8/16/2019 03 SEP600 601 Communication and Project Setup
1/15
PCM600Communication and project setup
1MRG003731 B
© SA-T TrainingSlide 1
Section 3What to learn with this chapter
With this resentation You will learn
What is needed to establish the communication between the physical
an .
How to set IP addresses for the IED objects in PCM600 and also for the
engineering PC itself running PCM600
Impact of sub networks
Creation of projects
Deletion of projects
Import/export functionality
1MRG003731 B
© SA-T TrainingSlide 2
-
8/16/2019 03 SEP600 601 Communication and Project Setup
2/15
Section 3
Communication setup IED – PC
Communication protocols
TCP/IP
IEC61850 communication connectivitypackage used
SPA onl 670 series
LON (only 670 series)
Front port
Galvanic
Rear port(s) Optic
Two channels possible for 670 series
One channel only for 650 series
1MRG003731 B
© SA-T TrainingSlide 3
Section 3Ethernet – IED – Front connection
IED Front port
Default IP address 10.1.150.3
Default Subnet mask 255.255.255.0
PC port setting
IP address 10.1.150.1 up to 254
Subnet mask 255.255.255.0
650 series front port has a DHCP
server
Dynamically assign IP address to the PC
1MRG003731 B
© SA-T TrainingSlide 4
-
8/16/2019 03 SEP600 601 Communication and Project Setup
3/15
Section 3
Ethernet – Optic network
IP: 192.168.1.11
Mask: 255.255.0.0
IED Rear port
Default IP address 192.168.1.10
IP: 192.168.1.10 Default Subnet mask 255.255.255.0
This is an example of Class B networkMask: 255.255.0.0
RX TX RX TX
Optical cablea ress ng concep
The two first segments
Ethernet swi tch
IP: 192.168.1.13
The two last segments
Define the Nodes
Rear Ethernet port NO DHCP server
Mask: 255.255.0.0
IP: 192.168.1.12
Note! All devices that shall communicate
with each other must belon to the same
Mask: 255.255.0.0
1MRG003731 B
sub network
Section 3Ethernet port settings at PC side
No settings in PCM600 for Ethernet port of PC, use WINDOWS control panel
Set TCP/IP properties on the connection to be used for the PCM600/IED communication
1MRG003731 B
© SA-T TrainingSlide 6
-
8/16/2019 03 SEP600 601 Communication and Project Setup
4/15
Section 3
IED Ethernet port settings
The IP address of the IED
object in PCM600 can be set in
two wa s
When creating the IED object in
PCM600, the IP address can be
“
Wizard”
Opening “Properties” at IED
level object and changing the
“IP Address” property
1MRG003731 B
© SA-T TrainingSlide 7
Section 3
PCM600 project handling
Manage projects
Create the plant structure
Create the IED objects
1MRG003731 B
© SA-T TrainingSlide 8
-
8/16/2019 03 SEP600 601 Communication and Project Setup
5/15
Section 3
Manage Projects
Create projects
Delete ro ects
Export projects
All data within the PCM600
project is exported to a file with
extension “.pcmp”.
Used for back-up purposes.
Import projects
Use earlier exported .pcmp file
ename pro ec s
1MRG003731 B
© SA-T TrainingSlide 9
Section 3Create the Plant Structure
wo ways o crea e o ec s;
Drag and drop from object types
” g c c on o ec , se ec ew
When creating IED objects, the
configuration wizard is
automatically started
Note:Only one substation level is allowed
1MRG003731 B
© SA-T TrainingSlide 10
-
8/16/2019 03 SEP600 601 Communication and Project Setup
6/15
Section 3
Create the IED objects
Configuration modes
Online configuration
Select the protocol to usefor the PCM600/IEDcommunication
IED available
Offline configuration Note: Not possible to
o ava a e
Use order files
commun ca e e ween
PCM600 and IED via SPA
and LON for the 650 series
1MRG003731 B
© SA-T TrainingSlide 11
Section 3Create the IED objects, Online configuration
Set IP address to use
Different default values
IED type, version, display type (Local HMI) and
housing (size of the IED) is automatically
“ ”or ron an earport.
1MRG003731 B
© SA-T TrainingSlide 12
-
8/16/2019 03 SEP600 601 Communication and Project Setup
7/15
Section 3
Create the IED objects, Offline configuration
IED version must be selected
manually
Order option file available
Enables only ordered SW and HWin PCM600
and physical IED
No order option file available
Enables all functionality in PCM600
Need to synchronize PCM600 and
,
“License Update Tool”
Possible to configure functionality in
accepted by the IED
1MRG003731 B
© SA-T TrainingSlide 13
Section 3Plant Structure, basics
Two main sections
IED configuration structure
Contains basic functionality such as
communication addresses and HW
Contains the configuration data
configured with ACT.
Synchronized with the Main Application
structure configured with ACT.
1MRG003731 B
© SA-T TrainingSlide 14
-
8/16/2019 03 SEP600 601 Communication and Project Setup
8/15
Section 3
License Update Tool
Synchronizes PCM600 IED object with
physical IED capabilities when it comes
Function options
1MRG003731 B
© SA-T TrainingSlide 15
Section 3Technical Keyno app ca e or ser es
Is used for security reasons, more
difficult to communicate with the wrong
IED since the technical ke at IED
object in PCM600 and in physical IED
must match. Unique identifier for each object in the
Plant Structure
Can be modified by the user
technical key, use the
“Set Technical Key” Tool
To change the technical key in
PCM600 only, go to object properties
1MRG003731 B
© SA-T TrainingSlide 16
-
8/16/2019 03 SEP600 601 Communication and Project Setup
9/15
Section 3
Set Technical Key
Technical key options
Use IED Technical key
Use PCM600 Technical key
-
No special characters
Max length 13 characters
No numbers in the beginning
Note that changing the Technical key
might have an impact on the IEC61850
configuration in your system
1MRG003731 B
© SA-T TrainingSlide 17
Section 3Export IED object
urpose:
Make backup
euse a con gure
Contains all configured data for the IED pp cat on on gurat on
Signal Matrix
arame er e ng
Graphical Display
SCL information
File extension is “.pcmi”
1MRG003731 B
© SA-T TrainingSlide 18
-
8/16/2019 03 SEP600 601 Communication and Project Setup
10/15
Section 3
Import IED object
Purpose:
To reuse a previously configured IED
o ec pcm e
Import of pcmi files can be made at the
“ ”
1MRG003731 B
© SA-T TrainingSlide 19
Section 3Create Template
To reuse a configured IED
-
For quick access
Right click IED object
.
Stored in PCM Databases/Templates
Same contents as the pcmi file
1MRG003731 B
© SA-T TrainingSlide 20
-
8/16/2019 03 SEP600 601 Communication and Project Setup
11/15
Section 3
Create new IED object from Template
Purpose:
To reuse a configured IED
Initiated from the Bay level object
New->Create from Template…
Templates structured based on IED
type
1MRG003731 B
© SA-T TrainingSlide 21
Section 3IEC 61850 configuration SCD
SCD file
Substations Configuration Description
Contains
SCL information for all IED’s within the
substation
Export/Import of SCD file
Done at Substation level
SCL engineering done outside
,
needed.
Note! When importing SCL files to PCM600, be sure to import an SCL
file that correlates with the PCM600 project or you might loose data
1MRG003731 B
© SA-T TrainingSlide 22
-
8/16/2019 03 SEP600 601 Communication and Project Setup
12/15
Section 3
IEC 61850 configuration ICD
ICD file
IED Capability Description
Contents
All that’s configured in the IED before
the system configuration
No SA Section
o ommun cat on sect on
IEDName = TEMPLATE
sage
System engineering
Export/Import of ICD file
1MRG003731 B
© SA-T TrainingSlide 23
Section 3IEC 61850 configuration CID
CID file
Configured IED Description
Contents
Extract of the SCD file
SCL information for one specific IED
Export/Import of ICD file
At IED level
1MRG003731 B
© SA-T TrainingSlide 24
-
8/16/2019 03 SEP600 601 Communication and Project Setup
13/15
Section 3
Report Parameters
Footer information for printouts
Application configuration
Local display, Graphical display editor
Parameter settings
Communication management
1MRG003731 B
© SA-T TrainingSlide 25
Section 3Hardware Configuration
oss e o manua y con gure s o pos ons
This information is already available if you have
created the IED object in “online mode”
Select correct card type in correct slot position
1MRG003731 B
© SA-T TrainingSlide 26
-
8/16/2019 03 SEP600 601 Communication and Project Setup
14/15
Section 3
Hardware Configuration
Compare configuration
Reads hardware configuration from the
configuration made in PCM600
Before you do any other configuration. .
Make sure that the HW configurationmatches with your physical IED
not,you might need to spend time forreconfigure of your IED.
1MRG003731 B
© SA-T TrainingSlide 27
Section 3Hardware Configuration, parameterization
Parameter Setting
Short-cut to parameters/settings for
t e w en too s open
Select HW module from hardwareconfi uration list
Press Parameter Setting button in
toolbar menu and that will issue the
PST
Only change of parameters possible
when opening PST from the HW
tool.
Read/Write with the IED is done from
“ordinary” PST.
(e.g. open PST from the PlantStructure).
1MRG003731 B
© SA-T TrainingSlide 28
-
8/16/2019 03 SEP600 601 Communication and Project Setup
15/15
Section 3
Time for exercise!xerc se , rea e a pro ec
1MRG003731 B
© SA-T TrainingSlide 29
Section 3