nepco national electrical power company etc تم رفعه بواسطة صفحة : الهندسه...

95
NEPCO National Electrical Power Company ETC طة س وا ب ه ع ف م ر ت ن ف م و عل ه ” ي ب ر لكه ه ا س د ن ه ل : ا ه ح ف ص مادى ح مد ح م لاء ع : م/ ن م د9 ا

Upload: noah-merritt

Post on 22-Dec-2015

235 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

 

NEPCO

National Electrical Power Company

ETC

بواسطة رفعه تمعلم : ” الكهربيه الهندسه صفحة

وفن“ / حمادى : محمد عالء م أدمن

Page 2: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

INSTRUMENT TRANSFORMERS

 An instrument transformer is a device  used to reduce the current or voltage values into values can be handled by other equipments.

 Is a device to transform the power system current and voltage to lower magnitudes, and provide an isolation between the power network and the relay and other instruments connected to the transformer secondary winding

National Electrical Power Company

NEPCO ETC

Page 3: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

-Reduce the voltage or current into values that other equipment can handle it.

 

-Isolate the equipments from the power network(i.e. we need more insulation)

-To provide possibilities of a standardization of instruments and relays to a few rated currents and voltages.

Instrument Transformers Why is it Needed?

National Electrical Power Company

NEPCO ETC

Page 4: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Classification of Instrument Transformers

-OIL IMMERSED

-CAST RESIN

-Epoxy

National Electrical Power Company

NEPCO ETC

Page 5: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

 Types Of Instrument Transformers   1-Current transformers

 2-Voltage transformers 

National Electrical Power Company

NEPCO ETC

Page 6: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CURRENT TRANSFORMER

National Electrical Power Company

NEPCO ETC

Page 7: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CURRENT TRANSFORMER

  

   A current transformer is used to transform a primary current quantity in terms of its magnitude and phase to a secondary value such that in normal conditions the secondary value is substantially proportional to the primary value.

IEC 60044

National Electrical Power Company

NEPCO ETC

Page 8: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Construction of Current Transformer 

  A current transformer is a transformer has its primaryprimary winding  is connected in series with the power circuit with thick windings and few turns , usually one turn. and the secondary with thin windings with many turns. Equation of current transformer:

 

Ip/Is = Ns/Np

National Electrical Power Company

NEPCO ETC

Page 9: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT Equivalent Circuit

National Electrical Power Company

NEPCO ETC

Referred to secondary

Page 10: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Wound primary type

Types Of Current Transformers

The wound type has a separate primary and secondary winding mounted on a laminated iron core. It is used for auxiliary current transformers and for many low or moderate ratio current transformers used in switchgear of up to 11kV Rating.

National Electrical Power Company

NEPCO ETC

Page 11: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The wound primary is used for the smaller currents, but it can only be applied on low fault level installations due to thermal limitations as well as structural requirements due to high magnetic forces.

This type of current transformer is designed so that the primary winding consists of one or more turns of heavy wire connected in series in the circuit The secondary winding consists of a larger number of turns of relatively smaller wires.And is connected to instruments or control devices

National Electrical Power Company

NEPCO ETC

Page 12: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Bushing type:

would be mounted in a transformer or circuit breakerFor currents greater than 100 A,

National Electrical Power Company

This consists of a cylindrical ring core built up of thin iron

laminations. Around the core is wound copper wire which forms

the secondary winding. The primary winding is formed by the

bushing conductor

NEPCO ETC

Page 13: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Window current transformer

If we enclose the current transformer in the bushing type In a molded case, we obtain another type of current transformer called the window type

Through the core and secondary winding, there is an insulated hole through which the user can place his own conductor.

National Electrical Power Company

NEPCO ETC

Page 14: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The rating of a CT has its own standards. the rating is 5 A , 2 A and 1 A

Current Transformer Rating

IEC 60044-1

National Electrical Power Company

NEPCO ETC

The current transformer is designed to give the secondary a current that is proportional to the primary current

Page 15: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Examples: CTR = 200/5 = 40CTR = 1200/5 = 240CTR = 400/1 = 400

National Electrical Power Company

NEPCO ETC

Page 16: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT errors results from the excitation current, so in order to check the ct function its essential to measure the excitation curve,

The magnetizing current of a CT depends on the cross section and the length of the magnetic circuit, the number of turns and the magnetic circuit material

This curve is the best method of determining a CT’s performance. It is a graph of the amount of magnetizing current required to generate an open-circuit voltage at the terminals of the unit.

CT Characteristics

National Electrical Power Company

NEPCO ETC

Page 17: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Current Transformer Knee-point

National Electrical Power Company

NEPCO ETC

Page 18: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

If the load and the magnitude of the primary current are large enough to saturate the CT, neither the flux nor the induced voltage are sinusoidal. The excitation current can take large magnitudes and the resulting error will be large.

The secondary current is no longer proportional to the primary current. The current error which corresponds to the magnetization current increases significantly

CT response in saturated state

National Electrical Power Company

NEPCO ETC

Page 19: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT Secondary Current transformers generally work at a low flux density. Core is then made of very good metal to give small magnetizing current the e.m.f, induced in the secondary winding isthat required to drive the secondary current through the total impedance of the secondary circuit,

And that the core flux inducing this e.m.f, on open-circuit, secondary impedance now becomes infinite and the core saturates. This induces a very high voltage in the primary up to approximately system volts and the corresponding volts in the secondary will depend on the number of turns, multiplying up by the ratio (i.e. volts/turn × no. of turns).

National Electrical Power Company

NEPCO ETC

Page 20: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Or we can say.With CT’s the increase of CT secondary burden will also increase the secondary voltage. This is maintain the correct magnitude of secondary current.

As the burden decreased will result in decreasing the secondary voltage as well.This voltage increase will increase the secondary burden, supposing that we have infinite secondary burden, theoretically the secondary voltage is infinite, but for practical reasons, the voltage will be very high. In terms of hundreds of kilovolts. This voltage will cause to break down the insulation between secondary and primary voltage, or between the secondary coils, so the secondary of CT should never be opened.

National Electrical Power Company

NEPCO ETC

Page 21: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Since CT normally has much more turns in secondary compared to the primary, the voltage generated on the open-circuited CT will be much more than the system volts, leading to flashovers.

this peak value may be as low as a few hundred volts in a small measuring c.t. with a 5A secondary winding, but it might reach many kilovolts in the case of, say a 2000/1A protective c.t. with a large core section.

 

open circuit voltage at CT is almost:V=(3.5*Zb*Ip/Ns)^.5

THEY CAN KILL YOU!

National Electrical Power Company

NEPCO ETC

Page 22: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

WYE CONNECTION:

Current Transformer Connection

National Electrical Power Company

NEPCO ETC

Page 23: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

DELTA CONNECTION:

National Electrical Power Company

NEPCO ETC

Page 24: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Current Transformer Grounding

 The grounding of CTs is important to both safety and the correct operation of protective relays.

To assure safe and reliable operation, the neutral of the CT secondary should have a single ground location for each circuit.

National Electrical Power Company

NEPCO ETC

Page 25: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The grounding of CTs is important to both safety and the correct operation of protective relays. To assure safe and reliable operation, the neutral of the CT secondary should have a single ground location for each circuit.

The recommended method of grounding is to install a single ground point at the first point of application (switchboard or relay panel) of the CT secondary circuit. The grounding is done only at one point. Multi point may introduce some problems…….?

National Electrical Power Company

NEPCO ETC

Page 26: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electrical Power Company

NEPCO ETC

Page 27: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

the grounding is done at the instrument transformer location at

the site or at the first panel application. Grounding the ct’s at the

site location may cause a problems:

Another grounding may be done at the panel without knowing that there

is a grounding at the location

The grounding is done mainly at the common point,

*NEPCO grounding standard :

The CTs are grounded at the place where the metering or relaying

*other standard. GE, ABB ….. ETC

National Electrical Power Company

NEPCO ETC

Page 28: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The unused CT secondaries:

The unused secondary of the current transformers as there may be multi secondaries , and no all the secondaries are used, these un used secondaries must be grounding. The grounding practice as we mentioned later at the instrument transformers location or at the first point of application.

Page 29: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

In case of multi ratio secondaries:One of these connection are applicable

Sometimes shorting terminals are available at the transformer secondaies.

Page 30: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT Standards

There are primarily two standards that are used to specify the performance of CTs for protection applications.

ANSI and the IEC

National Electrical Power Company

NEPCO ETC

Page 31: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

DIFFERENCES BETWEEN THE ANSI & THE IEC

National Electrical Power Company

NEPCO ETC

Page 32: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

A Ct can be separated into 2 distinct groups

1-Metering Type

2-Protection Type

National Electrical Power Company

NEPCO ETC

Page 33: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Current Transformers Specifications:

Rated primary currents:10 - 12.5 - 15 - 20 - 25 - 30 - 40 - 50 - 60 – 75 and their multiple factors

Accuracy power: this also called the “BURDEN” and it’s the maximum load can be connected to the CT secondary for the rated secondary current.Standard values: (1 - 2.5 - 5 - 10 - 15 -30) VA.

Accuracy class: this defines the guaranteed transformation ratio and phase displacement error limits under specific power and current conditions.

National Electric Power Company

NEPCO ETC

Page 34: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Metering current transformers according to the IEC -60044-1 the metering Ct must have the accuracy for the rated current.

The standardized IEC accuracy classes are: 0.1 - 0.2 - 0.5 - 1 - 3 - 5.Classes 0.5 and 1 are used in the majority of cases.Class 0.2 is only used for precision metering.Classes 0.1 - 3 - 5 are never used in medium voltage.

Metering symbols :B, Fs or sometimes there is no symbol

National Electric Power Company

NEPCO ETC

Page 35: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Metering CTs In general, the following appliesCLASS:

• 0.1 or 0.2 for precision measurements

• 0.5 for high grade kilowatt hour meters for commercial grade kilowatt hour meters

• 3 for general industrial measurements

• 3 or 5 for approximate measurements

National Electric Power Company

NEPCO ETC

Page 36: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Accuracy limit factor:ALF represents the value of the primary current at which the accuracy class still presents.

National Electric Power Company

NEPCO ETC

Page 37: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

EXAMPLE:500/1 A 15 VA cl 0.5

National Electric Power Company

NEPCO ETC

Page 38: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Burden

 Is the amount of the impedance connected to the ct secondary and rated in ohms or VA.  The burden can be expressed in two ways. The burden can be expressed as the total impedance in ohms of the circuit or the total volt-amperes and power factor at a specified value of current or voltage and frequency. Ex: the burden of a CT is 25 VA, with 5A secondary.So the burden in ohms :25= VI = I*R *I = I²R25=5*5*RR= burden in ohms = 1 Ohm

National Electric Power Company

NEPCO ETC

Page 39: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

BURDEN (depending on pilot lead length)

• Moving iron ammeter 1-2VA

• Moving coil rectifier ammeter 1-2.5VA

• Electrodynamics instrument 2.5-5VA

• Maximum demand ammeter 3-6VA

• Recording ammeter or transducer 1-2.5VA

National Electric Power Company

NEPCO ETC

Page 40: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT’s for Protection:

Protection symbols V,H,L T and P1.IEC 60044-1 Accuracy is defined by the accuracy class.The IEC accuracy classes are 5P and 10PThe IEC ALF values are: 5 - 10 - 15 - 20 - 30.

National Electric Power Company

NEPCO ETC

Page 41: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electrical Power Company

NEPCO ETC

Example:100/1 A 15 VA 5P10

Page 42: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Protection CT’s In general the following applies:

• Instantaneous over current relays & trip coils - 2.5VA Class 10P5• Thermal inverse time relays - 7.5VA Class 10P10• Low consumption Relay - 2.5VA Class 10P10• Inverse definite min. time relays (IDMT) over current - 15VA Class 10P10/15• IDMT Earth fault relays with approximate time grading - 15VA Class 10P10• IDMT Earth fault relays with phase fault stability or accurate time grading required - 15VA Class 5P10

National Electric Power Company

NEPCO ETC

Page 43: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

BS 3938 (class X)BS 3938 specifically defines current transformers designed for protection under the heading class X.

This defines the rated knee-point voltage VK . . This voltage, when applied to the terminals of the secondary increased by 10%, causes a maximum increase in magnetizing current of 50%.

National Electric Power Company

NEPCO ETC

Page 44: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electric Power Company

NEPCO ETC

Page 45: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Class PX: Class X CTs are special CTs used mainly in balanced protection systems (including restricted earth fault) where the system is sensitively dependenton CT accuracy. Further to the general CT specifications, the manufacturer needs to know:

• Vkp - Voltage knee point• Io - Maximum magnetizing current at Vkp• Rs - Maximum resistance of the secondary winding

National Electric Power Company

NEPCO ETC

Page 46: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The "X" indicates that they do not belong to any standardized class. They are customized transformers therefore it is necessary to specify the individual characteristics of the current transformers such as the turns ratio, rated primary and secondary current, Voltage knee point, the maximum magnetizing current at the knee point and the Maximum resistance of the secondary winding.

Class X CTs are generally used where high knee points are require to prevent operation at higher currents without saturation.

Class X CTs are further divided into Class A and Class B CTs.

Class A CTs are more expensive and are designed to operate even at maximum fault current without saturating. Class B CTs cost less and are used in high-impedance applications. They tend to saturate during transient conditions.

National Electric Power Company

NEPCO ETC

Page 47: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

       ERRORS IN CT 

 

1-Ratio errorrepresent the difference between the rated ratio and the measured ratio

%E=(actual turns ratio-rated turns ratio)/rated turns ratio *100%  

2-Phase error:represents the phase difference between the primary and the secondary

currents

(delta= θ (Ip)- θ (Is

National Electric Power Company

NEPCO ETC

Page 48: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

 Primary                                                 P1     P2       

                Secondary:

* single core secondary                       S1     S2                                    

* single core multi ratio secondary      S1-S2,S3 

* multi core secondary         1S1, 1S1-2S2,2S2 ......

CT Terminal Marking

National Electrical Power Company

NEPCO ETC

Page 49: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

According to IEC 60044-1National Electrical Power Company

NEPCO ETC

Page 50: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

  CT Symbols

National Electrical Power Company

NEPCO ETC

Page 51: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CT'S USED IN NEPCO

National Electrical Power Company

NEPCO ETC

Page 52: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

-800/400/1 A for distance protection and fault location equipments

-800/400/1 A for directional overcurrent, earth fault, sensitive earth fault protection and fault recorder

-800/400/1A for Busbar zone protection

For 132 KV Line Circuit

National Electrical Power Company

NEPCO ETC

Page 53: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

For 132 KV Transformer Circuit HV Side

-100/1A for restricted earth fault protection

-100/1A overcurrrent protection

-1200/600/1A for busbar zone protection

-100/1A transformer differential protection

National Electrical Power Company

NEPCO ETC

Page 54: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

 For 33KV Feeder Circuit

-400/200/1A for over current , earth fault and sensitive earth fault protection

-400/200/1 for metering

National Electrical Power Company

NEPCO ETC

Page 55: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

For 132KV Transformer Circuit MV Side

-800/400/1A for directional overcurrent and earth fault protection

-800/400/1A for transformer differential protection and restricted earth fault protection

-400/200/1A for metering

National Electrical Power Company

NEPCO ETC

Page 56: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electric Power Company

NEPCO ETC

CT’s Used In EDCO

Page 57: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Current Transformer Nameplate

National Electrical Power Company

NEPCO ETC

Page 58: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electrical Power Company

NEPCO ETC

Page 59: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

1-polarity test:

Each transformer should be tested in order to verify the polarity of the current transformer, we perform this test to check the polarity of a CT.

such that we connect a dc  battery to the primary "almost 12 Vdc". and we connect an ammeter to the secondary winding.

a low voltage battery is used to energize the primary winding, on closing the push button the dc ammeter should give a positive flick, and at open a negative flick,

.  

Current Transformer Tests

National Electrical Power Company

NEPCO ETC

Page 60: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

According to BS 3938 states that at the instant when current is flowing from P1 to P2 in primary, then current, in secondary must flow from S1 to S2 through the external circuit

Connect battery –ve terminal to the current transformer P2 primary terminal.

 This arrangement will cause current to flow from P1 to P2 when +ve terminal is connected to P1 until the primary is saturated. If the polarities are correct, a momentary current will flow from S1 to S2.

National Electrical Power Company

NEPCO ETC

Page 61: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Connection Diagram Of Polarity Test

National Electrical Power Company

NEPCO ETC

Page 62: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

2-magnetizing current curve.

Several points should be tested on each current transformer magnetization curve. this can be done energizing the secondary winding from local main supply through a variable autotransformer, while the primary circuit remains open.

The magnetizing current is measured on the ammeter, an the secondary voltage on the voltmeter. the applied voltage should be raised slowly till the magnetizing current is seen to rise very rapidly for a small increase of voltage. this indicates the approximate knee-point or saturation flux level of the current transformer.

National Electrical Power Company

NEPCO ETC

Page 63: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Connection Diagram Of Magnetizing Curve Test

National Electrical Power Company

NEPCO ETC

Page 64: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

3-Insulation TestIn this test we will measure the insulation resistance between the primary winding and ground And between secondary winding and ground Between secondary and primary

P1 with E P2 with E S1 and E S2 and EP1 and S1 P2 and S1 P2 and S1 P2 and S2

4-Secondary resistance test

5-continuity Test:Determine if there is no broken conductor within the transformer winding, we will use an ohm meter and connection cord, test resistance between primary windings terminals,test resistance between secondary winding terminals.

National Electrical Power Company

NEPCO ETC

Page 65: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

6-Ratio Test:

  Determine the transformation ratio, we will use a primary injection set, amps meters, connection cords.

we inject a current into the primary then we record the secondary and find the ratio.

National Electrical Power Company

NEPCO ETC

Page 66: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

7-dc Winding resistance Test:The CT resistance must be checked during the routine maintenance.A dc voltage is applied then a voltmeter measure the voltage , then the current is measured .

The resistance is then R= V/I

But this resistance must be compared with the manufacturer dataThe temperature conversion must be done to the 75 degrees….. ?

National Electric Power Company

NEPCO ETC

Page 67: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

The following factors affect CT prices:

1.Specifying a higher VA or CLASS than necessary usually results in a higher cost

2.The cost generally increases as the CT's internal diameter increases

13.A CT’s are usually more expensive than 5A

National Electrical Power Company

NEPCO ETC

Page 68: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

VOLTAGE TRANSFORMER

National Electrical Power Company

Page 69: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

NEPCO

National Electric Power Company

ETC

Page 70: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى
Page 71: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

VOLTAGE TRANSFORMER

  I s a device used to decrease the network voltage into values can be handled by other equipments.

Equation of VT:

  Vp/Vs=Np/Ns

National Electrical Power Company

NEPCO ETC

Page 72: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Secondary Of Voltage Transformer

IEC 60044-2

Rated secondary voltage 100, 100/sqrt3, 110110/sqrt3 volts depending on the type of connection

National Electrical Power Company

NEPCO ETC

Page 73: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage Transformer ErrorsPrimary source of errors is overloadingthe transformer.

Ratio error:  Represents the difference between the primary voltage multiplied by the transformation ratio and the secondary voltage.

E%=(actual ratio-rated ratio)/rated ratio *100%

Phase Error:  Represents the phase difference between the primary side and the secondary side.

Delta= θ(Vp)-θ(Vs)

National Electrical Power Company

NEPCO ETC

Page 74: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

VT ConnectionVoltage transformers are commonly used in three-phase groups,

generally in star–star configuration

WYE connection

National Electrical Power Company

NEPCO ETC

Page 75: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

OPEN DELTA Connection

It is common to detect earth faults in a three-phase system using the displacement that occurs in the neutral voltagewindings connected in a broken delta.

The residual voltage (neutral displacement voltage, polarizing voltage) for earth fault relays can be obtained from a three-phase set of VTs, which have their primary winding connectedphase to earth and one of the secondary

National Electrical Power Company

NEPCO ETC

Page 76: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

To prevent secondary circuits from reaching dangerous potential, the circuits should be earthed. Earthing should be made at only one point of a VT secondary circuit

Secondary earthing of voltage transformers

National Electrical Power Company

NEPCO ETC

Page 77: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage Transformer Accuracy:

Accuracy Grade : represents the ratio and phase error in the transformer.

Voltage Factor: represents the transformer withstand voltage for 30 sec or for some VT's continuous. maximum primary voltage can the VT withstand depends on earthling system and VT primary connection.

IEC specifies

the voltage factors:1.9 for systems not being solidly earthed.1.5 for solidly earthed systems.

  

VT Accuracy Class

National Electrical Power Company

NEPCO ETC

Page 78: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Accuracy power: or the burden is the rated load that the VT can supply at the rated voltage

The standardized values are:10 - 15 - 25 - 30 - 50 - 75 - 100 - 150 - 200 - 300 - 400 - 500 - VA.

NEPCO

National Electric Power Company

ETC

Page 79: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage transformers used for measuring

The standardized IEC accuracy classes are: 0.1 - 0.2 - 0.5 - 1 - 3.– Classes 0.1 and 0.2 are only used for laboratory devices.– Classes 0.5 and 1 are used in the majority of cases.– Class 3 is used very little.

NEPCO

National Electric Power Company

ETC

Page 80: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Example:

NEPCO

National Electric Power Company

ETC

Page 81: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage transformer for protection:

The IEC accuracy classes are 3P and 6P. In practice, only class 3P is used

NEPCO

National Electric Power Company

ETC

Page 82: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Types Of Voltage Transformers

shell type

dry type oil type

National Electrical Power Company

NEPCO ETC

Page 83: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Note:

VT must never be short-circuited on the secondary, because the power supplied increases and the transformercan be damaged by the resulting heat rise

National Electrical Power Company

NEPCO ETC

Page 84: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage drop in voltage transformers

The voltage drop in the secondary circuit is of importance. The voltage drop in thesecondary fuses and long connection wires can change the accuracy of the measurement.

The voltage drop in the leads from the VT to the associated equipment must be considered as this, in practice, can be alarming mainly in case of measuring circuits. This is the one that separates the metering circuits (with low burden) from protective circuits (with higher burdens)

National Electrical Power Company

NEPCO ETC

Page 85: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage Transformer Nameplate

National Electrical Power Company

NEPCO ETC

Page 86: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

NEPCO

National Electric Power Company

ETC

Page 87: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

Voltage Transformer Testing

Polarity Test

Insulation Resistance Test

Ratio Test

continuity Test

High voltage test

National Electrical Power Company

NEPCO ETC

Page 88: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

In general, the size of an inductive VT is   proportional to its nominal voltage and, for this reason, the cost increases in a similar manner to that of a high voltage transformer. One alternative, and a more economic solution, is to use a capacitor voltage transformer . A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra- high voltage signals and provide low voltage signals either for measurement or to operate a protective relay. In its most basic form the device consists of three parts: two capacitors across which the voltage signal is split, an inductive element used to tune the device to the supply frequency and a transformer used to isolate and further step-down the voltage for the instrumentation or protective relay.

 Capacitor Voltage Transformer

National Electrical Power Company

NEPCO ETC

Page 89: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CVT Equivalent Circuit

National Electrical Power Company

NEPCO ETC

Page 90: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

This device is effectively a capacitance voltage divider, and is similar to a resistive divider in that the output voltage at the point of connection is affected by the load

in fact the two parts of the divider taken together can be considered as the source impedance which produces a drop in voltage when the load is connected

National Electrical Power Company

NEPCO ETC

Page 91: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

CVT Nameplate

National Electrical Power Company

NEPCO ETC

Page 92: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

VT’S Used In NEPCO

VT’S Used In EDCO

National Electrical Power Company

NEPCO ETC

Page 93: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

THE END

National Electrical Power Company

NEPCO ETC

Page 94: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

National Electrical Power Company

NEPCO ETC

Appendix

Page 95: NEPCO National Electrical Power Company ETC تم رفعه بواسطة صفحة : الهندسه الكهربيه ”علم وفن“ أدمن : م/علاء محمد حمادى

References supporting these papers:1.SEL protection Instrument Transformers part 7

2.ETC Instrument transformers3.IEC 60044-1, 60044-2

4 .Current Transformer Grounding, netaworld.org by Jim wenPowell Electrical ,Manufacturing Co

5 .C&C Ltd Catalogue & Price List May 2006NOTES ON CURRENT TRANSFORMERS6. Current transformers for HV protection by Michel Orlhac7.Shnider protection guide

8 .Current transformer the basics, NK Technologies 9. Protection of Electrical Networks, Christophe Prévé

National Electrical Power Company

NEPCO ETC