
Freestanding installation kit O O O RMR-A90Order codes
12kV, 16kA, 75kV BIL, 0.35bG MU2-M1/16 MU2-M2/16 MU2-M3/16
General arrangement drawing - t ransformer mounted RMINST-07/08Page 78 - 79
RMINST-07/08Page 78 - 79
RMINST-07/08Page 78 - 79
Schematic diagram RMSCH-14 Page 97 RMSCH-14 Page 97 RMSCH-14 Page 97
Key: v Factory fitted accessory OLoose accessory, assembled on site
Ringmaster range
Section 1Non-extensible metering unit200 AAccessories
-
7/21/2019 Catalogue Ringmaster Part1
38/7036 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible metering unit200 AMU2-M1
Non-extensible metering unit
Protection & control - CB
N/A
Metering transformers
Metering CTs R & B phases
50/25/5A
7.5VA class 0.5s
Metering VT ph - ph
11kV/110V 50VA
class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1sNormal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for detailsOrder information
Code Rating
MU2-M1/16 16kA, 12kV, 75kV BIL
b
v
v
b
v
v
DE60210
-
7/21/2019 Catalogue Ringmaster Part1
39/7037AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible metering unit200 AMU2-M2
Non-extensible metering unit
Protection & control - CB
N/A
Metering transformers
Metering CTs R & B phases
100/50/5A
10VA class 0.5s
Metering VT ph - ph
11kV/110V 50VA
class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1sNormal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for details
Order information
Code Rating
MU2-M2/16 16kA, 12kV, 75kV BIL
b
v
v
b
v
v
DE60210
-
7/21/2019 Catalogue Ringmaster Part1
40/7038 AMTED399086EN.indd
Ringmaster range
Section 1Non-extensible metering unit200 AMU2-M3
Non-extensible metering unit
Protection & control - CB
N/A
Metering transformers
Metering CTs R & B phases
200/100/5A
10VA class 0.5s
Metering VT ph - ph
11kV/110V 50VA
class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1sNormal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for detailsOrder information
Code Rating
MU2-M3/16 16kA, 12kV, 75kV BIL
b
v
v
b
v
v
DE60210
-
7/21/2019 Catalogue Ringmaster Part1
41/7039AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breakers200 ASpecification
CE2-
T2
CE2-
T3
CE2-
T7
CE2-
T11
CE2-
T12
CE2-
T13
CE2-
T14
CE2-
T15
CE2-
T16
CE2-
T19
CE2-
T20
CE2-
T21
Environment
Indoor / outdoor b b b b b b b b b b b b
IP54 b b b b b b b b b b b b
Ratings
Busbars 630A b b b b b b b b b b b b
Circuit breaker normal rated current 200A b b b b b b b b b b b b
12kV 16kA 3 seconds 75kV BIL b b b b b b b b b b b b
13.8kV 21kA 3 seconds 95kV BIL O O O O O O O O O O O O
Cable earth switch 16kA 3 seconds b b b b b b b b b b b b
Cable earth switch 21kA 3 seconds O O O O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b b b b
Provision for actuator 24V DC b b b b
Actuator 24V DC O O O O
Operating handle b b b b b b b b b b b b
Protection systemCTs dual ratio - 500/200/1A class x b b
Overcurrent relay - VIP 30 b
CTs dual ratio - 100/50/5A class X b
CT ratio - 200/1A class X b b b b b b b b b
Overcurrent & earth fault CT operated trip coils b
Overcurrent & earth fault relay VIP 35 b
Time fuse link O
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
20V-250shunt trip coil b b b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b b b
Metering
CTs -200/100/5A 0.5s 10VA b b b b b b b
VTs -13.8kV/110V 0.5 10VA 13.8/110V/110V 0.5 50VA 3P 20VA b b
VTs -11kV/110V 0.5 50VA b b b
VTs -6.6kV/110V 0.5 50VA b b
VTs phase - phase, CTs R & B b b b b
VTs phase - earth, CTs RYB b b b
Indication
Mechanical ON/OFF b b b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b b b
Cable neon indication (6.6 - 13.8kV) O O O O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b b
Test facility
Integral cable test facility b b b b b b b b b b b b
Cable
Bottom entry up to 300mm21 x 3c b b b b b b b b b b b b
Bottom entry up to 630mm23 x 1c b b b b b b b b b b b b
Top entry cables O O O O O O O O O O O O
Key: bStandard feature OOptional feature
-
7/21/2019 Catalogue Ringmaster Part1
42/7040 AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breakers200 AAccessories
CE2-
T2
CE2-
T3
CE2-
T7
CE2-
T11
CE2-
T12
CE2-
T13
CE2-
T14
CE2-
T15
CE2-
T16
CE2-
T19
CE2-
T20
CE2-
T21
Kit no.
Cable kits
Gland plate 1 x 3C O O O O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132
Top entry cables standardpanels
v v v v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630A O O O O O RMR-A14
3 phase busbars 630A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6
Foundation bolts (not requiredfor transformer mounting)
b b b b b b b b b b b b RMR-A22
Multicore pilot glands O O O O O O O O O O O O RMR-A16
Time limit fuses (set of 2 - specifyrating as table page 115)
O RMR-A17
Operational items
Operating handle b b b b b b b b b b b b RMR-A23
Cable neon indication(6.6 - 13.8kV)
v v v v v v v v v v v v RMR-F108
Neon lamp test unit(including lamp)
v v v v v v v v v v v v RMR-A24
Neon lamp O O O O O O O O O O O RMR-A81
VAP 6 test unit for VIP 300 O O O O O O O O O O O RMR-A202
Actuator 24V DC v v v RMR-F67Polarity conversion kit** v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v v RMR-F85
Key free, MAIN OFF v v v v v v RMR-F86
N. B. specify lock symbol at timeof ordering (3 digits max)not available with motormechanisms
Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site**Only required when unit is used with RE2c ring main units and automation.
-
7/21/2019 Catalogue Ringmaster Part1
43/7041AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breakers200 AAccessories
CE2-
T2
CE2-
T3
CE2-
T7
CE2-
T11
CE2-
T12
CE2-
T13
CE2-
T14
CE2-
T15
CE2-
T16
CE2-
T19
CE2-
T20
CE2-
T21
Kit no.
Earth fault passage
indication (choose
provision kit and an EFPI
required if not using
Easergy 200E)
EFPI provision kit, insidecable box
O O O O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1O O O O O O O O O O O O RMR-A278
Bowden LV reset & alarmtype NB2
O O O O O O O O O O O O RMR-A279
Bowden RR EFPI and CT O O O O O O O O O O O O RMR-A56
Fundamentals ER FINDEFPI and CT
O O O O O O O O O O O O RMR-A57
Ancillary items
Tool box O O O O O O O O O O O O RMR-A80
Order code12kV, 16kA, 75kV BIL, 0.35bG CE2-
T2/16CE2-T3/16
CE2-T7/16
CE2-T11/16
CE2-T12/16
CE2-T13/16
CE2-T14/16
CE2-T15/16
CE2-T16/16
N/A CE2-T20/16
N/A
13.8kV, 21kA, 95kV BIL, 0.8bG CE2-T2/21
CE2-T3/21
CE2-T7/21
CE2-T11/21
CE2-T12/21
CE2-T13/21
CE2-T14/21
CE2-T15/21
CE2-T16/21
CE2-T19/21
N/A CE2-T21/21
General arrangement drawing RMINST-03Page 74
RMINST-02
Page 73
RMINST-03
Page 74
RMINST-02
Page 73
RMINST-03
Page 74
RMINST-02
Page 73
RMINST-02
Page 73
RMINST-03
Page 74
RMINST-03
Page 74
RMINST-02
Page 73
RMINST-02
Page 73
RMINST-02
Page 73
Schematic drawing RMSCH-07Page 92
RMSCH-09
Page 94
RMSCH-06
Page 91
RMSCH-09
Page 94
RMSCH-19
Page 100
RMSCH-20
Page 101
RMSCH-20
Page 101
RMSCH-07
Page 92
RMSCH-07
Page 92
RMSCH-35
Page 109
RMSCH-35
Page 109
RMSCH-36
Page 110
Key: bStandard feature v Factory fitted accessory OLoose accessory, assembled on site**Only required when unit is used with RE2c ring main units and automation.
-
7/21/2019 Catalogue Ringmaster Part1
44/7042 AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T2
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-07
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3sNormal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code Rating
CE2-T2/16 16kA, 12kV, 75kV BIL
CE2-T2/21 21kA, 13.8kV, 95kV BIL
b
v
v
DE60251
-
7/21/2019 Catalogue Ringmaster Part1
45/7043AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T7
Transformer protection up to 1.5MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision
for time fuse links.
Protection CTs - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-06
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kVOperating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
CableBottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code Rating
CE2-T7/16 16kA, 12kV, 75kV BIL
CE2-T7/21 21kA, 13.8kV, 95kV BIL
DE60196
-
7/21/2019 Catalogue Ringmaster Part1
46/7044 AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T*
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Metering transformers
Metering CTs R & B phases
200/100/5A
10VA class 0.5s
Metering VT
see below
Environment
Indoor/outdoor
IP54Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Anti-reflex operating handle
Standard features
Cable earth switch, 16/21kA 3s
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicatorAuxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cablesSee page 40 for details
Order code
16kA, 12kV, 75kV BIL21kA, 13.8kV, 95kV BIL
CE2-T3/16CE2-T3/21
CE2-T11/16CE2-T11/21
N/ACE2-T19/21
CE2-T20/16N/A
Metering VT information:Phase to phase
b b
Phase to earth b b
6.6kV/110V b
11kV/110V* b b
13.8kV/110V b
General arrangement drawing RMINST-02Page 73
RMINST-02Page 73
RMINST-02Page 73
RMINST-02Page 73
Schematic diagram RMSCH-09Page 94
RMSCH-09Page 94
RMSCH-35Page 109
RMSCH-35Page 109
*Please consult Schneider Electric when ordering units with 95kV BIL voltageTel: +44(0)113 290 3500
b
v
v
b
v
v
b
v
DE60252
(Select VT rating and switchgear rating from table below).
-
7/21/2019 Catalogue Ringmaster Part1
47/7045AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T12
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-19
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3sNormal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NOGas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cablesSee page 40 for details
Order information
Code Rating
CE2-T12/16 16kA, 12kV, 75kV BIL
CE2-T12/21 21kA, 13.8kV, 95kV BIL
b
v
v
DE60253
-
7/21/2019 Catalogue Ringmaster Part1
48/7046 AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T**
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Metering transformers
Metering CTs
200/100/5A
10VA class 0.5s
Metering VT
see below
Environment
Indoor/outdoor
IP54Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicatorMechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
InterlocksOperating handle
Busbar kit
Top entry cables
See page 40 for details
Order code
16kA, 12kV, 75kV BIL21kA, 13.8kV, 95kV BIL
CE2-T14/16CE2-T14/21
N/ACE2-T21/21
Metering VT information:Phase to phase
b
Phase to earth b
6.6kV/110V b
11kV/110V*
13.8kV/110V b
General arrangement drawing RMINST-02
Page 73
RMINST-02
Page 73Schematic diagram RMSCH-20
Page 101RMSCH-36Page 110
*Please consult Schneider Electric when ordering units with 95kV BIL voltageTel: +44(0)113 290 3500
b
v
v
b
v
v
b
v
DE60254
(Select VT rating and switchgear rating from table below).
-
7/21/2019 Catalogue Ringmaster Part1
49/7047AMTED399086EN.indd
Ringmaster range
Section 1Extensible circuit breaker 200 ACE2-T13
Feeder protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
Setting range:
Overcurrent: 20-200A
Earth fault: 2-160A
Metering transformers
Metering CTs
200/100/5A
10VA class 0.5s
Metering VT ph - ph
11kV/110V 50VA
class 0.5
Documents
Installation drawing ref: RMINST-02Schematic drawing ref: RMSCH-20
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3sAnti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm21 x 3c
Bottom entry up to 630mm23 x 1c
AccessoriesNeon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code Rating
CE2-T13/16 16kA, 12kV, 75kV BIL
CE2-T13/21 21kA, 13.8kV, 95kV BIL
b
v
v
b
v