tq technical manual
TRANSCRIPT
-
8/11/2019 TQ Technical Manual
1/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
TECHNICAL MANUAL
2007 TQ Environmental Plc
This manual must not be copied or reproduced in part without the express written permission of TQEnvironmental PLC. All information contained herein is subject to modification.
TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP 44 (0) 1924 380700; FAX 44 (0) 1924 361700; E-Mail: [email protected]
TQ ENVIRONMENTAL PLC BS EN ISO 9001
Filename: 7748/TMIssue 0: 09-02-07Author: G Thompson.
JOC INTERNATIONAL
TQ4400 PUMP ROOM GAS SAMPLING SYSTEM
-
8/11/2019 TQ Technical Manual
2/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
-
8/11/2019 TQ Technical Manual
3/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
MODIFICATION RECORD
CLIENT: JOC INTERNATIONAL
CUSTOMER ORDER NO: SPO504/505/506
VESSELS:
SYSTEM: TQ4400 PUMP ROOM GAS
SAMPLING SYSTEM
DOCUMENT: TECHNICAL MANUAL
VENDOR: TQ ENVIRONMENTAL PLC
WORKS JOB NO: 7748
ISSUE DESCRIPTION CHECKED DATE APP DATE
1 Technical Manual( As Built )
NDA 09-02-07 GT 09-02-07
-
8/11/2019 TQ Technical Manual
4/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
-
8/11/2019 TQ Technical Manual
5/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
CONTENTS
SECTION DESCRIPTION
1.0 Introduction.
1.1 Information Specific to this Application.
2.0 Drawings. *
3.0 TQ4400 OPERATING MANUAL.
* see section for sub-index
-
8/11/2019 TQ Technical Manual
6/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
-
8/11/2019 TQ Technical Manual
7/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
1.0 Introduction
The Flammable Gas Detection System supplied to JOC INTERNATIONAL consists
of a 3 point TQ 4400 Pump Room Gas Detection Systems for monitoring flammable,
Toxic and oxygen levels in pump room areas. The Sampling Unit supplied has a
separate control set up box responsible to alter key parameters such as calibration,
dwell times, alarm settings and other, before any changes decided to be applied the
operator must first have carefully understood it is operation.Special Caution is to be
applied when handling the set-up box parameters and technician mode*. Alarm
settings and other; before any changes decided to be applied the operator must again
first have carefully understood it is operation. Otherwise it may prevent the unit from
it is designed operation.
*Please See Sections [3] within this Technical Manual, for more details.
1.1 Information Specific to this Application.
Sequential Sampling Locations = 3
PUMP ROOM
Sample Location Name Gas Types Monitored
Line No. H2S Flammable Co O2
1
2
3
4
5
6
7
8
-
8/11/2019 TQ Technical Manual
8/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
-
8/11/2019 TQ Technical Manual
9/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
2.0 DRAWING LIST.
DOCUMENT REVISION DATE TITLE
TQ 4400 Tankscan
7748A 1 31-07-06 Analysing Unit Sample Tube & Cable Entry Details
7748 B 1 31-07-06 Electrical Schematic
7748C 2 05-08-06 Pumproom Sampling system Enclosure Dimensions
7748D 2 05-08-06 Termination Details
7748E 1 31-07-06 TQ4400 PR Unit Internal Layout
7748N 1 31-07-06 Power Supply Changeover Unit Enclosure Details
7748P 1 31-07-06 Power Supply Changeover Unit Internal Layout
7748U 1 31-07-06 TQ Interanal Gas Detector Overview
7748V 2 05-08-06 Electrical Connection
7748W 1 31-07-06 Shut off Valve with Weld Tube Detail & Vent line Weld Tube
Detail
7748Y 1 31-07-06 Weld Tube Dimensional Detail
7748Z 1 31-07-06 End of Line Filter Drawing
7748F 2 05-08-06 TQ4400 Pump Room Pneumatic Schematic
7748G 2 05-08-06 Power Supply Wiring Diagram
7748H 2 05-08-06 TQ4400 PR sensor flow fail Wiring diagram
7748J 2 05-08-06 TQ4400 PR Solenoid Valve and Relay CCT Diagram
7748K 2 05-08-06 TQ4400 Set up Display Wiring Diagram
7748L 1 31-07-06 TQ4400 Front Panel Circuit Diagram
-
8/11/2019 TQ Technical Manual
10/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
-
8/11/2019 TQ Technical Manual
11/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
*
PROJECTION
SCALE
N/A
7748
JOC
INTERNATIONAL
ANALYSING
UNITSAMPLE
TUBEANDCABL
E
ENTRYDETAILS
Sample
Linesx3
Fla
me
Arre
stors
x
4
HAZARDOUSAREA
SAFEAREA
Brass
Compression
FittingsForConnection
NOTES
1)3=Num
berofsamplepoints
2)Ventlin
eistobelettoatmospherew
iththe
outletar
rangedinasafelocationawayfrom
ignition
sources.
Theendoftheventline
mustbe
bentdownwards
topreventwater
ingress.
3)Shutoffvalvesandpenetrationssupplied
4)8mmODCoppersamplelinesrecommended,
Fittingo
nflamearrestorsmaybechangedto
suitothersizes.
AnalysingUnit
SampleLinesConn
ectDirectlyontoFlame
ArrestorsViaBrassCompressionFittings
(Flamearrestorsare1/8"BSP/Pinternal
thread
forconnectionto1/8"BSP-P
(ISO)Malefittings.)
1/4"BSPPSt-St
Shutoffvalve
sx
3
(SuppliedasL
ooseItems)
SeeNote3
CabinetGas
InternalLeak
Detector
Penetra
tionsx4
(150mmWeldTubes)
REARVIEW
OF
FIXINGBRACKET
15
29
20
54
10
SIDEVIEW
OF
FIXINGBRACKET
20
FIXINGDETAIL
7748A1
CablesEnterThrough
BottomleftofCab
inet
VentFlameA
rrestors
(ConnectionV
ia8mm
BrassCompressionFitting)
8mmVentLine
(SeeNote2)
TestPoint
TQ4400
PUMP
ROOMSAMPLINGSYSTEM
UserInterfaceDisp
lay
31-0
7-0
6
*
TQ4400CO
NTROLUNIT
ALARM
1
ALARM
2
SYSTEM
HEALTHY
UP
DOWN
SELECT
MENU
WATCHDOG
-
8/11/2019 TQ Technical Manual
12/99
-
8/11/2019 TQ Technical Manual
13/99
7748B1
7748
JOC
INTERNATIONAL
31-0
7-0
6
G.T
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
ELECTRICAL
SCHEMATIC
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
PROJECTION
SCALE
N/A
NOTES
1)Cab
leSpe
cisaTQrecommendation.
2)Cab
inetG
asAlarmV
.F.C.
isgeneratedfrom
powersup
plychangeoverunitand
allowsfor
remotemonitoringofleakswithinthe
gassamplingdetection/controlunitifrequired.
3)Provision
isprovidedforremotemonitoringof
mainsfail
,systemfault&Low/Highconcentrat
ion
alarms,ViaVo
ltfreecontacts,ifrequired.
GasDetection\ControlU
nit
PowerSupply
ChangeoverUnit
3Core1
.5mmsqBlack
ArmouredCabletoBS6883
3Core
1.5
mmsqBlack
ArmouredCablewithOveral
l
ScreentoBS6883
SAFEAREA
220Vac
60Hz
10A
220Vac
60Hz10A
2Core1
.5mmsq
BlackArmoured
CabletoBS6883
3Core
1.5
mmsq
BlackArmoured
CabletoBS6883
CabinetGasAlarm
V.F.C.
(SeeNote2
)
2Core1
.5mmsq
Black
Armoured
CabletoBS6883
CabinetGasInternal
LeakDetector
STANDBY
MAIN
* *
31-0
7-0
6
31-0
7-0
6
TQ4400CONTROLUNIT
ALARM
1
ALARM
2
SYSTEM
HEALTHY
UP
DOWN
SELECT
MENU
WATCHDOG
-
8/11/2019 TQ Technical Manual
14/99
-
8/11/2019 TQ Technical Manual
15/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748C2
ProjNo.
Client.
Drn.
Date.
12-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
PUMPROOMSAMPL
ING
SYSTEM
ENCLOSUREDIMENS
IONS
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
12-0
7-0
6
* *
12-0
7-0
6
PROJECTION
SCALE
N/A
JOC
INTERNATIONAL
7748
TQ4400
PUMP
ROOMSAMPLINGSYSTEM
NOTES:
1)Pro
tect
ion
Rat
ingo
fIP66
2)Samp
leline
ODcan
bechanged
ifrequ
ired
LEFTHan
d
Open
ing
Door
1
2
3
VENT
546
MOUNTING
BRACKET
DETAIL
R4
.5
R7
.5
1
2
3
4
5
6
7
8
SAMPLELINES
(UPTO8)
VENT
CABLEENT
RY
(UPTO7M20GLANDS)
FRONT
FRONT
400
360
263
500
67
185
TOPOF
CABINE
T
BOTTOMOF
CABINET
162
SAMPLES+VENT
8MMDiaTu
bing
(NOTE2)
TUBINGENTRY
86
605
90
15
210
91
29
05-0
8-0
6
G.T
05-0
8-0
6
N.D.A
1.
Int.GasDetector
Moved
-
8/11/2019 TQ Technical Manual
16/99
-
8/11/2019 TQ Technical Manual
17/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748D2
ProjNo.
Client.
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
TERMINATIONDETA
IL
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
31-0
7-0
6
PROJECTION
SCALE
N/A
JOC
INTERNATIONAL
7748
TQ4400PUMP
ROOMSAMPLINGSYSTEM
CommonAla
rm2
i.e30%LEL
CH4
19%VOLO2
15PPMH2S
24VDCO
/P
(BEACON
)
CommonAlarm2
i.e30%LELCH4
19%VOLO
2
15PPMH2
S
24VDCO/P
(SOUND)
220vac
60Hz
FromPOWER
SUPPLYUNIT
ISOLATOR
"C"
9
101112
1
2
3
7
8
AL1
AL2
FAULT
RL1-1
VFC
RL2
RL3
TBF
-03
9
101112
1
2
3
7
8
RL3
RL2
5
4
7
2
6
3
8
1
RL1
3 1 2 4
F4
F3
F2
F1
2A
Isolator
N N
3 N2 E
1 L
24V
TBF-01
TBF-02
TB-01
0V
2
1
4
3
4
3
2
1
4
3
2
1
0V
3 1 2 4
F5F6F7
5
4
7
2
6
3
8
1
54
72
63
81
6
4
5AL1
RL1-2 6
4
5
05-0
8-0
6
G.T
05-0
8-0
6
NDA
ExtraC
ontactsAdded
1.
-
8/11/2019 TQ Technical Manual
18/99
-
8/11/2019 TQ Technical Manual
19/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748E1
ProjNo.
Client.
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
31-0
7-0
6
PROJECTION
SCALE
N/A
JOC
INTERNATIONAL
7748
TQ4400PUM
P
ROOMSAMPLINGSYSTEM
PUMP
C
ONTROL
BOARD
ForTermination
SeeDrg.
7748D
1
F1
NV1
TBF
-01
SolenoidBankMounting
SUPPRESSOR
T R U N K I N G
T R U N K I N G
TBF
-02
RL 1
RL 2
RL 3
TBF
-03
TB01
LeftHand
Moun
tingPlate
R
ightHand
Mo
un
tingPlate
TBO2
ISOLATOR
FUSES
FLOW
FAIL
O2
H2S
CH4
TQ123-2
51
TQ123-5
31
TQ4400PR
INTERNALLAYOUT
-
8/11/2019 TQ Technical Manual
20/99
-
8/11/2019 TQ Technical Manual
21/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
POWERSUPPLY
CHANGE-O
VERCONTROL
UNITENCLOSUREDE
TAIL
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
PROJECTION
SCALE
N/A
380
322
380
RightHandOpeningDoor
10
210
410
570
580
POWERSUPPLYCHANGE
-OVERUNIT
FORGASSAMPLINGSYSTEM
4Holes
x10.0mm
220V
60Hz
ACStan
dby
Supply
220V60Hz
ACSupp
ly
toMain
Panel
Cabinet
GasAlarm
V.F.C
(SeeNo
te2)
'U'
'U'
'V'
'V'
'V'
220V
60Hz
ACMain
Supply
GasDetection/
ControlUnit
Internal
Leak
Detector
'A'
'A'
'A'
25
80
135
190
245
300
'A'
65
NOTES:
1)Gland
s:
'U'To
SuitCableOD11
.5mm
'V'To
SuitCableOD11
.9mm
2)Onlyrequiredifusingcabinetgasremote
monitoringfacility
.
DESIGNED&MANUFACTUREDBY:
TQENVIRONMENTALPLC
FlanshawWay,Wakefield,W
Yorks
England,WF29LP
Tel:+441924380700
Fax:+441924361700
Email:[email protected]
website:http://www.tqplc.com
* *
31-0
7-0
6
31-0
7-0
6
31-0
7-0
6
7748
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
JOC
INTERNATIONAL
7748N1
MAINSUPPLY
STANDBYSUPPLY
GASALARM
STANDBYFAIL
ALARMRESET
ALARMMUTE
LAMPTEST
-
8/11/2019 TQ Technical Manual
22/99
-
8/11/2019 TQ Technical Manual
23/99
6
K2
F4-
5
10
(SeeNote2)
RESET
MUTE
TEST
T
BF-0
1
ISOLATOR'A'
K1
F1-
3
PSU1
TB-0
1
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
POWERSUPPLY
CHANGE-O
VERUN
IT
INTERNALLAYOU
T
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
PROJECTION
SCALE
N/A
4
*
E 14
NOTES:
1)ItemNumbersrefertopartslist
SeeDoc.4826DC
2)ShowsItemsMountedon
EnclosureDoor.
3)EMCSuppressor'slocatedunder
railcontaining
Isolator's
31-0
7-0
6
31-0
7-0
6
7748
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
JOC
INTERNATIONAL
7748P1
MAIN
STA
NDBY
STA
NDBY
FAIL
GASALARM
7
12
RL1 5
1
2
3
8
9
RL2-
3
5
13
16
17
DT1-
4
FERRITE
RING
ISOLATOR'B'
E
EMC
SURPRESSOR
15
9123
TBF-0
2
123
ISOLATOR'C'
E
EMC
SURPRESSOR
FerriteRing
Buzzer
*
31-0
7-0
6
-
8/11/2019 TQ Technical Manual
24/99
-
8/11/2019 TQ Technical Manual
25/99
TQENVIRONMENTAL
PLC
FlanshawWay
Wakefield
WestYorkshire
WF29LP
Proje
ctTitle.
Draw
ingTitle.
DwgNo.
7748U1
ProjNo.
7748
Client.
Drn.
Date.
31
-07
-06
G.T
Chkd.
Date.
11
-08
-99
D.A.W
App.
Date.
12
-08
-99
D.A.W
Sig.
Date.
R
evisions.
No.
Copyrig
hto
f
CWeb:http//www.t
qplc
.com
Email:sales@tqplc
.com
TQ4400PUMP
RO
OMSAMPLINGSYSTEM
TQTANKSCAN
INTERNALGAS
D
ETECTOROVERVIEW
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
Temp
lateChanged
1.
31
-07
-06
* *
31
-07
-06
PROJECTION
SCALE
N/A
JOC
INTERNATIONAL
126F
NC
NO
COM
24V
0V
Bl
Gr
Red
TQ122
-212
Flammab
le0
-100%
LEL
SENSORCONNECT
ION
+
100uF
25V
Electro
yltic
Capa
citor
-
Blk
Red
232
128W
hite
1 2 3
A21A
185
6 7
TB
-01
27White
LOCATEDONTO
P
OFSAMPLINGUN
IT
CABINET
TOTBF
-02OF
POWER
SUPPLYUNIT
SEEDWG'S
7748P&7748V
3
2
1
A2-
A1+
6
7
4 5
2
8
1
10
TQ1220
-100%LELCH4
PTNO122
-210
-
8/11/2019 TQ Technical Manual
26/99
-
8/11/2019 TQ Technical Manual
27/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748V2
ProjNo.
Client.
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ELECTRICAL
CONNECTION
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
31-0
7-0
6
PROJECTION
SCALE
N/A
JOC
INTERNATIONAL
7748
PUMPROOM
SAMPLINGSYSTEM
T
BF-0
2 4
1
23
TBF-0
1
45
6
TB
F-0
3 789
123
TBF
-01
ISOLATOR
'A'
E
ISOLATOR
'B'
E
123
TBF
-02
12
3ISOLATOR
'C'
E
E
TBF-0
1
123
NL
N
L
NL
NL
TQ4400
SAMPLINGSYSTE
M
7748D
TQINTERNAL
GASDE
TECTOR
(LOCA
TEDON
TOPOFSAMPLING
CAB
INET)
DWG
7748U
POWERSUPPLYUNIT
DWG7748P
MAINS
SUPPLY
220VAC
60HZ
6A
STANDBY
SUPPLY
220VAC
60HZ
6A
MAINS
FAIL
VOLT
FREE
CONTACT
GASAL1
VOLTFRE
E
CONTACT
10%LELCH4
10PPMH2
S
19%VOLO
2
GASAL2
VOLTFREE
CONTACT
30%LELCH4
15PPMH2S
18%VOLO2
24V
DC
ALMO/P
24VDC
ALM
O/P
3Core1
.5mmsq
Black
A
rmouredCabletoBS6883
3Core1
.5m
msq
BlackArmoured
CabletoBS
6883
2Core1.5mmsqBlackArmouredCabletoBS6883
IFREQUIRED
IFREQUIRED
2Core1.5mmsqBlackArmouredCabletoBS6883
IFREQUIRE
DIFREQUIRED
IFREQUIR
EDIFREQUIRED
101112
SYSTEM
FAULT
VOLT
FREE
CONTACT
IFREQUIRED
123
GASAL1
VOLTFREE
CONTACT
10%LELCH4
10PPMH2S
19%VOLO2
IFREQUIRED
05-0
8-0
6
G.T
05-0
8-0
6
N.D.A
1.
Alarm
C
ontactaddedtoTBF-0
3
-
8/11/2019 TQ Technical Manual
28/99
-
8/11/2019 TQ Technical Manual
29/99
7748W1
JOC
INTERNATIONAL
TQ4400P
UMP
ROOMSAMPLINGSYS
TEM
7748
31-0
7-0
6
31-0
7-0
6
*
SHUTOFFVALVEW
ITH
WELDTUBEDETAI
L&
VENTLINEWELDTUBE
DETAIL
N/A
SCALE
PROJECTION
DATE
CLIENT
SERVICE
DEVELOPMENT
PRODUCTION
ISSUECONTROL
Emai
l:sa
les@
tqp
lc.c
om
Web:
http
//www
.tqp
lc.c
om
C
Copyrightof
No.
Revisions.
Date.
Sig.
Date.
App.
Date.
Chkd.
G.T
Date.
Drn.
Client.
ProjNo.
DwgNo.
DrawingTitle.
ProjectTitle.
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
TQENVIRONMENTAL
PLC
ITEM
NO.
DESCRIPTION
PARTNO
.
QTY
1 2 3
1/4"ST-S
TBallValve
1/4"BSPP-
1/4"
BSPPParra
llelNipple(Brass)
1 1
4 5
1/4"BondedWasher
1/4"BSPP-8mm
ODCompressionFitting(Brass)
4 2
BULKHEAD BULKHEAD
5
4
2
3
1
5
4
4
4
50
615-0
08
611-0
23
689-
473
610-1
01
105
ThreadedWeld
Tube(150mm)
615-0
07
1
N
OTES
1
)SeeDrg.7
748Yforweldtubedetails
.
150
100
1
5
4
4
5
DESCRIPTION
BULK
HEAD
BULK
HEAD
SAMPL
ELINE
VENTL
INE
-
8/11/2019 TQ Technical Manual
30/99
-
8/11/2019 TQ Technical Manual
31/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
G.T.
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
WELDTUBE
DIMENSIONAL
DETAILS
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
*
PROJECTION
SCALE
1:5
150
19
.05
Drill&TapBothEnds
For1/4"BSPParallel
19
.05mm
13
.16mm
11
.46mm
NOTES:
1)Mater
ial:19
.05mmODMildSteelBrightTube
WallT
hickness6
.35mm
15
15
31-0
7-0
6
31-0
7-0
6
7748
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
JOC
INTERNATIONAL
7748Y1
-
8/11/2019 TQ Technical Manual
32/99
-
8/11/2019 TQ Technical Manual
33/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748Z1
ProjNo.
Client.
JOC
INTERNATIONAL
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ENDOFLINEFILT
ER
DRAWING
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
31-0
7-0
6
PROJECTION
SCALE
7748
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
316LSt/St
housing
PourosSt/St
w
ashablefilter
element
316LSt/St
endcap
Oring
Vitondowty
seal
8mmto1/4BSP
paraellelfittingBrass
N/A
-
8/11/2019 TQ Technical Manual
34/99
-
8/11/2019 TQ Technical Manual
35/99
Pump
FILTER
8Way
So
leno
idBan
k
VENT
FLOW
INDICATOR
NOTES:
1)AllInternalp
ipework
fittings
tobe
6.0
mm
ODUOS
8mm
Compress
ion
Fittings
Samp
le
Lines
8
Pressure
Differen
tial
Valve
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748F2
ProjNo.
Client.
Drn.
Date.
12
-07
-06
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
TQ4400PUMPROOM
PNEUMATIC
SCHEMTAIC
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
12
-07
-06
* *
24-0
1-0
0
PROJECTION
SCALE
N/A
12
-07
-06
*
P r e s s
u r e
D i f f e
r e n
t i a l
F l o w
F a i
l
D e v i c e
+ V
e
- V e
GD129
FLAM
SENSOR
TQ123
H2S
SENSOR
TQ123
O2
SENSOR
7654321
FLAME
ARRESTORS
BYPASS
VALVE
3Way
CALIBRATION
VALVE
CALIBRATION
PORT
JOC
INTERNATIONAL
7748
TQ4400PUM
P
ROOMSAMPLINGSYSTEM
05
-08
-06
G.T
05
-08
-06
N.D.A
Tex
tCh
anged
1.
-
8/11/2019 TQ Technical Manual
36/99
-
8/11/2019 TQ Technical Manual
37/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748G2
ProjNo.
Client.
JOC
INTERNATIONAL
Drn.
Date.
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
24-0
1-0
0
PROJECTION
SCALE
N/A
7748
TQ4400
PUMP
ROOMSAMPLINGSY
STEM
31-0
7-0
6
G.T
POWERSUPPLY
WIRINGDIAGRAM
1/2/3+5
13+24
-0V
L N E
1
ISOLATOR
PUMP
PSU
1 2
TBF-0
2
RL2
6
F6(1A)
F5(1A)
F4(1A)
14
18
5
57
6
240/
110Vac
60Hz
2A
EMC
SUPRESSOR
Brown
Blue
85-
254
VAC
NOTE
S:
1)All
ACwiringtobe
0.5mmtri-ratedU
.O.S.
All
DCwiring
tobe
20A
WGUL1007UOS
Violet
TBF01
3
+24 0
V+24
LOCAL
VISUAL
LOCAL
AUDIBLE
L N E
4
0V
Green/Yellow
4.0
mm
Green/Yellow
Enclosure
EarthStud
Red
Blue
4/5/6/7
31-0
7-0
6
*
F7
5
2
TB-0
1
0V
5
Black
Red
Red
15Red
16Red
17Red
17
8/9+12
F2(2A)
F1(2A)
10Violet
11Violet
ToControlboardConn6Pin2
Seedw
g7748H
TodisplayboardConn6Pin2
Seedw
g7748L
F3(1A)
12Orange
ToControlboardConn6Pin3
Seedwg7748H
TodisplayboardConn6Pin3
Seedwg7748L
6 7 8
ToFlowFailUnit
Seedw
g7748H
Black
Red
Orange
05-0
8-0
6
G.T
05-0
8-0
6
N.D.A
1.
TextChanged
-
8/11/2019 TQ Technical Manual
38/99
-
8/11/2019 TQ Technical Manual
39/99
TQENVIRONMENTAL
PLC
FlanshawWay
Wakefield
WestYorkshire
WF29LP
ProjectTitle.
Draw
ingTitle.
DwgNo.
ProjNo.
Client.
Drn.
Date.
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
R
evisions.
No.
Copyrightof
CWeb:http//www.tqplc.com
Email:[email protected]
TQ4400PRSENSOR,
FLOWFAIL
CIRCUITDIAGRAM
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
PROJECTION
SCALE
N/A
23
TQ4400
Con
tro
lBoar
d
NOTES:
1)ALLWIRINGTOBE
20AWGUL1007U
.O.S
3 2 1
24V
5V 0
V
CONN8
CONN6
1
Red
Blue
F1
F4
TB
-01
0V
Red
14
Violet
10
Black
5
*
7748H2
31-07-06
31-07-06
7748
TQ4400PUMP
ROOMSAMPLINGSYSTEM
2Core
Tw
isted
Pair
WithOveral
lScreen
ToConn8
ofDisplay
Board
JOC
INTERNATIONAL
3
CONN12
Links
Lk1
-In
Lk2
-AInpos
2-3
BInpos
4-5
CInpos
7-8
DOu
t
Lk3
-N/A
Lk4
-11
-Inpos
1-2
(Towar
dMH4)
Lk12
-In
Lk13-
Inpos
2-3
Lk14-
In
Lk15
-Inpos
2-3
(Towar
dm
iddleo
fPCB)
Lk16-
Inpos
2-3
(Towar
dou
tsideo
fPCB
)
Lk17-
Inpos
2-3
(Towar
dou
tsideo
fPCB
)
Cabledetailadded
Re
d22
DIFFERENTIAL
F/FAIL
DEVICE
PtNo
.140
-021
0V
SIG
12V
2
1
CONN2
2 87
CONN1
654321
Topushb
uttons
See
Dwg.
7748K
Black 5
12
CONN9
Green
/
Yel
low
9
Red
Clear
Black
123
34
PO
GD129
(CH4Sensor)
+-
FB
H2S
SENSOR#1
PO
OXYGEN
SENSOR#2
PO
56
PO
Red
Blue
1
2
CONN15
9
3
4
87
CONN1
654321
To
So
leno
ids
See
Dwg.
7748J
2
3
1
F3
TB
-01
0V
Orange
12
Black
5
Toalarmre
lays
See
Dwg
.4826CB
Yel
low
21
Black
5
TOCONN
12
PIN3DIS
PLAY
CARDSE
E7748L
3Core
BELDON
TYPECABLE
G.T
05-08-06
N.D.A
05-08-06
1.
-
8/11/2019 TQ Technical Manual
40/99
-
8/11/2019 TQ Technical Manual
41/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748J2
ProjNo.
Client.
JOC
INTERNATIONAL
Drn.
Date.
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
* *
24-0
1-0
0
PROJECTION
SCALE
N/A
7748
TQ4400PUMP
ROOMSAMPLINGSY
STEM
31-0
7-0
6
TQ4400PR
SOLENOIDVALVE
&
RELAYCCTDIAGR
AM
1
2
3
4
5
6
7
8
9
CONN3
+24V
G.T
31-0
7-0
6
*
9 8 7 6 5 4 3 2 1
CONN 15
+24V
RL
1
RL2
RL3
A2
A1
A2
A1
A2
A1
1
2
3
AL1
1 8
1 8
1 8
7
8
9
AL2
101112
Fault
2 4
3
2 4
3
2 4
3
50515
2
535455
565758
White
White
TBF-0
3
TBF-0
3
TBF-0
3
White
SOL#1
SOL#2
SOL#3
SOL#4
SOL#5
SOL#6
SOL#7
SOL#8
Contro
lBoard
Red45
Blue46
Red43
Blue44
Red41
Blue42
Red39
Blue40
Red37
Blue38
Red35
Blue36
Red33
Blue34
Red31
Blue32
TB-
02
R
ed
28
21
Red23
Black24
Black
25
Black
26
Red23
Red23
4
5
6
AL1
5
6
150
151
152
White
TBF-0
37
RL1-1
RL1-2
05-0
8-0
6
G.T
05-0
8-0
6
N.D.A
1.
RL1ContactsAdded
-
8/11/2019 TQ Technical Manual
42/99
-
8/11/2019 TQ Technical Manual
43/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo.
7748K1
ProjNo.
Client.
JOC
INTERNATIONAL
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
TQ4400SETUPDISP
LAY
WIRINGDIAGRAM
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
*
PROJECTION
SCALE
7748
N/A
TQ4400PUMP
ROOMSAMPLINGSYSTEM
1)Connectribboncable
redwiretopin1
.
A C
DISPLAY(PartNo.
814-
010)
REDWIRE
TOBOTTOM
16PIN
CONNECTO
R
200mm
1
16WayRibbon
CONNECTTOCONN5
OFPCB4200
I1
PtNo.
913-0
16-0
02
2)CutPCBTracksFrontand
RearasIndicated,
andFit
6R2Limmiting
Resistor
SolderedtoPads.
3)AllWireToBe20AWG
UL1007
CutTrack
CutTrack
6R2@0
.6W
A K
Rear
Of
Display
NOTE:
SELECT
UP
DOWN
MENU
Grey
Orange
White
CONN1
,PIN8
CONN1
,PIN5
CONN1
,PIN4
Blue
CONN1
,PIN1
SeeDwg.
7748H
ControlPCB
91
92
93
94
SeeDwg.
7748H
ControlPCB
95Red
Conn13, Pin 9
05-0
8-0
6
G.T
05-0
8-0
6
N.D.A
ButtonConnectionsChd
1.
-
8/11/2019 TQ Technical Manual
44/99
-
8/11/2019 TQ Technical Manual
45/99
TQENVIRONMENTAL
PLC
Flanshaw
Way
Wakef
ield
Wes
tYorksh
ire
WF29LP
ProjectTitle.
DrawingTitle.
DwgNo. 7
748L1
ProjNo.
Client.
JOC
INTERNATIONAL
Drn.
Date.
31-0
7-0
6
G.T
Chkd.
Date.
App.
Date.
Sig.
Date.
Revisions.
No.
Copyrightof
CWeb:
http
//www
.tqp
lc.c
om
Emai
l:sa
les@
tqp
lc.c
om
TQ4400PRFRONTPA
NEL
CCTDIAGRAM
ISSUECONTROL
PRODUCTION
DEVELOPMENT
SERVICE
CLIENT
DATE
31-0
7-0
6
*
PROJECTION
SCALE
N/A
7748
TQ4400PUMP
ROONSAMPLINGSYST
EM
1)AllWiringtobe20AWG
UL1007UOS
NOTES:
+24V
SYSTEMHEALTHY
ALARM
2
ACK
SKIP
HOLD
RESET
64
66
60
61
62
63
ALARM
1
65
69Red
White
White
White
White
Black
Black
Black
+
-Buzzer
23
TQ4400
DisplayBoard
3 2 1
24V
5V 0
V
CONN8
CONN6
1
Red
Blue
F2
F5
TB-0
1
0V
Red1
5
Violet
11
Black
5
2
CoreTwisted
PairW
ithOverallScreen
ToConn8
ofControl
Board
3
CONN12
Red22
2
87
CONN1
654321
B
lack 5
Red
Blue
1
2
CONN15
9
3
4
CutTrack
6R2
@0.6W
A K
RearOf
Display
67
A C
DISPLAY(Par
tNo
.814
-010)
REDWIRE
TOBOTTOM
16PIN
CONNECTOR
200mm
16WayRibbon
CONNECTTOCONN5
OFPCB4200I1
PtNo
.913
-016
-002
CutTrack
-
8/11/2019 TQ Technical Manual
46/99
-
8/11/2019 TQ Technical Manual
47/99
DOC: 7748/TMTQ ENVIRONMENTAL PLC
Tel: +44(0) 1924 380700
3.0 TQ4400 Operating Manual
-
8/11/2019 TQ Technical Manual
48/99
-
8/11/2019 TQ Technical Manual
49/99
TQ Environmental Plc
Filename: Technical Manual Page 1 of 51
TQ4400 PUMPROOM
GAS SAMPLING SYSTEM
OPERATING MANUAL
TQ Environmental Plc 2007
This manual must not be copied or reproduced in part without the express written
permission of TQ Environmental PLC. All information contained herein is subject to
modification.
TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP
44 (0) 1924 380700; FAX 44 (0) 1924 361700.
E-mail : [email protected]
Web Site : www.tqplc.com
TQ ENVIRONMENTAL PLC BS EN ISO 9001
Date of Issue: 25thOctober 2006
Author: G Thompson
-
8/11/2019 TQ Technical Manual
50/99
Page 2 of 51 Filename: Technical Manual
-
8/11/2019 TQ Technical Manual
51/99
TQ Environmental Plc
Filename: Technical Manual Page 3 of 51
CONTENTS
1. INTRODUCTION 52. SYSTEM DESCRIPTION 7
2.1 Pneumatics 7
2.2. Sensors 9
2.3 Control and Display Electronics. 10
2.4 Power Supply Change Over Unit 13
2.5 Outputs. 13
2.6 Technical Specification 14
3. OPERATION 15
3.1 System Start-up 15
3.2 Normal Operation 15
3.3 Panel Controls 163.4 Alarm Conditions 18
4. SYSTEM SETTINGS 21
4.1 Set up Controls 21
4.2 Power Up 21
4.3 Set Up-Menu Access 22
4.4 Parameters 24
4.5 Sensor Menu 28
4.6 Technician Sub Menu 32
4.7 Sensor Menu 37
5. INSTALLATION 405.1 TQ4400 Analysing Unit 40
5.2 Power Supply Change over Unit 40
5.3 Manual Shut Off Valves 40
5.4 End of Line filters 42
5.5 In-Line Filters 42
5.6 Sample Lines 43
6 COMMISSIONING 45
6.1 Installation. 45
6.2 System Power Up. 45
6.3 Setting the Flow Rate 46
6.4 Sample Location Set-Up Test 466.5 Testing Gas Concentration Alarms 46
6.6 Testing Analysing Unit Cabinet Gas Detector 46
7 SCHEDULED MAINTENANCE 47
7.1 System Confidence Test Sequential Sampling Part 47
7.2 Filter Check 47
7.3 System Calibration (All Sensors) 48
7.4 Pump Service 48
7.5 Testing and Calibrating the TQ126F 48
8 PARTS LIST 50
Appendix A 51
-
8/11/2019 TQ Technical Manual
52/99
-
8/11/2019 TQ Technical Manual
53/99
TQ Environmental Plc
Filename: Technical Manual Page 5 of 51
1. INTRODUCTION
The TQ4400 Pump room sampling system is a multipoint, sequential, aspirated, gas
sampling system. The System is designed to meet with IMO / SOLAS requirements,
and comply with classification rules for monitoring Void Spaces on board Gas
Carriers and Oil & Gas Tankers, in areas adjacent to the cargo areas.
The TQ4400 Pump room sampling system extracts a gas sample from a desired
location, via transport lines to an analysing unit where the sample is monitored for
Flammable, Toxic and Oxygen gases. The TQ4400 in its usual form uses fixed
gas sensor heads to constantly monitor gases in conjunction with solenoids and a
pump to make this into a cost effective sampling system.
** The TQ4400 Pump room sampling system should not be regarded as a primary
unit for the safety of the personnel within the Pump room. Portable personal hand
held devices are recommended as primary protection for personnel in confined spaces.
**
The number of locations for a TQ4400 is restricted to 8. Any more, then the TQ 4400
Ballast tank monitoring system should be used
Typical explosive and toxic gas sensors, which can be installed within the TQ4400,
can be seen in table 1, (other gases are available on request.)
Explosive Toxic
Methane 0-100% LEL H2S Various ranges
Butane 0-100% LEL CO Various ranges
Methane 0-100% VOL CO2 Various ranges
Butane 0-100% VOL Oxygen 0-25% VOL
Table 1
The TQ4400 is capable of providing individual low and high alarm outputs for
each Gas sensor installed and corresponding alarm relays. This can provide an
interface with alarm management systems, remote mimic panels, and audible / visual
warning devices.
The TQ4400 Unit is mounted within the cabinet. The operator interface is via four
push buttons and a backlit LCD. During normal operation the LCD display will
provide the gas type and sample concentration for each individual location.
-
8/11/2019 TQ Technical Manual
54/99
Page 6 of 51 Filename: Technical Manual
-
8/11/2019 TQ Technical Manual
55/99
TQ Environmental Plc
Filename: Technical Manual Page 7 of 51
2. SYSTEM DESCRIPTION
The TQ4400 Pump room sampling system standard Analysing Unit is housed in a
wall-mounted enclosure complete with front panel Display Unit. The enclosure
contains all electrical, electronic and pneumatic equipment required to monitor,
display, control and provide alarm outputs for the relevant locations.
The TQ4400 Pump room sampling systemis divided into the following main
components:
Pneumatics
Sensors
Control & Display Unit
Power Supply Change Over Unit
Sample Line Accessories
Outputs
Technical Specification
2.1 Pneumatics
Every Sample Line from the relevant location is firstly connected to its
respective external Shut-off Valve to provide sample line isolation. The
sample then passes through a flame arrestor mounted externally on the bottom
of the cabinet, and into the Analyser Unit.
The typical Analysing Unit contains the following pneumatic devices:
Solenoid Valves
Particulate Filter Pump
Flow Detector
Leak Detection
2.1.1 The Solenoid Valves are mounted singularly on the back panel of the
cabinet. Each solenoid is then individually plumbed to the gland plate
where they are fitted with a deflagration flame arrestor from which the
sample line can be connected.
Connected to each solenoid is a timer relay the time set on this relaygoverns the sample time. Each timer will then trigger the subsequent timer
on completion of sample, therefore resulting in a sequential sample
Each valve is complete with a 24V D.C. coil, and connection to each coil
is via a 3 pole connector containing an LED and snubbing diode.
2.1.2 The Particulate Filter is fitted with a micro-fibre filter element, which
cannot be cleaned and therefore must be replaced when it is suspected of
reducing air flow. This unit is also fitted with a poly-carbonate bowl to
allow visual inspection of the filter element. Spare filter elements can be
supplied, refer to Section 8 for Part numbers.
-
8/11/2019 TQ Technical Manual
56/99
Page 8 of 51 Filename: Technical Manual
2.1.3 The Pump is an Industrial type to ensure adequate flow rates for the
larger installations. As an example on transport tube dimensions of
4.0mm I/D, flow rates in excess of 4 litres/min. are achievable for sample
line lengths up to 300 metres. Based on these figures, sample times for a
300 metre sample line will be in the order of 1 minute, providing sharp
bends and fittings are kept to a minimum. A Pump Service Kit can be
supplied refer to Section 8 for Part numbers
2.1.4 The Flow Meter is fitted in the sample flow line to indicate airflow to the
sensors and works in conjunction with the Sample by-pass needle valve.
The steel float, sensing ring and control relay, are all part of the flow fail
device. If the float passes down through the sensor a Low Flow signal is
sent to its control relay. When flow returns the float will raise back
through the sensor and the signal to its control relay will revert to normal.
2.1.5 A Leak Detection System is incorporated within the TQ4400 Analyser
enclosure and monitors for any accumulation of flammable gases within
the enclosure. This system utilises a TQ122 catalytic flammable gasdetector fitted in the top of the enclosure, which is connected to a
TQ126Fcontroller fitted in the Power Supply Change-over Unit.
If the gas concentration within the enclosure exceeds 30% LEL the Power
Supply Change-over Unit will disconnect the power supply to the
TQ4400Analysing Unit. The power supply cannot be re-connected until
the gas concentration has fallen below the alarm level and a manual reset
at the Power Supply Change-over Unit has been carried out.
2.1.6 Sample Line Equipment is optionally available in several forms to suitthe sample location.
End of Line filters for Dry areas,
In-line filter (where an End of line filter is not practical)
There are two types of End of Line Filters. See section 5.4 & 5.5
A fibre element type where the filter element has to be replaced
periodically.
A stainless steel type where the filter element can be cleaned.
Both of the above filters are supplied with dual compression fittings tosuit pipe sizes 6 or 8mm O/D, in either brass or stainless steel. It is
advisable to protect the Filter when installed in a location where damage
may occur.
The In-Line Filteris a stainless steel unit that is suitable for attaching to
a stop-valve when fitted in a stop valve box or can be fitted to the line in a
serviceable location. It is advisable to remove the In-Line Filter complete
for cleaning, as splitting the filter in situ may damage the threads.
-
8/11/2019 TQ Technical Manual
57/99
TQ Environmental Plc
Filename: Technical Manual Page 9 of 51
2.2. Sensors
There are two type of sensors, the infrared type, for flammable gases, or the
electro-chemical type for Toxic and Oxygen gases. When a system comprises
of more than one sensor, they are connected in series in the sample line which
then is vented out from the enclosure through a flame arrestor.
2.2.1 Infrared Sensor (GD 129NI)
The operation of the infrared sensor within the TQ4400 Pump room
sampling system is to measure the absorption of infra red light by a target
hydrocarbon gas and converting that absorption to an electronic signal.
The infrared sensor is now packaged as a GD-129 stand-alone unit within
the TQ4400 and provides a 4-20mA signal for their respective target gas
concentrations.
Part Number for the GD129 for 0-100%LEL METHANE is 340-020
2.2.2 Electro-chemical Type.
These sensors typically monitor for Oxygen and Toxic gases and because
of their properties have a life span of approximately 1-2 years depending
on conditions.
The Electrochemical types, as with the Infrared sensor, provide a 4-20mA
signal for their respective gas concentrations.
Part Number for the TQ123 for 0-25%VOL OXYGEN is 123-531
Part Number for the TQ123 for 0-50PPM H2S is 123-251
-
8/11/2019 TQ Technical Manual
58/99
Page 10 of 51 Filename: Technical Manual
2.3 Control and Display Electronics.
The settings for the TQ4400 Pump room sampling system is divided into two
Parts, a) the TQ4400 display and b) the TQ 4400 Set Up/ Control
The TQ4400 Set up/ Control monitors the signal the signal from each gas
detector in the sample system and controls the solenoids sequentially.
The TQ4400 Set up/ Control analyses the gas and transmits back to the TQ4400
display card concentrations and any alarm associated with the recent analysis of
the gas sample
TQ 4400
CONTROLCARD
INFRA RED
FLAMMABLE
ELECTROCHEM
O2
ELECTRO
CHEM
H2S
FLOW FAILPUMP
SOLENOID 1
SOLENOID 2
SOLENOID 3
4-20mA
SIGNAL
Vent
SOLENOID 4Sample line 4
Sample line 1
Sample line 2
Sample line 3
TQ 4400DISPLAY
CARD
Fig. 1 Block diagram of System
2.3.1 The TQ4400 DisplayUnit
The 4400 Unit houses the display PCB board and the control PCB. The
display PCB board accepts details of the sensor status from the set up /
control, and displays the current system status.
During normal operation the Unit will show the gas type, gas
concentration and fault alarm status. Refer to section 3 for operation.
The Front Panel Display includes: (fig 2 Page 8)
Liquid Crystal Display.
4 Push buttons (Ack, Reset, Hold and Skip function).
3 LEDs (Low Alarm, High Alarm and System Healthy)
-
8/11/2019 TQ Technical Manual
59/99
TQ Environmental Plc
Filename: Technical Manual Page 11 of 51
TQ4400 PUMP ROOM UNIT
ALARM
1
ALARM
2
SYSTEM
HEALTHY
ACK RESET HOLD SKIP
LCD DISPLAY
ALARM LED's
PUSH BUTTONS
Fig 2 Front Display of TQ4400
2.3.2 The TQ4400 Control Unit
The 4400 Control unit or PCB Unit is position within the TQ 4400
enclosure and performs the logic behind the TQ4400
During normal operation this Unit will show the location with A-D
conversion done. Refer to section 4 for settings.
The Panel Display includes:
Liquid Crystal Display.
4 Push buttons (Select, Up, Down and Skip function).
The user can alter any of the settings from the panel display.
-
8/11/2019 TQ Technical Manual
60/99
Page 12 of 51 Filename: Technical Manual
3 8 0
3 2
2
3 8 0
Rig
htH
andO
pen
ing
Doo
r
10
8.3
4 1 0
570
580
POWER
SUPPLYCHANGE
-OVER
UNIT
FORTANKSCANGAS
SAMPLINGSYSTEM
4Holes
x10
.0mm
MAIN
SUPPLY
STANDBYSU
PPLY
GASALARM
RESET
TQENVIRONMENT
ALPLC
F l a
n s h a w
W a y
, W
a k e f
i e l d
, W Y
o r k s
E n g
l a n
d ,
W F 2 9 L P
T e
l : + 4 4 1 9 2 4 3 8 0 7 0 0
F a x :
+ 4 4 1 9 2 4 3 6 1 7 0 0
E m a i
l : s a
l e s @
t q p
l c . c
o m
w e b s i
t e : h
t t p : /
/ w w w
. t q p l c . c o m
NO
TES
:
1)P
rote
ctio
nR
atin
go
fca
bin
ent
isIP65
Fig 3 Power Supply Change-over Unit
-
8/11/2019 TQ Technical Manual
61/99
TQ Environmental Plc
Filename: Technical Manual Page 13 of 51
2.4 Power Supply Change Over Unit
Refer to Fig 3, Page 9.
This Unit is connected to the Ships Main and Emergency Power Supplies,
to provide an automatic changeover for the supply to the Analyser Unit in the
event of a Mains Supply failure.
The unit is either a 110-120 or 220-240V (not both) a.c., 50-60 Hz input, and
will automatically change back to Main when the main supply is restored.
Incorporated within the Power Supply Change-Over Unit is a TQ126F
controller, which monitors the TQ4400Analysing Units Leak Detection gas
detector. The TQ126Fwill disconnect the power supply to the Analyser Unit if
the sensor detects a gas concentration of 30% LEL. The power supply to the
Analyser Unit will not be restored until the gas concentration has fallen below
30% LEL and the reset button on the front of the Power Supply Change-Over
Unit has been pressed.
Front Panel indications are provided for:
Mains Supply On
Emergency Supply On
Internal Gas Alarm
2.5 Outputs.
The TQ4400standard outputs are in the form of:
Two sets of Volt Free Change-over relay contacts for Common
Concentration Alarm Low.
One sets of Volt Free Change-over relay contacts for Common
Concentration Alarm High.
One set of Volt Free Change-over relay contacts for System Fault Alarm.
Two 24VDC Output for Common Concentration Alarm High. (typically
rated for beacon and sounder connection
-
8/11/2019 TQ Technical Manual
62/99
Page 14 of 51 Filename: Technical Manual
2.6 Technical Specification
Power 110/240V 50/60Hz @ 4 Amps non
inductive
Internal d.c. power supplies 1 x 5V DC (System Electronics)
1 x 24V DC (Sensors / Solenoids)(factory fitted dependent on sensor
ratings and overall system requirement)
Max no. of locations for sequential
monitoring per Max no. of Sensor
8 Locations for 3 Sensors
Sensor types 4-20mA current sources (2 or 3 wire)
Pump Capacity 11 Litres / Minute (open ended)
Gas Concentration Alarm Outputs Standard: - 2 x Common Low / 1 x
Common High Volt Free Contacts, @
5Amps. Resistive.
Custom: - Up to 1 Individual Volt Free
Contact per Sample Location Gas Alarm,
5A.
Sample Lines Seamless Stainless Steel
316(Preferred)/.Copper
OD 6mm - 8mm, ID 4mm - 6mm.
Max length 300Metre @ 4.0mm I/D
Fault Alarm Outputs 1 x System Fault Volt Free Contact
Data communications RS 485 configurable for use with Printer
Additional Outputs
Operational temperature and humidity
range
0oC-40oC 0-90%RH non-condensing.
-
8/11/2019 TQ Technical Manual
63/99
TQ Environmental Plc
Filename: Technical Manual Page 15 of 51
3. OPERATION
This section explains in detail the TQ4400 system operation and typical alarm
conditions.
3.1 System Start-up
When power is applied to the system, the display will indicate System Set-up
mode, as below
SYSTEM SETUP
PLEASE WAIT
The system will stay in this mode for approximately 150 seconds.
3.2 Normal Operation
After the start-up delay the system will enter the normal operating mode.
CHAN 1
METHANE 00015%LEL
The top line of the display shows the channel location and the bottom line of
the display will show the gas sensor name, concentration of the gas, and the
units of the gas being analysed. The system will sequentially sample all of the
channel locations, displaying the appropriate data on the LCD.
-
8/11/2019 TQ Technical Manual
64/99
Page 16 of 51 Filename: Technical Manual
3.3 Panel Controls
ACK- Acknowledge alarm. This button allows the user to accept the gas
alarm, mute buzzer and to visualise further sampling. See section 3.4.2
(Except fault & flow fail)
RESET- Reset alarm. This button allows the user to reset the gas alarm, mutebuzzer and to continue sampling; it will reset any cleared faults also. See
section 3.4
HOLD-Hold Channel. See Section 3.3.2 below
SKIP-Skip Channel. See Section 3.3.2 below
At any time during the normal operating mode, the user has the option to
GOTO, Hold or Skip a channel. These functions are invoked by pressing
down the relevant push button, and are discussed further below:
3.3.1 GOTO Channel
The user may press down and hold theRESETandHOLDbutton until thedisplay reads GOTO, the user must then release the RESETand HOLD
button. You can then select which sample location to GOTO by using
ACK to go up and RESET to go down through the sample locations.
PressingHoldselects the desired channel.
Once the unit is sampling from the desired location you can then either
HOLD, SKIP or Reverse Purge the location.
3.3.2 Hold Channel
The user may press down and hold the HOLD button until the display
readsHOLD CHANNEL, the user must then release theHOLDbutton.
CHAN 1
HOLD CHANNEL
This will invoke the Hold Channel function. The current Channel location
will be continuously sampled for a maximum period of 20 minutes after
which time the system will revert to sequential sampling. At any time the
user may release the channel and enable the system to revert back to
sequential sampling.
This is achieved by pressing down and holding theHOLDbutton until the
display readsRELEASE CHANNEL, the user must then release theHOLD
button.
-
8/11/2019 TQ Technical Manual
65/99
TQ Environmental Plc
Filename: Technical Manual Page 17 of 51
CHAN 1
RELEASE CHANNEL
3.3.3 Skip Channel
The user may press down and hold the SKIPbutton until the display reads
SKIP MODE, the user must then release the SKIPbutton.
CHAN 1
SKIP MODE
This will invoke the Skip Channel function. The current channel location
will be skipped when the system is sequentially sampling the channel
locations. When the system returns to the skipped channel, the LCD will
display SKIP MODEfor 5 seconds and then proceed to the next sequential
channel. When the LCD displays SKIP MODE the user may revoke the
skip command by pressing down and holding the SKIP button until the
display reads NORMAL MODE, the user must then release the SKIP
button.
CHAN 1
NORMAL MODE
3.3.4 Manual Global Reverse Purge.
The user may press down and hold theACKandRESETbuttons until the
display reads GLOBAL REVERSE PURGE followed by REVERSE
PURGE. This initiates a global reverse purge where air is blown down
every sample line for a set period of time. The purge duration is factory
set and a Button box is required to be interfaced to the controller BTC
board to change the value.
After the system has finished purging it will revert back to sampling.
-
8/11/2019 TQ Technical Manual
66/99
-
8/11/2019 TQ Technical Manual
67/99
TQ Environmental Plc
Filename: Technical Manual Page 19 of 51
FLOW FAIL
To clear the Fault condition press clear blockage or SKIP the channel,
then hold the RESETbutton until the display reads RESET ALARM. At
the same time, the System Healthy led will illuminate and the Fault relay
will be de-activated. The alarm will not clear until the system has flow
again, it may require re-booting to allow user to SKIP the problem
channel.
RESET ALARMS
3.4.1.3 Communications Failure
A Comms Failure will initiate when communications are interrupted for
more than 2 minutes between the Display BTC PCB and the Control BTC
PCB.
COMMS FAILURE
This cannot be reset by theRESETbutton; the panel has to be opened and
powered down and back up again. However it is preferred to do this from
the power supply changeover unit.
3.4.2 Concentration Alarms
There are two alarms on the system, a low level alarm, ALARM 1, and a
high level alarm,ALARM 2. When the gas concentration exceeds the set
levels, the appropriate alarms will be activated, and operate the
appropriate LEDs and alarm relays. The LCD will display the first
channel to be in alarm, together with the sensor gas type and relevant
alarm condition. The system will continue to sample the channels
sequentially.
-
8/11/2019 TQ Technical Manual
68/99
Page 20 of 51 Filename: Technical Manual
CHAN 1
METHANE LOW ALARM
CHAN 1
METHANE HI ALARM
The user may reset the alarmed channel by pressing theRESETbutton. At
which point the alarms for that channel will be cleared. If there are any
pending alarms then the LCD will display the next alarmed channelinformation. The user must again press the RESET button to clear that
particular alarm. When no more alarms are present, the system will
display the concentration as normal.
The user may press the Ackbutton to clear the audible buzzer (if fitted).
This will acknowledge the alarmed channel and display ALARM
ACKNOWLEDGEDon the LCD.
CHAN 1
ACKNOWLEDGED ALARM
If there is a pending alarm the LCD will display the pending alarm
information. When all alarmed channels have been acknowledged, the
system will display the gas concentration sequentially, but will also
display ALARM ACKNOWLEDGED on the LCD for 5 seconds. To de-
activate the alarm relays the user must use the RESET function as
described above.
RESET ALARMS
Each alarm is then reset on a channel per channel basis, i.e. if a particular
channel is in alarm then another channel comes into alarm, then the first
channel requires one reset and a second reset clears the next set of alarmsin the second channel.
-
8/11/2019 TQ Technical Manual
69/99
TQ Environmental Plc
Filename: Technical Manual Page 21 of 51
4. SYSTEM SETTINGS
In the TQ4400 Enclosure there is a Panel marked TQ4400 Set Up/Test Panel
or Box with four push buttons and a LCD display (see below). During
Normal operation this display will show the channel name followed by A-D
conversion Done
SELECT UP DOWN MENU
TQ4400 SET UP PANEL
Fig 4 Typical TQ4400 Set Up Panel.
If any parameter requires changing within the system, and if the sensorrequires a calibration check, then the Technical and Parameters Menu will
required to be accessed from this Panel.
Parameters Include: - Location Names, Sensor Names, Dwell Times, Gas
Units, Gas Range, and Alarm Levels.
Technical Parts Include: - Calibration, No. of Sample Points, No. of channels,
reverse purge frequency, reverse purge times and another Skip Channel
function.
A MENU MAP IS ENCLOSED ON PAGE 35, 36 & 37 which may help when
using the menus.
4.1 Set up Controls
The set-up controls consist of four push buttons SELECT, UP, DOWN and
MENUwhich interfaces with the TQ4400 control circuit board which is fitted
behind the Buttons and LCD.
4.2 Power Up
When the system is first powered up the title screen will be displayed showing
the software name and version number.
-
8/11/2019 TQ Technical Manual
70/99
Page 22 of 51 Filename: Technical Manual
TQ ENVIRONMENTAL
CONTROL Ver. 1.5
4.3 Set Up-Menu Access
After the title screen is displayed, the display will then read TRANSFERRING
SYSTEMand dots appear on the bottom line of the display (One dot for each
sample point being monitored).
TRANSFERING SYSTEM
....
To access the menu system, theMENUbutton must be pressed and held down
as the dots appear on the bottom line.
TRANSFERING SYSTEM
. . . . . . . . .
When the last dot has appeared on the bottom line of the display then the
display will showMENU- PARAMETERS and therefore successful entry to the
menu structure.
MENU
PARAMETERS
The menu may now be navigated by pressing the UP and DOWN buttons,
which will enable the user to scroll through the menu items. The menu items
-
8/11/2019 TQ Technical Manual
71/99
-
8/11/2019 TQ Technical Manual
72/99
Page 24 of 51 Filename: Technical Manual
4.4 Parameters
System parameters may be set and edited by entering the PARAMETERS
menu option. Each parameter is set on a Location by Location Basis, therefore
what ever is set for channel 1 does not apply to channel 2, with exception to
the GLOBAL SENSOR settings (see section 4.4.5). The GLOBAL SENSORMenu setting will apply to all channels.
Once entered, the display will prompt the user to select a desired channel for
editing. The user must press the UP and DOWN buttons to display the
required channel location and then press the SELECT button to accept that
channel location.
PARAMETERS MENU
CHANNEL 1
When a channel has been selected, the user may cycle through the Parameters
Sub Menu using the UP and DOWN buttons and select the required
Parameters Sub Menu Item using the SELECTbutton.
PARAMETERS MENU
SET LOCATION
When performing a task within the parameters menu the unit will always
return to the following screen: -
PARAMETERS MENU
CHANNEL 1
To exit completely, press SELECT, thenDOWNonce to PARAMETERS
MENU-EXIT MENU and press SELECT.
Detailed descriptions of the Parameters Sub Menu items now follow:
-
8/11/2019 TQ Technical Manual
73/99
TQ Environmental Plc
Filename: Technical Manual Page 25 of 51
4.4.1 Parameters Sub Menu - Set Location
The channel locations are set by default to CHANNEL 1, CHANNEL
2, etc. This option will allow the user to change the name of the channel
locations to a more meaningful description up to 20 characters in length,
including the character.
SET LOCATION
CH_
The user must use the UP and DOWN buttons to cycle through the
alphanumeric characters, pressing the SELECT button when the display
shows the required character. To leave spaces, select the character and press the SELECT button. When the SELECT button has
been pressed the next digit on the right will be displayed.
It is important to press SELECTat the end to leave a space otherwise it
may leave the last character off the end of the location.
*-NOTE - If there is no intension of changing the location name then the
SELECT button must be pressed until the cursor has reached the right
hand side of the display followed byMENU.*
To accept the channel location description the user must press the MENUbutton.
4.4.2. Parameters Sub Menu - Set Gas Type
PARAMETERS MENU
SET GAS TYPE
This option is used to set a particular gas to a particular channel location.
The current channel location is the one entered at the beginning of the
parameters sub menu. To set a particular gas the user must press the UP
andDOWNbuttons to cycle through the available gasses. This option will
allow the user to change the name of the sensor gas type to a more
meaningful description up to 10 characters in length, including the
character.
-
8/11/2019 TQ Technical Manual
74/99
Page 26 of 51 Filename: Technical Manual
SET GAS TYPE
METH_
The user must use the UP and DOWN buttons to cycle through the
alphanumeric characters, pressing the SELECT button when the display
shows the required character. To leave spaces, select the
character and press the SELECT button. When the SELECT button has
been pressed the next digit on the right will be displayed.
It is important to press SELECTat the end to leave a space otherwise it
may leave the last character off the end of the location.
*-NOTE - If there is no intension of changing the Gas type then the
SELECT button must be pressed until the cursor has reached the righthand side of the display followed byMENU.*
To accept the channel location description the user must press the MENU
button.
4.4.3. Parameters Sub Menu - Set Dwell Time
This option allows the user to specify the time in seconds that the system
will remain in a particular channel location before sequentially
incrementing to the next channel location. The dwell time is variable in therange from 0 to 300 seconds.
PARAMETERS MENU
SET DWELL TIME
To change the dwell time for that particular channel the user must press theUP and DOWN buttons and the SELECT button when the desired dwell
time is displayed.
SET DWELL TIME
00040
-
8/11/2019 TQ Technical Manual
75/99
TQ Environmental Plc
Filename: Technical Manual Page 27 of 51
4.4.4 Parameters Sub Menu - Select Local Sensor
This option will allow the user to set sensor parameters for a specified
sensor on a specified channel.
PARAMETERS MENU
SELECT LOCAL SENSOR
To select a particular sensor the user must press the UPandDOWNbuttons
to cycle through the available sensors and SELECTbutton when the desired
sensor is displayed.
SENSOR MENU
FLAMMABLE
4.4.5. Parameters Sub Menu - Select Global Sensor
PARAMETERS MENU
SELECT GLOBAL SENSOR
This option will allow the user to set sensor parameters for a specified
sensor on all channels. The sensor parameters are the same as the Select
Local Sensor parameters and are described as follows:
To select a particular sensor the user must press the UPandDOWNbuttons
to cycle through the available sensors and SELECTbutton when the desired
sensor is displayed.
SENSOR MENU
FLAMMABLE
-
8/11/2019 TQ Technical Manual
76/99
-
8/11/2019 TQ Technical Manual
77/99
TQ Environmental Plc
Filename: Technical Manual Page 29 of 51
SET HIGH ALARM
00040
When the desired alarm point level is displayed, the user must press the
SELECTbutton to accept the displayed value.
Set Alarm Type
This option allows the user to specify a rising alarm + or a falling alarm -.
HIGH ALARM MENU
SET ALARM TYPE
SET ALARM TYPE
+_
Press UPorDOWNto toggle between a rising alarm + or a falling alarm -.
Then press SELECTon required alarm type.
4.5.1.2 Set Alarms - Select Low Alarm
This option is the same as the Set High Alarm above section 4.5.1.1, but
refers to the low alarm point.
SET ALARMS
SELECT LOW ALARM
-
8/11/2019 TQ Technical Manual
78/99
Page 30 of 51 Filename: Technical Manual
4.5.1.3 Set Alarms Set Latch Status
This option allows any gas concentration alarm to be automatically
cancelled as soon as the concentration of gas has returned to a level not
beyond it alarm set point.
SET ALARMS
SELECT LATCH STATUS
Press SELECTto enter.
LOW HIGH
UNLATCHED LATCHED
Press UP / DOWN to choose the combination of LATCH requirement for
the High and Low Alarms. When the desired latch status is displayed, the
user must press the SELECTbutton to accept the displayed value.
4.5.2 Sensor Menu- Set Units
This option will allow the user to select the appropriate units corresponding
to the gas type. The available units are as follows: PPM, %LEL, %VOL,
and MGM. Press UP / DOWN to choose which units are required followed
by the SELECTButton.
SET UNITS
%LEL
4.5.3 Sensor Menu - Set Range
This option allows the user to set the desired gas sensor range. The sensor
range is determined by the particular sensor installed. i.e H2S would be 50
for a 0-50 PPM sensor, 4mA = 0PPM & 20mA = 50PPM
*-NOTE This figure does not correspond to the gas calibration levelrequired - *
-
8/11/2019 TQ Technical Manual
79/99
-
8/11/2019 TQ Technical Manual
80/99
Page 32 of 51 Filename: Technical Manual
4.6 Technician Sub Menu
4.6.1 Technician Sub Menu - Set No. Of Channels
This option allows the user to select the desired number of channels.
TECHNICIAN MENU
SET NO. OF CHANNELS
SET NO. OF CHANNELS
12
This is set by the upor downbuttons. When the desired number of channels
is displayed, the user must press the SELECTbutton to accept the displayed
value.
4.6.2 Technician Sub Menu - Set No. Of Sensors
This option allows the user to select the desired number of sensors.
TECHNICIAN MENU
SET NO. OF SENSORS
SET NO. OF SENSORS
01
This is set by the upor downbuttons. When the desired number of sensors
is displayed, the user must press the SELECTbutton to accept the displayed
value.
-
8/11/2019 TQ Technical Manual
81/99
TQ Environmental Plc
Filename: Technical Manual Page 33 of 51
4.6.3 Technician Sub Menu - Skip Channel Number
This performs the same function as Section 3.3.3. This option allows the
user to skip a channel. When the SELECT button is pressed, the display
will show SKIP MODE or NORMAL MODE to indicate to the user the
channel status.
TECHNICIAN MENU
SKIP CHANNEL
Press SELECTto enter.
SKIP ZONE NUMBER
CHANNEL 1
Press UP / DOWN to choose the channel required to be skipped. When the
desired channel is displayed, the user must press the SELECTbutton and
SKIP MODE-CHANNEL1 will flash up on display before returning to
TECHNICAL MENU-SET No. OF CHANNELS (SECTION 4.6.1)
To un-skip the channel, repeat as above but NORMAL MODE-
CHANNEL1 will flash up on display before returning to TECHNICAL
MENU-SET No. OF CHANNELS.
4.6.4 Technician Sub Menu - Set Purge Time
**Please note this option is not available on the TQ4400 Pump Room
system as there is no hardware to drive this function. Please keep the below
setting at 00000.**
This option allows the user to set a time period for the purge of each sample
line.
TECHNICIAN MENU
SET PURGE TIME
Press SELECTto enter.
-
8/11/2019 TQ Technical Manual
82/99
Page 34 of 51 Filename: Technical Manual
SET PURGE TIME
00060
This is set by the upor downbuttons. When the desired purge time is
displayed, the user must press the SELECTbutton to accept the displayed
value.
4.6.5 Technician Sub Menu - Set Purge Cycle
This option operates in conjunction with the Set Purge Time option. Set
Purge Cycle is the number of complete cycles of all sample lines before a
purge is processed. Purge may be turned off by setting Purge Cycle to 0.
**Please note this option is not available on the TQ4400 Pump Room
system as there is no hardware to drive this function. Please keep the below
setting at 00000.**
SET PURGE CYCLE
00
This is set by the upor downbuttons. When the desired number of cycles is
displayed, the user must press the SELECTbutton to accept the displayed
value.
4.6.6 Technician Sub Menu - Calibrate Sensor
From the technician sub menu the user should use the up and down keys
until the CALIBRATE SENSOR option is displayed. The user should then
use the SELECTbutton to enter calibration mode.
TECHNICIAN MENU
CALIBRATE SENSOR
This option will allow the user to calibrate a particular sensor. The user is
prompted to select a sensor. Use the up and down keys until the sensor to
be calibrated is displayed then pressSELECTbutton to calibrate the sensor.
-
8/11/2019 TQ Technical Manual
83/99
TQ Environmental Plc
Filename: Technical Manual Page 35 of 51
* NOTE The system does not zero the sensor, it assumes sensor zero to
be 4mA and there is not adjustment in this Menu. If a sensor is not 4mA
with Zero gas then the sensor would be assumed faulty.- *
SELECT SENSOR
FLAMMABLE
With the correct sensor selected the 1stsample solenoid will open and user
should apply calibration gas to the sensor via the calibration port or 3 way
valve or direct into the sensor head. (Oxygen Sensors usually require a
normal clean sample and dont require the next 3 steps)
i) Apply gas to the calibration port or to the port on the provided 3 way
valve.
ii) Turn on the gas bottle. Gas should be regulated to between 1 and 2 LPM.
iii)Turn the 3 way Valve handle 180o.
The gas concentration on the LCD will start to change after a few seconds.
If the concentration does not move then the sensor may need replacement.
Test electrically by placing voltmeter positive probe on clear (GD129) or
yellow (TQ122) wire from sensor and negative probe on Zero volts any
black wire. 0.88-0.91VDC will be a zero reading for the sensor and this willrise up to 4.8volts for the full range of the sensor, typically with respect to
4-20mA.
When gas concentration reading stops changing e.g. when the gas
concentration reading has settled, accept the reading by pressing the
SELECTbutton.
* NOTE When calibrating oxygen at 21% and a normal sample is used
for calibration please wait at least 60 seconds, as the sensor will usually
initially show over 25% and will take time to adjust for pressure differences
when the 1stsample solenoid opens.
SELECT TO ACCEPT
00047
When SELECT VALUE is displayed the user should use the UP / DOWNkeys to adjust the output reading displayed when the current gas
-
8/11/2019 TQ Technical Manual
84/99
Page 36 of 51 Filename: Technical Manual
concentration is present at the sensor and press the SELECT button to
accept the value. These values will then be scaled and stored in the
NVRAM for future reference.
SELECT VALUE
00050
* - NOTE - If the user enters the Calibrate Sensor Menu again for the same
sensor then the system will always display its original default calibration
setting, not the new value recently adjusted. - *
H2S sensors can take a very long time to return to zero, this is due to the
gas sticking to the lining of the system pipe work. If system shows 1 2
PPM please allow a few days for it to fully return to zero.
4.6.7 Technician Sub Menu - Clear Calibration
This option allows the user to clear all calibration data from the NVRAM
and in doing so sets all sensors to default calibration.
Press SELECTto clear calibration.
TECHNICIAN MENU
CLEAR CALIBRATION
-
8/11/2019 TQ Technical Manual
85/99
TQ Environmental Plc
Filename: Technical Manual Page 37 of 51
4.7 Sensor Menu
T Q
E n v
i r o n m e
n t a
l
C O
NT
R O L R
e v
. 1
. 5
T R A
N F E R I N G
S Y
S T E M
. . . .
M E N
U
P A R
A M E T E R S
M E N U
T E C H N
I C A L M O D
E
M E N U
E X I T M E N U
MENU
SELECT
DOW
N
UP
DOW
N
UP
SELE
CT
SELECT
TOREB
OOT
SY
STEM
EIT
HER
POWER
DOW
N
TH
ENUPA
GA
INAT
MA
INBRE
AKER
OR
PR
ESS
PU
SHHA
RDRE
SET
BU
TT
ONONCAR
DAS
SH
OWN
PRE
SSANDHO
LDMENU
BU
TTONONT
HISSCRE
EN
SEE
PAGE
36
SEE
PAG
E35
-
8/11/2019 TQ Technical Manual
86/99
-
8/11/2019 TQ Technical Manual
87/99
TQ Environmental Plc
Filename: Technical Manual Page 39 of 51
MAINMEN
U
TECHNICIANMODE
TECHNICIA
NM
ENU
SETNOOFCH
ANNELS
TEC
HNICIAN
MEN
U
SETN
OOFS
ENSO
RS
SETNOOF
CHANNELS
23
SET
NOOFSENS
ORS
04
TECHNICIAN
MENU
SKIPCHANN
EL
SKIPCHAN
NEL
FPTANK
FPTANK
SKIPMODE
FP
TANK
NORMALMO
DE
TE
CHNICIAN
ME
NU
SET
PURGETIM
E
SE
TPURGETI M
E
00
020
TECHN
ICIAN
MENU
SETPURG
EC
YCLE
SETPU
RGECYCLE
00010
TEC
HNICIAN
ME
NU
CALIB
RATES
ENSO
R
SEL
ECTSENSOR
FLAM
MABLE
SEL
ECTTOACC
EPT
00028
DA
TAACCEPT
ED
00028
TECHNIC
IAN
MENU
CLEARCA
LIB
RATION
TE
CHNICIAN
MENU
EX
ITMENU
SELECTS
ENSOR
H2S
SELECTT
OACCEPT
00015
SEL
ECTSENSOR
OX
YGEN
SEL
ECTTOACC
EPT
00
027
S E L
E C T
D O W
N
U P
S E L
E C T
D O W N
U P
D O W
N
U P
D O W N
U P
D O
W N
U P
S E L E C T
S E L
E C T
S E L E C T
S E L E C T
S E L E C T
S E
L E C T
S E L E C T
S E L
E C T
S E L
E C T
S E L E C T
SEL
ECTVALU
E
00050
P R E S S
U P / D O W N
T O C O
R R E C T
C O N C E N
T R A T I O N
T H E N S E L
E C T
I N S E
R T S P A N G A
S &
W A
I T 3 0 S E C O N
D S
O R S O
F O R R E A D I N G
T O S
T A B A L I S E
DATAA
CCEPTED
00023
S EL
E C T
SELECTV
ALU
E
00025
P R E S S U P / D O
W N
T O C O R R E C T
C O
N C E N T R A T
I O N
TH
E N S E L E C T
I N S E R T
S P A N G A S &
W A I T 6 0
S E C O N D S
O R S O F O
R R E A D I N G
T O S T A B A
L I S E
* I M
P O R T A N T *
W A I T
3 0 S E C O N D
S
O R S O
F O R R E