    Differential pressure control valve

    CIM 767

    Description

    Cim 767 are designed for automatic control

    of differential pressure (DPCV) in order to

    maintain constant differential pressure

    between two points of the installation. The

    flow rate of each branch of a circuit may

    change according to temperature

    requirements. Since flow rates depend on

    p, the main feature of Cim 767 is to

    maintain constant the nominal flow rate

    through open terminal units, regardless

    partial or full closing of them. Cim 767 is

    suitable for heating and cooling installations,

    assuring a good modulating control and

    reducing the noise risks coming from two-ways control valves, when high p values might be present in the

    installation. Cim 767 is normally coupled with a partner balancing valve placed on feed line, enabling the

    flow regulation.

    Cim 767differential pressure control valve is made of CR Corrosion Resistant brass with female-female

    threads according to ISO 228 standard and it is suitable for working pressure up to 16 bar, within the working

    temperature range of -10C and +120C.

    They are manufactured in sizes from DN 15 up to DN 50 and work properly up to a maximum differential

    pressure of 400 KPa. The maximum flow rate is 15 m3/h.

    Picture 1

  • 7/27/2019 Technical Leaflet Cim 767

    2/13

    Page 2 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    The main features of Cim 767are as follows:

    Keeping of selected p at the ends of the circuit, by operating on screw of the handle of the valve with

    Allen key.

    Differential pressure control at the ends of the valve, using a p measuring instrument connected tobinder points.

    Noise clearance when installation is in overpressure conditions.

    Reduction of balancing costs, improved energy saving and high environmental comfort.

    Easy flushing procedure thanks to quick and simple removal of differential pressure control cartridge,

    placed inside valve body.

    Reduced installation dimensions thanks to compact valve construction, which does not require inlet and

    outlet straight pipelines to stabilize the flow.

    Installation

    Before installation ofCim 767, check that inside the valve and the pipes there are no foreign matters which

    might damage the tightness of the valve.

    Burr pipe connections after having threaded them and distribute the sealing material on pipe threads only

    and not on valve threads.

    Make sure that required flow rate is within operating range of the valve. Cim 767 shall be installed on the

    return line either on horizontal or vertical position, but following the arrow direction casted on valve body,

    which shall be the same as the flow one. Cim 767 is coupled with partner valve Cim 787DP, installed on

    feed line by a copper capillary pipe.

    For assembly purpose, use a spanner, not a pipe

    wrench, by applying necessary working torque

    only on the valve end nearest to the pipe. This

    helps get a firmer grip and avoids potential

    damages to valve body. Make sure that pipe

    threading length is not longer than valve threads.

    After DPC cartridge removal, it is possible to flush

    the system branch where the valve is installed;

    when flushing process is over, reposition the DPC

    control cartridge.

    Cim 787DP

    Cim 767

    Picture 2

  • 7/27/2019 Technical Leaflet Cim 767

    3/13

    Page 3 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    Valve regulation

    p regulation ofCim 767 valve (see picture 3) is carried out by Allen key in 4 mm.

    The relation between flow rate, p of feed line and return line and screwing turns of regulating Allen screw

    are given by the tables stated on following pages (see Graphs and Tables).

    p increase and decrease is reached by turning clockwise or anticlockwise Allen screw respectively (see

    picture 3).

    During regulation of differential pressure, the valve

    shall be set to minimum value to proceed with turns

    numbering; after that, the valve shall be regulated

    according to tables.

    p of the system is measured through differential

    manometer Cim 726 with the two sensors, red and

    blue, which are inserted in binder points PF- and P+

    respectively (see picture 4).

    Flow rate of the system is regulated through a

    partner balancing valve Cim 787DP, by

    measuring the difference in pressure between

    points PF+ and PF- and referring to the graphs

    ofCim 787 valve.

    Flow rate drop ofCim 767 valve under service

    is shown when the two sensors of measuring

    device are inserted in the binder points of the

    said valve.

    Maintenance

    As a rule, the balancing valve does not need

    any maintenance. In case of replacement or need of disassembling of some components of the valve, f.i. for

    flushing the cartridge of differential pressure, make sure that the installation is not under service or pressure.

    Picture 3

    Picture 4

  • 7/27/2019 Technical Leaflet Cim 767

    4/13

    Page 4 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    The following table shows the dimensions of full range of valves Cim 767.

    DN A B C CH

    1/2 55 79 95,5 27

    3/4 55 79 96,5 32

    1 75 91 132 39

    11/4 75 91 132 47

    11/2 87 97 144,5 54

    2 90 106 155 68

    Picture 5

  • 7/27/2019 Technical Leaflet Cim 767

    5/13

    Page 5 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    Graphs and Tables

    CIM 767 - 1/2 DN 15 Lowp = 530 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa)l/h l/s gpm*

    Kvs

    5 30 50 600 0,014 0,167 0,22 2,65 3,6

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    6/13

    Page 6 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 3/4 DN 20 Lowp = 530 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATE

    Control p range(KPa)

    l/h l/s gpm*

    Kvs

    5 30 100 1000 0,028 0,278 0,44 4,41 4,0

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    7/13

    Page 7 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 1 DN 25 Lowp = 530 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa)l/h l/s gpm*

    Kvs

    5 30 600 2500 0,167 0,694 2,65 11,02 9,5

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    8/13

    Page 8 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 1/2 DN 15 High p = 2060 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 60 100 1200 0,028 0,333 0,44 5,29 3,6

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    9/13

    Page 9 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 3/4 DN 20 High p = 2060 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 60 150 2000 0,042 0,556 0,66 8,82 4,0

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    10/13

    Page 10 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 1 DN 25 High p = 2060 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 60 700 4200 0,194 1,167 3,09 18,52 9,5

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    11/13

    Page 11 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 11/4 DN 32 High p = 2080 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 80 1000 5000 0,278 1,389 4,41 22,05 11,4

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    12/13

    Page 12 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 11/2 DN 40 High p = 2080 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 80 3000 8000 0,833 2,222 13,23 35,27 16,4

    * The gpm values are corresponding to US gallon per minute.

  • 7/27/2019 Technical Leaflet Cim 767

    13/13

    Page 13 of 13

    Technical Leaflet Cim 767Revision 0

    Issue 06/2011

    CIM 767 2 DN 50 High p = 2080 KPa

    p differential pressure according to number of turns of Allen screw

    FLOW RATEControl p range

    (KPa) l/h l/s gpm*

    Kvs

    20 80 5000 15000 1,389 4,167 22,05 66,14 17,9

    * The gpm values are corresponding to US gallon per minute.