powerfactory emt model3

Upload: ratana-kem

Post on 02-Jun-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 PowerFactory EMT Model3

    1/6

  • 8/10/2019 PowerFactory EMT Model3

    2/6

    26

    - Polynomial: the saturation curve is approximated by a polynomial of user-defined

    order. The polynomial fits asymptotically into the piecewise linear definition.

    - ,M sati Magnetizing Current pu

    -M Magnetizing Flux pu

    -M

    L Linear Reactance pu

    -0 This parameter is automatically calculated to

    that the polynomial characteristic fits the

    saturated reactance in full saturation and

    transits steadily in to the piece-wise linear

    characteristic at the knee point. Pu

    - ksat Saturation exponent, i.e. polynomial degree pu

    Figure 4.23 Two slope and polynomial saturation curves

  • 8/10/2019 PowerFactory EMT Model3

    3/6

    27

    Parameter Description Unit

    Knee Flux Knee-point of asymptotic piece-wise linear characteristic.Typical value around 1.1 to 1.2 times the rated flux.

    p.u.

    Linear (unsaturated)

    Reactance

    Magnetizing reactance for unsaturated conditions Lunsa.

    In p.u. values, the linear reactance is equal to the

    reciprocal of the magnetizing current (reactance part of

    the exciting current)

    p.u.

    Saturated Reactance Magnetizing reactance for saturated condition Lsat. p.u.

    Saturation Exponent

    Exponent of polynomial representation (ksat). Typical

    values are 9, 13, and 15. The higher the exponent thesharper, the saturation curves.

    -

    - Current/Flux values: The user can also define the saturation curve in terms of

    measured current-flux values and select between a piecewise linearor spline interpolation.

    The base quantities of the p.u. values in the current-flux table are also referred to the peak

    values of the corresponding nominal variables:

    3[ ][ ] 2 103 [ ]

    base

    basebase

    S MVAI A

    U kV=

    3[ ] / 3[ ] 2 102 [ ]

    basebase

    base

    U kVV s

    f kHz =

    The zero sequence magnetizing reactance strongly depends on the construction

    characteristic of the transformer core (three-legged, five-legged, shell-type, etc.) and its

    vector group. Figure below shows the equivalent circuit for the zero sequence.

    Table 4.2 Basic data of the two-slope and polynomial saturation characteristics

    Figure 4.24 Equivalent circuit for the zero sequence

  • 8/10/2019 PowerFactory EMT Model3

    4/6

    28

    Transformer with delta-connected windings

    If the transformer has delta-connected windings, then any zero sequence excitation

    approximates a zero-sequence short-circuit, as the delta-connected winding short-circuits the

    zero sequence current. In that case there is no need to represent zero sequence saturation.

    Transformer without delta-connected windings

    If the transformer type does not have delta-connected windings, then the zero-

    sequence excitation current results generally higher than the positive-sequence excitation

    current and strongly depends on the core type.

    To account for the higher zero-sequence linear exciting current when no delta-

    connected winding is available, PowerFactory allows for the definition of linear (unsaturated)

    zero-sequence magnetizing impedance. This zero-sequence magnetizing impedance and its

    R/X ratio is defined in the load flow page (TypTr2nLoad flow); the parameters are made

    available depending on the vector group (i.e. hidden in case of delta-connected winding).

    To account for the core type dependency of the zero-sequence saturation

    characteristic, the transformer model supports the following two options in the EMT-

    simulation page:

    3 Limbs core: use this option for three-legged core designs. In this core type, the

    fluxes are roughly equal in the three legs and must therefore return outside the core through

    the air-gap and the tank. Because of the fact that the air-gap and the tanks are no-magnetic,

    the zero-sequence magnetizing current is nearly linear and therefore the model uses the linear

    zero-sequence magnetizing impedance defined in the load flow page. In other words, it does

    not consider zero-sequence saturation effects.

    5 Limbs core: use this option for five-legged and shell-type cores. As the zero-

    sequence fluxes return inside the core, the model uses the saturation characteristic (of the

    positive sequence) in the zero-sequence magnetizing reactance as well.

    4.3.4.2.

    Three-winding Transformer (3-phase)

    In PowerFactoryeach winding of a transformer can have taps, however only one of

    the tap changers can be controlled in the load-flow calculation. The adjustment of the taps

  • 8/10/2019 PowerFactory EMT Model3

    5/6

    29

    can be set in the load-flow of the transformer type or can be enabled for automatic control

    before run load-flow solution.

    For a three-winding transformer, the third winding is referred to the minimum rated

    power of the other two windings. For example, for a 60/60/10 MVA, 132/22/11 kV

    transformer, a value of 10% is specified both for the HV-MV and LV-HV positive-sequence

    short-circuit voltages. The impedance value (referred to HV-side) of the impedance between;

    - the HV and MV terminals is;

    ( )2

    1320.1 29.04

    60

    kVprimary

    MVA =

    - the HV and LV terminals is

    ( )2

    1320.1 174.24

    10

    kVprimary

    MVA =

    Figure 4.25 PF Positive-sequence model of the 3-winding transformer, taps modelled

    Figure 4.26 PF Positive-sequence model of the 3-winding transformer, taps modelled

  • 8/10/2019 PowerFactory EMT Model3

    6/6

    30

    The model diagrams Figure 4.10 and Figure 4.11 and input parameters in Positive,

    Negative and Zero sequence models will be list in table below:

    Parameter Unit Description

    Ur,T,HVUr,T,HVUr,T,HV

    kV Rated Voltage on HV/MV/LV side

    Sr,T,HVSr,T,HVSr,T,HV

    MVA Rated Power for the windings on HV/MV/LV side

    usc,HV-MVusc,MV-LVusc,LV-HV

    % Relative short-circuit voltage of paths HV-MV, MV-LV, LV-HV

    PCu,HV-MVPCu,MV-LVPCu,LV-HV

    kW Copper losses of path HV-MV, MV-LV, LV-HV

    ur.sc,HV-MVur,sc,MV-LVur,sc,LV-HV

    %Relative short-circuit voltage, resistive part of paths HV-MV, MV-

    LV, LV-HV

    X/RHV-MV

    X/RMV-LVX/RLV-HV

    Relative short-circuit voltage ratio, X/R ratio of path HV-MV, MV-

    LV, LV-HV

    i0 % No-Load current, related to rate current at HV side

    PFe kW No-Load losses

    It is possible to use manufacturers or any other available measurement data for load-

    flow calculation.

    Table 4.3 Positive and Negative sequence in put parameter

    Figure 4.27 Measurement data input page for three-winding transformer