control box - boiler parts - boilerparts.co.ke
DESCRIPTION
Control Box parts from the following manufacturer(s):BRAHMA - CSB.240CEM ECEE - CSB.241DANFOSS - CSB.243DUNGS - CSB.244ELESTA - CSB.244HONEYWELL - CSB.244LANDIS & GYR - STAEFA - SIEMENS - CSB.247PACTROL - CSB.252RIELLO - CSB.253RV - CSB.254SATRONIC - CSB.254SIT - CSB.258Insulation transformer - CSB.259Micro ammeter - CSB.259Connector - CSB.259Ignition spark detector - CSB.262TRANSCRIPT
CSB
LOA 24
Controlunit
BO
Cont
rol u
nit
BO
BRAHMA ................................. CSB.240
CEM ECEE ................................CSB.241
DANFOSS .................................. CSB.243
DUNGS ..................................... CSB.244
ELESTA ......................................CSB.244
HONEYWELL ..............................CSB.244
LANDIS & GYR - STAEFA -SIEMENS ...............................................CSB.247
PACTROL ................................... CSB.252
RIELLO ...................................... CSB.253
RV ............................................ CSB.254
SATRONIC ..................................CSB.254
SIT .............................................CSB.258
Insulation transformer .............. CSB.259
Micro ammeter ......................... CSB.259
Connector .................................CSB.259
Ignition spark detector ..............CSB.262
Control and Flame security
Sit control unit
Cell
Microammeter
Double connector
Control unit
CSB.238
BO
Cont
rol u
nit
Classifi cation by brand and manufacturer references
CEM
ECE
E
MA 26 501300 CSB.241
MA 28 501310 CSB.241
MA 29 501320 CSB.241
MA 310-12 501100 CSB.241
MA 41 501370 CSB.242
MA 410-1 501010 CSB.241
MA 43 501350 CSB.242
MA 45 501380 CSB.242
MA 46 501385 CSB.242
MA 510-1 501010 CSB.241
MA 510-1 501009 CSB.241
MA 52 501375 CSB.241
MA 53 501374 CSB.241
MA 55 501376 CSB.242
MA 55D 501373 CSB.242
MA 55E 501379 CSB.242
MA 55H 501377 CSB.242
MA 55R 501378 CSB.242
MA 610-1 501020 CSB.241
MA 710 501020 CSB.241
MA 72 501330 CSB.241
MA 73 501340 CSB.241
MA 800 501040 CSB.241
MA 803 501050 CSB.241
MA 810 501060 CSB.241
MA 86-02 501391 CSB.241
MA 86-04 501391 CSB.241
MA 86-05B 501391 CSB.241
MA 86-11 501392 CSB.241
MA 87-02 501391 CSB.241
MA 910 501020 CSB.241
DANF
OSS
BHO 62-7034/7234 see 505156 CSB.243
BHO 62D-7035/7235 see 505156 CSB.243
BHO 64.1-7037 see 505157 CSB.243
BHO 64-7036/7236 see 505156 CSB.243
BHO 72.10 57H6102 505156 CSB.243
BHO 72.11 57H6103 505157 CSB.243
BHO 73.10 57H6104 505158 CSB.243
BHO 74.10 57H6105 505159 CSB.243
FFW 507320 CSB.244
DUNG
S
DGAI 19.2 509000 CSB.244
DGAI 69 509005 CSB.244
VDK200A 509001 CSB.244
VPS504 509003 CSB.244
VPS504 509004 CSB.244
W-FM20 V3.02 502 407103 CSB.244
HON
EYW
ELL
S4560 A 1024 508019 CSB.249
S4560 A 1032 508035 CSB.249
S4560 B 1006 508057 CSB.249
S4560 B 1022 508028 CSB.249
S4560 B 1048 508009 CSB.249
S4560 B 1063 508036 CSB.249
S4560 C 1004 508062 CSB.249
S4560 C 1038 508024 CSB.249
S4560 C 1053 508038 CSB.249
S4560 CB 1022 508012 CSB.249
S4560 D 1077 508020 CSB.249
S4560 D 1135 508039 CSB.249
S4560 D 1143 508034 CSB.249
S4560 D 1150 508059 CSB.249
S4560 M 1036 508025 CSB.249
S4561 A 1007 508056 CSB.249
S4561 A 1015 508040 CSB.249
BRAH
MA
AT5 504031 CSB.240
AT5/TR1 504030 CSB.240
CM11 504036 CSB.240
CM11F 504050 CSB.240
CM191.1 504003 CSB.240
CM191.2/T1.5 504049 CSB.240
CM31 504039 CSB.240
CM31 504040 CSB.240
CM31 40030 CSB.240
CM31 504055 CSB.240
CM31F 504005 CSB.240
CM32 504002 CSB.240
CM32 504037 CSB.240
CM32 504038 CSB.240
CM32 504051 CSB.240
CM32 504052 CSB.240
CM32 PR 504056 CSB.240
CM391.2 504035 CSB.240
CM391.2 504057 CSB.240
CM391.2 504060 CSB.240
CM391.2 40029 CSB.240
DM 32 504054 CSB.240
EM41 37201031 402010 CSB.240
ER1 see 402023 CSB.240
ER1H see 402023 CSB.240
FR1 504044 CSB.240
G22/03 seule 504019 CSB.240
G22/09 seule 504023 CSB.240
G33/03 504006 CSB.240
GF2/03 seule 504018 CSB.240
GF3/03 seule 504004 CSB.240
M300/02 504027 CSB.240
MF2/02 504033 CSB.240
OF1PR 504058 CSB.240
OR3/B 431131 CSB.240
SM11 504024 CSB.240
SM152.2 504001 CSB.240
SM152.2 504059 CSB.240
SM191.2 504048 CSB.240
SM192.2 504053 CSB.240
SR3/02 504028 CSB.240
SR3/TR see 504029 CSB.240
SR3/TR01 504029 CSB.240
SR3/TR15 504026 CSB.240
SR3V 504047 CSB.240
TEC3 431260 CSB.240
TM11-37059010 504042 CSB.240
TM31-37065010 504043 CSB.240
VE3-2/05 504025 CSB.240
XM11F 40054 CSB.240
CEM
ECE
E
AE25 501900 CSB.242
GA 2410 501615 CSB.242
GA 2510 501620 CSB.242
GB 650 501656 CSB.242
GB 650.1 501622 CSB.242
GE 143 501600 CSB.242
GE 145 501605 CSB.242
GE 236-01 501650 CSB.242
GE 296 501601 CSB.242
GE 633 501630 CSB.242
GE 650 501656 CSB.242
GE 733 501631 CSB.242
GE 735 501632 CSB.242
GU 336-01 501655 CSB.243
MA 152.01 sur devis CSB.241
MA 23 501360 CSB.241
MA 25 501300 CSB.241
HON
EYW
ELL
S4561 B 1005 508041 CSB.249
S4561 B 1013 508042 CSB.249
S4561 B 1039 508007 CSB.249
S4562 A 1055 508005 CSB.249
S4562 C 1069 508006 CSB.249
S4562 DM 1006 40503 CSB.249
S4565 A 2019 508026 CSB.244
S4565 A 2027 508003 CSB.244
S4565 A 2035 508050 CSB.244
S4565 A 2050 508021 CSB.244
S4565 A 2068 508053 CSB.244
S4565 A 2076 508082 CSB.244
S4565 AD 2056 508016 CSB.244
S4565 AD 2072 508004 CSB.244
S4565 AD 2080 508079 CSB.244
S4565 AF 1007 508054 CSB.244
S4565 AF 1064 508060 CSB.244
S4565 B 2066 404049 CSB.244
S4565 BD 2021 508073 CSB.244
S4565 BF 1005 508052 CSB.244
S4565 BF 1047 508051 CSB.244
S4565 BF 1054 508074 CSB.244
S4565 BF 1062 508029 CSB.244
S4565 BF 1112 508043 CSB.245
S4565 BF 1161 508071 CSB.245
S4565 BM 1080 508072 CSB.244
S4565 C 1025 508058 CSB.244
S4565 C 1132 508075 CSB.244
S4565 CD 1021 508076 CSB.245
S4565 CD 2029 508002 CSB.244
S4565 CF 1045 508001 CSB.245
S4565 CF 1052 508063 CSB.244
S4565 CF 1060 508046 CSB.245
S4565 D 1007 508047 CSB.244
S4565 DD 1003 508081 CSB.245
S4565 DD 1045 431171 CSB.245
S4565 DF 1050 508078 CSB.245
S4565 DM 1029 508064 CSB.245
S4565 DM 1045 508048 CSB.244
S4565 P 2024 508008 CSB.244
S4565 QM 1012 508065 CSB.245
S4565 RF 1000 508077 CSB.244
S4565 SD 2005 508069 CSB.244
S4565CD2037 508083 CSB.245
S4565D1023 508084 CSB.245
S4570 AS 1012 508030 CSB.245
S4570 BS 1002 508011 CSB.245
S4570 BS 1010 508027 CSB.245
S4570 BS 1028 508067 CSB.245
S4570 BS 1036 508031 CSB.245
S4570 LS 1000 508033 CSB.245
S4570 LS 1026 508066 CSB.245
S4570 LS 1059 454064 CSB.245
S4570 LS 1091 508086 CSB.245
LAND
IS &
GYR
- ST
AEFA
- SI
EMEN
S
LAE 1/1355 502172 CSB.247
LAL 1.25 502091 CSB.247
LAL 2.14 502092 CSB.247
LAL 2.25 502094 CSB.247
LAL 2.65 502093 CSB.247
LDU 11 523A27 502111 CSB.252
LEC 1/8 853 502173 CSB.249
LFE 10 502170 CSB.249
LFE 50 502001 CSB.249
LFL 1.122 502107 CSB.250
LFL 1.133 502004 CSB.250
LFL 1.148 502112 CSB.250
LFL 1.322 502101 CSB.250
LFL 1.322F 502104 CSB.250
LFL 1.333 502109 CSB.250
Manufact. Ref. Ref Page Manufact. Ref. Ref Page Manufact. Ref. Ref Page
Control unit
CSB.239
Cont
rol u
nit
BO
LAND
IS &
GYR
- ST
AEFA
- SI
EMEN
S
LFL 1.335 502102 CSB.250
LFL 1.622 502110 CSB.250
LFL 1.622F 502103 CSB.250
LFL 1.635 502106 CSB.250
LGB 21 130A27 502205 CSB.250
LGB 21 330A27 502177 CSB.250
LGB 21 350A27 502206 CSB.250
LGB 21 550A27 502024 CSB.250
LGB 22 230B27 502182 CSB.250
LGB 22 330A27 502178 CSB.250
LGB 41 258A27 502179 CSB.250
LGC 22 002C271 502180 CSB.250
LGK 16.322A27 502113 CSB.250
LGK 16.622A27 502060 CSB.250
LGK 16.635A27 502114 CSB.250
LME 21 230A2 502012 CSB.250
LME 22 232A2 502017 CSB.251
LME 11 330A2 502010 CSB.250
LME 21 120A2 502011 CSB.250
LME 21 33A2 502013 CSB.250
LME 21 35A2 502014 CSB.250
LME 21 55A2 502015 CSB.251
LME 22 131A2 502016 CSB.251
LME 22 233A2 502018 CSB.251
LME 22 331A2 502019 CSB.251
LME 23 331A2 502020 CSB.251
LME 23 351A2 502021 CSB.251
LME 44 056A2 502022 CSB.251
LME 44 057A2 502023 CSB.251
LMG 21 230A27 see 502012 CSB.251
LMG 21 330B27 see 502013 CSB.251
LMG 22 233A27 see 502018 CSB.251
LMG 22 330A27 see 502019 CSB.251
LMO 24 111A2 502385 CSB.247
LMO 44 255A2 502383 CSB.247
LMO 54 200B2BU 420035 CSB.247
LMO 54 200B2BU 420035 CSB.247
LMO 54 210B2V 424005 CSB.247
LMO 54 210B2V 424005 CSB.247
LMO 64 302A2B 432022 CSB.247
LMO 82 100C2WH 407024 CSB.247
LMO 82 100C2WH 407024 CSB.251
LMO 82 100C2WH 407024 CSB.247
LMO14 111A2 ou B2 502006 CSB.247
LMO14 111A2 ou B2 502006 CSB.247
LOA 14 171B2V 424004 CSB.247
LOA 24 502052 CSB.247
LOA 26 502049 CSB.247
LOA 36 502048 CSB.247
LOA 44 see 502383 CSB.247
LOK 16 250A27 502056 CSB.247
PACT
ROL
CSA 12 448065 CSB.253
CSA 6 448066 CSB.253
CSS 01-24R/E 448050 CSB.253
CSS01.12 448064 CSB.253
CSS01-12SJV11 448062 CSB.253
CSS01-24JV03 448063 CSB.253
P14 110 AL 443010 CSB.253
P16 AFT 448014 CSB.253P16 HIJ 409701 448010 CSB.253P16B 402701 see 448009 CSB.253P16C /FL402801 see 448005 CSB.253P16D /402901 448005 CSB.253P16DI / S (NF) 400601/V03 448002 CSB.253
P16DI /400601 448001 CSB.253
P16FI (CE)406203 448007 CSB.253
RIEL
LO
483 SE see 404894 CSB.252
503 SE 404062 CSB.252
508 SE 404067 CSB.254
509 SE 404019 CSB.254
520 SE 404071 CSB.254
522 RBO 404021 CSB.254
525 SE 404068 CSB.254
530 SE 404894 CSB.254
531 SE 404895 CSB.254
535 RSE 404025 CSB.254
550SE =550 SMD 404640 CSB.254
552SE 404265 CSB.254
553SE 404638 CSB.254
555SE 404024 CSB.254
MG 569 404020 CSB.254
RMG88.62A2 404268 CSB.254
RV
05125001 Type 448002 CSB.255
05125004 Type 453009 CSB.255
0514 Type 453005 CSB.255
SATR
ONIC
Elcopen Analyser defect 402025 CSB.255
Elcopen Analyser defect 402025 CSB.257
DKG 972 507049 CSB.257
DKG 972 507049 CSB.257
DKG 972 mod 21 507065 CSB.257
DKO 970 507009 CSB.255
DKO 972 507012 CSB.255
DKO 974 507014 CSB.255
DKO 976 507015 CSB.255
DKW 972 507059 CSB.255
DKW 972 + prolong. 507060 CSB.255
DKW 976 507061 CSB.255
DKW 976 + prolong. 507062 CSB.255
DMG971 507063 (except Guillot) CSB.257
FFW 930 FIOUL - GAZ 507320 CSB.257
EM41 Kit replace-ment relay 402024 CSB.257
ER1 Kit replace-ment relay voir 402023 CSB.240
ER1H Kit replace-ment relay 402023 CSB.240
MMG 810-33 507056 CSB.257
MMG 811-63 507058 CSB.257
MMI 810-33 507037 CSB.257
MMI 810-35 507034 CSB.257
MMI 811-35 replaced by 507063 (except guillot) CSB.257
MMI 812-23 replaced by 507033 CSB.257
MMI 812-33 replaced by 507033 CSB.257
MMI 813.1 mod 23 507042 CSB.257
MMI 815 mod 10 replaced by 507049 CSB.257
MMI 815 mod 5 replaced by 507049 CSB.257
MMI 962-23 507033 CSB.257
MMO 872
replaced by 507060 + (Detector IRD1010 following brand if IRD810 or 910 or 911 in position or cell UVD codes 507003)
CSB.255
MMO 876
replaced by 507062 + (Detector IRD1010 following brand if IRD810 or 910 or 911 in position or cell UVD codes 507003)
CSB.255
SG 113 406009 CSB.257
SG 513 406020 CSB.257
SATR
ONIC
SH 113 406013 CSB.255
SH 213 mod C1 406019 CSB.256
TF 801 507005 CSB.254
TF 802 507006 CSB.254
TF 804 507007 CSB.255
TF 830 507051 CSB.255
TF 830.3 507064 CSB.255
TF 832 507053 CSB.255
TF 834 see 507001 CSB.255
TF 834.3 507001 CSB.255
TF 834E.3 see 507001 CSB.255
TF 836 507050 CSB.255
TF 840 507054 CSB.255
TF 844 507057 CSB.255
TF 874 405002 CSB.255
TF 974 507016 CSB.255
TFI 812-2 maxi 120 Kw mod 10 507043 CSB.257
TFI 812-2 maxi 350 Kw mod 5 507041 CSB.257
TFI 812-2 mod 10E replaced by 507049 CSB.257
TMG 740.3 type 32-32 replaces TMG 740.2 type 32-32
507032 CSB.257
TMG 740.3 type 43-35 replaces TMG 740.2 type 45-54
507039 CSB.257
TMO 720-4-35 507020 CSB.255
TTG 760 FN replaced by 507058 CSB.257
TTG 760 FN replaced by 507058 CSB.257
TTG 760-33 replaced by 507056 CSB.257
TTG 760-33 replaced by 507056 CSB.257
TTO 810-35
replaced by 507060 + (cell MZ ref 507101 If cell FZ in position or detector IRD1010 following brand or cel UVD ref 507003)
CSB.255
TTO 836-35
replaced by 507062 + (cell MZ ref 507101 If cell FZ in position or detector IRD1010 following brand or cel UVD ref 507003)
CSB.255
TTO 872
replaced by 507060 + (Detector IRD1010 following brand if IRD810 or 910 or 911 in position or cell UVD codes 507003)
CSB.255
TTO 876
replaced by 507062 + (Detector IRD1010 following brand if IRD810 or 910 or 911 in position or cell UVD codes 507003)
CSB.255
SIT
0.503.501 503009 CSB.258
0.503.501 503010 CSB.258
0.503.501 503011 CSB.258
0.537.002 DMT type 404026 CSB.258
0.537.301 DMT type 431015 CSB.258
0.577.009 503002 CSB.258
0.577.211 503005 CSB.258
0.577.304 503007 CSB.258
0.577.308 503003 CSB.258
0.577.311 503004 CSB.258
0.577.503 471003 CSB.258
0.577.504 503001 CSB.258
0.577.701 503013 CSB.258
0.577.702 503012 CSB.258
0.577.705 503006 CSB.258
Classifi cation by brand and manufacturer referencesManufact. Ref. Ref Page Manufact. Ref. Ref Page Manufact. Ref. Ref Page
Control unit
CSB.240
BO
Cont
rol u
nit
BRAHMA CONTROL BOXFUEL type
Fuel burners compatible with a fuel flow less than 30 kg/hour.
Type Pre Purge Safety Time Detection RefCharacteristic : 1 fi ring rateG33/03 15 10 Cell 504006Characteristic : 1 fi ring rateG22/03 only one 15 10 Cell 504019G22/09 only one *
10 10 Cell 504023Characteristic : 2 fi ring ratesGF2/03 only one 15 5 Cell 504018GF3/03 only one 20 5 Cell 504004Characteristic : for FERROLIFR1 10 10 Cell 504044Characteristic : for BALTUROR3/B 20 5 Cell 431131TEC3 10 10 Cell 431260Characteristic : for ELCO
ER1 10 5 Cellsee
402023
ER1H 15 5 Cellsee
402023
** replaces models G22/05, G22/06 and G22/07
NOTE :
Application Ref
ECOFLAM - FRANCO BELGE - FBR - THERMITALsee
504006JOANNES - BALTUR - BIASI - FINTERM - THERMOMATIC - CGA FRANCO BELGE - ECOFLAM - DREIZLER - CHAUFFAGE FRANÇAIS - IDÉAL CLIMA - JUHATHERM - TERMONAFTA -MAZECO - SLCF - SANT ANDRÉA - BLOWTHERM - THERMOMEC
504019
BALTUR - HS FRANCE- FIM - CTC - THERMOMATIC - RADIANT ECOFLAM - FRANCO BELGE - FONDITAL - PORCHER - CTC - CGA 504023JOANNES - THERMOMEC - FINTERM - THERMOMATIC - DREIZLER - JUHATHERM - TERMONAFTA -BLOWTHERM 504018FER-FERROLI 504044BALTUR 431131BALTUR 431260
CELL
1 2 3Description Mark Ref
FC7/R side shot 1 504207FC8/R frontal shot 2 504210TEC3 blue frontal and side shot 3 431259FC13 red frontal and side shot 3 431141FC13AL ELCO pluggable - 402002
BASE
Description RefG22 - GF2 - G22Z 504015
GAS type
1 2Type Pre Purge Safety Time Detection Mark Ref
AT5 15" 5" Io 1 504031AT5/TR1 15" 10" Io 1 504030CM11 20" 10" Io 2 504036CM11F 15" 5" Io 2 504050Characteristic : BPSCM31 30" 10" - 2 504039CM31 30" 5" - 2 504040Characteristic : FRISQUETCM31 15" 5" Io 2 40030Characteristic : SEETCM31F 10" 5" - 1 504005CM32 30" 15" lo 2 504002CM32 20" 10" Io 2 504037Characteristic : SLCFCM32 5" 5" - 2 504038CM32 30" 10" - 2 504051Characteristic : SLCFCM32 - - - 2 504052CM 191.1 - - Io 1 504003CM191.2/T1.5 15" 10" Io 1 504049CM391.2 15" 5" lo 1 40029CM391.2 * 20" 10" Io 1 504035Characteristic : GAZ INDUSTRIE gas relay 20sDM 32 - - - - 504054M300/02 30" 2" Io/UV 1 504027MF2/02 30" 2" Io/UV 1 504033SM11 1.5" 5" Io 2 504024SM152.2 30" 10" lo 1 504001Characteristic : EMATSM191.2 20" 10" Io 1 504048CM391.2 1 504057Characteristic : CHAFFOTEAUXSM192.2 - - - 1 504053SR3/TR01 30" 3" Io/UV 1 504029SR3/02 30" 3" Io 1 504028Characteristic : SLCF
SR3/TR 30" 3" - 1 See504029
SR3/TR15 15" 3" Io/UV 1 504026Characteristic : COUSSEMENTSR3V 20" 3" Io 1 504047TM11-37059010
15" 10" Io - 504042TM31-37065010
15" 10" Io - 504043VE3-2/05 30" 2" Io 1 504025Characteristic : FRISQUETXM11F 15" 5" Io 2 40054Characteristic : ELCOEM41 37201031
30" 3" Io 3 402010Characteristic : CHAUFFAGE FRANÇAISCM391.2 - - - 504060
Characteristic : ACCORONICM31 - - - 504055
Characteristic : (CLIMAIR) ROBURCM32 PR - - - 504056
Characteristic : GUILLOTSM152.2 - - - 504059
Characteristic : replaces OF1OF1PR - - - 504058
* Hydromotrix
3
Control unit
CSB.241
Cont
rol u
nit
BO
NOTE :Application Ref
JOANNES - FINTERM 504031EMAT 504036GEMINOX - PENSOTTI 504050EMAT - BPS - WESPER 504039EMAT- ACCORRONI - NALSON - WESPER 504040EMAT- CHAUFFAGE FRANÇAIS 504037AERMAX- APEN GROUP - GENERFEU - SOLYGAZ - THERMOVUR CHAUFFAGE FRANÇAIS 504038AERMAX 504051ABIG - PENSOTTI - IMMERGAS 504049EMAT - BALTUR FRISQUET - CHAUFFAGE FRANÇAIS 504035EMAT 504048CHAUFFAGE FRANÇAIS 504029CHAUFFAGE FRANÇAIS - ACCORRONI - WESPER 504026JOANNES 504042JOANNES 504043FRISQUET 40054FRANCO BELGE-JOANNES-MAZECO-ECOFLAM - FINTERM CHAUFFAGE FRANÇAIS 504027WESPER-ACCORRONI-EMAT-JOANNES - FINTERM 504033UNIGAS - WESPER - ACCORRONI - BALTUR - ECOFLAM - EMAT-EUROWARM - FRANCO BELGE - AERMAX - APEN GROUPGENERFEU - SOLYGAS - THERMOVUR - CGA - COLLARD TROLART - PORCHER - LAMBORGHINI - SANT ANDRÉA
504028ECOFLAM-JOANNES-BALTUR - PORCHER - CHAUFFAGE FRANÇAIS 504025
CELL
1 2Description Mark Ref
UV 1 Ø22 mm 1 504218FC11 Ø8 mm frontal shot 2 504215
BASE
Description Ref
for MF2 504013for AT5 / TR-CM391 504014for AT5 / SR302 / M300 / VE3-2 504016for SR3 / TR / CM191 504017
CEM ECEE FUEL CONTROL UNITOLD FUEL MODEL
Fuel burners compatible with a fuel flow less than 30 kg/hour.
Type Cell Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 2 fi ring rates 220VMA 310-1 8205 30" 30" 20" 5" or 10" 501100Characteristic : replaced by MA 510-1MA 410-1 8205 30" 5" 15" 5" or 10" 501010Characteristic : 220VMA 510-1 8205 30" 30" 15" 5" or 10" 501010Characteristic : 380VMA 510-1 8205 30" 30" 15" 5" or 10" 501009
Type Cell Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 220VMA 610-1 8205 10" 10" 6" 10" 501020Characteristic : 220V replaced by MA 610MA 710 8205 - - 6" 10" 501020Characteristic : single phase 110/220VMA 800 8205 - - - 10" 501040Characteristic : three phase 220/380VMA 803 8205 - - - 10" 501050Characteristic : single phase 220VMA 810 8205 - - - 10" 501060Characteristic : Replaced by MA610MA 910 8205 10" 10" - 10" 501020Characteristic : MA 152.01 8205 24" 24" 18" 5"/8" on request
REPLACEMENT INDEXOLD BOX NEW MODEL Notes
MA 22 MA 26 BASE without replacementMA 25 MA 26 Cell Replaced by 8206MA 86-02 MA 86-05 BASE without replacementMA 87-02 MA 86-05 Cell without replacement
20 type
Pull out equipment. Use with Fuel-oil burner
Type Cell Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 2 fi ring ratesMA 23 8208 15" 12" 2" 10" 501360Characteristic : replaced by MA 26MA 25 8208 15" 15" 2" 10"Characteristic : Cell 8210/8211MA 26 8206 10" 10" 5" 10" 501300MA 28 8206 - - - 10" 501310MA 29 8206 10" 10" - 10" 501320
PROTECTOBLOC type
Pull out equipment. Use with CEM motor and protectobloc transformer
Type Cell Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : motor 90WMA 72 8205 5" 5" - 10" 501330Characteristic : motor 150WMA 73 8205 5" 5" - 10" 501340
MA 52 8209 12/7" 2" 2" 10" 501375
MA 53 8207 10" 10" - 10" 501374Characteristic : replaced by MA 86-05MA 86-02 8212 7" 10" - 10" 501391MA 86-04 8212 7" 5" 1" 10“ 501391
MA 86-05B 8212 5/7" 5/7" 0,5" 10" 501391
MA 86-11 8212 5/7" 5/7" 0,5" 10" 501392Characteristic : replaced by MA 86-05MA 87-02 8212 - - 12" 10" 501391
Control unit
CSB.242
BO
Cont
rol u
nit
CEM ECEE FUEL CONTROL UNIT41/43/45/46/ 55 type
Type Cell Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 2 fi ring ratesMA 41 8212 15" 15" 40" 5" 501370MA 43 8212 10" 10" 15" 10" 501350Characteristic : Security on stray lightMA 45 8212 10" 10" 3" 10" 501380MA 46 8212 10" 10" 3" 10" 501385
MA 55 8209 10" 10" 3" 10" 501376Characteristic : Used with preheater
MA 55H 8209 10" 10" 3" 10" 501377Characteristic : maintains the tension even if the klixon heater breaks
MA 55R8207/8209
10" 10" 3" 10" 501378Characteristic : ionizationMA 55E - 10" 10" 3" 10" 501379Characteristic : Remote control
MA 55D8207/8209
10" 10" 3" 10" 501373
CELL
1 2 3 5
4 6 7Description Mark Ref
8205 for MA 800/72/73/152-01 types (supplied without fl ange) 1 5012208206 use with MA 26/28/29 (side and frontal shots) 2 5012608207 use with MA 55R - no fl ange 3 5012618208 use with MA 23 and 25 5 5012908209 use with MA 23 / 25 / 52 / 55 4 5015008210 use with MA 26/28/29 (side Ø17 shots) 2 see 5012608211 use with MA 26/28/29 (side Ø14 shots) 7 5015108212 use with MA 86/ 41/43/45/46 6 5015208212 RR same model extended for GIANOLA 6 501530
BASE
1 2 3Description Mark Ref
S801 for MA 800/803/810 1 501200SP06 for MA 152.01 - GE 232/236 3 501202S20 for all MA 20 types 2 501250S401 for MA 40 and 55 types 2 501252S72 for MA 72 2 501255S73 for MA 73 - 501256S407 for MA 52 2 501257S803 for MA 803 exclusively 1 501410
CEM ECEE CONTROL UNITGAS FLAME
Pull out equipment - Transistor amplifier detects gas flame with a ionization electrode.
FEATURES : � Monophased voltage : 220V +10% +15% 50Hz � Contact of fl ame relay : 220V 2A � Current of fl ame ensuring a correct operation: between 5 and 120 micro amps � Consumption : 3VA � Ambiant temperature : 50°C maxi � Response time of the fl ame relay : lower than 0,5 second with the appearance and the extinction of the fl ame.
Description Ref
AE 25 ionization detector 501900
GA / GB / GE type
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : Blown air burner
GA 2410 30" - - 5" 501615Characteristic : atmospheric burner
GA 2510 5"/10" - - 5" 501620Characteristic : Used absolutely with an air pressure switchRelay GB 650 replaces completely GE 650 subject to short circuit of the terminals 12 and 13 which do not exist on the GE 650.
GB 650 0" - - 4" 501656Characteristic : ionization sensor
GB 650.1 0" - - 4" 501622Characteristic : blown air burner
GE 143 20" - - 5" 501600Characteristic : atmospheric burner
GE 145 10" - - 5" 501605Characteristic : monotube blown air burner
GE 236-01 60" 3" 3" 2" 501650Characteristic : -
GE 296 - - - - 501601Characteristic : not recyclic
GE 633 3" - 3" - 501630Characteristic : can work with shunt on air manostat
GE 650 10" - - 8" 501656Characteristic : 2 fi ring rates
GE 733 30" - 2" 2,5" 501631GE 735 30" - 40" 4,5" 501632
Control unit
CSB.243
Cont
rol u
nit
BO
GU (UV) type
Control and security equipment with flame monitoring by UV sensitive cell.
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time Ref
Characteristic : ignition spark controlGU 336-01 60“ - 2“ 4“ 501655
CELL
1 2 3Description Mark Ref
8300 UV Detector 1 5016908301 UV Detector industrial model 2 501691SYLVANIA UV P607.88 - Ø22 mm - 4 pin plugs 3 502312
BASE
1 2 3Description Mark Ref
SP06 for GE 218/230/232/236/650/GB650/ GU330/336 - MA 152.01 1 501202S402 for GE 143 / 145 3 501204S412 for GE 733 / 735 2 501205
SPARK DETECTORLinked to a flame detector circuit that uses ionization electrode, the system detects a flame signaling a spark.It replaces the UV cell for ignition spark detection when the use is compromized.
Description RefDA 51 for GE 633/ 733 501660
SEE THE INSTALLATION DRAFT AT THE END OF THIS CHAPTER
DANFOSS CONTROL BOXBHO 62/64/72/74 type
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : Landis & Gyr switch positionReplaced by 505154 after exhaustion of stocks BHO 62 - 7034/7234 13" 13" 15" 10" see 505156Characteristic : Landis & Gyr switch positionBHO 64.1 - 7037 6" 6" 20" 10" see 505157Characteristic : Danfoss switch positionBHO 62D-7035/7235 13" 13" 15" 10" see 505156
BHO 62/64/72/74 type (continuation)
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : Landis & Gyr switch positionBHO 64 - 7036/7236 13" 13" 15" 10" see 505156Characteristic : electronic box with diagnostic blinking light replaces BHO64BHO 72.10 57H6102 13" 15" 15" 10" 505156Characteristic : electronic box with diagnostic blinking light replaces BHO64.1BHO 72.11 57H6103 16" 20" 20" 10" 505157Characteristic : electronic box with diagnostic blinking light replaces BHO64ABHO 73.10 57H6104 13" 2" 15" 10" 505158Characteristic : electronic box with diagnostic blinking light equivalent LMO44BHO 74.10 57H6105 25" 2" 5" 5" 505159
CELL
Description Ref
LD (6 LUX) 057H 7079 - with length 780 mm 505260LD (6 LUX) lg 65,5mm 057H 7079/7279 - with length780 mm 505263LDS (2 LUX) 057H 7085 - with length 500 mm 505261LDS long 057H 7091 for BENTONE - DEVILLE - HS FRANCE 505262
ADAPTER
Description Ref
BHO 70 ADAPTER KIT 505411
BASE
Description Ref
Base 057H 7010 - 057H 7011 for BHO 61/62/62D/64.1 505401
FRA / FRU type Flame control relay used for fl ame control on semi-automatic installations .
Control unit
CSB.244
BO
Cont
rol u
nit
DANFOSS CONTROL UNITFFW type for FRA / FRU replacement
For fuel or gas, atmospheric or ventilated burner.For semi-automatic installation. � Ionization monitoring or cell UVZ or infrared IRD 1020 detector
Description Ref
FFW FUEL - GAS 507320BASE 507300ZT 870 Transformer 805913AZ5 Pilot burner 708790
DUNGS CONTROL BOXDGAI 19 type
DGAI 19.2 control box for atmospheric gas burner, 220VA - 600 Kw, ionization electrode detection.
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Characte-ristic
Ref
DGAI 19.2 4" 5" 4" 13"/8" - 509000DGAI 69 50" 1" 0" - - 509005
VDK / VPS / W-F
1 2 3
4
TypePre
PurgePre
IgnitionPost-
IgnitionSafety Time
Mark Ref
VDK200A 02 type - - - - 1 509001VPS504 02 type - - - - 2 509003VPS504 04 type - - - - 3 509004W-FM20 V3.02 502
- - - 2/5" 4 407103
ELESTA CONTROL BOX ACCESSORYReplacement cell
Description Ref8209 Fuel oil fl ame control cell /all types of control boxes 501500
HONEYWELL CONTROL BOXS4565 GAS type
TypePre
PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Relay used by GEMINOX
S4565 A 2027 - - - - 508003Relay used by DE DIETRICH - RADIANT
S4565 A 2019 - - - - 508026Relay used by DE DIETRICH - ZAEGEL HELD- ST ROCH -COUVIN
S4565 A 2035 - - - - 508050Relay used by CHAFFOTEAUX - ZAEGEL HELD
S4565 A 2050 - - - 5" 508021Relay used by ACV
S4565 A 2068 - - - - 508053S4565 AD 2080 - - - - 508079Relay used by ROCA
S4565 A 2076 - - - - 508082Relay used by RIELLO - BERETTAS4565 B 2066 replace S4565 B 2017
- - - - 404049
Relay used by RIELLO - SIME - CALORTECNICA
S4565 CF 1052 - - - - 508063Relay used by RIELLO
S4565 RF 1000 - - - - 508077Relay used by DE DIETRICH - CICH - IDEAL STANDARD - APEN GROUP CALORTECNICA - THERMITALS4565 C 1025 - - - - 508058Relay used by VIESSMANN
S4565 C 1132 - - - - 508075Relay used by ACTI - SOLARONICS-GUILLOT-GAZ INDUSTRIE
S4565 D 1007 - - - - 508047Relay used by GEMINOX
S4565 AD 2072 - - - - 508004S4565 BM 1080 - - - - 508072S4565 DM 1045replaced by S4565 DM 1086
- - - - 508048
Relay used by RADIANT SPACE RAY
S4565 P 2024 - - - - 508008Relay used by FERROLI
S4565 AD 2056 - - - - 508016S4565 CD 2029 - - - 10" 508002Relay used by SIME - UNICAL - SAUNIER DUVAL (THELIA 30E)
S4565 AF 1007 - - - - 508054Relay used by CHAUFFAGE FRANÇAIS
S4565 AF 1064 - - - - 508060Relay used by FRANCO BELGE
S4565 BD 2021 - - - - 508073Relay used by DE DIETRICH - IDEAL CLIMA
S4565 BF 1005 - - - - 508052Relay used by DE DIETRICH
S4565 SD 2005 - - - - 508069Relay used by SOLARONICS
S4565 BF 1047 - - - - 508051Relay used by THERMITAL - VIESMANN
S4565 BF 1054 - - - - 508074Relay used by IDEAL CLIMA- AO SMITH - CHAPPEE -IDEAL STANDARD- THERMITAL
S4565 BF 1062 - - - - 508029
Control unit
CSB.245
Cont
rol u
nit
BO
S4565 GAS (continuation)
TypePre
PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Relay used by DE DIETRICH - OERTLI - ROCAS4565 BF 1112 - - - - 508043S4565 BF 1161 - - - - 508071Relay used by UNICALS4565 CD 1021 - - - - 508076S4565 DF 1050 - - - - 508078Relay used by BIASI - MANAUT - RIELLO - ALLIANCES4565 DD 1003 - - - - 508081Relay used by UNICAL - APEN GROUPS4565 DM 1029 - - - - 508064Relay used by RIELLO - DOMUS- HERMANS4565 CF 1045 - - - - 508001Relay used by DEVILLE-ZAEGEL HELD- ST ROCH COUVINS4565 CF 1060 - - - - 508046Relay used by BALTUR - HERMANNS4565 DD 1045 - - - 10“ 431171Relay used by BERETTAS4565 QM 1012 - - - - 508065Relay used by GENERFEUS4565D1023 508084Relay used by ZAEGEL HELDS4565CD2037 508083
S4560 / S4561 /S4562 /S4570 GAS type
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Relay used by ACV - INOX G-GES4560 A 1024 - 4" 2,5" 5" 508019Relay used by FRANCO BELGE - BONGIOANNIS4560 A 1032 - 4" 2,5" 10" 508035Relay used by ROCAS4560 B 1006 - 4" 2,5" 10" 508057Relay used by NESTOR MARTIN - GUILLOT - ATLANTICS4560 B 1022 - 4" 2,5" 5" 508028Relay used by BUREXS4560 B 1048 - - - - 508009Relay used by SOLARONICS - GUILLOTS4560 B 1063 - 4" 10" 25" 508036 -S4560 C 1004 - - - - 508062Characteristic : DEVILLES4560 C 1038 8" 4" -- 5" 508024Characteristic : UNICAL - ACCORRONI - AO SMITH - ATI -BOSCHETTI - ICIS4560 C 1053 24" 4" - 10" 508038Characteristic : burner with GEMINOX fan ground boiler w/burner (replaces S4560 D 1028)S4560 D 1077 10" 35" - 5" 508020Characteristic : ACTICharacteristic : ACTI - SOLARONICS - INTERCALS4560 D 1135 24" 4" - 25" 508039Characteristic : CHAPPEES4560 D 1143 16" 4" - 25" 508034Characteristic : -S4560 D 1150 - - - - 508059Characteristic : GEMINOXS4560 M 1036 - - - - 508025
S4560/S4561/S4562/S4570 GAS type (continuation)
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : NESTOR MARTINS4560 CB 1022 - - - - 508012Characteristic : UNICAL - SANT ANDREA - FER - FERROLIS4561 A 1007 - - - - 508056Characteristic : FER - FERROLIS4561 A 1015 - - - - 508040Characteristic : FER - FERROLI - VAILLANTS4561 B 1013 - - - - 508042Characteristic : IDEAL CLIMA - BALTURS4561 B 1005 - - - - 508041Characteristic : CHAUFFE FRANÇAIS - FERROLIS4561 B 1039 - - - - 508007Characteristic : FERROLIS4562 A 1055 - - - - 508005S4562 C 1069 - - - - 508006S4562 DM 1006 - - - - 40503Characteristic : AUERS4570 AS 1012 - - - - 508030Characteristic : DE DIETRICHS4570 BS 1002 - 17" 1" 10" 508011S4570 BS 1036 - 17" 3" 10" 508031S4570 LS 1026 - - - - 508066Characteristic : SOLARONICS - GUILLOTS4570 BS 1010 - - - - 508027Characteristic : FRANCO BELGES4570 BS 1028 - - - - 508067Characteristic : SOLARONICS - GUILLOTS4570 LS 1000 30" 35" 1" 5" 508033Characteristic : REZNOR-GAZ INDUSTRIE-SOLARONICSS4570 LS 1059 15" - - 5" 454064Characteristic : SOLARONICSS4570 LS 1091 - - - - 508086
CONTROL and FLAME SECURITYfor HONEYWELL INDUSTRIAL BURNERS
CELL
1
2
Description Mark RefUV Cell C7027A1049 Monoblock tube frontal shot IP677 Fixing 1/2“ NPT - Cable 2,4m - Temperature -18 to +102°C
1 508202
UV Cell C7027A1056 Monoblock tube frontal shot IP677 Fixing 1/2“ NPT - Cable 2,4m - Temperature -18 to +102°C
1 508203
UV Cell C7027A1064 Monoblock tube frontal shot IP677 Fixing 1/2“ NPT - Cable 7m - Temperature -18 to +102°C
1 508204
UV Cell C7027A1023 Monoblock tube frontal shot IP677 Fixing 1“ NPT - Cable 1,8m - Temperature -18 to +121°C
2 508205
UV Cell C7061A1020-ST001 IP677 - Temperature -40 to +80°C with amplifi er lens 3 508206
3
Control unit
CSB.246
BO
Cont
rol u
nit
CONTROL and FLAME SECURITYfor HONEYWELL INDUSTRIAL BURNERS PROGRAMMER
Universal programmer pluggable to Q 7800 baseAPAVE D 15/97 -43.2 approved
Description Ref
EC7850A1072 - 230Vac - post purge : 2s 508227
BASE
For 7800 type
Description Ref
Q7800A1005 plastic version 508208
PRE-VENTILATION CARD
Range of purge timer
Description Ref
ST7800A1013 - 7s 508224ST7800A1039 - 30s 508225
AMPLIFIER
For UV : R7824/47/49/61/86 - Pluggable - additional modules
Description Ref
R7849A1023 standard - 2s - for C7027/35/44 detector 508219R7861A1026 Auto-verifying - 2s - for C7061 detectorAPAVE D 15/97 -43.2 approved 508220
For flame electrode : R7847A/B - Pluggable - additional modules
Description Ref
R7847A1033 standard - 2s - for C7012A/G detector 508217R7847B1031 Auto-verifying - 2s - electrodes detectorAPAVE D 15/97 -43.2 approved 508218
MANUAL REMOTE RESET MODULE
Description Ref
S7820A1007 only remote reset 508222
RELAY
Primary relay with reversing switch
Description RefR4343D1041-ST005 Standard amplifi er incorporated - Ioniza-tion 115/230Vac - 2 reversing switches : 4A cos ϕ 6,35 508209R4343E1048-ST005 UV standard amplifi er incorporated for mini Cell C7027 or C7035 - 115/230Vac - 2 reversing switches : 4A cos ϕ 6,35
508210
Half automatical industrial relays - Universal relay- 115/230VAC Start auto control for pluggable amplifier R72xx - 2 independant relays
Description RefR4348B1057 Output and LED meter contact rating 4-20MA Gives an indication of fl ame current strength (onlynfor measure not for security) IP54 APAVE D 15/95 -40.1 approved
508212
R4348B1008 Standard model - without fl ame current jack socket - IP54 508211
BASE
Description Ref
Base box R4348 508200
AMPLIFIER
1 2
For UV : R7824/47/49/61/86 - Pluggable - additional modules
Description Mark RefR7323B1026 standard (U.V.) - 2s - for detector C7027/35/44 1 508216R7323B1018 standard (U.V.) - 2s 1 508215R7061A1016 Auto-verifying (U.V.) - 2s - for detector C7061 APAVE D 15/86 -10.3 approved 2 508213R7247A1005 Auto-verifying (U.V.) - 2s - for detector C7012E APAVE D 15/95 -40.1 approved 2 508214
SEAL CONTROL PROGRAMMER
Air pressure control LED display
Description Ref
A4021A1002 230 Vac 508201
BASE
Description Ref
ZL030001 Seal control base 508226
Control unit
CSB.247
Cont
rol u
nit
BO
ADAPTER
Adapter 4-20mA for M9184 (internal connection)
Description Ref
Q7230A005 4 - 20mA 508207
LANDIS & GYR STAEFA - SIEMENS FUEL CONTROL BOXLOA type
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : Special VIESSMANN
LOA 14 171B2V - - - - 424004Characteristic : alternative for LOA 22 + decrease voltage security
LOA 24 13" 13" 0/13" 10" 502052Characteristic : Will replace LOA 24 when no more available.
LMO 24 111A2 (1)(2) 16" 15" 10" 10" 502385
Characteristic : Special CHAPPEE - IDEAL STANDARD
LMO14 111A2 ou B2 (1)(2) 16" 15" 10" 10" 502006
Characteristic : Special WEISHAUPT
LMO 82 100C2WH (1)(2) - - - 3s gas
5s fuel 407024
Characteristic : Special BUDERUS
LMO 54 200B2BU (1)(2) - - - 7s 420035
Characteristic : Special VIESSMANN
LMO 54 210B2V (1)(2) - - - - 424005
Characteristic : decrease voltage protection
LOA 26 13" 13" 15" 10" 502049Characteristic : 2 fi ring rates + 30 kg/h
LOA 44 25" 25“ 5/8" 5" see 502383
Characteristic : Will replace LOA 24 when no more available.
LMO 44 255A2 (1)(2) 26" 25" 5" 5" 502383
Characteristic : Special BENTONE
LMO 64 302A2B (1)(2) - - - - 432022
Characteristic : voltage light - fl ame light
LOA 36 13" 13" 15" 10" 502048
(1) Automatic failure detection box.3 blinking different colors signal a defect.(2) Use with QRB1 or QRC1. No needs to replace the base.
LAL ... /LOK type
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 3 stages remote lockout + Switch for airdamper QRB1
LAL 1.25 22.5" 27.5"/2.5" 22,5"/5" 5" 502091Characteristic : 3 stages remote lockout +Switch for airdamper RAR or QRB1
LAL 2.14 14" 14"/2" 10"/4" 5" 502092LAL 2.65 67.5" 27.5"/2.5" 22.5"/5" 5" 502093Characteristic : photo resistant or electric cell + air pressure + QRB1
LAL 2.25 27.5" 27.5"/2.5" 22,5"/5" 5" 502094Characteristic : Detection by RAR 7 or RAR 6
LOK 16 250A27 27.5" 27.5"/2.5" 15" 5" 502056
ADDITIONAL TECHNICAL OVERVIEWIMPORTANT : For telegestion, replace LAL by LOK 16.In that case move the polarization pins.
Box typeLAL LOK 16
250A271.25 2.14 2.25 2.65
Intermittent functioning X X X X -
Permanent functioning - - - - X
Voltage 230V X X X X X
Box model M X X X X X
Contact MO = motor (synchrone)
X X X X X
Programmable starter X X X X X Decrease voltage Protection X X X X X Remote control release X X X X XCell QRB X X X X -Cell QRB X X X X -
Cell RAR - X X X X
Contact 2 Ev X X X X X
Contact air fl ap X X X X X
Temperature adjustment or boiler pressure
X X X X X
LAE typeNOTE : Adjustable preventilation from 8" to 63".Total preventilation and post ventilation cannot exceed 90" (when Pre-purge = 8", post-purge = 82" etc...)Adjustable security delay from 0“ to 9"
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
LAE 1/1355 30" 3" -: 5" 502172
FLAME DETECTORYellow flame detector box for fuel oil burner flame control. Use with cell RAR7 and RAR8.Use with program LEC1.
Description Ref
LAE 10 502171
Control unit
CSB.248
BO
Cont
rol u
nit
LANDIS & GYR STAEFA - SIEMENS FUEL CONTROL BOXCell
1
Description Mark Ref
QRB1A with cable L800mm for WEISHAUPT lg 65mm 1 407137QRB1A with AMP II n°9 for WEISHAUPT lg 65mm 2 407144QRB1B with AMP III for CHAPPEE - IS - BAXI Cell lg 50mm- lg 190mm 2 401061QRB1A with AMP III n°13 for WEISHAUPT lg 65mm 3 407143QRB1A for LAI - LAB- LAC - LOA - and LAL1 Ø9 mm 4 502221QRB1A A068B70B 4 502025QRB1B A048B70B 4 502026QRB1B A068B70B 4 502027QRB1B D022X20B 4 502029QRB1B D025B40B 4 502031
5 6 7
8 9Description Mark Ref
QRB1B A148B70B - 502226QRB1B high sensibility 5 502222QRB1B wire 1,50 m 6 502224QRC1 UV sensitive.Use with boxes ref: LOA & LMO (except LOA 25 & LOA 28) 7 502235
QRB1B specifi c CUENOD and ELCO 8 502223QRB1B 4MST with AMP II for KORTING 9 502225QRC1.A1.170C27A 7 502234
10 11 12
Description Mark Ref
QRB1B C036B40A 13 502028QRB1B 4MST with AMP II for WEISHAUPT Lg 56 mm 10 407011QRB1B with AMP III n°13 for WEISHAUPT Lg 65 mm 10 407043QRB3 for LAI - LAB - LAL1 - LOA - LAC - LAE 11 502230RAR7 selenium cell replaces RAR2 12 see 502261
RAR8 selenium cell replaces RAR3 12 see 502261
RAR9 Cell 12 502261
BASE
1 2Description Mark Ref
AGK 86.10A27 for Weishaupt WG30 2 407086AGK4 104.13450 for LAE 10 - LAI - LAB - LF1 - LFM height 20 mm 1 502350AGK4 104.90250 for LAI - LAB - LF1 - LFM - height 27 mm 1 502351
2 3 4
13
BASE
1 2Description Mark Ref
AGK11 for LOA - LGA - LMO 2 502352AGK85.22A27 for WEISHAUPT 2 502355AGM410.490500 for LAL 1 502367AGM16 for LOK16 - 502354
ADAPTER KF type
Allows the replacement of old control boxes without re-wiring LAI - LAB - LAC LFA - LFB - LFi - LFM
Description Ref
KF 8819 in replacement of LAI et LAB by LOA 502370KF 8826 in replacement of LAL 12.1 by LOA 24 (MONARCH) QRB1 407300KF 8852 in replacement of LFI 7 by LGB 502378KF 8880 in replacement of LFM by LGB2(burner with fan) 502360KF 8862 in replacement of LFM by LB41 (atmospheric burner) 502381IMPORTANT : Fix these adapters between the new box and the old box base
CONTROL BOX TESTERLANDIS & GYR - STAEFA - SIEMENS KF 8840 type
The fixed adapter, located between the base and the box, indicates the activa-tion program, and at the same time measures the voltage control through the pin plugs. There are 2 measuring sockets to control the flame signal and one simulation selector
Description Ref
KF 8840 TESTER 502199
LAI / LAB / RBQ REPLACEMENT INDEXThe adapters are necessary when out- of -production security boxes need to be replaced.The new KITS, are easy to fix and avoid the replacement of the base ; they are designed to keep the same height position.When a replacement is needed, a wiring modification may be necessary : the instructions are then provided.
OLD RELAY ADAPTATION KIT
RefType New Relay Primary all Adapter
Cell
with noneLAI 1/2/4 - LAB 16.3 type 01
LOA 24 QRB1/3 KF 8819 - X 502062LAI 12 type 01 LOA 24 QRB1/3 KF 8826 - X LAI 12.1 LOA 24 QRB1/3 KF 8826 - X LAB 1 LOA 44 QRB1/3 KF 8819 - X 502063LAB 15 / 15.1 LOA 44 QRB1/3 KF 8819 - X 502063LAB 16.3 type 3 LOA 44 QRB1/3 KF 8819 X 502063RBQ 31 / 34 LAL 1.25 QRB3 re-wire - - - RBQ 33 LAL 1.25 QRB3 re-wire - - -
Control unit
CSB.249
Cont
rol u
nit
BO
LAI / LAB by LOA type REPLACEMENT KIT
LOA 21 & LOA 22 , have been stopped in january. 1997.Those are replaced by ref: LOA 24 ,CE conform.
Description for Replacement KIT Composition Ref
KIT LAILAI 1 / LAI2 / LAI 2.2/ LAI 4 /LAB 16.3 type 01
LOA 24 + KF 8819no cell replacement 502062
KIT LABLAB 1/ LAB15 /15.1
LAB 16.3 type 03LOA 44 + KF 8819no cell replacement 502063
LANDIS & GYR STAEFA - SIEMENS FUEL CONTROL BOXLAC 1/2/3 REPLACEMENT INDEXThe adapters are necessary when out-of-production security boxes need to be replaced.The new KITS, are easy to fix and avoid the replacement of the base ; they are designed to keep the same height position.When a replacement is needed, a wiring modification may be necessary : the instructions are then provided.
Old boxADAPTATION KIT
Replaced by Primary all Adapter
Characteristic : -
LAC 1.013 LAL 2.14 QRB1 -
LAC 1.025 LAL 1.25 QRB1 -
LAC 1.035 LAL 1.25 QRB1 -
Characteristic : QRB1 & QRB3 are used according to burner type.
LAC 1.125 LAL 2.65 QRB1/3 -
LAC 2.013 LAL 2.14 QRB1 -
LAC 2.025 LAL 1.25 QRB1 -
LAC 2.035 LAL 1.25 QRB1 -
Characteristic : QRB1 & QRB3 are used according to burner type.
LAC 2.125 LAL 2.65 QRB1/3 KF 8808
Characteristic : -
LAC 3.013 LAL 2.14 QRB1 KF 8810
Characteristic : If there is any control connection to screw 8 or 14, replace the LAC3 with a LAL 2.25 type.
LAC 3.025 LAL 1.25 QRB1 KF 8810
Characteristic : If there is any control connection to screw 8 or 14, replace the LAC3 with a LAL 2.25 type.
LAC 3.035 LAL 1.25 QRB1 KF 8810
Characteristic : QRB1 & QRB3 are used according to burner type.
LAC 3.125 LAL 2.65 QRB1/3 KF 8808
RAQ / RAI / LAB10 REPLACEMENT INDEXOUT OF PRODUCTION boxes. Base re-wiring and a new cell are necessary
Old box Replaced by Cell
RAQ 15.1 LAE 1/1 355 RAR 7/8/9
RAQ 15.2 LAE 1/1 355 RAR 7/8/9
RAQ 15.3 LAE 1/1 355 RAR 7/8/9
RAQ 10.1/2 LAE 10 RAR 7/8/9
RAI 20 LAE 10 RAR 7/8/9
RAI 15.1 LAE 1/1 355 RAR 7/8/9
RAI 15.3d LAE 1/1 355 RAR 7/8/9
RAQ 15.4d LAE 1/1 355 RAR 7/8/9
LAB 10 LAE 10 RAR 7/8/9
LANDIS & GYR STAEFA - SIEMENS MIXED CONTROL BOX
MIXED LEC type
Scheduler for double monitoring with detector LAE 10 or LFE 10.NOTE : Adjustable preventilation from 8“ to 63“.Total Preventilation time + post-ventilation can not exceed 90“ (when Preventilation = 8“, post-ventilation = 82“ etc...)
TypePre-
PurgePre-
IgnitionPost-
IgnitionSafety Time Ref
LEC 1/8 853 30" 3" - 5" 502173
MIXED LFE10 type
Blue flame detector used for fuel or gas. Link with LEC program.
Description Ref
LFE 10 502170
BASE
1Description Mark Ref
AGG4 104.1713 (AE) 1 502364AGK4 104.13450 for LFE 10 2 502350
RWA REPLACEMENT INDEXOld box Replaced by Cell
RWA2 LEC1 NONE
LANDIS & GYR STAEFA - SIEMENS GAS CONTROL BOXLFE type
TypePre-
PurgePre-
IgnitionPost
IgnitionSafety Time
Ref
LFE 50 * - - - - 502001NOTE : * Control box of flame that works with a LEC1 relay. The direction is done with a QRA50M (frontal shot) or QRA51M (side shot)
2
Control unit
CSB.250
BO
Cont
rol u
nit
LANDIS & GYR STAEFA - SIEMENS GAS CONTROL BOXLFI 7 / LFM 1 type
LFI relay provides automatic activation and monitoring of blown air gas burner (monotube 1 firing rate). LFM relay is used for automatic control and activa-tion of gas burner (with 1 or 2 stages; with or without a fan).
TypePre-
PurgePre-
IgnitionPost
IgnitionSafety Time
Ref
Characteristic : instant steam generator LFI 7-13 8" 0,5" 3" 3"Characteristic : -LFI 7-33 30" 0,5" 3" 3"Characteristic : atmospheric burnerLFI 7-35 30" 0,5" 5" 5"Characteristic : ignition spark controlLFM 1-33F 30" 0,5" 3" 3"Characteristic : atmospheric burnerLFM 1-35 30" 0,5" 5" 5"
LFL type
Flame control by UV or ionization
Type Pre Purge Pre Ignition Post-
Ignition Safety Time
Ref
Characteristic : steam generator LFL 1.122 14" 4" 2" 2" 502107Characteristic : - LFL 1.133 14" 4" 3" 3" 502004Characteristic : 2 ionization sensors possible LFL 1.148 14" 2" 4" 4" 502112Characteristic : burner 1 or 2 tubes 3 fi ring rates remote control release + air damper ionization or UV LFL 1.322 37,5" 4"/2" 2"/4" 2"/4" 502101 LFL 1.335 37,5" 5"/2,5" 2,5"/5" 2,5"/5" 502102Characteristic : burner 1 or 2 tubes 3 fi ring rates remote control release + air damper ionization or UVLFL 1.622 66" 4"/2" 2"/4" 2"/4" 502110LFL 1.333 32" 6" 3" 3" 502109With spark detection by QRE1. Control by ionization or UV. Characteristic : burner 1 or 2 tubes 3 fi ring ratesremote control release+ air damper ionization or UV monitoringLFL 1.622F 66" 4"/2" 2"/4" 2"/4" 502103Characteristic : -LFL 1.322F 37,5" 4"/2" 2"/4" 2"/4" 502104Characteristic : gas and mixedLFL 1.635 67,5" 5"/2,5" 2,5" 2,5" 502106
LGB 21 / 22 / 41 typeBox for small or medium power gas burners, with orwithout a fan. Flame monitoring by ionization sensor or UV sensor. Lower voltage Security . Remote control release . Air pressure control when startup.When operating without any motor, it is necessary to cable on plug 3 a resistance type AGK 2500 A 27 (except for LGB41) When a LFI is replaced you must adapt the monitoring module UV A6Q2.1A27 ref 502321.
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : steam generator 2 fi ring rates
LGB 21 130A27 7" 2" 2,4" 3" 502205Characteristic : 2 fi ring rates
LGB 21 330A27 30" 2" 2,4" 3" 502177LGB 21 350A27 30" 2" 4" 5" 502206
see replacementindex page CSB.252
LGB 21 / 22 / 41 type (continuation)
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : -LGB 21 550A27 - - - - 502024
Characteristic : 2 fi ring progressive ratesLGB 22 330A27 30" 3" 2,4" 3" 502178Characteristic : BENTONELGB 22 230B27 - - - - 502182
Characteristic : 2 fi ring rates /atmospheric burnerLGB 41 258A27 18" 2" 4" 5" 502179
NOTE : For the startup with ignition spark control use QRE1 for LGB 21/22 and 41.
LGC 22 type
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : Box for wall unit gas boilerspecifi c to BROTJE (270961) LGC 22 002C271 1,5" - - 10" 502180
LGK type
LGK 16.622A27 self-controled detection circuit, linked to a ionization sensor or UV cell like QRA 53/55 ; same program as LFL boxesNOTE : LGK 16 Necessary for self or remote heating plant. It replaces the LFL relay.
Description Ref
LGK 16.622A27 502060LGK 16.322A27 502113LGK 16.635A27 502114
LME type
Can replace LGB and LMG boxes and detect any defect (blinking reset button) When operating with UV sensor, you must use a control module (AGQ3 Ref 502323)
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : defect box detectionLME 11 330A2 30" 2" - 3" 502010Characteristic : defect box detection replaces LGB 21.130A27 and LMG 21.130B27LME 21 120A2 7" 2" - 3" 502011Characteristic : defect box detection replaces LGB 21.230A27 and LMG 21.230B27LME 21 230A2 20" 3" - 3" 502012Characteristic : defect box detection replaces LGB 21.330A27 and LMG 21.330B27LME 21 33A2 30" 2" - 3" 502013Characteristic : defect box detection LGB 21.350A27 et LMG21.350B27LME 21 35A2 30" 2" - 5" 502014
Control unit
CSB.251
Cont
rol u
nit
BO
LME type (continuation)
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : defect box detection replaces LGB 21.550A27 and LMG 21.550B27
LME 21 55A2 50" 2" - 5" 502015Characteristic : defect box detection replaces LGB 22.130A27 and LMG 22.130B27
LME 22 131A2 50" 3" - 3" 502016Characteristic : defect box detection replaces LGB 22.230A27 and LMG 22.230B27
LME 22 232A2 20" 3" - 3" 502017Characteristic : defect box detection replaces LMG 22.330B27
LME 22 233A2 20" 3" - 3" 502018Characteristic : defect box detection replaces LGB 22.330A27
LME 22 331A2 30" 3" - 3" 502019Characteristic : defect box detection replaces LGB 32.330A27
LME 23 331A2 30" 1" - 5" 502020Characteristic : defect box detection replaces LGB 32.350A27
LME 23 351A2 30" 1" - 5" 502021Characteristic : defect box detection replaces LGB 41.255A27
LME 44 056A2 9" 2" - 5" 502022Characteristic : defect box detection replaces LGB 41.258A27
LME 44 057A2 9" 2" - 5" 502023
LMG/ LMO typeThese control boxes can replace the LGB types(the detection and defect analysis).It uses reset switches that blink.example : � flame detection defect - 2 blinks � pressure air defect - 3 blinksThe analysis is stored even when device is off.When operating without any motor, it is necessary to cable on plug 3 a resis-tance type AGK 2500 A 27 (except for LGB41)when a LFI is replaced you must adapt the monitoring module UV A6Q2.1A27 ref 502321.
TypePre-
PurgePre-
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : defect box detection
LMG 21 230A27 20" 2" - 3" See 502012
LMG 21 330B27 30" 2" - 3" See 502019
LMG 22 330A27 30" 3" - 3" See 502019
LMG 22 233A27 20" 3" - 3" See 502018
Characteristic : Limp mixed gas and fuel for Weishaupt
LMO 82 100C2WH - - - 3" 407024
Cell
1
Description Mark Ref
QRA 2 UV detection cell for gas or mixed burner RED SPOT 2 502310
QRA 2M UV detection cell, same application, high sensitivity GREEN SPOT - 502311
QRA 10C UV Cell - 502308QRA 10MC UV high sensitivity cell - 502309QRA 55 UV Cell of 70 mm for LGK 16 1 502320QRA 50M UV Cell 3 502002QRA 51M UV Cell 4 502003
3 42
LAMP / REPLACEMENT BULB
Description Ref
UV LAMP standard for QRA ref AGR 45 02 11310 502313UV LAMP high sensitivity ref AGR 45 02 0650M 502314
BASE
1Description Mark Ref
AGG4 104.1713 (LFE1) - 502362AGK11 for LOA - LGA - LMO 1 502352AGK 4101 13450 for LFI - LFE10 - LFM - LAE 10 2 502350AGK 4101 90250 same base for these different models height 27 mm instead of 20 mm - 502351LGK16 BASE AGM17 3 502356LFL BASE 4104 0550 - 502366AGK85.22A27 for Weishaupt - 502355
KF ADAPTER
Description Ref
KF 8852 in replacement of LFI 7 by LGB 502378KF 8853K in replacement of LFI 7 by LGB22 502361KF 8880 in replacement of LFM by LGB 2 502360KF 8862 in replacement of LFM by LGB 41 502381
SPARK DETECTORQRE 1 spark ignition electronical detector. Used on burner controlled by ionization whose light fl ow is higher than 15% of the nominal capacity
Description RefQRE 1 see 502032QRE1 150 502032
RC CIRCUITEssential when LFI / LFM et LGA- LGB - LMG are connected to 220V mono electric supply (between 2 phases).
Description Ref
RC circuit 502316
UV MONITORING MODULEAGQ1.1A27 for relay type LGB... LMGAdditional module for gas burner flame monitoring with UV sensor type QRA...Under base assembly.
Description Ref
AGQ1.1A27 for relay type LGB... LMG 502321AGQ3.1A27 for relay type LME 502323
2 3
Control unit
CSB.252
BO
Cont
rol u
nit
LANDIS & GYR STAEFA - SIEMENS GAS CONTROL BOX LFG / LFI / LFM REPLACEMENT INDEXNot necessary to rewire, when replacing
Type Replaced by Primary cell Adapter noneCharacteristic : -
LFG 1.33 LGB21 330A27orLMG21 330A27
502177 or 502007 502350 X
LFI 713 LGB 21 130A27 Io KF8852 X
LFI 733 LGB 21 330A27 orLMG 21 330A27 Io KF8852 X
LFI 735 LGB 21 330A27 Io KF8852 XCharacteristic : Check that terminal 4 stays connected to the old baseFor UV type, add module AGQ ref Diff 502321LFM 1.33 LFM 1.33F LFM1.35
LGB 21 330A27 orLMG 21 330A27 Io/UV
KF8880except
CUENODX
LFM 1.35 LGB 21 350A27 orLGB 22 330A27 orLMG22 330A27
Io/UV KF8880 X
Characteristic : Check that terminal 4 stays connected to the old base.Replacements for atmospheric burners LFM 1.33 LFM 1.33F LFM1.35
LGB 41 258A27 Io KF8862 X
LFC / LFI REPLACEMENT INDEXOLD BOX ADAPTATION KIT
Type Replaced byPrimary
cellAdapter
Cellwith none
Characteristic : -LFC 1.1 LGA 41 173A 27 Sensor Io - - XLFI 5.19 type 02 LGA 41 173A 27 Sensor Io - - XCharacteristic : without ventilator 1 fi ring rateLFI 1 série 02 LGA 41 173A 27 Sensor Io - - XCharacteristic : without ventilator 2 fi ring ratesLFI 1 série 02 LGA 52 150A 27 Sensor Io - - X
LFA / LFB / REPLACEMENT INDEXOLD BOX ADAPTATION KIT
Type Replaced byPrimary
cellAdapter
Cellwith none
Characteristic : when ignition spark detected, use boxes type F+QRE Ref 502315
LFA 2.12LFL 1.122 type 02
Io - - X
Characteristic : (1) when ignition spark detected, use boxes type F+QRE Ref 502315(2) LFA ionization fl ame monitoring(3) LFB UV fl ame monitoringLFA (2) or LFB (3)1.32/ 1.322 (1)2.32 /2.322 (1)
LFL 1.322type 02
Io or UV - - X
4.32/ 4.322 (1) - - XLFA (2) or LFB (3)1.33/ 1.355 2.33/ 2.355 LFL 1.335
type 01Io or UV
- - X
4.33/ 4.355 (1) - - -
LFA (2) or LFB (3)1.62/ 1.622 (1)2.62/ 2.622 (1)
LFL 1.622type 02
Io or UV - - X
4.62/ 4.622 (1) - - XLFA (2) or LFB (3)1.63/ 1.635 2.63/ 2.695
LFL 1.635type 01
Io or UV - - X
LFD REPLACEMENT INDEXType Replaced by Ref
Base for re-wiring ref
Cell
Characteristic :(1) use these models for atmospheric burnersLFD 1.33 type 02
LFL 1.335 or LGB 41 (1)
502102 or 502179 (1)
502366 or 502350
none
LFD 2.35LFL 1.335 or LGB 41 (1)
502102 ru 502179 (1)
502366 or 502350
none
LFD 2.38LFL 1.335 or LGB 41 (1)
502102 or 502179 (1)
502366 or 502350
none
RAI / RAQ REPLACEMENT INDEXOUT OF PRODUCTION boxes. Base re-wiring and a new cell are necessary, when you take a new box.
OLD BOX Replaced by Cell
RAI 15.2 LFE 1/8 853 Io
RAI 15.1 LFE Io or QRA2
RAI 15.3d LFE Io or QRA2
RAQ 10.1 LFE 10 Io
RAI 20 LFE 10 Io or QRA
LDU type CONTROL BOX
The Leak detector LDU11 is designed for double shuttingsgas installations .After each activation cycle, the box programs automatically the seal control, and prevents the burner to start in case of internal leakage
Description Ref
LDU 11 523A27 type 220 volts 502111
PACTROL CONTROL BOXP14 type
Description Ref
P14 110 AL for radiant gas (selfcontrol gas) 443010
P16 type
Range of Control boxes, completely automatic, for atmospheric or air (forced up to 60 kw) burners. The case includes an ignition generator and a single or double electrode .The range of PACTROL P16 controls alternatively the ignition and the flame for burners up to 60 Kw (forced air) or above. Supplied without base.
TypePre
PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : 1 fi ring rate
P16C /FL402801 - 6"-12" - 5" see 448005
Characteristic : 2 fi ring rates
P16D /402901 - 6"-12" - 5"-10" 448005P16DI /400601 - 6"-12" - 5"-10" 448001P16DI / S (NF)400601/V03
- 6"-12" - 5" 448002
P16FI (CE)406203 - 30" - 5" 448007P16 HIJ 409701 - 10" - 20" 448010Characteristic : -
P16B 402701 - - see 448009
P16 AFT - - 448014
Control unit
CSB.253
Cont
rol u
nit
BO
CFR - CSS - CSA type
Type Pre Purge Pre IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : -CSS 01-24R/E 20" - - 7" 448050Characteristic : 2 electrodes ignition and detectionCSS01.12 9" - - 12" 448064Characteristic : same electrode ignition and detectionCSS01-12SJV11 9" - - 12" 448062Characteristic : -CSS01-24JV03 30" - - 24" 448063CSA 12 10" - - 12" 448065CSA 6 10" - - 6" 448066
CONNECTOR
Description Ref
CONNECTOR 10 terminals for P16 448012CONNECTOR 12 terminals for P16 448013
BASE
Description Ref
Base for box CSS01.24 448051
APPLICATION INDEXType Manufacturer
P 16 A / FL 402601 SOLARONICS
P 16 C / FL 402801 FERROLI (NEF) / SOLARONICS / SOLARTUBE/DIFOTHERM
P 16 D / FL 402901 SPAO RAY/FADIME / LAIDETP 16 DI / FL 400601 SCHWANKP 16 DIA / FL 400601 / V07 GENERFEU/KUBBLER
P 16 DI /S (NF) 400601/ V03 GAZ INDUSTRIE / EMAT / DIFOTHERM/FADIME/AIRGARRY/JETTO
P 16 FI (CE) 406203 BABCOCK / AIRCALOP 16 402701 EMATP 16 FIS 406203 / V01 (CE) AIRCALOP 16 H 403402 BABCOCK / SCHWANKP 16 HI - J 409701 SCHWANK / BABCOCKCSS 01 - 24 RE REZNOR / CIATCFR V 401400 -P 14 110 AL GENERFEUCSS 01 - 12 GENERFEUCSS 01 - 12 SJV 11 ETACSS 01 - 24 JV 03 HAMWORTHY / POWELL DUFFRYNCSA 12 SARGICSA 6 SARGI / SMITH INDUSTRIE
RIELLO FUEL CONTROL BOXACCESSORIES for 480 SE
1
Description Mark Ref
Replacement kit / cell 300 5737 1 404185Spare plug for replacement kit 2 404890
503 SE type
NOTE : The RMO 503 SE (new model) with its release button replaces the 503SE, but not the old version of the 502SE.
Type CellPre
PurgePre
IgnitionPost
IgnitionSafety Time
Manufactu-rer ref.
Ref
503SE 2 + 3 34" 8" 7" 5" 300.1150 404062
483/520/522 RBO/530/531 SE/535 RSE type
1
Type CellPre
PurgeSafety Time
Manufacturer ref.
Mark Ref
483 SE* 3 10" 5" see 530 SE - 520 SE** 3 6" 4" 300.1132 Mectron
Four 1 404071
530 SE 3 10" 10" 300.1156 replaces 483 SE 404894
531 SE 3 10" 10"300.1158
for burner with preheater
404895
522 RBO 3 10" 10" 300.3896 for RL28 to 190 burner 2 404021
535 RSE - - -300.8652 for burner
with preheater 404025
* replacement of 483 SE by 530 SE , except when delay timer on 483 SE is out of order (531 SE with Base in that case.)** Replacement box kit + coil
550 / 552 / 553 SE type
Control box for blue flame burner (Gulliver BLU BG1).
Type CellPre
Purge
Pre Igni-tion
Post Igni-tion
Safety Time
Manufac-turer ref.
Ref
550SE =550 SMD *
IRD 5" - - - 300.1168 404640552SE - 8" - - - 300.1174 404265553SE - - - - - 300.1175 404638555SE - - - - - 300.8850 404024* A wiring modification is sometimes necessary.
2
2
Control unit
CSB.254
BO
Cont
rol u
nit
RIELLO FUEL CONTROL BOXCELL
1
4 5
7
Description Mark Ref
Replacement kit of Cell 300 5737 1 404185Spare plug for replacement KIT 2 404890Cell 300 2280 for 483/530/531 SE /520 5 404891Cell 300 7839 for 552 / 553 SE 3 404639Cell 300 7492 for 550 SE 4 404637Cell 300.8646 for 535 SE 6 404088MZ770S Cell 300.2548 7 404098
BASE
1 2Description Mark Ref
BASE 300 2256 for 502/503/505/506/508 SE 1 404061BASE 300 2278 for 483/520/530 SE 2 404889BASE 300 2310 for 531 SE 2 404896
DELAY TIMER
Description Ref
Delay timer 300 2301 G20D 404641
RIELLO GAS CONTROL BOX505 - 506 - 508 SE type
The RMG 508SE with its release button replaces the 508SE, but not the old version of the 505 + 506SE NOTE : Wiring modification supplied with the box
Type CellPre
Purge
Pre Igni-tion
Post Igni-tion
Safety Time
Manufacturer ref.
Ref
508SE Ionizat. 38" - 2,5" 3" 300.1138 404067
509SE ionizat. 35" - 2,5" 3" 300.1139 for FS 10/15/20 404019
2 3
6
525 SE / RMG 88 type
Type Cell Pre Purge
Pre Igni-tion
Post Igni-tion
Safety Time
Manufac-turer ref. Ref
525SE Io 30" - - 5" 300.1164 404068RMG88.62A2 - - - - 3" 301 3073 404268
566 / 568 SE / MG 569 typeBlue flame, oil burner control box (GULLIVER BLU BS 1/2/3/4)
Type Cell Pre Purge
Pre Igni-tion
Post Igni-tion
Safety Time
Manufac-turer ref. Ref
MG 569 replaced 568SE and 566SEIoniza-tion - - - - 300.1176 404020
BASE
1 2
Description Mark Ref
BASE 300 2256 for 505 /506 / 508 1 404061BASE 300 2307 for 525 2 404069
RV GAS CONTROL BOX05 type
Description Ref
Model 05125001 for EMAT (RS22) replaced by P16DIS 448002Model 0514 for SOLARONICS (SR21/31/41/42/62/82) 453005Model 05125004 for SOLARONICS/TRATHERM/RENDAMAX replaced model 05125002 and 05125003 453009
SATRONIC FUEL CONTROL BOXTF type
Pull-out equipment for oil burner control and security . Flame monitoring byphoto-resistant cell .
Type Pre Purge Pre IgnitionPost-
IgnitionSafety Tme Ref
Characteristic : 1 fi ring rate - Replaces TF 701 on 1 fi ring rate burners
TF 801 12" 12" 20" 10" 507005Characteristic : 2 fi ring rates same for 2 fi ring rates burners.
TF 802 12" 12" 20" 10" 507006
Control unit
CSB.255
Cont
rol u
nit
BO
TF type(continuation)
Type Pre Purge Pre IgnitionPost-
IgnitionSafety Tme Ref
Characteristic : 2 fi ring rates.
TF 804 12" 12" 3" - 5" 10" 507007Characteristic : With amplifi er of the detection circuit. Replaces without changing the base the TF 730 with an extension cable for the release button.
TF 830 12" 12" 18" 10" 507051Characteristic : . 220/240V -50Hz 5VA for ECOFLAM
TF 830.3 10" 10" 10" 10" 507064 TF 974 10" 10" 10" 10" 507016Characteristic : 2 fi ring rates.
TF 832 12" 12" 24" 10" 507053 TF 840 12" 12" 5" 10" 507054Characteristic : For burner with pre-heating 1 fi ring rate. Replaces without changing the base the TF 734 with an extension cable for the release button.
TF 834 12" 12" 18" 10" see507001
Characteristic : Security low voltage.
TF 834.3 12" 12" 20" 10" 507001Characteristic : Security low voltage no Post-ignition.
TF 834E.3 12" 12" - 10"see
507001
Characteristic : For burner with pre-heating 2 Firing rates.
TF 836 12" 12" 25" 10" 507050Characteristic : 1 or 2 fi ring rates.
TF 844 12" 12" 5" 10" 507057Characteristic :
TF 874 12" 12" 25" 10" 405002Note : TF700 boxes are replaced by Type 800 while adding an extension cable ref 507301 adjusting the reset switch level
TMO /TTO/MMO/DKW/DKO type
Pull-out equipment with flame monitoring by photo-resistant cell (on medium and high power burners). �Remote control release. �With or without recycling.
Type Pre PurgePre
IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : - TMO 720-4-35 30" 30" 10" 5" 507020Characteristic : 2 fi ring rates TTO 810-35 30" 30" 20" 5" (1) TTO 836-35 30" 30" 20" 5" (2)Characteristic : - TTO 872 30" 30" 20" 5" (3)Characteristic : Use with preheater TTO 876 20" 20" 4" 5" (4)Characteristic : - MMO 872 10" 23,5" 8,5" 5" (3)Characteristic : preheater MMO 876 10" 23,5" 8,5" 5" (4)Characteristic : - DKO 970 - - - - 507009 DKO 972 - - - - 507012 DKO 974 - - - - 507014 DKO 976 - - - - 507015Characteristic : Replaces TTO 810-35/ TTO 872-MMO 872 DKW 972 + prolong. 10" 23,5" 8,5" 5" 507060Characteristic : Replaces TTO 836-35/ TTO 876-MMO 876 DKW 976 + prolong. 10" 23,5" 8,5" 5" 507062
TMO /TTO/MMO/DKW/DKO typeType Pre Purge
Pre Ignition
Post-Ignition
Safety Time
Ref
Characteristic : - DKW 972 10" 23,5" 8,5" 5" 507059 DKW 976 10" 23,5" 8,5" 5" 507061Characteristic : Special CUENOD - ELCO SH 113 - - - - 406013replacement KitER1 relay - - - - see
402023replacement KitER1H relay - - - - 402023Elcopen Analyser defect - - - - 402025NOTE : DXX type boxes, have a defect detection device. The reset switch blinks in a coding type, which indicates the defect location. A pocket size terminal type SATROPEN and PC module type SATROCOM are available on request.(1) Replaced by 507060 + (MZ cell ref 507101 if FZ cell stands or detec-tor IRD1010 depending on brand or cell UVD ref 507003).(2) Replaced by 507062 + (MZ r cell ef 507101 if FZ cell stands or detec-tor IRD1010 depending on brand or cell UVD ref 507003).(3) Replaced by 507060 + (detector IRD1010 depending on brand if IRD810 or 910 or 911 stands or cell UVD ref 507003).(4) Replaced by 507062 + (IRD1010 detector depending on brand if IRD810 or 910 or 911 stands or cell UVD ref 507003).
CELL
1Description Mark Ref
* FZ 711 S OERTLI and DE DIETRICH. special box Square plug - Red side detection 1 To consult
us* FZ 711 S white Cell - side and frontal detection for TTO 910 - TMO 720 2* It is necessary to change Cell and the box
SATRONIC FUEL CONTROL BOXCELL
1 2
3 4
Description Mark RefMZ 770 S Cell reduced, to be used only with boxes TF730-1/ TF730/ 733/734 & TF 821/822/830/834/840/740.1 - Supplied with FZ transformation taper
1 507101
MZ 770 long GIERSCH 4 507102MZ 770 S long BROTJE 3 507103Sheath and joint for MZ 770 BROTJE 2 430112
SH type
Type Pre Purge Pre IgnitionPost-
IgnitionSafety Time
Ref
Characteristic : Special CUENOD - ELCOSH 213 mod C1 - - - 5" 406019
2
Control unit
CSB.256
BO
Cont
rol u
nit
IRD INFRARED DETECTORFOR FUEL
1The monitoring function follows the infrared light vibration principle.
Description Mark Ref
MAN- BUDERUS IRD 1010 white axial shot - 507339BROTJE- BALTUR IRD 1010 blue side shot 2 430412KORTING IRD 1010 blue axial shot 1 507342NOTE : IRD 810/910/911 and 820/920 are replaced by type 1010 and 1020.you must know the brand of the device to find the right IRD detector.
BASE
1 2 3
Description Mark Ref
TF 804/836/844 2 507308TF 701/730/734/801/802/830/832/834/840 / 874TTO - MMO 1 507300TMO 720 3 507310S98 for DKW/DKG/DKO/DMG - 507004
ACCESSORIES
1Description Mark Ref
Extension to fi nd the same height with ref : TF 801 & 802 and ref : TF 701 1 507301Extension specifi c to BROTJE 1 430733BROTJE Joint Cell support - 430700BROTJE Glass Cell support - 430699
FR 870 MODEL
Application : � When it’s hard to reach heating equipment. � If burner fails, diffi cult to be reactivated. � Remote control reset is a necessary.
Description RefFR 870 compatible with ref : TF 800/ TFI 800 / MMI / MMG and TTO 876 507304
2
KBR and TF REPLACEMENT INDEXOLD BOX
Replaced by
ADAPTATION KITRefAdapter Extension Cell
with noneTF20/TF21A
TF 832Base to re-wire
507300
yes507301
Use Cell MZ507101
- -TF22KBR611KBR612
KBR612ATF 832
Base to re-wire
507300
yes507301
Use Cell MZ507101
- -KBR614AKBR617A/AC
TF 740 TF 840 - -Use
Cell MZ507101
- 507023
TF 701/TF714 TF 832 - - - - 507006TF 704 TF 834 - - - - 507007
TF 721 TF 832 - -Use
Cell MZ507101
- -
TF 821TF 822 TF 832 - -
Use Cell MZ507101
- -
TF 730 TF 832 - -Use
Cell MZ507101
- -
TF 734 TF 834 - -Use
Cell MZ507101
- -
TF 740 TF 840 - - Use Cell MZ507101 - -
TMO / TTO / MMO REPLACEMENT INDEXOLD BOX Replaced by Note
TTO 750-1 DKW972 Change Cell TTO 810 model 35 DKW972 Change CellTTO 836 model 35 DKW976 Change CellTTO 872 DKW972 Change CellTTO 876 DKW976 Change CellMMO 872 DKW972 Change CellMMO 876 DKW976 Change CellTMO 720
TMO 720.4 -TMO 720.2 TMO 721
SATRONIC GAS CONTROL BOX MMI/ MMG/ DKG/ DMG/ TTG/ SG type
Pull-out equipment with flame monitoring using ionization or UV cell (for medium and high power burners). Remote control release. With or without recycling.
Type Pre Purge Pre-
Ignition Post-
Ignition Safety Time
Ref
Characteristic : 2 Firing rates ionization replace box TTI 790-33
MMI 810-33 33" 3,5" 2,5" 1" 507037Characteristic : 2 Firing rates
MMI 810-35 30" 3" - 5" 507034Characteristic : 1 or 2 Firing rates detection by ionization or IRD
MMI 811-35 30" - - 5"replaced by 507063(except Guillot)
Characteristic : 1 Firing rate ionization with air fl ap control
MMI 812-33MMI 812-23
63" 3,5" 2,5" 1"replaced by 507033
Control unit
CSB.257
Cont
rol u
nit
BO
Type Pre Purge Pre-
Ignition Post-
Ignition Safety Time
Ref
Characteristic : 2 Firing rate ionization with air fl ap control
MMI 813.1 mod 23
63" 3,5" 2,5" 1" 507042
Characteristic : -
MMI 815 mod 5MMI 815 mod 10
- - - 5"or 10"replaced by507049
Characteristic : 1 Firing rate ionization with air fl ap control
MMI 962-23 63" 3,5“ 2,5" 1" 507033Characteristic : 2 Firing rates replaces without changingthe base the TTG 760-33 with an extension cable for the reset switch
MMG 810-33 30" - 3" 5" 507056Characteristic : 2 Firing rates
MMG 811-63 57" 3" 2,5" 3" 507058Characteristic : replaces box MMI 811 mod. 35
DMG971 - 24" - 3"507063
(except Guillot)
Characteristic : replaces box MMG 810-33
TTG 760-33 30" - 3" 3"replaced by507056
Characteristic : with control of parasite light and 2 Firing rates
TTG 760 FN 60" - 3" 3" replaced by507058
Characteristic : -
DKG 972 - - - 10“ 507049DKG 972 mod 21
- - - 21" 507065
Characteristic : Special CUENOD - ELCO
SG 113 - - - - 406009SG 513 - - - - 406020Kit replacement relay EM41
- - - - 402024
Elcopen Analy-ser defect
- - - - 402025
NOTE : DXX type boxes have a defect detection device. The reset switch blinks in a coding type, which indicates the defect location. A pocket size terminal type SATROPEN and a PC module type SATROCOM are availableon request.
TFI / DKG type
Pull-out equipment with flame monitoring using ionization or UV cell (for medium and high power burners). Remote control release. With or without recycling.
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : Special for REZNOR TFI 812-2 mod 10E
- - - 10"replaced by 507049
Characteristic : - DKG 972 - - - 10" 507049Characteristic : for atmospheric gas burner 2 fi ring ratesreplaces box TFI 712-10. For remote control reset use FR 870 ref 507304. TFI 812-2 maxi 120 Kw mod 10
-- 10" non 10" 507043Characteristic : for atmospheric gas burner 2 fi ring ratesreplaces box TFI 712 without changing the base ; with an exten-sion cable for reset switch. TFI 812-2 maxi 350 Kw mod 5
- 15" - 5" 507041
NOTE : DXX type boxes, have a defect detection device. The reset switch blinks in a coding type, which indicates the defect location. A pocket size terminal type SATROPEN and PC module type SATROCOM are availableon request
TTG type
Type Pre Purge Pre Igni-
tion Post-
Ignition Safety Time
Ref
Characteristic : replaced by MMG 810-33
TTG 760-33 30" - 3" 3"replaced by507056
Characteristic : with control of parasite light and 2 fi ring rates.
TTG 760 FN 60" - 3" 3" replaced by 507058
TMG typeProgrammable control box and ionization flame monitoring .Designed for gas burner models, the TMG can be used with a UV sensor on fuel-oil burner equipment.
Type Pre
Purge Pre
Ignition Post-
Ignition Safety Time
Ref
Characteristic : for fuel-oil and gas burner (2 Firing rates)TMG 740.3 model 32-32replaces TMG740.2 model 32-32
30" 3" - 2" 507032
TMG 740.3 model 43-35replaces TMG740.2 model 45-54
30" 3" 5" 5" 507039
FFW type to REPLACE FRA - FRU DANFOSSFor Atmospheric, ventilated, fuel or gas burner � For semi-automatic installation. � Flame formation delay : 1 second. � Flame safety time delay : 1 second.Control by Ionization or cell UVZ or infrared detector IRD 1020.
Description Ref
FFW 930 FUEL - GAS 507320
SATRONIC GAS CONTROL BOX CELL
Description Ref
UVZ 780 red spot - UV fl ame control cell for MMG 810 and 811 507111UVZ 780 white spot - UV fl ame control cell for TMG 740-2 and 740-3 +TTG 507112
UV DETECTION LAMP
Description Ref
SYLVANIA UV detection Lamp P607.08 Ø 22mm - 4 pin plugs 502312
Control unit
CSB.258
BO
Cont
rol u
nit
IRD INFRARED DETECTOR
For Gas The monitoring function follows the infrared light vibration principle
Description RefOLYMP -HG-HLG IRD 1020 BLEUE side shot ( IRD 920 replacement with IRD 1020 needs a M93 support) 507341
NOTE : IRD 810/910/911 and 820/920 are replaced by type 1010 and 1020. you must know the brand of the device to find the right IRD detector.
ACCESSORIES
1
Description Mark Ref
M93 Magnetic support for IRD 1020 - 507350ZT 870 Transformer 1 805913AZ 5 Burner 2 708790
BASE
1The extension for TFI is used to adjust the height on the old boxes (The new ones are lower)
Description Mark Ref
TMG 740 1 507307TTG - FN - MMI 811/ 812 - MMG 811/ 812 - TTG - TTI MMI 810 - MMG 810- TTI 790 - TF 804 /836/844 - 507308
TFI/TMG740 3 507300DKG/DMG/DKO - 507004Extension TFI 812 2 507301Extension specifi c BROTJE - 430733
IBR - BR - GBR - TTG TFI - MMI - TMA - TMG TTI REPLACEMENT INDEX
OLD BOX Kit or replacement box RefReplaced by Adapter
IBR 661 TME 780 (on request)
Base to re-wire (esti-mat request)
cell to change (UVZE est req.)
-
BR 661 TMG 740-3 (Ref 507032)
Base to re-wire (ref 507302) cell to
change (ref 507112)-
GBR 681 or GBR 681/74
MMI 810.33 (Ref 507037)
Base to re-wire (Ref 507308) -
TTG 760.33 MMG 810 mod 33
Terminal 1 and 9 rewire on base 507056
TTG 760 FN MMG 811 mod 63 - 507058
TFI 712F-1 /TFI 712FTFI 812-1 mod 5 TFI 812-2 mod 5 Provide switch exten-
tion 507301 507041TFI 712-1 /TFI 712TFI 812-1 mod 10
TFI 812-2 mod 10
Provide switch exten-tion 507301 507043
TFI 812-2 mod 10E DKG 972 - 507049MMI 810 mod 32 MMI 810.33 - 507037
MMI 811 mod 35 DMG 971 Caution: pressure
switch wiringto terminals 4 and 7
507063(except Guillot)
2
2 3
IBR - BR - GBR - TTG TFI - MMI - TMA - TMG TTI REPLACEMENT INDEX (continuation)
OLD BOX Kit or replacement box RefReplaced by Adapter
MMI 812 mod 23 MMI 812 mod 33MMI 812-1 mod 23MMI 812 mod 63
MMI 962-1 mod23 - 507033
MMI 815 mod 5MMI 815 mod 10 DKG 972 - 507049TMG 720 /TMG 740 TMG 740-1
TMG 740-3 mod 32-32 - 507032
TMG 740-2 mod 45-54
TMG 740-3 mod 43-35 - 507039
TTI 790-33 MMI 810-33 terminal 1 & 9 rewire on Base 507037
SIT GAS CONTROL BOX503 and 537 type
Type Pre Purge Pre
Ignition Post-
Ignition Safety Time Ref
Characteristic : RIELLO - SEET0.503.902 - - - - 503008Characteristic : WOLF - DE DIETRICH0.503.501 - - - - 503009Characteristic : BALTUR - ARIANE - SIME - HERMANN - UNICAL 0.537.301 type DMT 1,5" - - 10" 431015Characteristic : BENESSERE - PRONTACQUE SALVASPAZIO BERETTA - RIELLO0.537.002 type DMT 1,5" - - 7,5“ 404026Characteristic : DOMUSA (CGAS 000130)0.537.201 - - - - 503010
Characteristic : -0.537.501 - - - - 503011
577 typeType Pre Purge
Pre Ignition
Post-Ignition
Safety Time Ref
Characteristic : GAZ INDUSTRIE
0.577.503 30" - - 30" 471003Characteristic : GAZ INDUSTRIE - BIASI
0.577.504 5" - - 30" 503001Characteristic : ACV
0.577.009 - - - 5" 503002Characteristic : EMAT
0.577.308 - - - 5" 503003Characteristic : SAUNIER - UNICAL
0.577.311 1,5" - - 10" 503004Characteristic : OERTLI - DE DIETRICH
0.577.211 - - - 55" 503005Characteristic : DE DIETRICH
0;577.705 - - - 10" 503006Characteristic : SAUNIER
0.577.304 1,5" - - 10" 503007Characteristic : DE DIETRICH
0.577.702 - - - - 5030120.577.701 - - - - 503013
Control unit
CSB.259
Cont
rol u
nit
BO
STANDARD INSULATION TRANSFORMERFEATURES :
� IN : 220- 240V OUT : 260-280V � 50 -60 HZ � Power : 20VA � Connection : Terminal faston 6,35 mm
Sizes Fixation Entraxe
L l H F E G HT
64 54 52 72 44 - -
Description Ref
INSULATION TRANSFORMER 805961NOTE : To increase and regulate the ionization sensor signal
USE: To increase and regulate the ionization sensor signal in control box installa-tions which are not earthed neutral wired.
APPLICATION :The ionization sensor wire comes from the control box, goes through the isola-tion transformer secondary and returns to the sensor. The isolation transformer primary is supplied through the same supply as the control box..
Note: be careful this transformer is a primary and secondary transformer. The fact of using the primary and the secondary is harmful.
MICROAMMETER type MAP portable
USE � The micro Ammeter MAP measures the very low intensity of the ionization and UV cell current for fuel blue fl ame burners with ionization sensor. � Checks functionning state of fl ame detection : �By ionization (burner with electrode) �By UV cell � Measurement -10µA / 0 / +10µA, -50µA/ 0 /-50µA ou -100µA / 0 / -100µA (according to the selected model). Its zero allows measurement even if the wires are commutated.
A micro Ammeter is installed in series (on the same line as the probe or the cell to be measured).
Description Ref
MAP -10/0/+10µA Size : L 140 x H 85 x E 55 mm 906567MAP -50/0/+50µA Size : L 140 x H 85 x E 45 mm 906565MAP -100/0/+100µA Size : L 140 x H 85 x E 55 mm 906562
IONIZATION CURRENT MONITORING - RC MODULE
Improves the value of the ionization current when, in the electric feeder systems, the zero lead has a weak potential difference with the mass of the burner. Bipolar connection between the zero lead and the mass of the burner. � Size : L 25 x P10 x H 18m
Description Ref
Module RC model ARC4 66890660 502316
VARIOUS AMP and MULTICONTACT CONNECTOR
12
3 4
Description Mark Ref
With 3 wires cable 0,40 m for RAPA valve, SUNTEC, DANFOSS Electrovalve 3 803030
With 3 wires cable 0,40 m for RAPA valve, SUNTEC, DANFOSS Electrovalve 3 803034
With 3 wires cable 0,80 m for RAPA valve, SUNTEC, DANFOSS Electrovalve 3 803029
With 3 wires cable for ELCO, CUENOD ignition transformer 3 803031
Straight male 3 pin plugs 4 803032Straight female 3 pin plugs 1 803033Cable with connector for preheater 2 see 803036
Angle connector Female 3 pin plugs 1 470003
DOUBLE CONNECTOR
Description Ref
Double contact connector WEISHAUPT - connector DIN 407100
x 6
x 6
x 6
x 1
Control unit
CSB.260
BO
Cont
rol u
nit
DOUBLE CONNECTORWIELAND type1
2Many burners are connected with a 6 male poles plug. The same piece can be connected between different installation equipment such as the circulator, and the regulation and control board. For the 6 poles plug, we choose the locking type. Anyway, the 2 parts stay pluggable, with or without a locking system.
Description Mark Ref
Male 3 poles 2 803050Female 3 poles 2 803051Male 4 poles - 803040Female 4 poles - 803041Male 5 poles - 803010Female 5 poles - 803011Male 6 poles 1 803001Female 6 poles 1 803002Male 7 poles - 803020Female 7 poles - 803021
PRE-WIRED BASEBROTJE
Type Characteristic Manufacturer ref Ref
0.501 M for ESB 24-28 521185 4303740.501 M for ESB 32-41 521192 -0.30U for EB-U 17-25 533577 4303680.32U Blue Jet
533577430368
0.32.1 - 0.31.1 - 0.30.1 4303680.501 M for DU 19 539098 -0.41.1 - 0.42 536004 4307150.112 without starter Base wired with
preheater530309 -
0.112 without starter 530316 -
CHAPPEE
1
Type Manufacturer ref Mark Ref
Characteristic : Base wired with preheater
TIGRA CF 500 58539863 1 401031TIGRA CF 500 58539864 2 401032Characteristic : Base wired with preheaterLANDIS type
TIGRA CF 500 58539910 1 401042
2
CUENOD
Type Manufacturer ref Ref
Characteristic : -
NC 4 gas - NC 6 gas - NC 9 gas grey cap 13010521 406008Characteristic : Base wired with preheater
NC 4 - NC 6 - NC 9 grey cap 13010979 406011
DE DIETRICH
1
Type Manufacturer ref Mark Ref
Characteristic : Base wired without preheater
MX10 -M1.4S - M1.5S - M1.6S M1.5CS - M1.6CS - M14S M18S M19S - M18CS - M19CS - M10CS
9790-7598 1 405700
Characteristic : Base wired without preheater
M104 9795-5503 1 439118M10R -M16RS -M17RS -M16RCS M1.4RCS 9790-7599 405701
Characteristic : Base wired with preheater
M1.3RS -M1.4RS - M1.3RCS M1.4RCS M10RD - M10RCS M10RCS 9790-7597 2 405702
M104 9795-5504 2 439119
ELCO
TypeManufacturer
refRef
Characteristic : Only SIP66 Base not wired, used to repair SIP 45/46/63/64/65 pre-wired base
- CAS 106295 803061Characteristic : SIP45 Base wired without preheater
EL 01A2H /A3H/ A5H CAS 106244 402101Characteristic : Base wired without preheater
EL 03B20V/30V - EL 1B3/B5/B8 - EL02B16 CAS 106684 402102Characteristic : SIP45 Base wired without preheater
EL 03.20H / 20V/ 30H/ 30VEL 01 A3/ A5/ A8 - EL 02.9/02.15 CAS 106156 402100
Characteristic : SIP65 Base wired without preheater
EL 03.20 1D/1DO - EL03.30 1D/1DOEL02.9 1D/1DO - EL02.15 1D/1DO SIP 065 402104
2
Control unit
CSB.261
Cont
rol u
nit
BO
IDEAL STANDARD
TypeManufacturer
refRef
Characteristic : Base wired with preheaterHELIS 500 / HELIS MI500 58539863 401031Characteristic : Base wired without preheaterHELIS 500 / HELIS MI500 58539864 401032Characteristic : Base wired with preheater LANDIS typeHELIS 500 / HELIS M500 58539910 401042
OERTLI
1 2
TypeManufacturer
refMark Ref
Characteristic : Base wired without preheaterOES 310 LE - OES 130 LE 102102 1 405700Characteristic : Base wired with preheater OES 310 LEV 101754 2 405701OES 130 LEV 102104 2 405702
Control unit
CSB.262
BO
Cont
rol u
nit
IGNITION SPARK DETECTORDEFINITION :Linked to a flame detector circuit that uses ionization electrode, the system detects a flame signaling a spark.It replaces the UV cell for ignition spark detection when the use is compromized.
IGNITION SPARK DETECTOR model DA51 ECEE ref : diff 501660
IGNITION SPARK DETECTOR model QRE1 Landis and Gyr ref : diff 502315ormodel RT1 Brahma ref : diff 504220
Note : In both cases, the high frequency wave created by the ignition spark, provides a necessary contact when ionization sensor current goes through. The detection avoids trouble in case of short-circuit electrode.
INFORMATION
On fuel or gas burners, the modernization and miniaturization of control boxes allow rapid and safe maintenance, through the use of microprocessors.
On the new generation relays, breakdowns indeed are automatically detected by electronics, thus enabling quick diagnosis and reducing attendance.
LMO (replacing soon LOA relays) and LMG (replacing soon LGB relays) have a very fi ne process. Through a blinking light code, they show the cause of the failure
Failure code tables
LMOBlinking code CauseBlinking 2x
••no fl ame at the end of “TSA” � Defective or clogged fuel valves � Defective or clogged cell � Bad burner adjustment or no fuel � Defective ignition system
Blinking 4x
••••parasite light when burner starts
Blinking 7x
•••••••fl ame disappearing too often � Defective or clogged fuel valves � Defective or clogged cell � Bad burner adjustment
Blinking 8x
••••••••Time control of the fuel preheater
Blinking 10x
••••••••••Bad wiring, internal defect or output con-
tacts
LMGBlinking code Cause
Blinking 2 x ••
no fl ame at the end of "TSA" � Defective or clogged fuel valves � Defective or clogged electrode/cell � Bad burner adjustment
Blinking 3x •••
Pressure switch does not close� Defective "LP"� "LP" not adjusted � the fan does not function
Blinking 4x ••••
Pressure switch does not open; parasite light when burner starts� Defective "LP" � "LP" not adjusted
Blinking 5x ••••• parasite light during preventilation or internal defect
Blinking 7x •••••••
fl ame stops during the operation � Bad burner adjustment � Defective or clogged fuel valves� Short circuit between ionization electrode and earth
Blinking 18x ••••••••••••••••••
the pressure switch opens during preventilation or operation � "LP" badly adjusted� fl ame stops for the 4th time
Blinking 19x •••••••••••••••••••
defective ouptput contacts� Bad wiring
� Or another power supply at the output Blinking 20x ••••••••••••••••••••
internal defect