Page 1: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

TECHNICAL CATALOGUE

Fire dampers PL-10, PL-19, PL-20

Page 2: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

PL-19 PL-20

FIRE DAMPERS

Fire dampers are installed in rectangular or circular ventilation ducts at the passages through the fire compartments. In case of fire, the fire dampers close automatically, thus preventing fire from spreading through the ventilation ducts.Fire resistance: 120 min.

Types concerning the release mode:• basic: with thermal release• with electric actuator

FIRE DAMPERS

FIRE DAMPERS

PL-10-1 PL-10-2

Page 3: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS

Fire dampers Page

Fire dampers PL-10 ....................................................................................................................................................................................................................2Types.......................................................................................................................................................................................................................................3Installation...............................................................................................................................................................................................................................4Ordering key.............................................................................................................................................................................................................................8Certificate.................................................................................................................... ............................................................................................................9

01..................................................................................................................................................................................................................91-LP srepmad eriFTypes.....................................................................................................................................................................................................................................11Installation.............................................................................................................................................................................................................................12

51...........................................................................................................................................................................................................................yek gniredrOCertificate.................................................................................................................... ..........................................................................................................16

71...................................................................................................................................................................................................................02-LP srepmad eriF 81.....................................................................................................................................................................................................................................sepyT

Installation............................................................................................................................................................................................................................1922...........................................................................................................................................................................................................................yek gniredrO

Certificate..............................................................................................................................................................................................................................23

Page 4: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Fire Dampers PL-10

General

Application:Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation ducts in buildings. They are installed in openings of constructions or on passages through partition compartments with limited fire resistance (fire walls, partition walls).

Description:The fire dampers PL-10 consist of a blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C (or higher for special requirements). A silicon profile sealant makes the fire dampers PL-10 resistant also to cold smoke thus improving the fire safety.Due to its special construction a blade is 25 mm thick, which improves energy efficiency of the fire damper.

Fire resistance and classification:

Fire damper's basic fire resistance is EI 120-S.

Types of fire dampers

PL-10-1 circular fire dampers only with manual-spring actuators for spiral ductsPL-10-2 circular fire dampers with manual-spring or electric actuators for spiral

ducts

Nominal dimensions PL-10

Nominal diameters DN (mm)

Standard lengths of PL-10The standard length of PL-10-1... L = 170 mm.The standard length of PL-10-2... L = 300 mm.

Installation*:

In rigid walls, the minimum thickness 100 mm In light walls, the minimum thickness 100 mmIn light walls, the minimum thickness 125 mm In rigid ceiling plates, the minimum thickness 150 mm

* Check for installation details in the installation manual

DN (mm) 100 125 150 160 180 200

PL-10-1

PL-10-2

FIRE DAMPERS PL-10

2

Page 5: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

PL-10-1/A

170

DN

123 45

85

25

PL-10-2/A8

123 45 6

7300

85DNcca 35

PL-10-2/E..

300

84,76

max 85

123

4

5

DN

24,9

9

Electric actuators type PL-10-2/E...

1. Housing made of galvanised steel sheet2. Blade made of calcium silicate and intumescent sealant3. Thermal fuse4. Silicone gasket for cold smoke5. Electric actuator

Duct connection PL-10

MWithout designation – insertion type

M – sleeve type (a duct is inserted into a fire damper)

(a fire damper is inserted into a duct), standard type

Manual-spring actuator type PL-10-2/A8

1. Housing made of galvanised steel sheet2. Blade made of calcium silicate and intumescent sealant3. Thermal release link with melting point at 70°C (optional 120°C).4. Silicone gasket for cold smoke5. Spring6. Release handle7. Revision cover

Types of actuators

Manual-spring actuator type PL-10-1/A

1. Housing made of galvanised steel sheet2. Blade made of calcium silicate and intumescent sealant3. Thermal release link with melting point at 70°C (optional 120°C).4. Silicone gasket for cold smoke5. Spring

FIRE DAMPERS PL-10 TYPES

3

Page 6: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Installation

The fire dampers should be installed according to the designer's project for the fire safety. A fire damper should not be statically stressed by a building's structure.

During the installation the wooden supports should be used (see the picture).

When mounting, a removable duct extension should be installed to carry out control inside a fire damper!

Please, follow the detailed instructions for installation and use - as available by our sales employees.

Installation in a rigid wall

A fire damper should be installed in a rigid wall of the minumum thickness W = 100 mm into a circular or rectangular opening, gap min. s = 50 mm. A wall can be made of concrete, bricks or aerated bricks. Filler is either concrete or mortar. When mounting, the installation dimension K = 35 mm should be taken into account. For a thicker wall an extension should be added since the fire damper does not get through the wall!A position of an actuator is optional in one or the other fire compartment.

Use of wooden supports during the installation

Installation in a rigid wall PL-10-1

DN

K

DN+2sW

1

2

s

3

Installation in a rigid wall PL-10-2

12

DN

DN+2s

3

W

s

K

Legend:

1. Wall (fire resistant)2. Filler3. Fire damper PL-10-1

1. Wall (fire resistant)2. Filler3. Fire damper PL-10-2

W Wall thickness (mm)35 (mm)Length of a fire damper (mm) Nominal diameter of a fire damper (mm)Gap (mm)

KLDNs

Legend:

W Wall thickness (mm)K 165 (mm)L Length of a fire damper (mm)

Nominal diameter of a fire damper (mm)Gap (mm)

DNs

4

FIRE DAMPERS PL-10 TYPES

Page 7: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Installation in a rigid ceiling plate

A fire damper should be installed in a rigid ceiling plate of the minimum thickness W = 150 mm, gap s = 50 mm. A ceiling plate is made of concrete. Filler can be either concrete or mortar. When mounting, the installation dimension K = 165 mm should be taken into account. For thicker wall an extension should be added since a fire damper does not get through the wall!

A position of an actuator is optional at the bottom or at the top in one or the other fire compartment.

Installation in a rigid ceiling plate PL-10-1

K1 2

s

34

W

Installation in a rigid ceiling plate PL-10-2

1 2

s

34

WK

Legend:

1. Ceiling plate (fire resistant)2. Filler3. Fire damper PL-10-14. Extension (if required)

W Ceiling plate thickness (mm)35 (mm)Nominal diameter of a fire damper (mm)Gap (mm)

KDNs

Legend:

1. Ceiling plate (fire resistant )2. Filler3. Fire damper PL-10-24. Extension (if required)

W Ceiling plate thickness (mm)165 (mm)Length of a fire damper (mm) Nominal diameter of a fire damper (mm)Gap (mm)

KLDNs

FIRE DAMPERS PL-10 INSTALLATION

5

Page 8: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Installation fixed in a light wall

W

DN+2s

s

K

DN+2

s

a=< 625mm

CW ProfileCW Profile

UW

Profile

UW Profile

UW Profile

UW/CW Profile

7 6

5

2

34

1

2

Profile sub construction

8

8

Direct installation in a light wall

123

4

CW ProfilCW Profil

UW Profil

UW Profil

CW/UW

Profil

UW Profil

Wa=<625 mm

DN

K

Legend:

1. Fire damper PL-102. Filler 2 x 50 mm rock wool plates of density > 130 kg/m3, melting point > 1000°C3. Wall (fire resistant), fire resistant plasterboard plates 2 x 12,5 mm on each side (2+2 plates)4. Rock wool 50 mm density > 50 kg/m3

5. Sleeve OPL-106. Steel bars of diameter 12 mm7. Intumescent coating Intumex CSP-L, 2 layers8. Flexible duct compensator

A fire damper should be installed in a light wall plate of the minimum thickness W = 100 mm, gap min. s = 100 mm. Fixing in a wall and using of flexible duct compensators required. When mounting, the installation dimension K = 165 mm at the standard length of a fire damper L = 400 mm should be taken into account.

A position of an actuator is optional in one or the other fire compartment.

Legend:

1. Fire damper PL-102. Rock wool 50 mm density > 50 kg/m3

3. Wall (fire resistant), fire resistant plasterboard plates 2 x 12,5 mm on each side (2+2 plates)4. All gaps should be sealed with fire resistant putty

A fire damper should be installed in a light wall of the minimum thickness W = 125 mm. When mounting, the installation dimension K = 150 mm at the standard length of a fire damper L = 300 mm should be taken into account. A position of an actuator is optional, in one or the other fire compartment

6

FIRE DAMPERS PL-10 INSTALLATION

Page 9: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Permitted installation positions of the fire dampers

Installation in a wall without connection ducts

234 5 124 4

4

31

10

10 22

22

When mounting, a blade axis and the actuator position are oriented optionally from horizontal to vertical position.

Legend:

1. Fire damper PL-102. Partition wall (100, 125 mm , rigid or lightweight – see ways of installation for each type) or a concrete ceiling 150 mm3. Optional extension (required for DN > 180)4. Protection grille PG5. Air duct

A fire damper can be installed in a fire resistant partition wall without connection ducts or with a duct on one side and a protection grille on a free wall.

Maintenance and inspection:

The fire dampers should be maintained and inspected twice a year. If two successive inspections show no malfunctions, it is sufficient to perform further examinations only once a year. Maintenance and inspection should only be carried out by authorized service.

WARNINGA standard type of the fire dampers PL-10 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation devices which exhaust mixture of air and explosive gases. In such cases, special explosion-proof fire dampers should be installed. Neither are the standard fire dampers PL-10 suitable for dusty ambients.

7

FIRE DAMPERS PL-10 INSTALLATION

Page 10: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Pressure drop diagram for PL-10

100

50

25

16

10

6

4

2

1

200 40010050301064 208 15

DN =

100

DN =

200

75

DN =

125

DN =

150

DN =

160

DN =

180

v = 5 m/s

l/s

Pa

v = 3 m/s

t

V

20 50 1007030 200 400 700 1200

m /h3

300150

DN

OPL-10

M

T1T2

T12TS DO

E15E16E19

AA8

PL-10-1PL-10-2

Dimensions:Nominal diameter in mm

Installation accessories:Without designation – no accessoriesfixing clamp for installation – light installation, light wall*

Connection:Without designation – standard insertion type (a fire damper inserted into a duct)Sleeve type (a duct inserted into a fire damper)

Accessories:Limit switch “closed” (only for PL-10-2)Limit switch “open” (only for PL-10-2)Limit switch (2 pcs) “closed”,” open” (only for PL-10-2)Limit switch “closed”, max. 24 V- safety low voltage (SELV)Junction box (option for electric actuators, designation E…)

Actuators:Electric actuator Belimo BLF-24 T, (only for PL-10-2)Electric actuator Belimo BLF-230 T, (only for PL-10-2)Electric actuator Belimo BLF 24-T-ST + BKN 230-24, (only for PL-10-2)Manual actuator - basic, with thermal link, 70°C; (only for PL-0-1)Manual actuator - basic, with thermal link, 70°C; (only for PL-0-2)

Types of the fire dampers:L = 170 mm, classification EI 120-SL = 300 mm, classification EI 120-S

Electric actuators variants E…. are fitted with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature of theelectric actuator is 72°C.For increased temperatures in the ducts the non-standard release temperatures are available, 120°C for manual actuators and 95°C for electric actuators respectively.Additional protection grilles PG and adjusting are available upon request.*Check the required accessories and material, concerning the type of installation - for details sees the manual for installation and use

Ordering key :

8

FIRE DAMPERS PL-10 ORDERING KEY

Page 11: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-10 CERTIFICATE

9

Text for a project list:

Circular fire dampers for separation of fire compartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance EI 120S.Construction characteristics: a fire damper PL-10 consists of a housing made of galvanized steel sheet and blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C. A silicon profile gasket between the housing and blade makes the fire damper also resistant to cold smoke. Installed in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's instructions.

Manufacturer:Type:

Ordering example:

Manufacturer:Type:Quantity:____ pcs

Page 12: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-19

FIRE DAMPERS PL-19

General

Application:Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation ducts in buildings. They are installed in openings of constructions or on passages through partition compartments with limited fire resistance (fire walls, partition walls).

e

Description:A fire damper PL-19 consists of a blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C (or higher for special requirements). A housing of galvanised steel sheet is separated by a calcium silicate heat insulated frame. A silicon profile gasket makes the fire damper PL-19 resistant also to cold smoke, thus improving fire safety. Due to its special construction the blade is 30 mm thick which improves energy efficiency of a fire damper.

Fire resistance and classification:

Fire damper's basic fire resistance is EI 120-S.

Types of the fire dampers concerning the installation into the ducts

PL-19 rectangular fire damper with flange – for installation into the rectangular ducts

Nominal dimensions PL-19

Max. dimensions B x H=1500 x 800 mmMin. dimensions B x H=150 x 150 mmStandard length Lmin = 400 mmAny dimension B x H within given dimension range available upon request.

Installation*:

Within rigid walls, the minimum thickness 100 mm Within light walls, the minimum thickness 100 mm Within rigid ceiling plates, the minimum thickness 150 mm

* Check for installation details in the installation manual

PL-19

PL-19- Dimensions

B

H

min. 200 min. 200

L

32,5

32,5

30

10

Page 13: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-19 TYPES

PL-19/A2

1 2

3

9

6

5

78

A2

A2

3

4

9

PL-19/E...

1 2

94

3

3

5 9

Detail A Detail B

A B A B

10.5

10

32.5

R6

R4.75

R6

12.4

12.4

1645°

R4.75

32.5

300 300

(n-1) x 300

n = 1,3

(n-1) x 300

n = 2,4

Flange connection dimensions

Dim. H or B (mm) No. of holes - nup to 399 0400 - 699 1700 - 849 2

850 - 1339 31400 4

Electric actuators type PL-19/E...

1. Housing made of galvanised steel sheet, separated by calcium silicate-heat insulation frame2. Blade made of calcium silicate and intumescent sealant3. Thermal fuse4. Silicone gasket for cold smoke5. Electric actuator6. Revision cover

Types of actuators

Manual-spring actuator type PL-19/A2

1. Housing made of galvanised steel sheet, separated by calcium silicate-heat insulation frame2. Blade made of calcium silicate and intumescent sealant 3. A2 – thermal release link with melting point at 70°C (optional 120°C).4. Silicone gasket for cold smoke5. Spring6. Inspection release handle7. Limit switch T1 - closed8. Limit switch T2 - open 9. Revision cover

11

Page 14: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-19 INSTALLATION

Installation

The fire dampers should be installed according to the designer's project of the fire safety. A fire damper should not be statically stressed by a building's structure.

During the installation the wooden supports should be used (see the picture).

Follow the detailed instructions for installation and use - as available by our sales employees.

A fire damper should be installed in a wall of the minumum thickness W = 100 mm into a rectangular opening, gap s = 100 mm. A wall can be made of concrete, bricks or aerated bricks. Filler is either concrete or mortar. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

Use of wooden supports during the installation

Installation in a rigid wall

L

H / B

W

K1

2

3

s

Installation in a rigid ceiling plate

L

H / B

W

K

1 2 3s

Legend:

1. Fire damper PL-192. Filler3. Wall (fire resistant)

W Wall plate thickness (mm)Distance from a wall on the actuator’s side (mm)Length of a fire damper (mm)

KLB or H Nominal width or height of a fire damper (mm)s Gap (mm)

A fire damper should be installed in a wall of the minumum thickness W = 100 mm into a rectangular opening, gap s = 100 mm. A wall can be made of concrete, bricks or aerated bricks. Filler is either concrete or mortar. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

Legend:

1. Fire damper PL-192. Filler3. Ceiling plate (fire resistant)

W Ceiling plate thickness (mm)Distance from the ceiling on the actuator’s side (mm)Length of a fire damper (mm)

KLB or H Nominal width or height of a fire damper (mm)s Gap (mm)

12

Page 15: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Installation in a light wall and fixed in a ceiling

CW Profile

UW Profile

UW Profile

CW Profile

H +

2s

B + 2s

CW Profile

UW / CW Profile

CW Profile

s

a=<625 a=<625 a=<625

W

K1

26

34

5

77

88 99

max. 1000mmmax. 1000mm

A

27

7

3 4

A

Profile sub construction

Profile sub construction

Legend:

1. Fire damper PL-192. Filler 2 x 50 mm rock wool plates of density > 130 kg/m3, melting point > 1000°C.3. Wall (fire resistant, type W112), fire resistant plasterboard plates 2 x 12,5 mm on each side (2+2 plates)4. Rock wool of thickness 50 mm, density > 50 kg/m3

5. Sleeve LWB-19 6. Steel bars of diameter 12 mm – fixed in a ceiling7. Intumescent coating Intumex CSP-L, 2 layers8. Flexible duct compensator9. Air duct

A fire damper should be installed in a lightweight wall of the minimum thickness W = 100 mm, gap min. s = 100 mm. Fixed in a ceiling and use of duct compensators required. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

Direct installation in a light wall fixed in a wall, with a cover frame

CW Profile

UW Profile

UW Profile

CW Profile

H +

2s

B + 2s

CW Profile

UW / CW Profile

CW Profile

a=<625 a=<625 a=<625

W

3

1

2

6

5

7K

s

8

4

6

752

43 A

A

min

. 80

mm

Legend:

1. Fire damper PL-192. Filler 2 x 50 mm rock wool plates of density > 130 kg/m3, melting point > 1000°C3. Wall (fire resistant, type W112), fire resistant plasterboard plates on each side 2 x 12,5 mm (2+2 plates)4. Rock wool 50 mm, density > 50 kg/m3

5. Clip angles PKL-19 6. Cover frame – fire resistant plasterboard plates 2 x 12,5 mm, on each side (2+2 plates)7. Intumescent coating Intumex CSP-L, 2 layers (100 mm on a fire damper, 40 mm on a cover frame)8. Air duct

A fire damper should be installed in a light wall plate of the minimum thickness W = 100 mm, gap min. s = 100 mm. Fixed in a profile construction of a wall and use of a cover frame required. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

13

FIRE DAMPERS PL-19 INSTALLATION

Page 16: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

When mounting, a blade axis and the actuator position are oriented optionally from horizontal to vertical position.

A fire damper can be installed in a fire resistant partition wall without connection ducts or with a duct on one side and a protection grille on a free wall.

Maintenance and inspection:The fire dampers should be maintained and inspected twice a year. If two successive inspections show no malfunctions, it is sufficient to perform further examinations only once a year. Maintenance and inspection must only be carried out by authorized service.

WARNINGStandard fire dampers PL-19 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation devices which exhaust mixture of air and explosive gases. In such cases special explosion-proof fire dampers should be installed. Neither are the standard fire dampers PL-19 suitable for dusty ambients.

Permitted installation positions of the fire dampers

B

H B

H

B

H

B

H

Installation in a wall without connection ducts

1234 5 1234

3 4

4

10

10 22

22

Legend:

1. Fire damper PL-192. Partition wall (100 mm, rigid or light – see ways of installation for each type) or a concrete ceiling 150 mm3. Optional extension (required for H > L)4. Protection grille PG5. Air duct

14

FIRE DAMPERS PL-19 INSTALLATION

Page 17: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

BxH

LWB-19PKL-19

T1T2

T12DO

E5E6E9

E15E16E19A2

PL-19

Dimensions:Nominal width and height in mm

Installation accessories:Brackets for installation – installation in a light wall*Brackets for installation – direct installation, light wall*

Accessories:Limit switch “closed” Limit switch “open” Limit switch (2 pcs) “closed”,“open”Junction box (option for electrical actuators, designation E...)

Actuators:Electrical actuator Belimo BF 24-T Electrical actuator Belimo BF 230-T Electrical actuator Belimo BF 24-T-ST + BKN 230-24 Electrical actuator Belimo BLF-24 T **Electrical actuator Belimo BLF-230 T **Electrical actuator Belimo BLF 24-T-ST + BKN 230-24 **Spring/manual actuator – advanced – thermal release link 70˚C - thermal release link replaceable from the outside

Types of the fire dampers:rectangular fire damper with a flange – classification EI 120-S

Electric actuators variants E…. are fitted with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature of the electric actuator is 72°C.For increased temperatures in the ducts the non-standard release temperatures are available, 120°C for manual actuators and 95°C for electric actuators respectively.Additional protection grilles PG and adjusting are available upon request.*Check the required accessories and material concerning the type of installation - for details sees the manual for installation and use

Ordering key:

** Application range for actuators E15, E16, E19

BxH

150

200

250

300

350

400

450

500

550

600

650

700

750

800

850

900

950

150 200 250 300 350 400 450 500 550

1000

15

FIRE DAMPERS PL-19 ORDERING KEY

Page 18: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-19 CERTIFICATE

16

Text for a project list:

The rectangular fire dampers for separation of firecompartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance EI 120-S.Construction characteristics: a fire damper PL-19 consists of a housing made of galvanized steel sheet and blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C. A housing of galvanised steel sheet is separated by a calcium silicate heat insulated frame. A silicon profile gasket makes the fire dampers PL-19 also resistant to cold smokeInstallation in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's instructions.

Manufacturer:Type:

Ordering example:

Manufacturer:Type:Quantity:___pcs

Page 19: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-20

FIRE DAMPERS PL-20

General

Application:Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation ducts in buildings. They are installed in openings of constructions or on passages through partition compartments with limited fire resistance (fire walls, partition walls).

Description:The fire dampers PL-20 consist of a blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C (or higher for special requirements). A housing of galvanised steel sheet is separated by calcium silicate heat insulated frame. A silicon profile gasket makes fire dampers PL-20 resistant also to cold smoke, thus improving fire safety. Due to its special construction the blade is 30 mm thick, which improves airflow efficiency.

Fire resistance and classification:

Fire damper's basic fire resistance is EI 120-S.

Types of the fire dampers concerning installation into the ducts

PL-20-F - circular fire damper with a flange- circular fire damper for spiral ductsPL-20-S

Nominal dimensions PL-20

PL-20-S DN= 100*, 125*, 150,160, 180, 200, 224, 250, 280, 300, 315, 350, 355, 400, 500 mm* Reduced from DN = 150 mm

PL-20-F DN=315, 400, 450, 500, 630 mmFlange according to DIN 24154 range part 1 (edition 06/90) or EN 12220

Standard length PL-20; Lmin = 400 mm

Installation*:

Within rigid walls, the minimum thickness 100 mm Within light walls, the minimum thickness 100 mm Within rigid ceiling plates, the minimum thickness 150 mm

* Check for installation details in the installation manual

PL-20

PL-20 - Dimensions

PL-20 Dimensions of reduced variants DN 100 and DN 125

A

L

ØDN

min. 200 min. 200

30

PL-20-F...

PL-20-S...

40

400

DN 1

00 (D

N 12

5)

20

495 5

DN 1

50

17

Page 20: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

FIRE DAMPERS PL-20 INSTALLATION

PL-20/../A2

1 2

3

9

6

5

78

A

A2

3

4

PL-20/…/E..

A

1 25

3

9

4

Electric actuators type PL-20/.../E...

1. Housing made of galvanised steel sheet separated by calcium silicate -heat insulation frame2. Blade made of calcium silicate and intumescent sealant3. Thermal fuse4. Silicone gasket for cold smoke5. Electric actuator9. Revision cover

Types of actuators

Manual-spring actuators type PL-20/.../ A2

1. Housing made of galvanised steel sheet, separated by calcium silicate-heat insulation frame2. Blade made of calcium silicate and intumescent sealant 3. A2 – thermal release link, melting point at 70°C (optional 120°C).4. Silicone gasket for cold smoke5. Spring6. Release handle7. Limit switch T1 - closed8. Limit switch T2 - open 9. Revision cover

Installation

The fire dampers should be installed according to the designer's project for the fire safety. A fire damper should not be statically stressed by a building's structure.

During the installation the wooden supports should be used (see the picture).

Follow the detailed instructions for installation and use - as available by our sales employees.

Use of wooden supports during the installation

18

Page 21: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

A fire damper should be installed in a rigid wall of the minimun thickness W = 100 mm into a rectangular opening, gap s = 100 mm. A wall can be made of concrete, bricks or aerated bricks. Filler is either conrete or mortar. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

Installation in a rigid wall

L

DN

W

K1

2

3

s

Installation in a rigid ceiling plate

L

DN

W

K

1 2 3

s

Legend:

1. Fire damper PL-202. Filler3. Wall (fire resistant)

W Wall thickness (mm)Distance from a wall on the actuator’s side (mm)Length of a fire damper (mm) Nominal diameter of a fire damper (mm)Gap (mm)

KLDNs

Legend:

1. Fire damper PL-202. Filler3. Ceiling plate (fire resistant)

W Ceiling thickness (mm)Distance from a ceiling on the actuator’s side (mm)Length of a fire damper (mm) Nominal diameter of a fire damper (mm)Gap (mm)

KLDNs

A fire damper should be installed in a rigid ceiling plate of the minimum thickness W = 150 mm, gap s = 100 mm. A ceiling plate is made of concrete.Filler can be either concrete or mortar. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional in one or the other fire compartment.

19

FIRE DAMPERS PL-20 INSTALLATION

Page 22: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Installation in a light wall and fixed in a ceiling

UW Profile

UW Profile

CW Profile

UW / CW

Profile

DN + 2s

DN +

2s

W

3

1

2

6

5

CW Profile

a=<625 mm

CW Profile

a=<625 mm

77

K s

max 1000 mm max 1000 mm

8 9

Profile sub construction

4

7 7234

2

Legend:

1. Fire damper PL-202. Filler 2 x 50 mm rock wool plates of density > 130 kg/m3, melting point > 1000°C3. Wall (fire resistant, type W112), fire resistant plasterboard plates 2 x 12,5 mm on each side (2+2 plates)4. Rock wool thickness 50 mm, density > 50 kg/m3

5. Sleeve OPL-20 Hidria 2 sets6. Steel bars with diameter 12 mm- fixed in a ceiling7. Intumescent coating Intumex CSP-L, 2 layers8. Flexible duct compensator9. Air duct

A fire damper should be installed in a light wall of the minimum thickness W = 100 mm, gap min. s = 100 mm. Necessery fixed in a ceiling by usingduct compensators. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional, in one or the other fire compartment.

Direct installation fixed in a light wall and with a cover frame

UW Profile

UW Profile

CW ProfileCW Profile

CW Profile

Profile sub construction

UW / CW

Profile

DN + 2s

DN +

2s

W

3

1

2

6

5

a=<625 mm a=<625 mm

7Ks

8

2

min

. 80

mm

4

A6

77

25

4

A

Legend:

1. Fire damper PL-202. Filler 2 x 50 mm rock wool plates of density > 130 kg/m3, melting point > 1000°C3. Wall (fire resistant, type W112), fire resistant plasterboard plates 2 x 12,5 mm on each side (2+2 plates)4. Rock wool 50 mm density > 50 kg/m3

5. Clip angles PKL-20 6. Cover frame – fire resistant plasterboard plates 2 x 12,5 mm, on each side (2+2 plates)7. Intumescent coating Intumex CSP-L, 2 layers, (100 mm on a blade, 40 mm on a cover frame)8. Air duct

A fire damper should be installed in a light wall of the minimum thickness W = 100 mm, gap min. s = 100 mm. Necessery fixed in a ceiling by usingduct compensators. When mounting, the installation dimension K = 145 mm at the standard length of a fire damper L = 400 mm should be taken into account.A position of an actuator is optional, in one or the other fire compartment.

20

FIRE DAMPERS PL-20 INSTALLATION

Page 23: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

When mounting, a blade axis and actuator position is oriented optionally from horizontal to vertical position.

A fire damper can be installed in a fire resistant partition wall without connection ducts or with a duct on one side and a protection grille on a free wall.

Maintenance and inspection:The fire dampers should be maintained and inspected twice a year. If two successive inspections show no errors, it is sufficient to perform further examinations only once a year. Maintenance and inspection should only be carried out by authorized service.

WARNINGA standard type of the fire dampers PL-20 are not allowed to be installed in the explosion hazardous places. Neither are they allowed to be installed in the ventilation devices which exhaust mixture of air and explosive gases. In such cases, special explosion-proof fire dampers should be installed. Neither are the standard fire dampers PL-20 suitable for dusty ambients.

Permitted installation positions of the fire dampers

Installation in a wall without connection ducts

1234 5 1234

3 4

4

10

10 22

22

Legend:

1. Fire damper PL-202. Partition wall (100 mm, rigid or light – see ways of installation for each type) or a concrete ceiling of 150 mm3. Optional extension (required for DN > L)4. Protection grille PG5. Air duct

21

FIRE DAMPERS PL-20 INSTALLATION

Page 24: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

22

FIRE DAMPERS PL-20 ORDERING KEY

DN

OPL-20PKL-20

T1T2

T12DO

E5E6E9

E15E16E19A2

PL-20-FPL-20-S

Dimensions:Nominal diameter v mm

Installation accessories:Installation clamps – lightweight installation, light wall*Brackets– direct installation, light wall*

Accessories:Limit switch “closed” Limit switch “open” Limit switch (2 pcs) “closed”,“open”Junction box (option for electric actuators, designation E…)

Actuators:Electric actuator Belimo BF 24-T Electric actuator Belimo BF 230-T Electric actuator Belimo BF 24-T-ST + BKN 230-24 Electric actuator Belimo BLF-24 T **Electric actuator Belimo BLF-230 T **Electric actuator Belimo BLF 24-T-ST + BKN 230-24 **Spring/manual actuator – advanced – thermal release link 70°C, thermal link replaceable from the outside

Types of the fire dampers:Circular fire damper with flange – classification EI 120-SCircular fire damper for spiral ducts- classification EI 120-S

Electric actuators variants E…. are equipped with limit switches, additional limit switches (T1, T2, T12) are not applicable. Standard release temperature of the electric actuator is 72°C.For increased temperatures in the ducts the non-standard release temperatures are available, 120°C for manual actuators and 95°C for electric actuators respectively.Additional protection grilles PG and adjusting are available upon request.* Check the required accessories and materials concerning the type of installation – for details see the manual for installation and application.** Electric actuators type E15, E16, E19 can be used only for the dimension range DN=150-500 mm.

Ordering key:

Page 25: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

23

FIRE DAMPERS PL-20 CERTIFICATE

Text for a project list:

The circular fire dampers for separation of fire compartments in ventilation and air conditioning systems, resistant to fire and cold smoke, fire resistance EI 120-S.Construction characteristics: the fire dampers PL-20 consist of a blade of calcium silicate, intumescent sealant and thermal release mechanism with the release temperature 70˚C A housing of galvanised steel sheet is separated by a calcium silicate heat insulated frame. A silicon profile gasket makes the fire dampers PL-20 also resistant to cold smoke.Installation in a rigid or light wall of the minimum thickness 100 mm or in a rigid ceiling plate of the minimum thickness 150 mm, according to the manufacturer's instructions.

Manufacturer:Type:

Ordering example:

Manufacturer:Type: Quantity:___pcs

Page 26: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

24

The right for technical changes reserved.

Page 27: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Production: Hidria IMP Klima d.o.o., Layout: Grafi~ni studio K, d.o.o., Print: Grafika So~a, June 2010

Page 28: TECHNICAL CATALOGUE - Hidria 10-19-20 UKR.pdf · Fire Dampers PL-10 General Application: Fire dampers prevent fire and smoke from spreading through air conditioning and ventilation

Hidria IMP Klima d.o.o.Godovi~ 1505275 Godovi~SloveniaT: +386 5 37 43 000F: +386 5 37 47 188E: klima≤hidria.comwww.hidria.com