substation design (1)

Upload: rajendraprasadnaik

Post on 10-Oct-2015

53 views

Category:

Documents


9 download

TRANSCRIPT

  • 5/20/2018 Substation Design (1)

    1/69

    The protection system is designed to limit the effects of disturbances in power

    system, which when allowed persisting, may damage the substation and interrupt the

    supply of electrical energy. It covers various types of protection used in substation for

    220/132/33 ! transmission lines such as bus bar protection relays, auto reclosing

    schemes, etc.,

    The present day electrical power system is "# i.e., electric power is generated,

    transmitted and distributed in the form of alternating current. The electric power is

    produced at the power stations which are located at favourable places, generally $uite

    away from the consumers. It is delivered to the consumers through a large networ% of

    transmission and distribution. "t many places in the line of the power, it may be desirable

    and necessary to change some characteristics of power supply. This is accomplished by

    suitable apparatus called &ubstation.

    'enerating voltage at the power station is stepped upto high voltage for

    transmission of electric power. The assembly of apparatus used for this purpose is the

    substation. &imilarly,near the consumers localities, the voltage may have to be stepped

    down to utili(ation level. This )ob is again accomplished by a suitable apparatus called

    substation. The type of e$uipment needed in the substation will depend upon the service

    re$uirement.

    1

  • 5/20/2018 Substation Design (1)

    2/69

    Introduction

    "n electrical substation is a subsidiary station of an electricity generation,

    transmission and distribution system where voltage is transformed from high to low or

    the reverse using transformers. *lectric power flows through several substations between

    generating plant and consumer changing the voltage level in several stages.

    " substation that has a step+up transformer increases the voltage with decreasing

    current, while a step+down transformer decreases the voltage with increasing the current

    for domestic and commercial distribution. The word substation comes from the daysbefore the distribution system became a grid. "t first substations were connected to only

    one power station where the generator was housed and were subsidiaries of that power

    station.

    2.2 Elements of Substation

    &ubstations generally contain one or more transformers and have switching,

    protection and control e$uipment. In a large substation, circuit brea%ers are used to

    interrupt any short+circuits or overload currents that may occur on the networ%. &maller

    distribution stations may use re+closer circuit brea%ers or fuses for protection of branch

    circuits. " typical substation will contain line termination structures, high+voltage

    switchgear, one or more power transformers, low voltage switchgear, surge protection,

    controls, grounding earthing- system, and metering. ther devices such as power factor

    correction capacitors and voltage regulators may also be located at a substation.

    &ubstations may be on the surface in fenced enclosures, underground, or located in

    special+purpose buildings.

    2

  • 5/20/2018 Substation Design (1)

    3/69

    igh+rise buildings may have indoor substations. Indoor substations are usually

    found in urban areas to reduce the noise from the transformers, to protect switchgear

    from etreme climate or pollution conditions.

    2.3 Types of Substation

    &ubstations are of three types. They are

    a- Transmission &ubstation

    b- istribution &ubstation

    c- #ollector &ubstation

    a) Transmission Substation

    " transmission substation connects two or more transmission lines. The simplest

    case is where all transmission lines have the same voltage. In such cases, the substation

    contains high+voltage switches that allow lines to be connected or isolated for fault

    clearance or maintenance. " transmission station may have transformers to convert the

    voltage from voltage level to other, voltage control devices such as capacitors, reactors or

    &tatic !" #ompensators and e$uipment such as phase shifting transformers to control

    power flow between two ad)acent power systems. The largest transmission substations

    can cover a large area several acres/hectares- with multiple voltage levels, many circuit

    brea%ers and a large amount of protection and control e$uipment voltage and current

    transformers, relays and "" systems-. 4odern substations may be implementedusing International &tandards such as I*#51670.

    3

  • 5/20/2018 Substation Design (1)

    4/69

    b) Distribution Substation

    " distribution substation transfers power from the transmission system to the

    distribution system of an area. It is uneconomical to directly connect electricity

    consumers to the high+voltage main transmission networ%, unless they use large amounts

    of power. &o the distribution station reduces voltage to a value suitable for local

    distribution. The input for a distribution substation is typically at least two transmission

    or sub transmission lines. Input voltage may be, for eample, 220! or whatever is

    common in the area. istribution voltages are typically medium voltage, between 33 and

    55 %! depending on the si(e of the area served and the practices of the local utility.

    8esides changing the voltage, the )ob of the distribution substation is to isolate

    faults in either the transmission or distribution systems. istribution substations may also

    be the points of voltage regulation, although on long distribution circuits several

    %m/miles-, voltage regulation e$uipment may also be installed along the line.

    #omplicated distribution substations can be found in the downtown areas of large

    cities, with high+voltage switching and, switching and bac%up systems on the low+voltage

    side. 4ost of the typical distribution substations have a switch, one transformer, and

    minimal facilities on the low+voltage side.

    c) Collector substation

    In distributed generation pro)ects such as a wind farm, a collector substation may

    be re$uired. It somewhat resembles a distribution substation although power flow is in

    the opposite direction. 9sually for economy of construction the collector system operates

    around 37 !, and the collector substation steps up voltage to a transmission voltage for

    the grid. The collector substation also provides power factor correction, metering and

    control of the wind farm.

    2.4 Substation Transformer Type

    :

  • 5/20/2018 Substation Design (1)

    5/69

    ;urther, transmission substations are mainly classified into two types depending on

    changes made to the voltage level.They are

    a- &tep+9p Transmission &ubstations.

    b- &tep+own Transmission &ubstations.

    a) Step-Up Transmission Substation

    " step+up transmission substation receives electric power from a near by

    generating facility and uses a large power transformer to increase the voltage for

    transmission to distant locations.

    There can also be a tap on the incoming power feed from the generation plant to

    provide electric power to operate e$uipment in the generation plant.

    b) Step-Don Transmission Substation

    &tep+down transmission substations are located at switching points in an electrical

    grid. They connect different parts of a grid and are a source for sub transmission lines or

    distribution lines.

    2.! "eneral Considerations

    The general considerations regarding the substation that are discussed are

    functions,design and different layouts of the substation.

    a) T#e $unctions of t#e substation are%

    i. To #hange voltage from one level to another.

    ii.To egulate voltage to compensate for system voltage changes.

    7

  • 5/20/2018 Substation Design (1)

    6/69

    iii. To &witch transmission and distribution circuits into and out of the grid system.

    iv. To 4easure electric power $uantity flowing in the circuits.

    v. To #onnect communication signals to the circuits.

    vi. To *liminate lightning and other electrical surges from the system.

    vii. To #onnect electric generation plants to the system.

    viii. To 4a%e interconnections between the electric systems of more than one utility.

    b) Desi&n

    The main issues facing a power engineer are reliability and cost. " good design

    attempts to stri%e a balance between these two to achieve sufficient reliability without

    ecessive cost. The design should also allow easy epansion of the station, if re$uired.

    &election of the location of a substation must consider many factors. &ufficient

    land area is re$uired for installation of e$uipment with necessary clearances for electrical

    safety and for access to maintain large apparatus such as transformers.

  • 5/20/2018 Substation Design (1)

    7/69

    substation. This design also places minimum reliance on signaling for satisfactory

    operation of protection. "dditionally there is the facility to support the economical

    operation of future feeder bays.

    $i& 2. s#os sin&le bus bar Substation

    &uch a substation has the following characteristics.

    a. *ach circuit is protected by its own circuit brea%er and hence plant outage does

    not necessarily result in loss of supply.

    b. " fault on the feeder or transformer circuit brea%er causes loss of the transformer

    and feeder circuit, one of which may be restored after isolating the faulty circuit

    brea%er.

    c. " fault on the bus section circuit brea%er causes complete shutdown of the

    substation. "ll circuits may be restored after isolating the faulty circuit brea%er.

    d. " bus+bar fault causes loss of one transformer and one feeder. 4aintenance of one

    bus+bar section or isolator will cause the temporary outage of two circuits.

    e. 4aintenance of a feeder or transformer circuit brea%er involves loss of the circuit.

    ii) *es# Substation

    The general layout for a full mesh substation is shown in the schematic ;ig2.2

    The characteristics of such a substation are as follows

    =

  • 5/20/2018 Substation Design (1)

    8/69

    a. peration of two circuit brea%ers is re$uired to connect or disconnect a circuit,

    and disconnection involves opening of a mesh.

    b. #ircuit brea%ers may be maintained without loss of supply or protection, and no

    additional bypass facilities are re$uired.

    c. 8us+bar faults will only cause the loss of one circuit brea%er. 8rea%er faults will

    involve the loss of a maimum of two circuits.

    d. 'enerally, not more than twice as many outgoing circuits as infeeds are used in

    order to rationalise circuit e$uipment load capabilities and rating.

    4esh substation

    6

  • 5/20/2018 Substation Design (1)

    9/69

    $i& 2.2 s#os mes# substation.

    2.+ 'ayout

    a) ,rinciple of Substation 'ayouts

    &ubstation layout consists essentially in arranging a number of switchgear

    components in an ordered pattern governed by their function and rules of spatial

    separation.

    b- Spatial Seperation

    i. *arth #learance This is the clearance between live parts and earthed structures,

    walls, screens and ground.

    ii. >hase #learance This is the clearance between live parts of different phases.

    iii. Isolating istance This is the clearance between the terminals of an isolator and

    the connections.

    iv. &ection #learance This is the clearance between live parts and the terminals of a

    wor% section. The limits of this wor% section, or maintenance (one, may be the

    ground or a platform from which the man wor%s .

    c) Separation of maintenance ones

    Two methods are available for separating e$uipment in a maintenance (one that

    has been isolated and made dead.

    i. The provision of a section clearance

    ?

  • 5/20/2018 Substation Design (1)

    10/69

    ii. 9se of an intervening earthed barrier

    The choice between the two methods depends on the voltage and whether hori(ontal

    or vertical clearances are involved.

    i. " section clearance is composed of the reach of a man ta%en as 6 feet plus an

    earth clearance.

    ii. ;or the voltage at which the earth clearance is 6 feet the space re$uired will be the

    same whether a section clearance or an earthed barrier is used .

    2. *aintenance

    4aintenance plays a ma)or role in increasing the efficiency and decreasing thebrea%down. The rules and basic principle are discussed.

    &eparation by earthed barrier @ *arth #learance A 70mm for barrier A *arth #learance

    &eparation by section clearance @ 2.::m A *arth clearance

    i. ;or vertical clearances it is necessary to ta%e into account the space occupied by

    the e$uipment and the need for an access platform at higher voltages.

    ii. The height of the platform is ta%en as 1.3=m below the highest point of wor%.

    *aintenance is done t#rou to ays%

    a- 8y *stablishing 4aintenance Bones.

    b- 8y *lectrical &eparations.

    a) Establis#in& *aintenance /ones

    &ome maintenance (ones are easily defined and the need for them is self evident

    as in the case of a circuit brea%er. There should be a means of isolation on each side of

    10

  • 5/20/2018 Substation Design (1)

    11/69

    the circuit brea%er, and to separate it from ad)acent live parts when isolated either by

    section clearances or earth barriers

    b) Electrical Separations

    Together with maintenance (oning, the separation, by isolating distance and phase

    clearances, of the substation components and of the conductors interconnecting them

    constitute the main basis of substation layouts.

    There are at least three such electrical separations per phase that are needed in a

    circuit

    i. 8etween the terminals of the bus bar isolator and their connections.

    ii. 8etween the terminals of the circuit brea%er and their connections.

    iii. 8etween the terminals of the feeder isolator and their connections.

    2.0 Conclusion%

  • 5/20/2018 Substation Design (1)

    12/69

    connection of 220 ! line and also about the lines that feeds this substation from

    generating units.

    3.2 'ine dia&ram%

    In power engineering, a one+line diagram or single+line diagram is a simplified

    notation for representing a three+phase power system. The one+line diagram has its largest

    application in power flow studies. *lectrical elements such as circuit brea%ers,

    transformers, capacitors, bus bars, and conductors are shown by standardi(ed schematic

    symbols. Instead of representing each of three phases with a separate line or terminal,

    only one conductor is represented. It is a form of bloc% diagram graphically depicting the

    paths for power flow between entities of the system. *lements on the diagram do not

    represent the physical si(e or location of the electrical e$uipment, but it is a common

    convention to organi(e the diagram with the same left+to+right, top+to+bottom se$uence as

    the switchgear or other apparatus represented.

    &1 and

    the other from which have two lines, named as 4al%aram1 C 4al%aram 2.

    The single line diagram of 220/132/33 %! &">9 D"'" sub station is

    shown at the end of this report.

    3.3 T#e interconnection of 221 "rid Substations

    The interconnection of 220! to different grid substations is given below,

    220 ! &">9D"'" + '"#I89D"'" + '"#I8

  • 5/20/2018 Substation Design (1)

    13/69

    circuit conductors leave the substation from a circuit brea%er via underground cables,

    called substation eit cables. The underground cables connect to a nearby overhead

    primary circuit outside the substation. This eliminates multiple circuits on the poles

    ad)acent to the substations there by improving the overall appearance of the substation.

    $i&.3. s#os 3-p#ase distribution feeder bay

    This substation has two types of feeder i.e. 132 ! and 33 ! feeder. They are

    12 feeders of 132 ! which are basically collector substation and it has 15 feeders of

    33! which are industries and for domestic user.

    a) T#e interconnection of 32 "rid Substations

    The interconnection of 132! to different grid substations is given below,

    i. &">9D"'" + 4*#"E+ I circuit Do.1.

    ii. &">9D"'" + 4*#"E+I circuit Do. 2.

    iii. &">9D"'" + .#.>9"4.

    iv. &">9D"'" + D"&">9.v. &">9D"'" + "E*.

    vi. &">9D"'" + '944"I "E".

    vii. &">9D"'" + 8DI'I.viii. &">9D"'" + '9D#.

    i. &">9D"'" + 49E"EI.

    . &">9D"'" + I>E.i. &">9D"'" + &"D"TD"'" "IE9D"'" + 8EE""4.

    b- T#e interconnection of 33 "rid Substations

    The interconnection of 33! to different substations is given below,

    i. &">9D"'" + &">9D"'"

    13

  • 5/20/2018 Substation Design (1)

    14/69

    ii. &">9D"'" + G**I4*TE" circuit Do.1

    iii. &">9D"'" + G**I4*TE" circuit Do.2

    iv. &">9D"'" + G**I4*TE" circuit Do.3v. &">9D"'" + G**I4*TE" circuit Do. :

    vi. &">9D"'" + &"TF"4 circuit Do. 1

    vii. &">9D"'" + &"TF"4 circuit Do. 2viii. &">9D"'" + G"I"G circuit Do.1

    i. &">9D"'" + G"I"G circuit Do. 2

    . &">9D"'" + "I;#* "#"*4F circuit Do. 1i. &">9D"'" + "I;#* "#"*4F circuit Do. 2

    ii. &">9D"'" + ##

    iii. &">9D"'" + 8.>"EEIF

    iv. &">9D"'" + .".Ev. &">9D"'" + I>E

    vi. &">9D"'" + .4.T

    3.! Conclusion

  • 5/20/2018 Substation Design (1)

    15/69

  • 5/20/2018 Substation Design (1)

    16/69

    " simplified transformer design is shown in ;ig :.1. " current passing through the

    primary coil creates a varying magnetic field. The primary and secondary coils are

    wrapped around a core of very high magnetic permeability, such as iron, This ensures that

    most of the magnetic field lines produced by the primary current are within the iron core

    and pass through the secondary coil as well as the primary coil. Transformers are

    essential for high voltage power transmission, which ma%es long distance transmission

    economically practical.

    c) ,ractical Considerations

    i. Effect of freuency

    The time+derivative term in ;aradayHs Eaw shows that the flu in the core is the

    integral of the applied voltage. ypothetically an ideal transformer would wor% with

    direct+current ecitation, with the core flu increasing linearly with time. In practice, the

    flu would rise to the point where magnetic saturation of the core occurs, causing a huge

    increase in the magneti(ing current and overheating the transformer. "ll practical

    transformers must therefore operate with alternating current.

    ii. Transformer uni5ersal E*$ euation

    If the flu in the core is sinusoidal, the relationship for either winding between its

    !oltage of the winding E, and the supply fre$uency f, number of turns N, core cross+

    sectional area a and pea% magnetic flu density B is given by the universal *4;

    e$uation

    The *4; of a transformer at a given flu density increases with fre$uency. 8y

    operating at higher fre$uencies, transformers can be physically more compact because a

    given core is able to transfer more power without reaching saturation and fewer turns are

    needed to achieve the same impedance.

    15

  • 5/20/2018 Substation Design (1)

    17/69

    owever properties such as core loss and conductor s%in effect also increase with

    fre$uency. "ircraft and military e$uipment employ :00 ( power supply which reduce

    core and winding weight.

    iii. Ener&y 'osses

    "n ideal transformer would have no energy losses, and would be 100 efficient.

    In practical transformers energy is dissipated in the windings, core, and surrounding

    structures. Earger transformers are generally more efficient, and those rated for electricity

    distribution usually perform better than ?6.*perimental transformers using

    superconducting windings achieve efficiencies of ??.67, while the increase in

    efficiency is small, when applied to large heavily+loaded transformers the annual savings

    in energy losses are significant.

    Transformer losses are divided into losses in the windings, termed copper loss, and

    those in the magnetic circuit, termed iron loss. Eosses in the transformer arise from

    i.

  • 5/20/2018 Substation Design (1)

    18/69

    4.2 Construction

    The constructional details of the transformer are

    a.) Cores

    i 'aminated steel cores

    ii Solid cores

    iii Toroidal cores

    i5 6ir cores

    b) 7indin&s

    7indings are usually arranged concentrically to minimi(e flu lea%age.

    $i&. 4.28i) s#os indin&s of transformer

    The ;ig :.2 i- shows #ut view through transformer windings. rimary winding made of oygen+free

    copper. ed &econdary winding. Top left Toroidal transformer. ight #+core, but *+

    core would be similar. The blac% windings are made of film.

    Top *$ually low capacitance between all ends of both the windings. &ince most

    cores are at least moderately conductive they also need insulation at 8ottom.

    16

  • 5/20/2018 Substation Design (1)

    19/69

    c) Coolant

    The oil reservoir is visible at the top. adioactive fins aid the dissipation of heat

    $i& 4.28ii) s#os coolant of transformer

    igh temperatures will damage the winding insulation. >ower transformers rated

    up to several hundred !" can be ade$uately cooled by natural convective air+cooling,

    sometimes assissted by fans. &ome power transformers are immersed in transformer oil

    that both cools and insulates the windings. The oil is a highly refined mineral oil that

    remains stable at transformer operating temperature. The oil+filled tan% often hasradiators through which the oil circulates by natural convection some large transformers

    employ forced circulation of the oil by electric pumps, aided by eternal fans or water+

    cooled heat echangers.

    il+filled transformers undergo prolonged drying processes to ensure that the

    transformer is completely free of water vapuor before the cooling oil is introduced. This

    helps to prevent electrical brea%down under load. il+filled transformers may be

    e$uipped with 8uchhol( relays, which detect gas evolved during internal arcing and

    rapidly de+energi(e the transformer to avert catastrophic failure.

    *perimental power transformers in the 2 4!" range have been built with

    superconducting windings which eliminates the copper losses, but not the core steel loss

    but these are cooled by li$uid nitrogen or helium.

    1?

  • 5/20/2018 Substation Design (1)

    20/69

    d) Tappin&s

    Do+load tap changers DET#- or load tap changers ET#- can be obtained on

    power transformers.

    The addition of no+load taps in the primary of a substation transformer ma%es it

    possible to adapt the transformer to a range of supply voltages usually a 10 percent

    overall range of which 7 percent is above nominal and 7 percent below nominal, usually

    in 2.7 percent steps-. &ince no+load taps are not capable of interrupting any current

    including transformer charging current, the transformers have to be de+energi(ed when

    the manual no+load tap position is changed. "ll taps should have full capacity ratings.

    "ny decision to use load tap changing transformers should be based on a careful

    analysis of the particular voltage re$uirements of the loads served and consideration of

    the advantages and disadvantages including costs of alternatives such as separate voltage

    regulators.

    e) Terminals

    !ery small transformers will have wire leads connected directly to the ends of the

    coils and brought out to the base of the unit for circuit connections. Earger transformers

    may have heavy bolted terminals, bus bars or high+voltage insulated bushings made of

    polymers or porcelain.

    " large bushing can be of comple structure since it must provide careful control

    of the electric field gradient without letting the transformer lea% oil.

    4.3 Types and Classification $actors

    " wide variety of transformer designs are used for different applications though

    they share several common features. Important common transformer types include

    a. "uto transformer

    b. >oly >hase transformers

    20

  • 5/20/2018 Substation Design (1)

    21/69

    c. Eea%age transformer

    d. esonant transformers

    e. Instrument transformers

    Classification of Transformers is based on folloin& factors.

    i. 8y power capacity from a fraction of a volt+ampere !"- to over a thousand

    4!".

    ii. 8y fre$uency range power, audio, or radio fre$uency.

    iii. 8y voltage class from a few volts to hundreds of %ilovolts.

    iv. 8y cooling type air cooled, oil filled, fan cooled, or water cooled.

    v. 8y application such as power supply, impedance matching, output voltage and

    current stabili(er, or circuit isolation.

    vi. 8y end purpose distribution, rectifier, arc furnace, amplifier output.

    vii. 8y winding turns ratio step+up, step+down, isolating e$ual or near+e$ual ratio-,

    and variable.

    "mong the above mentioned transformers only instrument transformers are widely

    used in the sub station. ence only instrument transformers are discussed in this

    section.

    4.3. Instrument Transformer%

    Instrument transformers are used to step+down the current or voltage to

    measurable values. They provide standardi(ed, useable levels of current or voltage in a

    variety of power monitoring and measurement applications.

    8oth current and voltage instrument transformers are designed to have

    predictable characteristics on overloads.

    21

  • 5/20/2018 Substation Design (1)

    22/69

    >roper operation of over+current protection relays re$uires that current

    transformers provide a predictable transformation ratio even during a short Jcircuit.

    These are further classified into two types which are discussed below.

    a- #urrent Transformers

    b- !oltage Transformers

    a) Current Transformers%

    i. ,rinciple of 9peration

    " current transformer is defined as as an instrument transformer in which the

    secondary current is substantially proportional to the primary current under normal

    conditions of operation- and differs in phase from it by an angle which is approimately

    (ero for an appropriate direction of the connections. This highlights the accuracy

    re$uirement of the current transformer but also important is the isolating function, which

    means no matter what the system voltage the secondary circuit need to be insulated onlyfor a low voltage.

    The current transformer wor%s on the principle of variable flu. In the ideal current

    transformer, secondary current would be eactly e$ual when multiplied by the turns

    ratio- and opposite to the primary current.

    8ut, as in the voltage transformer, some of the primary current or the primary

    ampere+turns are utili(ed for magneti(ing the core, thus leaving less than the actual

    primary ampere turns to be transformed into the secondary ampere+turns. This naturally

    introduces an error in the transformation. The error is classified into current ratio error

    and the phase error.

    ii. Definitions

    22

  • 5/20/2018 Substation Design (1)

    23/69

    Typical terms used for specifying current transformer are,

    :ated primary current%The value of current which is to be transformed to a

    lower value. In #T parallence, the load of the #T refers to the primary current.

    :ated secondary current%The current in the secondary circuit and on which the

    performance of the #T is based. Typical values of secondary current are 1 " or 7 ".

    :ated burden%The apparent power of the secondary circuit in !olt+amperes

    epressed at the rated secondary current and at a specific power factor.

    Composite Error% The 4& value of the difference between the instantaneous

    primary current and the instantaneous secondary current multiplied by the turns ratio,

    under steady state conditions.

    6ccuracy limit factor%The value of primary current up to which the #T compiles

    with composite error re$uirements. This is typically 7, 10 or 17, which means that the

    composite error of the #T has to be within specified limits at 7, 10 or 17 times the rated

    primary current.

    S#ort time ratin&%The value of primary current in %"- that the #T should be able

    to withstand both thermally and dynamically without damage to the windings with the

    secondary circuit being short+circuited. The time specified is usually 1 or 3 seconds.

    Class ,S; < CT% In balance systems of protection, #T s with a high degree of

    similarity in their characteristics are re$uired. These re$uirements are met by #lass >&

    K- #T s. Their performance is defined in terms of a %nee+point voltage >!-, the

    magneti(ing current Image- at the %nee point voltage or 1/2 or 1/: the %nee+point

    voltage, and the resistance of the #T secondary winding corrected to =7#. "ccuracy is

    defined in terms of the turns ratio.

    nee point 5olta&e%The point on the magneti(ing curve where an increase of

    10 in the flu density voltage- causes an increase of 70 in the magneti(ing force

    current-.

    23

  • 5/20/2018 Substation Design (1)

    24/69

    Summation CT%

  • 5/20/2018 Substation Design (1)

    25/69

    i5. Typical specification for a @ CT

    &ystem voltage11 %!

    Insulation level voltage IE!- 12/26/=7 %!

    atio 200/1 + 1 + 0.7== "

    #ore 1 1", metering, 17 !"/class 1, I&;M10

    #ore 2 1 ", protection, 17 !"/7>10

    #ore 3 0.7== ",#lass >&, >!N@ 170 !,Img at !%/2 M@30 m", #T at =7 #M@2

    &hort time rating20 %" for 1 second

    #THs may be accommodate in one of si manners

    a. ver #ircuit 8rea%er bushings or in pedestals.

    b. In separate post type housings.

    c. ver moving bushings of some types of insulators.

    d. ver power transformers of reactor bushings.

    e. ver wall or roof bushings.

    f. ver cables.

    In all ecept the second of the list, the #THs occupy incidental space and do not

    affect the si(e of the layout. The #THs become more remote from the circuit brea%er in the

    order listed above. "ccommodation of #THs over isolator bushings or bushings through

    walls or roofs is usually confined to indoor substations.

    b) olta&e Transformers

    i. ,rinciple of operation

    The standards define a voltage transformer as one in which the secondary

    voltage is substantially proportional to the primary voltage and differs in phase from it by

    an angle which is approimately e$ual to (ero for an appropriate direction of the

    27

  • 5/20/2018 Substation Design (1)

    26/69

    connections. This in essence means that the voltage transformer has to be as close as

    possible to the ideal transformer.

    In an ideal transformer, the secondary voltage vector is eactly opposite and

    e$ual to the primary voltage vector when multiplied by the turnLs ratio.

    In a practical transformer, errors are introduced because some current is drawn for

    the magneti(ation of the core and because of drops in the primary and secondary

    windings due to lea%age reactance and winding resistance. ne can thus tal% of a voltage

    error which is the amount by which the voltage is less than the applied primary voltage

    and the phase error which is the phase angle by which the reversed secondary voltage

    vector is displaced from the primary voltage vector.

    ii. Definitions

    Typical terms used for specifying a voltage transformer !T- are

    a. :ated primary 5olta&e%This is the rated voltage of the system whose voltage is

    re$uired to be stepped down for measurement and protective purposes.

    b. :ated secondary 5olta&e%This is the voltage at which the meters and protective

    devices connected to the secondary circuit of the voltage transformer operations.

    c. :ated burden%This is the load in terms of volt+amperes !"- posed by the

    devices in the secondary circuit on the !T. This includes the burden imposed by

    the connecting leads. The !T is re$uired to be accurate at both the rated burden

    and 27 of the rated burden.

    d. :ated 5olta&e factor%epending on the system in which the !T is to be used,

    the rated voltage factors to be specified are different. The table :.2 below is

    adopted from Indian and International standards.

    Table 4.2 s#os rated 5ota&e factor for Ts

    25

  • 5/20/2018 Substation Design (1)

    27/69

    :ated

    5olta&e

    factor

    :ated

    time*et#od of connectin& primary indin& in

    system

    1.2 #ontinuous 8etween phases in any networ%.

    8etween transformer star+point and earth in any

    networ%.

    1.2

    1.7

    #ontinuous 8etween phase and in an effectively earthed

    neutral system.

    1.2

    1.?

    #ontinuous

    for 30

    seconds

    8etween phase and earth in a non+effectively

    earthed neutral system with automatic fault

    tripping.

    1.2

    1.?

    #ontinuous

    for 6 hours

    8etween phase and earth in an isolated neutral

    system without automatic fault tripping or in a

    resonant earthed system without automatic fault

    tripping.

    e. Temperature class of insulation% The permissible temperature rise over the

    specified ambient temperature. Typically, classes *, 8 and ;.

    f. :esidual 5olta&e transformer 8:T)%!Ts are used for residual earth faultprotection and for discharging capacitor ban%s. The secondary residual voltage

    winding is connected in open delta. 9nder normal conditions of operation, there is

    no voltage output across the residual voltage winding.

  • 5/20/2018 Substation Design (1)

    28/69

    Table 4.3 s#os standard references for Ts

    StandardStandard

    >umber?ear

    Indian I& 3175 1??2

    8ritish 8& 36:1 1?=3

    "merican "D&I #.7=.13 1?=6

    Typical specification for a @ T

    &ystem voltage 11 %!

    Insulation level voltage IE!- 12 /26/=7 %!

    Dumber of phases Three

    !ector 'roup &tar / &tar

    atio 11 %!/ 110 !

    8urden 100 !"

    "ccuracy #lass 0.7

    !oltage ;actor 1.2 continuous and 1.7 for 30 seconds

    with provision for fuse

    c) Couplin& capacitor 5olta&e transformers

    #oupling capacitor voltage transformers, commonly termed capacitor voltage

    transformers #!Ts-, are devices used for coupling to a power line to provide low

    voltage for the operation of relays and metering instruments.

    >ower line carrier accessories or provisions for future installation of carrier

    accessories may be included in the base. #oupling capacitor voltage transformers are

    26

  • 5/20/2018 Substation Design (1)

    29/69

    commonly supplied without carrier accessories, especially at voltages above 11 %!, as a

    more economical alternative to inductive voltage transformers. #oupling capacitor

    voltage transformers can be provided with the same ratings and accuracy as inductive

    voltage transformers

    $i& 4.28iii)s#oin& Couplin& capacitor 5olta&e transformers

    owever, because of the energy+storage capability of capacitors, sudden

    reductions in the power line voltage may result in momentary distortion of the ##!T

    secondary voltage. The amount of distortion is related to ##!T capacitance and the

    burden secondary load- value and configuration. 4odern ##!T designs are available to

    minimi(e this problem.

    4.3.2 ,oer Transformers

    >ower transformers convert power+level voltages from one level or phase

    configuration to another. They can include features for electrical isolation, power

    distribution, and control and instrumentation applications

    *! power transformers are usually oil immersed with all three phases in one

    tan%. "uto transformers can offer advantage of smaller physical si(e and reduced losses.

    The different classes of power transformers are

    i. .D. il immersed, natural cooling.

    ii. .8. il immersed, air blast cooling.

    iii. .;.D. il immersed, oil circulation forced.

    iv. ;.". il immersed, oil circulation forced, air blast cooling.

    2?

  • 5/20/2018 Substation Design (1)

    30/69

    >ower transformers are usually the largest single e$uipment in a substation. ;or economy

    of service roads, transformers are located on one side of a substation and the connection to

    switchgear is by bare conductors. 8ecause of the large $uantity of oil, it is essential to ta%e

    precaution against the spread of fire. ence, the transformer is usually located around a sump

    used to collect the ecess oil.

    4.4 Tests

    " number of routine and type tests have to be conducted on !T s and #Ts before

    they can meet the standards specified above. The tests can be classified as

    i. "ccuracy tests

    ii. ielectric insulation tests

    iii. Temperature rise tests

    iv. &hort circuit tests.

    4.! Commissionin&

    nce the unit is received and pac%ing is opened first thing is to chec% whether

    there are any transit damages.

    In case of minor damages, such as loose screws or li%ewise, they can be attended

    immediately. In case of ma)or damages, the report for this is to be sent to the supplier

    who can immediately attend these.

    nce the unit is found to have received in good condition, the following need to be

    chec%ed

    i. #hec% the primary terminals.

    ii. #hec% the secondary terminals.

    iii. #hec% *arthing.

    iv. #hec% oil level

    30

  • 5/20/2018 Substation Design (1)

    31/69

    v. #hec% Insulation esistance ;or primary .T- winding it should be minimum

    700m ohms with 1000!..#.4eggar and for secondary E.T- winding. It should

    be minimum 274 ohms with 700!..# 4erger.

    vi. #hec% atio+ for this a- >ass the rated primary current through primary

    b- #hec% the secondary current across the respective Terminals.

    If everything is all right, put transformer into operation verification of terminal

    mar%ings and polarity

    4.+ 6pplications and "eneral Instructions

    There are certain applications of transformers and general instructions for

    erection, uses and maintenance.

    a) 6pplications

    " ma)or application of transformers is to increase voltage before transmitting

    electrical energy over long distances through wires.

  • 5/20/2018 Substation Design (1)

    32/69

    iv. Transformers should be mounted on corresponding supports or base and firmly

    tightened for this purpose.

    v. #hec% up whether base to which transformer is fied is in hori(ontal position.

    vi. #onnecting cables/conductors by means of which transformer is connected to

    high voltage bus+bar or supply system should be correctly dimensioned placed

    and mounted not to cause additional over stresses of transformer connections.

    vii. >rior to the connection of transformer compare connection diagram with

    indications on the transformer and carryout connection in compliance with

    corresponding indications.

    viii. >roperly carryout earthing on all intended spots on boes and or base

    frame of transformers.

    i. 9pon completion of above chec% up prior to putting in operation if assembly

    properly done.

    . >ut connected transformer on line.

    i. #ompare instrument indicated with operational condition in supply system.

    c) "eneral Instructions for use

    i. egular periodical inspection

    ii. #hec% up of all sealed spots in order to ascertain oil lea%, if any

    iii. #leaning of insulator and possible painting of transformer.

    iv. #hec% up of all placement of diaphragm and oil level in oil level indicators.

    v. In case of damage of diaphragm or if there is no oil level indicators,

    transformer should be thoroughly chec%ed up by the service mechanic since

    probably more serious defect occurred. This should be carried out at least once

    a year or in two.

    vi. #hec% up of primary and secondary connections. their cleaning and tightening

    is precaution.

    32

  • 5/20/2018 Substation Design (1)

    33/69

    vii. #hec% up of sealed places consists of detection of oil around connections,

    flanges etc. no case transformer should be opened.

    viii. "ll earthed parts should be chec%ed and if re$uired, they should be cleaned

    and tightened.

    i. >ainting of originally painted transformer parts is advisable if re$uired during

    regular chec%+ups.

    . Transformer should not be opened barring in service wor%shop.

    d) "eneral Instructions for *aintenance

    The maintenance of transformer is usually done in speciali(ed wor%shops, but ifpossible also on the spot.

    "fter the maintenance,

    i. ;ollow all steps as said under erection, commissioning C inspection.

    ii 4easure insulation resistance and loss angle after ma)or maintenance.

    4. Conclusion

  • 5/20/2018 Substation Design (1)

    34/69

    !. Introduction

  • 5/20/2018 Substation Design (1)

    35/69

    $i& !.28i) litnin& arresters

    The >ressure elief arrangement transfers the internal arc to outside in the remote event

    of arrester failure.

    ii. Installation of 'itnin& 6rresters

    Three simple rules to be followed in installing lightning arresters for the effective

    protection of the e$uipment

    i. The arrester should be connected to a ground of low resistance for effective

    discharge of the surge current.ii. The arrester should be mounted close to e$uipment to be protected and connected

    with shortest possible leads. n both the line and ground side to reduce the

    inductive effects of the leads while discharging large surge currents.

    iii. To protect the transformer windings. It is desirable to interconnect the ground lead

    of the arrester with the tan% and also the neutral of the secondary. This

    interconnection reduces the stress imposed on the transformer winding by the

    surge currents to the etent of the drop across the ground.

    iii. *aAimum Continuous 9peratin& olta&e

    9nder actual service conditions 4*T!" functions as insulators at the

    maimum line to ground operating voltage. ;or each arrester rating there is a limit to the

    magnitude of the voltage that may be continuously applied. There for 4.#..! is the

    designated maimum permissible power fre$uency voltage that may be applied

    continuously across the arrester terminal.

    i5. Caution

    37

  • 5/20/2018 Substation Design (1)

    36/69

    9nder no circumstances, the 4aimum #ontinuous >ower ;re$uency !oltage

    between phase and ground appearing the arrester should eceed the arrester 4.#..! as

    specified in the name plate.

    5. ,ac@in&

    *ach arrester is pac%ed in a wooden bo with proper cushioning material. The

    terminal connectors are also pac%ed in the same wooden bo ta%en to see that the arrester

    housing is not damaged due to rough handling

    b) Control and :elay ,anel

    The control and relay panel is of cubical construction suitable for floor mounting.

    "ll protective, indicating and control elements are mounted on the front panel for ease of

    operation and control. The hinged rear door will provide access to all the internal

    components to facilitate easy inspection and maintenance. >rovision is made for

    terminating incoming cables at the bottom of the panels by providing separate line+up

    terminal bloc%s. ;or cable entry provision is made both from top and bottom.

    The control and relay panel accepts #T, >T au 230 "# and 220!/10! #

    connections at respective designated terminal points. 220!/10! # supply is used for

    control supply of all internal relays and timers and also for energi(ing closing and

    tripping coils of the brea%ers. 230! "# station auiliary supply is used for internal

    illumination lamp of the panel and the space heater. >rotective # fuse are provided

    with in the panel for >.T secondary. "u "# and battery supplies.

    *ach #apacitor 8an% is controlled by brea%er and provided with a line ammeter with

    selector switch for 3 phase system C ver current relay 2 phase and 1 *arth fault for 3

    ph system-. 9nder voltage and over voltage elays.

    Deutral #urrent 9nbalance elays are for both "larm and Trip facilities brea%er

    control switch with local/remote selector switch, master trip relay and trip alarms

    ac%nowledge and reset facilities.

    35

  • 5/20/2018 Substation Design (1)

    37/69

    c) ,rotecti5e :elayin&

    >rotective relays are used to detect defective lines or apparatus and to initiate the

    operation of circuit interrupting devices to isolate the defective e$uipment. elays are

    also used to detect abnormal or undesirable operating conditions other than those caused

    by defective e$uipment and either operate an alarm or initiate operation of circuit+

    interrupting devices. >rotective relays protect the electrical system by causing the

    defective apparatus or lines to be disconnected to minimi(e damage and maintain service

    continuity to the rest of the system

    There are different types of relays.

    i. ver current relay

    ii. istance relay

    iii. ifferential relay

    iv. irectional over current relay

    i. 95er Current :elay

    The over current relay responds to a magnitude of current above a specified value.

    There are four basic types of construction They are plunger, rotating disc, static, and

    microprocessor type. In the plunger type, a plunger is moved by magnetic attraction when

    the current eceeds a specified value. In the rotating induction+disc type, which is a

    motor, the disc rotates by electromagnetic induction when the current eceeds a specified

    value.

    &tatic types convert the current to a proportional .# mill volt signal and apply it to a

    level detector with voltage or contact output. &uch relays can be designed to have various

    current+versus+time operating characteristics. In a special type of rotating induction+disc

    relay, called the voltage restrained over current relay.

    The magnitude of voltage restrains the operation of the disc until the magnitude of

    the voltage drops below a threshold value. &tatic over current relays are e$uipped with

    3=

  • 5/20/2018 Substation Design (1)

    38/69

    multiple curve characteristics and can duplicate almost any shape of electromechanical

    relay curve. 4icroprocessor relays convert the current to a digital signal. The digital

    signal can then be compared to the setting values input into the relay.

  • 5/20/2018 Substation Design (1)

    39/69

    The differential relay is used to provide internal fault protection to e$uipment such

    as transformers, generators, and buses. elays are designed to permit differences in the

    input currents as a result of current transformer mismatch and applications where the

    input currents come from different system voltages, such as transformers. " current

    differential relay provides restraint coils on the incoming current circuits. The restraint

    coils in combination with the operating coil provide an operation curve, above which the

    relay will operate. ifferential relays are often used with a loc%out relay to trip all power

    sources to the device and prevent the device from being automatically or remotely re+

    energi(ed. These relays are very sensitive. The operation of the device usually means

    ma)or problems with the protected e$uipment and the li%ely failure in re+energi(ing the

    e$uipment

    i5. Directional 95er current :elay

    " directional over current relay operates only for ecessive current flow in a given

    direction. irectional over current relays are available in electromechanical, static, and

    microprocessor constructions. "n electromechanical overcorrect relay is made directional

    by adding a directional unit that prevents the over current relay from operating until the

    directional unit has operated. The directional unit responds to the product of the

    magnitude of current, voltage, and the phase angle between them or to the product of two

    currents and the phase angle between them. The value of this product necessary to

    provide operation of the directional unit is small, so that it will not limit the sensitivity of

    the relay such as an over current relay that it controls-. In most cases, the directional

    element is mounted inside the same case as the relay it controls. ;or eample, an over

    current relay and a directional element are mounted in the same case, and the

    combination is called a directional over current relay. 4icroprocessor relays often

    provide a choice as to the polari(ing method that can be used in providing the direction of

    fault, such as applying residual current or voltage or negative se$uence current or voltage

    polari(ing functions to the relay.

    d) Circuit (rea@ers

    3?

  • 5/20/2018 Substation Design (1)

    40/69

    " circuit brea@er is an automatically+operated electrical switch designed to

    protect an electrical circuit from damage caused by overload or short circuit. Its basic

    function is to detect a fault condition and these by interrupting continuity, to immediately

    discontinue electrical flow.

    i. ,rinciple of 9peration

    "ll circuit brea%ers have common features in their operation, although details vary

    substantially depending on the voltage class, current rating and type of the circuit brea%er.

    The circuit brea%er must detect a fault condition in low+voltage circuit brea%ers this

    is usually done within the brea%er enclosure. #ircuit brea%ers for large currents or high

    voltages are usually arranged with pilot devices to sense a fault current and to operate the

    trip opening mechanism. The trip solenoid that releases the latch is usually energi(ed by a

    separate battery, although some high+voltage circuit brea%ers are self+contained with

    current transformers, protection relays and an internal control power source.

    nce a fault is detected, contacts within the circuit brea%er must open to interrupt the

    circuit. &ome mechanically+stored energy using something such as springs or

    compressed air- contained within the brea%er is used to separate the contacts, although

    some of the energy re$uired may be obtained from the fault current itself. The circuit

    brea%er contacts must carry the load current without ecessive heating, and must also

    withstand the heat of the arc produced when interrupting the circuit. #ontacts are made of

    copper or copper alloys, silver alloys and other materials. &ervice life of the contacts is

    limited by the erosion due to interrupting the arc. 4iniature circuit brea%ers are usually

    discarded when the contacts are worn, but power circuit brea%ers and high+voltage circuit

    brea%ers have replaceable contacts.

  • 5/20/2018 Substation Design (1)

    41/69

    i. Eengthening of the arc

    ii. Intensive cooling in )et chambers-

    iii. ivision into partial arcs

    iv. Bero point $uenching

    v. #onnecting capacitors in parallel with contacts in # circuits

    ;inally, once the fault condition has been cleared, the contacts must again be

    closed to restore power to the interrupted circuit.

    ii. 6rc Interruption

    4iniature low+voltage circuit brea%ers use air alone to etinguish the arc. Earger

    ratings will have metal plates or non+metallic arc chutes to divide and cool the arc.

    4agnetic blowout coils deflect the arc into the arc chute.

    In larger ratings, oil circuit brea%ers rely upon vapori(ation of some of the oil to blast

    a )et of oil through the arc.

    'as usually sulfur heafluoride- circuit brea%ers sometimes stretch the arc using amagnetic field, and then rely upon the dielectric strength of the sulfur heafluoride &; 5-

    to $uench the stretched arc.

    !acuum circuit brea%ers have minimal arcing as there is nothing to ioni(e other than

    the contact material-, so the arc $uenches when it is stretched a very small amount M2+3

    mm-. !acuum circuit brea%ers are fre$uently used in modern medium+voltage switchgear

    to 37,000 volts.

    "ir circuit brea%ers may use compressed air to blow out the arc, or alternatively, the

    contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air

    thus blowing out the arc.

    :1

  • 5/20/2018 Substation Design (1)

    42/69

    #ircuit brea%ers are usually able to terminate all current very $uic%ly. Typically the

    arc is etinguished between 30 ms and 170 ms after the mechanism has been tripped,

    depending upon age and construction of the device.

    iii. S#ort circuit current

    " circuit brea%er must incorporate various features to divide and etinguish the arc.

    The maimum short+circuit current that a brea%er can interrupt is determined by testing.

    "pplication of a brea%er in a circuit with a prospective short+circuit current higher than

    the brea%erHs interrupting capacity rating may result in failure of the brea%er to safely

    interrupt a fault. In a worst+case scenario the brea%er may successfully interrupt the fault,

    only to eplode when reset.

    4iniature circuit brea%ers used to protect control circuits or small appliances may not

    have sufficient interrupting capacity to use at a panelboard. These circuit brea%ers are

    called Osupplemental circuit protectorsO to distinguish them from distribution+type circuit

    brea%er.

    i5. Bi-5olta&e circuit brea@ers

    :00! &;5 circuit brea%ers

    *lectrical power transmission networ%s are protected and controlled by high+voltage

    brea%ers. The definition of Ohigh voltageO varies but in power transmission wor% is

    usually thought to be =2,700 ! or higher according to a recent definition by the

    International *lectro technical #ommission I*#-.

    igh+voltage brea%ers are nearly always solenoid+operated, with current sensing

    protective relays operated through current transformers. In substations the protection

    relay scheme can be comple, protecting e$uipment and busses from various types of

    overload or ground/earth fault.

    :2

  • 5/20/2018 Substation Design (1)

    43/69

    igh+voltage brea%ers are broadly classified by the medium used to etinguish the

    arc.

    i. 8ul% oil

    ii. 4inimum oil

    iii. "ir blast

    iv. &;5

    $i&.!.2 8iii) s#os

    circuit brea@er

    igh+voltage circuit brea%ers used on transmission systems may be arranged to

    allow a single pole of a three+phase line to trip, instead of tripping all three poles.;or

    some classes of faults this improves the system stability and availability.

    e) Conductor Systems

    "n ideal conductor should fulfill the following re$uirements

    i. &hould be capable of carrying the specified load currents and short time currents.

    ii. &hould be able to withstand forces on it due to its situation. These forces comprise

    self weight, and weight of other conductors and e$uipment, short circuit forces

    and atmospheric forces such as wind and ice loading.

    iii. &hould be corona free at rated voltage.

    iv. &hould have the minimum number of )oints.

    v. &hould need the minimum number of supporting insulators.

    vi. &hould be economical.

    :3

  • 5/20/2018 Substation Design (1)

    44/69

    vii. The most suitable material for the conductor system is copper or aluminum. &teel

    may be used but has limitations of poor conductivity and high susceptibility to

    corrosion.

    $i&.!.28iii) s#os Conductor systems

    In an effort to ma%e the conductor ideal, three different types have been utili(ed,

    and these include

    i. ;lat surfaced #onductors.

    ii. &tranded #onductors.

    iii. Tubular #onductors.

    f ) DC ,oer Supply

    i. DC (attery and C#ar&er

    "ll but the smallest substations include auiliary power supplies. "# power is

    re$uired for substation building small power, lighting, heating and ventilation, some

    communications e$uipment, switchgear operating mechanisms, anti+condensation heaters

    and motors. # power is used to feed essential services such as circuit brea%er trip coils

    and associated relays, supervisory control and data ac$uisition ""- and

    communications e$uipment. This describes how these auiliary supplies are derived and

    eplains how to specify such e$uipment.

    ii. (attery and C#ar&er confi&urations

    ::

  • 5/20/2018 Substation Design (1)

    45/69

    #apital cost and reliability ob)ectives must first be considered before defining the

    battery and battery charger combination to be used for a specific installation. The

    comparison given in Table 7.1 describes the advantages and disadvantages of three such

    combinations.

    Table 7.1 #apital cost and reliability ob)ectives must first be considered before defining

    the battery/battery charger combination to be used for a specific installation. The

    comparison given describes the advantages and disadvantages of three such combinations

    Type Advantages Disadvantages

    1. &ingle

    100 battery

    and 100

    charger

    Eow capital cost

    Do standby # &ystem outage for

    maintenance Deed to isolate battery/charger

    combination from load under boost charge

    conditions in order to prevent high boost

    voltages appearing on # distribution

    system

    2. &emi+

    duplicate

    70 batteries

    and

    100

    chargers

    4edium capital cost &tandby

    # provided which is 100capacity on loss of one

    charger *ach battery or

    charger can be maintained in

    turn. *ach battery can be

    isolated and...

    ++++++++++++++++++++++++++++++

    iii. 221 DC (attery

    4a%e *ide, #apacity 300 " at 2=P

    Do. of #ells 110 Do. , ate of installation 05/200

    4a%e 9niversal, &r. Do. 8# 1020/62

    :7

  • 5/20/2018 Substation Design (1)

    46/69

    ate of installation 1?63

    Input ating !oltage :17 ! A 10

    ;re$uency 70 (. 3 >hase

    utput ating

    ;loat 220 !, 10 "mp $i&.!.28i5) s#os 221 (attery C#ar&er

    8oost 160 !, 30"mp

    &) 7a5e Trapper

    This is relevant in >ower Eine #arrier #ommunication >E##- systems for

    communication among various substations without dependence on the telecom company

    networ%. The signals are primarily teleportation signals and in addition, voice and data

    communication signals. Eine trap also is %nown as

  • 5/20/2018 Substation Design (1)

    47/69

    Deutral bus bars may also be insulated. *arth bus bars are typically bolted directly

    onto any metal chassis of their enclosure. 8us bars may be enclosed in a metal housing,

    in the form of bus duct or bus way, segregated+phase bus, or isolated+phase bus.

    i. ,rotection

    8us bars are vital parts of a power system and so a fault should be cleared as fast

    as possible. " bus bar must have its own protection, although they have high degrees

    of reliability. 8earing in mind the ris% of unnecessary trips, the protection should be

    dependable, selective and should be stable for eternal faults, called Hthrough faultsH.

    The most common fault is phase to ground, which usually results from human

    error.

    There are many types of relaying principles used in bus bar.

    " special attention should be made to current transformer selection since

    measuring errors need to be considered.

    i) Isolators

    Isolators are used to connect and disconnect high voltage power systems under no

    load conditions.

    These are essentially off load devices although they are capable of dealing with small

    charging currents of bus bars and connections. The design of isolators is closely related to

    the design of substations. Isolator design is considered in the following aspects

    i. &pace ;actor

    ii. Insulation &ecurity

    iii. &tandardi(ation

    iv. *ase of 4aintenance

    :=

  • 5/20/2018 Substation Design (1)

    48/69

    v. #ost

    Some types of isolators include%

    i. ori(ontal Isolation types

    ii. !ertical Isolation types

    iii. 4oving 8ushing types

    i. ,roperties

    The isolators comprises three identical poles in the case of the three phase system

    only- each pole consisting of

    i. " 'alvani(ed ;abricated 8ase out of 4& #hannel having one supporting

    insulation mounting stool.

    ii. Three post insulators stac%s one for mounting one the centre rotating stool and

    other two stac%s on both ends of the base channel.

    iii. 4oving contact assembly for mounting on the centre rotating insulator stac% and

    the fied contact assembly with terminal pad or two outer insulator stac%s.

    iv. Tandem pipe for interlin%ing the three poles and operating down pipe to lin% the

    tandem pipe with the bottom operating mechanism of 3 phase system.v. 8ottom operating mechanism bo.

    vi. *arthing switch moving contact assembly

    vii. *arthing switch fied contact assembly for fiing to the main switch fied

    contacts.

    viii. *arthing switch operating down pipe to lin% earth switch tandem pipe to the

    bottom

    i. 8ottom operating mechanism bo

    . 4echanical interloc% between main switch and earthling switch.

    !.3 Conclusion

    :6

  • 5/20/2018 Substation Design (1)

    49/69

  • 5/20/2018 Substation Design (1)

    50/69

    The principle dielectric used on overhead power lines is air at atmospheric

    pressure. The air surrounding the bare high voltage threshold. It is however necessary to

    attach the conductors at certain points onto the cross arms of the pylons. The problem of

    reliably suspending the conductors of high voltage transmission lines has therefore been

    with us since the turn of the century. The tas% is particularly comple, bearing in mind the

    multiple etreme stresses present are mechanical, electrical and environmental stresses.

    +.2 Types of Insulators

    a) Porcelain pin type

    insulators

    These were originally used for

    telephone lines and lightning conductors, have

    been adapted for power transmission and some

    variations are still in use for medium voltage

    systems. " pin+type insulator is shown

    schematically in figure 5.2i-and 5.2ii-

    Fig. 6.2(i)

    Porcelain Insulator

    b) Cap and Pin Type Insulators

    The pin+type insulator is so called because in use it is screwed onto a galvani(ed

    forged steel HpinH which mounted vertically on a metal or wooden cross arm.

    ;or low voltage systems, 5.5 to 11 %!, it is usual to have a one+piece insulator

    shed in which the porcelain is loaded largely in compression. " typical pin+type insulator

    is shown in ;igure 5.2ii-.The s%etches show that the top of the porcelain body is formed

    into a groove into which the conductor is bound by means of wire or fied with the aid of

    special clips. Toughened glass pin+type insulators re$uire a metal capQ this holds together

    the HdicedH pieces of glass which result if the glass becomes shattered.

    70

  • 5/20/2018 Substation Design (1)

    51/69

    Fig.62 (ii): shows cap & pin insulator

    c) ,ost Type Insulator

    These insulators consist of a solid porcelain cylinder, corrugated to increase the

    lea%+ age length, with metalware on each end. They are used to support the high voltage

    conductor and are mounted on pedestals or on the power line cross arms. >ost insulators

    are tall and are mainly used in substations. These insulators are #lass "Q the shortest

    distance through the porcelain eceeds 70 of the shortest distance through air between

    the electrodes. They are therefore un puncturable. " typical eample of a post insulator is

    shown schematically in figure 5.2iii-

    $i&.+.28iii)post insulator

    d) Porcelain ong !od Insulators

    Eong rod insulators are similar to post insulators but are lighter, slimmer and are

    71

  • 5/20/2018 Substation Design (1)

    52/69

    used as suspension insulators.

    Eong rod insulators have the apparent advantage over cap and pin insulators in

    that metal fittings eist only at the ends of the insulators.

    +.3 (us#in&s

    8ushings are used to insulate the conductors of the high voltage terminals

    of a transformer as is shown schematically in figure 7. 3 Traditionally, transformer

    bushings are manufactured using porcelain. #apacitive grading, using foil

    cylinders is often used to improve the aial and radial field distribution.

    $i&.+.3 s#os bus#in&s

    +.4 Terminolo&y

  • 5/20/2018 Substation Design (1)

    53/69

    pulled piece of string.

    Inter s#ed spacin&%The distance between corresponding points on ad)acent sheds.

    +.! ,ollution Deposition ,rocess

    Insulators eposed to the environment collect pollutants from various sources.

    >ollutants that become conducting when moistened are of particular concern.

    Two ma)or sources are

    i. #oastal pollution the salt spray from the sea or wind+driven salt laden solid

    material such as sand collects on the insulator surface. These layers become

    conducting during periods of high humidity and fog. &odium chloride is the mainconstituent of this type of pollution.

    ii. Industrial pollution substations and power lines near industrial complees are

    sub)ect to the stac% emissions from nearby plants. These materials are usually dry

    when depositedQ they may then become conducting when wetted. The materials

    will absorb moisture to different degrees, and apart from salts, acids are also

    deposited on the insulator.

    a) T#e role of t#e eat#er

  • 5/20/2018 Substation Design (1)

    54/69

    flash over

    6.6 Failure "odes o# Insulators

    ;lashovers, caused by air brea%down or pollution, generally do not cause physical

    damage to the insulators and the system can often be restored by means of auto closing.

    &ome other events, however cause ir+repairable damage to the insulators.

    a) ,uncture

    "s previously mentioned, porcelain pin+type and cap and pin insulators may suffer

    punctures between the pin and the either the pin or the high voltage conductor.

    These occurrences are usually caused by very steep impulse voltages, where the time

    delay for air flashover eceeds that of puncture of porcelain. >unctures caused by severe

    stress over dry bands also occur on composite insulators on sheds and through the sheath.

    " puncture of the sheath is particularly serious as this eposes the glass fiber rod to the

    environment .

    b) S#atterin&

    'lass insulators shatter when eposed to severe arcing or puncturing due to

    vandalism. ne advantage is that they retain their mechanical integrity.

    c) Erosion

    >rolonged arcing of glass insulators leads to erosion of the surface layer of the

    glass. This may lead to shattering of the glass discs + a result of the tempering processused during manufacture. "rcing and corona over long periods may cause removal of

    shed or sheath material in the case of polymeric insulators. &evere erosion may lead to

    the eposure of the glass fiber core.

    d) Trac@in&

    7:

  • 5/20/2018 Substation Design (1)

    55/69

    Trac%ing occurs when carboni(ed trac%s form because of arcing. These trac%s are

    conductive. This phenomenon only occurs in carbon+based polymers.

    e) (rittle $racture

  • 5/20/2018 Substation Design (1)

    56/69

    and protected from moisture. The disadvantage of greasing is that the spent grease must

    be removed and new grease applied, usually annually.

    c) C#oice of Creep a&e 'en&t#

  • 5/20/2018 Substation Design (1)

    57/69

    possible by good grounding, improves the overall safety and reliability of an electrical

    system. Therefore, substation reliability must be as Obuilt+inO as possible because of the

    high available fault current levels present and unli%ely occurrence of follow+up

    grounding inspections.

    $i&.. s#os &roundin&

    =.2 Types and *et#ods of "roundin&

    There are different types and methods of grounding which ensures the reliable

    performance of a substation.

    a) Types

    'rounding of earth may be classified as i- *$uipment grounding ii- &ystem

    groundingand iii- Deutral grounding.

    *$uipment grounding deals with earthing the non current carrying metal parts of

    the electrical e$uipment. n the other hand, system grounding means earthing some part

    of the electrical system e.g. earthing of neutral point of star connected system in

    generating stations and substations.

    i. Euipment "roundin&

    The process of connecting non current carrying metal parts of the electrical

    e$uipment to earth in such a way that in case of insulation failure, the enclosure

    effectively remains at earth potential is called *$uipment grounding.

    ii. System "roundin&

    7=

  • 5/20/2018 Substation Design (1)

    58/69

    The process of connecting some electrical part of the power system neutral point of

    a star connected system, one conductor of the secondary of a transformer- to earth is

    called &ystem grounding.

    iii. >eutral "roundin&

    The process of connecting neutral point of 3+phase system to earth either directly or

    through some circuit element e.g. resistance or reactance etc.- is called Deutral

    grounding.

    Deutral grounding provides protection to personal and e$uipment. It is because

    during earth fault the current path is completed through the earthed neutral and the

    protective devices operate to isolate the faulty conductor from the rest of the system.

    b) *et#ods of "roundin&

    The methods commonly used for grounding the neutral point of a 3+phase system

    are

    i- &olid or effective grounding ii- esistance grounding

    iii- eactance grounding iv- esonant grounding

    i. Solid "roundin&

    ermits the easy operation of earth fault relay.

    Disad5anta&es%

    a- It causes the system to become unstable.

    76

  • 5/20/2018 Substation Design (1)

    59/69

    b- The increased earth fault current results in greater interference in the neighboring

    communication lines.

    ii. :esistance "roundin&

  • 5/20/2018 Substation Design (1)

    60/69

    b- igh transient voltages appear under fault conditions.

    i5. :esonant "roundin&

    eterson coil grounding as the arc suppression coil used here is the >eterson coil which is

    an iron cored connected between the neutral and earth. The resultant current in the fault

    will be (ero or can be reduced by ad)usting the tappings on the >eterson coil.

    6d5anta&es%

    The >eterson coil grounding has the following advantages

    a- The >eterson coil is completely effective in preventing any damage by an arcingground.

    b- This coil has the advantage of ungrounded neutral system.

    Disad5anta&es%

    The >eterson coil grounding has following disadvantages

    a- ue to varying operational conditions, the capacitance of the networ% changes from

    time to time. Therefore, inductance E of >eterson coil re$uires read)ustment.

    b- The lines should be transposed.

    .3 Eart#in& and (ondin&

    The function of an earthing and bonding system is to provide an earthing system

    connection to which transformer neutrals or earthing impedances may be connected in

    order to pass the maimum fault current. The earthing system also ensures that no

    thermal or mechanical damage occurs on the e$uipment within the substation, thereby

    resulting in safety to operation and maintenance personnel.

    The earthing system also guarantees e$ui+potential bonding such that there are no

    dangerous potential gradients developed in the substation.

    50

  • 5/20/2018 Substation Design (1)

    61/69

    a) Substation Eart#in& Calculation *et#odolo&y

    #alculations for earth impedances and touch and step potentials are based on site

    measurements of ground resistivity and system fault levels. " grid layout with particular

    conductors is then analy(ed to determine the effective substation earthing resistance,

    from which the earthing voltage is calculated. In practice, it is normal to ta%e the highest

    fault level for substation earth grid calculation purposes.

    To determine the earth resistivity, probe tests are carried out on the site. These tests

    are best performed in dry weather such that conservative resistivity readings are obtained.

    b) Eart#in& *aterials

    i) Conductors8are copper conductor is usually used for the substation earthing grid. The

    copper bars themselves usually have a cross+sectional area of ?7 s$uare millimeters, and

    they are laid at a shallow depth of 0.27+0.7m, in 3+=m s$uares. In addition to the buried

    potential earth grid, a separate above ground earthing ring is usually provided, to which

    all metallic substation plant is bonded.

    ii) Connections #onnections to the grid and other earthing )oints should not be soldered

    because the heat generated during fault conditions could cause a soldered )oint to fail.

    Goints are usually bolted, and in this case, the face of the )oints should be tinned.

    iii) Eart#in& :ods The earthing grid must be supplemented by earthing rods to assist in

    the dissipation of earth fault currents and further reduce the overall substation earthing

    resistance. These rods are usually made of solid copper or copper clad steel.

    i5) Sitc#yard $ence Eart#in&% The switchyard fence earthing practices are possibleand are used by different utilities. *tend the substation earth grid 0.7m+1.7m beyond the

    fence perimeter. The fence is then bonded to the grid at regular intervals.

    51

  • 5/20/2018 Substation Design (1)

    62/69

    >lace the fence beyond the perimeter of the switchyard earthing grid and bond the

    fence to its own earthing rod system. This earthing rod system is not coupled to the main

    substation earthing grid.

    .4 Conclusion

    In this chapter we have discussed about the various earthing /grounding techni$ue

    used in substation for the protection of the e$uipment from the high voltage and eternal

    faults.

    0. Introduction

    In this chapter we are going to discuss about the various power factor correction

    techni$ue used in the substation and they mentions as well as protection of this

    e$uipments.

    9nder normal operating conditions certain electrical loads draw not only active

    power from the supply %ilowatts

  • 5/20/2018 Substation Design (1)

    63/69

    This reactive power has no useful function, but is necessary for the e$uipment to operate

    correctly. Eoads such as induction motors, welding e$uipment, arc furnaces and

    fluorescent lighting would fall into this category.

    a) Definition

    The >ower ;actor of a load is defined as being the ratio of active power to total

    demand. The uncorrected power factor of a load is cos S where S is the phase angle

    between the uncorrected load and unity-, and the corrected power factor is cos S2 where

    S2 is the phase angle between the corrected load and unity-. "s cos S approaches to

    unity, reactive power drawn from the supply is minimi(ed

    0.2 Compensatin& Capacitor

    " capacitor inside an op+amp that prevents oscillations is called compensating

    caacitor.. "lso any capacitor that stabili(es an amplifier with a negative+feedbac% path.

    ower factor will be improved by connecting capacitors in parallel to the

    load.

    53

  • 5/20/2018 Substation Design (1)

    64/69

    0.3 ,oer factor correction

    In electric power distribution, capacitors are used for power factor correction. &uch

    capacitors often come as three capacitors connected as a three phase load. 9sually, the

    values of these capacitors are given not in farads but rather as a reactive power in volt+

    amperes reactive !"-. The purpose is to counteract inductive loading from devices li%e

    electric motors and transmission lines to ma%e the load appear to be mostly resistive.

    Individual motor or lamp loads may have capacitors for power factor correction, or larger

    sets of capacitors usually with automatic switching devices- may be installed at a load

    center within a building or in a large utility substation.

    $i&.0.3 ,.$ Correction

  • 5/20/2018 Substation Design (1)

    65/69

    If possible, capacitors should be located at position 2. This does not change the

    current flowing through motor overload protectors. #onnection of capacitors at position 3

    re$uires a change of overload protectors. #apacitors should be located at position 1 for

    applications listed in paragraph 2 above. 8e sure bus power factor is not increased above

    ?7 under all loading conditions to avoid over ecitation.

    The table 6.1 below shows the power factor correction.

    riginal

    >ower

    ;actor

    >ercent

    Desired ,oer $actor ,ercent

    100 ?7 ?0 67 60

    50 1.333 1.00: 0.6:? 0.=13 0.763

    52 1.255 0.?3= 0.=62 0.5:5 0.715

    5: 1.201 0.6=2 0.=1= 0.761 0.:71

    55 1.136 0.60? 0.57: 0.716 0.366

    56 1.0=6 0.=:? 0.7?: 0.:76 0.326

    =0 1.020 0.5?1 0.735 0.:00 0.2=0

    =2 0.?5: 0.537 0.:60 0.3:: 0.21:

    =: 0.?0? 0.760 0.:27 0.26? 0.17?

    =5 0.677 0.725 0.3=1 0.237 0.107

    =6 0.602 0.:=3 0.316 0.162 0.072

    =? 0.==5 0.::= 0.2?2 0.175 0.025

    60 0.=70 0.:21 0.255 0.130 +

    61 0.=2: 0.3?7 0.2:0 0.10: +

    62 0.5?6 0.35? 0.21: 0.0=6 +

    63 0.5=2 0.3:3 0.166 0.072 +6: 0.5:5 0.31= 0.152 0.205 +

    67 0.520 0.2?1 0.135 + +

    65 0.7?3 0.25: 0.10? + +

    6= 0.75= 0.236 0.063 + +

    57

  • 5/20/2018 Substation Design (1)

    66/69

    6? 0.712 0.163 0.026 + +

    ?0 0.:6: 0.177 + + +

    ?1 0.:75 0.12= + + +

    ?2 0.:25 0.0?= + + +

    ?3 0.3?7 0.055 + + +

    ?: 0.353 0.03: + + +

    ?7 0.32? + "ssume Total plant load is 100

    < at 50 power factor.

    #apacitor !" rating

    necessary to improve power

    factor to 60 is found by

    multiplying < 100- by the

    multiplier in table 0.763-

    which gives !" 76.3-,

    nearest standard rating 50

    !"- should be used.

    ?5 0.2?2 +

    ?= 0.271 +

    ?? 0.1:3 +

    The connection of a capacitor capable of OcorrectingO half of the reactive power

    of a load leads to a reduction in the demand on the supply of approimately 17. This

    results in the following

    a- The load on the cables and switches is reduced.

    b- The supply is now able to support additional load

    c- The charges made by the electricity supply company are li%ely to be reduced

    8y reducing the load on cables and switches, power loss is reduced and life is

    etended. The facility to connect additional load is always useful to an epanding

    company.

    0.4 Conclusion

    In this chapter we have discussed about the various power factor correction

    techni$ues involved in substation and benefits of it.

    55

  • 5/20/2018 Substation Design (1)

    67/69

    In our pro)ect we have studied about the operation of different e$uipments in

    substation. It includes study of transmission lines, bus bars, circuit brea%ers, isolators,

    earth switches, current transformers, voltage transformers, lightning arresters, wave traps

    and grounding system of substation.

  • 5/20/2018 Substation Design (1)

    68/69

    (I('I9":6,B?

    1. *lectric >ower &ubstations *ngineering 8y James C. Burke and Anne-Marie

    Sahazizian.>ublisher ##.

    2. *lectric >ower &ystems " #onceptual Introduction 8y "leandra von 4eier

    >ublisher .!.'upta,9.&

    8hatnagar.

    >ublisher hanpat ai C #o

    7. Transmission, istribution and 9tili(ation !olume III, 8y 8.E.T*"G" C

    "..T*"G"

    >ublisher &.#"D C #4>"DF ET. 200:

    56

  • 5/20/2018 Substation Design (1)

    69/69

    5?