© 2019 Emerson Climate Technologies, Inc. 1 AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable Speed Drives 208-240 V, 4.2 kW & 7.1 kW TABLE OF CONTENTS SAFETY INSTRUCTIONS ........................................... 2 Important Safety Information .................................... 2 QUALIFIED PERSONNEL ONLY ........................ 2 ELECTRICAL SHOCK HAZARD ......................... 2 FIRE HAZARD NOT FOR USE WITH FLAMMABLE REFRIGERANTS .......................... 2 Signal Word Definition ............................................ 2 INTRODUCTION ......................................................... 3 Product Description .................................................. 3 Theory of Drive Operation ........................................ 3 Agency Recognition ................................................. 3 Nomenclature ........................................................... 3 INSTALLATION ........................................................... 3 Drive Handling.......................................................... 3 Handle and store the drive correctly to prevent damage. ................................................................... 3 Mounting .................................................................. 3 Drive Accessories and Dimensions ......................... 3 Wiring Diagram ........................................................ 3 OPERATION & FUNCTION ........................................ 3 Hi-pot Procedure / Set-up ........................................ 3 Temperature, Humidity and Altitude ......................... 3 Pre-operation Checks ............................................... 4 Power On/Off ............................................................ 4 Communication Setting ............................................ 4 Input Voltage and Input Current ............................... 5 Compressor & External Fan Speed Control ............. 5 Start-up ..................................................................... 5 Shutdown .................................................................. 5 Fault Clearing ........................................................... 6 Lockout Faults .......................................................... 6 Stator Heat Control ................................................... 6 Status Indication ....................................................... 6 RGB LED (LED1) ................................................. 6 Power Interrupt ......................................................... 6 Drive Configuration ................................................... 6 High Pressure Cut Out ............................................. 7 Drive Cooling ............................................................ 7 Drive Over Temperature Protection ......................... 7 Air Cooled Heat Exchanger ...................................... 7 Foldback ................................................................... 7 Troubleshooting ........................................................ 7 EMC Guidelines: ....................................................... 7 Table 1 J7 (Modbus) Communication Connector Pin Definition ............................................................ 9 Table 2 Sensor Connector Pin Definition ............ 10 Table 3 J8 Fan Motor Connector Pin Definition .. 10

Upload: others

Post on 17-Mar-2020

28 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

1

AE8-1435 R1 May 2019

EVA3 Single Phase Series Variable Speed Drives

208-240 V, 4.2 kW & 7.1 kW

TABLE OF CONTENTS

SAFETY INSTRUCTIONS ........................................... 2

Important Safety Information .................................... 2 QUALIFIED PERSONNEL ONLY ........................ 2 ELECTRICAL SHOCK HAZARD ......................... 2 FIRE HAZARD – NOT FOR USE WITH FLAMMABLE REFRIGERANTS .......................... 2

Signal Word Definition ............................................ 2

INTRODUCTION ......................................................... 3

Product Description .................................................. 3 Theory of Drive Operation ........................................ 3 Agency Recognition ................................................. 3 Nomenclature ........................................................... 3

INSTALLATION ........................................................... 3

Drive Handling .......................................................... 3 Handle and store the drive correctly to prevent damage. ................................................................... 3 Mounting .................................................................. 3 Drive Accessories and Dimensions ......................... 3 Wiring Diagram ........................................................ 3

OPERATION & FUNCTION ........................................ 3

Hi-pot Procedure / Set-up ........................................ 3

Temperature, Humidity and Altitude ......................... 3 Pre-operation Checks ............................................... 4 Power On/Off ............................................................ 4 Communication Setting ............................................ 4 Input Voltage and Input Current ............................... 5 Compressor & External Fan Speed Control ............. 5 Start-up ..................................................................... 5 Shutdown .................................................................. 5 Fault Clearing ........................................................... 6 Lockout Faults .......................................................... 6 Stator Heat Control ................................................... 6 Status Indication ....................................................... 6

RGB LED (LED1) ................................................. 6 Power Interrupt ......................................................... 6 Drive Configuration ................................................... 6 High Pressure Cut Out ............................................. 7 Drive Cooling ............................................................ 7 Drive Over Temperature Protection ......................... 7 Air Cooled Heat Exchanger ...................................... 7 Foldback ................................................................... 7 Troubleshooting ........................................................ 7 EMC Guidelines: ....................................................... 7 Table 1 – J7 (Modbus) Communication Connector Pin Definition ............................................................ 9 Table 2 – Sensor Connector Pin Definition ............ 10 Table 3 – J8 Fan Motor Connector Pin Definition .. 10

Page 2: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

AE8-1435 R1

© 2019 Emerson Climate Technologies, Inc.

2

SAFETY INSTRUCTIONS

This bulletin includes important safety information. OEMs integrating the Copeland Scroll™ variable speed drive into a system should ensure that their own employees follow this bulletin and provide any necessary safety information to those involved in manufacturing/installing the drive, purchasers of systems, and service personnel who may need to maintain and repair the systems.

Important Safety Information

Failure to follow these warnings could result in serious personal injury or death.

QUALIFIED PERSONNEL ONLY

• OEMs are responsible for system design, selection of appropriate components, integration of this component into the system, and testing the system. OEMs must ensure that staff involved in these activities are competent and qualified.

• Only qualified and authorized HVAC or refrigeration personnel are permitted to install, commission, troubleshoot and maintain this equipment. Electrical connections must be made by qualified electrical personnel.

• Observe all applicable standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment.

ELECTRICAL SHOCK HAZARD

• Before servicing, disconnect and lock out power, and discharge all capacitors for a minimum of two minutes.

• Molded electrical plug must be used when required.

FIRE HAZARD – NOT FOR USE WITH FLAMMABLE REFRIGERANTS

• This drive is not for use in systems with flammable refrigerants. In the event of a refrigerant leak, the drive may ignite the refrigerant resulting in fire and explosion.

Signal Word Definition

The signal word explained below is used throughout the document to indicate safety messages.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

WARNING

These commodities, technology or software, are subject to the U.S. Export Administration Regulations (EAR). Diversion contrary to U.S. law is prohibited. ECCN: EAR99

Page 3: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

AE8-1435 R1

© 2019 Emerson Climate Technologies, Inc.

3

INTRODUCTION

Product Description

The inverter drive has been developed specifically for variable speed compressors and condenser fans utilizing non-flammable refrigerants. The drive will power the compressor; control the compressor and the fan running speed; provide compressor, fan and drive protection and communicate with the master controller. The drive requires cooling and is typically installed in a system near the compressor.

Theory of Drive Operation

The primary purpose of the drive is to convert the 50/60 Hz AC input voltage into a variable frequency, variable voltage output to power the variable speed scroll compressor. The drive conditions the AC input voltage through a series of conditioning processes to arrive at the desired output. The drive first converts the AC input voltage into a DC voltage. The DC voltage is then pulse-width modulated to replicate a sinusoidal current at the desired frequency and voltage.

Agency Recognition

UL 60730-1, IEC 60335-1, IEC 60335-2-34

Nomenclature

The model number of the drive includes the power rating and nominal voltage input to the drive. See Applications Engineering for a complete explanation of the alpha and numeric characters in the drive model number.

INSTALLATION

Drive Handling

Handle and store the drive correctly to prevent damage.

• Never cut across the drive with anything sharp. Do not use a sharp blade to open the protection bag.

• Hold the drive only by the tray or edges of the heatsink. Do not hold by the components on the drive or drive accessories.

• Once opened do not stack the drives on each other.

• Use electrostatic discharge control wristbands and anti-static mats when touching the drive.

• Torque all screw terminals to 18-20 lb-in (2.0-3 N-m) to prevent any damaged to the inverter and filter board.

Mounting

The drive should be located as close to the compressor as possible, preferably within 5 feet, since the wiring between the drive and the compressor is unshielded.

Air-cooled drives are supported inside the HVAC system by an extended heatsink plate. The plate mounts through an opening in the cabinet sheet metal to expose the heatsink to the condenser fan air stream. The flange contains a gasket surface to prevent water from entering the electronics side of the control box.

The flat plate option accommodates installation to systems using the mating gas or liquid cooled cold plate heat exchanger. The cold coupling plate is designed by OEM to accommodate the system design.

There are holes in the drive mounting flange for mounting purposes. These holes will accommodate an M5 sized screw for mounting.

Drive Accessories and Dimensions

Refer to Addendum for accessories. Contact Application Engineering for detailed dimensions with tolerance and drawings.

Wiring Diagram

Refer to Figure 1 for a detailed description of the drive wiring diagrams. Refer to Table 1 and Table 2 for a detailed description of the connector pin definition.

OPERATION & FUNCTION

Hi-pot Procedure / Set-up

Refer to Addendum for hi-pot procedure and setup. Please call your Application Engineer for additional details.

Temperature, Humidity and Altitude

Drive operating temperature range: -20°C to 60°C

Full Performance temperature range: -20°C to 55°C Drive storage temperature range: -40°C to 85°C Humidity: Maximum relative humidity 95%

The drive is designed to meet creepage and clearance requirements for a maximum altitude of 2000 meters.

The storage/shelf life of the drives are 6-12 months without powering them.

Page 4: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

4

AE8-1435 R1

Pre-operation Checks

Before operating, make sure that all the wires are correctly and tightly connected. Improper connections may cause fire or electric shock.

Power On/Off

The drive should use rated AC power supply: 50/60Hz,208~240V. Use of an incorrect power supply may damage the drive. Make sure that the correct combination of a power supply and drive is used.

When powering off the drive, wait for at least 2 minutes to ensure that the drive is completely turned off.

Communication Setting

The drive is designed to be used in a master-slave configuration where the master is a system controller. Standard Modbus® protocols: RTU.

The default communication configuration displays on the rolling LED after power ON. User can write 0x1776 password to Register 200 to get access level for Reg.201 to Reg.234. By default, the drive operates in RTU mode, and the baud rate is automatically detected and adjusted based on Master devices’ baud rate.

Users can also change the slave ID. Detailed parameters and default values are in the Modbus Map (refer to Addendum).

Modbus uses a three-layer protocol – physical, data link, and application. Refer to Addendum for additional details.

o Physical Layer The physical layer defines the hardware interface to the master. The standard control interface uses a two-wire serial communication (RS485 physical layer) scheme. The recommended cable is an 18 AWG stranded copper with 2 conductors and a drain wire. The mating Molex plug part number to plug into CN15 is Molex P/N 39-01-2065.

o Data Link Layer

The data link layer defines the reliable transfer of a message transferred from the master to one of the slave devices and the reliable transfer of the response message back to the master. The drive code sets the default node address of 045 for Modbus RTU.

If the Modbus communications for the inverter is in RTU

mode, the default character framing will be a 11 bit character as follows:

• 1 including Start bit

• 8 Data bits

• 1 Even parity

• 1 Stop bit

o Application Layer

The application layer defines the type of message that will be sent and the format of the message. Read data

are available through Modbus function code 03 (0x03)

read holding registers. See Example 1.

Starting addresses 0 to 7 must be handled in a special

way: each address (at least 0 to 2) represents a

character string (up to 32 byte ASCII). In that case,

the byte count in the response frame is the length of

the string (which might be odd), and the data part of

the frame represents the string as an array of bytes

(without any kind of byte swapping). In the request

frame, the quantity of registers does not matter (and

should be set to 0).

Example 1

Request

Function code 1 Byte 0x03

Starting Address 2 Bytes 0x0000 to 0xFFFF

Quantity of Registers 2 Bytes 1 to 125 (0x7D)

Response

Function code 1 Byte 0x03

Byte count 1 Byte 2 x N*

Holding Registers N* x 2 Bytes

*N = Quantity of Input Registers (N<=25)

Error

Error code 1 Byte 0x83

Exception code 1 Byte 01 or 02 or 03 or

04

WARNING

Page 5: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

5

AE8-1435 R1

01 = Function code not supported

02 = Starting address + quantity of registers out of range

03 = Quantity of registers out of range

04 = Read of input registers failed

Write data are available through Modbus function code

06 (0x06) write single register. See Example 2.

Request

Function code 1 Byte 0x06

Register Address 2 Bytes 0x0000 to 0xFFFF

Register Value 2 Bytes 0x0000 to 0xFFFF

Response

Function code 1 Byte 0x06

Register Address 2 Bytes 0x0000 to 0xFFFF

Register Value 2 Bytes 0x0000 to 0xFFFF

Error

Error code 1 Byte 0x86

Exception code 1 Byte 01 r 02 or

03 or 04

01= Function code not supported

02= Register address invalid

03= Register value out of range

04= Write single register failed, this may also occur if the configuration value is out of bounds.

Input Voltage and Input Current

The drives are designed for an input power supply of 208 to 240 volts 50/60 Hz. Published performance of the drive and compressor combination will have a performance tolerance specified on the compressor performance data sheet when the drive input voltage is in the range of 208 to 240 volts.

Drive Max AC Input Current

EVA3042B 18.5A RMS

EVA3071B 31.0A RMS

Power Factor Correction

The drive has active power factor correction. The drive is capable of correcting the AC input current to maximize system efficiency.

Compressor & External Fan Speed Control

The EVA3 drive supports both compressor speed & external cooling fan control. Both these controls are configured and operated separately. The speed range of EVA3 drive is from 900 RPM to 7200 RPM for compressor and cooling fan. If the speed set by the system controller is less than 900 RPM but not zero, then the compressor will work at 900 RPM. Similarly, if the speed set by the system controller is greater than 7200 RPM, then the compressor will operate at 7200 RPM. The same logic applies to external cooling fan control.

Start-up

The drive will not start with faults present. Modbus registers 78 through 85, and 1078 to 1082 should all be equal to 0. To clear faults, use "Fault Clearing" method shown below. Start the compressor using the following method:

1. Enable drive by writing '1' to Modbus register 100.

2. Write the target RPM to Modbus register 101.

Start-up control is divided into 3 stages. For a detailed description, refer to Addendum for start-up procedures and requirements. After a successful start-up, the compressor will run at the frequency that the system controller is commanding.

Shutdown

A running compressor will shut down in one of the three cases: Case I (Controlled shut down): A '0' is written to Modbus register 100 and/or register 101 depending upon control strategy. There are 3 stages to finish shutdown sequence.

Refer to Addendum for shutdown procedures and requirements.

Case II (Faulted condition): When drive faults occur, the drive will shut down the compressor. There are two types of shutdown; immediate and controlled. As per Modbus map in the Addendum, the drive trips the compressor immediately (from running frequency to zero frequency) for faults marked as “immediate shutdown.” The drive trips the compressor in the same sequence as mentioned in Case I, for faults marked as “controlled shutdown.” As mentioned above, clear faults using the "Fault Clearing" method shown below.

Page 6: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

6

AE8-1435 R1

Case III (Loss of power shut down): This is un-controlled shutdown and compressor is halted in the same way as immediate shutdown sequence.

Fault Clearing

Faults will not clear unless they are commanded by system control.

To clear faults, use the following method:

1. The compressor has been shut down for at least 35 seconds.

2. The fault condition no longer exists (registers 78-85 & registers 1078-1081).

3. The drive has received a zero-speed command (register 101 = 0 & register 1101 = 0).

4. The drive has been disabled (register 100 = 0).

5. Write any “non-zero” value to register 103.

Faults will not clear unless all items above are true.

Lockout Faults

There are specific faults that will cause the drive to 'lockout' after 10 consecutive occurrences. These faults are noted in the Addendum.

These faults will not clear unless the power to the drive is fully cycled.

Stator Heat Control

In actual use, the system controller may decide whether to preheat or not according to the environment. When preheating is needed, the system controller sends register 100 a compressor enable command and register 102 a stator heating power value. The drive transmits up to 50W DC power to warm up the compressor.

The stator heating is on if the following are true:

1. There are no active errors.

2. Compressor enabled.

3. Compressor speed is set zero.

4. Stator heater power setting is from 10~50.

If the system sends a speed demand to the drive while the stator is heating; the drive will stop stator heating and start the compressor. While running, if the system sends a zero-speed command, the drive will shut down the compressor automatically, and then resume the stator heating to the value saved in Stator Heater Power Memory Register (a value or zero = off).

Status Indication

There are two controller chips on the drive; one is ARM microcontroller another is FPGA. There are two LEDs on the drive board; one is LED1 which is near the ARM microcontroller and is used for drive diagnostics, another LED is D56 which is used for indicating power status of Modbus communication.

RGB LED (LED1)

1. Blinking RED (fast) – There is a fault present on the drive

2. Blinking GREEN (slow) – There are no faults present

3. Blinking GREEN (fast) – MODBUS message successfully received

4. Solid RED – FPGA configuration failed 5. Solid CYAN – Loading new main (DSP) software

failed 6. Solid MAGENTA – Loading new FPGA software

failed 7. Solid YELLOW – Loading new boot (DSP)

software failed Rolling LED The drive has a rolling LED display with rolling text feature. a. During power on stage, the LED indicates software version and Modbus configuration. b. In normal running condition, it displays “EMERSON.” c. In fault condition, it displays fault code & name. d. The rolling LED “display speed” is configurable via Modbus. Refer to Modbus Map and Troubleshooting Sections in the Addendum for more details.

Power Interrupt

Power interrupts can result in a drive trip that won't harm the drive. The drive can withstand interrupts of short duration (<=10 ms) but will trip on anything longer.

Drive Configuration

Another feature available on the drive is the option to change communication parameters, configure the drive to use different types of compressors and sensors. Modbus registers 200-207, 211-218, 220, 221, 231, 234 serve this function (refer to Modbus Map within the Addendum for details).

These options are password protected. Register 200 must have the correct password written before any parameters can be changed. All register functions and default values are located in the Modbus Map.

Page 7: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

7

AE8-1435 R1

Once configured only changes to registers 201-204 will require power cycle for the changes to be implemented.

Refer to Addendum for configuration process flow and communication settings process flow.

High Pressure Cut Out

J6 is a 2-port connector. The output is a 3.3VDC signal. The high-pressure cutout switch can be configured. The output current range for the high-pressure contact will be around 1mA or lower. To ensure correct functionality of the high-pressure switch for the system’s lifetime, typically gold-plated contacts are recommended. Refer Table-2 for detailed pinout.

This port is hardware Protected Electronic Circuit (PEC) according to IEC 60335-1 and software is Class-B.

Drive Cooling

Because of the power electronics used in the drive and the associated heat generation, drive cooling is required to keep the drive components in their design temperature range. The allowable temperature range of the drive (the ambient air surrounding the drive) -20°C to 60°C. Drive temperature should be monitored during system development at system extreme conditions to ensure that the maximum allowable drive temperature is not exceeded. The highest drive temperature will typically occur during high load conditions or high drive ambient.

The minimum recommended thermal capacity removal should be approximately 270 Watts.

Drive Over Temperature Protection

The drive is self-protected against high internal temperatures. There are different modes of protection (temperature high and foldback). For temperature high refer to Troubleshooting Table within Addendum. For foldback protection, refer to Addendum for more information.

Air Cooled Heat Exchanger

Drives cooled by the aluminum air-cooled heat exchanger are designed to be in the air flow stream of the condenser. The air-cooled heat exchanger must be installed so that the heat exchanger fins are parallel to the cooling air flow. The airflow must be a minimum of 3 meters/secs measured at the outlet of the heatsink in the direction of the airflow.

Foldback

To protect the drive components and the compressor; the compressor speed will 'foldback' or slow down to

help reduce risk to components. The foldback event(s) will be flagged in the drive's Modbus registers. This will allow the operating system to respond and mitigate the conditions causing foldback.

For further information, refer to Addendum.

Troubleshooting

The drive may indicate a fault or protection for various reasons. If a fault or protection occurs, users should power down the drive, check the drive, and check the drive running condition carefully. For the description, check and handling of these faults or protections, please refer to the Troubleshooting – Fault and Protection within Addendum

EMC Guidelines:

Install the star earth (ground) connection as close as possible to the drive. A non-coating screw is recommended for installation on the service panel to maintain a good ground connection. The star connection includes:

• System Input ground

• Drive Heat-sink ground

The use of additional ferrites and numbers of turns in the input power supply cables, compressor cables, sensor cables, aluminum shielding enclosure are optional but preferred based on system application and noise level.

Any of the input power supply cables, sensor cables, compressor cables, and communication cables should not cross or touch each other to avoid noise coupling.

Use of shielded cable is optional depending on system application, but if used, it’s mandatory to have correct connections on both sides of the cable.

Page 8: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

8

AE8-1435 R1

Figure 1 – 4.2kW Drive Wiring Diagram

Page 9: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

9

AE8-1435 R1

Figure 2 – 7.1kW Drive Wiring Diagram

Table 1 – J7 (Modbus) Communication Connector Pin Definition

Pin Number

Description Figure

1 Not Connected

2 B

3 A

4 GND_CH

Description Part Number

4-Pin Connector Header JST P/N B04B-PAEK-1 or

Equivalent

Page 10: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

© 2019 Emerson Climate Technologies, Inc.

10

AE8-1435 R1

Table 2 – Sensor Connector Pin Definition

Pin Number

Description Figure

1 DLT1 DLT: RED HP: YELLOW

2 DLT2

1 HP1

2 HP1

J5 (DLT Sensor) Connector P/N Information

Description Part Number

2-Pin Connector Header JST P/N B02B-PATRK-1 or

Equivalent

J6 (HPS) Connector P/N Information

Description Part Number

2-Pin Connector Header JST P/N B02B-PAFYK-1 or

Equivalent

Table 3 – J8 Fan Motor Connector Pin Definition

Pin Number

Description Figure

1 Fan_U

2 Fan_V

3 Fan_W

Description Part Number

3-Pin Connector Header JST P/N B3P-VH-M or Equivalent

The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding

the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable,

reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or

maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.

Page 11: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

TABLE OF CONTENTS

1 Start-up and Shutdown Sequence OF THE COMPRESSOR ..................................................... 2

2 Drive Foldback Information ............................................................................................................... 5

3 Modbus Map ....................................................................................................................................... 7

4 Drive Configuration Flow Charts .................................................................................................... 15

5 Troubleshooting Guide .................................................................................................................... 17

6 Hi-pot Testing .................................................................................................................................... 20

7 Accessories ....................................................................................................................................... 21

ADDENDUM to AE8-1435 06/24/2019

Page 12: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

1 START-UP AND SHUTDOWN SEQUENCE OF THE COMPRESSOR

Table 1 - Start-up Sequence

Stage Description Target Speed (rpm) Ramp Up Rate (rpm/s)

Duration (s)

I Compressor command started 1800 1600 4

II Compressor remains at the platform speed

3600 (Configurable) - 10 (Configurable)

III Compressor reaches commanded speed

Commanded Default = 200 -

Table 2 - Shutdown Sequence

Stage Description Target Speed (rpm) Ramp Down Rate (rpm/s)

I Compressor Shutdown requested - -

II Compressor gets to minimum speed

900 Default = 200

III Compressor Stop - -

Page 13: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Figure 1 – Start-up Sequence

Speed

Time

Dwell Speed 1500-3600 RPM (Reg.213) Default: 3600RPM

Dwell Time 10 - 300s (Reg.234) Default: 10s

1600RPM/S

Positive Ramp Rate 30-600RPM/s (Reg.211) Default: 200RPM/s

Negative Ramp Rate 30-600RPM/s (Reg.212) Default: 200RPM/s

I II

III 20RPM

1800RPM

1000RPM/S

Page 14: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Figure 2 – Shutdown Sequence

Shutdown Initiated

Speed

Time

Positive Ramp Rate 30-600RPM/s (Reg.211) Default: 200RPM/s

Stop

Compressor Stop Speed Default: 900RPM *Defined in Compressor Data File

I II III

Page 15: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

2 DRIVE FOLDBACK INFORMATION

Table 3 – Envelop Control

Modbus (Reg231) Envelop Control Mode Description

0 Basic Envelope Protection Compressor will be tripped when torque is out of torque limit

1 Basic Envelope Protection with Minimum Speed Control

Compressor will reduce speed to mini speed at first

2 Active Envelope Compressor will be tripped when Evaporating and condensing temperature is out of envelop map

3 Active Envelope with Minimum Speed Control

Compressor will reduce speed to mini speed at first

Table 4 – Basic Envelop Foldback With Minimum Speed Control

Condition Action taken by the Drive

1 Torque >= Torque Limit Will reduce the speed at the rate of 200 rpm/s

2 Torque < Torque Limit Speed will be recovered to commanded speed

3

If the compressor load is not recovered and continue to exceed the foldback limit in one of the conditions below:

• After compressor running speed has reached to envelop limit speed and then stay at envelop limit speed for >= 30sec. OR

• If the original running speed was already < envelop limit speed for >= 30sec

Compressor will be tripped

Table 5 – Active Envelop Foldback With Minimum Speed Control

Drive uses evaporating temperature (Reg111) and condensing temperature (Reg112) for active envelop

foldback.

Envelop map is divided into multiple speed zones. Each speed zone has an allowed speed range as

shown in Figure 3.

Condition Action taken by the Drive

1 Speed > The Max speed of each speed zone Compressor will reduce to max speed of that

speed zone

2 Min speed < Speed < Max speed Keep the current speed

3 When the speed is outside the envelope and the timeout has occurred (the time displayed in register 47)

Compressor will be tripped

For example: If the evaporating temperature (Reg111) and condensing temperature (Reg112) is in below

area 6, and the speed range of area 6 is 1300RPM to 5000RPPM.

Speed demand = 7000rpm, drive will reduce speed to 5000RPM

Speed demand = 1200rpm and timeout has occurred (register47 = 0), compressor will be tripped

Page 16: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Figure 3 – Operating Envelope Example

Table 6 – Inverter Temperature Foldback

Condition Action taken by the Drive

1 Inverter Temperature >= Foldback Temperature Will reduce the speed at the rate of 200 rpm/s

2 Recovering Temperature <= Inverter Temperature < Foldback Temperature

Will remain in the current speed

3 Inverter Temperature < Recovering Temperature Speed will be recovered to commanded speed

4

If the Inverter Temperature is not recovered and continue to exceed the foldback limit in one of the conditions below:

• After compressor running speed has reached to envelop limit speed and then stay at envelop limit speed for >= 30sec. OR

• If the original running speed was already < envelop limit speed for >= 30sec

Compressor will be tripped

Page 17: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

3 MODBUS MAP

Modbus Register

Register Type Description Fault Shutdown

Units Bytes Data Format

0

Serial and Model Numbers

(Read)

Drive Model Number

N/A N/A 32 bytes ASCII

character

string

EVA30XXB-C9-XXX 0XX:power Ex. 042 = 4.2kW max capacity

1

Drive Serial Number

N/A N/A 32 bytes ASCII

character

string

ADXXXXXXX Ex. AD13K0001 AD: Production Code 13:2013,production year. K: Month Code, A=Jan, B=Feb,…,L=Dec. 0001: Product Serial Number.

3

Configuration and Status Parameter

(Read)

Allowed maximum Speed

N/A Hz 2 Bytes 16.0

4

Allowed minimum Speed

N/A Hz 2 Bytes 16.0

5

Drive status

N/A

N/A

2 Bytes

Bit2: Drive Running Status 0 = Normal 1= Under Faults Bit4: Compressor Status 0 = OFF 1 = ON Bit8: Frequency Stable Flag 0 = Stable 1 = Not Stable

8

SW Version (Read)

Compressor Motor software version (High Word)

N/A N/A 2 Bytes 8.8.8.8 Ex. 2.11.2.0: 2=Product ver; 11=Major ver; 2=Minor ver; 0= Test ver

9 Compressor Motor software version (Low Word)

N/A N/A 2 Bytes

10 FPGA SW Version (High Word)

N/A N/A 2 Bytes

11 FPGA SW Version (Low Word)

N/A N/A 2 Bytes

12 DSP Boot Version (High Word)

N/A N/A 2 Bytes

13 DSP Boot Version (Low Word)

N/A N/A 2 Bytes

14 DSP Main Version (High Word)

N/A N/A 2 Bytes

15 DSP Main Version (Low Word) N/A N/A 2 Bytes

16

Compressor Phase Over Current Limit

N/A Amps (RMS) 2 Bytes 8.8 Ex. If Value = 512, then Conversion = 512/(2^8)

17 AC Input Over Current N/A Amps (RMS) 2 Bytes 8.8

18 DC Bus Over Voltage N/A Volts (RMS) 2 Bytes 12.4

19 DC Bus Under Voltage N/A Volts (RMS) 2 Bytes 12.4

20 AC Input Over Voltage N/A Volts (RMS) 2 Bytes 12.4

21 AC Input Under Voltage N/A Volts (RMS) 2 Bytes 12.4

Page 18: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

22

Trip Limits (Read)

Power Module Over Temp N/A Celsius 2 Bytes 11.5

23 PFC-IGBT Over Temp N/A Celsius 2 Bytes 11.5

32 DC Bus Voltage Low N/A Volts (RMS) 2 Bytes 12.4

34 Board Temperature High N/A Celsius 2 Bytes 11.5

35 Power Module Temp High N/A Celsius 2 Bytes 11.5

36 PFC-IGBT Temp High N/A Celsius 2 Bytes 11.5

38 Sensor 2 (Thermistor, DLT) High Temp Limit

N/A Celsius 2 Bytes 11.5

40

Drive Status/Readings

(Read)

Input Current Foldback Limit N/A Amps (RMS) 2 Bytes 8.8

41 Compressor Output Current Foldback Limit

N/A Amps (RMS) 2 Bytes 8.8

44 Minimum Allowed Speed @ Operation Point

N/A RPM 2 Bytes 16.0

45 Maximum Allowed Speed @ Operation Point

N/A RPM 2 Bytes 16.0

47 Envelope Time Out Remaining Time

N/A ms 2 Bytes 26.-10 Ex. If Value = 20, then Conversion = 20/(2^(-10))

51 Fold Back Status N/A N/A 2 Bytes Bit0: External Flash Configuration Status 0 = OK 1= Data Corrupt Bit1: Output Voltage Limit 0 = Not limited 1= Limited Bit3: AC Input Current Foldback Status 0 = OFF 1 = ON Bit4: Compressor Phase Current Foldback Status 0 = OFF 1 = ON Bit5: Compressor Power Module Temperature Foldback Status 0 = OFF 1 = ON Bit7: Envelope Foldback Status 0 = OFF 1 = ON Bit8: Autosaved Data Status 0 = OK 1= Data Corrupt

52 Max. Allowed Stator Heater Power

N/A Watt 2 Bytes 16.0

59 Power-Up Status N/A N/A 2 Bytes 0 = Not Ready 1 = Power-Up Complete

60 Compressor running speed N/A RPM 2 Bytes 15.1

61 Compressor Phase Current N/A Amps (RMS) 2 Bytes 7.9

62 Compressor Phase Current Limit

N/A Amps (RMS) 2 Bytes 7.9

63 Out-of-Volts Percentage (AC Output Voltage)

N/A % 2 Bytes 2.14

64 DC Bus Voltage N/A Volts (DC) 2 Bytes 12.4

65 AC Input Voltage N/A Volts (RMS) 2 Bytes 12.4

66 AC Input Current N/A Amps (RMS) 2 Bytes 8.8

67 AC Input Power N/A Watts 2 Bytes 16.0

68 Compressor Phase Current N/A Amps (RMS) 2 Bytes 8.8

69 Board Temperature N/A Celsius 2 Bytes 11.5

70 Power Module Temp N/A Celsius 2 Bytes 11.5

Page 19: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

73

PFC-IGBT Temp

N/A

Celsius

2 Bytes

11.5

77

Sensor 2 (Thermistor, DLT) Reading

N/A

Celsius

2 Bytes 11.5

78

1st Fault Occurred (Read)

Compressor Phase Over Current

Immediate Shutdown

N/A Bit 0 0 = No; 1 = Yes 10 times Lockout function*

AC Input Over Current Immediate Shutdown

N/A Bit 1

DC Bus Over Voltage Immediate Shutdown

N/A Bit 2

DC Bus Under Voltage Immediate Shutdown

N/A Bit 3

AC Input Over Voltage Immediate Shutdown

N/A Bit 4

AC Input Under Voltage Immediate Shutdown

N/A Bit 5

Inverter Desaturation Immediate Shutdown

N/A Bit 7

Sensor 1 (High Pressure Switch Open)

Immediate Shutdown

N/A Bit 8

Loss of Compressor Motor Control

Immediate Shutdown

N/A Bit 10

Power Module Over Temp Immediate Shutdown

N/A Bit 11

PFC-IGBT Over Temp Immediate Shutdown

N/A Bit 12

Compressor Startup Fault Immediate Shutdown

N/A Bit 13 10 times Lockout function*

Precharge Relay Open Immediate Shutdown

N/A Bit 15

79

1st Fault Occurred (Read)

DC Bus Voltage Low N/A N/A Bit 0

Compressor Phase Current Fold Back Timeout

Controlled Shutdown

N/A Bit 2

Power Module Temp. Fold Back Timeout

Controlled Shutdown

N/A Bit 3

Modbus Communication Lost Controlled Shutdown

N/A Bit 7

Sensor 2 (Thermistor, DLT) High Temp

Controlled Shutdown

N/A Bit 8

Board Temperature High Controlled Shutdown

N/A Bit 10

Power Module Temp High Controlled Shutdown

N/A Bit 11

PFC-IGBT Temp High Controlled Shutdown

N/A Bit 12

80

Multiple Faults Occurred (Read)

Compressor Phase Over Current

Immediate Shutdown

N/A Bit 0 10 times Lockout function*

AC Input Over Current Immediate Shutdown

N/A Bit 1

DC Bus Over Voltage Immediate Shutdown

N/A Bit 2

DC Bus Under Voltage Immediate Shutdown

N/A Bit 3

AC Input Over Voltage Immediate Shutdown

N/A Bit 4

AC Input Under Voltage Immediate Shutdown

N/A Bit 5

Inverter Desaturation Immediate Shutdown

N/A Bit 7

Sensor 1 (High Pressure Switch Open)

Immediate Shutdown

N/A Bit 8

Loss of Compressor Motor Control

Immediate Shutdown

N/A Bit 10

Power Module Over Temp Immediate Shutdown

N/A Bit 11

PFC-IGBT Over Temp Immediate Shutdown

N/A Bit 12

Page 20: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Compressor Startup Fault Immediate Shutdown

N/A Bit 13 10 times Lockout function*

Precharge Relay Open Immediate Shutdown

N/A Bit 15

81

Multiple Faults Occurred (Read)

DC Bus Voltage Low Controlled Shutdown

N/A Bit 0

Compressor Phase Current Fold Back Timeout

Controlled Shutdown

N/A Bit 2

Power Module Temp. Fold Back Timeout

Controlled Shutdown

N/A Bit 3

Modbus Communication Lost Controlled Shutdown

N/A Bit 7

Sensor 2 (Thermistor, DLT) High Temp

Controlled Shutdown

N/A Bit 8

Board Temperature High Controlled Shutdown

N/A Bit 10

Power Module Temp High Controlled Shutdown

N/A Bit 11

PFC-IGBT Temp High Controlled Shutdown

N/A Bit 12

DC Bus Voltage Low Controlled Shutdown

N/A Bit 0

Compressor Phase Current Fold Back Timeout

Controlled Shutdown

N/A Bit 2

82

1st Fault Occurred (Read)

Compressor Phase Current Imbalance

Immediate Shutdown

N/A Bit 0

Micro Electronic Fault Immediate Shutdown

N/A Bit 2

Motor Overspeed Immediate Shutdown

N/A Bit 3

External Flash Immediate Shutdown

N/A Bit 4

Compressor Model Configuration Error

Immediate Shutdown

N/A Bit 6

Compressor U-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 8 10 times Lockout function*

Compressor V-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 9 10 times Lockout function*

Compressor W-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 10 10 times Lockout function*

Compressor HW Over Current Immediate Shutdown

N/A Bit 11 10 times Lockout function*

83

1st Fault Occurred (Read)

Sensor 2 (Thermistor, DLT) Low Temp or Open

Controlled Shutdown

N/A Bit 2

Board Temperature Low Controlled Shutdown

N/A Bit 4

Power Module Temp Low or Sensor Open fault

Controlled Shutdown

N/A Bit 5

PFC-IGBT Temp Low or Sensor Open fault

Controlled Shutdown

N/A Bit 6

Fault Limit Lockout Controlled Shutdown

N/A Bit 15

84

Multiple Faults Occurred (Read)

Compressor Phase Current Imbalance

Immediate Shutdown

N/A Bit 0

Micro Electronic Fault Immediate Shutdown

N/A Bit 2

Motor Overspeed Immediate Shutdown

N/A Bit 3

External Flash Immediate Shutdown

N/A Bit 4

Compressor Model Configuration Error

Immediate Shutdown

N/A Bit 6

Compressor U-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 8 10 times Lockout function*

Compressor V-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 9 10 times Lockout function*

Compressor W-Phase OC/Sensor Fault

Immediate Shutdown

N/A Bit 10 10 times Lockout function*

Page 21: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Compressor HW Over Current Immediate Shutdown

N/A Bit 11 10 times Lockout function*

85

Multiple Faults Occurred (Read)

Sensor 2 (Thermistor, DLT) Low Temp or Open

Controlled Shutdown

N/A Bit 2

Board Temperature Low Controlled Shutdown

N/A Bit 4

Power Module Temp Low or Sensor Open fault

Controlled Shutdown

N/A Bit 5

PFC-IGBT Temp Low or Sensor Open fault

Controlled Shutdown

N/A Bit 6

Fault Limit Lockout Controlled Shutdown

N/A Bit 15

Modbus Register

Register Type Description Bytes Data Format Default Values

Additional Notes

100

Standard Commands (Read/Write)

Compressor Enable

2 Bytes 0 = Disable 1 = Enable 0

101 Compressor Speed

Demand

2 Bytes 16.0 Ex. If Value = 512, then Conversion = 512/(2^0) 1RPM/bit

0

102 Stator Heater

Demand

2 Bytes 16.0 0 = Disable Ex. If Value = 512, then Conversion = 512/(2^0) 1Watt/bit

0

103 Faults Clear Command

2 Bytes Writing any value will clear the faults

0

107 Time/Date Stamp (Hours & Minutes)

2 Bytes 8.8: 8 bits for Minutes 8 bits for Hours

0

108 Time/Date Stamp (Year, Month &

Day)

2 Bytes 7.4.5: 7 bits for Year 4 bits for Month 5 bits for Day

0

111

Evaporating Temperature

2 Bytes

11.5 Ex. If Value = 512, then Conversion = 512/(2^5) 1F/bit

0

112

Condensing Temperature

2 Bytes

11.5 Ex. If Value = 512, then Conversion = 512/(2^5) 1F/bit

0

200

Map access Password

2 Bytes Password = 0x1776 Customer access to 201~234

N/A

202 ModBUS Slave ID Address

2 Bytes 1-247 45 The drive has a feature to detect the baud rate and parity of the system

controller and automatically configure to Reg203 =0.

203 ModBUS Baud Rate

2 Bytes 0-65535 0

204

ModBUS Parity

2 Bytes

1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No Parity, 1 stop bits:

1

205

Compressor Model Number

32 bytes ASCII

character

string

4.2kW Drive:

ZPV0212E-2E9

ZHV0212P-2E9

ZHW0152P-2E9

7.1kW Drive:

ZPV0282E-2E9

ZPV0342E-2E9

ZHV0342P-2E9

ZPV0382E-2E9

ZPV038CE-2E9

ZHW0302P-2E9

ZPV0412E-2E9

ZPV041CE-2E9

32 bytes ASCII character string

When configured to ZPV0212E-2E9 compressor, compressor model number should be converted to string char according to ASCII table. The ASCII code of “ZPV0212E-2E9” is 5A 50 56 30 32 31 32 45 2D 32 45 39. For example: Use below command for ZPV0212E-2E9 compressor 2D 06 00 CD 5A 50 56 30 32 31 32 45 2D 32 45 39 A8 87

Page 22: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

206

Customer Configuration

Parameter (Read/Write)

Sensor 1 (HP Switch)

2 Bytes 0 - Unconfigured 1 - 99 - HPC Sensor Unused 100 - Normally Closed (N/C) 101 - Normally Open (N/O

0

If no HP switch, it needs to be configured to “101” to disable HP protection.

207 Sensor 2 (Scroll Thermistor, DLT)

2 Bytes 0 = Unused 100 = 10k Scroll Thermistor Range 0 - 100

100 When configured to “100”, the DLT limit at Reg.38 is not applicable, it is only for lab usage.

211

Speed Ramp-up Rate Config Option

2 Bytes

16.0 0 = Not Configured Can be configured in increments of "20" (20 to 120). Decimal value of 20 = 60rpm/sec Ex. If Value = 20, then it's 60rpm/sec

200

212

Speed Ramp-down Rate Config Option

2 Bytes 16.0 0 = Not Configured Can be configured in increments of "20" (20 to 120). Decimal value of 20 = 60rpm/sec Ex. If Value = 20, then it's 60rpm/sec

200

This register is read only.

213

Dwell Speed

2 Bytes

Compressor Dwell Speed Range: 1500 - 3600

3600

214

Compressor Model Number

32 bytes ASCII

character

string

ZPV0212E-2E9

ZHV0212P-2E9

ZHW0152P-2E9

ZPV0282E-2E9 ZPV0342E-2E9 ZHV0342P-2E9 ZPV0382E-2E9 ZPV038CE-2E9 ZHW0302P-2E9 ZPV0412E-2E9 ZPV041CE-2E9

32 bytes ASCII

character

string

215

Scrolling LED Message Refresh

Rate

2 Bytes Sets the rate at which the scrolling LED displays messages.

100

When configured to 200, the speed of rolling LED will be slower.

216

Manually Save Parameters

2 Bytes Writing any value will store external flash

0

Need to write this register to store configured parameters in external flash

217 Modbus Baud Rate [High Word]

2 Bytes Modbus Baud Rate [High Word] [0 - 7]

0 This register is for higher baud rate.

218 Filename Selection

32 bytes ASCII

character

string

This selects the main code. This is determined by the compressor and fan motor combination.

32 bytes ASCII

character

string

It has different fan motor and compressor model. Follow the same method as Reg205 to use the string char of hex filename.

220 Extended Password

4 Bytes Write the password, returns the access level

0 This register is 32bits extended password for high level access. It has 4 bytes using special function code(0x64). Passwords --> Access Level: 0x00000000 --> 0, 0x00001776 --> 1, 0x12345678 --> 2, 0x12345678 --> 3

221 Set Access Level Password

32 bytes ASCII

charact

Sets the access level passwords

0 ID+ Special Function Code+ Address+ Access Level+ Old password+ New Password+ CRC:

Page 23: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

er string

For example: Change level 2 password from 0x12345678 to 0x03081234 0x2D + 0x64 + 0x 00 0xDD + 0x02 + 0x 12 0x34 0x56 0x 78 +0x03 0x08 0x12 0x34 + CRC

231 Envelope Control Mode

2 Bytes 0 = Basic Envelope Protection 1 = Basic Envelope Protection w/ Minimum Speed Control 2 = Active Envelope 3 = Active Envelope w/ Minimum

1

234 Compressor Dwell Time

2 Bytes Compressor Dwell Time Range: 10 - 300

10

Modbus Register

Register Type Description Fault Shutdown

Units Bytes Data Format

1003

Configuration and Status Parameter

(Read)

Allowed maximum Speed

N/A Hz 2 Bytes 16.0

1004

Allowed minimum Speed

N/A Hz 2 Bytes 16.0

1005

Fan status

N/A

N/A

2 Bytes

Bit4: Fan Status 0 = OFF 1 = ON Bit8: Frequency Stable Flag 0 = Stable 1 = Not Stable

1008

SW Version (Read)

Fan Motor software version (High Word)

N/A N/A 2 Bytes 8.8.8.8 Ex. 1.1.0.0: 1=Fan ver; 1=Major ver; 0=Minor ver;0 = Test ver

1009 Fan Motor software version (Low Word)

N/A N/A 2 Bytes

1016

Trip Limits (Read)

Fan Motor Phase Over Current Limit

N/A Amps (RMS) 2 Bytes 8.8

1022 Fan Power Module Over Temp N/A Celsius 2 Bytes 11.5

1035 Fan Power Module Temp High N/A Celsius 2 Bytes 11.5

1041

Drive Status/Readings

(Read)

Fan Motor Output Current Foldback Limit

N/A Amps (RMS) 2 Bytes 8.8

1051

Fold Module Back Status

N/A

N/A

2 Bytes

Bit1: Speed Foldback Flag (Output Voltage Limit) 0 = Normal 1= Folding Back Bit4: Fan Phase Current Foldback Status 0 = Normal 1 = Folding Back

1060 Fan Motor Speed N/A RPM 2 Bytes 15.1

1061 Fan Torque N/A Amps (RMS) 2 Bytes 7.9

1068 Fan Motor Phase Current N/A Amps (RMS) 2 Bytes 8.8

1070 Fan Power Module Temp N/A Celsius 2 Bytes 11.5

Fan Motor Phase Over Current

Immediate Shutdown

N/A Bit 0 10 times Lockout function*

Fan Motor Phase Current Imbalance

Immediate Shutdown

N/A Bit 1

Page 24: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

1078

1st Fault Occurred (Read)

Fan Motor Overspeed Immediate Shutdown

N/A Bit 2

Fan Motor U-Phase Over Current Fault

Immediate Shutdown

N/A Bit 5 10 times Lockout function*

Fan Motor V-Phase Over Current Fault

Immediate Shutdown

N/A Bit 6 10 times Lockout function*

Fan Motor W-Phase Over Current Fault

Immediate Shutdown

N/A Bit 7 10 times Lockout function*

Fan Motor HW Over Current Immediate Shutdown

N/A Bit 8 10 times Lockout function*

Loss of Fan Motor Control Immediate Shutdown

N/A Bit 8

Fan Power Module Over Temp Immediate Shutdown

N/A Bit 10

Fan Motor Startup Fault

Immediate Shutdown

N/A Bit 11 10 times Lockout function*

1079

1st Fault Occurred (Read)

Fan Power Module Temperature High

Controlled Shutdown

N/A

Bit 11

1080

Multiple Faults Occurred (Read)

Fan Motor Phase Over Current

Immediate Shutdown

N/A Bit 0 10 times Lockout function*

Fan Motor Phase Current Imbalance

Immediate Shutdown

N/A Bit 1

Fan Motor Overspeed Immediate Shutdown

N/A Bit 2

Fan Motor U-Phase Over Current Fault

Immediate Shutdown

N/A Bit 3 10 times Lockout function*

Fan Motor V-Phase Over Current Fault

Immediate Shutdown

N/A Bit 4 10 times Lockout function*

Fan Motor W-Phase Over Current Fault

Immediate Shutdown

N/A Bit 5 10 times Lockout function*

Fan Motor HW Over Current Immediate Shutdown

N/A Bit 7 10 times Lockout function*

Loss of Fan Motor Control Immediate Shutdown

N/A Bit 8

Fan Power Module Over Temp Immediate Shutdown

N/A Bit 10

Fan Motor Startup Fault Immediate Shutdown

N/A Bit 11 10 times Lockout function*

1081

Multiple Faults Occurred (Read)

Fan Power Module Temperature High

Controlled Shutdown

N/A Bit 11

Modbus Register

Register Type Description Bytes Data Format Default Values

Additional Notes

1101 Standard Commands (Read/Write)

Fan Speed Demand

2 Bytes 16.0

0

__________________________________________________________________________________________

*Note: After 10 occurrences of a lockout related fault within 10hours time, the drive will go into hard lockout. The

lockout fault requires a reset command to be sent to the drive (register 299) or a power cycle. The lockout fault will

also clear itself after 10 hours.

Page 25: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

4 DRIVE CONFIGURATION FLOW CHARTS

Apply Power to Drive

Write Password “0x1776” to Register 200.

Read Registers 201 to 214(203 & 204 are

autoconfigured by the drive)

Do values match spec?

Faults?Query fault status

Write values according to Modbus Map to Registers

205 to 234Operate drive

Troubleshoot according to the fault

YES

YES

NO

NO

Page 26: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

Apply Power to Drive

Write Password “0x1776” to Register 200.

Select cooling fan model by Reg218

Reset drive by Reg299

Configure other values according to Modbus Map

to Registers 201 to 234

Select compressor file by Reg205

Configure high pressure by Reg206

Configure DLT by Reg207

All above parameters need to store external

flash by Reg216

Page 27: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

5 TROUBLESHOOTING GUIDE

Item Fault/Protection Check and Handling Registers Bit

1

Compressor Phase Over Current

1. Check the U/V/W connections on drive side

78 80 0

2. Check the compressor motor windings

3. Check the compressor is operating with in specified limits.

Sensor on Drive not reading properly - Replace Drive

2 Compressor Phase Current Fold Back

Timeout

Check if the compressor is operating outside the specified speed range.

79 81 2

3

AC Input Over Current

1. Check the line voltage if it is < 187VAC.

78

80

1

2. Check the line voltage for noise. 3. Check the compressor is operating with in specified limits. 4. If the problem still persists, then it's possibly a drive component issue. Replace the drive

4

DC Bus Over Voltage

1. Check the line voltage if it is > 265VAC. 2. Check the DC bus voltage if it is >385VDC 3. Check the compressor is operating with in specified limits.

78

80

2

5

DC Bus Under Voltage

1. Check the line voltage if it is < 187VAC. 2. Check the DC bus voltage if it is < 385VDC 3. Check the compressor is operating with in specified limits.

78

80

3

6

AC Input Over Voltage

1. Check the line voltage if it is > 265VAC. 2. Check the DC bus voltage if it is > 385VDC 3. Check the compressor is operating with in specified limits.

78

80

4

7

AC Input Under Voltage

1. Check the line voltage if it is < 187VAC. 2. Check the DC bus voltage if it is < 385VDC 3. Check the compressor is operating with in specified limits.

78

80

5

8 Inverter Desaturation

1. Check the power supply and DC bus voltage 2. Check the cooling air speed across heatsink 3. Check the compressor is operating with in specified limits

78 80 7

9

Power Module Over

Temp

Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within

78

80

11

Page 28: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

10 PFC-IGBT Over Temp

specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem, still persists replace the drive.

78 80 12

11

Loss of Compressor

Motor Control

1. Check the U/V/W connections on drive

side & compressor side.

2. Check the compressor motor windings

78

80

13

12 Compressor Phase

Current Imbalance 82 84 0

13

Microelectronic Fault

1. DSP self-check error, restart the drive and fault should go away. 2. If problem persists, replace the drive.

82

84

2

14 Motor Overspeed 1. Check the U/V/W connections on the drive side & compressor side. 2. Check the compressor motor windings 3. Check the compressor is operating with in specified limits.

82 84 3

15 External Flash Fault 1. Re-configure external flash by Reg216 2. Power cycle the drive 3. If the problem still persists, replace the drive.

82 84 4

16 Power Module Temp Low or Sensor Open

fault

Temperature sensing devices on the drive are possibly defective. If problem persists, replace the drive.

83 85 5

17

DC Bus Voltage Low

1. Check the line voltage if it is < 187VAC. 2. Check the DC bus voltage if it is < 385VDC. 3. Check the compressor is operating with in specified limits.

79 81 0

18

AC Input Current

Fold Back Timeout.

1. Check the line voltage if it is < 187VAC. 2. Check the compressor is operating with in specified limits. 3. If problem persists, replace the drive.

79 81 4

19

Modbus Communication Lost

1. Check mod-bus communication cable connections. 2. Check the communication parameters are set right. 3. Power cycle the drive. 4. If problem persists, replace the drive.

79

81

7

20 Sensor 2 (Thermistor, DLT)

High Temp

1. Check the DLT/Scroll Thermistor connection. 2. Check the compressor is operating with in specified limits.

79 81 8

21

Power Module Temp High

Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem still persists, replace the drive.

79

81

11

22 PFC-IGBT High Temp

79 81 12

Page 29: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

23 PFC-IGBT Temp Low or Sensor Open

fault

Verify proper airflow over the heat-sink of the drive. Remove any obstructions. Check that the compressor is operating within specified limits. Check the mounting screws on the drive, make sure they are tight. If the problem still persists, replace the drive.

83 85 6

24 Power Module Temp. Fold Back

Timeout

79 81 3

25 Sensor 1 (High Pressure Switch

Open)

Condensing Pressure beyond limit, system issue.

78 80 8

26 Sensor 1 (High Pressure Sensor)

Low or Open

Condensing Pressure below limit, system issue.

82 84 5

27 Compressor Model Configuration Error

Compressor model and configuration code do not match

82 84 6

28 High Pressure Sensor Type

Configuration Error

Pressure sensor and configuration code do not match

82 84 7

29 Sensor 2 (Thermistor, DLT)

Low Temp or Open

1. Check the DLT/Scroll Thermistor connection. 2. Check the resistance of the sensor to ensure values are with in specified limits.

83 85 2

30 Board Temperature Low

1. Check the ambient temperature 2. Power cycle the drive 3. If the problem still persists, replace the drive.

83 85 4

31 Fault Limit Lockout Certain faults have a trip limit, see Modbus map for details

83 85 15

Note: All Faults are displayed on the Rolling LED.

Page 30: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

6 HI-POT TESTING

There many different types of dielectric testers available. When selecting one to use ensure it

has the following features:

• Can test to voltages up to 3000VDC or higher.

• Can read leakage currents less than 10µA.

• Has Arc Detection available.

Recommended test settings:

• APPLIED VOLTAGE: 2500 VDC

• MAXIMUM LEAKAGE CURRENT: Contact Applications Engineer

• RAMP UP TIME: 8 Seconds

• DWELL TIME: 5 Seconds

• RAMP DOWN: 8 Seconds

Test Procedure:

• Setup test on a clean and dry non-conductive surface.

• Ensure samples are handled properly and using ESD precautions.

• Verify the dielectric tester is calibrated and configured per “Recommended test settings”.

• Contact Application Engineer for more details on connections and wiring setup.

• Execute Test.

• Note and record the maximum leakage current during the dwell period.

• Once test is complete, safely disconnect the component and store it properly.

Page 31: AE8-1435 R1 May 2019 EVA3 Single Phase Series Variable ...climate.emerson.com/CPID/GRAPHICS/Types/AEB/ae1435.pdf · character string (up to 32 byte ASCII). In that case, the byte

7 ACCESSORIES

Accessory Assembly P/N Drive Models Compressor/Fan Models

Compressor Molded Plug Cable

529-0243-00

4.2kW, 7.1kW

4.2kW: ZPV0212E-2E9 ZHV0212P-2E9 ZHW0152P-2E9

7.1kW: ZPV0282E-2E9 ZPV0342E-2E9 ZHV0342P-2E9 ZPV0382E-2E9 ZPV038CE-2E9 ZHW0302P-2E9 ZPV0412E-2E9 ZPV041CE-2E9

Compressor Molded Plug Cable (Service)P

1

TBD 4.2kW, 7.1kW All Compressors

Drive to Fan Motor Cable

529-0432-00 529-0483-00

4.2kW, 7.1kW

4.2kW: HC38GR224

M055PWESB-1231 7.1kW:

Genteq ½ HP Nidec ½ HP

P

1P Service cable will require field mounting of proper connector type on drive end of power cable