Page 1: 02 Communication and Project Setup

1MRG001848

© SA-T Training November 12, 2014 | Slide 1

PCM600 V2.6 Communication and project setup

Page 2: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 2

Communication setup

IED

PC

PCM600 project setup

Create new project

Handling IED objects

License Update

Set technical key

Export/Import

Report parameters

Content

Page 3: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 3

Communication protocol

TCP/IP

Ethernet ports

Front

Galvanic

Rear

Optic (one channel only)

Communication setup IED – PC

Page 4: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 4

IED Front port

Default IP address 10.1.150.3 (650/670)

Default IP address 192.168.0.254

(611/615/620/630)

Default Subnet mask 255.255.255.0

PC port setting

IP address 10.1.150.xx up to 254

IP address 192.168.0.xx up to 254

Subnet mask 255.255.255.0

Crossed over Ethernet cable

IED Front has DHCP server

Dynamically assign IP addresses

Ethernet – IED – Front connection

Page 5: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 5

Ethernet – Optic network

RX TX RX TX

Ethernet switch

IP: 172.16.0.11

Optical cable

IP: 172.16.0.10

IP: 172.16.0.12

IP: 172.16.0.13

IED Rear port

Default IP address 192.168.1.10

Default Subnet mask 255.255.255.0

This is an example of Class B network

addressing concept

The two first segments

Defines the Network

The two last segments

Define the Nodes

Rear Ethernet port NO DHCP server

Mask: 255.255.0.0

Mask: 255.255.0.0

Mask: 255.255.0.0

Mask: 255.255.0.0

Page 6: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 6

Ethernet port settings

PC Port setting

No settings in PCM600 for Ethernet port of PC

WINDOWS controls panel

Setup corresponding network

Page 7: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 7

IED Ethernet port settings

Object properties

Property group address

Page 8: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 8

PCM600 Setup

PCM600 Setup

Create project

Create Plant structure

Create IED objects

Unique IP address

Page 9: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 9

Project Manager

Open/Manage projects

Top menu File

Open/Manage Projects

Distinguish between versions

New Project

Delete project

Import project

.pcmp file

Export project

.pcmp file is created

Page 10: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 10

Create Plant Structure

Drag and drop

Objects into Plant Structure

Right click on object

Select New/General/Object

Shows current object

The IED object

Initiates configuration wizard

Note:

Only one substation level is allowed

Page 11: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 11

Online configuration

Configuration modes

Online configuration

Offline configuration

Select IED protocol

IEC61850

Note: Not possible to configure IED via SPA and LON

Page 12: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 12

Online configuration

Communication Port

Front port

Rear port

Scan IED

IED Type

IED Version

Page 13: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 13

Online configuration

Housing

Housing type

Display type

Complete

Summarize

Page 14: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 14

Offline configuration

Select IED version

Order option file

Enables ordered SW and HW

No need to synchronize

No order option specific file

Enables all functionality

Need to synchronize

License Update Tool

Page 15: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 15

Basic Plant Structure – Completed

After completed wizard

IED configurations structures

Contains base functionality

Application configuration structure

Contains the configuration data

Page 16: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 16

License update Tool

Synchronize PCM600 IED object with

physical IED

Function options

Hardware options

Page 17: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 17

License update

Synchronizing steps

Backup PCM 600 IED .pcmi

Yes/No

Update mode selection

Offline

Order option file is needed

Online

Scan IED, reads options

Complete

Page 18: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 18

Technical Key

Unique identifier for each object in Plant

Structure

IED technical key

AA1J1Q01A1

Automatic method of naming objects

AA1 – Substations

J1 – Voltage Level

Q01 – Bay

AA1J1Q01A1– IED

PCM600 and IED technical key must match

Enables transactions

Read/Write

User defined technical key

Tool executed from Plant Structure

Page 19: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 19

Set Technical Key

Set technical key steps

Information

Ok/Cancel

Reading Technical key from IED

Technical key options

Use IED Technical key

Impacts on IEC61850 configuration

Use PCM600 Technical key

Reboots IED

User-defined Technical key

Reboots IED

No special characters

Max length 13 characters

No numbers in the beginning

Page 20: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 20

Export IED object

Save and reuse configured IED

Export issued from Plant structure

Right click IED object

Creates a .pcmi file

Contains all configured data

Application Configuration

Signal Matrix

Parameter Setting

Graphical Display

Communication Management (DNP)

SCL information

Hardware configuration

Page 21: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 21

Import IED object

Use a configured IED object

Import issued from Plant structure

Bay level

Right click object

Select .pcmi file

Page 22: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 22

Create Template

Save and reuse configured IED

In a pre-defined place

For quick access

Creation of template issued from Plant

structure

Right click IED object

Creates a .pcmt file

Ends up in PCMDatabases\Templates

Contains all configured data

Same content as pcmi file

Page 23: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 23

Create new IED object from Template

Use a configured IED object

New object created from Plant

structure

Bay level

Right click object

Template Manager

Select current IED object

Press Create button

Instantiates object in Plant structure

Page 24: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 24

Copy/Paste IED object

Copy/Paste issued from Plant Structure

Right click IED object

All configured data is copied

Technical Key automatically updated

Page 25: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 25

IEC 61850 configuration SCD

SCD file

Substations Configuration Description

Contents

SCL information for all IED’s within the

substation

Export/Import SCD file

Engineering of SCL information

Substation level

Page 26: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 26

IEC 61850 configuration ICD

ICD file

IED Capability Description

New feature

Contents

All that’s configured in IED before system configuration

No SA Section

No Communication section

IEDName = TEMPLATE

Usage

System engineering

Merging to a SCD file

Export/Import of ICD file

On IED level

Page 27: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 27

IEC 61850 configuration CID

CID file

Configured IED Description

Contents

Extract of the SCD file

SCL information for one specific IED

Export/Import of ICD file

On IED level

Page 28: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 28

Report Parameters

Drawing Header information

Application configuration

Local display, Graphical display editor

Parameter settings

Communication management

Page 29: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 29

Drawing

Drawing size

Fixed to A3 Landscape

Margins can’t be change

Page 30: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 30

Hardware Configuration

Changing configuration

Add/Remove Binary Input/Output Module

(BIO)

Alter Transformer Module (TRM)

Fixed card position

Add/Remove Analog Input Module (AIM)

Alter module

Alter Power Supply Module (PSM)

Fixed card position

Page 31: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 31

Hardware Configuration

Select card in drop down menu

Add/Remove cards in fixed order

Add from p3

Remove from p6

AIM module in p4

Position 3 must be empty

Page 32: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 32

Hardware Configuration

Compare configuration

Reads hardware configuration form

IED

Issue compare from toolbar menu

Page 33: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 33

Hardware Configuration

Simple Parameter Setting

Parameterize hardware modules

Binary Inputs

Analog Inputs

Select module from hardware

configuration list

Press Parameter Setting button in

toolbar menu that will issue

simplePST

Can not Read/Write parameters form

simplePST

Page 34: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 34

Hardware Configuration

Print hardware configuration

Print preview

Page 35: 02 Communication and Project Setup

1MRG001848

Section 2

© SA-T Training November 12, 2014 | Slide 35