series lc/lce - america's best built boiler...cap which can control wind effects. 5. this...
TRANSCRIPT
LC/LCE™
Gas/Oil Boilers – Steam
SeriesOil, Gas &
Installation,Operation &MaintenanceManual
USING THIS MANUALA. INSTRUCTION MANUALS . . . . . . . . . . . . . . .1B. SPECIAL ATTENTION BOXES . . . . . . . . . . . .1
1. PREINSTALLATION
A. ACCESSIBILITY CLEARANCES . . . . . . . . . . .2B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . .3C. COMBUSTION AND VENTILATION AIR . . . .3
D. CHIMNEY OR VENT . . . . . . . . . . . . . . . . . . . .3
E. BOILER SETTING . . . . . . . . . . . . . . . . . . . . . .4
F. INSTALLATION SURVEY . . . . . . . . . . . . . . . .5
G. PLANNING THE LAYOUT . . . . . . . . . . . . . . . .5
H. VERIFY COMPONENTS . . . . . . . . . . . . . . . . .5
2. PLACE THE BOILER
A. PACKAGED BOILER . . . . . . . . . . . . . . . . . . .10
B. ASSEMBLED BLOCK BOILER . . . . . . . . . . .10
C. KNOCKDOWN BOILER – PLACINGTHE SECTIONS . . . . . . . . . . . . . . . . . . . . . .10
D. INSTALL COILS OR PLATES . . . . . . . . . . . .17
E. HYDROSTATIC TEST THE BOILER . . . . . . .17
F. APPLY CLEANOUT COVER PLATES . . . . . .19
G. INSTALL FLUE COLLAR . . . . . . . . . . . . . . . .19
H. INSTALL FLUE BAFFLES . . . . . . . . . . . . . . .20
I. INSTALL CHAMBER LINER . . . . . . . . . . . . .20
3. PIPE THE BOILERA. PREPARATION . . . . . . . . . . . . . . . . . . . . . . .21B. SUPPLY AND RETURN PIPING . . . . . . . . . .21C. LOW SYSTEM TEMPERATURE . . . . . . . . . .21D. MULTIPLE BOILER INSTALLATIONS . . . . . .22
4. ASSEMBLE THE JACKETA. PREPARE THE PARTS . . . . . . . . . . . . . . . . .25B. APPLY JACKET SIDES AND CORNERS . . .25C. APPLY JACKET FRONT PANELS . . . . . . . . .25D. APPLY JACKET REAR PANEL . . . . . . . . . . .25E. APPLY JACKET TOP PANELS . . . . . . . . . . .25F. APPLY PLATES AND LABELS . . . . . . . . . . .25
5. VENTING 27
6. INSTALL THE BURNERA. BURNER APPLICATION . . . . . . . . . . . . . . . .27B. INSTALL BURNER MOUNTING PLATE . . . .27C. MOUNT THE BURNER . . . . . . . . . . . . . . . . .27
7. CONNECT FUEL PIPINGA. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . .29B. INSTALL FUEL OIL PIPING . . . . . . . . . . . . .29C. INSTALL GAS SUPPLY PIPING . . . . . . . . . .29D. TEST GAS SUPPLY PIPING . . . . . . . . . . . . .29
8. INSTALL CONTROLS AND TRIMA. INSTALL SAFETY VALVES . . . . . . . . . . . . .31B. INSTALL BLOWDOWN VALVE . . . . . . . . . . .31C. INSTALL LOW WATER CUTOFF(S) . . . . . . .31D. INSTALL PRESSURE CONTROLS . . . . . . . .31E. PIPE TANKLESS HEATERS(S) . . . . . . . . . . .31F. CONNECT SUPPLY WIRING . . . . . . . . . . . .31G. INSTALL CONTROL WIRING . . . . . . . . . . . .32
9. STARTING THE BOILERA. CHECK THE PIPING . . . . . . . . . . . . . . . . . . .39B. FILL THE BOILER . . . . . . . . . . . . . . . . . . . . .39C. RUN BURNER CHECK-OUT . . . . . . . . . . . . .39D. CHECK BOILER CONTROLS . . . . . . . . . . . .39E. CLEAN THE BOILER . . . . . . . . . . . . . . . . . . .39
10. MAINTENANCEA. PLACING BOILER IN OPERATION . . . . . . . .42B. TO SHUT DOWN THE BOILER . . . . . . . . . .42C. MAINTENANCE – ANNUAL . . . . . . . . . . . . .42D. MONTHLY MAINTENANCE . . . . . . . . . . . . .43E. DAILY MAINTENANCE . . . . . . . . . . . . . . . . .43
11. BOILER RATINGS & DIMENSIONS 44
12. REPAIR PARTSA. SERIES LC™ BOILER ASSEMBLY . . . . . . . .47B. SERIES LCE™ BOILER ASSEMBLY . . . . . . .50
TABLE OF CONTENTS
TABLE OF CONTENTS
1
A. INSTRUCTION MANUALSThe Series LC/LCE™ Installation, Operation &Maintenance Manual is divided into four basic sections:
1. Preinstallation (Section 1)2. Installation (Sections 2 through 8)3. Start-Up (Section 9)4. Maintenance (Section 10)
B. SPECIAL ATTENTION BOXESThroughout this manual you will see special attentionboxes intended to supplement the instructions and makespecial notice of potential hazards. These categoriesmean, in the judgment of PB Heat, LLC:
Indicates special attention is needed, but not directlyrelated to potential personal injury or propertydamage.
NOTICE
Indicates a condition or hazard which will or cancause minor personal injury or property damage.
CAUTION
DANGERIndicates a condition or hazard which will causesevere personal injury, death or major propertydamage.
USING THIS MANUAL
USING THIS MANUAL
Indicates a condition or hazard which may causesevere personal injury, death or major propertydamage.
WARNING
A. ACCESSIBILITY CLEARANCES
1. Clearances for service and from combustible surfacesare the same for the LCE as for the LC. Thefollowing recommendations allow for reasonableaccess to the boiler. Follow local codes andrequirements when setting actual layout. SeeFigure 1.1.a) For installing, removing and servicing the burner:
provide 48" between the front of the boiler andany adjacent wall or other appliance.
b) For access to the top of the boiler for cleaningflueways: provide 24" above top of jacket.
c) For accessing and servicing of level controls andinspection tappings (if used): provide 24"minimum from the right side of the boiler to anywall or obstruction.
d) For installation of jacket: provide at least 12"from the left side of the boiler to any wall orobstruction. More clearance may be needed forlonger boilers unless the jacket is pre-assembledbefore placing the boiler.
e) For installation and removal of tankless heaters:provide 45" between the end of the boiler andany adjacent wall of obstruction. [This providesfor all available tankless coils. The spacing canbe closer for Heater Number X-1020 (allow 30")or Heater Number X-1021 (allow 35")].
The equipment must be installed in accordance with installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSIZ223.1/NFPA 54.
Where required by the authority having jurisdiction, the installation must conform to American Society ofMechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.
NOTICE
PREINSTALLATION
1. PREINSTALLATION
Carefully read these instructions before beginning work. Understand all aspects of the installation. Contact your PB Heat, LLCsales representative or customer service for help in answering questions.
This boiler must be installed by a qualified contractor. The boiler warranty can be voided if the boiler is not installed correctly.
Figure 1.1: Clearance Requirements
2
B. CLEARANCE FROM COMBUSTIBLE CONSTRUCTIONProvide the following minimum clearances tocombustible construction. See Figure 1.1.
1. Sides: 6"2. Rear of Jacket: 6"3. Front of Jacket: 24"4. Top of Jacket: 24"5. Steam and Hot Water Pipes: 6"6. Vent or Chimney Connector: 18"
C. COMBUSTION AND VENTILATION AIR
1. The installation must provide adequate air forcombustion and ventilation.
2. Unless the boiler room construction and natural airinfiltration are sure to provide all the air needed,provide an opening or duct to the outside with a freecross sectional area of at least 1 square inch per4000 Btuh input for all installed appliances. At highaltitude, increase this requirement 4% for each 1000feet above sea level.
3. The boiler room must never be under negativepressure. If exhaust fans or other equipment cancause a negative pressure in the boiler room, the airopenings and equipment design must be engineeredto assure a neutral or slightly positive pressure in theboiler room at all times of operation. If theequipment design and air openings cannot assurethis, then the boiler must be located in an isolatedroom.
4. Using combustion air dampers:a) If motorized dampers are used on the
combustion and ventilation air openings, wirethem such that they must open when the boilertries to operate. They must include a switchwhich prevents the boiler from operating if theydo not open. See Figure 1.2.
D. CHIMNEY OR VENT
1. Inspect the existing chimney or vent system. Makesure it is in good condition. Inspect chimney linerand repair or replace if necessary.
2. The vent system and installation must be inaccordance with the current edition of the AmericanNational Standard ANSI/NFPA 211, “Chimneys,Fireplaces, Vents, and Solid Fuel BurningAppliances”, or applicable provisions of the localbuilding codes. The venting requirements for theLCE are the same as for the LC. Figure 1.3 showsthe top flue outlet required on LCE boilers.
3. Chimney/Vent Operation: The vent system must besized and installed to remove all combustionproducts. If the vent system is not sized properly, theburner may not operate properly. This can causepoor combustion or sooting to occur.
4. If the vent terminates in an area where wind-generated downdrafts are likely, install a suitable ventcap which can control wind effects.
5. This boiler is designed to fire only with a pressurizedfire box. The breeching and vent may be sized fornegative, neutral or positive pressure (no more than0.l inches water column at the boiler outlet) asdesired. But negative pressure overfire can causelifting of the flame and poor combustion oroverheating of the boiler crown sheet.
6. Forced draft breechings and vents must be sealedand of heavy gauge steel construction and mustcomply with all applicable codes of construction.
7. The vent diameter and minimum height for stubvents are listed in the Ratings and DimensionsSection of this manual. Always extend ventterminations at least 3 feet above the roof line. SeeFigure 1.3.
3
PREINSTALLATION
Figure 1.2: Motorized Vent Damper Interlock Figure 1.3: Vent Termination, Typical
Failure to provide adequate venting can result insevere property damage, personal injury or death.
WARNING
4
8. Exterior Vents:a) Insulate sufficiently to ensure adequate draft and
to prevent vent damage due to condensation.
9. Vent Connection to Boiler:a) Support the weight of the vent system
independently of the boiler flue connection.
b) Provide support of the vent connector(breeching) at maximum 12 foot intervals toprevent sagging and to provide a minimumupward slope of 1/4" per foot.
10. Do not vent natural draft appliances in a combinedvent which operates under positive pressure.
11. Draft Regulator: Install a barometric draft regulatorwhere using high chimney or any high draft vent.This is needed to prevent causing negative draft inthe boiler. Excess draft will cause flame lifting andpossible impingement.
12. The Draft Damper for the LCE boiler is a separatepiece, shipped in the Top Flue Outlet Carton.a) Install the Draft Damper as close as possible to
the boiler flue outlet. It can be installed verticallyor horizontally provided that the connecting ventpiping and fittings are designed and installed forpressurized service.
b) Secure the damper to the vent with screws andseal the joints with a bead of high temperaturesilicone sealant (found in Section Assembly Kits).
c) The vent must be installed so it can bedisconnected and the Top Flue Outlet removedfor proper cleaning of the flueways.
E. BOILER SETTING
1. If the boiler room floor is not level or if additionalstructural support is needed, provide a good, levelfoundation for the boiler with the minimumdimensions given in Table 1.1. The flooring andstructural support system must be suitable for theoperating weight of the boiler and any connectedpiping. Place the Steel Channels on the foundationas shown in Figure 1.4.
2. Do not operate the boiler until the foundation, if newconcrete, has thoroughly cured. The concrete mightbe damaged if heated too quickly due to theentrained moisture remaining.
3. If the boiler is installed in a penthouse or if wiring ofany sort is run underneath the boiler foundation,construct the foundation with provision for air flowunderneath between the main floor and the top ofthe boiler foundation.a) An acceptable foundation would be concrete
blocks laid with the openings lined up.
Do not install this boiler on carpeting or anycombustible flooring. A significant fire hazard couldresult, with potential for property damage, personalinjury or death.
WARNING
Figure 1.4: Foundation Layout
PREINSTALLATION
5
b) If the foundation must be a concrete slab, use anair cell high temperature insulating board, at least1/2" inch thick, with aluminum backing, aluminumside up. 1/2" inch thick high temperaturemillboard with aluminum backing is acceptableas well. Place the insulating board on the slabbetween the steel channels.
F. INSTALLATION SURVEYFor new and existing installations, a Steam InstallationSurvey is available from PB Heat, LLC. The survey willprovide information on how a steam boiler works withyour specific system and will provide an overview ofsteam system operation in general.
You can also use this survey to locate system problemswhich will have to be corrected. To obtain copies of theSteam Installation Survey, contact your PB Heatrepresentative or download it from PeerlessBoilers.com.
G. PLANNING THE LAYOUTPrepare sketches and notes of the layout to minimize thepossibility of interferences with new or existingequipment, piping, venting and wiring.
H. VERIFY COMPONENTS
1. Packaged: All components should be inside crate. Insome cases the burner may be shipped separately.Optional equipment, such as barometric draftdampers, may also be shipped separately.
2. Knockdown: All components shipped for fieldassembly. See Table 1.2 for standard components.See Tables 1.3 through 1.7 for optional components.a) Channel Rails
b) Sections
c) Assembly Kit Carton(s): Includes flow portgaskets, tie rods with hardware, high temperaturerope, and cleanout cover plates.
d) Flue Box Carton: Includes flue box, rear fluecover plate (LCE only), rear observationassembly and port cover plates.
e) Baffle Carton
i) LC: Includes baffles, combustion chamberliner, rating label
ii) LCE-21 through LCE-24: Baffles
f) Jacket Cartons: Includes ASME plate
g) Draft Damper (LCE only)
h) Label Carton (LCE only)
i) Burner Mounting Plate
j) Trim Carton: Includes safety relief valve andtemperature-pressure gage
k) Control Carton: Limit controls
l) Tankless Heater(s)
m) Additional controls and fittings
3. Assembled Block: Same as knockdown exceptchannel rails, sections and assembly kit cartons areassembled into a block as a single shipping levelcomponent.
Table 1.1: Foundation Lengths
LC-04LC-05LC-06LC-07LC-08LC-09LC-10LC-11LC-12
LCE-13LCE-14LCE-15LCE-16LCE-17LCE-18LCE-19LCE-20LCE-21LCE-22LCE-23LCE-24
Model Foundation Length, Inches
37¹⁵⁄₁₆
4348¹⁄₁₆
53¹⁄₈
58⁵⁄₁₆
63³⁄₈
68⁷⁄₁₆
73¹⁄₂
78⁹⁄₁₆
83³⁄₄
88¹³⁄₁₆
93⁷⁄₈
98¹⁵⁄₁₆
104¹⁄₈
109³⁄₁₆
114¹⁄₄
119⁷⁄₁₆
124¹⁄₂
129⁹⁄₁₆
134⁵⁄₈
139¹¹⁄₁₆
PREINSTALLATION
6
PREINSTALLATION
Table
1.2
A:
Seri
es
LC™
Ship
pin
g L
ist
Cha
nnel
Rai
lB
undl
eFr
ont
Bac
kP
lain
Inte
rm.
1"
LWC
OIn
term
.3"
Tap.
Inte
rm.
Baf
fle
Car
ton
Con
tent
sSe
e B
elow
Item
1
Con
tent
sSe
e B
elow
Item
2
Cha
mbe
rLi
ner
Enc
lose
d
Fron
t/Rea
rPa
nels
Har
dwar
e
Top/
Side
Pane
lsH
ardw
are
Sta
ndar
d S
ecti
ons
(See
Tab
le 1
.3 fo
r O
ptio
ns)
Ass
embl
y K
it C
tns.
Jack
et C
arto
ns(T
bl 1
.4 O
ptio
ns)
Flue
C
tn.
LC-0
4
LC-0
5R
LC-0
5
LC-0
6
LC-0
7
LC-0
8
LC-0
9
LC-1
0
LC-1
1
LC-1
2
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
1
9016
0
1
9016
1
1
9016
1
1
9016
2
1
9016
3
1
9016
4
1
9016
5
1
9016
6
1
9016
7
1
9016
8
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
000
8600
4
2
LC-1
000
8600
4
2
LC-1
000
8600
4
3
LC-1
000
8600
4
4
LC-1
000
8600
4
5
LC-1
000
8600
4
6
LC-1
000
8600
4
7
LC-1
000
8600
4
7
LC-1
000
8600
4
8
LC-1
000
8600
4
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
003
8600
8
1
LC-1
003
8600
8
1
LC-1
023
LC-0
4
8500
4
1
LC-1
023
LC-0
5
8510
5
1
LC-1
023-
1
LC-0
5
8500
5
1
LC-1
023-
2
LC-0
6
8500
6
1
LC-1
023-
3
LC-0
7
8500
7
1
LC-1
023-
4
LC-0
8
8500
8
1
LC-1
023-
5
LC-0
9
8500
9
1
LC-1
023-
6
LC-1
0
8501
0
1
LC-1
023-
7
LC-1
1
8501
1
1
LC-1
023-
8
LC-1
2
8501
2
1
LC-1
022
A
8605
0
1
LC-1
022-
1
B
8605
1
1
LC-1
022-
1
B
8605
1
1
LC-1
022-
2
C
8605
2
1
LC-1
022-
3
D
8605
3
1
LC-1
022
A
8605
0
2
LC-1
022-
1
B
8605
1
1
LC-1
022-
1
B
8605
1
2
LC-1
022-
2
C
8605
2
1
LC-1
022-
2
C
8605
2
1
LC-1
022-
1
B
8605
1
1
LC-1
022-
2
C
8605
2
1
LC-1
022-
3
D
8605
3
1
LC-5
004
A
8604
0
1
LC-5
004
A
8604
0
1
LC-5
004
A
8604
0
1
LC-5
004-
1
B
8604
1
1
LC-5
004-
1
B
8604
1
1
LC-5
004-
1
B
8604
1
1
LC-5
004-
2
C
8604
2
1
LC-5
004-
2
C
8604
2
1
LC-5
004-
2
C
8604
2
1
LC-5
004-
2
C
8604
2
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
016
8603
0
1
LC-6
017
A
8603
1
1
LC-6
017-
1
B
8603
2
1
LC-6
017-
1
B
8603
2
1
LC-6
017-
2
C
8603
3
1
LC-6
017-
3
D
8603
4
1
LC-6
017
A
8603
1
2
LC-6
017-
1
B
8603
2
1
LC-6
017-
1
B
8603
2
2
LC-6
017-
2
C
8603
3
1
LC-6
017-
2
C
8603
3
1
LC-6
017-
1
B
8603
2
1
LC-6
017-
2
C
8603
3
1
LC-6
017-
3
D
8603
4
1A
ssem
bly
Kit
Car
tons
Con
tent
s: F
low
Por
t Gas
kets
, Sili
cone
Sea
lant
, Tie
Rod
s, W
ashe
rs, T
ie R
od N
uts,
Sec
tion
Seal
Rop
e, R
ope
Adh
esiv
e or
Spr
ay A
dhes
ive,
Cle
anou
t Pla
tes,
Mou
ntin
g H
ardw
are
2Fl
ue B
ox C
arto
n C
onte
nts:
Flu
e B
ox, S
eal R
ope,
Obs
erva
tion
Ass
embl
y, C
oil C
over
Pla
tes,
Cov
er P
late
Gas
kets
, Mou
ntin
g H
ardw
are
Boi
ler
Mod
elN
umber
7
PREINSTALLATION
Table
1.2
B:
Seri
es
LCE™
Ship
pin
g L
ist
Cha
nnel
Rai
lB
undl
eFr
ont
Top
Flu
eIn
term
.
1"
LWC
OIn
term
.3"
Tap.
Inte
rm.
Pla
inIn
term
.B
ack
Baf
fle
Car
ton
Flow
Por
t Gas
kets
, Sili
cone
Sea
lant
,Ti
e R
ods,
Was
hers
, Tie
Rod
Nut
s, S
ectio
n Se
al R
ope,
Rop
e A
dhes
ive
or S
pray
Adh
esiv
e, C
lean
out P
late
s,M
ount
ing
Har
dwar
e
Con
tent
sSe
e B
elow
Item
1
Fron
t/Rea
rPa
nels
Har
dwar
e
Top/
Side
Pane
lsH
ardw
are
Cha
mbe
r Li
ner
Sta
ndar
d S
ecti
ons
(See
Tab
le 1
.3 fo
r O
ptio
ns)
Ass
embly
Kit
Car
tons
Jack
et C
arto
ns (S
ee T
able
1.4
for
Opt
ions
)Fl
ue C
tn.
Lbl.
Ctn
.B
oile
rM
odel
Num
ber
LCE
-13
LCE
-14
LCE
-15
LCE
-16
LCE
-17
LCE
-18
LCE
-19
LCE
-20
LCE
-21
LCE
-22
LCE
-23
LCE
-24
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
Qua
ntity
Part
No.
Lab
el
Stoc
k C
ode
2
9016
9
2
9016
2
2
9016
3
2
9016
3
2
9016
4
2
9016
4
2
9016
5
2
9016
5
2
9016
6
2
9016
6
2
9016
7
2
9016
7
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
1
LC-1
001
8600
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
3
LCE
-105
6
8610
0
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
000-
1
8600
5
1
LC-1
003
8600
8
2
LC-1
003
8600
8
2
LC-1
003
8600
8
2
LC-1
003
8600
8
3
LC-1
003
8600
8
3
LC-1
003
8600
8
3
LC-1
003
8600
8
4
LC-1
003
8600
8
4
LC-1
003
8600
8
4
LC-1
003
8600
8
4
LC-1
003
8600
8
4
LC-1
003
8600
8
6
LC-1
000
8600
4
6
LC-1
000
8600
4
7
LC-1
000
8600
4
8
LC-1
000
8600
4
8
LC-1
000
8600
4
9
LC-1
000
8600
4
10
LC-1
000
8600
4
10
LC-1
000
8600
4
11
LC-1
000
8600
4
12
LC-1
000
8600
4
13
LC-1
000
8600
4
14
LC-1
000
8600
4
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LC-1
007
8602
2
1
LCE
-107
4
8611
3
1
LCE
-107
4
8611
3
1
LCE
-107
4
8611
3
1
LCE
-107
4
8611
3
1 C
8605
2
1 D
8605
3
1 A
8605
0
2 B
8605
1
1 B
8605
1
2 C
8605
2
1 C
8605
2
2 D
8605
3
1 A
8605
0
2 B
8605
1
1 B
8605
1
2 C
8605
2
1 E
8605
4
1 E
8605
4
1 B
8605
1
1 E
8605
4
1 C
8605
2
1 E
8605
4
1 D
8605
3
1 E
8605
4
1 B
8605
1
1 D
8605
3
1 C
8605
2
1 D
8605
3
1 E
8605
4
1 E
8605
4
1 E
8605
4
1 D
8605
3
1 E
8605
4
1 D
8605
3
1 E
8605
4
1 E
8605
4
1 E
8605
4
1
LC-5
011
D
8604
3
1
LC-5
011
D
8604
3
1
LC-5
011
D
8604
3
1
LC-5
011
D
8604
3
1
LC-5
011
D
8604
3
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LC-5
012
E
8604
4
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LCE
-601
6
8603
0
1
LC-6
017
A
8603
1
2
LC-6
017-
1
B
8603
2
1
LC-6
017-
1
B
8603
2
2
LC-6
017-
2
C
8603
3
1
LC-6
017
A
8603
1
3
LC-6
017-
1
B
8603
2
2
LC-6
017-
1
B
8603
2
2
LC-6
017
A
8603
1
1
LC-6
017
A
8603
1
4
LC-6
017-
1
B
8603
2
3
LC-6
017-
1
B
8603
2
2
LC-6
017-
1
B
8603
2
1
LC-6
017-
1
B
8603
2
1
LC-6
017-
2
C
8603
3
2
LC-6
017-
1
B
8603
2
1
LC-6
017-
2
C
8603
3
2
LC-6
017-
1
B
8603
2
3
LC-6
017-
1
B
8603
2
1
LC-6
017-
2
C
8603
3
2
LC-6
017-
2
C
8603
3
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
LCE
-602
3
E
8609
4
1
S-50
07-3
A
9052
3
1
S-50
07-3
A
9052
3
1
S-50
07-3
A
9052
3
1
S-50
07-3
A
9052
3
1
S-50
07-3
A
9052
3
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
S-50
07-4
B
9052
4
1
LCE
-802
8
8501
3
1
LCE
-802
8-1
8501
4
1
LCE
-802
8-2
8501
5
1
LCE
-802
8-3
8501
6
1
LCE
-802
8-4
8501
7
1
LCE
-802
8-5
8501
8
1
LCE
-802
8-6
8501
9
1
LCE
-802
8-7
8502
0
1
LCE
-802
8-8
8502
1
1
LCE
-802
8-9
8502
2
1
LCE-
8028
-10
8502
3
1
LCE-
8028
-11
8502
4
Dra
ftD
ampe
rR
atin
gL
abel
1Fl
ue B
ox C
arto
n C
onte
nts:
Top
Flu
e P
late
, Rea
r Fl
ue C
over
, Sea
l Rop
e, O
bser
vatio
n A
ssem
bly,
Coi
l Cov
er P
late
s, C
over
Pla
te, G
aske
ts, M
ount
ing
Har
dwar
e
8
PREINSTALLATION
Note: Boilers with inspection tappings in front and back sections only usestandard cartons.
Table 1.4: Standard and Optional Jacket Cartons,Top/Side Panels
ABCDE
Jacket Label
8603186032860338603486094
Standard(No Inspection
Tappings)
8610186102861038610486097
With InspectionTappings
Table 1.3: Standard and Optional Sections for Knockdown Boilers
Table 1.5A: Burner Mounting Plates
* Standard Burner Mounting Plate
Sections15 psig Steam MAWP
Standard w/Inspection TappingsPart # Stock Code Part # ITP Stock Code
Front LC-1001 86000 LC-1013 86010Intermediate LC-1000 86004 LC-1014 86014
LWCO Intermediate LC-1000-1 86005 LC-1014-2 86092Top Flue Intermediate LCE-1056 86100 LCE-1064 861103" Tapped Intermediate LC-1003 86008 LC-1015 86016
Closed Back LC-1007 86022 LC-1016 86018Coil Back LC-1002 86036 LC-1017 86026
ModelBoiler Model
LC-04 LC-05R LC-05 LC-06 LC-07 LC-08 LC-09 LC-10 LC-11 LC-12
Beckett
CF-800 86070* 86070*CF-1400 86069* 86069* 86069*CF-2300 86074* 86074* 86074* 86074* 86074*CG-10 86085CG-15 86074 86074 86074 86074CG-25 86074 86074 86074 86074 86074
Carlin301CRD 86070* 86070*702CRD 86069* 86069* 86069* 86069*801CRD 86073 86073 86073 86073
GordonPiatt
R6.X 86078 86078 86078 86078R8.X 86079 86079 86079 86079 86079 86079
PowerFlame
C1 86071 86071 86071 86071 86071C2 86076 86076 86076 86076 86076
J15A 86072 86072J30A 86072 86072 86072J50A 86077 86077 86077 86077
Webster JB1 86071 86071 86071 86071 86071 86075 86075 86075 86075 86075
9
PREINSTALLATION
Table 1.7: Control Cartons
Table 1.6: Trim Cartons
1 Safety Relief Valve selection based on capacity determined by boiler output (Gross I=B=R Output). Applies to most locations in United States and Canada.
Table 1.5B: Burner Mounting Plates
* Standard Burner Mounting Plate
Model StockCode Label
LC-04LC-05RLC-05
870008700087000
AAA
LC-06LC-07LC-08
870008700087000
AAA
LC-09LC-10LC-11LC-12
87001870018700187001
BBBB
LCE-13LCE-14LCE-15
870028700287002
CCC
LCE-16LCE-17LCE-18
870028700387003
CDD
LCE-19LCE-20LCE-21
870038700387003
DDD
LCE-22LCE-23LCE-24
870038700487004
DEE
Model Stock Code Label
LC-04ThroughLCE-24
88511 Steam
ModelBoiler Model
LCE-13 LCE-14 LCE-15 LCE-16 LCE-17 LCE-18 LCE-19 LCE-20 LCE-21 LCE-22 LCE-23 LCE-24
Beckett
CF2300AKG 80674*
Not AvailableCF2300AKB 86083* 86083*
CF2500 86074* 86074*CF3500AKM 86083* 86083* 86083*CF3500AKL 86080* 86080*
CG-50 86083 86083 86083 86083 86083 86083 86083 86083 86083 86083 86083 N/A
Carlin801CRD 86073 86073
N/A1050FFD 86086 860861150FFD 86087 86087 86087 86087 86087 86087 86087
GordonPiatt R10.X 86088 86088 86088 86088 86088 86088 86088 86088 86088 86088 86088 86088
PowerFlame
C2 86076 86076 86076C3 86080 86080 86080 86080 86080 86080 86080 86080 86080
Webster JB2 86081 86081 86081 86081 86081 86081 86081 86081 86081 86081 86081 86081
10
A. PACKAGED BOILER
1. Remove crate top and sides. Remove any loosecartons. Remove burner support pedestal andnipple, if supplied
2. Lift boiler off crate pallet. Move to locationdetermined in Chapter 1: Preinstallation.
3. Remove lifting frame and hardware.
4. Re-install burner support pedestal and nipple ifnecessary.
5. Proceed to Chapter 3: Piping the Boiler.
B. ASSEMBLED BLOCK BOILER
1. Move block to location determined in Chapter 1:Preinstallation.
2. Remove lifting frame and hardware.
3. Proceed to Section D: Install Coils or Plates
C. KNOCKDOWN BOILER
1. Place channel rails as shown in Figure 1.4.
2. Open the Section Assembly Kit cartons. Thesecartons contain the parts needed for assembly of thesections.
3. Place the Back Section on the floor as shown inFigure 2.1.
4. The Back Section combustion chamber area is linedwith a ceramic fiber blanket liner. Make sure the lineris in good condition. Minor tears are not a problem,but there should be no holes in the insulation.
PLACE THE BOILER
2. PLACE THE BOILER
Figure 2.1: Lay Sections on Floor and Apply Rope Seal and Gaskets
11
5. Clean the area around the flow ports and in the sealrecess. Use solvent and a clean cloth to thoroughlyclean all of the sealing surfaces. Remove all foreignmatter to assure a water tight seal when the sectionsare drawn together.
6. Place a Flow Port Gasket in each of the three flowport recesses as shown in Figures 2.1 and 2.2.
7. Apply rope adhesive or spray adhesive in the ropegroove around the perimeter of the section.
8. Place the sealing rope completely around the ropegroove, being careful not to stretch the rope. Extendthe rope from 1/4" to 1/2" past the end of the grooveon both sides of the cleanout opening on top of thesection. This will assure a gas tight seal when thecleanout cover plate is applied.
9. Apply a bead of silicone sealant around each flowport as shown in Figure 2.3. Do not get sealant onthe flow port gaskets.
10. Lift up the Rear Section and move into position onthe steel channels on the boiler foundation.
11. Screw a 3" pipe at least 30 inches long into thelower 3" tapping on the back of the Rear Section asshown in Figure 2.4. Place a block under the pipe asshown in the figure and use as a brace duringassembly.
12. Place a Plain Intermediate Section on the floor andprepare as above.
13. Carefully place the Intermediate Section against theRear Section and visually line up the flow ports asclose as possible.
14. Insert a tie rod with one nut and washer applied into each of the four tie rod lugs. See Figures 2.5and 2.6.
15. Place the nut and washer on the other end of the tierod and draw finger tight.
PLACE THE BOILER
Figure 2.3: Apply Silcone Sealant
Gaskets will be damaged by petroleum or itsderivatives. Completely remove all solvent residuebefore placing gaskets.
Do not use petroleum based compounds in theboiler.
CAUTION
Figure 2.2: Flow Port Machining & Gasket
The sections are heavy and must be supportedsecurely.
WARNING
12
Figure 2.4: Install Additional Sections. Use level on each section as tie rod bolts are drawn up.
PLACE THE BOILER
13 13
PLACE THE BOILER
Figure 2.5: Series LC™ Boiler Assembly – Right Side View
14
PLACE THE BOILER
Figure 2.6: Series LCE™ Boiler Assembly – Right Side View
15
16. To properly assemble LC/LCE sections in the field,the following steps must be followed to ensure thatno damage occurs to the tie rod lugs. A 0-100 ft-lbstorque wrench is required.a. Use a spirit level as shown in Figure 2.4 to check
the alignment of the sections as the nuts aredrawn up. Keep the sections plumb.
b. Draw the sections together evenly, in threerotations. Torque each port to 20 ft-lbs for thefirst rotation, then to 40 ft-lbs for the secondrotation, then to 60 ft-lbs for the third rotation.Use the following sequence until all three portstouch metal-to-metal at 60 ft-lbs. See Figure 2.7for port reference.
i) First: Lower Top Port
ii) Second: Bottom Port
iii) Third: Upper Top Port
c. Tighten these (3) three locations only to a torquevalue of 60 ft-lbs. DO NOT EXCEED.
d. After the three ports have been tightened to 60ft-lbs, tighten the draw rod at the bumping padsuntil metal-to-metal contact is reached. This willassure a proper gas tight seal and prevent theproducts of combustion from migrating into theboiler room.
17. Repeat with the remaining sections.a. Save the LWCO Intermediate with two 1"
tappings (for level control) for use as the sectionclosest to the front section.
b. Place the Intermediate Section with 3" toptapping (Tapped Intermediate) in the positiongiven in Figure 2.9.
c. LCE ONLY. Save the (3) Top Flue OutletIntermediates (with wide opening in top of theflue collector) for use as the sections closest tothe LWCO Intermediate Section. See Figure 2.9.
i) The sequence from Front to Rear is:• Front Section• 1" Low Water Cut-off Intermediate• Three (3) Top Flue Outlet Intermediates
ii) The remaining intermediate sections are 3"Tapped Intermediates or Plain Intermediatesas shown in Figure 2.8 and Figure 2.9.
Do not exceed the manufacturer’s torquerecommendations.
WARNING
PLACE THE BOILER
Figure 2.7: Torque Specification/Procedure
Figure 2.8: Section Positioning Numbering
Table 2.1: Section Numbering Sequence
LC-04LC-05LC-06LC-07LC-08LC-09LC-10LC-11LC-12
LCE-13LCE-14LCE-15LCE-16LCE-17LCE-18LCE-19LCE-20LCE-21LCE-22LCE-23LCE-24
ModelPlace a Tapped Intermediate
Section at Position(Numbered Rear to Front)
NANANANANANANA668
5, 96, 106, 11
5, 9, 125, 9, 135, 9, 14
5, 9, 12, 155, 9, 13, 165, 9, 13, 17
6, 10, 14, 186, 10, 14, 19
16
Figure 2.9: LC/LCE Boiler Section Assembly Sequence
PLACE THE BOILER
17
D. INSTALL COILS OR PLATES
1. Remove the coil cover plates, gaskets and mountinghardware, located in the Flue Box Carton.
2. Place the cover plates and gaskets over any unusedheater openings. Place the cover plate with two 3/4"NPT tappings on the upper flow port opening(Position #2) of the Front Section.
3. Install tankless heaters, if used, in openings #1 and#3. (Optional on Rear Section)
4. See Figure 2.10.
5. Steam boilers may have up to two coils installedwhen supplied with special tankless coil rear seciton.
6. Standard Rear Sections do not have a tanklessopening (position #3). This is available only asoptional construction. This special rear section isneeded to install two coils on a steam boiler.
E. HYDROSTATIC TEST THE BOILER
1. Install a drain valve in the Rear Section, Tapping 13.See Figure 8.2.
2. Provide a water supply line to the boiler.
3. Plug all open tappings in the boiler.
4. Provide a means to vent air as the boiler fills.
5. Fill the boiler with water, venting air as water levelrises.
6. Pressurize boiler to:• 45 psig• DO NOT EXCEED THESE PRESSURES.
a) Maintain pressure while checking all joints andfittings for leaks.
7. After inspection is complete, drain the boiler andremove plugs from tappings that are to be used.
PLACE THE BOILER
Figure 2.10: Tankless Coil Openings
18
Table 2.2: Tankless Coil Ratings
LC-04LC-05RLC-05LC-06LC-07LC-08LC-09LC-10LC-11LC-12
LCE-13LCE-14LCE-15LCE-16LCE-17LCE-18LCE-19LCE-20LCE-21LCE-22LCE-23LCE-24
ModelGPM Location
5.55.625.756.256.57.0
7.257.58.0–––––––––––––
111111111–––––––––––––
GPM Location
–6.57.0
7.758.5
9.2510.0
10.7511.5012.25
131313131313131313131313
–111111111111111111111
GPM Location
––––
13.013.7514.515.516.517.518.0
18.7519.5202020202020202020
––––111111111111111111
GPM Location
––––––
14.515.016.0
–––––––––––––
––––––
1 & 31 & 31 & 3
–––––––––––––
GPM Location
–––––––
21.523.524.5262626262626262626262626
–––––––
1 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 3
GPM Location
––––––––––––
33.535.537.539.5404040404040
––––––––––––
1 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 31 & 3
Heater No.X-1020
Heater No.X-1021
Heater No.X-1022
Two Heaters No.X-1020
Two Heaters No.X-1021
Two Heaters No.X-1022
Above heater ratings are based on intermittent demand for water from 40°F to 140°F with 200°F boiler water.Steam boilers require a special rear section with coil opening in order to use two tankless heaters.DANGER: Install mixing valve in hot water supply piping. Water temperature over 125°F can cause severe burns instantly or death from scalds.
PLACE THE BOILER
19
F. APPLY CLEANOUT COVER PLATES
1. Apply the Cleanout Cover Plates on the tops of thesection joints as shown in Figure 2.11.
2. Pre-assemble a steel flat washer and steel nut on thecarriage bolts. Place a carriage bolt into each side ofthe cleanout opening as shown in the figure.
3. Tighten the lower nut securely.
4. Press the Cleanout Plate with insulation over theprotruding carriage bolts until the insulation laysflush against the cast iron.
5. Apply a flat washer and brass nut to the carriagebolt. Draw the brass nuts down until the insulationpresses firmly against the iron.
G. INSTALL FLUE COLLAR
1. (LC) Remove the Flue Collar and Rear ObservationDoor Assembly from the LC Rear Flue Box Carton.(LCE) Remove the Top Flue Outlet Plate, the RearFlue Cover Plate and the Rear Observation DoorAssembly from the LCE Top Flue Outlet Carton.
2. (LC) Attach the Flue Collar to the Back Section with5/16" x 1¹⁄₂" studs, flat washers and hex nutssupplied. See Figure 2.12.(LCE) Attach the Rear Flue Cover Plate to the RearSection with 5/16" x 1¹⁄₂" studs, flat washers and nutssupplied.
3. (LCE) Apply high tack adhesive or spray adhesive(supplied in Section Assembly Kits) to the rope grooveon the bottom of the Top Flue Outlet Plate. Place thehigh temperature rope seal in the groove, overlappingat the ends for a good seal.a) Place the plate over the opening provided by the
three top flue intermediate sections at the front ofthe boiler. NOTE: Top flue outlet plate is marked“FRONT▼” for proper orientation.
b) Secure the plate and compress using the 3/8" tiedown assembly, nuts and washers provided. SeeFigure 2.13.
c) Inspect the finished seal, particularly where theplate crosses the section joints.
d) The correct Top Flue Outlet Plate for the LCEboiler is:
• LCE-13 thru LCE-17 use the 14" flue opening,part number LCE-5007, Carton D
• LCE-18 thru LCE-24 use the 16" flue opening,part number LCE-5007-1, Carton E
4. Attach the Rear Observation Door to the RearSection with four (4) 5/16"-18 x 3/4" hex head boltsprovided.
PLACE THE BOILER
Figure 2.12: Rear Flue Collar Attachment Figure 2.13: Top Flue Collar Attachment
Figure 2.11: Install Cleanout Cover Plates
20
H. INSTALL FLUE BAFFLES
1. Remove the Front Cleanout Plate from FrontSection.
2. Open Baffles carton. Remove Baffles. For LC Only –Save Ceramic Fiber Liner for Section I. Save RatingLabel for Chapter 4. Models LCE-13 through LCE-20 do not require baffles.
3. Place baffles as shown in Figure 2.14. Three of theseare special stainless steel baffles, identified with a1/4" hole punched in each end. These baffles mustbe placed in the lowest row of tubes.
4. Install the Front Cleanout Plate.
I. INSTALL CHAMBER LINER
1. (LCE) Remove Ceramic Fiber Liner from JacketCarton E. Place the liner on the floor of thecombustion chamber. Place the front end of the linerflush with the inside of the Front Section. The liner is24 inches wide. It will not extend all the way to therear of the boiler on all boiler sizes. No adhesive isrequired, just press the liner down firmly.
PLACE THE BOILER
Figure 2.14: Flue Baffle Locations
21
A. PREPARATION
1. The boiler must be pressure tested as outlined in thechapter “Place the Boiler Sections” of this manual.
2. The Supply and Return piping can be installedbefore installing the jacket. Use nipples long enoughto extend through the jacket.
B. SUPPLY AND RETURN PIPING
1. See Figure 3.3 for piping illustration.
2. Install Top connections sized per Table 3.1.a) Model LC-04 requires one riser off the Rear
Section. Plug the 4" tapping in the top of theFront Section.
b) Models LC-05 through LC-10 require two risers,one off the Front and one off the Rear Section.
c) Models LC-11 and LC-12 require three risers,one each off the Front and Rear Sections plusone off the Tapped Intermediate Section.
d) LCE models require three or more risers.
3. Size the Header per Table 3.1. Pipe the header atleast 24 inches above the normal boiler water line.See Figure 3.1. This is required to prevent waterfrom carrying over into the header and then to thesystem.
4. Figure 3.3 shows the Supply and Return piping forParallel Flow Gravity systems and all Pumped ReturnSystems.
5. Counterflow Gravity systems require the boiler steamline to enter the top of the steam main. SeeFigure 3.2 for this special case.
6. Do not reduce the size or number of risersshown. These are required for reliable operation ofthe boiler. If the risers are undersized or incorrectlyplaced, a sloped water line can occur in the boiler,causing possible overheating of some sections.
7. Pipe the Header with an offset as shown in thedrawings. This offset prevents the expansion andcontraction of the Header from damaging the boilersections.
8. Always locate the Steam Supply take-offbetween the Equalizer and the last BoilerRiser. (See PB Heat, LLC's “Steam InstallationSurvey” for discussion). Locating the steam supplybetween the risers will cause water carryover to thesystem.
9. Do not use a bull head tee to provide steam supplyand equalizer connections. This will cause water levelbounce and carryover.
C. LOW SYSTEM TEMPERATURE
1. The use of a Hartford loop is recommended in allinstallations. See Figure 3.1. The loop providesadditional reliability for the system.
2. A check valve must still be installed on the pumpdischarge of all pumped return systems.
3. PIPE THE BOILER
Figure 3.1: Supply and Return Connections, Skim Piping, Hartford Loop
PIPE THE BOILER
22
3. On pumped return systems, install a boiler cock afterthe pump to allow throttling of the pump discharge.The pressure after the boiler cock should be no morethan 5 psig above the boiler operating pressure.Pumping the water into the boiler too fast will causecollapse of the water level and level control problems.
4. Size the equalizer per Table 3.1. Models LC-11, LC-12 and LCE-13 through LCE 24 require two returnconnections to the boiler off of the equalizer line.
5. Pipe the Hartford loop tee so the inside top of theclose nipple is 2 to 4 inches below the normal boilerwater line. See Figure 3.1.
6. If the pump discharge is looped overhead, above theboiler water line, install spring-loaded check valves atboth the pump discharge and the connection to theboiler return.
D. MULTIPLE BOILER INSTALLATIONS
1. Figure 3.4 shows typical piping for multiple boilerGravity Return systems. Figure 3.5 show typicalpiping for multiple boiler Pumped Return Systems.
2. Provide separate feed lines for multiple boilerpumped return systems. Use either separate feedpumps or solenoid or motorized valves to isolatefeeding of the boilers. This is needed to providereliable level control and avoid nuisanceperformance problems.
3. Condensate return units are not effective for multipleboiler installations since they do not respond to theneeds of the boilers. always use Boiler Feed Units.
4. Install a Float and Thermostatic trap at the boilerwater level on each of the mulitple boilers on apumped return system. This prevents flooding of idleboilers due to condensation of steam.
Figure 3.2: Supply and Return Piping –Counterflow Gravity Systems
PIPE THE BOILER
Table 3.1: Header, Risers & Equalizer Sizing
ModelGrossOutputMBH
End SectionRisers
Intermediate SectionRisers Equalizer
(Inches)
HeaderSize
(inches)Number Size(inches) Number Size
(inches)
LC-04LC-05RLC-05
547649707
122
433
–––
–––
222
455
LC-06LC-07LC-08
86810291189
222
444
–––
–––
22¹⁄₂
2¹⁄₂
556
LC-09LC-10LC-11LC-12
1350151116721832
2222
4444
––11
––33
2¹⁄₂
2¹⁄₂
33
6666
LCE-13LCE-14LCE-15
196621252284
222
444
122
333
333
688
LCE-16LCE-17LCE-18
244426032763
222
444
233
333
344
888
LCE-19LCE-20LCE-21
292230823256
222
444
344
333
444
888
LCE-22LCE-23LCE-24
343036043777
222
444
444
333
444
888
23
PIPE THE BOILER
Figure 3.3: Supply and Return Piping – Pumped Return and Parallel Flow Gravity Systems
24
PIPE THE BOILER
Figure 3.5: Piping Multiple Boilers, Typical, Pumped Return Systems
Figure 3.4: Piping Multiple Boilers, Typical, Gravity Return Systems
25
A. PREPARE THE PARTS
1. Collect all the jacket cartons: Jacket Front & BackCarton plus Jacket Side & Top Cartons. Seethe Shipping List in the front of this manual for thejacket cartons required. The cartons contain thejacket parts and screws. The jacket panels are pre-insulated.
2. Remove all needed knockouts from the jacket partsbefore beginning assembly.
B. APPLY JACKET SIDES AND CORNERS
1. See Figure 4.2 for details.
2. The Side Panels can be used on either side of the boiler.
3. Place the Jacket Side Panels on each side leanedagainst the Boiler Sections.
4. On Models LC-08 through LC-12, each side usestwo panels. Place the panels so the seam is centeredon the Tapped Intermediate Section. On LCEmodels, place panels in the sequence shown in Table 4.1.
5. On boilers with two or more Jacket Side Panels perside, join the panels together with #10 x 1/2" sheetmetal screws. Also attach the Jacket Side PanelReinforcing Angle inside the jacket at the bottom ofthe seam.
6. Attach the Left Front Corner Panel to the Left SidePanel with #10 x 1/2" sheet metal screws.
7. Attach the Right Front Corner Panel to the RightSide Panel with #10 x 1/2" sheet metal screws.
C. APPLY JACKET FRONT PANELS
1. Attach the Upper Front Panel to the Right and LeftFront Corner Panels with #10 x 1/2" sheet metalscrews.
2. Attach the Middle Front Panel and Lower Front Railin the same manner.
3. Position the Jacket Assembly with the front panelspushed up against the front section. You will needthe jacket in this position to install the BurnerMounting Plate.
D. APPLY JACKET REAR PANEL
1. Attach the Rear Jacket Panel to the Jacket SidePanels with #10 x 1/2" sheet metal screws.
E. APPLY JACKET TOP PANELS
1. Attach the Top Front Panel to the Sides and UpperFront Panel with #10 x 1/2" sheet metal screws.
2. Models LC-08 through LC-12 use two Jacket TopPanels. Place them on top with the seam at the samepoint as the side panels. Join them at their seamwith #10 x 1/2" sheet metal screws. On LCE models,place panels in the sequence shown in Table 4.1.
3. Attach the Jacket Top Panel to the Jacket Top FrontPanel with #10 x 1/2" sheet metal screws.
4. Attach the Top Rear Panel to the Jacket Top Panelwith #10 x 1/2" sheet metal screws.
5. Finish by placing #10 x 1/2" sheet metal screws inthe remaining holes along the Jacket Top Panelflanges, into the Jacket Side Panels.
F. APPLY PLATES AND LABELS
1. Mount Boiler Rating Plates and Agency Plates on theUpper Jacket Front Panel as shown in Figure 4.1.
2. Secure metal plates with #6 x 1/4" sheet metalscrews. Apply all adhesive-backed labels.
4. ASSEMBLE THE JACKET
Figure 4.1: Location of Rating, Agency andInstruction Plates on Jacket FrontTop Panel
Table 4.1: Jacket Top & Side Panel Placement
LCE-13LCE-14LCE-15LCE-16LCE-17LCE-18LCE-19LCE-20LCE-21LCE-22LCE-23LCE-24
Model
Locate Jacket Top and Side Panels inthe Position Below
(Numbers are from Rear to Front)
5(Front) 4 3 2 1
(Rear)
–––––––EEEEE
––––EEEAABBC
EEEEABCABBBB
BBBCBBBBBBBB
ABCCBBBBBBCC
ASSEMBLE THE JACKET
26
ASSEMBLE THE JACKET
Figure 4.2: Jacket Assembly
27
VENTING/INSTALL THE BURNER
5. VENTING
Refer to Chapter 1, Preinstallation, Section D. Chimneyor Vent for installation requirements. Refer toChapter 9, Starting the Boiler, Section C. Run BurnerCheck Out for damper settings and draft requirements.
6. INSTALL THE BURNER
A. BURNER APPLICATION
1. Refer to Burner Spec and Data Sheets for the Oiland Gas/Oil Burners pre-tested with Series LC/LCE™boilers.
2. Make sure the nozzle sizing and spray pattern matchthose given in the spec and data sheets.
3. See Figure 6.1 and Table 6.1 for combustionchamber dimensions.
B. INSTALL BURNER MOUNTING PLATE
1. The Burner Mounting Plate is made to fit the burnerbeing used. Burners vary in bolt pattern for theflange, burner tube diameter, insertion length andnear-tube configuration. Make sure the front plate iscorrect for your burner if purchased separately fromthe boiler.
2. Remove the Burner Mounting Plate and HardwareBag from the crate.
3. Screw (7) 3/8"-16 x 2 1/4" studs into the holes in thefront section around the chamber opening.
4. Secure the Burner Mounting Plate to the frontsection with the flat washers and hex nuts.
C. MOUNT THE BURNER
1. Remove the Burner from its crate. Read the burnerinstructions.
2. Insert (4) 3/8"-16 x 1 1/4" studs supplied with BurnerMounting Plate into the front plate holes.
3. Place the high temperature gasket on the burnerfront plate and secure the burner to the front platewith 3/8" flat washers and hex nuts.
4. If the burner is supplied with a pedestal, install it tothe burner per the Burner Manufacturer’sInstructions. The pedestal provides additionalsupport and prevents the burner from sagging.
28
INSTALL THE BURNER
Figure 6.1: Combustion Chamber Layout – See Table 6.1 for Dimensions
Model
ChamberLength
“A”(Inches)
Burner Front Plate Extension Past Jacket (Inches)
BeckettGas
BeckettOil Carlin Gordon-
PiattPowerFlame Webster
LC-04LC-05RLC-05
18⁷⁄₈
23¹⁵⁄₁₆
23¹⁵⁄₁₆
1¹⁄₈
1¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
1¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
LC-06LC-07LC-08
2934¹⁄₁₆
39¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
6¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
1¹⁄₈
6¹⁄₈
6¹⁄₈
1¹⁄₈
LC-09LC-10LC-11LC-12
44³⁄₁₆
49¹⁄₄
54⁵⁄₁₆
59³⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
LCE-13LCE-14LCE-15
64⁷⁄₁₆
69¹⁄₂
74⁹⁄₁₆
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
LCE-16LCE-17LCE-18
79⁵⁄₈
84¹¹⁄₁₆
89³⁄₄
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈ 1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
LCE-19LCE-20LCE-21
94¹³⁄₁₆
99⁷⁄₈
104¹⁵⁄₁₆
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
LCE-22LCE-23LCE-24
110
115¹⁄₁₆
120¹⁄₈
1¹⁄₈
1¹⁄₈
N/A
1¹⁄₈
N/AN/A
1¹⁄₈
1¹⁄₈
N/A
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
1¹⁄₈
29
A. GENERAL
1. Read the Burner Instruction Manual, supplied withthe boiler or with the burner if purchased separately.Review applicable code requirements for burner andfuel piping installations.
2. Install piping to allow removal of burner and accessto combustion chamber for cleaning or service.
B. INSTALL FUEL OIL PIPING
1. Place the fuel oil tank and install the piping inaccordance with NFPA-31 and all other applicablecodes.
2. General Guidelines for Oil Pipinga) Follow the guidelines in the Burner Manual for
sizing oil lines. Never use smaller than 1/2" ODcopper tubing.
b) Install manual shut-off valves on the suction lineat the burner and at the oil line entrance to thebuilding. If installing a shut-off valve on thereturn line, you must provide an oil pressurerelief valve piped ahead of the shut-off valve anddischarged to the tank to prevent over-pressureconditions.
c) Install a two-pipe oil distribution system whenpossible. It will improve the reliability of the oildelivery to the burner.
d) Use flare fittings when using copper tubing.
e) Provide an oil line filter in the suction line. Sizethe filter for the suction gear capacity of theburner oil pump if running a two-pipe system.
f) If burner is above the top of the fuel oil tank,install a check valve on the oil suction line at theburner to prevent oil from evacuating the line. Ifburner is below the top of the tank, install ananti-siphon device to prevent oil flow should theoil line break.
C. INSTALL GAS SUPPLY PIPING
1. Size the piping as required by the National Fuel GasCode, ANSI Z223.1 or as required by local codes.a) Use Table 7.1 for sizing of natural gas for a
system pressure drop of 0.3 inch water column.
2. The standard gas train is designed for a maximumpressure of 1/2 psig (14 inches water column). Makesure the system regulator will not allow a higherpressure to the Gas Control Train under anyconditions.
3. The minimum gas supply pressure is listed on theBurner Rating Plate. Make sure the system regulatorand the piping are sized and adjusted properly toprovide this pressure under all conditions.
4. Install a Service Valve, Sediment Trap and GroundJoint Union at the supply connection to the GasControl Train as shown in Figure 7.1. These are notsupplied with the boiler. Install them in accordancewith local codes.
5. Use only pipe joint compounds rated for use withLiquefied Petroleum Gases.
D. TEST GAS SUPPLY PIPING
1. ISOLATE THE BOILER GAS CONTROL TRAINFROM THE SYSTEM DURING TEST:a) Test pressure 1/2 psig or less – Close the Manual
Shut-Off Valve on the Boiler Gas Control Train.
b) Test pressure over 1/2 psig – Disconnect the gassupply piping upstream of the Boiler ManualShut-Off Valve.
CONNECT FUEL PIPING
7. CONNECT FUEL PIPING
Figure 7.1: Gas Supply Connection to Boiler
Do not expose the Gas Control Train to excessivepressure. The gas valves can be damaged. This couldresult in explosion hazard and severe personal injuryor death.
Do not test gas supply piping with open flame. Use asoap suds mixture brushed onto the pipe joints totest for leaks.
WARNING
30
CONNECT FUEL PIPING
Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet Per Hour of Natural Gas for Pressure Drop of 0.3 inch Water Column.
10
20
30
40
50
60
70
90
100
150
1050
730
590
500
440
400
350
320
305
250
1600
1100
890
760
670
610
560
490
460
380
3050
2100
1650
1450
1270
1150
1050
930
870
710
4800
3300
2700
2300
2000
1850
1700
1500
1400
1130
8500
5900
4700
4100
3600
3250
3000
2600
2500
2000
17500
12000
9700
8300
7400
6800
6200
5400
5100
4100
44000
31000
25000
22000
20000
18000
17000
15000
14000
11500
Pipe Length(Feet)
1-1/4"Pipe
1-1/2"Pipe
2"Pipe
2-1/2"Pipe
3"Pipe
4"Pipe
6"Pipe
Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches water column. No allowance is needed forpipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:
Specific Gravity
Multiply Capacity by: 1.10
0.50
1.04
0.55
1.00
0.60
0.962
0.65
0.926
0.70
31
A. INSTALL SAFETY VALVES
1. Pipe the Pop Safety Valve on a tee mounted in the2¹⁄₂" tapping located on the upper left side of theRear Section. Make sure the relief valve sizing meetslocal code requirements.
2. Install a 2" ball valve for skimming off the end of thetee as shown in the piping drawings in this manual.
B. INSTALL BLOWDOWN VALVES
1. Install a 1¹⁄₂" full port ball valve off of the returnconnection as shown in the “Pipe the Boiler” sectionof this manual. See Figure 8.1.
2. Pipe the valve discharge to a floor drain if availableor apply a nipple and cap to close off when not inuse.
C. INSTALL LOW WATER CUTOFF(S)
1. Mount a float type Low Water Cutoff and GaugeGlass in the tappings provided in the side of the frontsection or the side and top of the first intermediatesection.
2. Do not apply piping which would raise or lower thelocation of the cutoff relative to the tappings in theboiler. Raising the water level over the design heightwill cause water carryover to the system.
3. For correct location of typical low water cutoff/feederor low water cutoff/pump control, see Figures 8.4through 8.7.
4. See Figure 8.2 for the location of control connectiontappings.
5. Provide each float low water cutoff with a blowdownvalve. Pipe the blowdown away from traffic to a floordrain if available. The blowdown valve is requiredfor proper maintenance of the control.
6. Maintain a height of 46¹⁄₂" from boiler foundation tothe normal water level.
7. When using Multiple Float Type Controls: Alwayspipe the controls off of the same tappings to theboiler. Do not mount on different ends of the boileror in different tappings. This can cause erraticoperation and nuisance problems with the controls.
D. INSTALL PRESSURE CONTROLS
1. Pipe the Steam Pressure Gauge and Boiler Limit andOperating Pressure Controls as shown in Figure 8.3.Connect the control assembly to the 1/2" tapping inthe front section.
E. PIPE TANKLESS HEATER(S)
1. Connect piping to any installed tankless heaters. SeeFigure 8.8 for suggested piping for single coils andFigure 8.9 for suggested piping for dual coils.
F. CONNECT SUPPLY WIRING
1. Install all wiring in accordance with local codes, theNational Electrical Code and other controllingagencies or governing bodies.
2. Use #14 gauge or heavier wire for supply wiring.Protect the circuit with a fused disconnect switch (byothers) and a grounded neutral.
3. Mount an electrical junction box on the boiler FrontPanel for connection of supply wiring anddistribution to the boiler controls.
4. Follow the instructions in the Burner Manual and theWiring Diagrams supplied with the burner and theboiler.
INSTALL CONTROLS, TRIM & WIRING
8. INSTALL CONTROLS, TRIM & WIRING
Pipe the discharge of the Safety Relief Valve awayfrom any traffic area, preferably to a floor drain. Thisis necessary to prevent injury should the valvedischarge.
Pipe the discharge full size of valve outlet.
CAUTIONMake sure that the ignition system components,electrical controls, junction boxes and electricalpanels are protected from water (dripping, spraying,rain, etc.) during boiler operation and service (trapservicing, control replacements or other).
CAUTION
The boiler/burner must be electrically grounded inaccordance with the requirements of the authorityhaving jurisdiction, or in the absence of suchrequirements, with the current edition of the NationalElectrical Code, ANSI/NFPA Number 70.
NOTICE
32
G. INSTALL CONTROL WIRING
1. Wire the boiler according to the wiring diagramssupplied with the burner and the boiler (in the BoilerEnvelope).
2. Low Energy Safety Control wiring, if used, mustfollow the contour of the boiler. Some local codesmay require that all wiring, even low voltage, berouted in conduit.
3. Install line voltage wiring in conduit.
4. Do not install single pole switches, including safetycontrols, in a grounded line.
INSTALL CONTROLS, TRIM & WIRING
Figure 8.1: Blowdown Valve, Safety Valve and Skim Valve Piping
33
INSTALL CONTROLS, TRIM & WIRING
Figure 8.2: Control and Pipe Tapping Locations
34
INSTALL CONTROLS, TRIM & WIRING
Figure 8.3: Control and Pipe Tapping Locations
35
INSTALL CONTROLS, TRIM & WIRING
Figure 8.5: Optional Model 47-2 Low Water Cutoff/Feeder – Use only up to Model LC-07
Figure 8.4: Optional Model 67PE2 Float Low Water Cutoff
36
INSTALL CONTROLS, TRIM & WIRING
Figure 8.6: Optional Float Type Pump Control/Low Water Cutoff, Model 157
37
INSTALL CONTROLS, TRIM & WIRING
Figure 8.7: Optional Feeder/Low Water Cutoff, Type 51-2
38
INSTALL CONTROLS, TRIM & WIRING
Figure 8.9: Suggested Piping – Dual Tankless Coil Installation
Figure 8.8: Suggested Piping – Single Tankless Coil Installation
39
A. CHECK THE PIPING
1. Steam Pipinga) The Boiler must have been hydrostatically tested.
b) Check the attached piping for joint tightness.
c) Continue monitoring as you proceed throughstart up.
2. Gas Pipinga) Make sure the gas system piping and the
connections to the boiler Gas Control Train(s)have been leak tested.
b) After the boiler is in operation, check thetightness of all joints in the boiler gas piping witha soap suds solution.
c) Purge the gas piping of all air up to the boilerGas Control Train.
3. Oil Pipinga) Check the oil piping visually. Make sure all joints
are tight.
b) When the burner is firing, check the suction lineand return line pressures.
c) If the pressure exceeds the allowable pressure inthe Burner Manual or if the suction line vacuumis higher than allowable, correct the piping asneeded to bring the suction line and return linepressures within acceptable range.
d) Excess pressure can cause pump seal failures.Excess vacuum will cause fuel flow problemswith the burner oil pump.
B. FILL THE BOILER
1. Fill the boiler to the normal water line.a) Gravity Systems and Pumped Return with
Condensate Units – Fill to 46¹⁄₂" above the boilerfoundation (center of gauge glass).
b) Pumped Return with Boiler Feed Unit - Fill theboiler using the boiler feed unit. Fill level willdepend on the control being used, but should be46¹⁄₂" above the boiler foundation (just belowcenter of gauge glass) when the pump stops.
C. RUN BURNER CHECK-OUT
1. Before firing the burner, slide the Slide Gate Damperon the rear flue box all the way down (full open) onLC’s or open the LCE Draft Damper until the handleis parallel to the vent pipe (full open).
2. Follow the instructions in the Burner Manual forstarting the burner, adjusting air openings and fuelrates. Perform ignition system and flame supervisorycontrol test and checkout as described in the manual.
3. After burner is set at rate, close the damper until thepressure reading at the test opening in the rear flue boxor draft damper is between 0" wc and 0.1" wc positive.See Table 9.1 for typical overfire pressure (measuredat the burner front plate) and boiler draft loss.
When a barometric draft regulator is installed in theventing system, adjust the boiler damper for 0" wcpressure reading at the damper. Adjust the draftregulator for -0.05" wc draft between the boilerdamper and the draft regulator.
4. Adjust the burner as needed for a CO2 reading of:a) Oil burners: CO2 approximately 12.5% or 1%
less than the level at which the smoke readinggoes above a trace on the Bacharach scale.
b) Gas burners: 9% to 10% with CO less than 50 ppm.
5. Inspect all flue gas joints (sections, attachments,breeching and vent) for gas tightness. Remove thejacket panels in order to thoroughly inspect all ropeseal joints between the sections.
D. CHECK BOILER CONTROLS
1. Limit and Operating Temperature Controlsa) Lower the setting of each control until the burner
shuts down.
2. Low Water Cutoffsa) Test probe type controls by using the Push-to-Test
Button.
b) Test float type controls.
3. Follow additional instructions in the Burner Manualfor proving the burner component operation.
4. Check all controls to make sure they functioncorrectly.
5. After all controls have been proven, set theOperating and High Limit Temperature Controls tothe temperatures desired.
E. CLEAN THE BOILER
1. Clean the boiler as described below no later thanone week after the initial start-up. Cleaning will bemore effective if the boiler operates a day or two toloosen sediment and impurities in the system.
9. STARTING THE BOILER
STARTING THE BOILER
Cleaning the boiler requires the use of very hot waterand corrosive chemicals. Use care when handling toprevent injury.
WARNING
On installations with high draft, do not leave theboiler with a negative draft reading at the rear fluebox or draft damper. High negative draft can pull theflame up into the boiler crown sheet and overheat theiron. This can result in cracked sections or shortenedboiler life.
CAUTION
40
2. The boiler must be cleaned to remove anyaccumulation of oil, grease, sludge, etc. that may bein the system. These substances can cause foamingand surging of the boiler water, producing unstablewater line and water carryover to the system.
3. The piping for a 2" Skim Valve must be done asshown in this manual, with the skim valve mountedoff the Pop Safety Valve tee on the rear of the boiler.
4. Use common washing soda (such as Arm and HammerSuper Washing Soda). Mix the soda with water in a 10quart pail. Use a proportion of one pound of washingsoda for each 800 square feet EDR net boiler rating.Remove the Pop Safety Valve and pour the washingsoda solution into the boiler through the Pop SafetyValve tee. Replace Pop Safety Valve.
5. Connect a 2 inch drain line off of the Skim Valve,run to a point of safe discharge.
6. Close all valves to the system. Provide a means ofcontinuous fresh water to the boiler for the cleaningprocess.
7. Open the Skim Valve. Fill the boiler until waterbegins to flow out of the valve.
8. Turn burner on and allow the boiler water to heat upto just below steaming (180° to 200° F). Cycle theburner to maintain temperature during skimming. Donot allow the boiler to steam. Steaming mixes up thecontaminants in the water instead of floating them atthe surface.
9. Open the make-up water valve to continuously feedwater to the boiler. Allow water to flow out the skimtapping.
10. Continue skimming the boiler until the water flowingfrom the skim tapping flows clear. This will takesome time, possibly several hours for a dirty system.
11. After skimming is complete, close the skim valve andturn off the boiler.
12. Close the make-up water valve and open the boilerblowdown valves.
13. Drain the boiler completely, then refill and drainagain one or two times to make sure all of the sodahas been washed out.
14. Restore piping to normal. Pipe a nipple and cap inthe skim valve.
15. Note: If the gauge glass becomes dirty again, thisindicates more contaminants have worked loose inthe system. Repeat the cleaning and skimmingprocess as needed to clean the system.
STARTING THE BOILER
Table 9.1: Typical Combustion Chamber Pressure and Boiler Draft Loss
LC-04LC-05RLC-05LC-06LC-07LC-08LC-09LC-10LC-11LC-12
LCE-13LCE-14LCE-15LCE-16LCE-17LCE-18LCE-19LCE-20LCE-21LCE-22LCE-23LCE-24
+ 0.22+ 0.22+ 0.24+ 0.26+ 0.27+ 0.28+ 0.29+ 0.30+ 0.31+ 0.32+ 0.24+ 0.25+ 0.26+ 0.27+ 0.28+ 0.29+ 0.30+ 0.31+ 0.31+ 0.31+ 0.32+ 0.32
Model Boiler Draft Loss(Inches w.c.)
Combustion Chamber Pressurewith 0.1" w.c. at Rear Flue Box Test Port
(Inches w.c.)
0.120.120.140.160.170.180.190.200.210.220.140.150.160.170.180.190.200.210.210.210.220.22
NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger,deposits in the flueways, actual burner firing rate and excess air conditions. Use the above numbers as a general guide only. If the measured draftloss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate.
Do not leave the boiler unattended while firing.
Take great care not to allow the water level to dropbelow the bottom of the gauge glass or to allow freshwater make-up to flow in too fast. This will avoid thepossibility of causing the boiler sections to fracture.
CAUTION
WARNING
Product Safety InformationRefractory Ceramic Fiber Product
This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF,when inhaled, have been classified by the International Agency for Research on Cancer(IARC), as a possible carcinogen to humans. After the RCF materials have been exposed totemperatures above 1800°F (982°C), they can change into crystalline silica, which has beenclassified by the IARC as carcinogenic to humans. If particles become airborne duringservice or repair, inhalation of these particles may be hazardous to your health.
Avoid Breathing Fiber Particulates and Dust
Suppliers of RCF recommend the following precautions be taken when handling thesematerials:
Precautionary Measures:Provide adequate ventilation.Wear a NIOSH/MSHA approved respirator.Wear long sleeved, loose fitting clothing and gloves to prevent skin contact.Wear eye goggles.Minimize airborne dust prior to handling and removal by water misting the material andavoiding unnecessary disturbance of materials. Wash work clothes separately from others. Rinse washer thoroughly after use.Discard RCF materials by sealing in an airtight plastic bag.
First Aid Procedures:Inhalation: If breathing difficulty or irritation occurs, move to a location with fresh clean air.Seek immediate medical attention if symptoms persist.Skin Contact: Wash affected area gently with a mild soap and warm water. Seek immediatemedical attention if irritation persists.Eye Contact: Flush eyes with water for 15 minutes while holding eyelids apart. Do not rubeyes. Seek immediate medical attention if irritation persists.Ingestion: Drink 1 to 2 glasses of water. Do not induce vomiting. Seek immediate medicalattention.
41
10. MAINTENANCE
MAINTENANCE
42
A. PLACING BOILER IN OPERATION
1. Start up the Burner/Boiler per the Burner Manualand the instructions in this manual on starting theboiler.
2. Prove the correct operation of all controls on theboiler and burner as outlined below.
3. Check the operation of the ignition and flameproving controls as described in the Burner Manual.
4. Test the limit and operating controls to assure theyare operating correctly.
5. Inspect and test all low water cutoffs.
6. Test the safety relief valve(s) using the proceduregiven by the valve manufacturer on the valve tag.
7. Visually inspect the burner and pilot flames (ifapplicable).
B. TO SHUT DOWN THE BOILER
1. Turn off Burner.
2. Open main line power disconnect switch toboiler/burner.
3. Close fuel shut-off valves.
4. To take boiler out of service if the boiler and systemare not to be used when temperatures are belowfreezing:a) Drain the boiler and system completely and shut
off make-up water supply.
b) Open main line power disconnect switch toboiler/burner. Remove the fuses or secure theswitch so that the power cannot be turned onaccidentally.
c) Be certain that the boiler and system are refilledbefore returning to service. Follow theInstructions in this manual and the LightingInstructions to operate.
d) The system may be filled with a 50% inhibitedpropylene glycol solution for protection down to-35°F. Use only antifreeze solutions specificallydesigned for hydronic use.
C. MAINTENANCE – ANNUAL
1. Before the start of each heating season, inspectand make all necessary adjustments to insure properboiler and burner operation. Use the maintenanceand inspection procedures following.
2. Inspect the Venting Systema) Check the chimney or vent to make sure it is
clean and free from cracks or potential leaks.
b) All joints must be tight and sealed.
c) The vent connector must extend into, but notbeyond the inside edge of the chimney or vent.
3. Inspect the Boiler Areaa) The boiler area must be clean and free from
combustible materials, gasoline or any otherflammable liquids or vapors.
b) The combustion air openings and the areaaround the boiler must be unobstructed.
4. Inspect boiler flueways and burner for cleanliness. Ifcleaning is required, use the following procedure.a) Turn off all electrical power to the boiler.
b) Remove Jacket Middle Front Panel and JacketTop Panels. Remove Front Cleanout Plate andCleanout Cover Plates on each flueway. On LCEboilers, remove the top flue outlet plate and ventpiping as necessary to access the top of thesections.
c) Brush the boiler tube spaces both horizontally(through cleanout openings on ends) andvertically (from top of boiler through cleanoutopenings at flueways).
MAINTENANCE
Do not store or allow combustible or flammablematerials near the boiler. Substantial fire or explosionhazard could result, causing risk of personal injury,death or property damage.
Do not use this boiler if any part of it has been underwater. Immediately call a qualified service technicianto inspect the boiler. Any part of the control system,any gas control or any burner or gas componentwhich has been under water must be replaced.
Should overheating occur or the fuel supply fail toshut off: Shut off the fuel supply at a locationexternal to the boiler. Do not turn off or disconnectthe electrical supply to the pump. Immediately call aqualified service technician to inspect the boiler fordamage and defective components.
WARNING
Before servicing the boiler:
• Turn off all electrical power to the boiler.
• Close the Gas Service Valve and Oil Shut-Off Valve.
• Allow the boiler to cool if it has been operating.
• Label all wires prior to disconnection whenservicing controls. Wiring errors can causeimproper and dangerous operation. Verify properoperation after servicing.
CAUTION
43
d) Remove the Burner and Burner Mounting Plate.Remove any scale or soot from the combustionchamber by means of vacuum cleaning or otheravailable means. Take care not to damage thechamber floor liner or target wall liner.
e) Replace the Front Cleanout Plate, BurnerMounting Plate, Burner and all Cleanout CoverPlates on top of the sections. Make sure allsealing rope and seals are in good condition.Replace sealing rope if necessary.
f) Replace all Jacket Panels.
5. Inspect the boiler and piping for signs of leaks.Check to see if there are signs of heavy make-upwater addition to the system.
6. When placing boiler into operation, follow BurnerManual, all instructions supplied with the boiler andthe instructions in this chapter.
7. Test the operation of all limit controls, float controlsand ignition components as described in Part A,“Placing Boiler in Operation”, of this chapter.
D. MONTHLY MAINTENANCE
1. Inspect the burner and pilot flames as for the annualinspection.
2. Inspect the boiler and system for any signs ofleakage or excessive make-up water usage.
3. Inspect and check the operation of the ventingsystem.
E. DAILY MAINTENANCE
1. Inspect the boiler area to make sure the area is freefrom combustible or flammable materials and thatthere are not obstructions to the flow of air to theboiler or combustion air openings to the room.
2. Make sure there are no signs of abnormal operation,such as overfilling or leakage.
MAINTENANCE
Be very careful when adding water to a hot boiler.Add very slowly or, if possible, allow the boiler tocool naturally before adding water.
If an excessive loss of water occurs, check for a leakin the piping and correct the problem. Excessivemake-up water will cause corrosion and damage tothe boiler.
CAUTION
44
BOILER RATINGS & DIMENSIONS
11. BOILER RATINGS & DIMENSIONSTable 11.1: Series LC/LCE™ Boiler Ratings
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.2 Net water ratings based on an allowance of 1.15.3 Net steam ratings based on an allowance for LC-04 to LC-08=1.333, LC-09=1.323, LC-10=1.310, LC-11=1.298, LC-12=1.290,LCE-13 to LCE-24=1.288.4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.5 Combustion and thermal efficiencies are determined in accordance with BTS 2000 Testing Standard.
Figure 11.1: Tankless Coil Pressure Drops
Series LC/LCE™
BoilerModel
Oil Input¹ GasInput, MBH
GrossOutput, MBH
Net Ratings4 Oil Gas
GPH MBHSteam,
sqftWater²,MBH
Steam³,MBH
CombustionEfficiency5, %
ThermalEfficiency5, %
CombustionEfficiency5, %
ThermalEfficiency5, %
LC-04-S 4.75 665 686 547 1,708 — 410 83.7 82.2 81.2 79.8
LC-04-W 4.75 665 686 547 — 476 — 84.2 82.9 81.6 80.4
LC-05R 5.60 784 808 649 2,029 564 487 83.7 82.8 81.2 80.3
LC-05 6.10 854 881 707 2,208 615 530 83.7 82.8 81.2 80.3
LC-06 7.50 1,050 1,077 868 2,713 755 651 83.7 83.1 81.1 80.6
LC-07 8.80 1,232 1,273 1,029 3,217 895 772 83.6 83.3 81.1 80.8
LC-08 10.20 1,428 1,469 1,189 3,717 1,034 892 83.6 83.5 81.1 81.0
LC-09 11.60 1,624 1,664 1,350 4,250 1,174 1,020 83.6 83.6 81.1 81.1
LC-10 12.80 1,792 1,860 1,511 4,804 1,314 1,153 83.6 83.7 81.1 81.2
LC-11 14.20 1,988 2,056 1,672 5,367 1,454 1,288 83.6 83.8 81.1 81.3
LC-12 15.60 2,184 2,252 1,832 5,917 1,593 1,420 83.6 83.9 81.1 81.4
LCE-13 17.00 2,380 2,464 1,966 6,358 N/A 1,526 83.5 82.2 81.0 79.8
LCE-14 18.40 2,576 2,657 2,125 6,875 N/A 1,650 83.5 82.5 81.0 80.0
LCE-15 19.80 2,772 2,850 2,284 7,388 N/A 1,773 83.5 82.6 81.0 80.2
LCE-16 21.00 2,940 3,043 2,444 7,908 N/A 1,898 83.5 82.8 81.0 80.3
LCE-17 22.50 3,150 3,236 2,603 8,421 N/A 2,021 83.5 82.9 81.0 80.4
LCE-18 24.00 3,360 3,429 2,763 8,938 N/A 2,145 83.5 83.1 81.0 80.6
LCE-19 25.00 3,500 3,622 2,922 9,454 N/A 2,269 83.5 83.2 81.0 80.7
LCE-20 26.50 3,710 3,815 3,082 9,971 N/A 2,393 83.5 83.3 81.0 80.8
LCE-21 28.00 3,920 4,027 3,256 10,533 N/A 2,528 83.6 83.3 81.1 80.8
LCE-22 29.50 4,130 4,239 3,430 11,096 N/A 2,663 83.6 83.4 81.1 80.9
LCE-23 31.00 4,340 4,451 3,604 11,658 N/A 2,798 83.7 83.5 81.2 81.0
LCE-24 32.50 4,550 4,663 3,777 12,217 N/A 2,932 83.7 83.5 81.2 81.0
BoilerH.P.
16.3
16.3
19.4
21.1
25.9
30.7
35.5
40.3
45.1
50.0
54.7
58.7
63.5
68.2
73.0
77.7
82.5
87.3
92.1
97.3
102.5
107.7
112.8
BOILER RATINGS & DIMENSIONS
Figure 11.2: Series LC™ Dimensional Diagram
Figure 11.3: Series LCE™ Dimensional Diagram
45
46
BOILER RATINGS & DIMENSIONS
SE
RIE
S L
C/L
CE
BO
ILE
R D
IME
NS
ION
S
Boi
ler
Mod
elN
umbe
r
Jack
etSu
pply
Pip
ing
Ret
urn
Pipi
ngR
iser
Tap
ping
Loc
atio
ns*
Vent
Loc
atio
nVe
nt
Leng
th“A
”R
iser
sSi
zeR
ecom
.H
eade
r
End
Sec
t.Ta
ppin
gs“E
”
Inte
rmed
iate
Sec
tion
Tapp
ing
“B”
“C”
Dia
met
er“D
”M
inim
umH
eigh
tE
qual
izer
“E1”
“E2”
“E3”
“E4”
LC-0
425
-15/
16"
14"
4"2"
16-1
/2"
––
––
18-1
/4"
54-1
/8"
9"3'
LC-0
5R31
"2
3"5"
2"21
-9/1
6"–
––
–18
-1/4
"54
-1/8
"9"
3'LC
-05
31"
23"
5"2"
21-9
/16"
––
––
18-1
/4"
54-1
/8"
9"3'
LC-0
636
-1/1
6"2
4"5"
2"26
-5/8
"–
––
–18
-1/4
"54
-1/8
"10
"3'
LC-0
741
-1/8
"2
4"5"
2-1/
2"31
-11/
16"
––
––
18-1
/4"
54-1
/8"
10"
3'LC
-08
46-5
/16"
24"
6"2-
1/2"
36-1
3/16
"–
––
–18
-1/4
"54
-1/8
"10
"3'
LC-0
951
-3/8
"2
4"6"
2-1/
2"41
-7/8
"–
––
–18
-1/4
"54
-1/8
"12
"3'
LC-1
056
-7/1
6"2
4"6"
2-1/
2"46
-15/
16"
––
––
18-1
/4"
54-1
/8"
12"
3'LC
-11
61-1
/2"
2, 1
4", 3
"6"
3" (
2 R
et.)
52"
26"
––
–18
-1/4
"54
-1/8
"12
"3'
LC-1
266
-9/1
6"2,
14"
, 3"
6"3"
(2
Ret
.)57
-1/8
"26
"–
––
18-1
/4"
54-1
/8"
12"
3'LC
E-1
371
-3/4
"2,
14"
, 3"
6"3"
62-3
/16"
36-3
/16"
––
–16
"20
-1/2
"14
"3'
LCE
-14
76-1
3/16
"2,
24"
, 3"
8"3"
67-1
/4"
20-1
5/16
"20
-5/1
6"–
–16
"20
-1/2
"14
"3'
LCE
-15
81-7
/8"
2, 2
4", 3
"8"
3"72
-5/1
6"26
"20
-5/1
6"–
–16
"20
-1/2
"14
"3'
LCE
-16
86-1
5/16
"2,
24"
, 3"
8"3"
77-7
/16"
26"
25-7
/16"
––
16"
20-1
/2"
14"
3'LC
E-1
792
-1/8
"2,
34"
, 3"
8"4"
82-1
/2"
20-1
5/16
"20
-5/1
6"15
-1/4
"–
16"
20-1
/2"
14"
3'LC
E-1
897
-3/1
6"2,
34"
, 3"
8"4"
87-9
/16"
20-1
5/16
"20
-5/1
6"20
-5/1
6"–
16"
20-1
/2"
16"
3'LC
E-1
910
2-1/
4"2,
34"
, 3"
8"4"
92-5
/8"
20-1
5/16
"20
-5/1
6"25
-7/1
6"–
16"
20-1
/2"
16"
3'LC
E-2
010
7-7/
16"
2, 4
4", 3
"8"
4"97
-3/4
"20
-15/
16"
20-5
/16"
15-1
/4"
15-1
/4"
16"
20-1
/2"
16"
3'LC
E-2
111
2-1/
2"2,
44"
, 3"
8"4"
102-
3/16
"20
-15/
16"
20-5
/16"
20-5
/16"
15-1
/4"
16"
20-1
/2"
16"
3'LC
E-2
211
7-9/
16"
2, 4
4", 3
"8"
4"10
7-7/
8"20
-15/
16"
20-5
/16"
20-5
/16"
20-5
/16"
16"
20-1
/2"
16"
3'LC
E-2
312
2-5/
8"2,
44"
, 3"
8"4"
112-
15/1
6"26
"20
-5/1
6"20
-5/1
6"20
-5/1
6"16
"20
-1/2
"16
"3'
LCE
-24
127-
11/1
6"2,
44"
, 3"
8"4"
118-
1/16
"26
"20
-5/1
6"20
-5/1
6"26
"16
"20
-1/2
"16
"3'
*The
se d
imen
sion
s ar
e ap
prox
imat
e.
Table
11.2
:S
eri
es
LC/L
CE™
Boiler
Dim
ensi
ons
47
REPAIR PARTS
12. REPAIR PARTS
Figure 12.1: Series LC™ Boiler Assembly
Repair parts are available from your local PB Heat, LLC distributor or from Parts ToYour Door at 1 (610) 916-5380 (www.partstoyourdoor.com).Note: Remember to include the boiler model number and serial number when ordering parts.
48
REPAIR PARTS
Table 12.1A: Series LC™ Repair Parts
ItemNo. Description Part Selection Information Stock
Code
1 Front Section See Table 1.3 for Stock Code
2 Intermediate Section w/1" Tapping See Table 1.3 for Stock Code
3 Intermediate Section See Table 1.3 for Stock Code
4 Back Section See Table 1.3 for Stock Code
5 Tapped Intermediate Section See Table 1.3 for Stock Code
Upper Flow Port Gasket 2 Required per Flueway 51671
Lower Flow Port Gasket 1 Required per Flueway 51672
6 Tie Rod 4 Required per Flueway 51721
5/8" Diameter High Temp Rope 13 Feet Required per Flueway 55723
7 Ceramic Fiber Base Liner Models LC-04 through LC-12 50862
8 Ceramic Fiber Target Wall 50854
9 Front Cleanout Plate (C.I.) 51162
10 5/16"-18 x 1-1/4" Studs w/Brass Nuts 4 Required
11 Steel Cover Plate 51776
12 Steel Cover Plate 51777
13 Tankless Heater Location 1 Specify Heater Model Number
14 Tankless Heater Location 2 Not Used On Steam
15 Tankless Heater Location 3 (Rear; not shown) Specify Heater Model Number
16 Rubber Gasket Specify Quantity 51800
17 3/8"-16 x 3/4" SS Hex Head Cap Screw Specify Quantity
18 Rear Observation Assembly 90923
19 5/16"-18 x 3/4" Hex Head Cap Screw Specify Quantity
20 Burner Mounting Plate Specify Burner Model
21 3/8"-16 x 2-1/4" Studs with Nuts
22 Flame Observation Assembly 90922
23 3/8"-16 x 1" Studs for Burner Mounting 4 Required
24 1/4"-20 x 1/2" Hex Head Machine Screw 4 Required
25 Cleanout Cover Plate (Steel) 1 Required per Flueway 51772
26 Rear Flue Box w/9" Flue Outlet Models LC-04 and LC-05 86040
Rear Flue Box w/10" Flue Outlet Models LC-06, LC-07 and LC-08 86041
Rear Flue Box w/12" Flue Outlet Models LC-09, LC-10, LC-11 and LC-12 86042
27 Rear Flue Box Stud 5/16"-18 x 1-1/2" 7 Required
28 Rear Flue Box Hi Temp Rope, 1/4" Diameter x 65" Long
29 Side Jacket Panel LC-6000 For Models LC-04 and LC-08
Side Jacket Panel LC-6001 For Models LC-05, LC-08, LC-09 and LC-10
Side Jacket Panel LC-6002 For Models LC-06, LC-10, LC-11 and LC-12
Side Jacket Panel LC-6003 For Models LC-07 and LC-12
30 Left Front Jacket Corner Panel LC-6011
31 Right Front Jacket Corner Panel LC-6010
32 Upper Front Jacket Panel LC-6007
33 Middle Front Jacket Panel LC-6008
34 Lower Front Jacket Rail LC-6009
35 Back Jacket Panel LC-6012
36 Side Jacket Panel Support Angle LC-6014
37 Front Top Jacket Panel LC-6005
Part numbers may be subject to change without notice.
49
REPAIR PARTS
Table 12.1B: Series LC™ Repair Parts (continued)
38
39
Top Jacket Panel LC-6004
Top Jacket Panel LC6004-1
Top Jacket Panel LC-6004-2
Top Jacket Panel LC-6004-3
Rear Top Jacket Panel LC-6006
Single Rib Flue Baffle, Aluminized Steel LC-1018
Triple Rib Flue Baffle, Aluminized Steel LC-1019
Single Rib Flue Baffle, Stainless Steel LC-1020
Triple Rib Flue Baffle, Stainless Steel LC-1021
ItemNo. Description
For Models LC-04 and LC-08
For Models LC-05, LC-08, LC-09 and LC-10
For Models LC-06, LC-10, LC-11 and LC-12
For Models LC-07 and LC-12
Specify Boiler Model Number
Specify Boiler Model Number
Specify Boiler Model Number
Specify Boiler Model Number
Part Selection Information StockCode
50
REPAIR PARTS
Figure 12.2: Series LCE™ Boiler Assembly
51
REPAIR PARTS
Table 12.2A: Series LCE™ Repair Parts
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Front Section
Top Flue Outlet Intermediate Section
Intermediate Section w/1" Tapping
Intermediate Section
Back Section (Closed Back)
Back Section w/Tankless Coil Opening
Tapped Intermediate Section
Upper Flow Port Gasket
Lower Flow Port Gasket
Tie Rod
5/8" Diameter High Temp Rope
Ceramic Fiber Base Liner
Ceramic Fiber Target Wall
Front Cleanout Plate (C.I.)
5/16"-18 x 1-1/4" Studs w/Brass Nuts
Steel Cover Plate
Steel Cover Plate
Tankless Heater Location 1
Tankless Heater Location 2
Tankless Heater Location 3
Rubber Gasket
3/8"-16 x 3/4" SS Hex Head Cap Screw
Rear Observation Assembly
5/16"-18 x 3/4" Hex Head Cap Screw
Burner Mounting Plate
3/8"-16 x 2-1/4" Studs with Nuts
Front Observation Assembly
3/8"-16 x 1" Studs for Burner Mounting
1/4"-20 x 1/2" Hex Head Machine Screw
Cleanout Cover Plate (Steel)
Rear Flue Cover Plate
Rear Flue Cover Stud 5/16"-18 x 1-1/2"
Rear Flue Cover Hi Temp Rope, 1/4" Dia. x 65" Long
Side Jacket Panel LC-6000
Side Jacket Panel LC-6001
Side Jacket Panel LC-6002
Left Front Jacket Corner Panel LC-6011
Right Front Jacket Corner Panel LC-6010
Upper Front Jacket Panel LC-6007
Middle Front Jacket Panel LC-6008
Lower Front Jacket Rail LC-6009
Back Jacket Panel LC-6012
Side Jacket Panel Support Angle LC-6014
Front Top Jacket Panel LC-6005
Top Jacket Panel LC-6004
Top Jacket Panel LC-6004-1
ItemNo. Description
86022
86036
86008
51671
51672
51721
55723
50862
50854
51162
51776
51777
51800
90923
90922
51772
51131
See Table for Stock Code
2 Required per Flueway
1 Required per Flueway
4 Required per Flueway
13 Feet Required per Flueway
For All LCE Boilers
4 Required
Specify Heater Model Number
Not Used On Steam
Specify Heater Model Number
Specify Quantity
Specify Quantity
Specify Quantity
Specify Burner Model
7 Required
4 Required
4 Required
1 Required per Flueway
For All LCE Boilers
5 Required
For Models LCE-13, -17, -20 & -21
For Models LCE-13 to LCE-15, LCE-17 to LCE-24
For All LCE Boilers
For Models LCE-13, -17, -20 & -21
For Models LCE-13 to LCE-15, LCE-17 to LCE-24
Part Selection Information StockCode
Part numbers may be subject to change without notice.
52
REPAIR PARTS
Table 12.2B: Series LCE™ Repair Parts (continued)
38
40
39
41
42
43
44
Top Jacket Panel LC-6004-2
Top Jacket Panel with Flue Opening LC-6022
Rear Top Jacket Panel LC-6006
Top Flue Outlet Plate (14" Flue)
Top Flue Outlet Plate (16" Flue)
5/8" Diameter High Temperature Rope
3/8" Diameter Tie Down Assembly
Draft Damper, 14"
Draft Damper, 16"
Baffles
ItemNo. Description
51132
51133
55723
51604
90523
90524
86113
For Models LCE-15, -16, -19, -23 & -24
For All LCE Boilers
For Models LCE-13 through LCE-17
For Models LCE-18 and Larger
For Top Flue Outlet Plate, 6 Feet
For Top Flue Outlet Plate, 4 Required
For Models LCE-13 through LCE-17
For Models LCE-18 and Larger
Models LCE-21 through LCE-24 Only
Part Selection Information StockCode
LC/LCE™
Gas/Oil BoilersSteam
SeriesOil, Gas &
Installation,Operation &MaintenanceManualTO THE INSTALLER:
This manual is the property of the owner and mustbe affixed near the boiler for future reference.
TO THE OWNER:This boiler should be inspected annually by aQualified Service Agency.
©2015 PB Heat, LLC. All rights reserved.
PB HEAT, LLC131 S. CHURCH STREET• BALLY, PA 19503
LC8046 R9 (03/15-5C)Printed in U.S.A.