presentation_ solpaur revised 1
DESCRIPTION
ELECTRICALTRANSCRIPT
1
Brief history of Solapur Sub-Station. On Solapur – Akkalkot SH 151
in Village Limbi- Chincholi
22 Km away from Solapur City, 20 away from Akkalkot ( Sri Swami Samarth).
Total 94.79 acres
400/220 KV Station- 39.79 acres
765/400KV Sub Station- 55 acres.
LOCAL GRID NETWORK
RAIPUR`
PUNE
PARLI 2``PARLI 1
KOLH 1 KOLH 2
SEB 4
SEB 3
KUMBARI 2
KUMBARI1
KARAD LAMBOTTI
765 400 220
RAICHUR`
SOLAPUR SUBSTATION
22O KV220 KV
400
400KVKV
FEEDER DETAILS CONNECTED TO SOLAPUR SUB STATION
400 KV SOLAPUR – KARAD LINE : 299 KMS 400 KV SOLAPUR – LAMBOTI LINE : 179 KMS 400 KV SOLAPUR – PARLI LINE I : 135 KMS 400 KV SOLAPUR – PARLI LINE 2 : 135 KMS
400 KV SOLAPUR – KOLHAPUR I : 219
KMS 400 KV SOLAPUR – KOLHAPUR 2 : 219
KMS 220 KV SOLAPUR – KHUMBARI 1 : 10
KMS 220 KV SOLAPUR – KHUMBARI 2 : 10
KMS
NAME OF FEEDER LINE LENGTH
MILESTONESMILESTONES
400KV SUBSTATION400KV SUBSTATION
EventsEvents Date of Date of CommissioningCommissioning
315 MVA ICT-1315 MVA ICT-1 21 21stst Jan, 2011 Jan, 2011
63 MVAR Bus Reactor63 MVAR Bus Reactor 21 21stst Jan, 2011 Jan, 2011Karad line Bays (299 KM)Karad line Bays (299 KM) 21 21stst Jan, 2011 Jan, 2011Lamboti line Bays (166 KM)Lamboti line Bays (166 KM) 21 21stst Jan, Jan,
20112011Kolhapur line I&II Bays Kolhapur line I&II Bays 21 21stst Jan, 2011 Jan, 2011Parli I&II line Bays Parli I&II line Bays 21 21stst Jan, 2011 Jan, 2011
220 KV Bus Bars 220 KV Bus Bars 21 21stst Jan, 2011 Jan, 2011315 MVA ICT-2315 MVA ICT-2 31 31stst Mar, 2011 Mar, 2011
EQUIPMENT POPULATION
315 MVA ICT : 02 Nos. SHUNT / LINE REACTOR : 03 Nos. CIRCUIT BREAKER : 22 Sets. (14
+8) CVT : 42 Nos. (24+18) BAY KIOSK : 09 Nos DG SET : 01 Nos FF SYSTEM : 01 Nos
SOLAPUR TEAM
EXEC. SUPER. WORKMEN
------- -------- -----------
A. STATION I/C OFFICE 1 0 1
B. SUB-STATION CONSTRUCTION 3 1
C. SUB-STATION O&M 4 3 6
----------------------------TOTAL (S/S O&M & CONST.) 08 04
07 ----------------------------TOTAL = 19
400kV ONE AND A HALF SCHEME
220kV DMT SCHEME
PROTECTION & SCADA
DISTANCE PROTECTION-MAIN 1 REL 670
DISTANCE PROTECTION MAIN 2 7SA52(SIEMENS)
Bus Bar protection- REB 500 Decentralised scheme with star topology
SCADA-MICROSCADA PRO
O&M MAJOR ACHIEVEMENT…
INTRODUCED GOOSE FAIL ALARM IN SCADA.
WILL GENERATEALARM IN CASE OF FAILURE SOTHAT PREVENTIVE MEASURES CAN BE TAKEN
EARLIER.
AUTORECLOSURER IN 400kV THROUGH BOTH HARDWIRING AND GOOSE TO ENSURE 100% SUCCESS.HARDWIRING IS DONE AT SITE.
RESULT-100% AUTORECLOSURE RATE
O&M MAJOR ACHIEVEMENT…
O&M MAJOR ACHIEVEMENT
SOLAPUR TEAM MAINTAINS 2 X 315 MVA TRANSFORMERS, 63 MVAR BUS REACTOR, 2X50 MVAR LINE REACTORS, 14 Nos 400 KV BAYS, 06 NOS 220 KV BAYS AND ASSOCIATED EQUIPMENTS WITH 100% AVAILABILITY
THANK YOUTHANK YOUTHANK YOUTHANK YOU