plc hc900 honeywell

Upload: marcos-vazquez

Post on 02-Jun-2018

223 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/10/2019 PLC HC900 Honeywell

    1/179

    HC900 Training Part 1 1Version 4.1 11/16//06Honeywell Proprietary

    Industrial Measurement and Control

    HC900 Hybrid Controller

    Training - Part 1Controller, OI & HC Designer

  • 8/10/2019 PLC HC900 Honeywell

    2/179

    HC900 Training Part 1 2Version 4.1 11/16//06Honeywell Proprietary

    3 Components Integrated Together

    Controller, Operator Interface, Hybrid Control Designer

  • 8/10/2019 PLC HC900 Honeywell

    3/179

    HC900 Training Part 1 3Version 4.1 11/16//06Honeywell Proprietary

    Controller

  • 8/10/2019 PLC HC900 Honeywell

    4/179

    HC900 Training Part 1 4Version 4.1 11/16//06Honeywell Proprietary

    HC900 Controller

    Ethernet Supervisory

    Peer-to-peer

    1 port on C30 & C50

    Remote I/O port

    (not on C30)

    I/O Modules I/O Status LEDsController

    Module

    Power

    Supply

    Termination

    Cover &

    Label

    Field

    Wiring

    Terminals

    Size: Height 5.5

    139.7 mm Width10.5

    266.7 mm

    Depth 5.9

    149.9 mm

    Serial Ports (RS232/485

    Configuration Modbus Master/Slave

    . Honeywell OI

  • 8/10/2019 PLC HC900 Honeywell

    5/179

    HC900 Training Part 1 5Version 4.1 11/16//06Honeywell Proprietary

    Modular Design

    Select appropriate componentsto match application requirements purchase only what is needed

    expand any time

    replace any component

    any I/O module can be located in any I/O slot

    any chassis size can be a CPU rack

    4 I/O slot rack

    8 I/O slot rack

    12 I/O slot rack

    Can be a Controller or a Remote I/O Scanner Module

  • 8/10/2019 PLC HC900 Honeywell

    6/179

    HC900 Training Part 1 6Version 4.1 11/16//06Honeywell Proprietary

    HC900

    RemoteI/O Racks

    Moxa Hub

    10Base-T

    CAT5 STP cables

    100m each

    300 m max.

    Rack 2

    Remote I/O Racks

    Main CPU

    Rack 1

    Rack 3

    Rack 4

    Rack 5

    Ethernet private (proprietary protocol)

    link, 10Base-T, 10MBits/sec.

    Fast scan rate reduced 50ms

    I/O data synchronized with start of scan

    Supports all control Output types

    I/O removal / insertion detected

    Max. of 4 Expansion I/O Racks

    Industrial Hubs can be used to increase

    distance to 984ft (300m)

    Scanner failure results in use of previous

    scan data. Three consecutive scans with

    failure and scanner is removed from scan

    and CPU posts a diagnostic.

  • 8/10/2019 PLC HC900 Honeywell

    7/179

    HC900 Training Part 1 7Version 4.1 11/16//06Honeywell Proprietary

    Family of Processors

    C30 C50 C70 C70RFamily of CPUs for desired performance and price points

    C30 C50 C70 C70R

    Economy Workhorse Performance RedundancyMax I/O 384 1920 1920 1920

    Max AI 192 960 960 960

    I/O Slots 12 60 60 60

    Remote I/O NO YES YES YES

    Function Blocks 400 2000 5000 5000

    Enet, RS232/485, Peer YES YES YES YES

    Redundancy NO No No YES

    Min Process scan rate 500ms 500ms 500ms 500ms

    Min Logic scan rate 54ms 27ms 27ms 54ms

  • 8/10/2019 PLC HC900 Honeywell

    8/179

    HC900 Training Part 1 8Version 4.1 11/16//06Honeywell Proprietary

    HC900 Controller Ports

    Modbus Master/Slave

    or ConfigurationConf: 9.6 - 57.6KB, private protocol

    Modbus RTU: 9.6 57.6KB

    Modbus Master/Slave

    or 559/1042 OI2-wire RS-485, 3-pin connector

    OI: 38.4, 57.6KB, private protocol

    Modbus RTU: 9.6- 57.6KB

    HC 900 Controller CPU

    Host, Peer-to-PeerEthernet, 10Base-T (RJ-45)

    (single port on C30 & C50)

    Remote I/OEthernet Private, 10Base-T (RJ-45)

    (not on C30)

    2000 Ft or Modem2000 Ft or Modem

  • 8/10/2019 PLC HC900 Honeywell

    9/179

    HC900 Training Part 1 9Version 4.1 11/16//06Honeywell Proprietary

    PC to Controller Connections

    Serial Port ConnectionsSerial Port S1 is factory configured

    as RS232 with ELN Protocol . Used for HC Designer

    Serial Port S2 is factory configuredAs RS484 with ELN Protocol. Used for OI

    Ethernet Connections

    E1 and E2 always active

    Up to 10 Sockets

    Auto-detecting Ports

    Default IP Addresses

    E1 = 192.168.1.254E2 = 192.168.2.254

    E1 & E2 Must be on different Sub-nets

    10/100BaseT support

  • 8/10/2019 PLC HC900 Honeywell

    10/179

    HC900 Training Part 1 10Version 4.1 11/16//06Honeywell Proprietary

    Serial Ports

    Serial Port SetupSwitches on the CPU are used to configure serial ports

    In a redundant configuration the

    lead and Reserve CPU must match

    Label provides switch settings

    Selections

    RS232/RS485 (Default)

    RS232/RS232

    RS485/RS485*

    Protocols supported (selected via HC Designer)

    ELN

    Modbus RTU Slave (2)

    Modbus RTU Master(1)

    *Note: Although Honeywell operator interfaces use RS485,

    only one OI may be connected to a C70R redundant pair.

  • 8/10/2019 PLC HC900 Honeywell

    11/179

    HC900 Training Part 1 11Version 4.1 11/16//06Honeywell Proprietary

    HC900 I/O

    I/O Designed for Process Control with FamiliarPackaging Style

    Intelligent (CPU per Module) LED pt indicators on Digital I/O cards

    Fault Status indicator on all cards

    Field Wiring Labels

    Remove & Insert Under Controller

    Power

    Safe handling I/O connector housing

    Three (3) Terminal Block DesignsBarrier (lug screw)Euro (compression block)Remote Termination Panels

    I/O Modules

    Analog In 8 pt

    Analog In 16pt

    Analog Out 4 pt Contact DI 16 pt

    24 vdc DI 16 pt

    24 vdc DI 32pt

    120/240 vac DI 16 pt

    24 vdc DO 16 pt

    24 vdc DO 32 pt

    120/240 vac DO 8 pt

    Relay DO 8 pt

    Pulse/Freq In 4 pt

  • 8/10/2019 PLC HC900 Honeywell

    12/179

    HC900 Training Part 1 Version 4.1 11/16//06Honeywell Proprietary

    Analog Inputs

    High Level Analog Input Specifications

    Inputs per module 16(isolated)

    Input types V, mA

    Input Isolation 400 VDC point to point,

    Accuracy 0.1 % of range.

    A/D Resolution 15 Bits

    Update rate 500ms

    Calibration Stored in non-volatile memory.

    Field Calibration via HC Designer

    1

    3

    5

    7

    9

    11

    8

    2

    18

    19

    23

    25

    27

    29

    31

    35

    33

    4

    6

    8

    10

    12

    14

    16

    20

    22

    24

    26

    28

    30

    32

    34

    36

    In 1+

    In 2+

    In 1-

    In 2-

    In 3+

    In 4+

    In 3-

    In 4-

    In 5+

    In 6+

    In 5-

    In 6-

    In 7+

    In 8+

    In 7-

    In 8-

    In 9+

    In 10+

    In 9-

    In 10-In 11+

    In 12+

    In 11-

    In 12-

    In 13+

    In 14+

    In 13-

    In 14-

    In 15+

    In 16+

    In 15-

    In 16-

    NC

    NC

    NC

    NC

    21

    13

    15

    1

    3

    5

    7

    9

    11

    8

    2

    18

    19

    23

    25

    27

    29

    31

    35

    33

    4

    6

    8

    10

    12

    14

    16

    20

    22

    24

    26

    28

    30

    32

    34

    36

    In 1+

    In 2+

    In 1-

    In 2-

    In 3+

    In 4+

    In 3-

    In 4-

    In 5+

    In 6+

    In 5-

    In 6-

    In 7+

    In 8+

    In 7-

    In 8-

    In 9+

    In 10+

    In 9-

    In 10-In 11+

    In 12+

    In 11-

    In 12-

    In 13+

    In 14+

    In 13-

    In 14-

    In 15+

    In 16+

    In 15-

    In 16-

    NC

    NC

    NC

    NC

    In 1+

    In 2+

    In 1-

    In 2-

    In 3+

    In 4+

    In 3-

    In 4-

    In 5+

    In 6+

    In 5-

    In 6-

    In 7+

    In 8+

    In 7-

    In 8-

    In 9+

    In 10+

    In 9-

    In 10-In 11+

    In 12+

    In 11-

    In 12-

    In 13+

    In 14+

    In 13-

    In 14-

    In 15+

    In 16+

    In 15-

    In 16-

    NC

    NC

    NC

    NC

    21

    13

    15

    Analog Input Specifications

    Inputs per module 8 (isolated)

    Input types mV, V, T/C, RTD, ohms, mA, slidewire assigned to

    any channel

    Input Isolation 400 VDC point to point

    Burnout T/C, mV, V (see manual for exceptions)

    configurable to upscale, downscale, defined value,

    Stored in non-volatile memory.

    Field Calibration via HC Designer

    Calibration

    Via 2 RTDs at top/bottom of moduleReference Junction

    15 BitsA/D Resolution

    0.1 % of rangeAccuracy

  • 8/10/2019 PLC HC900 Honeywell

    13/179

    HC900 Training Part 1 13Version 4.1 11/16//06Honeywell Proprietary

    Analog Input Wiring

    12

    34

    5 6

    78

    91 0

    1 1

    1 21 3

    1 4

    1 51 6

    1 71 8

    1 9 2 0

    12

    34

    5 6

    78

    91 0

    1 1

    1 21 3

    1 4

    1 51 6

    1 71 8

    1 9 2 0

    IN 1 +

    IN 1 -

    IN 1 & 2

    I N 2 +

    IN 2 -

    IN 3 -

    I N 3 +m V , V

    I n p u t

    X m t r

    2 4 V dc

    2 5 0

    O h m s4 2 0 m A

    IN 8 +

    I N 8

    R T D

    T h e r m o c o u p le

    I N 5 +

    I N 6 +

    I N 4 +

    I N 6 -

    I N 3 +

    I N 4 -

    IN 7 -

    I N 5 -

  • 8/10/2019 PLC HC900 Honeywell

    14/179

    HC900 Training Part 1 Version 4.1 11/16//06Honeywell Proprietary

    Analog Outputs

    Outputs per

    module

    4 (isolated)

    Current 0 to 21.8 mA, range selectable

    Loadresistance

    750 ohms max

    Isolation 500VDC Channel to Channel

    600 VDC Channel to Logic

    Accuracy 0.1% full scale

    Modulesper rack

    10 max

    Calibration

    Data

    Stored in non-volatile memory.

    Field Calibration via HC

    Designer

    D/A

    Resolution

    12 bits

    12

    3 4

    56

    78

    910

    11

    1213

    14

    1516

    1718

    1920

    Out 1 +

    Out 1 -

    Out 2 +

    Out 2 -

    Out 3+

    Out 3 -

    Out 4+

    Out 4 -

    12

    3 4

    56

    78

    910

    11

    1213

    14

    1516

    1718

    1920

    12

    3 4

    56

    78

    910

    11

    1213

    14

    1516

    1718

    1920

    Out 1 +

    Out 1 -

    Out 2 +

    Out 2 -

    Out 3+

    Out 3 -

    Out 4+

    Out 4 -

  • 8/10/2019 PLC HC900 Honeywell

    15/179

    HC900 Training Part 1 Version 4.1 11/16//06Honeywell Proprietary

    Digital Inputs

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    In 1+

    In 2 +

    In 7+

    In 8+

    In 9+

    In 10+

    In15+

    In 16+

    In 3+

    In 4+In 5+

    In 6+

    1-8 COM

    1-8 COM

    9-16 COM

    9-16 COM

    In 11+In 12+

    In 13+

    In 14+

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    In 1+

    In 2 +

    In 7+

    In 8+

    In 9+

    In 10+

    In15+

    In 16+

    In 3+

    In 4+In 5+

    In 6+

    1-8 COM

    1-8 COM

    9-16 COM

    9-16 COM

    In 11+In 12+

    In 13+

    In 14+

    Operating

    Voltage

    10 to 32 VDC

    80 to 264 VAC

    No Power for Contact

    Inputs perModule

    16

    Isolation 2 Groups of 8

    DC Input Type Sinking

    ResponseTime

    34 ms (off to on) AC50 ms (on to off) AC

    4 ms (off to on) DC

    4 ms (on to off) DC

    4 ms (off to on) Contact

    6 ms (on to off) Contact

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    In 1

    In 2

    In 7In 8

    In 9

    In 10

    In15

    In 16

    In 3

    In 4In 5

    In 6

    1-8 COM

    1-8 COM

    9-16 COM

    9-16 COM

    In 11In 12

    In 13In 14

  • 8/10/2019 PLC HC900 Honeywell

    16/179

    HC900 Training Part 1 16Version 4.1 11/16//06Honeywell Proprietary

    Digital Input Wiring

  • 8/10/2019 PLC HC900 Honeywell

    17/179

    HC900 Training Part 1 Version 4.1 11/16//06Honeywell Proprietary

    Digital Outputs

    12

    34

    56

    78

    910

    11

    1213

    14

    1516

    1718

    1920

    Out 1+

    Out 2 +

    Out 7+

    Out 8+

    Out 9+

    Out 10+

    Out15+Out 16+

    Out 3+

    Out 4+Out 5+

    Out 6+

    + V1

    1-8 COM

    + V2

    9-16 COM

    Out 11+Out 12+

    Out 13+Out 14+

    12

    34

    56

    78

    910

    11

    1213

    14

    1516

    1718

    1920

    12

    34

    56

    78

    910

    11

    12

    1314

    1516

    1718

    1920

    Out 1+

    Out 2 +

    Out 7+

    Out 8+

    Out 9+

    Out 10+

    Out15+Out 16+

    Out 3+Out 4+Out 5+

    Out 6+

    + V1

    1-8 COM

    + V2

    9-16 COM

    Out 11+Out 12+

    Out 13+Out 14+

    Specifications:

    Operating

    Voltage

    6.5 to 32 VDC

    85 to 240 VAC

    Form A & C Relays

    Qutputs perModule

    16 DC Outputs

    8 AC Outputs (Triac w/fuse)

    8 Relay Outputs

    Isolation 2 Groups of 8 DC

    Per Output ACMaximum Load

    AC

    DC

    Relay

    2A per point, 8A per module

    1A per point, 8A per module

    4A@240vac/30vdc (resistive)

    Response Time 10 ms (off to on) DC

    5 ms (on to off) DC

    2 ms + cycle AC

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    Out 1 H

    Out 1NO

    Out 3 H

    Out 3 NO

    Out 6 H

    Out 6 NO

    Out 8 HOut 8 NO

    Out 2 H

    Out 2 NO

    Out 4 H

    Out 4 NO

    Out 5 HOut 5 NO

    Out 7 HOut 7 NO

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    Out 1 H

    Out 1NO

    Out 3 H

    Out 3 NO

    Out 6 H

    Out 6 NO

    Out 8 HOut 8 NO

    Out 2 H

    Out 2 NO

    Out 4 H

    Out 4 NO

    Out 5 HOut 5 NO

    Out 7 HOut 7 NO

    12

    34

    56

    78

    910

    1112

    1314

    1516

    1718

    1920

    Out 1 NO

    Out 1COM

    Out 3 NOOut 3 COM

    Out 6 NO

    Out 6 COM

    Out 8 COM

    Out 8 NC

    Out 2 COM

    Out 2 NC

    Out 4 NO

    Out 4 COM

    Out 5 NOOut 5 COM

    Out 7 NOOut 7 COM

    Out 1 NC

    Out 2 NO

    Out 7 NC

    Out 8 NO

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1112

    13

    14

    15

    16

    17

    18

    19

    20

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1112

    13

    14

    15

    16

    17

    18

    19

    20

    Out 1 NO

    Out 1COM

    Out 3 NO

    Out 3 COM

    Out 6 NO

    Out 6 COM

    Out 8 COM

    Out 8 NC

    Out 2 COM

    Out 2 NC

    Out 4 NO

    Out 4 COM

    Out 5 NOOut 5 COM

    Out 7 NO

    Out 7 COM

    Out 1 NC

    Out 2 NO

    Out 7 NC

    Out 8 NO

  • 8/10/2019 PLC HC900 Honeywell

    18/179

    HC900 Training Part 1 18Version 4.1 11/16//06Honeywell Proprietary

    Digital Output Wiring

  • 8/10/2019 PLC HC900 Honeywell

    19/179

    HC900 Training Part 1 19Version 4.1 11/16//06Honeywell Proprietary

    32 Channel DI, 24vdc

    1

    19

    In 1+

    2+

    3+4+

    5+

    6+

    7+8+

    9+10+

    11+

    12+13+14+15+

    16+1-16COM

    1-16COM17+

    18+

    19+

    20+

    21+

    22+23+

    24+25+

    26+

    27+

    28+29+

    30+

    31+

    32+17-32COM17-32COM

    Input 10 to 32 VDC

    Type Sinking

    Isolation 2 Groups of 16

    On to off

    response time

    5ms

    Off to On

    response time

    5ms

    Specifications:

    Uses 36 point terminal block

    Model # 900TCK-0001

  • 8/10/2019 PLC HC900 Honeywell

    20/179

    HC900 Training Part 1 20Version 4.1 11/16//06Honeywell Proprietary

    32 Channel DO, 24vdc

    Output 10.5 to 32 VDC

    Type Sourcing

    Isolation 2 Groups of 16

    Maximum Load 0.5A per channel,

    12 Amp per card

    (resistive load)

    On to off

    response time

    6ms

    Off to On

    response time

    6ms

    Fusing Electronic

    Limiting

    Specifications:1

    3

    5

    7

    9

    11

    13

    15

    17

    2

    18

    23

    25

    27

    29

    31

    35

    33

    4

    6

    8

    10

    12

    14

    16

    20

    22

    24

    26

    28

    30

    32

    34

    36

    Out 1+

    2+

    3+4+

    5+

    6+

    7+8+

    9+

    10+

    11+

    12+13+14+15+

    16++V1

    COM1

    Out 17+18+

    19+

    20+

    21+

    22+23+

    24+25+

    26+

    27+

    28+29+

    30+

    31+32+

    +V2

    COM2

    21

    19

  • 8/10/2019 PLC HC900 Honeywell

    21/179

    HC900 Training Part 1 21Version 4.1 11/16//06Honeywell Proprietary

    Pulse/Frequency/Quadrature Module (PFQ)

    Multi-function module used with high spped digital pulse generatingdevices such as flow meters, gas meters, proximity switches, speed

    sensors, etc. Has 4 user configurable input channels (4 modules per

    rack)

    Pulse counting counts pulses and provides a rate over a settable time

    period. Preset value compared against accumulated count to perform control

    action with output on block & module (PREI)

    Pulse Frequency measures pulses occurring at a frequency (10hz to

    100Khz) scaled to represent a rate. An application example is a flow meter torepresent gallons/hour.

    Pulse Output generates a pulse train output. An application example is

    conveyor speed control using a variable speed drive. Configurable to

    generate a finite # of pulses at a specified rate or a continuous pulse train

    Quadrature Input Determines direction, speed and position of moving

    devices using 2 digital inputs. Typical input would be from a digital encoder.

  • 8/10/2019 PLC HC900 Honeywell

    22/179

    HC900 Training Part 1 22Version 4.1 11/16//06Honeywell Proprietary

    Pulse Input

    Specifications:

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    In 1+

    In 1 -

    In 4+

    In 4 -

    COM

    In 2+

    In 2 -

    In 3+

    In 3 -

    INDEX+

    INDEX-

    OUTPUT1

    ENCODE+

    SENSE+

    OUTPUT2

    OUTPUT3

    OUTPUT4

    ENCODE-

    SENSE-

    +V

    Inputs per module Up to 4

    Input 0 to 24Vdc

    ON Voltage 4.5V

    OFF Voltage 0.5V

    Minimum Pulse 3 Microseconds

    Counter size 32 bits

    Discrete Preset

    Output

    Pulse ON, or Hold

    ON

    Output type Open collector(sinking)

    Output Rating 5 to 24Vdc, 30mA

  • 8/10/2019 PLC HC900 Honeywell

    23/179

    HC900 Training Part 1 23Version 4.1 11/16//06Honeywell Proprietary

    Pulse Output

    Outputs permodule

    Up to 4

    Output Type Open collector, 5 to 30Vdc,

    30mA max

    Frequency Range 25 Hz to 10KHz

    Duty Cycle 50% - fixed

    Pulse train

    duration

    Number of pulses: up to

    999999 and continuous

    Used to generate a pulse train Each output consumes a module channel

    Provides square wave outputs (50% duty cycle)

    User specified frequency

    Specified quantity of pulses generated

    Continuous pulse output is selectable Failsafe Action

    Stop (low)

    Finish pulse train

  • 8/10/2019 PLC HC900 Honeywell

    24/179

    HC900 Training Part 1 24Version 4.1 11/16//06Honeywell Proprietary

    Frequency Input

    Inputs per Module Up to 4

    Input 0 to 24 VDC

    ON Voltage 4.5V Min.

    Off Voltage 0.5 V Max.

    Frequency 10 to 100KHz

    Minimum Pulse

    Widths

    10-500Hz = 500usec

    500-5KHz = 50usec

    5K-100KHz = 2.5usec

    Module Digital

    Output

    On if frequency out of range

    Fusing Electronic Limiting

    Specifications:

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    In 1+

    In 1 -

    In 4+

    In 4 -

    COM

    In 2+

    In 2 -

    In 3+

    In 3 -

    INDEX+

    INDEX-

    OUTPUT1

    ENCODE+

    SENSE+

    OUTPUT2

    OUTPUT3

    OUTPUT4

    ENCODE-

    SENSE-

    +V

  • 8/10/2019 PLC HC900 Honeywell

    25/179

    HC900 Training Part 1 25Version 4.1 11/16//06Honeywell Proprietary

    Quadrature Input

    Quadrature Used to measure position, speed and directionusing pulse count, frequency and phase of two digital inputs.

    Inputs per

    Module

    One (1)

    Input Voltage Differential: +/- 6 V (0V&5V=off, 5V&0V=on)

    Single Ended 0 to 24V (0V&5V=on, 0V&0V=off)

    On Voltage Differential: 0.2V min

    Single ended 2V minimum

    Off Voltage Differential: +/-2V MaxSingle Ended 1V max.

    Module Encoder

    Power

    5V, 0.5A

    Input Frequency 200KHz Max.

    Quadrature

    Modes

    3

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    In 1+

    In 1 -

    In 4+

    In 4 -

    COM

    In 2+

    In 2 -

    In 3+

    In 3 -

    INDEX+

    INDEX-

    OUTPUT1

    ENCODE+

    SENSE+

    OUTPUT2

    OUTPUT3

    OUTPUT4

    ENCODE-

    SENSE-

    +V

  • 8/10/2019 PLC HC900 Honeywell

    26/179

    HC900 Training Part 1 26Version 4.1 11/16//06Honeywell Proprietary

    Quadrature Wiring

    IN1+

    IN1-

    IN2+

    IN2-

    IN3+

    IN3-

    IN4+

    IN4-

    INDEX+

    INDEX-

    OUTPUT1

    OUTPUT2

    OUTPUT3

    OUTPUT4ENCODE+

    ENCODE-

    SENSE+SENSE-

    V+COM

    A+

    -

    B+

    -

    Quadrature Inputs

    I+

    -Quadrature Input

    DC Power to encoder+

    -

    Isolated 5 VDC 500mA max

    Single Ended

    Low 0.0 to 1.0 VDC

    High 3 to 24 VDC

    Differential

    Low -200 to -6.0 VDCHigh 200mV to 6.0 VDC

    Internal

    connection at

    encoder

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1112

    13

    14

    15

    16

    1718

    19

    20

  • 8/10/2019 PLC HC900 Honeywell

    27/179

    HC900 Training Part 1 27Version 4.1 11/16//06Honeywell Proprietary

    Remote Terminal Panels

    3 RTP types and pre-wired cables: (1, 2.5 and 5m)

    Reduces Customer Wiring Cost

    Provide Field power disconnect for RIUP

    Provide 250 ohm shunts for mA inputs

    24Vdc power terminals and fuses for transmitters High & low voltage cables to match I/O module type TC inputs not supported

    HC900

    Rack

    RTPs

    Field wiring

    Cables

    with

    Connectors

  • 8/10/2019 PLC HC900 Honeywell

    28/179

    HC900 Training Part 1 28Version 4.1 11/16//06Honeywell Proprietary

    Redundancy

  • 8/10/2019 PLC HC900 Honeywell

    29/179

    HC900 Training Part 1 29Version 4.1 11/16//06Honeywell Proprietary

    Controller Rack

  • 8/10/2019 PLC HC900 Honeywell

    30/179

    HC900 Training Part 1 30Version 4.1 11/16//06Honeywell Proprietary

    C70R Redundant Controller Operation

    All user and process interaction is with the Lead CPU.All user and process interaction is with the Lead CPU. Either CPU can be the LeadEither CPU can be the Lead

    Both CPUs receive InputsBoth CPUs receive Inputs

    Both CPUs execute function blocksBoth CPUs execute function blocks

    Lead CPU writes outputsLead CPU writes outputs

    Lead CPU automatically configuresLead CPU automatically configuresReserveReserve

    All Communication isAll Communication iswith Lead CPUwith Lead CPU

    Redundant Switch Module (RSM)Redundant Switch Module (RSM)

    Visual Indication of the Lead and Reserve CPUsVisual Indication of the Lead and Reserve CPUs

    Provides Manual FailProvides Manual Fail--over of the Lead CPU (Key switch)over of the Lead CPU (Key switch) Passive modulePassive module

    Function Block execution resumes on start of next scan followinFunction Block execution resumes on start of next scan following a failg a fail--overover

    Lead CPU Reserve CPU

    Power for

    Reserve CPU

    Power for

    Lead CPU

    RSM To I/O

    Racks

  • 8/10/2019 PLC HC900 Honeywell

    31/179

    HC900 Training Part 1 31Version 4.1 11/16//06Honeywell Proprietary

    Redundant Switch Module

    RSM Module

    Positioned between CPU A and CPU B

    Identifies CPU A and CPU B

    Identifies Lead CPU and Reserve CPU

    Mode Switch

    Changes the mode of both CPUs

    Mode change via Key switch

    Remove key from RUN & RUN/PGRM Positions

    Key cannot be removed while in Program

    Fail-over is a momentary position

    RIUP

    S

  • 8/10/2019 PLC HC900 Honeywell

    32/179

    HC900 Training Part 1 32Version 4.1 11/16//06Honeywell Proprietary

    Scanner

    One Scanner2 Module per I/O Rack

    Two ports one for each C70R CPU

    Maintains communications with Leadand Reserve C70R CPUs to facilitatefail-over

    Reads inputs from modules & writesoutputs to modules in rack

    Status LED Indicator

    Connection to C70R-A (I/O A)

    Connection to C70R-B (I/O B)

    RIUP

    R d d t P

  • 8/10/2019 PLC HC900 Honeywell

    33/179

    HC900 Training Part 1 33Version 4.1 11/16//06Honeywell Proprietary

    Redundant Power

    Provides backup power for Racks with I/O

    May be used with Redundant and Non-redundant systems

    Supports P01 (60W), P02 (28W) and P03 (24VDC) Power Supplies

    Available for 8-Slot and 12-Slot I/O Racks

    Power Status Module (PSM) provides status of power supplies

    Uses new extended rack to hold a 2nd (Reserve) power supply andPower Status Module.

    Maintains power to the rack if the Primary power supply fails

    Allows either power supply to be replaced while maintaining power tothe rack.

    Available as an optional field installation kit

    O t I t f

  • 8/10/2019 PLC HC900 Honeywell

    34/179

    HC900 Training Part 1 34Version 4.1 11/16//06Honeywell Proprietary

    Operator Interface

    Honeywell Operator Interface ConnectionsOnly Lead CPU Communicates

    No Fail-over detection on loss of link

    RS 485

    ELNProtocol

    OI maintains communication to new Lead

    following Fail-over

    Only one OI per CPU pair

    HC Designer Network Settings

  • 8/10/2019 PLC HC900 Honeywell

    35/179

    HC900 Training Part 1 35Version 4.1 11/16//06Honeywell Proprietary

    HC Designer Network Settings

    New Device Name for controller + IP Address

    Two IP addresses must be on different Sub-Net

    Redundancy Diagnostic Monitoring

  • 8/10/2019 PLC HC900 Honeywell

    36/179

    HC900 Training Part 1 36Version 4.1 11/16//06Honeywell Proprietary

    Redundancy Diagnostic Monitoring

    PC with Simplex Network

  • 8/10/2019 PLC HC900 Honeywell

    37/179

    HC900 Training Part 1 37Version 4.1 11/16//06Honeywell Proprietary

    PC with Simplex Network

    BA

    100 base-T

    Up to 100m

    Ethernet

    Switch

    RS-485

    Twisted Pair

    10/100 base-T

    Small Redundant System

  • 8/10/2019 PLC HC900 Honeywell

    38/179

    HC900 Training Part 1 38Version 4.1 11/16//06Honeywell Proprietary

    Small Redundant System

    BA

    100 base-T

    Up to 100m

    10/100 base-T

    RS-485

    Twisted Pair

    Vista R400, Specviewor 3rd Party Software

    OPC Server

    with Dual

    Ethernet support

    Controller withRedundant Power,

    Redundant CPU,

    RSM

    Ethernet

    Switch

    Large Redundant System

  • 8/10/2019 PLC HC900 Honeywell

    39/179

    HC900 Training Part 1 39Version 4.1 11/16//06Honeywell Proprietary

    Large Redundant System

    BA

    100 baseT

    10/100 baseT

    Peer to Peer

    Data Exchange

    Ethernet Switch,

    Honeywell 8 Port

    Switching Hub

    Controller

    Rack

    OPC Server

    to PC Software

    Ethernet

    Switch

    I/O

    Rack

    Redundant HC900 Controller with Five I/O Racks

    Expanded Architecture

  • 8/10/2019 PLC HC900 Honeywell

    40/179

    HC900 Training Part 1 40Version 4.1 11/16//06Honeywell Proprietary

    Expanded Architecture

    Network with Redundant & Non-redundant Controllers

    B

    A

    100 baseT

    10 baseT

    Peer to Peer

    Data Exchange

    Redundant HC900, Redundant Network Non-Redundant HC900

    I/O Rack

    Controller & I/O

    Rack

    I/O Rack

    I/O Rack

    Controller

    Rack

    OPC Server with

    Redundant Network Support

  • 8/10/2019 PLC HC900 Honeywell

    41/179

    HC900 Training Part 1 60Version 4.1 11/16//06Honeywell Proprietary

    HC Designer

    Save Time Using HC900s One-Stop Tool

  • 8/10/2019 PLC HC900 Honeywell

    42/179

    HC900 Training Part 1 61Version 4.1 11/16//06Honeywell Proprietary

    g p

    Control Strategy configuration Drag and drop and soft-wire function blocks

    Multiple worksheets for process segmentation

    Operator Interface Configuration

    Standard and User defined displays

    OI Data Storage Configuration

    Configure data groups, storage rates, continuous or batch selection

    Create files for data storage setup

    Alarms and Events, plus E-mailed Alarm/Event Setup

    Select tags for alarms/events, set priorities for e-mail of occurrence Set up alarm groups, remote acknowledge plus common alarm output

    Communications Setup Ethernet Host and Peer-to-peer

    Serial Modbus Master/Slave

    Documentation - Preview, Print Out, and Export Function block configurations, Tag List / Modbus addresses, I/O list, OI Display

    setup

    Recipes, profiles, schedules, sequences

    Significant Features

  • 8/10/2019 PLC HC900 Honeywell

    43/179

    HC900 Training Part 1 62Version 4.1 11/16//06Honeywell Proprietary

    g

    RUN Mode editing, with limited process disturbanceAdd, delete, modify analog and logic blocks, add tags, change soft-wiring

    On-line monitoring for debug and setup

    Use watch windows, view multiple function blocks, change internal block values,force block outputs including I/O, view live logic power flow, signal trace back & find

    Operate Control Loops, SP programmers, SequencersOn-line operation for testing, or override (includes auto-tune)

    Annotate configuration with 4 text sizes

    4 colors, plus Bold, Italic attributes

    Controller / Network Diagnostics

    Check I/O, Controller, Network Host Connections, Peer Controller status

    Architecture

  • 8/10/2019 PLC HC900 Honeywell

    44/179

    HC900 Training Part 1 63Version 4.1 11/16//06Honeywell Proprietary

    Use Ethernet 10Base-T, RS232 direct, or RS232 modem connectionfor access including monitoring, run-mode configuration edits

    Windows NT, 2000 & XP compatible

    Access multiple controllers connected via Ethernet or over Internet

    Use concurrently with HMI, DAQ software over Ethernet

    Ethernet 10Base-T LAN or Internet / Intranet

    Direct RS-232, RS-485

    9.6 57.6KB

    Modem

    9.6 - 38.4 KB

    Or

    Or

    Switch

    See Quick Start Guide

    HC Designer Layout

  • 8/10/2019 PLC HC900 Honeywell

    45/179

    HC900 Training Part 1 64Version 4.1 11/16//06Honeywell Proprietary

    File Browser

    WorksheetToolbox

    Function Block

    Worksheets (20) Worksheet Category Tabs

    Graphic

    Configuration Page

    Fast, Normal Scan

    & ConfigurationFunction Block Lists

    Main Toolbar

    Main menu

    WorksheetToolbar

    Functional Tabs

  • 8/10/2019 PLC HC900 Honeywell

    46/179

    HC900 Training Part 1 65Version 4.1 11/16//06Honeywell Proprietary

    Listing of Controller

    I/O Used Including Ranges

    Operator Interface Display Key AssignmentsFunction Block Diagram Worksheet Pages

    Controller Utility Functions

    Hybrid Control Designer Organizes Your Configuration and Setup Tasks

    with Separate Tools Related to Each Function

    Graphic Function Block Configuration

  • 8/10/2019 PLC HC900 Honeywell

    47/179

    HC900 Training Part 1 66Version 4.1 11/16//06Honeywell Proprietary

    Simply Drag and Drop Function Blocks and Soft-Wire

    Over 100

    Function Block Types!

    Click on desired item

    and drag to diagram

    Click on output

    pin and connect to input

    pin of another block

    or to a Signal Tag

    Click on block to

    view dialog box for

    block entries

    Analog Input Dialog box - simple address, input type and range assignment backup

    HC900 Function Blocks

  • 8/10/2019 PLC HC900 Honeywell

    48/179

    HC900 Training Part 1 67Version 4.1 11/16//06Honeywell Proprietary

    What are Function Blocks?

    Pre-programmed

    functions or

    algorithms for user

    configuration of

    control strategiesthrough soft-wire

    connection

    Function Block Attributes

  • 8/10/2019 PLC HC900 Honeywell

    49/179

    HC900 Training Part 1 68Version 4.1 11/16//06Honeywell Proprietary

    Function Block Number

    assigned by the sequence

    of programming.

    AI = mnemonic

    267 = block #267

    Block Order number, or sequenceof execution during On-line

    operation.

    11 = the 11th block to be executed.

    The order may be changed from

    the Configure menu

    Principal Blocks such asPID Blocks and Setpoint

    programmer blocks have

    tag names.

    Outputs

    Inputs

    Analog Pin

    Digital Pin

    I/O BlockPhysical address:

    010201 = Rack #1,

    Module #2, Channel #1

    =Transitional

    (Rising Edge) Trigger

    Function Block Attributes

  • 8/10/2019 PLC HC900 Honeywell

    50/179

    HC900 Training Part 1 69Version 4.1 11/16//06Honeywell Proprietary

    Digital

    Variable for

    disabling

    analog input

    Softwire connectionsDouble-click on output pin

    & single-click on input pin

    Analog Input Function Block

    Analog Output

    Function Block

    PID Function

    Block

    Signal Tags for reference and

    use by OI & Host devices

    Page Connectorto connect function block pins

    on same page, different pages or different

    worksheets. Does not use Modbus address

    Analog

    Variable

    for RSP

    HC Designer Worksheets

  • 8/10/2019 PLC HC900 Honeywell

    51/179

    HC900 Training Part 1 70Version 4.1 11/16//06Honeywell Proprietary

    Segment Your Configuration Logically for Convenient Access

    Use Signal Tags and Connectors for reference within / between worksheets orto substitute for soft-wiring

    Signal Tag

    Connector

    HC Designer Tool Bars

  • 8/10/2019 PLC HC900 Honeywell

    52/179

    HC900 Training Part 1 71Version 4.1 11/16//06Honeywell Proprietary

    Convenient Tool Bars are Provided for Configuration Selections

    Main Tool bar

    For Function Block programming:

    Add Worksheet Cut, Copy &

    Paste

    Zoom In, Out

    Set up Alarms, Events

    Readjust

    Block Order Unlock protected

    Worksheet

    Upload, Download Configuration

    For 1042 OI Display configuration

    Monitor ModeSignal

    Traceback

    Show / Hide Tool Box, Browser

    Help topics

    Controller Operations

    Configure e-mail

    alarms, eventsSet Controller name

    Print I/O list

    Configure

    DisplaysConfigure

    Data Storage

    Configure alarms, events

    Configure

    OI security

    Configure

    Help Displays

    Find GridPropertiesPrint

    Worksheet

    Unlock Display

    Worksheet

    File

    Names

    Startup

    Display

    Print Report

    Re-arrange sheets

    Print

    Display

    List

    Unlock Controller

    Operations Worksheet

    Operator Interface Configuration

  • 8/10/2019 PLC HC900 Honeywell

    53/179

    HC900 Training Part 1 72Version 4.1 11/16//06Honeywell Proprietary

    Its Simple - because the database is integrated!

    Select OI Display Button (1- 8)Apply Display Format to a Display Position

    Select Tags for Display Group,Apply to Display Format

    Configuration Editing

  • 8/10/2019 PLC HC900 Honeywell

    54/179

    HC900 Training Part 1 73Version 4.1 11/16//06Honeywell Proprietary

    Make Configuration Changes While In the RUN Mode

    Add/delete analog and logic blocks (other than I/O blocks), tags, invert logic inputs

    Change soft-wiring

    Add a worksheet

    Change / add profiles, sequences, schedules, recipes

    Change / add operator interface displays

    Download Complete

    Hot Start

    The Controller is in RUN Mode

    Use the configuration I just downloaded. Do not re-

    initialize the controllers memory. Outputs will be held

    during restart. Stay in RUN mode.

    Cold StartUse the configuration I just downloaded. Re-initialize

    the controllers memory. Outputs will be de-energized

    during restart. Return to RUN mode.

    AbortDo not use the configuration I just downloaded. I want

    to continue as if I did not perform this new download.

    Stay in RUN mode.

    Stay in

    PROGRAM

    Mode

    Not available in this mode.

    Save, then download configuration (held in a memory buffer)

    The controller validates the change

    Using Hot Start selection, outputs are then held, configuration is updated in

    minimal time with continuation at the beginning of a scan

    Use configuration with changes

    Actions for enabling RUN Mode change:

    Use configuration with

    changes, initialize all values

    Keep present configuration now

    running in controller

    Configuration Editing

  • 8/10/2019 PLC HC900 Honeywell

    55/179

    HC900 Training Part 1 74Version 4.1 11/16//06Honeywell Proprietary

    Increase Process Up-timeWith

    Expanded Hot-start after download

    Provides approximate time

    outputs will be held.

    Supports I/O changes

    and extensive edits

    (previous Cold Start only)

    Outputs are held during

    Hot-start restart.

    Users choice to doHot-start or Cold-start.

    HCD Monitoring Mode

  • 8/10/2019 PLC HC900 Honeywell

    56/179

    HC900 Training Part 1 75Version 4.1 11/16//06Honeywell Proprietary

    Tools For Testing Your Configuration

    Watch

    Windows Data Categories

    - Tags

    - Variables- I/O

    - Display data

    User-defined

    data Window

    Column Sorting

    Write values Force outputs

    Select Tag to

    go to location

    Multiple Block

    Monitoring

    Block Entries

    Force outputs

    Operate loops,

    programmers,

    sequencers

    Pin

    Monitoring

    (live data)

    Color-Coded Logic Power Flow

    Signal Traceback

  • 8/10/2019 PLC HC900 Honeywell

    57/179

    HC900 Training Part 1 76Version 4.1 11/16//06Honeywell Proprietary

    Use Signal traceback to determine source of input for debug

    Right click on function block pin to trace back to source, even

    through multiple worksheets

    Return back by clicking on source tag to Find where used

    Click line to

    Access

    Location

    Where does PB1 tagoriginate?

    Configuration Security

  • 8/10/2019 PLC HC900 Honeywell

    58/179

    HC900 Training Part 1 77Version 4.1 11/16//06Honeywell Proprietary

    Password Protect Your Configuration

    From General Read Access (No access without password)

    On a Worksheet Basis (allows access to other Worksheets or to other functions only)

    Protect Operator Interface Display Changes

    Protect Controller Changes for Controller Name, E-Mail Setup

    Total Read Access

    Password

    Entry

    Selective

    Worksheet

    Protection

    Utility Functions

    C i t A f

  • 8/10/2019 PLC HC900 Honeywell

    59/179

    HC900 Training Part 1 78Version 4.1 11/16//06Honeywell Proprietary

    Convenient Access for:

    Setup, Test,

    Selection of

    PC Ports for

    Controller

    Access

    Setup of

    Controller

    Serial Ports

    Setup of

    Controller Ethernet

    Address, Name.Mail Server address,

    Mode, Time

    OI Data Storage

    SetupCalibration

    of Analog I/O

    Controller,I/O,

    Remote Rack

    Diagnostic

    Status

    Upload/

    Download

    Configuration Reports

  • 8/10/2019 PLC HC900 Honeywell

    60/179

    HC900 Training Part 1 79Version 4.1 11/16//06Honeywell Proprietary

    Make Selection of Desired Report Printout:

    Controller I/O

    Used List

    Function Block Diagram

    Worksheets

    Operator Interface Display List

    Recipe, Profile,

    Schedule, Sequence

    Printout by name

    Alarm Groups,

    Events Assigned

    Principal block

    (PID, SPP, etc.) lists

    User-defined Modbus

    register map with data types

    assignable (for interface to

    touch panels and HMI software)

    Signal Tags, Variables &

    Function Block Parameters

    by number with Modbus addresses

    Sample Reports

  • 8/10/2019 PLC HC900 Honeywell

    61/179

    HC900 Training Part 1 80Version 4.1 11/16//06Honeywell Proprietary

    Function Block Diagram Pages

    Sample Reports

  • 8/10/2019 PLC HC900 Honeywell

    62/179

    HC900 Training Part 1 81Version 4.1 11/16//06Honeywell Proprietary

    Setpoint Profile Report

    Sample Reports

  • 8/10/2019 PLC HC900 Honeywell

    63/179

    HC900 Training Part 1 82Version 4.1 11/16//06Honeywell Proprietary

    Select .csv or .txt formats, export

    to Excel or Word: I/O list

    Tag lists with Modbus addresses

    (for 3rd Party HMI Interface)

    Recipes

    Sample Reports

  • 8/10/2019 PLC HC900 Honeywell

    64/179

    HC900 Training Part 1 83Version 4.1 11/16//06Honeywell Proprietary

    I/O Configuration File (.txt format)

    Tag Information Report ( CSV File)

    Report File Export Signals & Variables

  • 8/10/2019 PLC HC900 Honeywell

    65/179

    HC900 Training Part 1 84Version 4.1 11/16//06Honeywell Proprietary

    Viewing tag export forHC900 Signal Tags in Excel

    Tag Information Report (.CSV File)

    Signals Only, Variables Only or Signals and Variables Lists Modbus addresses in Hex and decimal formats

    Used for HMI integration (edit format and import where applicable)

    Report File Export PID Loops

  • 8/10/2019 PLC HC900 Honeywell

    66/179

    HC900 Training Part 1 85Version 4.1 11/16//06Honeywell Proprietary

    Viewing Modbus function

    block registers in Excel

    PID Loops .CSV File (lists all PID parameters)

    Report File Export Where Used List

    Identify data source and

  • 8/10/2019 PLC HC900 Honeywell

    67/179

    HC900 Training Part 1 86Version 4.1 11/16//06Honeywell Proprietary

    Identify data source and

    all blocks that use the data

    Save time troubleshooting.

    Document configurations.

    Verify function block connections.

    Worksheet Page

    Alarms - Overview

    A li d t Di it l Si l T

  • 8/10/2019 PLC HC900 Honeywell

    68/179

    HC900 Training Part 1 87Version 4.1 11/16//06Honeywell Proprietary

    Applied to any Digital Signal Tag

    Capacity- 240 Alarm Points

    20 Alarm Groups (12 Alarm Points per Group)

    Only active when put into an Alarm Group orassigned to an OI Alarm Display

    Alarm Detection- Choice of Off-to-On or On-to-Off on a per Alarm Point basis

    Alarm Acknowledgement- Choice of Manual or Automatic for each point

    Auto will acknowledge the alarm when point returns to non-alarmstate (will not transition into Clearedstate). Does not require useracknowledgement

    Alarm Priority for each point Low (2), Medium (3), High (4), Emergency (5)

    Alarm Priority is used for Routing alarms to E-mail

    Alarm Blocks

    HITEMP output is on

  • 8/10/2019 PLC HC900 Honeywell

    69/179

    HC900 Training Part 1 88Version 4.1 11/16//06Honeywell Proprietary

    HITEMP output is on

    when SIGNAL A isgreater then HIALMSP1

    This Alarm block has been configured

    to alarm when F2ZONE1PV is greater

    them F2ZON2PV by the value ofZONEDVSP. The alarm output

    ZONEDEV is configured to latch on

    Selections

    Alarms Contd

    Alarm Group Function Block

  • 8/10/2019 PLC HC900 Honeywell

    70/179

    HC900 Training Part 1 89Version 4.1 11/16//06Honeywell Proprietary

    Alarm Group Function Block

    ACTIV pin ON if any alarms in the group are active

    UNACK pin ON if any alarms in the group have

    not been acknowledged

    Lo-to-Hi transition on ACK pin acknowledges allalarms in the group

    Alarm Details & Storage

  • 8/10/2019 PLC HC900 Honeywell

    71/179

    HC900 Training Part 1 90Version 4.1 11/16//06Honeywell Proprietary

    Details -

    Number of Alarm Occurrences

    Counts number of transitions into alarm state Per Alarm Point

    Displayed on OI Alarm Point Detail Screen

    Reset on controller cold start

    Storage on OI Disk

    Alarm File Record Limit

    Configurable from 150 to 1500 alarm records

    Events

  • 8/10/2019 PLC HC900 Honeywell

    72/179

    HC900 Training Part 1 91Version 4.1 11/16//06Honeywell Proprietary

    64 Event Points

    Choice of On-to-Off or Off-to-On on a

    per Event Point basis Event Priority

    Events do not have multiple priorities as

    do Alarms Events considered at a priority lower than

    alarms

    Event processing in the OI

  • 8/10/2019 PLC HC900 Honeywell

    73/179

    HC900 Training Part 1 92Version 4.1 11/16//06Honeywell Proprietary

    Filtering Each event point may be configured to go to:

    OI Event File on the data archive disk

    OI Status Line and Event Summary Screen

    E-Mail

    Any or all (at least one) of the above

    Summary Screen

    Last 150 events

    Adds tag name and state text to event descriptor for

    each record

    Storage on OI Disk

    Event File Record Limit

    Configurable from 150 to 1500 event records

    Alarm Setup

  • 8/10/2019 PLC HC900 Honeywell

    74/179

    HC900 Training Part 1 93Version 4.1 11/16//06Honeywell Proprietary

    20 Alarm Groups, each with 12 alarms provides a total of 240 alarms

    Event Setup

  • 8/10/2019 PLC HC900 Honeywell

    75/179

    HC900 Training Part 1 94Version 4.1 11/16//06Honeywell Proprietary

    Provides reportable event 16-character notification on OI banner line,

    replaced by next reportable event

    Email Notification Setup

  • 8/10/2019 PLC HC900 Honeywell

    76/179

    HC900 Training Part 1 95Version 4.1 11/16//06Honeywell Proprietary

    Alarm & Event E-Mail

  • 8/10/2019 PLC HC900 Honeywell

    77/179

    HC900 Training Part 1 96Version 4.1 11/16//06Honeywell Proprietary

    Email will contain From: Controller Name

    Subject: (Configurable Text)

    Body of E-mail: Date & Time

    Alarm or Event Tag Name

    Alarm State

    48 Character alarm or event text

    HC Utilities

  • 8/10/2019 PLC HC900 Honeywell

    78/179

    HC900 Training Part 1 97Version 4.1 11/16//06Honeywell Proprietary

    Configure recipes, data storage files off-line Save to floppy disk or load to pool in controller directly

    Monitor configurations using serial or Ethernet ports Use all HC Designer Monitor tools

    Alter values on-line Variables, loop parameters, block values, etc.

    No forcing allowed of I/O, block outputs

    Save Configurations

    No Function Block Configuration Changes Allowed!

    HC Utilities

    Create and Edit

  • 8/10/2019 PLC HC900 Honeywell

    79/179

    HC900 Training Part 1 98Version 4.1 11/16//06Honeywell Proprietary

    Create and Edit

    Recipe Files

    Save files and download

    separately or load via OI disk.

    Save to File

    Download to pool

    Model/Revision Numbers

  • 8/10/2019 PLC HC900 Honeywell

    80/179

    HC900 Training Part 1 99Version 4.1 11/16//06Honeywell Proprietary

    HC900 components that may change as the CPU firmware changes.Scanner Modules

    Hybrid Control Designer Software

    Hybrid Control Utilities Software

    1042, 559 Operator Interfaces

    User Manuals/CD

    HC900 Firmware Revisions

  • 8/10/2019 PLC HC900 Honeywell

    81/179

    HC900 Training Part 1 100Version 4.1 11/16//06Honeywell Proprietary

    CPU - use HC Designer, controller diagnostic function in the Monitor mode(also displayed on OI Unit Setup, Controller Status display)

    HC900 Firmware Revisions

    I/O Scanner- use HC Designer, rack diagnostic function in the Monitor

  • 8/10/2019 PLC HC900 Honeywell

    82/179

    HC900 Training Part 1 101Version 4.1 11/16//06Honeywell Proprietary

    mode

    HC900 Firmware Revisions

    HC Designer- In HC Designer, under the Help pull-down menu, select About.

  • 8/10/2019 PLC HC900 Honeywell

    83/179

    HC900 Training Part 1 102Version 4.1 11/16//06Honeywell Proprietary

    HC900 Firmware Revisions

  • 8/10/2019 PLC HC900 Honeywell

    84/179

    HC900 Training Part 1 103Version 4.1 11/16//06Honeywell Proprietary

    Operator Interface Appears in lower right corner of Log Off display

    UNIT LOGGED OFFAUG09

    11:30

    HYBRID

    CONTROLLER

    HC900

    WHEN YOU NEED MORE THAN

    JUST DISCRETE CONTROL

    PRESS ENTER TO LOG ON

    51452188 FIRMWARE VERSION 4.000

    UNIT LOGGED OFFAUG09

    11:30

    HYBRID

    CONTROLLER

    HC900

    WHEN YOU NEED MORE THAN

    JUST DISCRETE CONTROL

    PRESS ENTER TO LOG ON

    51452188 FIRMWARE VERSION 4.000

    HC900 Firmware Revisions

    Firmware can be downloaded (no-charge) at:

  • 8/10/2019 PLC HC900 Honeywell

    85/179

    HC900 Training Part 1 104Version 4.1 11/16//06Honeywell Proprietary

    http://content.honeywell.com/ipc/faq/

    HC900 Firmware Revisions

  • 8/10/2019 PLC HC900 Honeywell

    86/179

    HC900 Training Part 1 105Version 4.1 11/16//06Honeywell Proprietary

    Downloading CPU firmware upgrade

    Use Utilities functional tab

    Industrial Measurement and Control

    HC900 H b id C t ll

  • 8/10/2019 PLC HC900 Honeywell

    87/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary 1Version 4.1 11/16//06

    HC900 Hybrid ControllerTraining - Part 2

    Function Blocks

    Process Control (65 Algorithms)

    Process Function Blocks (21)

    AI, AO, PID, ON/OFF

    Math / Calculations (19)

    Scale and Bias

  • 8/10/2019 PLC HC900 Honeywell

    88/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary 2Version 4.1 11/16//06

    Carbon Potential (CARB)

    3 Position Step (TPSC)

    Time Proportional Out (TPO)

    Position Proportional Out (PPO)

    SP Programmer (SPP) SP Scheduler (SPS) / Aux (SPSA)

    Loop, Mode, State Switches

    Mode, State Flags

    Write Tuning Con, Auto Man. Bias

    Recipe Selector, Event Decoder

    (ADD, SUB, MUL, DIV, ABS

    4ADD, 4SUB, 4MUL, SQRT

    Relative Humidity, Dew Point

    Compare, Deviation Compare,

    Negate, Totalizer, Cont. Average Free Form Math

    Mass Flow, Max-Min-Avg-Sum

    AGA

    Auxiliary (16)

    Function Generator

    Lead Lag, Track and Hold

    Alternator, Stage, Ramp

    Device Control, Hand-Off-Auto

    High-Low Limiter, Velocity Limiter Rate of Change

    Read Constant, Write Constant

    Digital Encoder/Decoder

    Alarm Monitor / Selector (9)

    High, Low and System Monitor

    Analog Alarm High Selector, Low Selector

    Analog Switch, Rotary Switch

    Bumpless Transfer

    Logic Control (45 Algorithms)

    Logic Function Blocks (21) DI, 8DI, DO, 8DO

    Communications (6)

    Peer Read

  • 8/10/2019 PLC HC900 Honeywell

    89/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary 3Version 4.1 11/16//06

    2, 4, 8 AND; 2, 4, 8 OR, XOR, NOT

    Digital Switch, Trigger, Latch

    Toggle Flip-Flop, Pushbutton

    Free-Form Logic

    Four Selector Switch

    Sequencer

    System Monitor

    Peer Read Peer Write

    Peer Comm

    Modbus Slave

    Modbus Read

    Modbus Write

    Modbus TCP Slave

    Modbus TCP Read

    Modbus TCP Write

    Counters/Timers (5) Resetable Timer Periodic Timer

    Off Delay Timer, On Delay Timer

    Up Down Counter

    Real Time Clock Calendar

    Control Execution

    InputsInputsInputsInputs

  • 8/10/2019 PLC HC900 Honeywell

    90/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary 4Version 4.1 11/16//06

    Comm.Comm.

    Processing

    Fault detectFault detect

    Processing

    Fast ScanFast Scan

    Processing

    Normal ScanNormal Scan

    Processing Processing ProcessingProcessingProcessing

    OutputsOutputsOutputs Outputs

    500ms (typical)500ms (typical) 27 to 107ms27 to 107ms

    Inputs measured, outputs set each scan

    No over-sampling

    400 fast logic blocks at 27msec (50msec. with remote I/O) Cycle time will adjust to level the processor load

    Normal Scan cycle time not linked to number of AI modules

    HC900 Capacity

    5100 total function block capacity

  • 8/10/2019 PLC HC900 Honeywell

    91/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary 5Version 4.1 11/16//06

    5100 - total function block capacity 5000 user blocks

    100 reserved (system) blocks

    Execute regardless of configuration system monitor (fast and slow)

    rack monitor (5)

    alarm group (30)

    port blocks

    variables

    constants

    User defined blocks start at 101

    Database Expansion Some Examples

    V2.4 V4.0

  • 8/10/2019 PLC HC900 Honeywell

    92/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary6

    Version 4.1 11/16//06

    Item

    Type

    C30 C50 C70 C70R C30 C50 C70 C70R

    User FB 400 2000 5000 5000 400 2000 5000 5000

    PID 8 32 32 32 400 2000 2568 856

    SPP 8 8 8 8 400 1325 1325 441

    SEQ 4 4 4 4 400 >1100 >1100 >360

    Device 16 16 16 16 400 2000 5000 5000

    Alternator 6 6 6 6 400 1820 1820 606

    Variables 600 600 600 600 2048 2048 2048 2048Alarms 240 240 240 240 360 360 360 360

    Signals 2000 2000 2000 2000 Available

    Memory

    Available

    Memory

    Available

    Memory

    Available

    Memory

    Modbus

    Slave

    16 16 16 16 32 32 32 32

    Slave

    values

    384 384 384 384 1024 1024 1024 1024

    Database Expansion contd

    HCD displays memory utilization and normal

    & fast cycle times

  • 8/10/2019 PLC HC900 Honeywell

    93/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary7

    Version 4.1 11/16//06

    & fast cycle times

    HC900 Database size vs Performance

    No preset limits on individual function block type quantity Limited only by available memory and required scan rate

    User can allocate memory for function blocks recipes etc to

  • 8/10/2019 PLC HC900 Honeywell

    94/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary8

    Version 4.1 11/16//06

    User can allocate memory for function blocks, recipes, etc. to

    maximize the power of HC900

    C 70 CPU Performance examples

    Total

    Function

    Blocks

    PID

    Blocks

    Fast

    Scan

    Blocks

    Recipes

    &

    Profiles

    Config

    Memory

    Usage

    Normal

    (Process)

    Scan Time

    Fast

    (Logic)

    Scan

    Time

    230 40 50 99 7.37% 507 ms 27 ms

    630 75 225 99 9.64% 533 ms 53 ms

    1015 100 375 99 12.12% 800 ms 53 ms1975 125 750 99 17.45% 1067 ms 107 ms

    1975 125 750 1000 70.93% 1067 ms 107 ms

    AI Block

  • 8/10/2019 PLC HC900 Honeywell

    95/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary9

    Version 4.1 11/16//06

    Burnout check - T/Cs Bad Channel Detection Un-

    checking eliminates diagnostic failureindication in controllerDisable Channel -

    Output value when

    channel is disabled.Range: For Linear Inputs Only

    Actuation Input = 4-20mA

    Process variable = Flow

    Range of Flow = 0 to 250 gal/minHigh Range Display Value = 250

    Low range Display Value = 0

    Filter Time - Digital filter

    smooths the input.Configurable the first order

    lag time constant from 1 to

    120 seconds. Noisy Sensor

    Bias To compensate

    input for drift of an input

    value due to deterioration

    of a sensor, or some

    other cause. Calibration

    Failsafe - Value output will go to protect

    against the effects of failure of the

    equipment, such as, fuel shut-off if there is

    loss of flame in a furnace, or a sensor

    break.

    AI with Remote CJ

  • 8/10/2019 PLC HC900 Honeywell

    96/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary10

    Version 4.1 11/16//06

    Process

    Remote

    Junction

    Panel

    Compensated

    Leadwire

    Copperwire

    Compensated

    Leadwire

    Process

    Remote

    Junction

    Panel

    Compensated

    Leadwire

    Copperwire

    Compensated

    Leadwire

    AI with Remote CJ

    In the I/O folder

  • 8/10/2019 PLC HC900 Honeywell

    97/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary11

    Version 4.1 11/16//06

    In the I/O folder Use when TC Cold Junction is NOT

    at the AI Module terminals

    Thermocouples only

    Use dedicated AI channel to measureRemote Junction Temp:Connect Output to all associated RCJ Input(s).Connect Fail Pin to all associated RSTAT Input(s)

    Copper Wire connection from RemoteTerminals to AI Module

    Rcj Input in C only

    Rcj Temp Range: -30 to 90 CWarn or Fail if outside limits (user configurable)

    AI with Remote CJ Sample Configuration

    RCJ i t i D C

  • 8/10/2019 PLC HC900 Honeywell

    98/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary12

    Version 4.1 11/16//06

    RCJ input in Deg C

    AO Block

    Slew Rate is the

    maximum rate of

    change required todri e the o tp t from

  • 8/10/2019 PLC HC900 Honeywell

    99/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    13

    Version 4.1 11/16//06

    drive the output from

    full OFF (0% - typically

    4 mA) to full ON (100%

    - typically 20mA).

    Convert this to a

    maximum change of themilliamp output per

    execution cycle of the

    block. 0.0 to 99

    Failure output on module error

    Output Pin (mA)

    Failsafe - CPU Comm failure ormodule not available

    Use Value - sets the output to the

    programmed value when failure is

    detected. 0 to 21 mA Default = 0

    High - sets the output of the blockto the High Output Range Value

    when failure is detected

    Low - sets the output of the block

    to the Low Output Range Value

    when failure is detected

    Hold - maintains the last value of

    the block just prior to the failure

    being detected

    See Note Page

    DI Block

    Digital Inputs

    Configurable Inversion

  • 8/10/2019 PLC HC900 Honeywell

    100/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    14

    Version 4.1 11/16//06

    g FAIL output pin

    TRUE when input card fails

    Configurable failsafe (per

    channel on 8 Input block) Fail OFF, Fail ON, Fail HOLD

    8 Input Block

    All inputs on the same module

    (channels 1-8 or 9-16)

  • 8/10/2019 PLC HC900 Honeywell

    101/179

    Pulse Input Block

    Reads input pulses (3 usec) and measures rate (pulses/time in EU).

    Sends the preset values, reset, preset action, and hold flags to the module

    Module returns pulse count, preset indicator (PREI), overflow (OVFL), and FAIL. Preset value in EU (triggers block and module output)

  • 8/10/2019 PLC HC900 Honeywell

    102/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    16

    Version 4.1 11/16//06

    Preset value in EU (triggers block and module output)

    Preset action checked = Pulse output for 1 second when Count = Preset

    Preset Action unchecked = output ON and count stopped until Reset

    Inputs

    HOLD = ON holds count (OUT) at current value.RPRES = Remote preset value.

    ^RST = Resets pulse counter & OUT to zero.

    OutputsFAIL = ON when module reports a failure. Cleared by the ^RST input.

    PREI = ON when the count (OUT) reaches the local or remote preset value.OVFL = Overflow flag turns ON when the counter on module is full.

    RATE = Rate in pulses in EU/Time (hour,min,sec)

    Out = Accumulated EU count

    Pulse Ouput Block

    Generates a pulse train following a start instruction

    Pulse frequency is selectable. Output controls an output transistor on the module.

  • 8/10/2019 PLC HC900 Honeywell

    103/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    17

    Version 4.1 11/16//06

    p p

    Pulses remaining (following start) present on OUT

    InputsENABL = ON enables the block

    ^START #PLS = ON transition starts the pulse train#PULSES = Number of pulses in the pulse train

    START CONT. = Start Continuous Pulse Train.

    Superceedes ^START #PLS.OutputFAIL = On when module reports a failure.

    OUT = Pulses remaining when START CONT. is off.Zero if START CONT. is ON

    Frequency Input Block

    Measures speed and rate.

    The signal is scaled from the selected frequency span tothe selected output range

  • 8/10/2019 PLC HC900 Honeywell

    104/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    18

    Version 4.1 11/16//06

    p g

    Provides an output value in engineering units.

    Signal is rejected if it is not within selected pulse width range.

    Rejection causes output to go to failsafe and a

    failure-to-convert error occurs.

    InputsENABL = Enables block. Ignored if not connected and default

    state is enabled. If block is disabled the output goes to zero.

    Outputs

    FAIL = ON when module reports a failure.OUT = The frequency input value scaled to engineering units

    (after filters, ranges, bias, or failsafe conditions have been

    applied).

    Frequency Span

    50-400HzPulse Width (Range)10-500Hz

    Quadrature Block

    Measures/controls movement of an actuated device.

    Digital encoder produces two square wave channels.

    There are 4 logic states between these two waves.

    Counting the passing rising edges of the square waves the block measures:

    1) Di t h t EU b i t ll d b th d i

  • 8/10/2019 PLC HC900 Honeywell

    105/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    19Version 4.1 11/16//06

    1) Distance or whatever EU are being controlled by the device.

    2) Distance from zero marker (position)

    3) Sequence between channels; A leads B or B leads A (direction).

    InputsBIAS = Value added to the output in EU.

    ENBIAS = The bias is added to the output.

    ICLR = Index - resets the output to zero (plus bias).

    ^RST = Resets the output to zero (plus bias).

    ^CLFG = Clears error flags to zero.

    OutputsINC = Count is incrementing

    DEC = Count is decrementing

    INDEX = Index pulse is detected and ICLR are asserted.

    CNTERR = Count overflow or underflow (32 bit counter)

    RNGERR = Count exceeds range limits.CDIS = Module detects a cable disconnect.

    FAIL = Module failed. (INC and DEC both ON).

    OUT = Count in EUs.

    Quadrature

    LRL URL

    15 i h

    Uses two pulse inputs, A & B

    1st input detected indicates

  • 8/10/2019 PLC HC900 Honeywell

    106/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    20Version 4.1 11/16//06

    -15 inches0 pulses

    15 inches15,000 pulses

    0 inches7,500 pulses

    position

    -9.8 inches2,600 pulses

    p

    direction

    Index input on Module resets

    counter to zero

    Sense input on the moduleconfirms Encoder connection

    Modes

    X1- rising edge of A are countedX2- rising/falling edge of A are counted

    X4- rising/falling edged of A & B arecounted

    Process Control PID Loops

    PID Block 2 Setpoints (1 local and 1 remote or 2 local)

    32 Loops-C50/C70,C70R, 8 Loops -C30

  • 8/10/2019 PLC HC900 Honeywell

    107/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary

    21Version 4.1 11/16//06

    p ( )

    2 Sets of PID constants (bumpless transfer selection)

    2 Alarms (2 levels each)

    PID-A or PID-B (only integral response to SP change)

    Feedforward Input Output Tracking of external input

    Logic interface for control of mode (A/M, R/L)

    Logic interface for tuning constant selection, auto-tuning

    Soft-start (output limiting on startup)

    Control Types Duplex - Heat/Cool (Dual Output)

    Internal Cascade

    Ratio (with bias)

    Position Proportioning (3-position step)

    Position Proportioning with slidewire feedback for actuators)

    AI Block

    PID Block

    Output Block

    (4-20mA)

    PID Block

  • 8/10/2019 PLC HC900 Honeywell

    108/179

    HC900 Training - Part 2 5/31/06Honeywell Proprietary

    22Version 4.1 11/16//06

    INPUT - PV

    OTHER INPUTS

    Working Set Point in EU

    Alarm 1 Digital Signal

    Alarm 2 Digital Signal

    Autotune Indicator (ON = Autotune in progress)

    A/M Output & Setpoint Mode indication (to MDFL block)

    Back Calculation Output (for Cascade control)

    OTHER OUTPUTS

    Remote Set Point Signal (Eng. unit or %)

    Feed Forward value in %

    Output Track value in %

    Output Track Command (ON/OFF) or Soft Start

    Remote Bias Value for Ratio PID

    Switch Inputs (from SWO on LPSW function block)

    External Mode request (from MDSW block)

    Back Calculation Input (for Cascade control)

    Direct or Reverse Output Status

    (see note page)

    CONTROL OUTPUT

    PID Block - General Tab

    PID A, a step change in setpoint will result in a

    step change in output. The output can be

    adjusted between 100 % and 0 %. It applies allthree control actions

  • 8/10/2019 PLC HC900 Honeywell

    109/179

    HC900 Training - Part 2 5/31/06Honeywell Proprietary

    23Version 4.1 11/16//06

    PID B - Controller gives only an integral

    response to a setpoint change, with no effect

    on the output due to the Gain or Rate

    DUPA - like PID A but provides an automatic

    method to switch tuning constant sets forHeat/Cool applications.

    DUPB - like PID B but provides an automatic

    method to switch tuning constant sets for

    Heat/Cool applications

    Direct - causes output to increase as processvariable increases.

    Reverse - causes output to decrease as

    process variable increases

    Track PV - When control mode is "manual", local setpoint tracks process variable.

    Track RSP - When setpoint is "remote setpoint", local setpoint tracks remote setpoint. Used when

    switching from remote to local setpoint.

    PID Block - Start/Restart Tab

    Output at Power up

    Failsafe - Failsafe output value

  • 8/10/2019 PLC HC900 Honeywell

    110/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary24

    Version 4.1 11/16//06

    p

    Last Out - Same as at power down value

    Initial Setpoint Value - Use initial LSP

    Click on radio button to select. Enter InitialLocal Setpoint Value

    High Output Overide Limit

    Delay Time - time in minutes to use TRV

    as the output high limit.

    Ramp Rate - for High Limit Output (%

    per minute to ramp the default output high

    limit after delay time elapses

    Initial Mode - Cold start or from program

    mode.

    Control Loops

    PID Soft-Start Alternate selection for TRC and TRV inputs

  • 8/10/2019 PLC HC900 Honeywell

    111/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary25

    Version 4.1 11/16//06

    Provides dynamic output limiting

    TRV input sets the initial high limit for the PIDoutput when the TRC input is ON.

    User entries: Limit time - Sets the amount of time the output

    will be limited.

    Rate of increase- Sets the rate at which theoutput limit will increase until the normal PIDlimit is reached.

    Soft-start cancelled if TRC turns OFF

    Soft-Start is Reset when TRC Off, then ON.

    Zero time - TRV sets the PID output when

    TRC in ON ( no time or ramp rate)

    Control Loops

    Soft Start (Continued)

  • 8/10/2019 PLC HC900 Honeywell

    112/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary26

    Version 4.1 11/16//06

    Setup Dialog

    Normal PID Limit

    Output %Output %

    00

    100100

    PID Output Limit with SoftPID Output Limit with Soft--startstart

    Ramp Rate

    Time

    Time Delay

    PID Block - RSP Tab

    Use RSP Input (EU) - Use Remote Setpointin Engineering Units

    Use RSP Inp t (%) U R mot S tpoi t

  • 8/10/2019 PLC HC900 Honeywell

    113/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary27

    Version 4.1 11/16//06

    Use RSP Input (%) - Use Remote Setpoint

    in Percent. When used in a secondary loop

    of a cascade configuration.

    Use LSP2 (EU) - Use Local Setpoint #2 in

    Engineering Units

    No Ratio or Bias - No ratio and bias

    applied to the RSP

    Use Local Bias - Use Bias value selectedon Tab. Enter value at "Local Bias Value"

    on tab.

    Use Bias Input - Use Bias value attached

    to an input to the block

    Local Bias Value (EU) - Enter local biasvalue in engineering units.

    Ratio - Gain value for Ratio PID 20 to

    +20

    PID Block - Range/Limit Tab

    Ranging

    PV High Range - PV High Range Value

    PV Low Range - PV Low Range Value

  • 8/10/2019 PLC HC900 Honeywell

    114/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary28

    Version 4.1 11/16//06

    Limiting

    SP High Limit - prevents the local & remote

    setpoints from going above this value.

    SP Low Limit - prevents the local & remote

    setpoints from going below this value

    Out High Limit - highest automatic output

    value (5 % - 105 %)

    Out Low Limit - lowest automatic output

    value (5 % - 105 %)

    SP Rate Down - rate at which setpoint will

    change from original down to the new one. 0

    (off) to 99999 (eu/min)

    SP Rate Up - rate at which setpoint will

    change from original setpoint up to the newone. 0 (off) to 99999 (eu/min)

    Display

    Decimal Places - Digits to display after

    decimal point (0 to 5)

    Units - Text to display for EU (4

    characters)

    PID Block - Tuning Tab

    Tuning Constants

    Proportional Band (PB) - % of the range ofthe measured variable for which a proportional

    controller will produce a 100 % change in its

  • 8/10/2019 PLC HC900 Honeywell

    115/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary29

    Version 4.1 11/16//06

    controller will produce a 100 % change in its

    output. (0.1 to 1000%)

    Gain - ratio of output change (%) over the

    measured variable change (%) that caused

    it.where PB is the proportional Band (0.1 % to1000 %)

    Reset - Integral Time - adjusts the controller

    output according to both the size of the

    deviation (SP-PV) and the time it lasts. (0.02

    to 50)

    Rate - affects the controllers output whenever

    the deviation is changing; and affects it more

    when the deviation is changing faster. (0 or 0.1

    to 10.00 minutes)

    Manual Reset - Allows correction of output toaccount for load changes to bring the PV up to

    setpoint. Not applicable with Reset (integral time).

    100 to 100 (in % of Output)

    Feedforward Gain - Feedforward Input is

    multiplied by this value. (0.0 to 10.0)

    PID Block - Accutune III Tab

  • 8/10/2019 PLC HC900 Honeywell

    116/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary30

    Version 4.1 11/16//06

    Accutune III

    Cycle Tuning

    - Normal (conservative) and Fast (aggressive) response selections- Cycles the output between the output limit values to create two process oscillation

    cycles about SP. The PV does not have to be stable as with Setpoint tuning. Rate time isusually the Reset time

    - Simplex or duplex output support (calculates one or two tuning sets)

  • 8/10/2019 PLC HC900 Honeywell

    117/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary31

    Version 4.1 11/16//06

    - Simplex or duplex output support (calculates one or two tuning sets)

    Duplex, three action selections:

    Auto calculate both heating and cooling tuning

    Manual manually tune each side

    Disable use only one set of tuning parameters

    Setpoint Tuning-Tunes (on demand) based on the process response to step change in the SP (normal &

    fast response selections) with the objective of reducing process overshoot

    -Introduces a temporary change in the SP by % of FS in the direction selected and holds

    the output at a calculated value until the process response is identified and tuning

    parameters are recalculated. Then normal automatic control is resumed using the

    original SP value. The identification determines tuning parameters values based on one

    or two lag process models with consideration to dead time. If single lag there is no rate

    component.

    - Requires a STABLE PV that is at or nearthe SP before starting.

    -Additional selections: SP Change amount and Change direction.

    - PV Adaptive Tuning

    - Monitors the PV and adjusts tuning constants to eliminate process oscillations over time. -

    If the PV does not oscillate then there are NO tuning parameter changes.

    PID Block - Alarms Tab

  • 8/10/2019 PLC HC900 Honeywell

    118/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary32

    Version 4.1 11/16//06

    Alarm Setpoints

    99999 to 99999 in Engineering

    Units

    Within the PV range when alarm type

    is PV or SP

    Within PV span when alarm type is

    DEV

    5 % to 105 % when alarm type is

    output.

    Alarm Hysteresis - 0 % to 5 %

    PID Associated Blocks

    Activate auto-tune

    Change control action Force Bumpless Transfer

    Select tuning constants

  • 8/10/2019 PLC HC900 Honeywell

    119/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary33

    Version 4.1 11/16//06

    Change Auto/Man

    & Rem/Loc SP

    Select tuning constants

    Write tuning

    constants

    based onENable ON

    Mode Status

    PID Block #accepting writes

    See note page for LO & IMAN

    Position Proportional Output

    Up to 64 Blocks per configuration

    Motor travel time from 12 to 300 Sec. Direct Slidewire Measurements

    F ll A i F db k C lib i

  • 8/10/2019 PLC HC900 Honeywell

    120/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary34

    Version 4.1 11/16//06

    Motor position feedback in %Failed or stalled motor

    Failed slidewire (Defaults to TPSC)

    Slidewire Feedback

    100 1000 ohms

    0 to 5V, 0 to 1V

    0 to 20mA, 4 to 20mA

    Forward & Reverse

    Digital Outputs

    Fully Automatic Feedback Calibration

    SP Programmer

    Library of 99 Profiles in controller

    Up to 50 segments each

    1 Profile ASetpoint Programmer Load Profile by # or Name

  • 8/10/2019 PLC HC900 Honeywell

    121/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary35

    Version 4.1 11/16//06

    Setpoint Programmer

    Function Block

    Running Profile

    (On-line edits)

    Load Profile by # or Name2 Profile B

    3 Profile C

    4 Profile D

    99 Profile ZZ

    Reload on Reset

    Edit & Save Profile by #

    Using HC Designer: At OI

    Copy/Paste/Delete a Profile/Recipe

    Save to a file

    Upload from a file and add to Profile/Recipe poolPrint a Profile/Recipe

    Download selected Profile/Recipe

    Edit Profile Segments

    Save to pool or file

    Load from file

    SP Programmer - Inputs

    ENABL, Disabled if no connection, ON state = Block Enabled

    PV1 PV2 PV3AUX PV

    Used for Soak

    Guarantee

    Aux

    Output

  • 8/10/2019 PLC HC900 Honeywell

    122/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary36

    Version 4.1 11/16//06

    NPGM , New Program Number (1 to 99)

    NSEG, New segment number (1 to 50)

    SET, a pulse input used to load the profile on NPGM

    Jog, a pulse input to Jog to a predefined segment

    RESTRT, Pulse input for restart action after a powerinterruption

    GHOLD, Input ON holds program, input OFF restartsprogram (level)

    RESET, Pulse input to reset the program

    HOLD, Pulse input to hold the program, RUNneeded to restart

    RUN, Pulse input to start the program

    ADV, Pulse input to advance the program

    SP Programmer Block Outputs

    Outputs

  • 8/10/2019 PLC HC900 Honeywell

    123/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary37

    Version 4.1 11/16//06

    Setpoint Out Value

    Auxiliary Analog Output Value

    Time Remaining in Current Segment

    Segment Elapsed Time

    Elapsed Program Time

    Program in Guarantee Soak Hold

    Program in Reset StateProgram in Hold State

    Program in Run State

    Program at End

    Segment #Program State Program #

    Status

    0 = Until block is first

    run after power up

    1 = Reset2 = Hold

    3 = Run

    4 = Ghold

    5 = Stopped

    Event Decoder Block

    SP Programmer Setup

  • 8/10/2019 PLC HC900 Honeywell

    124/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary38

    Version 4.1 11/16//06

    Setpoint Profile Set Up

    Rack Monitor Block

    Monitor the status of a Rack

  • 8/10/2019 PLC HC900 Honeywell

    125/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary39

    Version 4.1 11/16//06

    Part of the reserved block

    space (blocks 96-100)

    Always in the configuration

    Sized to 16 modules to allowfor possible future products

    System Monitor Block

    CYCTIME - Control Block Cycle Time in seconds

    CYCMINS - Control Block Cycle Time in minutesNEWSTART - On for one control block cycle, following a New start (prog run)

    RESTART - On for one control block cycle, following power up. [Warm Start}

  • 8/10/2019 PLC HC900 Honeywell

    126/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary40

    Version 4.1 11/16//06

    y , g p p [ }

    ALM ACTIV - On if any operator panel alarm is ON.

    ALMUNACK - On if any operator panels alarm is unacknowledged.

    HWOK - On if no faults. Off when a Rack Monitor Block,s RACK OK pin is off.

    LOWBTRY - On if the battery is low, Off when battery is good.

    HI TEMP - On if the CJ temperature is >70 Deg C on any rack. (see notes)

    MSTR FAIL - On when Modbus master diagnostic is not good

    BAD BLOCK - On when block(s) are not operating properly (see notes).

    LOCKED - Controller locked in current mode by switch position.

    TIME OFF - Number of seconds power was turned off. Valid for one cycle of

    control blocks execution following power up. Then it is cleared to zero.

    DS LIMIT - On when the configured storage warning limit is exceeded. OFF when

    the storage capacity falls below the warning limit.

    RSV_AVAIL Reserve CPU available (appears only in C70R configuration)

    Restart Logic for SP Programmer

    The restart feature provides a controlled ramp back to set point after a power loss to prevent shock to

    the process work (such as in a kiln). The System Monitor block output pin (Restart) is

    on for the first scan cycle after power loss plus the TIME_OFF output indicates the time the power has

    been off. A Compare block can be used to evaluate the time off (the SET-TOFF Variable sets the

    compare time in secs) which will cause an output to initiate the restart through the AND logic block if this

    time is exceeded.

  • 8/10/2019 PLC HC900 Honeywell

    127/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary41

    Version 4.1 11/16//06

    Power loss

    SP=PV onpower restore

    *Restore RAMP rate

    Program continues

    * mustbe entered under SP Profile properties

    One scan cycle

    IfRESTART is On,

    the block will use

    PV1 as a starting

    value and ramp at

    Restart Rate backto the last SP

    value, then

    complete the

    remaining portion of

    the segment.

    Restart Rate is aproperty of the

    profile (program)

    Recipes

    Load setpoints, select setpoint programs, activate

    valves, set alarm limits and enter other values with a

    single selection

  • 8/10/2019 PLC HC900 Honeywell

    128/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary42

    Version 4.1 11/16//06

    Unlimited Recipes

    Up to 50 Variables/Recipe-Analog Values

    Setpoints

    Timer presets

    Compare values

    - Digital On/Off states

    - Setpoint Profile/Sequence numbers

    Select recipe at OI or via a Recipe blockRUN

    Pushbutton Display Configuration

    PUSH-BUTTON GROUP

    PMP1-LSON PUMP1-MASTER ActionF1

    F2

    Confirmation

  • 8/10/2019 PLC HC900 Honeywell

    129/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary43

    Version 4.1 11/16//06

    F4

    F3

    Toggle

    Flip/Flop

    Digital

    output

    ConfirmationDigital Input

    (Optional)

    American Gas Association (AGA) Blocks

    AGA8GS Compressibility (Gross)

    AGA8DL Compressibility (Detail)

    AGA3OM Orifice Meter

    AGA7TM Turbine Meter

  • 8/10/2019 PLC HC900 Honeywell

    130/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary44

    Version 4.1 11/16//06

    AGA9UM Ultrasonic Meter

    All are in the Calculations folder

    AGA8 Compressibility (Gross)

    The Gross method approximates natural gas compressibilityand density. It works over a limited range of conditions butrequires less instrumentation to implement.

    There are two methods: Method 1 calculates from knowledge of the relative

    density, heating value, carbon dioxide, hydrogen andcarbon monoxide components.M th d 2 l l t f k l d f th l ti

  • 8/10/2019 PLC HC900 Honeywell

    131/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary45

    Version 4.1 11/16//06

    Method 2 calculates from knowledge of the relativedensity, Nitrogen, carbon dioxide, hydrogen and carbonmonoxide components.

    HW is differential pressure. Only used with AGA3 meter block Gas components are local or remote Bottom pin is connected to an AGA meter block. It allows data

    to be passed to the meter block for its calculation. Calculated output pins are supplied for reference only.

    Typically, they are not connected to other blocks. ERR indicates the calculated outputs are set to 0 due to an error

    WARN indicates the calculated outputs are compromised

    STATUS is a number used in a lookup table to determine the nature of the

    error or warning

    Local gas composition can be changed in run-mode by HCD or Modbus

    Block has tagname for Modbus access

    AGA8 Gross with Turbine Meter

  • 8/10/2019 PLC HC900 Honeywell

    132/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary46

    Version 4.1 11/16//06

    AGA8 Compressibility (Detail)

    The Detail method uses the gas analysis of up

    to 21 components to calculate the super-compressibility factor, gas density at flowing

    and standard conditions, and gas relative

  • 8/10/2019 PLC HC900 Honeywell

    133/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary47

    Version 4.1 11/16//06

    density at standard conditions.

    Used when accurate gas analysis is availableeither via an on-line gas analyzer or from

    laboratory measurements.

    If this information is available, the Detail

    method is preferable, as accurate results areobtainable over a wider range of conditions

    than the Gross method.

    ACCESS HCD Calcs.

    AGA8 Detail with Orifice Meter

  • 8/10/2019 PLC HC900 Honeywell

    134/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary48

    Version 4.1 11/16//06

    AGA3 Orifice Meter

    Calculation is based on AGA Report 3

    Supports both flange and pipe-tap orifice meters

    Top pin must be connected to an AGA8 output pin to inherit

  • 8/10/2019 PLC HC900 Honeywell

    135/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary49

    Version 4.1 11/16//06

    AGA8 configuration and calculation results.

    QV, QB, QM, QH outputs are rates of flow which are typicallyconnected to totalizers.

    Rate outputs are individually configurable to be per day or per

    hour, and each have a scale multiplier.

    ERR indicates the calculated outputs are set to 0 due to an

    error. WARN indicates the calculated outputs are compromised due

    to marginal input values used in the calculation.

    STATUS is a number used in a lookup table to determine the

    nature of the error or warning.

    Disable pin forces all calculated outputs to 0, ERR/WARN to

    OFF, and STATUS to 99.

    AGA7 Turbine Meter

    Calculations for gas measurement by TurbineMeters

    QR is the raw flow in ft3/hr or m3/hr

  • 8/10/2019 PLC HC900 Honeywell

    136/179

    HC900 Training - Part 2 5/31/06 Honeywell Proprietary50