    PCM600Communication and project setup

    1MRG003731 B

    © SA-T TrainingSlide 1

    Section 3What to learn with this chapter

    With this resentation You will learn

    What is needed to establish the communication between the physical

    an .

    How to set IP addresses for the IED objects in PCM600 and also for the

    engineering PC itself running PCM600

    Impact of sub networks

     

    Creation of projects

    Deletion of projects

    Import/export functionality

     

    1MRG003731 B

    © SA-T TrainingSlide 2

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    2/15

    Section 3

    Communication setup IED – PC

    Communication protocols

    TCP/IP

    IEC61850 communication connectivitypackage used

    SPA onl 670 series 

    LON (only 670 series)

     

    Front port

    Galvanic

    Rear port(s) Optic

    Two channels possible for 670 series

    One channel only for 650 series

    1MRG003731 B

    © SA-T TrainingSlide 3

    Section 3Ethernet – IED – Front connection

    IED Front port

    Default IP address 10.1.150.3

    Default Subnet mask 255.255.255.0

    PC port setting

    IP address 10.1.150.1 up to 254

    Subnet mask 255.255.255.0

    650 series front port has a DHCP

    server 

    Dynamically assign IP address to the PC

    1MRG003731 B

    © SA-T TrainingSlide 4

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    3/15

    Section 3

    Ethernet – Optic network

    IP: 192.168.1.11

    Mask: 255.255.0.0

    IED Rear port

    Default IP address 192.168.1.10

    IP: 192.168.1.10  Default Subnet mask 255.255.255.0

    This is an example of Class B networkMask: 255.255.0.0

    RX TX RX TX

    Optical cablea ress ng concep

    The two first segments

    Ethernet swi tch

    IP: 192.168.1.13

     

    The two last segments

    Define the Nodes 

    Rear Ethernet port NO DHCP server 

    Mask: 255.255.0.0

    IP: 192.168.1.12

    Note! All devices that shall communicate

    with each other must belon to the same

    Mask: 255.255.0.0

    1MRG003731 B

    sub network

    Section 3Ethernet port settings at PC side

    No settings in PCM600 for Ethernet port of PC, use WINDOWS control panel

    Set TCP/IP properties on the connection to be used for the PCM600/IED communication

    1MRG003731 B

    © SA-T TrainingSlide 6

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    4/15

    Section 3

    IED Ethernet port settings

    The IP address of the IED

    object in PCM600 can be set in

    two wa s

    When creating the IED object in

    PCM600, the IP address can be

    “ 

    Wizard”

    Opening “Properties” at IED

    level object and changing the

    “IP Address” property

    1MRG003731 B

    © SA-T TrainingSlide 7

    Section 3

    PCM600 project handling

    Manage projects

    Create the plant structure

    Create the IED objects

    1MRG003731 B

    © SA-T TrainingSlide 8

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    5/15

    Section 3

    Manage Projects

     

    Create projects

    Delete ro ects

    Export projects

     All data within the PCM600

    project is exported to a file with

    extension “.pcmp”.

    Used for back-up purposes.

    Import projects

    Use earlier exported .pcmp file

    ename pro ec s

    1MRG003731 B

    © SA-T TrainingSlide 9

    Section 3Create the Plant Structure

    wo ways o crea e o ec s;

    Drag and drop from object types

    ” g c c on o ec , se ec ew

    When creating IED objects, the

    configuration wizard is

    automatically started

    Note:Only one substation level is allowed

    1MRG003731 B

    © SA-T TrainingSlide 10

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    6/15

    Section 3

    Create the IED objects

    Configuration modes

    Online configuration

    Select the protocol to usefor the PCM600/IEDcommunication

    IED available

    Offline configuration Note: Not possible to

    o ava a e

    Use order files

    commun ca e e ween

    PCM600 and IED via SPA

    and LON for the 650 series

    1MRG003731 B

    © SA-T TrainingSlide 11

    Section 3Create the IED objects, Online configuration

    Set IP address to use

    Different default values

    IED type, version, display type (Local HMI) and

    housing (size of the IED) is automatically

    “ ”or ron an earport.

     

    1MRG003731 B

    © SA-T TrainingSlide 12

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    7/15

    Section 3

    Create the IED objects, Offline configuration

    IED version must be selected

    manually

    Order option file available

    Enables only ordered SW and HWin PCM600

     

    and physical IED

    No order option file available

    Enables all functionality in PCM600

    Need to synchronize PCM600 and

    ,

    “License Update Tool”

    Possible to configure functionality in

    accepted by the IED

    1MRG003731 B

    © SA-T TrainingSlide 13

    Section 3Plant Structure, basics

    Two main sections

    IED configuration structure

    Contains basic functionality such as

    communication addresses and HW

     

    Contains the configuration data

    configured with ACT.

    Synchronized with the Main Application

    structure configured with ACT.

    1MRG003731 B

    © SA-T TrainingSlide 14

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    8/15

    Section 3

    License Update Tool

    Synchronizes PCM600 IED object with

    physical IED capabilities when it comes

    Function options

     

    1MRG003731 B

    © SA-T TrainingSlide 15

    Section 3Technical Keyno app ca e or ser es

    Is used for security reasons, more

    difficult to communicate with the wrong

    IED since the technical ke at IED 

    object in PCM600 and in physical IED

    must match. Unique identifier for each object in the

    Plant Structure

     

    Can be modified by the user 

     

    technical key, use the

    “Set Technical Key” Tool

    To change the technical key in

    PCM600 only, go to object properties

    1MRG003731 B

    © SA-T TrainingSlide 16

     

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    9/15

    Section 3

    Set Technical Key

    Technical key options

    Use IED Technical key

    Use PCM600 Technical key

    -

    No special characters

    Max length 13 characters

    No numbers in the beginning

    Note that changing the Technical key

    might have an impact on the IEC61850

    configuration in your system

    1MRG003731 B

    © SA-T TrainingSlide 17

    Section 3Export IED object

    urpose:

    Make backup

    euse a con gure

    Contains all configured data for the IED pp cat on on gurat on

    Signal Matrix

    arame er e ng

    Graphical Display

     

    SCL information

     

    File extension is “.pcmi”

    1MRG003731 B

    © SA-T TrainingSlide 18

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    10/15

    Section 3

    Import IED object

    Purpose:

    To reuse a previously configured IED

    o ec pcm e

    Import of pcmi files can be made at the

    “ ”

    1MRG003731 B

    © SA-T TrainingSlide 19

    Section 3Create Template

     

    To reuse a configured IED

    For quick access

     

    Right click IED object

      .

    Stored in PCM Databases/Templates

     

    Same contents as the pcmi file

    1MRG003731 B

    © SA-T TrainingSlide 20

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    11/15

    Section 3

    Create new IED object from Template

    Purpose:

    To reuse a configured IED

    Initiated from the Bay level object

    New->Create from Template…

    Templates structured based on IED

    type

    1MRG003731 B

    © SA-T TrainingSlide 21

    Section 3IEC 61850 configuration SCD

    SCD file

    Substations Configuration Description

    Contains

    SCL information for all IED’s within the

    substation

    Export/Import of SCD file

    Done at Substation level

    SCL engineering done outside

    ,

    needed.

    Note! When importing SCL files to PCM600, be sure to import an SCL

    file that correlates with the PCM600 project or you might loose data

    1MRG003731 B

    © SA-T TrainingSlide 22

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    12/15

    Section 3

    IEC 61850 configuration ICD

    ICD file

    IED Capability Description

    Contents

     All that’s configured in the IED before

    the system configuration

    No SA Section

    o ommun cat on sect on

    IEDName = TEMPLATE

    sage

    System engineering

     

    Export/Import of ICD file

    1MRG003731 B

    © SA-T TrainingSlide 23

     

    Section 3IEC 61850 configuration CID

    CID file

    Configured IED Description

    Contents

    Extract of the SCD file

    SCL information for one specific IED

    Export/Import of ICD file

     At IED level

    1MRG003731 B

    © SA-T TrainingSlide 24

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    13/15

    Section 3

    Report Parameters

    Footer information for printouts

     Application configuration

    Local display, Graphical display editor 

    Parameter settings

    Communication management

    1MRG003731 B

    © SA-T TrainingSlide 25

    Section 3Hardware Configuration

    oss e o manua y con gure s o pos ons

    This information is already available if you have

    created the IED object in “online mode”

    Select correct card type in correct slot position

    1MRG003731 B

    © SA-T TrainingSlide 26

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    14/15

    Section 3

    Hardware Configuration

    Compare configuration

    Reads hardware configuration from the

    configuration made in PCM600

    Before you do any other configuration. .

    Make sure that the HW configurationmatches with your physical IED

     not,you might need to spend time forreconfigure of your IED.

    1MRG003731 B

    © SA-T TrainingSlide 27

    Section 3Hardware Configuration, parameterization

    Parameter Setting

    Short-cut to parameters/settings for

    t e w en too s open

    Select HW module from hardwareconfi uration list

    Press Parameter Setting button in

    toolbar menu and that will issue the

    PST

    Only change of parameters possible

    when opening PST from the HW

    tool.

    Read/Write with the IED is done from

    “ordinary” PST.

    (e.g. open PST from the PlantStructure).

    1MRG003731 B

    © SA-T TrainingSlide 28

  • 8/16/2019 03 SEP600 601 Communication and Project Setup

    15/15

    Section 3

    Time for exercise!xerc se , rea e a pro ec

    1MRG003731 B

    © SA-T TrainingSlide 29

    Section 3