Page 1: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

ProtoNodeRERandProtoNodeLER

StartupGuideForInterfacingInfiniteEnergy2Products:

ArgusManaging/StandaloneBoilerandDependentBoilerToBuildingAutomationSystems:

BACnetMS/TP,BACnet/IP,Modbus/TCP,MetasysN2andLonWorks

Page 2: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page2of44

AQuickStartguide

1. Recordtheinformationabouttheunit.(SeeSection2.1)

2. Setthedevice’sModbusRTUserialsettings(i.e.baudrate,parity,stopbits)andModbusNode-IDforeachofthedevicesthatwillbeconnectedtoProtoNodeFPC-N34orFPC-N35.(Section2.2)

3. SettheProtoNodeFieldProtocolonSBankDIPSwitchesforBACnetMS/TP,BACnet/IP,ModbusRTUorMetasysN2.(Seesection2.3.11)

4. EnabletheProtoNode“AutoDiscovery”modeonDipSwitchBankS.(Seesection2.3.1)

5. SettheBACnetMS/TPMACAddressonDIPSwitchBankA.(Seesection2.4)

6. SetBACnetdevice addresses for ProtoNode FPC-N34:BACnetMS/TPhasboth aMACAddress and aDeviceInstance.BACnet/IPonlyhasaDeviceInstance.(Section2.4)

7. SettheBACnetMS/TPBAUDrateoftheFieldProtocolonDIPSwitchBankB.(Seesection2.5.15)

8. Connect FPC-N34 ProtoNode’s 3 pin RS-485 port to the Field Protocol cabling, or connect FPC-N35ProtoNode’s2pinLonWorksporttotheFieldProtocolcabling.

9. ConnectProtoNode’s6pinRS-485connectortotheModbusRS-485networkthatisconnectedtoeachofthedevices.(Section3)

10. ConnectPower toProtoNodeRERorLER. Itwill takeabout3minutes forall theOEMdevices tobediscovered,andtheconfigurationfiletobebuilt.(SeeSection3.5)

11. OncetheProtoNodehasfinishedcreatingtheconfigurationfile,setthe“AutoDiscovery”DipSwitchto“Off”tosavetheconfigurationsettings.(SeeSection3.5)

12. WheretheFieldprotocolisBACnet/IPorModbus/TCP,runProtoNodeWebGUIutilityprogramtochangetheIPaddress.Nochangestotheconfigurationarenecessary.(Section4)

13. ProtoNodeFPC-N35unitsmustbecommissionedontheLonWorksNetwork.ThisneedstobedonebytheLonWorksadministratorusingaLonWorksCommissioningtool.(SeeSection5)

Page 3: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page3of44

Certifications

§ BTLMARK–BACNETTESTINGLABORATORY

§ LONMARKCERTIFICATION

TheBTLMarkonProtoNodeRERisasymbolthatindicatesthataproducthaspassedaseriesofrigoroustestsconductedbyanindependentlaboratorywhichverifiesthattheproductcorrectly implementstheBACnetfeaturesclaimed inthe listing. Themark is a symbol of a high-quality BACnet product. Go tohttp://www.bacnetinternational.net/btl/ for more information about the BACnetTestingLaboratory.

LonMarkInternationalistherecognizedauthorityforcertification,education,andpromotion of interoperability standards for the benefit of manufacturers,integratorsandendusers.LonMarkInternationalhasdevelopedextensiveproductcertificationstandardsandteststoprovidetheintegratoranduserwithconfidencethatproductsfrommultiplemanufacturersutilizingLonMarkdevicesworktogether.FieldServer Technologies has more LonMark Certified gateways than any othergatewaymanufacturer,includingtheProtoCessor,ProtoCarrierandProtoNodeforOEMapplicationsandthefullfeatured,configurablegateways.

Page 4: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page4of44

TABLEOFCONTENTS

Introduction.........................................................................................................................................................6 1.1 ProtoNodeGateway......................................................................................................................................6 1.2 DevicesandPointCountAvailable................................................................................................................6

2 BACnet/LonWorksSetupforProtoCessorProtoNodeRER/LER.....................................................................7 2.1 RecordIdentificationData............................................................................................................................7 2.2 ConfigureModbusRTUCOMSettingsontheDevicesConnectedtoProtoNodeRER(FPC-N34)andProtoNodeLER(FPC-N35LonWorks)........................................................................................................................7 2.3 SelecttheDesiredFieldProtocol–BACnetMS/TP,BACnet/IP,Modbus/TCPorMetasysN2viaSBankDIPSwitchesforProtoNodeRER(FPC-N34BACnet).......................................................................................................8

2.3.1 UsingS0–S3bankofDIPSwitches.......................................................................................................8 2.4 SetMACAddressforBACnetMS/TP;SetDeviceInstanceforBACnetMS/TPandBACnet/IP;SetNode-IDforMetasysN2andModbus/TCPonProtoNodeRER(FPC-N34).............................................................................9

2.4.1 SettingtheMACAddressforBACnetMS/TPforProtoNodeRER(FPC-N34BACnet).............................9 2.4.2 SettingtheDeviceInstance(Node-ID)forBACnetMS/TPandBACnet/IPonProtoNodeRER(FPC-N34BACnet) 9 2.4.3 SettingtheDeviceNode-IDforMetasysN2andModbus/TCPonProtoNodeRER(FPC-N34MetasysN2) 11

2.5 SetBaudRateforBACnetMS/TPonProtoNodeRER(FPC-N34BACnet)....................................................11 2.5.1 SettingtheSerialBaudRate(DIPSwitchB0–B3)forBACnetMS/TP.................................................11

3 InterfacingProtoNodetoDevices...............................................................................................................12 3.1 ProtoNodeRER(FPC-N34)andLER(FPC-N35)ShowingConnectionPorts.................................................12 3.2 WiringConnectionstoProtoNodeRER(FPC-N34BACnet)andProtoNodeLER(FPC-N35LonWorks).......13

3.2.1 BiasingtheModbusRS-485Network..................................................................................................13 3.2.2 EndofLineTerminationSwitchfortheModbusRS-485portontheProtoNode.................................14

3.3 WiringProtoNodeRERtoRS-485FieldProtocol(BACnetMS/TPorMetasysN2)......................................15 3.4 WiringProtoNodeLER(FPC-N35)FieldPorttoaLonWorksNetwork........................................................15 3.5 Power-UpProtoNodeRER(FPC-N34BACnet)orProtoNodeLER(FPC-N35LonWorks)andAuto-DiscoverModbusRTUDevicesconnectedtotheProtoNode................................................................................................16

3.5.1 Auto-DiscoverAllDevices,BuildandAutomaticallyLoadsConfigurationFile....................................17 4 ChangetheprotonodeIPaddressusingthewebGUIforBACnet/ipandmodbustcp..................................19

4.1 ConnectthePCtoProtoNodeviatheEthernetPort...................................................................................19 4.2 UsetheProtoNodeWebGUItoConnecttotheProtoNode.......................................................................20 4.3 SetIPAddressforBACnet/IPandModbusTCP...........................................................................................21

5 CommissioningProtoNodeLERonaLonWorksNetwork.............................................................................23 5.1 CommissioningProtoNodeLERonaLonWorksNetwork...........................................................................23

5.1.1 InstructionstoUploadXIFFilefromProtoNodeLERUsingFieldServerGUIWebServer.....................23 6 CASBACnetExplorerforValidatingProtoNodeintheField.........................................................................25

6.1 DownloadingtheCASExplorerandRequestinganActivationKey.............................................................25 6.2 CASBACnetSetup.......................................................................................................................................26

6.2.1 CASBACnetMS/TPSetup....................................................................................................................26 6.2.2 CASBACnetBACnet/IPSetup...............................................................................................................26

AppendixA.Troubleshooting.............................................................................................................................27 AppendixA.1.CheckWiringandSettings...............................................................................................................27 AppendixA.2.TakeDiagnosticCaptureWiththeFieldServerUtilities...................................................................27 AppendixA.3.SettingtheNetworkNumberforBACnet/IPwhenmorethanoneProtoNodeisonthesameSubnet.....................................................................................................................................................................30 AppendixA.4.LEDDiagnosticsforModbusRTUCommunicationsBetweenProtoNodeandDevices...................30

AppendixB.VendorInformation-Cosmogas.....................................................................................................31 AppendixB.1.ArgusModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2andLonWorks..............31

AppendixC.MACAddressDIPSwitchSettings...................................................................................................37

Page 5: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page5of44

AppendixC.1.MACAddressDIPSwitchSettings....................................................................................................37 AppendixD.Reference.......................................................................................................................................40

AppendixD.1.Specifications...................................................................................................................................40 AppendixD.1.1. CompliancewithULRegulations...........................................................................................40

AppendixE.CascadeconnectionwithMODBUS.................................................................................................41 AppendixE.1.ExampleofMODBUSconnectionforheaterswithserialnumberupto14999999.........................41 AppendixE.2.ExampleofMODBUSconnectionforheaterswithserialnumberhigherthan15000000...............42

Page 6: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page6of44

INTRODUCTION

1.1 ProtoNodeGateway

ProtoNodeisanexternal,highperformanceBuildingAutomationmulti-protocolgatewaythatispreconfiguredtoAuto-Discoveranyof the IE2products (hereaftercalled“device”)connectedtotheProtoNodeandautomaticallyconfiguresthemforBACnet®1MS/TP,BACnet/IP,Metasys®2N2byJCI,ModbusTCPorLonWorks®3.Itisnotnecessarytodownloadanyconfigurationfilestosupporttherequiredapplications.

1.2 DevicesandPointCountAvailable

• The total number of devices attached to ProtoNode RER (FPC-N34) cannot exceed 1500 ModbusregistersforBACnetMS/TP,BACnet/IP,Modbus/TCPorMetasysN2.

o “RER”485isadescriptionoftheavailableports:RS-485+Ethernet+RS-485

• The total number of devices attached to ProtoNode LER (FPC-N35) cannot exceed 1000 ModbusregistersforLonWorks.

o “LER”isadescriptionoftheavailableports:LonWorks+Ethernet+RS-485

Devices PointCount

ArgusManaging/StandaloneBoiler 94DependentBoiler 48

Figure1:ModbusRegisters

1BACnetisaregisteredtrademarkofASHRAE2MetasysisaregisteredtrademarkofJohnsonControlsInc.3LonWorksisaregisteredtrademarkofEchelonCorporation

Page 7: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page7of44

2 BACNET/LONWORKSSETUPFORPROTOCESSORPROTONODERER/LER

2.1 RecordIdentificationData

EachProtoNodehasauniquepartnumber locatedon theundersideof theunit. Thisnumber shouldberecorded,asitmayberequiredfortechnicalsupport.Thenumbersareasfollows:

Model PartNumber

ProtoNodeRER FPC-N34-0948ProtoNodeLER FPC-N35-103-401-0953

Figure2:ProtoCessorPartNumbers

2.2 Configure Modbus RTU COM Settings on the Devices Connected to ProtoNode RER(FPC-N34)andProtoNodeLER(FPC-N35LonWorks)

• AlldevicesconnectedtoProtoNodeMUSTALLhavethesameBaudRate,DataBits,StopBits,andParity.(Figure3)

• Thefigurebelowdefinestheinstalleddefaultserialportsettingsnecessarytocommunicatewiththedevice.

SerialPortSetting Device

Protocol ModbusRTUBaudRate 9600Parity NoneDataBits 8StopBits 1

Figure3:ModbusRTUCOMSettings

• SetModbusNode-IDforeachofthedevicesattachedtoProtoNode.TheModbusNode-ID’sneedtobeuniquelyassignedbetween1and255.

o TheModbusNode-IDthatisassignedforeachdeviceneedstobedocumented.

o TheModbusNode-ID’sassignedareusedfordesignatingtheDeviceInstanceforBACnet/IPandBACnetMS/TP(Seesection2.4.2)

o TheMetasysN2andModbus/TCPNode-IDwillbesettosamevalueastheNode-IDoftheModbusRTUdevice

Page 8: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page8of44

2.3 SelecttheDesiredFieldProtocol–BACnetMS/TP,BACnet/IP,Modbus/TCPorMetasysN2viaSBankDIPSwitchesforProtoNodeRER(FPC-N34BACnet)

2.3.1 UsingS0–S3bankofDIPSwitches

• TheSbankofDIPswitches,S0–S2isusedtoselectBACnetMS/TP,BACnet/IP,Modbus/TCP,orMetasysN2onProtoNodeRER.

• TheS3DIPswitchisusedtoenableAuto-DiscoveryofknowndevicesattachedtotheProtoNodeRERandLER(LonWorks),aswellassavetherecentlydiscoveredconfiguration.WhentheS3DIPisOff,theProtoNodewillloadthecurrentsaveconfiguration.TurnS3toOn,iftheProtoNodeisbeinginstalledforthefirsttime.

• TheSbankofDIPswitchesonProtoNodeLERisdisabled.

• The following chart describes S0 – S2 DIP switch configuration settings for the devices to supportBACnetMS/TPorBACnet/IPonaProtoNodeRER.

• WhentheSbankofswitchesarealloff(defaultsetting)BACnet/IPisenabled.

• TheOFFpositioniswhentheDIPswitchesaresetclosesttotheoutsideofthebox.

ProtoNodeRER SBankDIPSwitches

Profile S0 S1 S2 S3BACnetIP Off Off Off OffBACnetMSTP On Off Off OffMetasysN2 Off On Off OffModbusTCP On On Off Off

S0 S1 S2 S3

S0–S3DIPSwitches

SBankDIPSwitchLocation

BACnetMS/TP,BACnet/IP,Modbus/TCP,andMetasysN2SettingsforProtoNodeRER(FPC-N34BACnet)

Figure4:SBankDIPSwitches

Page 9: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page9of44

2.4 Set MAC Address for BACnet MS/TP; Set Device Instance for BACnet MS/TP andBACnet/IP;SetNode-IDforMetasysN2andModbus/TCPonProtoNodeRER(FPC-N34)

2.4.1 SettingtheMACAddressforBACnetMS/TPforProtoNodeRER(FPC-N34BACnet)

• Only1MACaddressissetforProtoNoderegardlessofhowmanydevicesareconnectedtoProtoNode.

• Set the BACnetMS/TPMAC address of the ProtoNode to a value between 1 to 127 (MasterMACaddress);thisissothattheBMSFrontEndcanfindProtoNodeviaBACnetautodiscovery.

• Note:Never set a BACnet MS/TP MAC Address of the ProtoNode to a value from 128 to 255.Addressesfrom128to255areSlaveAddressesandcannotbediscoveredbyBMSFrontEndsthatsupportAutoDiscoveryofBACnetMS/TPdevices.

• SetDIPswitchesA0–A7toassignMACAddressforBACnetMS/TPfortheProtoNodeRER(FPC-N34).

• PleaserefertoAppendixC.1forthecompleterangeofMACAddressesandDIPswitchsettings.

• WhenusingMetasysN2andModbus/TCP,theABankofDIPswitchesaredisabledandnotused.TheyshouldbesettoOFF.

NOTE:WhensettingDIPSwitches,pleaseensurethatpowertotheboardisOFF.

2.4.2 Setting the Device Instance (Node-ID) for BACnet MS/TP and BACnet/IP onProtoNodeRER(FPC-N34BACnet)

• TheABankofDIPswitchesarealsousedtosettheBACnetDeviceInstances.

• TheBACnetdeviceinstanceswillbecalculatedbytakingtheNode_OffsetfoundinWebConfiguratorandaddingittotheModbusNode-IDthatwasassignedtothedevice(Section2.2).TheBACnetDeviceInstancecanrangefrom1to4,194,303.

Forexample:

o Node_Offsetdefault=50,000

o Device1hasaModbusNode-IDof1,Device2hasaModbusNode-IDof2,Device3hasaModbusNode-IDof3

o Device1-DeviceInstance=50,001

o Device2-DeviceInstance=50,002

o Device3-DeviceInstance=50,003

o Tochangethenode_offsetseeSection2.4.2.1.Thenodeoffsetcanbechangedfrom50,000to1to4,194,302viatheWebConfigurator.

2.4.2.1 SetNode_OfftoAssignSpecificDeviceinstancesforBACnetMS/TPandBACnet/IP

Figure5:MACAddressDIPSwitches

Page 10: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page10of44

• IftheDeviceInstancesneedtobesetforaddressesotherthan50,000to50,127,changetheNode+-

Offset(50,000isthedefaultforNode+Offset).SeeSection4.1tosetthePC’sIPaddresstothesameSubnetastheProtoNodeandSection4.2toconnecttotheProtoNode’sWebConfiguratorwhichisshowninFigure6.

• TheBACnetDeviceInstancecanrangefrom1to4,194,303.

• BACnet/IP/BACnet MS/TP Addressing: The BACnet device instances will be set by taking theNode_OffsetfoundinWebConfigurator(seeFigure6)andaddingittotheModbusNode-IDthatwasassignedtothedevice(Section2.2).

• SetthePC’sIP-addresstobeonthesamesubnetastheProtoNode.Seesection4.1onhowtochangetheIPaddress.

• OpenthePCbrowser;enterthedefaultIPaddressofProtoNode192.168.1.24,whichwillbringyoutotheFSTWebConfiguratorlandingpagefortheProtoNode.(SeeFigure6)

• ChangetheNode+Offsettomeettherequireddeviceinstance.

Forexample:RequiredDeviceInstance=20,001

o Node_Offsetchangedto=20,000.

o Device1hasaModbusNode-IDof1,Device2hasaModbusNode-IDof2,Device3hasaModbusNode-IDof3

o Device1-DeviceInstance=20,001

o Device2-DeviceInstance=20,002

o Device3-DeviceInstance=20,003

NOTE:TheModbusNodeaddress+Node_Offset=DeviceInstancesetting

Figure6:FSTWebGUIscreen

Page 11: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page11of44

2.4.3 SettingtheDeviceNode-IDforMetasysN2andModbus/TCPonProtoNodeRER(FPC-N34MetasysN2)

• TheModbusRTUNode-ID’sassignedtothedevicesattachedtotheProtoNodeinSection2.2willbetheMetasyN2andModbusTCPNode_ID’sforthefieldprotocols.

• MetasysN2andModbus/TCPNode-IDAddressing:MetasysN2andModbus/TCPNode-ID’srangefrom1-255.

2.5 SetBaudRateforBACnetMS/TPonProtoNodeRER(FPC-N34BACnet)

2.5.1 SettingtheSerialBaudRate(DIPSwitchB0–B3)forBACnetMS/TP

• DIPSwitchesB0–B3canbeusedtosettheserialbaudratetomatchthebaudrateprovidedbytheBuildingManagementSystemforBACnetMS/TP.

• DIPSwitchesB0–B3aredisabledonProtoNodeLER(FPC-N35LonWorks).

• ThebaudrateonProtoNode forMetasysN2 is set for9600.DIPSwitchesB0–B3aredisabled forMetasysN2onProtoNodeRER(FPC-N34).

B0 B1 B2 B3

2.5.1.1 BaudRateDIPSwitchSelection

Baud B0 B1 B2 B3

9600 On On On Off19200 Off Off Off On38400 On On Off On57600 Off Off On On76800 On Off On On

Figure8:BaudRate

Figure7:BaudRateDIPSwitches

Page 12: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page12of44

3 INTERFACINGPROTONODETODEVICES

3.1 ProtoNodeRER(FPC-N34)andLER(FPC-N35)ShowingConnectionPorts

Figure9:ProtoNodeBACnetRER(upper)andProtoNodeLER(lower)

Page 13: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page13of44

3.2 WiringConnectionstoProtoNodeRER(FPC-N34BACnet)andProtoNodeLER(FPC-N35LonWorks)

ProtoNode6PinPhoenixconnector–PinoutstoModbusRTUProducts• The6pinPhoenixconnectoristhesameforProtoNodeRER(FPC-N34BACnet)andProtoNode(FPC-

N35LonWorks).Pins1through3areforModbusRS-485tothedevicesandpins4through6areforpower.

3.2.1 BiasingtheModbusRS-485Network

• AnRS-485networkwithmorethanonedeviceneedstohavebiasingtoensurepropercommunication.Thebiasingneedstobedoneononedevice.

• TheProtoNodehasa510Ohmresistor switch that isused toset thebiasing. TheProtoNode’sdefaultpositionfortheBiasingswitchisOFFfromthefactory.

• ThebiasingMUSTalwaysbeleftintheOFFposition.TheOFFpositioniswhenthe2REDbiasingjumpersstraddlethe4pinsclosesttotheoutsideoftheboardoftheProtoNode.SeeFigure11.

• It is recommended that the biasing be left in the OFF position, unless there is a problem withcommunicatingwithmorethanonedevice,thentrysettingthebiasingtoON.

DevicePins ProtoNodePin# PinassignmentPinRS-485+ Pin1 RS-485+PinRS-485- Pin2 RS-485-PinGND Pin3 RS-485GND

PowerIn(+) Pin4 V+PowerIn(-) Pin5 V-

FrameGround Pin6 FRAMEGND

Figure10:PowerandRS-485Connections

Page 14: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page14of44

3.2.2 EndofLineTerminationSwitchfortheModbusRS-485portontheProtoNode

• OnlongRS-485cablingruns,theRS-485trunkmustbeproperlyterminatedateachend.• IftheProtoNodeisplacedatoneoftheendsofthetrunk,youturntheBlueRS-485End-of-Line

TerminatingswitchtoONposition.• OnshortcablingrunstheEOLswitchdoesnottoneedtobeturnedON.ThedefaultsettingforthisBlue

EOLswitchisOFF.• AlwaysleavethesingleRedJumperintheAposition.

ModbusRS-485EOLSwitch

LeaveinAPosition

RS-485BiasSwitch

Figure11:ModbusRS-485BiasingSwitchontheProtoNodeN34(left)andProtoNodeN35(right)

Figure12:ModbusRS-485End-Of-LineTerminationSwitchontheProtoNodeN34(left)andProtoNodeN35(right)

Page 15: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page15of44

3.3 WiringProtoNodeRERtoRS-485FieldProtocol(BACnetMS/TPorMetasysN2)

• ConnectBMSBACnetMS/TPorMetasysN2RS-485porttothe3-pinRS-485connectoronProtoNodeRERasshownbelow.

• SeeSection4.1forinformationonconnectingProtoNodeRERtoBACnet/IPnetwork.

• IftheProtoNodeisthelastdeviceontheBACnetMS/TPorMetasysN2trunk,thentheEnd-Of-LineTerminatorneedstobeenabled(SeeFigure14).Itisdisabledbydefault.

3.4 WiringProtoNodeLER(FPC-N35)FieldPorttoaLonWorksNetwork

• ConnectProtoNodetothefieldnetworkwiththeLonWorksterminalusingatwistedpairnon-shieldedcable.LonWorkshasnopolarity.

BMSRS-485Wiring

ProtoNodePin#

PinAssignment

RS-485+ Pin1 RS-485+RS-485- Pin2 RS-485-

- Pin3 RS-485GND G-

+

Figure13:ConnectionfromProtoNodetoRS-485FieldProtocol–BACnetMS/TP

Figure14:RS-485EOLSwitch

Figure15:LonWorksTerminal

End-of-LineSwitch

Page 16: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page16of44

3.5 Power-Up ProtoNode RER (FPC-N34 BACnet) or ProtoNode LER (FPC-N35 LonWorks)andAuto-DiscoverModbusRTUDevicesconnectedtotheProtoNode.

ApplypowertoProtoNode.EnsurethatthepowersupplyusedcomplieswiththespecificationsprovidedinAppendixD.1.Ensurethatthecableisgroundedusingthe“Frame-GND”terminal.ProtoNodeacceptseither9-30VDCor12-24VAC.

PowerRequirementforProtoNodeat9Vthrough30VDCor12-24VAC

CurrentDrawType

ProtoNodeFamily 12VDC/VAC 24VDC/VAC 30VDC

FPC–N34(Typical) 170mA 100mA 80mA

FPC–N34(Maximum) 240mA 140mA 100mA

FPC–N35(Typical) 210mA 100mA 90mA

FPC–N35(Maximum) 250mA 130mA 100mANote:Thesevaluesare‘nominal’andasafetymarginshouldbeaddedtothepowersupplyofthehostsystem.Asafetymarginof25%isrecommended.

Figure16:RequiredcurrentdrawfortheProtoNode

PowertoProtoNode

ProtoNodePin#

PinAssignment

PowerIn(+) Pin4 V+PowerIn(-) Pin5 V-

FrameGround Pin6 FRAMEGND

Figure17:PowerConnections

Page 17: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page17of44

3.5.1 Auto-DiscoverAllDevices,BuildandAutomaticallyLoadsConfigurationFile

ThefollowingchartdescribesS3DIPSwitchsettingfortheEnablingAuto-DiscoveringofknowndevicesattachedtotheProtoNodeRERorLER.

• SetS3DIPswitchtoturnOnpositiontoAuto-DiscoveranyoftheproductsattachedtotheProtoNode(makesurepowerisoffwhensettingtheswitch)

• WhentheProtoNodeiswiredtotheModbusdevices,turnonthepower.Itwilltake3minutestodiscoverallModbusRTUdevicesattachedtotheProtoNode.

• Once theProtoNodehasdiscoveredallof theModbusRTUdevices, set theS3DIPswitch to theOFFpositiontosavetherecentlybuiltconfiguration.

ProtoNodeRERandLER

S3DIPSwitchAuto-DiscoveryMode S3Auto-DiscoveryON–BuildNewConfiguration OnAuto-DiscoverOFF–LoadCurrentConfiguration Off

Figure18:S3DIPSwitchsettingforAutoDiscoveringDevices

TypicalinstallationforProtoNodeRER(BACnetIPandMS/TP)andProtoNodeLERforLonworksareshowedinthefiguresbelow:

Figure19:ConnectionwiringProtoNodeRERforBACnetIP

Page 18: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page18of44

Figure20:ConnectionwiringProtoNodeRERforBACnetMS/TP

Figure21:ConnectionwiringProtoNodeLERforLonWorks

Page 19: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page19of44

4 CHANGETHEPROTONODEIPADDRESSUSINGTHEWEBGUIFORBACNET/IPANDMODBUSTCP

4.1 ConnectthePCtoProtoNodeviatheEthernetPort

• ConnectastandardCAT5Ethernetcable(StraightthroughorCross-Over)betweenthePCandProtoNode

• The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC andProtoNodeareondifferentIPNetworks,assignastaticIPAddresstothePConthe192.168.1.xxxnetwork

• Goto > >

• Right-clickonLocalAreaConnection>Properties

• Highlight >

• Select:UsethefollowingIPaddress

• Click twice

Figure22:EthernetPortLocation

EthernetPort

Page 20: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page20of44

4.2 UsetheProtoNodeWebGUItoConnecttotheProtoNode

• OpenaPCwebbrowserandenterthedefault IPaddress192.168.1.24oftheProtoNode. Thebrowser’sdisplayofthemainlandingpagefortheProtoNode(Figure20)confirmstheProtoNodeiscommunicating

• UnderActiveProfiles,thediscoveredModbusRTUdeviceswiththeassociatedModbusRTUNodeID’scanbeseen. Ifnoprofilesarepresent,thenthewiring,baudrate,andDIPswitchsettingsmustbechecked,becausethereisaproblemwiththeModbusCOMs.AlltheactivedevicesmustshowthecorrectModbusNode-ID’sbeforeproceeding.

Figure23:FSTWebGUIscreen

Page 21: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page21of44

4.3 SetIPAddressforBACnet/IPandModbusTCP

• OpenaPCwebbrowser,enterthedefaultIPaddressoftheProtoNode192.168.1.24andconnecttotheProtoNode.

• FromtheGUImainlanding,clickonDiagnosticsandDebuggingtogettotheUtilitiessectionoftheGUI(tochangeIPAddressandothercapabilities).(SeeFigure25)

• From theGUI’s Utility page, click on setup and thenNetwork Settings to enter the Edit IP AddressSettingsmenu.

• ModifytheIPaddress(N1IPaddressfield)oftheProtoNodeEthernetport.

• Ifnecessary,changetheNetmask(N1Netmaskfield).

• TypeinanewSubnetMask

• Ifnecessary,changetheIPGateway(DefaultGatewayfield)

• TypeinanewIPGateway

• Note:IftheProtoNodeisconnectedtoarouter,theIPGatewayoftheProtoNodeshouldbesettotheIPaddressoftherouterthatitisconnectedto

• ResetProtoNode

• UnplugEthernetcablefromPCandconnectittothenetworkhuborrouter

Figure24:FSTWebGUIUtilitiespage

Page 22: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page22of44

Figure25:ChangingIPAddressviaFSTWebGUI

Page 23: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page23of44

5 COMMISSIONINGPROTONODELERONALONWORKSNETWORK

CommissioningmayonlybeperformedbytheLonWorksadministrator.

5.1 CommissioningProtoNodeLERonaLonWorksNetwork

TheUserwillbepromptedbytheLonWorksAdministratortohittheServicePinontheProtoNodeLERatthecorrectstepoftheCommissioningprocesswhichisdifferentforeachLonWorksNetworkManagementTool.• IfanXIFfileisrequired,seestepsinSection5.1.1togenerateXIF

5.1.1 Instructions to Upload XIF File from ProtoNode LER Using FieldServer GUI WebServer

• Connectastandardcat5EthernetcablebetweenthePCandProtoNode

• TheDefault IPAddressofProtoNode is192.168.1.24, SubnetMask is255.255.255.0. If thePCandProtoNode are ondifferent IPNetworks, assign a static IPAddress to the PCon the 192.168.1.xxxnetwork

• ForWindowsXP:

Goto > >

Right-clickonLocalAreaConnection>Properties

Highlight >

• ForWindows7:

Goto > >

> >

Right-clickonLocalAreaConnection>Properties

Highlight >

• ForWindowsXPandWindows7,select:UsethefollowingIPaddress

Figure26:LonWorksServicePinLocation

Page 24: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page24of44

• Click twice

• Openawebbrowserandgotothefollowingaddress:IPaddressofProtoCessor/fserver.xif• Example:192.168.1.24/fserver.xif• Ifthewebbrowserpromptsyoutosavefile,savethefileontothePC.Ifthewebbrowserdisplays

thexiffileasawebpage,savethefileonyourPCasfserver.xif

Figure27:SampleofFserver.XIFFileBeingGenerated

Page 25: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page25of44

6 CASBACNETEXPLORERFORVALIDATINGPROTONODEINTHEFIELD

ProtoCessorhasarrangedacomplementary2weekfullyfunctionalcopyofCASBACnetExplorer(throughChipkin Automation) that can be used to validate BACnet MS/TP and/or BACnet/IP communications ofProtoNodeinthefieldwithouthavingtohavetheBMSIntegratoronsite.ASerialorUSBtoRS-485converterisneededtotestBACnetMS/TP.

6.1 DownloadingtheCASExplorerandRequestinganActivationKey

• TorequestthecomplementaryBACnetCASkey,gotohttp://app.chipkin.com/activation/twoweek/andfillinalltheinformation.EnterVendorCode“Cosmogas2014”.Oncecompleted,thekeywillbesenttotheemailaddressthatwassubmitted.Fromthisemail,thelongkeywillneedtobecopiedandpastedintotheCASkeyactivationpage.

• Gotothefollowingwebsite,downloadandinstalltheCASBACnetExplorertoyourPC:http://www.chipkin.com/technical-resources/cas-bacnet-explorer/

• IntheCASActivationform,entertheemailaddressandpastetheCASkeythatwassent.Oncecompleted,selectActivation.

Figure28:DownloadingtheCASExplorer

Figure29:RequestingCASActivationKey

Page 26: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page26of44

6.2 CASBACnetSetup

ThesearetheinstructionstosetCASExplorerupforthefirsttimeonBACnetMS/STandBACnet/IP.

6.2.1 CASBACnetMS/TPSetup

• UsingtheSerialorUSBtoRS-485converter,connectittoyourPCandthe3PinBACnetMS/TPconnectoronProtoNodeRER.

• InCASExplorer,dothefollowing:

o Clickonsettings

o ChecktheBACnetMSTPboxandunchecktheBACnet/IPandBACnetEthernetboxes

o SettheBACnetMSTPMACaddressto0

o SettheBACnetMSTPBaudRateto38400

o ClickOk

o Onthebottomright-handcorner,makesurethattheBACnetMSTPboxisgreen

o Clickondiscover

o Checkall4boxes

o ClickSend

6.2.2 CASBACnetBACnet/IPSetup

• SeeSection5.1tosettheIPaddressandsubnetofthePCthatwillberunningtheCASExplorer.

• ConnectastraightthroughorcrossEthernetcablefromthePCtoProtoNode.

• InCASExplorer,dothefollowing:

o Clickonsettings

o ChecktheBACnet/IPboxandunchecktheBACnetMSTPandBACnetEthernetboxes

o Inthe“SelectaNetworkDevice”box,selectthenetworkcardofthePCbyclickingonit

o ClickOk

o Onthebottomright-handcorner,makesurethattheBACnet/IPboxisgreen

o Clickondiscover

o Checkall4boxes

o ClickSend

Page 27: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page27of44

AppendixA. Troubleshooting

AppendixA.1. CheckWiringandSettings

• NoCOMSonModbusRTUside.IfTx/RxarenotflashingrapidlythenthereisaCOMissueontheModbussideandyouneedtocheckthefollowingthings:o VisualobservationsofLEDsonProtoNode.(AppendixA.4)o Checkbaudrate,parity,databits,stopbitso CheckModbusdeviceaddresso Verifywiringo VerifyalltheModbusRTUdevicesthatwerediscoveredinFSTWebConfigurator.(SeeSection204.2)

• FieldCOMproblems:o VisualobservationsofLEDsonProtoNode.(AppendixA.4)o Visualdipswitchsettings(usingcorrectbaudrateanddeviceinstance)o VerifyIPaddresssettingo Verifywiring

Iftheproblemstillexists,aDiagnosticCaptureneedstobetakenandsenttoFieldServer.(AppendixA.2)

AppendixA.2. TakeDiagnosticCaptureWiththeFieldServerUtilities

• Once the log isDiagnosticCapture is complete,email it to support@protocessor.com.TheDiagnosticCapturewillallowustorapidlydiagnosetheproblem.

• MakesuretheFieldServerutilitiesareloadedonthePC

http://fieldserver.com/techsupport/utility/utility.php

• DisableanywirelessEthernetadaptersonthePC/Laptop

• Disablefirewallandvirusprotectionsoftwareifpossible

• Connectastandardcat5EthernetcablebetweenthePCandProtoNode

• The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC andProtoNodeareondifferentIPNetworks,assignastaticIPAddresstothePConthe192.168.1.xxxnetwork

• ForWindowsXP:

Goto > >

Right-clickonLocalAreaConnection>Properties

Highlight >

EthernetPort

Figure30:EthernetPortLocation

Page 28: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page28of44

• ForWindows7:

Goto > >

> >

Right-clickonLocalAreaConnection>Properties

Highlight >

• ForWindowsXPandWindows7,select:UsethefollowingIPaddress

• Click twice

• DoubleclickontheFSTDiagUtility

• Step1:SelectaFieldServerIPAddress

• TheIPaddresscanbeenteredmanuallyorselectedbyclickingonbutton1usingtheUtility

TypeintheProtoNodeIPaddressDefaultIPAddressis192.168.1.24

PressheretoretrievetheIPaddress.

LocatewherethelogissavedonthePC

Page 29: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page29of44

• Step2:TakeaLog

• PresstheTakeLogbutton.WhiletheUtilityrunsafewDOSpromptswillflashacrossthemonitor.Don'tclickortypeanythingintotheseDOSprompts.ThisstepmaytakeafewminutesdependingonthechosenLogTypeandcomputerspeed.WhentheUtilityisfinishedyouwillbepresentedwithalogofeventsthathaveoccurred.

• Step3:SendLog

• Clickthe“SendLog”buttonlocatednearthebottomofthedialog.Thefollowingdialogshouldappear

• Pushthe‘LocateFolder’buttontolaunchexplorerandhaveitpointdirectlyatthecorrectfolder.Thefileupload.zipmustbesenttosupport@fieldserver.com

• Step4:ClosetheProgram

• Presstheexitbuttonwhenthelogiscompleted

Selectalogtype.

PresstheTakeLogbutton.

Page 30: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page30of44

AppendixA.3. SettingtheNetworkNumberforBACnet/IPwhenmorethanoneProtoNodeisonthesameSubnet

OnthemainWebConfiguratorscreen,updatetheNetworkNumberintheNetwork_NrandhitSubmit.Pleasenotethatthedefaultvalueis50.

AppendixA.4. LEDDiagnosticsforModbusRTUCommunicationsBetweenProtoNodeandDevices

PleaseseethediagrambelowforProtoNodeRERandLERLEDLocations.

Tag DescriptionRTC UnusedRUN TheRUNLEDwillstartflashing20secondsafterpowerindicatingnormaloperation.

ERRTheSYSERRLEDwillgoonsolid15secondsafterpowerup.Itwillturnoffafter5seconds.AsteadyredlightwillindicatethereisasystemerroronProtoNode.Ifthisoccurs,immediatelyreporttherelated“systemerror”shownintheerrorscreenoftheGUIinterfacetoFieldServerTechnologiesforevaluation.

RX TheRXLEDwillflashwhenamessageisreceivedonthehostport.TX TheTXLEDwillflashwhenamessageissentonthehostport.PWR ThisisthepowerlightandshouldshowsteadygreenatalltimeswhenProtoNodeispowered.

Figure31:WebConfiguratorshowingsettingthenetworknumberforBACnet/IP

DiagnosticLEDs

Figure32:DiagnosticLEDs

Page 31: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page31of44

AppendixB. VendorInformation-Cosmogas

AppendixB.1. ArgusModbusRTUMappingstoBACnetMS/TP,BACnet/IP,MetasysN2andLonWorks

PointNameBACnetObjectType

BACnetObjectID

N2DataType

N2Point

Address

LonName LonSNVT Description

ModbusUnits AV 1 AO 1 nvoModUnits_000

SNVT_count_f

Bit0:°C/°FBit1:bar/psi

DeviceType AI 2 AI 2 nvoDevType_001

SNVT_count_f

Notapplicable

State AI 3 AI 3 nvoState_002

SNVT_count_f

Notapplicable

Status AI 4 AI 4 nvoStatus_003

SNVT_count_f

Notapplicable

ErrorCode AI 5 AI 5 nvoErrCode_004

SNVT_count_f

Forcompleteerrorlist,seetheheatermanual.255means“Noerror”.

WarningCode AI 6 AI 6 nvoWarnCode_005

SNVT_count_f

Notapplicable

CentralHeatingSetpoint

AV 7 AO 7 nvoBlrCHSP_006

SNVT_count_f

Heatingsetpoint:range68to179°F

DHWSetpoint AV 8 AO 8 nvoBlrDHWSP_007

SNVT_count_f

Indirectwaterheatersetpoint:range104to140°F

BoilerOperation AV 9 AO 9 nvoBlrOp_008

SNVT_count_f

Notapplicable

DHWType AV 10 AO 10 nvoDHWType_009

SNVT_count_f

Notapplicable

CHMode AV 11 AO 11 nvoCHMode_010

SNVT_count_f

0:CHwiththermostat;1:CHwithRTandoutdoorreset;2:CHwithfulloutdoorreset;3:CHwithpermanentheatdemand;4:CHwith0-10Vccinput

DHWMode AV 12 AO 12 nvoDHWMode_011

SNVT_count_f

0 = no DHW; 1 = DHW store with sensor; 2 = DHW store with thermostat; 3 = N/A; 4 = N/A; 5 = N/A

SupplyTemp AI 13 AI 13 nvoSupTmp_012

SNVT_count_f

Burner1(Manager)Supplytemperature

Page 32: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page32of44

ReturnTemp AI 14 AI 14 nvoRetTmp_013

SNVT_count_f

Burner1(Manager)Returntemperature

DHWTemp AI 15 AI 15 nvoDHWTmp_014

SNVT_count_f

Indirectwaterheatertemperature

FlueGasTemp AI 16 AI 16 nvoFluGasTmp_015

SNVT_count_f

Burner1(Manager)Fluegastemperature

HeatExchangerTemp AI 17 AI 17 nvoHtExcTmp_016

SNVT_count_f

HeaderTemperature

FiringRate AI 18 AI 18 nvoFirRate_017

SNVT_lev_percent

Burner1firingrate

MinFiringRate AI 19 AI 19 nvoMinFirRat_018

SNVT_lev_percent

Notapplicable

FlameCurrent AI 20 AI 20 nvoFlmCrnt_019

SNVT_count_f

Burner1(Manager)Ionizationcurrent

WaterPressure AI 21 AI 21 nvoWtrPrs_020

SNVT_count_f

Systemwaterpressure

Analogin AI 22 AI 22 nvoAnalogin_021

SNVT_count_f

Analoginput(0-10Vrange)

Analogout AI 23 AI 23 nvoAnalogout_022

SNVT_count_f

Notapplicable

Information AI 24 AI 24 nvoInfo_023

SNVT_count_f

Notapplicable

CHpumpstatus AI 25 AI 25 nvoCHpump_024

SNVT_count_f

0:pumpoff100:pumpon

DHWpumpstatus AI 26 AI 26 nvoDHWpump_025

SNVT_count_f

0:pumpoff100:pumpon

IgnitionCountOK AI 27 AI 27 nvoIgnCntOK_026

SNVT_count_f

Notapplicable

IgnitionCountFailed AI 28 AI 28 nvoIgnCntFl_027

SNVT_count_f

Notapplicable

FlameCountFailed AI 29 AI 29 nvoFlmCntFl_028

SNVT_count_f

Notapplicable

BurnerHighHours/CHHours

AI 30 AI 30 nvoBrnHiHrs_029

SNVT_time_hour

Notapplicable

BurnerMedHours/DHWHours

AI 31 AI 31 nvoBrnMedHrs_030

SNVT_time_hour

Notapplicable

BurnerLowHours AI 32 AI 32 nvoBrnLoHrs_031

SNVT_time_hour

Notapplicable

1stLockoutinHistory AI 33 AI 33 nvo1LkotHst_032

SNVT_count_f

Notapplicable

Timeafter1stLockout AI 34 AI 34 nvoTime1Lkot_033

SNVT_time_hour

Notapplicable

2ndLockout AI 35 AI 35 nvo2LkotHst_034

SNVT_count_f

Notapplicable

Timeafter2ndLockout

AI 36 AI 36 nvoTime2Lkot_035

SNVT_time_hour

Notapplicable

3rdLockout AI 37 AI 37 nvo3LkotHst_036

SNVT_count_f

Notapplicable

Timeafter3rdLockout AI 38 AI 38 nvoTime3kot_037

SNVT_time_hour

Notapplicable

Page 33: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page33of44

4thLockout AI 39 AI 39 nvo4Lkot_038

SNVT_count_f

Notapplicable

Timeafter4thLockout AI 40 AI 40 nvoTime4Lkot_039

SNVT_time_hour

Notapplicable

1stBlockingErrorinHistory

AI 41 AI 41 nvo1BlkErHst_040

SNVT_count_f

Notapplicable

Timeafter1stBlockingError

AI 42 AI 42 nvoTime1Blk_041

SNVT_time_hour

Notapplicable

2ndBlockingError AI 43 AI 43 nvo2BlkErHst_042

SNVT_count_f

Notapplicable

Timeafter2ndBlockingError

AI 44 AI 44 nvoTime2Blk_043

SNVT_time_hour

Notapplicable

3rdBlockingError AI 45 AI 45 nvo3BlkErHst_044

SNVT_count_f

Notapplicable

Timeafter3rdBlockingError

AI 46 AI 46 nvoTime3Blk_045

SNVT_time_hour

Notapplicable

4thBlockingError AI 47 AI 47 nvo4BlkErHst_046

SNVT_count_f

Notapplicable

Timeafter4thBlockingError

AI 48 AI 48 nvoTime4Blk_047

SNVT_time_hour

Notapplicable

Dependent_1State AI 49 AI 49 nvoD1State_048

SNVT_count_f

Notapplicable

Dependent_1Status AI 50 AI 50 nvoD1Status_049

SNVT_count_f

Notapplicable

Dependent_1ErrorNumber

AI 51 AI 51 nvoD1ErrNum_050

SNVT_count_f

Notapplicable

Dependent_1FiringRate

AI 52 AI 52 nvoD1FirRat_051

SNVT_lev_percent

Notapplicable

Dependent_2State AI 53 AI 53 nvoD2State_052

SNVT_count_f

Notapplicable

Dependent_2Status AI 54 AI 54 nvoD2Status_053

SNVT_count_f

Notapplicable

Dependent_2ErrorNumber

AI 55 AI 55 nvoD2ErrNum_054

SNVT_count_f

Notapplicable

Dependent_2FiringRate

AI 56 AI 56 nvoD2FirRat_055

SNVT_lev_percent

Notapplicable

Dependent_3State AI 57 AI 57 nvoD3State_056

SNVT_count_f

Notapplicable

Dependent_3Satus AI 58 AI 58 nvoD3Satus_057

SNVT_count_f

Notapplicable

Dependent_3ErrorNumber

AI 59 AI 59 nvoD3ErrNum_058

SNVT_count_f

Notapplicable

Dependent_3FiringRate

AI 60 AI 60 nvoD3FirRat_059

SNVT_lev_percent

Notapplicable

Dependent_4State AI 61 AI 61 nvoD4State_060

SNVT_count_f

Notapplicable

Dependent_4Status AI 62 AI 62 nvoD4Status_061

SNVT_count_f

Notapplicable

Dependent_4ErrorNumber

AI 63 AI 63 nvoD4ErrNum_062

SNVT_count_f

Notapplicable

Page 34: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page34of44

Dependent_4FiringRate

AI 64 AI 64 nvoD4FirRat_063

SNVT_lev_percent

Notapplicable

Dependent_5State AI 65 AI 65 nvoD5State_064

SNVT_count_f

Notapplicable

Dependent_5Status AI 66 AI 66 nvoD5Status_065

SNVT_count_f

Notapplicable

Dependent_5ErrorNumber

AI 67 AI 67 nvoD5ErrNum_066

SNVT_count_f

Notapplicable

Dependent_5FiringRate

AI 68 AI 68 nvoD5FirRat_067

SNVT_lev_percent

Notapplicable

Dependent_6State AI 69 AI 69 nvoD6State_068

SNVT_count_f

Notapplicable

Dependent_6Status AI 70 AI 70 nvoD6Status_069

SNVT_count_f

Notapplicable

Dependent_6ErrorNumber

AI 71 AI 71 nvoD6ErrNum_070

SNVT_count_f

Notapplicable

Dependent_6FiringRate

AI 72 AI 72 nvoD6FirRat_071

SNVT_lev_percent

Notapplicable

Dependent_7State AI 73 AI 73 nvoD7State_072

SNVT_count_f

Notapplicable

Dependent_7Status AI 74 AI 74 nvoD7Status_073

SNVT_count_f

Notapplicable

Dependent_7ErrorNumber

AI 75 AI 75 nvoD7ErrNum_074

SNVT_count_f

Notapplicable

Dependent_7FiringRate

AI 76 AI 76 nvoD7FirRat_075

SNVT_lev_percent

Notapplicable

ControllerState AI 77 AI 77 nvoCtlState_076

SNVT_count_f

Notapplicable

ControllerStatus AI 78 AI 78 nvoCtlStats_077

SNVT_count_f

Notapplicable

ControllerErrorCode AI 79 AI 79 nvoCtlErrCod_078

SNVT_count_f

Notapplicable

ControllerWarningCode

AI 80 AI 80 nvoCtlWrnCod_079

SNVT_count_f

Notapplicable

ControllerCHSP AV 81 AO 81 nvoCtlCHSP_080

SNVT_count_f

Notapplicable

ControllerDHWSP AV 82 AO 82 nvoCtlDHWSP_081

SNVT_count_f

Notapplicable

HighOutdoorAirTemp

AV 83 AO 83 nvoHiOATmp_082

SNVT_count_f

Notapplicable

MinimumOutdoorAirSP

AV 84 AO 84 nvoMinOASP_083

SNVT_count_f

Notapplicable

LowOutdoorAirTemp AV 85 AO 85 nvoLoOATmp_084

SNVT_count_f

Notapplicable

MaximumOutdoorAirSP

AV 86 AO 86 nvoMaxOASP_085

SNVT_count_f

Notapplicable

OutdoorAirShutdownTemp

AV 87 AO 87 nvoOAShdnTmp_086

SNVT_count_f

Warmweathershutdowntemperature

Page 35: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page35of44

NightSetback AV 88 AO 88 nvoNightStbk_087

SNVT_count_f

Notapplicable

HeaderTemp AI 89 AI 89 nvoHeaderTmp_088

SNVT_count_f

Notapplicable

OutsideTemp AI 90 AI 90 nvoOutsidTmp_089

SNVT_count_f

Externalsensortemperature

CascadeFiringRate AI 91 AI 91 nvoCscFirRat_090

SNVT_lev_percent

Notapplicable

MinFiringRate AI 92 AI 92 nvoMinFirR2_091

SNVT_lev_percent

Notapplicable

SystemPump AI 93 AI 93 nvoSysTmpump_092

SNVT_count_f

Notapplicable

Amountofdepdetected

AI 94 AI 94 nvoDepDetect_093

SNVT_count_f

Notapplicable

ModbusUnits nviModUnits_094

SNVT_count_f

Bit0:°C/°FBit1:bar/psi

CentralHeatingSetpoint

nviBlrCHSP_095

SNVT_count_f

Heatingsetpoint:range68to179°F

DHWSetpoint nviBlrDHWSP_096

SNVT_count_f

Indirectwaterheatersetpoint:range104to140°F

BoilerOperation nviBlrOp_097

SNVT_count_f

Notapplicable

DHWType nviDHWType_098

SNVT_count_f

Notapplicable

CHMode nviCHMode_099

SNVT_count_f

0:CHwiththermostat;1:CHwithRTandoutdoorreset;2:CHwithfulloutdoorreset;3:CHwithpermanentheatdemand;4:CHwith0-10Vccinput

DHWMode nviDHWMode_100

SNVT_count_f

0 = no DHW; 1 = DHW store with sensor; 2 = DHW store with thermostat; 3 = N/A; 4 = N/A; 5 = N/A

ControllerCHSP nviCtlCHSP_101

SNVT_count_f

Notapplicable

ControllerDHWSP nviCtlDHWSP_102

SNVT_count_f

Notapplicable

HighOutdoorAirTemp

nviHiOATmp_103

SNVT_count_f

Notapplicable

MinimumOutdoorAirSP

nviMinOASP_104

SNVT_count_f

Notapplicable

Page 36: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page36of44

LowOutdoorAirTemp nviLoOATmp_105

SNVT_count_f

Notapplicable

MaximumOutdoorAirSP

nviMaxOASP_106

SNVT_count_f

Notapplicable

OutdoorAirShutdownTemp

nviOAShdnTmp_107

SNVT_count_f

Warmweathershutdowntemperature

NightSetback nviNightStbk_108

SNVT_count_f

Notapplicable

ControlRegister MV 95 95 nviCtlWord_109

SNVT_count_f

Setto1beforeanyvariablechange

Page 37: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page37of44

AppendixC. MACAddressDIPSwitchSettings

AppendixC.1. MACAddressDIPSwitchSettings

Address A0 A1 A2 A3 A4 A5 A6 A7

0 Off Off Off Off Off Off Off Off

1 On Off Off Off Off Off Off Off

2 Off On Off Off Off Off Off Off

3 On On Off Off Off Off Off Off

4 Off Off On Off Off Off Off Off

5 On Off On Off Off Off Off Off

6 Off On On Off Off Off Off Off

7 On On On Off Off Off Off Off

8 Off Off Off On Off Off Off Off

9 On Off Off On Off Off Off Off

10 Off On Off On Off Off Off Off

11 On On Off On Off Off Off Off

12 Off Off On On Off Off Off Off

13 On Off On On Off Off Off Off

14 Off On On On Off Off Off Off

15 On On On On Off Off Off Off

16 Off Off Off Off On Off Off Off

17 On Off Off Off On Off Off Off

18 Off On Off Off On Off Off Off

19 On On Off Off On Off Off Off

20 Off Off On Off On Off Off Off

21 On Off On Off On Off Off Off

22 Off On On Off On Off Off Off

23 On On On Off On Off Off Off

24 Off Off Off On On Off Off Off

25 On Off Off On On Off Off Off

26 Off On Off On On Off Off Off

27 On On Off On On Off Off Off

28 Off Off On On On Off Off Off

29 On Off On On On Off Off Off

30 Off On On On On Off Off Off

31 On On On On On Off Off Off

32 Off Off Off Off Off On Off Off

33 On Off Off Off Off On Off Off

34 Off On Off Off Off On Off Off

35 On On Off Off Off On Off Off

36 Off Off On Off Off On Off Off

37 On Off On Off Off On Off Off

38 Off On On Off Off On Off Off

39 On On On Off Off On Off Off

40 Off Off Off On Off On Off Off

41 On Off Off On Off On Off Off

42 Off On Off On Off On Off Off

43 On On Off On Off On Off Off

44 Off Off On On Off On Off Off

45 On Off On On Off On Off Off

46 Off On On On Off On Off Off

Address A0 A1 A2 A3 A4 A5 A6 A7

47 On On On On Off On Off Off

48 Off Off Off Off On On Off Off

49 On Off Off Off On On Off Off

50 Off On Off Off On On Off Off

51 On On Off Off On On Off Off

52 Off Off On Off On On Off Off

53 On Off On Off On On Off Off

54 Off On On Off On On Off Off

55 On On On Off On On Off Off

56 Off Off Off On On On Off Off

57 On Off Off On On On Off Off

58 Off On Off On On On Off Off

59 On On Off On On On Off Off

60 Off Off On On On On Off Off

61 On Off On On On On Off Off

62 Off On On On On On Off Off

63 On On On On On On Off Off

64 Off Off Off Off Off Off On Off

65 On Off Off Off Off Off On Off

66 Off On Off Off Off Off On Off

67 On On Off Off Off Off On Off

68 Off Off On Off Off Off On Off

69 On Off On Off Off Off On Off

70 Off On On Off Off Off On Off

71 On On On Off Off Off On Off

72 Off Off Off On Off Off On Off

73 On Off Off On Off Off On Off

74 Off On Off On Off Off On Off

75 On On Off On Off Off On Off

76 Off Off On On Off Off On Off

77 On Off On On Off Off On Off

78 Off On On On Off Off On Off

79 On On On On Off Off On Off

80 Off Off Off Off On Off On Off

81 On Off Off Off On Off On Off

82 Off On Off Off On Off On Off

83 On On Off Off On Off On Off

84 Off Off On Off On Off On Off

85 On Off On Off On Off On Off

86 Off On On Off On Off On Off

87 On On On Off On Off On Off

88 Off Off Off On On Off On Off

89 On Off Off On On Off On Off

90 Off On Off On On Off On Off

91 On On Off On On Off On Off

92 Off Off On On On Off On Off

93 On Off On On On Off On Off

Page 38: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page38of44

Address A0 A1 A2 A3 A4 A5 A6 A7

94 Off On On On On Off On Off

95 On On On On On Off On Off

96 Off Off Off Off Off On On Off

97 On Off Off Off Off On On Off

98 Off On Off Off Off On On Off

99 On On Off Off Off On On Off

100 Off Off On Off Off On On Off

101 On Off On Off Off On On Off

102 Off On On Off Off On On Off

103 On On On Off Off On On Off

104 Off Off Off On Off On On Off

105 On Off Off On Off On On Off

106 Off On Off On Off On On Off

107 On On Off On Off On On Off

108 Off Off On On Off On On Off

109 On Off On On Off On On Off

110 Off On On On Off On On Off

111 On On On On Off On On Off

112 Off Off Off Off On On On Off

113 On Off Off Off On On On Off

114 Off On Off Off On On On Off

115 On On Off Off On On On Off

116 Off Off On Off On On On Off

117 On Off On Off On On On Off

118 Off On On Off On On On Off

119 On On On Off On On On Off

120 Off Off Off On On On On Off

121 On Off Off On On On On Off

122 Off On Off On On On On Off

123 On On Off On On On On Off

124 Off Off On On On On On Off

125 On Off On On On On On Off

126 Off On On On On On On Off

127 On On On On On On On Off

128 Off Off Off Off Off Off Off On

129 On Off Off Off Off Off Off On

130 Off On Off Off Off Off Off On

131 On On Off Off Off Off Off On

132 Off Off On Off Off Off Off On

133 On Off On Off Off Off Off On

134 Off On On Off Off Off Off On

135 On On On Off Off Off Off On

136 Off Off Off On Off Off Off On

137 On Off Off On Off Off Off On

138 Off On Off On Off Off Off On

139 On On Off On Off Off Off On

140 Off Off On On Off Off Off On

141 On Off On On Off Off Off On

142 Off On On On Off Off Off On

Address A0 A1 A2 A3 A4 A5 A6 A7

143 On On On On Off Off Off On

144 Off Off Off Off On Off Off On

145 On Off Off Off On Off Off On

146 Off On Off Off On Off Off On

147 On On Off Off On Off Off On

148 Off Off On Off On Off Off On

149 On Off On Off On Off Off On

150 Off On On Off On Off Off On

151 On On On Off On Off Off On

152 Off Off Off On On Off Off On

153 On Off Off On On Off Off On

154 Off On Off On On Off Off On

155 On On Off On On Off Off On

156 Off Off On On On Off Off On

157 On Off On On On Off Off On

158 Off On On On On Off Off On

159 On On On On On Off Off On

160 Off Off Off Off Off On Off On

161 On Off Off Off Off On Off On

162 Off On Off Off Off On Off On

163 On On Off Off Off On Off On

164 Off Off On Off Off On Off On

165 On Off On Off Off On Off On

166 Off On On Off Off On Off On

167 On On On Off Off On Off On

168 Off Off Off On Off On Off On

169 On Off Off On Off On Off On

170 Off On Off On Off On Off On

171 On On Off On Off On Off On

172 Off Off On On Off On Off On

173 On Off On On Off On Off On

174 Off On On On Off On Off On

175 On On On On Off On Off On

176 Off Off Off Off On On Off On

177 On Off Off Off On On Off On

178 Off On Off Off On On Off On

179 On On Off Off On On Off On

180 Off Off On Off On On Off On

181 On Off On Off On On Off On

182 Off On On Off On On Off On

183 On On On Off On On Off On

184 Off Off Off On On On Off On

185 On Off Off On On On Off On

186 Off On Off On On On Off On

187 On On Off On On On Off On

188 Off Off On On On On Off On

189 On Off On On On On Off On

190 Off On On On On On Off On

191 On On On On On On Off On

Page 39: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page39of44

Address A0 A1 A2 A3 A4 A5 A6 A7

192 Off Off Off Off Off Off On On

193 On Off Off Off Off Off On On

194 Off On Off Off Off Off On On

195 On On Off Off Off Off On On

196 Off Off On Off Off Off On On

197 On Off On Off Off Off On On

198 Off On On Off Off Off On On

199 On On On Off Off Off On On

200 Off Off Off On Off Off On On

201 On Off Off On Off Off On On

202 Off On Off On Off Off On On

203 On On Off On Off Off On On

204 Off Off On On Off Off On On

205 On Off On On Off Off On On

206 Off On On On Off Off On On

207 On On On On Off Off On On

208 Off Off Off Off On Off On On

209 On Off Off Off On Off On On

210 Off On Off Off On Off On On

211 On On Off Off On Off On On

212 Off Off On Off On Off On On

213 On Off On Off On Off On On

214 Off On On Off On Off On On

215 On On On Off On Off On On

216 Off Off Off On On Off On On

217 On Off Off On On Off On On

218 Off On Off On On Off On On

219 On On Off On On Off On On

220 Off Off On On On Off On On

221 On Off On On On Off On On

222 Off On On On On Off On On

223 On On On On On Off On On

224 Off Off Off Off Off On On On

225 On Off Off Off Off On On On

226 Off On Off Off Off On On On

227 On On Off Off Off On On On

228 Off Off On Off Off On On On

229 On Off On Off Off On On On

230 Off On On Off Off On On On

231 On On On Off Off On On On

232 Off Off Off On Off On On On

233 On Off Off On Off On On On

234 Off On Off On Off On On On

235 On On Off On Off On On On

236 Off Off On On Off On On On

237 On Off On On Off On On On

238 Off On On On Off On On On

239 On On On On Off On On On

240 Off Off Off Off On On On On

Address A0 A1 A2 A3 A4 A5 A6 A7

241 On Off Off Off On On On On

242 Off On Off Off On On On On

243 On On Off Off On On On On

244 Off Off On Off On On On On

245 On Off On Off On On On On

246 Off On On Off On On On On

247 On On On Off On On On On

248 Off Off Off On On On On On

249 On Off Off On On On On On

250 Off On Off On On On On On

251 On On Off On On On On On

252 Off Off On On On On On On

253 On Off On On On On On On

254 Off On On On On On On On

255 On On On On On On On On

Page 40: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

AppendixD. Reference

AppendixD.1. Specifications

ProtoNodeRER ProtoNodeLER

ElectricalConnections

One 6-pin Phoenix connector, one RS-485+/-groundport,power+/-framegroundportOne 3-pin RS-485 Phoenix connector, oneRS-485+/-groundportOneEthernet-10/100Ethernetport

One 6-pin Phoenix connector, one RS-485+/-groundport,power+/-framegroundportOneEthernet10/100BaseTportOneFTT-10LonWorksport

Approvals:Pending CE (EN55022;EN55024; EN60950), UL916, Pending FCC Class A Part 15, DNP3ConformanceTested,OPCSelf-testedforCompliance,RoHSCompliant,CSA205ApprovedBTLMarked LonMarkCertified

PowerRequirements Multi-modepoweradapter:9-30VDCor12-24VAC

PhysicalDimensions 11.5cmLx8.3cmWx4.1cmH(4.5x3.2x1.6in.)

Weight: 0.2kg(0.4lbs)OperatingTemperature: -40°Cto75°C(-40°Fto167°F)

SurgeSuppression EN61000-4-2ESDEN61000-4-3EMCEN61000-4-4EFTHumidity: 5-90%RH(non-condensing)(Specificationssubjecttochangewithoutnotice)

Figure33:Specifications

AppendixD.1.1. CompliancewithULRegulations

ForULcompliance,thefollowinginstructionsmustbemetwhenoperatingProtoNode.• The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating

temperaturerange.

• Theinterconnectingpowerconnectorandpowercableshall:• Complywithlocalelectricalcode.• Besuitedtotheexpectedoperatingtemperaturerange.• MeetthecurrentandvoltageratingforProtoNode/Net

• Furthermore,theinterconnectingpowercableshall:• Beoflengthnotexceeding3.05m(118.3”)• BeconstructedofmaterialsratedVW-1orFT-1orbetter

• If theunit is tobe installed inanoperatingenvironmentwitha temperatureabove65 °C, it shouldbeinstalledinaRestrictedAccessArearequiringakeyoraspecialtooltogainaccess

ThisdevicemustnotbeconnectedtoaLANsegmentwithoutdoorwiring.

Page 41: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page41of44

AppendixE. CascadeconnectionwithMODBUS

AppendixE.1. ExampleofMODBUSconnectionforheaterswithserialnumberupto14999999

Figure34:CascadeconnectionwithMODBUS

Page 42: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page42of44

AppendixE.2. ExampleofMODBUSconnectionforheaterswithserialnumberhigherthan15000000

Figure35:CascadeconnectionwithMODBUS

Page 43: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page43of44

ToconnecteachheaterofacascadetoaMODBUScascadeprotocol,installerhaveto:1-Makeadaisychainbetweenterminals28and29ofeachheatershouldbealreadyinplacefollowinstructionofthe885HCcascadesequencer(seefigure34).Forheaterswithserialnumberhigherthan15000000themanagerheaterneedtohavethewiringconnectedtoterminals30and31(seefigure35);2-Connectadaisychainbetweenterminals18,19and20ofallunits(seeFigures34or35).3-ConnectthedaisychaintotheRxTxterminalsoftheprotonode(seeFigure34or35).4-Usingthedisplayoftheheater,setoneachheatertheparameter3085inthefollowway:“1”forthemanagerunit,“2”forthefirstdependent,“3”fortheseconddependent,etc…(checkheatermanualforinstructiononhowtochangeparameter3085);5–Usingthe885HCcommand,setoneachheaterthe“Boileraddress”parameterasillustratedonthe885HCcommandinstruction.CAUTION!Performstepsintheordergiventoavoidmalfunctionstothecommunicationsystems

Page 44: ProtoNode RER and ProtoNode LER Startup Guide For ...mesteksa.com/fileuploads/Literature/RBI Water Heaters/Controls... · A Quick Start guide 1. Record the information about the unit

Page44of44

260 North Elm Street 7555 Tranmere Drive Westfield, MA 01085 Mississauga, Ontario L5S 1L4 Canada Phone: (413) 568-9571 Phone: (905) 670-5888

Fax: (413) 568-9613 Fax: (905) 670-5782 www.rbiwaterheaters.com