tq technical manual

Upload: abuzer1981

Post on 03-Jun-2018

611 views

Category:

Documents


45 download

TRANSCRIPT

  • 8/11/2019 TQ Technical Manual

    1/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    TECHNICAL MANUAL

    2007 TQ Environmental Plc

    This manual must not be copied or reproduced in part without the express written permission of TQEnvironmental PLC. All information contained herein is subject to modification.

    TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP 44 (0) 1924 380700; FAX 44 (0) 1924 361700; E-Mail: [email protected]

    TQ ENVIRONMENTAL PLC BS EN ISO 9001

    Filename: 7748/TMIssue 0: 09-02-07Author: G Thompson.

    JOC INTERNATIONAL

    TQ4400 PUMP ROOM GAS SAMPLING SYSTEM

  • 8/11/2019 TQ Technical Manual

    2/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

  • 8/11/2019 TQ Technical Manual

    3/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    MODIFICATION RECORD

    CLIENT: JOC INTERNATIONAL

    CUSTOMER ORDER NO: SPO504/505/506

    VESSELS:

    SYSTEM: TQ4400 PUMP ROOM GAS

    SAMPLING SYSTEM

    DOCUMENT: TECHNICAL MANUAL

    VENDOR: TQ ENVIRONMENTAL PLC

    WORKS JOB NO: 7748

    ISSUE DESCRIPTION CHECKED DATE APP DATE

    1 Technical Manual( As Built )

    NDA 09-02-07 GT 09-02-07

  • 8/11/2019 TQ Technical Manual

    4/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

  • 8/11/2019 TQ Technical Manual

    5/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    CONTENTS

    SECTION DESCRIPTION

    1.0 Introduction.

    1.1 Information Specific to this Application.

    2.0 Drawings. *

    3.0 TQ4400 OPERATING MANUAL.

    * see section for sub-index

  • 8/11/2019 TQ Technical Manual

    6/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

  • 8/11/2019 TQ Technical Manual

    7/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    1.0 Introduction

    The Flammable Gas Detection System supplied to JOC INTERNATIONAL consists

    of a 3 point TQ 4400 Pump Room Gas Detection Systems for monitoring flammable,

    Toxic and oxygen levels in pump room areas. The Sampling Unit supplied has a

    separate control set up box responsible to alter key parameters such as calibration,

    dwell times, alarm settings and other, before any changes decided to be applied the

    operator must first have carefully understood it is operation.Special Caution is to be

    applied when handling the set-up box parameters and technician mode*. Alarm

    settings and other; before any changes decided to be applied the operator must again

    first have carefully understood it is operation. Otherwise it may prevent the unit from

    it is designed operation.

    *Please See Sections [3] within this Technical Manual, for more details.

    1.1 Information Specific to this Application.

    Sequential Sampling Locations = 3

    PUMP ROOM

    Sample Location Name Gas Types Monitored

    Line No. H2S Flammable Co O2

    1

    2

    3

    4

    5

    6

    7

    8

  • 8/11/2019 TQ Technical Manual

    8/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

  • 8/11/2019 TQ Technical Manual

    9/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    2.0 DRAWING LIST.

    DOCUMENT REVISION DATE TITLE

    TQ 4400 Tankscan

    7748A 1 31-07-06 Analysing Unit Sample Tube & Cable Entry Details

    7748 B 1 31-07-06 Electrical Schematic

    7748C 2 05-08-06 Pumproom Sampling system Enclosure Dimensions

    7748D 2 05-08-06 Termination Details

    7748E 1 31-07-06 TQ4400 PR Unit Internal Layout

    7748N 1 31-07-06 Power Supply Changeover Unit Enclosure Details

    7748P 1 31-07-06 Power Supply Changeover Unit Internal Layout

    7748U 1 31-07-06 TQ Interanal Gas Detector Overview

    7748V 2 05-08-06 Electrical Connection

    7748W 1 31-07-06 Shut off Valve with Weld Tube Detail & Vent line Weld Tube

    Detail

    7748Y 1 31-07-06 Weld Tube Dimensional Detail

    7748Z 1 31-07-06 End of Line Filter Drawing

    7748F 2 05-08-06 TQ4400 Pump Room Pneumatic Schematic

    7748G 2 05-08-06 Power Supply Wiring Diagram

    7748H 2 05-08-06 TQ4400 PR sensor flow fail Wiring diagram

    7748J 2 05-08-06 TQ4400 PR Solenoid Valve and Relay CCT Diagram

    7748K 2 05-08-06 TQ4400 Set up Display Wiring Diagram

    7748L 1 31-07-06 TQ4400 Front Panel Circuit Diagram

  • 8/11/2019 TQ Technical Manual

    10/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

  • 8/11/2019 TQ Technical Manual

    11/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    *

    PROJECTION

    SCALE

    N/A

    7748

    JOC

    INTERNATIONAL

    ANALYSING

    UNITSAMPLE

    TUBEANDCABL

    E

    ENTRYDETAILS

    Sample

    Linesx3

    Fla

    me

    Arre

    stors

    x

    4

    HAZARDOUSAREA

    SAFEAREA

    Brass

    Compression

    FittingsForConnection

    NOTES

    1)3=Num

    berofsamplepoints

    2)Ventlin

    eistobelettoatmospherew

    iththe

    outletar

    rangedinasafelocationawayfrom

    ignition

    sources.

    Theendoftheventline

    mustbe

    bentdownwards

    topreventwater

    ingress.

    3)Shutoffvalvesandpenetrationssupplied

    4)8mmODCoppersamplelinesrecommended,

    Fittingo

    nflamearrestorsmaybechangedto

    suitothersizes.

    AnalysingUnit

    SampleLinesConn

    ectDirectlyontoFlame

    ArrestorsViaBrassCompressionFittings

    (Flamearrestorsare1/8"BSP/Pinternal

    thread

    forconnectionto1/8"BSP-P

    (ISO)Malefittings.)

    1/4"BSPPSt-St

    Shutoffvalve

    sx

    3

    (SuppliedasL

    ooseItems)

    SeeNote3

    CabinetGas

    InternalLeak

    Detector

    Penetra

    tionsx4

    (150mmWeldTubes)

    REARVIEW

    OF

    FIXINGBRACKET

    15

    29

    20

    54

    10

    SIDEVIEW

    OF

    FIXINGBRACKET

    20

    FIXINGDETAIL

    7748A1

    CablesEnterThrough

    BottomleftofCab

    inet

    VentFlameA

    rrestors

    (ConnectionV

    ia8mm

    BrassCompressionFitting)

    8mmVentLine

    (SeeNote2)

    TestPoint

    TQ4400

    PUMP

    ROOMSAMPLINGSYSTEM

    UserInterfaceDisp

    lay

    31-0

    7-0

    6

    *

    TQ4400CO

    NTROLUNIT

    ALARM

    1

    ALARM

    2

    SYSTEM

    HEALTHY

    UP

    DOWN

    SELECT

    MENU

    WATCHDOG

  • 8/11/2019 TQ Technical Manual

    12/99

  • 8/11/2019 TQ Technical Manual

    13/99

    7748B1

    7748

    JOC

    INTERNATIONAL

    31-0

    7-0

    6

    G.T

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    ELECTRICAL

    SCHEMATIC

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    PROJECTION

    SCALE

    N/A

    NOTES

    1)Cab

    leSpe

    cisaTQrecommendation.

    2)Cab

    inetG

    asAlarmV

    .F.C.

    isgeneratedfrom

    powersup

    plychangeoverunitand

    allowsfor

    remotemonitoringofleakswithinthe

    gassamplingdetection/controlunitifrequired.

    3)Provision

    isprovidedforremotemonitoringof

    mainsfail

    ,systemfault&Low/Highconcentrat

    ion

    alarms,ViaVo

    ltfreecontacts,ifrequired.

    GasDetection\ControlU

    nit

    PowerSupply

    ChangeoverUnit

    3Core1

    .5mmsqBlack

    ArmouredCabletoBS6883

    3Core

    1.5

    mmsqBlack

    ArmouredCablewithOveral

    l

    ScreentoBS6883

    SAFEAREA

    220Vac

    60Hz

    10A

    220Vac

    60Hz10A

    2Core1

    .5mmsq

    BlackArmoured

    CabletoBS6883

    3Core

    1.5

    mmsq

    BlackArmoured

    CabletoBS6883

    CabinetGasAlarm

    V.F.C.

    (SeeNote2

    )

    2Core1

    .5mmsq

    Black

    Armoured

    CabletoBS6883

    CabinetGasInternal

    LeakDetector

    STANDBY

    MAIN

    * *

    31-0

    7-0

    6

    31-0

    7-0

    6

    TQ4400CONTROLUNIT

    ALARM

    1

    ALARM

    2

    SYSTEM

    HEALTHY

    UP

    DOWN

    SELECT

    MENU

    WATCHDOG

  • 8/11/2019 TQ Technical Manual

    14/99

  • 8/11/2019 TQ Technical Manual

    15/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748C2

    ProjNo.

    Client.

    Drn.

    Date.

    12-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    PUMPROOMSAMPL

    ING

    SYSTEM

    ENCLOSUREDIMENS

    IONS

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    12-0

    7-0

    6

    * *

    12-0

    7-0

    6

    PROJECTION

    SCALE

    N/A

    JOC

    INTERNATIONAL

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSYSTEM

    NOTES:

    1)Pro

    tect

    ion

    Rat

    ingo

    fIP66

    2)Samp

    leline

    ODcan

    bechanged

    ifrequ

    ired

    LEFTHan

    d

    Open

    ing

    Door

    1

    2

    3

    VENT

    546

    MOUNTING

    BRACKET

    DETAIL

    R4

    .5

    R7

    .5

    1

    2

    3

    4

    5

    6

    7

    8

    SAMPLELINES

    (UPTO8)

    VENT

    CABLEENT

    RY

    (UPTO7M20GLANDS)

    FRONT

    FRONT

    400

    360

    263

    500

    67

    185

    TOPOF

    CABINE

    T

    BOTTOMOF

    CABINET

    162

    SAMPLES+VENT

    8MMDiaTu

    bing

    (NOTE2)

    TUBINGENTRY

    86

    605

    90

    15

    210

    91

    29

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    N.D.A

    1.

    Int.GasDetector

    Moved

  • 8/11/2019 TQ Technical Manual

    16/99

  • 8/11/2019 TQ Technical Manual

    17/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748D2

    ProjNo.

    Client.

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    TERMINATIONDETA

    IL

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    31-0

    7-0

    6

    PROJECTION

    SCALE

    N/A

    JOC

    INTERNATIONAL

    7748

    TQ4400PUMP

    ROOMSAMPLINGSYSTEM

    CommonAla

    rm2

    i.e30%LEL

    CH4

    19%VOLO2

    15PPMH2S

    24VDCO

    /P

    (BEACON

    )

    CommonAlarm2

    i.e30%LELCH4

    19%VOLO

    2

    15PPMH2

    S

    24VDCO/P

    (SOUND)

    220vac

    60Hz

    FromPOWER

    SUPPLYUNIT

    ISOLATOR

    "C"

    9

    101112

    1

    2

    3

    7

    8

    AL1

    AL2

    FAULT

    RL1-1

    VFC

    RL2

    RL3

    TBF

    -03

    9

    101112

    1

    2

    3

    7

    8

    RL3

    RL2

    5

    4

    7

    2

    6

    3

    8

    1

    RL1

    3 1 2 4

    F4

    F3

    F2

    F1

    2A

    Isolator

    N N

    3 N2 E

    1 L

    24V

    TBF-01

    TBF-02

    TB-01

    0V

    2

    1

    4

    3

    4

    3

    2

    1

    4

    3

    2

    1

    0V

    3 1 2 4

    F5F6F7

    5

    4

    7

    2

    6

    3

    8

    1

    54

    72

    63

    81

    6

    4

    5AL1

    RL1-2 6

    4

    5

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    NDA

    ExtraC

    ontactsAdded

    1.

  • 8/11/2019 TQ Technical Manual

    18/99

  • 8/11/2019 TQ Technical Manual

    19/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748E1

    ProjNo.

    Client.

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    31-0

    7-0

    6

    PROJECTION

    SCALE

    N/A

    JOC

    INTERNATIONAL

    7748

    TQ4400PUM

    P

    ROOMSAMPLINGSYSTEM

    PUMP

    C

    ONTROL

    BOARD

    ForTermination

    SeeDrg.

    7748D

    1

    F1

    NV1

    TBF

    -01

    SolenoidBankMounting

    SUPPRESSOR

    T R U N K I N G

    T R U N K I N G

    TBF

    -02

    RL 1

    RL 2

    RL 3

    TBF

    -03

    TB01

    LeftHand

    Moun

    tingPlate

    R

    ightHand

    Mo

    un

    tingPlate

    TBO2

    ISOLATOR

    FUSES

    FLOW

    FAIL

    O2

    H2S

    CH4

    TQ123-2

    51

    TQ123-5

    31

    TQ4400PR

    INTERNALLAYOUT

  • 8/11/2019 TQ Technical Manual

    20/99

  • 8/11/2019 TQ Technical Manual

    21/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    POWERSUPPLY

    CHANGE-O

    VERCONTROL

    UNITENCLOSUREDE

    TAIL

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    PROJECTION

    SCALE

    N/A

    380

    322

    380

    RightHandOpeningDoor

    10

    210

    410

    570

    580

    POWERSUPPLYCHANGE

    -OVERUNIT

    FORGASSAMPLINGSYSTEM

    4Holes

    x10.0mm

    220V

    60Hz

    ACStan

    dby

    Supply

    220V60Hz

    ACSupp

    ly

    toMain

    Panel

    Cabinet

    GasAlarm

    V.F.C

    (SeeNo

    te2)

    'U'

    'U'

    'V'

    'V'

    'V'

    220V

    60Hz

    ACMain

    Supply

    GasDetection/

    ControlUnit

    Internal

    Leak

    Detector

    'A'

    'A'

    'A'

    25

    80

    135

    190

    245

    300

    'A'

    65

    NOTES:

    1)Gland

    s:

    'U'To

    SuitCableOD11

    .5mm

    'V'To

    SuitCableOD11

    .9mm

    2)Onlyrequiredifusingcabinetgasremote

    monitoringfacility

    .

    DESIGNED&MANUFACTUREDBY:

    TQENVIRONMENTALPLC

    FlanshawWay,Wakefield,W

    Yorks

    England,WF29LP

    Tel:+441924380700

    Fax:+441924361700

    Email:[email protected]

    website:http://www.tqplc.com

    * *

    31-0

    7-0

    6

    31-0

    7-0

    6

    31-0

    7-0

    6

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    JOC

    INTERNATIONAL

    7748N1

    MAINSUPPLY

    STANDBYSUPPLY

    GASALARM

    STANDBYFAIL

    ALARMRESET

    ALARMMUTE

    LAMPTEST

  • 8/11/2019 TQ Technical Manual

    22/99

  • 8/11/2019 TQ Technical Manual

    23/99

    6

    K2

    F4-

    5

    10

    (SeeNote2)

    RESET

    MUTE

    TEST

    T

    BF-0

    1

    ISOLATOR'A'

    K1

    F1-

    3

    PSU1

    TB-0

    1

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    POWERSUPPLY

    CHANGE-O

    VERUN

    IT

    INTERNALLAYOU

    T

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    PROJECTION

    SCALE

    N/A

    4

    *

    E 14

    NOTES:

    1)ItemNumbersrefertopartslist

    SeeDoc.4826DC

    2)ShowsItemsMountedon

    EnclosureDoor.

    3)EMCSuppressor'slocatedunder

    railcontaining

    Isolator's

    31-0

    7-0

    6

    31-0

    7-0

    6

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    JOC

    INTERNATIONAL

    7748P1

    MAIN

    STA

    NDBY

    STA

    NDBY

    FAIL

    GASALARM

    7

    12

    RL1 5

    1

    2

    3

    8

    9

    RL2-

    3

    5

    13

    16

    17

    DT1-

    4

    FERRITE

    RING

    ISOLATOR'B'

    E

    EMC

    SURPRESSOR

    15

    9123

    TBF-0

    2

    123

    ISOLATOR'C'

    E

    EMC

    SURPRESSOR

    FerriteRing

    Buzzer

    *

    31-0

    7-0

    6

  • 8/11/2019 TQ Technical Manual

    24/99

  • 8/11/2019 TQ Technical Manual

    25/99

    TQENVIRONMENTAL

    PLC

    FlanshawWay

    Wakefield

    WestYorkshire

    WF29LP

    Proje

    ctTitle.

    Draw

    ingTitle.

    DwgNo.

    7748U1

    ProjNo.

    7748

    Client.

    Drn.

    Date.

    31

    -07

    -06

    G.T

    Chkd.

    Date.

    11

    -08

    -99

    D.A.W

    App.

    Date.

    12

    -08

    -99

    D.A.W

    Sig.

    Date.

    R

    evisions.

    No.

    Copyrig

    hto

    f

    CWeb:http//www.t

    qplc

    .com

    Email:sales@tqplc

    .com

    TQ4400PUMP

    RO

    OMSAMPLINGSYSTEM

    TQTANKSCAN

    INTERNALGAS

    D

    ETECTOROVERVIEW

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    Temp

    lateChanged

    1.

    31

    -07

    -06

    * *

    31

    -07

    -06

    PROJECTION

    SCALE

    N/A

    JOC

    INTERNATIONAL

    126F

    NC

    NO

    COM

    24V

    0V

    Bl

    Gr

    Red

    TQ122

    -212

    Flammab

    le0

    -100%

    LEL

    SENSORCONNECT

    ION

    +

    100uF

    25V

    Electro

    yltic

    Capa

    citor

    -

    Blk

    Red

    232

    128W

    hite

    1 2 3

    A21A

    185

    6 7

    TB

    -01

    27White

    LOCATEDONTO

    P

    OFSAMPLINGUN

    IT

    CABINET

    TOTBF

    -02OF

    POWER

    SUPPLYUNIT

    SEEDWG'S

    7748P&7748V

    3

    2

    1

    A2-

    A1+

    6

    7

    4 5

    2

    8

    1

    10

    TQ1220

    -100%LELCH4

    PTNO122

    -210

  • 8/11/2019 TQ Technical Manual

    26/99

  • 8/11/2019 TQ Technical Manual

    27/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748V2

    ProjNo.

    Client.

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ELECTRICAL

    CONNECTION

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    31-0

    7-0

    6

    PROJECTION

    SCALE

    N/A

    JOC

    INTERNATIONAL

    7748

    PUMPROOM

    SAMPLINGSYSTEM

    T

    BF-0

    2 4

    1

    23

    TBF-0

    1

    45

    6

    TB

    F-0

    3 789

    123

    TBF

    -01

    ISOLATOR

    'A'

    E

    ISOLATOR

    'B'

    E

    123

    TBF

    -02

    12

    3ISOLATOR

    'C'

    E

    E

    TBF-0

    1

    123

    NL

    N

    L

    NL

    NL

    TQ4400

    SAMPLINGSYSTE

    M

    7748D

    TQINTERNAL

    GASDE

    TECTOR

    (LOCA

    TEDON

    TOPOFSAMPLING

    CAB

    INET)

    DWG

    7748U

    POWERSUPPLYUNIT

    DWG7748P

    MAINS

    SUPPLY

    220VAC

    60HZ

    6A

    STANDBY

    SUPPLY

    220VAC

    60HZ

    6A

    MAINS

    FAIL

    VOLT

    FREE

    CONTACT

    GASAL1

    VOLTFRE

    E

    CONTACT

    10%LELCH4

    10PPMH2

    S

    19%VOLO

    2

    GASAL2

    VOLTFREE

    CONTACT

    30%LELCH4

    15PPMH2S

    18%VOLO2

    24V

    DC

    ALMO/P

    24VDC

    ALM

    O/P

    3Core1

    .5mmsq

    Black

    A

    rmouredCabletoBS6883

    3Core1

    .5m

    msq

    BlackArmoured

    CabletoBS

    6883

    2Core1.5mmsqBlackArmouredCabletoBS6883

    IFREQUIRED

    IFREQUIRED

    2Core1.5mmsqBlackArmouredCabletoBS6883

    IFREQUIRE

    DIFREQUIRED

    IFREQUIR

    EDIFREQUIRED

    101112

    SYSTEM

    FAULT

    VOLT

    FREE

    CONTACT

    IFREQUIRED

    123

    GASAL1

    VOLTFREE

    CONTACT

    10%LELCH4

    10PPMH2S

    19%VOLO2

    IFREQUIRED

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    N.D.A

    1.

    Alarm

    C

    ontactaddedtoTBF-0

    3

  • 8/11/2019 TQ Technical Manual

    28/99

  • 8/11/2019 TQ Technical Manual

    29/99

    7748W1

    JOC

    INTERNATIONAL

    TQ4400P

    UMP

    ROOMSAMPLINGSYS

    TEM

    7748

    31-0

    7-0

    6

    31-0

    7-0

    6

    *

    SHUTOFFVALVEW

    ITH

    WELDTUBEDETAI

    L&

    VENTLINEWELDTUBE

    DETAIL

    N/A

    SCALE

    PROJECTION

    DATE

    CLIENT

    SERVICE

    DEVELOPMENT

    PRODUCTION

    ISSUECONTROL

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    Web:

    http

    //www

    .tqp

    lc.c

    om

    C

    Copyrightof

    No.

    Revisions.

    Date.

    Sig.

    Date.

    App.

    Date.

    Chkd.

    G.T

    Date.

    Drn.

    Client.

    ProjNo.

    DwgNo.

    DrawingTitle.

    ProjectTitle.

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    TQENVIRONMENTAL

    PLC

    ITEM

    NO.

    DESCRIPTION

    PARTNO

    .

    QTY

    1 2 3

    1/4"ST-S

    TBallValve

    1/4"BSPP-

    1/4"

    BSPPParra

    llelNipple(Brass)

    1 1

    4 5

    1/4"BondedWasher

    1/4"BSPP-8mm

    ODCompressionFitting(Brass)

    4 2

    BULKHEAD BULKHEAD

    5

    4

    2

    3

    1

    5

    4

    4

    4

    50

    615-0

    08

    611-0

    23

    689-

    473

    610-1

    01

    105

    ThreadedWeld

    Tube(150mm)

    615-0

    07

    1

    N

    OTES

    1

    )SeeDrg.7

    748Yforweldtubedetails

    .

    150

    100

    1

    5

    4

    4

    5

    DESCRIPTION

    BULK

    HEAD

    BULK

    HEAD

    SAMPL

    ELINE

    VENTL

    INE

  • 8/11/2019 TQ Technical Manual

    30/99

  • 8/11/2019 TQ Technical Manual

    31/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    G.T.

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    WELDTUBE

    DIMENSIONAL

    DETAILS

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    *

    PROJECTION

    SCALE

    1:5

    150

    19

    .05

    Drill&TapBothEnds

    For1/4"BSPParallel

    19

    .05mm

    13

    .16mm

    11

    .46mm

    NOTES:

    1)Mater

    ial:19

    .05mmODMildSteelBrightTube

    WallT

    hickness6

    .35mm

    15

    15

    31-0

    7-0

    6

    31-0

    7-0

    6

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    JOC

    INTERNATIONAL

    7748Y1

  • 8/11/2019 TQ Technical Manual

    32/99

  • 8/11/2019 TQ Technical Manual

    33/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748Z1

    ProjNo.

    Client.

    JOC

    INTERNATIONAL

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ENDOFLINEFILT

    ER

    DRAWING

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    31-0

    7-0

    6

    PROJECTION

    SCALE

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    316LSt/St

    housing

    PourosSt/St

    w

    ashablefilter

    element

    316LSt/St

    endcap

    Oring

    Vitondowty

    seal

    8mmto1/4BSP

    paraellelfittingBrass

    N/A

  • 8/11/2019 TQ Technical Manual

    34/99

  • 8/11/2019 TQ Technical Manual

    35/99

    Pump

    FILTER

    8Way

    So

    leno

    idBan

    k

    VENT

    FLOW

    INDICATOR

    NOTES:

    1)AllInternalp

    ipework

    fittings

    tobe

    6.0

    mm

    ODUOS

    8mm

    Compress

    ion

    Fittings

    Samp

    le

    Lines

    8

    Pressure

    Differen

    tial

    Valve

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748F2

    ProjNo.

    Client.

    Drn.

    Date.

    12

    -07

    -06

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    TQ4400PUMPROOM

    PNEUMATIC

    SCHEMTAIC

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    12

    -07

    -06

    * *

    24-0

    1-0

    0

    PROJECTION

    SCALE

    N/A

    12

    -07

    -06

    *

    P r e s s

    u r e

    D i f f e

    r e n

    t i a l

    F l o w

    F a i

    l

    D e v i c e

    + V

    e

    - V e

    GD129

    FLAM

    SENSOR

    TQ123

    H2S

    SENSOR

    TQ123

    O2

    SENSOR

    7654321

    FLAME

    ARRESTORS

    BYPASS

    VALVE

    3Way

    CALIBRATION

    VALVE

    CALIBRATION

    PORT

    JOC

    INTERNATIONAL

    7748

    TQ4400PUM

    P

    ROOMSAMPLINGSYSTEM

    05

    -08

    -06

    G.T

    05

    -08

    -06

    N.D.A

    Tex

    tCh

    anged

    1.

  • 8/11/2019 TQ Technical Manual

    36/99

  • 8/11/2019 TQ Technical Manual

    37/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748G2

    ProjNo.

    Client.

    JOC

    INTERNATIONAL

    Drn.

    Date.

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    24-0

    1-0

    0

    PROJECTION

    SCALE

    N/A

    7748

    TQ4400

    PUMP

    ROOMSAMPLINGSY

    STEM

    31-0

    7-0

    6

    G.T

    POWERSUPPLY

    WIRINGDIAGRAM

    1/2/3+5

    13+24

    -0V

    L N E

    1

    ISOLATOR

    PUMP

    PSU

    1 2

    TBF-0

    2

    RL2

    6

    F6(1A)

    F5(1A)

    F4(1A)

    14

    18

    5

    57

    6

    240/

    110Vac

    60Hz

    2A

    EMC

    SUPRESSOR

    Brown

    Blue

    85-

    254

    VAC

    NOTE

    S:

    1)All

    ACwiringtobe

    0.5mmtri-ratedU

    .O.S.

    All

    DCwiring

    tobe

    20A

    WGUL1007UOS

    Violet

    TBF01

    3

    +24 0

    V+24

    LOCAL

    VISUAL

    LOCAL

    AUDIBLE

    L N E

    4

    0V

    Green/Yellow

    4.0

    mm

    Green/Yellow

    Enclosure

    EarthStud

    Red

    Blue

    4/5/6/7

    31-0

    7-0

    6

    *

    F7

    5

    2

    TB-0

    1

    0V

    5

    Black

    Red

    Red

    15Red

    16Red

    17Red

    17

    8/9+12

    F2(2A)

    F1(2A)

    10Violet

    11Violet

    ToControlboardConn6Pin2

    Seedw

    g7748H

    TodisplayboardConn6Pin2

    Seedw

    g7748L

    F3(1A)

    12Orange

    ToControlboardConn6Pin3

    Seedwg7748H

    TodisplayboardConn6Pin3

    Seedwg7748L

    6 7 8

    ToFlowFailUnit

    Seedw

    g7748H

    Black

    Red

    Orange

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    N.D.A

    1.

    TextChanged

  • 8/11/2019 TQ Technical Manual

    38/99

  • 8/11/2019 TQ Technical Manual

    39/99

    TQENVIRONMENTAL

    PLC

    FlanshawWay

    Wakefield

    WestYorkshire

    WF29LP

    ProjectTitle.

    Draw

    ingTitle.

    DwgNo.

    ProjNo.

    Client.

    Drn.

    Date.

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    R

    evisions.

    No.

    Copyrightof

    CWeb:http//www.tqplc.com

    Email:[email protected]

    TQ4400PRSENSOR,

    FLOWFAIL

    CIRCUITDIAGRAM

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    PROJECTION

    SCALE

    N/A

    23

    TQ4400

    Con

    tro

    lBoar

    d

    NOTES:

    1)ALLWIRINGTOBE

    20AWGUL1007U

    .O.S

    3 2 1

    24V

    5V 0

    V

    CONN8

    CONN6

    1

    Red

    Blue

    F1

    F4

    TB

    -01

    0V

    Red

    14

    Violet

    10

    Black

    5

    *

    7748H2

    31-07-06

    31-07-06

    7748

    TQ4400PUMP

    ROOMSAMPLINGSYSTEM

    2Core

    Tw

    isted

    Pair

    WithOveral

    lScreen

    ToConn8

    ofDisplay

    Board

    JOC

    INTERNATIONAL

    3

    CONN12

    Links

    Lk1

    -In

    Lk2

    -AInpos

    2-3

    BInpos

    4-5

    CInpos

    7-8

    DOu

    t

    Lk3

    -N/A

    Lk4

    -11

    -Inpos

    1-2

    (Towar

    dMH4)

    Lk12

    -In

    Lk13-

    Inpos

    2-3

    Lk14-

    In

    Lk15

    -Inpos

    2-3

    (Towar

    dm

    iddleo

    fPCB)

    Lk16-

    Inpos

    2-3

    (Towar

    dou

    tsideo

    fPCB

    )

    Lk17-

    Inpos

    2-3

    (Towar

    dou

    tsideo

    fPCB

    )

    Cabledetailadded

    Re

    d22

    DIFFERENTIAL

    F/FAIL

    DEVICE

    PtNo

    .140

    -021

    0V

    SIG

    12V

    2

    1

    CONN2

    2 87

    CONN1

    654321

    Topushb

    uttons

    See

    Dwg.

    7748K

    Black 5

    12

    CONN9

    Green

    /

    Yel

    low

    9

    Red

    Clear

    Black

    123

    34

    PO

    GD129

    (CH4Sensor)

    +-

    FB

    H2S

    SENSOR#1

    PO

    OXYGEN

    SENSOR#2

    PO

    56

    PO

    Red

    Blue

    1

    2

    CONN15

    9

    3

    4

    87

    CONN1

    654321

    To

    So

    leno

    ids

    See

    Dwg.

    7748J

    2

    3

    1

    F3

    TB

    -01

    0V

    Orange

    12

    Black

    5

    Toalarmre

    lays

    See

    Dwg

    .4826CB

    Yel

    low

    21

    Black

    5

    TOCONN

    12

    PIN3DIS

    PLAY

    CARDSE

    E7748L

    3Core

    BELDON

    TYPECABLE

    G.T

    05-08-06

    N.D.A

    05-08-06

    1.

  • 8/11/2019 TQ Technical Manual

    40/99

  • 8/11/2019 TQ Technical Manual

    41/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748J2

    ProjNo.

    Client.

    JOC

    INTERNATIONAL

    Drn.

    Date.

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    * *

    24-0

    1-0

    0

    PROJECTION

    SCALE

    N/A

    7748

    TQ4400PUMP

    ROOMSAMPLINGSY

    STEM

    31-0

    7-0

    6

    TQ4400PR

    SOLENOIDVALVE

    &

    RELAYCCTDIAGR

    AM

    1

    2

    3

    4

    5

    6

    7

    8

    9

    CONN3

    +24V

    G.T

    31-0

    7-0

    6

    *

    9 8 7 6 5 4 3 2 1

    CONN 15

    +24V

    RL

    1

    RL2

    RL3

    A2

    A1

    A2

    A1

    A2

    A1

    1

    2

    3

    AL1

    1 8

    1 8

    1 8

    7

    8

    9

    AL2

    101112

    Fault

    2 4

    3

    2 4

    3

    2 4

    3

    50515

    2

    535455

    565758

    White

    White

    TBF-0

    3

    TBF-0

    3

    TBF-0

    3

    White

    SOL#1

    SOL#2

    SOL#3

    SOL#4

    SOL#5

    SOL#6

    SOL#7

    SOL#8

    Contro

    lBoard

    Red45

    Blue46

    Red43

    Blue44

    Red41

    Blue42

    Red39

    Blue40

    Red37

    Blue38

    Red35

    Blue36

    Red33

    Blue34

    Red31

    Blue32

    TB-

    02

    R

    ed

    28

    21

    Red23

    Black24

    Black

    25

    Black

    26

    Red23

    Red23

    4

    5

    6

    AL1

    5

    6

    150

    151

    152

    White

    TBF-0

    37

    RL1-1

    RL1-2

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    N.D.A

    1.

    RL1ContactsAdded

  • 8/11/2019 TQ Technical Manual

    42/99

  • 8/11/2019 TQ Technical Manual

    43/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo.

    7748K1

    ProjNo.

    Client.

    JOC

    INTERNATIONAL

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    TQ4400SETUPDISP

    LAY

    WIRINGDIAGRAM

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    *

    PROJECTION

    SCALE

    7748

    N/A

    TQ4400PUMP

    ROOMSAMPLINGSYSTEM

    1)Connectribboncable

    redwiretopin1

    .

    A C

    DISPLAY(PartNo.

    814-

    010)

    REDWIRE

    TOBOTTOM

    16PIN

    CONNECTO

    R

    200mm

    1

    16WayRibbon

    CONNECTTOCONN5

    OFPCB4200

    I1

    PtNo.

    913-0

    16-0

    02

    2)CutPCBTracksFrontand

    RearasIndicated,

    andFit

    6R2Limmiting

    Resistor

    SolderedtoPads.

    3)AllWireToBe20AWG

    UL1007

    CutTrack

    CutTrack

    6R2@0

    .6W

    A K

    Rear

    Of

    Display

    NOTE:

    SELECT

    UP

    DOWN

    MENU

    Grey

    Orange

    White

    CONN1

    ,PIN8

    CONN1

    ,PIN5

    CONN1

    ,PIN4

    Blue

    CONN1

    ,PIN1

    SeeDwg.

    7748H

    ControlPCB

    91

    92

    93

    94

    SeeDwg.

    7748H

    ControlPCB

    95Red

    Conn13, Pin 9

    05-0

    8-0

    6

    G.T

    05-0

    8-0

    6

    N.D.A

    ButtonConnectionsChd

    1.

  • 8/11/2019 TQ Technical Manual

    44/99

  • 8/11/2019 TQ Technical Manual

    45/99

    TQENVIRONMENTAL

    PLC

    Flanshaw

    Way

    Wakef

    ield

    Wes

    tYorksh

    ire

    WF29LP

    ProjectTitle.

    DrawingTitle.

    DwgNo. 7

    748L1

    ProjNo.

    Client.

    JOC

    INTERNATIONAL

    Drn.

    Date.

    31-0

    7-0

    6

    G.T

    Chkd.

    Date.

    App.

    Date.

    Sig.

    Date.

    Revisions.

    No.

    Copyrightof

    CWeb:

    http

    //www

    .tqp

    lc.c

    om

    Emai

    l:sa

    les@

    tqp

    lc.c

    om

    TQ4400PRFRONTPA

    NEL

    CCTDIAGRAM

    ISSUECONTROL

    PRODUCTION

    DEVELOPMENT

    SERVICE

    CLIENT

    DATE

    31-0

    7-0

    6

    *

    PROJECTION

    SCALE

    N/A

    7748

    TQ4400PUMP

    ROONSAMPLINGSYST

    EM

    1)AllWiringtobe20AWG

    UL1007UOS

    NOTES:

    +24V

    SYSTEMHEALTHY

    ALARM

    2

    ACK

    SKIP

    HOLD

    RESET

    64

    66

    60

    61

    62

    63

    ALARM

    1

    65

    69Red

    White

    White

    White

    White

    Black

    Black

    Black

    +

    -Buzzer

    23

    TQ4400

    DisplayBoard

    3 2 1

    24V

    5V 0

    V

    CONN8

    CONN6

    1

    Red

    Blue

    F2

    F5

    TB-0

    1

    0V

    Red1

    5

    Violet

    11

    Black

    5

    2

    CoreTwisted

    PairW

    ithOverallScreen

    ToConn8

    ofControl

    Board

    3

    CONN12

    Red22

    2

    87

    CONN1

    654321

    B

    lack 5

    Red

    Blue

    1

    2

    CONN15

    9

    3

    4

    CutTrack

    6R2

    @0.6W

    A K

    RearOf

    Display

    67

    A C

    DISPLAY(Par

    tNo

    .814

    -010)

    REDWIRE

    TOBOTTOM

    16PIN

    CONNECTOR

    200mm

    16WayRibbon

    CONNECTTOCONN5

    OFPCB4200I1

    PtNo

    .913

    -016

    -002

    CutTrack

  • 8/11/2019 TQ Technical Manual

    46/99

  • 8/11/2019 TQ Technical Manual

    47/99

    DOC: 7748/TMTQ ENVIRONMENTAL PLC

    Tel: +44(0) 1924 380700

    3.0 TQ4400 Operating Manual

  • 8/11/2019 TQ Technical Manual

    48/99

  • 8/11/2019 TQ Technical Manual

    49/99

    TQ Environmental Plc

    Filename: Technical Manual Page 1 of 51

    TQ4400 PUMPROOM

    GAS SAMPLING SYSTEM

    OPERATING MANUAL

    TQ Environmental Plc 2007

    This manual must not be copied or reproduced in part without the express written

    permission of TQ Environmental PLC. All information contained herein is subject to

    modification.

    TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP

    44 (0) 1924 380700; FAX 44 (0) 1924 361700.

    E-mail : [email protected]

    Web Site : www.tqplc.com

    TQ ENVIRONMENTAL PLC BS EN ISO 9001

    Date of Issue: 25thOctober 2006

    Author: G Thompson

  • 8/11/2019 TQ Technical Manual

    50/99

    Page 2 of 51 Filename: Technical Manual

  • 8/11/2019 TQ Technical Manual

    51/99

    TQ Environmental Plc

    Filename: Technical Manual Page 3 of 51

    CONTENTS

    1. INTRODUCTION 52. SYSTEM DESCRIPTION 7

    2.1 Pneumatics 7

    2.2. Sensors 9

    2.3 Control and Display Electronics. 10

    2.4 Power Supply Change Over Unit 13

    2.5 Outputs. 13

    2.6 Technical Specification 14

    3. OPERATION 15

    3.1 System Start-up 15

    3.2 Normal Operation 15

    3.3 Panel Controls 163.4 Alarm Conditions 18

    4. SYSTEM SETTINGS 21

    4.1 Set up Controls 21

    4.2 Power Up 21

    4.3 Set Up-Menu Access 22

    4.4 Parameters 24

    4.5 Sensor Menu 28

    4.6 Technician Sub Menu 32

    4.7 Sensor Menu 37

    5. INSTALLATION 405.1 TQ4400 Analysing Unit 40

    5.2 Power Supply Change over Unit 40

    5.3 Manual Shut Off Valves 40

    5.4 End of Line filters 42

    5.5 In-Line Filters 42

    5.6 Sample Lines 43

    6 COMMISSIONING 45

    6.1 Installation. 45

    6.2 System Power Up. 45

    6.3 Setting the Flow Rate 46

    6.4 Sample Location Set-Up Test 466.5 Testing Gas Concentration Alarms 46

    6.6 Testing Analysing Unit Cabinet Gas Detector 46

    7 SCHEDULED MAINTENANCE 47

    7.1 System Confidence Test Sequential Sampling Part 47

    7.2 Filter Check 47

    7.3 System Calibration (All Sensors) 48

    7.4 Pump Service 48

    7.5 Testing and Calibrating the TQ126F 48

    8 PARTS LIST 50

    Appendix A 51

  • 8/11/2019 TQ Technical Manual

    52/99

  • 8/11/2019 TQ Technical Manual

    53/99

    TQ Environmental Plc

    Filename: Technical Manual Page 5 of 51

    1. INTRODUCTION

    The TQ4400 Pump room sampling system is a multipoint, sequential, aspirated, gas

    sampling system. The System is designed to meet with IMO / SOLAS requirements,

    and comply with classification rules for monitoring Void Spaces on board Gas

    Carriers and Oil & Gas Tankers, in areas adjacent to the cargo areas.

    The TQ4400 Pump room sampling system extracts a gas sample from a desired

    location, via transport lines to an analysing unit where the sample is monitored for

    Flammable, Toxic and Oxygen gases. The TQ4400 in its usual form uses fixed

    gas sensor heads to constantly monitor gases in conjunction with solenoids and a

    pump to make this into a cost effective sampling system.

    ** The TQ4400 Pump room sampling system should not be regarded as a primary

    unit for the safety of the personnel within the Pump room. Portable personal hand

    held devices are recommended as primary protection for personnel in confined spaces.

    **

    The number of locations for a TQ4400 is restricted to 8. Any more, then the TQ 4400

    Ballast tank monitoring system should be used

    Typical explosive and toxic gas sensors, which can be installed within the TQ4400,

    can be seen in table 1, (other gases are available on request.)

    Explosive Toxic

    Methane 0-100% LEL H2S Various ranges

    Butane 0-100% LEL CO Various ranges

    Methane 0-100% VOL CO2 Various ranges

    Butane 0-100% VOL Oxygen 0-25% VOL

    Table 1

    The TQ4400 is capable of providing individual low and high alarm outputs for

    each Gas sensor installed and corresponding alarm relays. This can provide an

    interface with alarm management systems, remote mimic panels, and audible / visual

    warning devices.

    The TQ4400 Unit is mounted within the cabinet. The operator interface is via four

    push buttons and a backlit LCD. During normal operation the LCD display will

    provide the gas type and sample concentration for each individual location.

  • 8/11/2019 TQ Technical Manual

    54/99

    Page 6 of 51 Filename: Technical Manual

  • 8/11/2019 TQ Technical Manual

    55/99

    TQ Environmental Plc

    Filename: Technical Manual Page 7 of 51

    2. SYSTEM DESCRIPTION

    The TQ4400 Pump room sampling system standard Analysing Unit is housed in a

    wall-mounted enclosure complete with front panel Display Unit. The enclosure

    contains all electrical, electronic and pneumatic equipment required to monitor,

    display, control and provide alarm outputs for the relevant locations.

    The TQ4400 Pump room sampling systemis divided into the following main

    components:

    Pneumatics

    Sensors

    Control & Display Unit

    Power Supply Change Over Unit

    Sample Line Accessories

    Outputs

    Technical Specification

    2.1 Pneumatics

    Every Sample Line from the relevant location is firstly connected to its

    respective external Shut-off Valve to provide sample line isolation. The

    sample then passes through a flame arrestor mounted externally on the bottom

    of the cabinet, and into the Analyser Unit.

    The typical Analysing Unit contains the following pneumatic devices:

    Solenoid Valves

    Particulate Filter Pump

    Flow Detector

    Leak Detection

    2.1.1 The Solenoid Valves are mounted singularly on the back panel of the

    cabinet. Each solenoid is then individually plumbed to the gland plate

    where they are fitted with a deflagration flame arrestor from which the

    sample line can be connected.

    Connected to each solenoid is a timer relay the time set on this relaygoverns the sample time. Each timer will then trigger the subsequent timer

    on completion of sample, therefore resulting in a sequential sample

    Each valve is complete with a 24V D.C. coil, and connection to each coil

    is via a 3 pole connector containing an LED and snubbing diode.

    2.1.2 The Particulate Filter is fitted with a micro-fibre filter element, which

    cannot be cleaned and therefore must be replaced when it is suspected of

    reducing air flow. This unit is also fitted with a poly-carbonate bowl to

    allow visual inspection of the filter element. Spare filter elements can be

    supplied, refer to Section 8 for Part numbers.

  • 8/11/2019 TQ Technical Manual

    56/99

    Page 8 of 51 Filename: Technical Manual

    2.1.3 The Pump is an Industrial type to ensure adequate flow rates for the

    larger installations. As an example on transport tube dimensions of

    4.0mm I/D, flow rates in excess of 4 litres/min. are achievable for sample

    line lengths up to 300 metres. Based on these figures, sample times for a

    300 metre sample line will be in the order of 1 minute, providing sharp

    bends and fittings are kept to a minimum. A Pump Service Kit can be

    supplied refer to Section 8 for Part numbers

    2.1.4 The Flow Meter is fitted in the sample flow line to indicate airflow to the

    sensors and works in conjunction with the Sample by-pass needle valve.

    The steel float, sensing ring and control relay, are all part of the flow fail

    device. If the float passes down through the sensor a Low Flow signal is

    sent to its control relay. When flow returns the float will raise back

    through the sensor and the signal to its control relay will revert to normal.

    2.1.5 A Leak Detection System is incorporated within the TQ4400 Analyser

    enclosure and monitors for any accumulation of flammable gases within

    the enclosure. This system utilises a TQ122 catalytic flammable gasdetector fitted in the top of the enclosure, which is connected to a

    TQ126Fcontroller fitted in the Power Supply Change-over Unit.

    If the gas concentration within the enclosure exceeds 30% LEL the Power

    Supply Change-over Unit will disconnect the power supply to the

    TQ4400Analysing Unit. The power supply cannot be re-connected until

    the gas concentration has fallen below the alarm level and a manual reset

    at the Power Supply Change-over Unit has been carried out.

    2.1.6 Sample Line Equipment is optionally available in several forms to suitthe sample location.

    End of Line filters for Dry areas,

    In-line filter (where an End of line filter is not practical)

    There are two types of End of Line Filters. See section 5.4 & 5.5

    A fibre element type where the filter element has to be replaced

    periodically.

    A stainless steel type where the filter element can be cleaned.

    Both of the above filters are supplied with dual compression fittings tosuit pipe sizes 6 or 8mm O/D, in either brass or stainless steel. It is

    advisable to protect the Filter when installed in a location where damage

    may occur.

    The In-Line Filteris a stainless steel unit that is suitable for attaching to

    a stop-valve when fitted in a stop valve box or can be fitted to the line in a

    serviceable location. It is advisable to remove the In-Line Filter complete

    for cleaning, as splitting the filter in situ may damage the threads.

  • 8/11/2019 TQ Technical Manual

    57/99

    TQ Environmental Plc

    Filename: Technical Manual Page 9 of 51

    2.2. Sensors

    There are two type of sensors, the infrared type, for flammable gases, or the

    electro-chemical type for Toxic and Oxygen gases. When a system comprises

    of more than one sensor, they are connected in series in the sample line which

    then is vented out from the enclosure through a flame arrestor.

    2.2.1 Infrared Sensor (GD 129NI)

    The operation of the infrared sensor within the TQ4400 Pump room

    sampling system is to measure the absorption of infra red light by a target

    hydrocarbon gas and converting that absorption to an electronic signal.

    The infrared sensor is now packaged as a GD-129 stand-alone unit within

    the TQ4400 and provides a 4-20mA signal for their respective target gas

    concentrations.

    Part Number for the GD129 for 0-100%LEL METHANE is 340-020

    2.2.2 Electro-chemical Type.

    These sensors typically monitor for Oxygen and Toxic gases and because

    of their properties have a life span of approximately 1-2 years depending

    on conditions.

    The Electrochemical types, as with the Infrared sensor, provide a 4-20mA

    signal for their respective gas concentrations.

    Part Number for the TQ123 for 0-25%VOL OXYGEN is 123-531

    Part Number for the TQ123 for 0-50PPM H2S is 123-251

  • 8/11/2019 TQ Technical Manual

    58/99

    Page 10 of 51 Filename: Technical Manual

    2.3 Control and Display Electronics.

    The settings for the TQ4400 Pump room sampling system is divided into two

    Parts, a) the TQ4400 display and b) the TQ 4400 Set Up/ Control

    The TQ4400 Set up/ Control monitors the signal the signal from each gas

    detector in the sample system and controls the solenoids sequentially.

    The TQ4400 Set up/ Control analyses the gas and transmits back to the TQ4400

    display card concentrations and any alarm associated with the recent analysis of

    the gas sample

    TQ 4400

    CONTROLCARD

    INFRA RED

    FLAMMABLE

    ELECTROCHEM

    O2

    ELECTRO

    CHEM

    H2S

    FLOW FAILPUMP

    SOLENOID 1

    SOLENOID 2

    SOLENOID 3

    4-20mA

    SIGNAL

    Vent

    SOLENOID 4Sample line 4

    Sample line 1

    Sample line 2

    Sample line 3

    TQ 4400DISPLAY

    CARD

    Fig. 1 Block diagram of System

    2.3.1 The TQ4400 DisplayUnit

    The 4400 Unit houses the display PCB board and the control PCB. The

    display PCB board accepts details of the sensor status from the set up /

    control, and displays the current system status.

    During normal operation the Unit will show the gas type, gas

    concentration and fault alarm status. Refer to section 3 for operation.

    The Front Panel Display includes: (fig 2 Page 8)

    Liquid Crystal Display.

    4 Push buttons (Ack, Reset, Hold and Skip function).

    3 LEDs (Low Alarm, High Alarm and System Healthy)

  • 8/11/2019 TQ Technical Manual

    59/99

    TQ Environmental Plc

    Filename: Technical Manual Page 11 of 51

    TQ4400 PUMP ROOM UNIT

    ALARM

    1

    ALARM

    2

    SYSTEM

    HEALTHY

    ACK RESET HOLD SKIP

    LCD DISPLAY

    ALARM LED's

    PUSH BUTTONS

    Fig 2 Front Display of TQ4400

    2.3.2 The TQ4400 Control Unit

    The 4400 Control unit or PCB Unit is position within the TQ 4400

    enclosure and performs the logic behind the TQ4400

    During normal operation this Unit will show the location with A-D

    conversion done. Refer to section 4 for settings.

    The Panel Display includes:

    Liquid Crystal Display.

    4 Push buttons (Select, Up, Down and Skip function).

    The user can alter any of the settings from the panel display.

  • 8/11/2019 TQ Technical Manual

    60/99

    Page 12 of 51 Filename: Technical Manual

    3 8 0

    3 2

    2

    3 8 0

    Rig

    htH

    andO

    pen

    ing

    Doo

    r

    10

    8.3

    4 1 0

    570

    580

    POWER

    SUPPLYCHANGE

    -OVER

    UNIT

    FORTANKSCANGAS

    SAMPLINGSYSTEM

    4Holes

    x10

    .0mm

    MAIN

    SUPPLY

    STANDBYSU

    PPLY

    GASALARM

    RESET

    TQENVIRONMENT

    ALPLC

    F l a

    n s h a w

    W a y

    , W

    a k e f

    i e l d

    , W Y

    o r k s

    E n g

    l a n

    d ,

    W F 2 9 L P

    T e

    l : + 4 4 1 9 2 4 3 8 0 7 0 0

    F a x :

    + 4 4 1 9 2 4 3 6 1 7 0 0

    E m a i

    l : s a

    l e s @

    t q p

    l c . c

    o m

    w e b s i

    t e : h

    t t p : /

    / w w w

    . t q p l c . c o m

    NO

    TES

    :

    1)P

    rote

    ctio

    nR

    atin

    go

    fca

    bin

    ent

    isIP65

    Fig 3 Power Supply Change-over Unit

  • 8/11/2019 TQ Technical Manual

    61/99

    TQ Environmental Plc

    Filename: Technical Manual Page 13 of 51

    2.4 Power Supply Change Over Unit

    Refer to Fig 3, Page 9.

    This Unit is connected to the Ships Main and Emergency Power Supplies,

    to provide an automatic changeover for the supply to the Analyser Unit in the

    event of a Mains Supply failure.

    The unit is either a 110-120 or 220-240V (not both) a.c., 50-60 Hz input, and

    will automatically change back to Main when the main supply is restored.

    Incorporated within the Power Supply Change-Over Unit is a TQ126F

    controller, which monitors the TQ4400Analysing Units Leak Detection gas

    detector. The TQ126Fwill disconnect the power supply to the Analyser Unit if

    the sensor detects a gas concentration of 30% LEL. The power supply to the

    Analyser Unit will not be restored until the gas concentration has fallen below

    30% LEL and the reset button on the front of the Power Supply Change-Over

    Unit has been pressed.

    Front Panel indications are provided for:

    Mains Supply On

    Emergency Supply On

    Internal Gas Alarm

    2.5 Outputs.

    The TQ4400standard outputs are in the form of:

    Two sets of Volt Free Change-over relay contacts for Common

    Concentration Alarm Low.

    One sets of Volt Free Change-over relay contacts for Common

    Concentration Alarm High.

    One set of Volt Free Change-over relay contacts for System Fault Alarm.

    Two 24VDC Output for Common Concentration Alarm High. (typically

    rated for beacon and sounder connection

  • 8/11/2019 TQ Technical Manual

    62/99

    Page 14 of 51 Filename: Technical Manual

    2.6 Technical Specification

    Power 110/240V 50/60Hz @ 4 Amps non

    inductive

    Internal d.c. power supplies 1 x 5V DC (System Electronics)

    1 x 24V DC (Sensors / Solenoids)(factory fitted dependent on sensor

    ratings and overall system requirement)

    Max no. of locations for sequential

    monitoring per Max no. of Sensor

    8 Locations for 3 Sensors

    Sensor types 4-20mA current sources (2 or 3 wire)

    Pump Capacity 11 Litres / Minute (open ended)

    Gas Concentration Alarm Outputs Standard: - 2 x Common Low / 1 x

    Common High Volt Free Contacts, @

    5Amps. Resistive.

    Custom: - Up to 1 Individual Volt Free

    Contact per Sample Location Gas Alarm,

    5A.

    Sample Lines Seamless Stainless Steel

    316(Preferred)/.Copper

    OD 6mm - 8mm, ID 4mm - 6mm.

    Max length 300Metre @ 4.0mm I/D

    Fault Alarm Outputs 1 x System Fault Volt Free Contact

    Data communications RS 485 configurable for use with Printer

    Additional Outputs

    Operational temperature and humidity

    range

    0oC-40oC 0-90%RH non-condensing.

  • 8/11/2019 TQ Technical Manual

    63/99

    TQ Environmental Plc

    Filename: Technical Manual Page 15 of 51

    3. OPERATION

    This section explains in detail the TQ4400 system operation and typical alarm

    conditions.

    3.1 System Start-up

    When power is applied to the system, the display will indicate System Set-up

    mode, as below

    SYSTEM SETUP

    PLEASE WAIT

    The system will stay in this mode for approximately 150 seconds.

    3.2 Normal Operation

    After the start-up delay the system will enter the normal operating mode.

    CHAN 1

    METHANE 00015%LEL

    The top line of the display shows the channel location and the bottom line of

    the display will show the gas sensor name, concentration of the gas, and the

    units of the gas being analysed. The system will sequentially sample all of the

    channel locations, displaying the appropriate data on the LCD.

  • 8/11/2019 TQ Technical Manual

    64/99

    Page 16 of 51 Filename: Technical Manual

    3.3 Panel Controls

    ACK- Acknowledge alarm. This button allows the user to accept the gas

    alarm, mute buzzer and to visualise further sampling. See section 3.4.2

    (Except fault & flow fail)

    RESET- Reset alarm. This button allows the user to reset the gas alarm, mutebuzzer and to continue sampling; it will reset any cleared faults also. See

    section 3.4

    HOLD-Hold Channel. See Section 3.3.2 below

    SKIP-Skip Channel. See Section 3.3.2 below

    At any time during the normal operating mode, the user has the option to

    GOTO, Hold or Skip a channel. These functions are invoked by pressing

    down the relevant push button, and are discussed further below:

    3.3.1 GOTO Channel

    The user may press down and hold theRESETandHOLDbutton until thedisplay reads GOTO, the user must then release the RESETand HOLD

    button. You can then select which sample location to GOTO by using

    ACK to go up and RESET to go down through the sample locations.

    PressingHoldselects the desired channel.

    Once the unit is sampling from the desired location you can then either

    HOLD, SKIP or Reverse Purge the location.

    3.3.2 Hold Channel

    The user may press down and hold the HOLD button until the display

    readsHOLD CHANNEL, the user must then release theHOLDbutton.

    CHAN 1

    HOLD CHANNEL

    This will invoke the Hold Channel function. The current Channel location

    will be continuously sampled for a maximum period of 20 minutes after

    which time the system will revert to sequential sampling. At any time the

    user may release the channel and enable the system to revert back to

    sequential sampling.

    This is achieved by pressing down and holding theHOLDbutton until the

    display readsRELEASE CHANNEL, the user must then release theHOLD

    button.

  • 8/11/2019 TQ Technical Manual

    65/99

    TQ Environmental Plc

    Filename: Technical Manual Page 17 of 51

    CHAN 1

    RELEASE CHANNEL

    3.3.3 Skip Channel

    The user may press down and hold the SKIPbutton until the display reads

    SKIP MODE, the user must then release the SKIPbutton.

    CHAN 1

    SKIP MODE

    This will invoke the Skip Channel function. The current channel location

    will be skipped when the system is sequentially sampling the channel

    locations. When the system returns to the skipped channel, the LCD will

    display SKIP MODEfor 5 seconds and then proceed to the next sequential

    channel. When the LCD displays SKIP MODE the user may revoke the

    skip command by pressing down and holding the SKIP button until the

    display reads NORMAL MODE, the user must then release the SKIP

    button.

    CHAN 1

    NORMAL MODE

    3.3.4 Manual Global Reverse Purge.

    The user may press down and hold theACKandRESETbuttons until the

    display reads GLOBAL REVERSE PURGE followed by REVERSE

    PURGE. This initiates a global reverse purge where air is blown down

    every sample line for a set period of time. The purge duration is factory

    set and a Button box is required to be interfaced to the controller BTC

    board to change the value.

    After the system has finished purging it will revert back to sampling.

  • 8/11/2019 TQ Technical Manual

    66/99

  • 8/11/2019 TQ Technical Manual

    67/99

    TQ Environmental Plc

    Filename: Technical Manual Page 19 of 51

    FLOW FAIL

    To clear the Fault condition press clear blockage or SKIP the channel,

    then hold the RESETbutton until the display reads RESET ALARM. At

    the same time, the System Healthy led will illuminate and the Fault relay

    will be de-activated. The alarm will not clear until the system has flow

    again, it may require re-booting to allow user to SKIP the problem

    channel.

    RESET ALARMS

    3.4.1.3 Communications Failure

    A Comms Failure will initiate when communications are interrupted for

    more than 2 minutes between the Display BTC PCB and the Control BTC

    PCB.

    COMMS FAILURE

    This cannot be reset by theRESETbutton; the panel has to be opened and

    powered down and back up again. However it is preferred to do this from

    the power supply changeover unit.

    3.4.2 Concentration Alarms

    There are two alarms on the system, a low level alarm, ALARM 1, and a

    high level alarm,ALARM 2. When the gas concentration exceeds the set

    levels, the appropriate alarms will be activated, and operate the

    appropriate LEDs and alarm relays. The LCD will display the first

    channel to be in alarm, together with the sensor gas type and relevant

    alarm condition. The system will continue to sample the channels

    sequentially.

  • 8/11/2019 TQ Technical Manual

    68/99

    Page 20 of 51 Filename: Technical Manual

    CHAN 1

    METHANE LOW ALARM

    CHAN 1

    METHANE HI ALARM

    The user may reset the alarmed channel by pressing theRESETbutton. At

    which point the alarms for that channel will be cleared. If there are any

    pending alarms then the LCD will display the next alarmed channelinformation. The user must again press the RESET button to clear that

    particular alarm. When no more alarms are present, the system will

    display the concentration as normal.

    The user may press the Ackbutton to clear the audible buzzer (if fitted).

    This will acknowledge the alarmed channel and display ALARM

    ACKNOWLEDGEDon the LCD.

    CHAN 1

    ACKNOWLEDGED ALARM

    If there is a pending alarm the LCD will display the pending alarm

    information. When all alarmed channels have been acknowledged, the

    system will display the gas concentration sequentially, but will also

    display ALARM ACKNOWLEDGED on the LCD for 5 seconds. To de-

    activate the alarm relays the user must use the RESET function as

    described above.

    RESET ALARMS

    Each alarm is then reset on a channel per channel basis, i.e. if a particular

    channel is in alarm then another channel comes into alarm, then the first

    channel requires one reset and a second reset clears the next set of alarmsin the second channel.

  • 8/11/2019 TQ Technical Manual

    69/99

    TQ Environmental Plc

    Filename: Technical Manual Page 21 of 51

    4. SYSTEM SETTINGS

    In the TQ4400 Enclosure there is a Panel marked TQ4400 Set Up/Test Panel

    or Box with four push buttons and a LCD display (see below). During

    Normal operation this display will show the channel name followed by A-D

    conversion Done

    SELECT UP DOWN MENU

    TQ4400 SET UP PANEL

    Fig 4 Typical TQ4400 Set Up Panel.

    If any parameter requires changing within the system, and if the sensorrequires a calibration check, then the Technical and Parameters Menu will

    required to be accessed from this Panel.

    Parameters Include: - Location Names, Sensor Names, Dwell Times, Gas

    Units, Gas Range, and Alarm Levels.

    Technical Parts Include: - Calibration, No. of Sample Points, No. of channels,

    reverse purge frequency, reverse purge times and another Skip Channel

    function.

    A MENU MAP IS ENCLOSED ON PAGE 35, 36 & 37 which may help when

    using the menus.

    4.1 Set up Controls

    The set-up controls consist of four push buttons SELECT, UP, DOWN and

    MENUwhich interfaces with the TQ4400 control circuit board which is fitted

    behind the Buttons and LCD.

    4.2 Power Up

    When the system is first powered up the title screen will be displayed showing

    the software name and version number.

  • 8/11/2019 TQ Technical Manual

    70/99

    Page 22 of 51 Filename: Technical Manual

    TQ ENVIRONMENTAL

    CONTROL Ver. 1.5

    4.3 Set Up-Menu Access

    After the title screen is displayed, the display will then read TRANSFERRING

    SYSTEMand dots appear on the bottom line of the display (One dot for each

    sample point being monitored).

    TRANSFERING SYSTEM

    ....

    To access the menu system, theMENUbutton must be pressed and held down

    as the dots appear on the bottom line.

    TRANSFERING SYSTEM

    . . . . . . . . .

    When the last dot has appeared on the bottom line of the display then the

    display will showMENU- PARAMETERS and therefore successful entry to the

    menu structure.

    MENU

    PARAMETERS

    The menu may now be navigated by pressing the UP and DOWN buttons,

    which will enable the user to scroll through the menu items. The menu items

  • 8/11/2019 TQ Technical Manual

    71/99

  • 8/11/2019 TQ Technical Manual

    72/99

    Page 24 of 51 Filename: Technical Manual

    4.4 Parameters

    System parameters may be set and edited by entering the PARAMETERS

    menu option. Each parameter is set on a Location by Location Basis, therefore

    what ever is set for channel 1 does not apply to channel 2, with exception to

    the GLOBAL SENSOR settings (see section 4.4.5). The GLOBAL SENSORMenu setting will apply to all channels.

    Once entered, the display will prompt the user to select a desired channel for

    editing. The user must press the UP and DOWN buttons to display the

    required channel location and then press the SELECT button to accept that

    channel location.

    PARAMETERS MENU

    CHANNEL 1

    When a channel has been selected, the user may cycle through the Parameters

    Sub Menu using the UP and DOWN buttons and select the required

    Parameters Sub Menu Item using the SELECTbutton.

    PARAMETERS MENU

    SET LOCATION

    When performing a task within the parameters menu the unit will always

    return to the following screen: -

    PARAMETERS MENU

    CHANNEL 1

    To exit completely, press SELECT, thenDOWNonce to PARAMETERS

    MENU-EXIT MENU and press SELECT.

    Detailed descriptions of the Parameters Sub Menu items now follow:

  • 8/11/2019 TQ Technical Manual

    73/99

    TQ Environmental Plc

    Filename: Technical Manual Page 25 of 51

    4.4.1 Parameters Sub Menu - Set Location

    The channel locations are set by default to CHANNEL 1, CHANNEL

    2, etc. This option will allow the user to change the name of the channel

    locations to a more meaningful description up to 20 characters in length,

    including the character.

    SET LOCATION

    CH_

    The user must use the UP and DOWN buttons to cycle through the

    alphanumeric characters, pressing the SELECT button when the display

    shows the required character. To leave spaces, select the character and press the SELECT button. When the SELECT button has

    been pressed the next digit on the right will be displayed.

    It is important to press SELECTat the end to leave a space otherwise it

    may leave the last character off the end of the location.

    *-NOTE - If there is no intension of changing the location name then the

    SELECT button must be pressed until the cursor has reached the right

    hand side of the display followed byMENU.*

    To accept the channel location description the user must press the MENUbutton.

    4.4.2. Parameters Sub Menu - Set Gas Type

    PARAMETERS MENU

    SET GAS TYPE

    This option is used to set a particular gas to a particular channel location.

    The current channel location is the one entered at the beginning of the

    parameters sub menu. To set a particular gas the user must press the UP

    andDOWNbuttons to cycle through the available gasses. This option will

    allow the user to change the name of the sensor gas type to a more

    meaningful description up to 10 characters in length, including the

    character.

  • 8/11/2019 TQ Technical Manual

    74/99

    Page 26 of 51 Filename: Technical Manual

    SET GAS TYPE

    METH_

    The user must use the UP and DOWN buttons to cycle through the

    alphanumeric characters, pressing the SELECT button when the display

    shows the required character. To leave spaces, select the

    character and press the SELECT button. When the SELECT button has

    been pressed the next digit on the right will be displayed.

    It is important to press SELECTat the end to leave a space otherwise it

    may leave the last character off the end of the location.

    *-NOTE - If there is no intension of changing the Gas type then the

    SELECT button must be pressed until the cursor has reached the righthand side of the display followed byMENU.*

    To accept the channel location description the user must press the MENU

    button.

    4.4.3. Parameters Sub Menu - Set Dwell Time

    This option allows the user to specify the time in seconds that the system

    will remain in a particular channel location before sequentially

    incrementing to the next channel location. The dwell time is variable in therange from 0 to 300 seconds.

    PARAMETERS MENU

    SET DWELL TIME

    To change the dwell time for that particular channel the user must press theUP and DOWN buttons and the SELECT button when the desired dwell

    time is displayed.

    SET DWELL TIME

    00040

  • 8/11/2019 TQ Technical Manual

    75/99

    TQ Environmental Plc

    Filename: Technical Manual Page 27 of 51

    4.4.4 Parameters Sub Menu - Select Local Sensor

    This option will allow the user to set sensor parameters for a specified

    sensor on a specified channel.

    PARAMETERS MENU

    SELECT LOCAL SENSOR

    To select a particular sensor the user must press the UPandDOWNbuttons

    to cycle through the available sensors and SELECTbutton when the desired

    sensor is displayed.

    SENSOR MENU

    FLAMMABLE

    4.4.5. Parameters Sub Menu - Select Global Sensor

    PARAMETERS MENU

    SELECT GLOBAL SENSOR

    This option will allow the user to set sensor parameters for a specified

    sensor on all channels. The sensor parameters are the same as the Select

    Local Sensor parameters and are described as follows:

    To select a particular sensor the user must press the UPandDOWNbuttons

    to cycle through the available sensors and SELECTbutton when the desired

    sensor is displayed.

    SENSOR MENU

    FLAMMABLE

  • 8/11/2019 TQ Technical Manual

    76/99

  • 8/11/2019 TQ Technical Manual

    77/99

    TQ Environmental Plc

    Filename: Technical Manual Page 29 of 51

    SET HIGH ALARM

    00040

    When the desired alarm point level is displayed, the user must press the

    SELECTbutton to accept the displayed value.

    Set Alarm Type

    This option allows the user to specify a rising alarm + or a falling alarm -.

    HIGH ALARM MENU

    SET ALARM TYPE

    SET ALARM TYPE

    +_

    Press UPorDOWNto toggle between a rising alarm + or a falling alarm -.

    Then press SELECTon required alarm type.

    4.5.1.2 Set Alarms - Select Low Alarm

    This option is the same as the Set High Alarm above section 4.5.1.1, but

    refers to the low alarm point.

    SET ALARMS

    SELECT LOW ALARM

  • 8/11/2019 TQ Technical Manual

    78/99

    Page 30 of 51 Filename: Technical Manual

    4.5.1.3 Set Alarms Set Latch Status

    This option allows any gas concentration alarm to be automatically

    cancelled as soon as the concentration of gas has returned to a level not

    beyond it alarm set point.

    SET ALARMS

    SELECT LATCH STATUS

    Press SELECTto enter.

    LOW HIGH

    UNLATCHED LATCHED

    Press UP / DOWN to choose the combination of LATCH requirement for

    the High and Low Alarms. When the desired latch status is displayed, the

    user must press the SELECTbutton to accept the displayed value.

    4.5.2 Sensor Menu- Set Units

    This option will allow the user to select the appropriate units corresponding

    to the gas type. The available units are as follows: PPM, %LEL, %VOL,

    and MGM. Press UP / DOWN to choose which units are required followed

    by the SELECTButton.

    SET UNITS

    %LEL

    4.5.3 Sensor Menu - Set Range

    This option allows the user to set the desired gas sensor range. The sensor

    range is determined by the particular sensor installed. i.e H2S would be 50

    for a 0-50 PPM sensor, 4mA = 0PPM & 20mA = 50PPM

    *-NOTE This figure does not correspond to the gas calibration levelrequired - *

  • 8/11/2019 TQ Technical Manual

    79/99

  • 8/11/2019 TQ Technical Manual

    80/99

    Page 32 of 51 Filename: Technical Manual

    4.6 Technician Sub Menu

    4.6.1 Technician Sub Menu - Set No. Of Channels

    This option allows the user to select the desired number of channels.

    TECHNICIAN MENU

    SET NO. OF CHANNELS

    SET NO. OF CHANNELS

    12

    This is set by the upor downbuttons. When the desired number of channels

    is displayed, the user must press the SELECTbutton to accept the displayed

    value.

    4.6.2 Technician Sub Menu - Set No. Of Sensors

    This option allows the user to select the desired number of sensors.

    TECHNICIAN MENU

    SET NO. OF SENSORS

    SET NO. OF SENSORS

    01

    This is set by the upor downbuttons. When the desired number of sensors

    is displayed, the user must press the SELECTbutton to accept the displayed

    value.

  • 8/11/2019 TQ Technical Manual

    81/99

    TQ Environmental Plc

    Filename: Technical Manual Page 33 of 51

    4.6.3 Technician Sub Menu - Skip Channel Number

    This performs the same function as Section 3.3.3. This option allows the

    user to skip a channel. When the SELECT button is pressed, the display

    will show SKIP MODE or NORMAL MODE to indicate to the user the

    channel status.

    TECHNICIAN MENU

    SKIP CHANNEL

    Press SELECTto enter.

    SKIP ZONE NUMBER

    CHANNEL 1

    Press UP / DOWN to choose the channel required to be skipped. When the

    desired channel is displayed, the user must press the SELECTbutton and

    SKIP MODE-CHANNEL1 will flash up on display before returning to

    TECHNICAL MENU-SET No. OF CHANNELS (SECTION 4.6.1)

    To un-skip the channel, repeat as above but NORMAL MODE-

    CHANNEL1 will flash up on display before returning to TECHNICAL

    MENU-SET No. OF CHANNELS.

    4.6.4 Technician Sub Menu - Set Purge Time

    **Please note this option is not available on the TQ4400 Pump Room

    system as there is no hardware to drive this function. Please keep the below

    setting at 00000.**

    This option allows the user to set a time period for the purge of each sample

    line.

    TECHNICIAN MENU

    SET PURGE TIME

    Press SELECTto enter.

  • 8/11/2019 TQ Technical Manual

    82/99

    Page 34 of 51 Filename: Technical Manual

    SET PURGE TIME

    00060

    This is set by the upor downbuttons. When the desired purge time is

    displayed, the user must press the SELECTbutton to accept the displayed

    value.

    4.6.5 Technician Sub Menu - Set Purge Cycle

    This option operates in conjunction with the Set Purge Time option. Set

    Purge Cycle is the number of complete cycles of all sample lines before a

    purge is processed. Purge may be turned off by setting Purge Cycle to 0.

    **Please note this option is not available on the TQ4400 Pump Room

    system as there is no hardware to drive this function. Please keep the below

    setting at 00000.**

    SET PURGE CYCLE

    00

    This is set by the upor downbuttons. When the desired number of cycles is

    displayed, the user must press the SELECTbutton to accept the displayed

    value.

    4.6.6 Technician Sub Menu - Calibrate Sensor

    From the technician sub menu the user should use the up and down keys

    until the CALIBRATE SENSOR option is displayed. The user should then

    use the SELECTbutton to enter calibration mode.

    TECHNICIAN MENU

    CALIBRATE SENSOR

    This option will allow the user to calibrate a particular sensor. The user is

    prompted to select a sensor. Use the up and down keys until the sensor to

    be calibrated is displayed then pressSELECTbutton to calibrate the sensor.

  • 8/11/2019 TQ Technical Manual

    83/99

    TQ Environmental Plc

    Filename: Technical Manual Page 35 of 51

    * NOTE The system does not zero the sensor, it assumes sensor zero to

    be 4mA and there is not adjustment in this Menu. If a sensor is not 4mA

    with Zero gas then the sensor would be assumed faulty.- *

    SELECT SENSOR

    FLAMMABLE

    With the correct sensor selected the 1stsample solenoid will open and user

    should apply calibration gas to the sensor via the calibration port or 3 way

    valve or direct into the sensor head. (Oxygen Sensors usually require a

    normal clean sample and dont require the next 3 steps)

    i) Apply gas to the calibration port or to the port on the provided 3 way

    valve.

    ii) Turn on the gas bottle. Gas should be regulated to between 1 and 2 LPM.

    iii)Turn the 3 way Valve handle 180o.

    The gas concentration on the LCD will start to change after a few seconds.

    If the concentration does not move then the sensor may need replacement.

    Test electrically by placing voltmeter positive probe on clear (GD129) or

    yellow (TQ122) wire from sensor and negative probe on Zero volts any

    black wire. 0.88-0.91VDC will be a zero reading for the sensor and this willrise up to 4.8volts for the full range of the sensor, typically with respect to

    4-20mA.

    When gas concentration reading stops changing e.g. when the gas

    concentration reading has settled, accept the reading by pressing the

    SELECTbutton.

    * NOTE When calibrating oxygen at 21% and a normal sample is used

    for calibration please wait at least 60 seconds, as the sensor will usually

    initially show over 25% and will take time to adjust for pressure differences

    when the 1stsample solenoid opens.

    SELECT TO ACCEPT

    00047

    When SELECT VALUE is displayed the user should use the UP / DOWNkeys to adjust the output reading displayed when the current gas

  • 8/11/2019 TQ Technical Manual

    84/99

    Page 36 of 51 Filename: Technical Manual

    concentration is present at the sensor and press the SELECT button to

    accept the value. These values will then be scaled and stored in the

    NVRAM for future reference.

    SELECT VALUE

    00050

    * - NOTE - If the user enters the Calibrate Sensor Menu again for the same

    sensor then the system will always display its original default calibration

    setting, not the new value recently adjusted. - *

    H2S sensors can take a very long time to return to zero, this is due to the

    gas sticking to the lining of the system pipe work. If system shows 1 2

    PPM please allow a few days for it to fully return to zero.

    4.6.7 Technician Sub Menu - Clear Calibration

    This option allows the user to clear all calibration data from the NVRAM

    and in doing so sets all sensors to default calibration.

    Press SELECTto clear calibration.

    TECHNICIAN MENU

    CLEAR CALIBRATION

  • 8/11/2019 TQ Technical Manual

    85/99

    TQ Environmental Plc

    Filename: Technical Manual Page 37 of 51

    4.7 Sensor Menu

    T Q

    E n v

    i r o n m e

    n t a

    l

    C O

    NT

    R O L R

    e v

    . 1

    . 5

    T R A

    N F E R I N G

    S Y

    S T E M

    . . . .

    M E N

    U

    P A R

    A M E T E R S

    M E N U

    T E C H N

    I C A L M O D

    E

    M E N U

    E X I T M E N U

    MENU

    SELECT

    DOW

    N

    UP

    DOW

    N

    UP

    SELE

    CT

    SELECT

    TOREB

    OOT

    SY

    STEM

    EIT

    HER

    POWER

    DOW

    N

    TH

    ENUPA

    GA

    INAT

    MA

    INBRE

    AKER

    OR

    PR

    ESS

    PU

    SHHA

    RDRE

    SET

    BU

    TT

    ONONCAR

    DAS

    SH

    OWN

    PRE

    SSANDHO

    LDMENU

    BU

    TTONONT

    HISSCRE

    EN

    SEE

    PAGE

    36

    SEE

    PAG

    E35

  • 8/11/2019 TQ Technical Manual

    86/99

  • 8/11/2019 TQ Technical Manual

    87/99

    TQ Environmental Plc

    Filename: Technical Manual Page 39 of 51

    MAINMEN

    U

    TECHNICIANMODE

    TECHNICIA

    NM

    ENU

    SETNOOFCH

    ANNELS

    TEC

    HNICIAN

    MEN

    U

    SETN

    OOFS

    ENSO

    RS

    SETNOOF

    CHANNELS

    23

    SET

    NOOFSENS

    ORS

    04

    TECHNICIAN

    MENU

    SKIPCHANN

    EL

    SKIPCHAN

    NEL

    FPTANK

    FPTANK

    SKIPMODE

    FP

    TANK

    NORMALMO

    DE

    TE

    CHNICIAN

    ME

    NU

    SET

    PURGETIM

    E

    SE

    TPURGETI M

    E

    00

    020

    TECHN

    ICIAN

    MENU

    SETPURG

    EC

    YCLE

    SETPU

    RGECYCLE

    00010

    TEC

    HNICIAN

    ME

    NU

    CALIB

    RATES

    ENSO

    R

    SEL

    ECTSENSOR

    FLAM

    MABLE

    SEL

    ECTTOACC

    EPT

    00028

    DA

    TAACCEPT

    ED

    00028

    TECHNIC

    IAN

    MENU

    CLEARCA

    LIB

    RATION

    TE

    CHNICIAN

    MENU

    EX

    ITMENU

    SELECTS

    ENSOR

    H2S

    SELECTT

    OACCEPT

    00015

    SEL

    ECTSENSOR

    OX

    YGEN

    SEL

    ECTTOACC

    EPT

    00

    027

    S E L

    E C T

    D O W

    N

    U P

    S E L

    E C T

    D O W N

    U P

    D O W

    N

    U P

    D O W N

    U P

    D O

    W N

    U P

    S E L E C T

    S E L

    E C T

    S E L E C T

    S E L E C T

    S E L E C T

    S E

    L E C T

    S E L E C T

    S E L

    E C T

    S E L

    E C T

    S E L E C T

    SEL

    ECTVALU

    E

    00050

    P R E S S

    U P / D O W N

    T O C O

    R R E C T

    C O N C E N

    T R A T I O N

    T H E N S E L

    E C T

    I N S E

    R T S P A N G A

    S &

    W A

    I T 3 0 S E C O N

    D S

    O R S O

    F O R R E A D I N G

    T O S

    T A B A L I S E

    DATAA

    CCEPTED

    00023

    S EL

    E C T

    SELECTV

    ALU

    E

    00025

    P R E S S U P / D O

    W N

    T O C O R R E C T

    C O

    N C E N T R A T

    I O N

    TH

    E N S E L E C T

    I N S E R T

    S P A N G A S &

    W A I T 6 0

    S E C O N D S

    O R S O F O

    R R E A D I N G

    T O S T A B A

    L I S E

    * I M

    P O R T A N T *

    W A I T

    3 0 S E C O N D

    S

    O R S O

    F O R R E