mid-rise shear walls & diaphragms - woodworks topics • shear wall types • shear wall...
TRANSCRIPT
By: R. Terry Malone, PE, SE
Senior Technical Director
Architectural & Engineering Solutions
928-775-9119
Mid-rise Shear Walls
& Diaphragms
Avalon Bay Communities
Photo credit: Arden Photography
120 Union, San Diego, CATogawa Smith Martin
Presentation updated to 2015 IBC, ASCE 7-10, 2015 SDPWS
Copyright McGraw-Hill, ICC
Portions Based On:
Presentation Topics
• Shear Wall Types
• Shear wall Anchorage
• SDPWS Code Requirements
• Complete Load Paths
• Offset Shear Walls and Relevant Code
Requirements
• Mid-rise Diaphragms and Tall Shear Walls
Wall
DL
V
v(plf)
Sh
ear
wall c
ho
rd
Sh
ear
wall c
ho
rd
h
Resist. mom. Arm 1C.L.
bearingC
C.L.
A.B.
T
b
Sheathing
joint as
occurs
2x blocking
as required
at joints.
DLhdr2DLhdr1
Anchor bolts
or nailing Hold down
anchor
V
v(plf)
WDL plf
tstuds
Sh
ear
wall c
ho
rd
Sh
ear
wall c
ho
rd
h1
Resist. mom. Arm 1
C
C.L.
A.B.
T b
Tstud + CLC.L.
bearing
Chord or
Strut
Chord
or Strut h2Wall
DL
DL hdr. DL hdr.
412
C.L.
SW
v
diaphragm shear
0M
Fv
Fchord/strut
Fchord/strut
Fv
Vvert
Vhoriz
Segmented Shear Walls
Segmented Wall Types- Standard & Sloped
L bearing
Hdr / strut Hdr / strut
Resist. mom. Arm 2
Resist. mom. Arm 2
v(plf)
0M
Wall
DL
V or F
Sh
ear
wall c
ho
rd
Sh
ear
wall c
ho
rd
h
C
T b
WDL plf
Segmented Shear Wall Deflection and Stiffness
∆𝑺𝑾=𝟖𝒗𝒉𝟑
𝑬𝑨𝒃+
𝒗𝒉
𝟏𝟎𝟎𝟎𝑮𝒂+ 𝒉∆𝒂
𝒃
∆𝑺𝑾
Vertical elongation
• Device elongation
• Rod elongation
Bending
Apparent shear stiffness
• Nail slip
• Panel shear deformation
Deflection of standard segmented shear wall
Tests were based on Aspect Ratio (A/R) = 2:1
Deflection permitted to be calculated based
on rational analysis where apparent shear
stiffness accounts for:
• Panel shear deformation
• Non-linear nail slip
4.3-1
Deflection of unblocked segmented shear wall
• Use Eq.4.3-1 with v/Cub per 4.3.2.2
v v v
∆𝒔𝒘 =𝟖𝒗
𝑪𝒖𝒃𝒉𝟑
𝑬𝑨𝑩+
𝒗
𝑪𝒖𝒃𝒉
𝟏𝟎𝟎𝟎𝑮𝒂+𝒉
𝒃∆𝒂
ATS
Wall stiffness k = 𝑭
∆
Perforated Shear Walls- Empirical Design
Hdr
Hold downs at
Ends per section
4.3.6.4.2
Intermediate uplift anchorage is
required at each full height panel
locations… ”in addition to…” per
section 4.3.6.4.2.1.
Collector per SDPWS section 4.3.5.3
(Full length of wall)
Top and bottom
of wall cannot be
stepped
Opening
Hdr
Opening
Use other
methods
Typical
boundary
member
All full hgt. sections
must meet the aspect
ratio requirements of
section 4.3.4.1.
Common sheathing
joint locations
vmax
Tint
Li (typ)
V
Wall
segment
Wall
segment
Wall
segment
Header sections
do not have to
comply with
aspect ratios.
Openings are
allowed at end
of wall but
cannot be part
of wall
Inter. uplift
anchorage
Inter. uplift
anchorage
Inter. uplift anchorage
• APA Diaph-and-SW Construction Guide
• AWC-Perforated Shear Wall Design
Reference examples
F
(a) Perforated Shear Wall
AWC SDPWS Figure 4C
Bottom
of roof
diaph.
framing
Floor
diaph.
Floor
diaph.
Bottom
of diaph.
framing
Bottom
of diaph.
framing
Segment
Width, b
Sto
ry a
nd
wall
seg
men
t h
eig
ht,
h
Wd.
Wd.
Dr.
Wall
segment
Segment
Width, b
Wall
segment
Segment
Width, b
Wall
segment
Segment
Width, b
Wall
segment
Sto
ry a
nd
wall
seg
men
t h
eig
ht,
h
Sheathing is
provided above
and below all
openings
Figure 4D for
segmented walls
is the same as this
figure, except this
section is added.
Foundation wall
Allowable Perforated Shear Wall Aspect Ratios
• Sections exceeding 3.5:1 aspect
ratio shall not be considered a
part of the wall.
• The aspect ratio limitations of
Table 4.3.4 shall apply.
• Vn ≤ 1740 seismic-WSP 1 side
• Vn ≤ 2435 plf wind-WSP 1 side
• Vn ≤ 2435 plf wind-WSP 2 sides
• A full height pier section shall be
located at each end of the wall.
• Where a horizontal offset occurs,
portions on each side of the
offset shall be considered as
separate perforated walls.
• Collectors for shear transfer shall
be provided through the full
length of the wall.
• Uniform top-of-wall and bottom-of
wall plate lines. Other conditions
require other methods.
• Maximum wall height ≤ 20’.
Limitations:
Maximum Shear @ full hgt. sect.
Sheathing
area ratio
Empirically determined shear resistance reduction factors, C0 – based on maximum
opening height and percentage of full height wall segments.
Sugiyama Method-Reduced shear capacity is multiplied by the full length of the wall.
IBC/SDPWS Method- Reduced shear capacity is multiplied by the sum of the lengths
of the full height sections (slightly more conservative).
Hdr
Opening
Hdr M
ax. o
pen
ing
heig
ht
vmax
Tint
V
Wall
segment
Wall
segment
Wall
segment
h m
ax
=20 f
t
Li (typ) Li (typ)Li (typ)
Vallow = (v Tabular ) x (CO) x ∑Li
Where:
Per SDPWS
Table 4.3.3.5𝑪𝟎 =
𝒓
𝟑 − 𝟐𝒓
𝑳𝒕𝒐𝒕𝚺𝑳𝒊
𝒓 =𝟏
𝟏 +𝑨𝟎𝒉𝚺𝑳𝒊
Ao = total area of openings
Hold down at ends
𝒗𝒎𝒂𝒙 = 𝑽
𝑪𝒐 ∑𝑳𝒊
𝒗𝒎𝒂𝒙 = 𝑻𝒊𝒏𝒕 =𝑽
𝑪𝟎𝚺𝑳𝒊
𝑻 = 𝑪 =𝑽𝒉
𝑪𝟎𝚺𝑳𝑰
At full-hgt. segments
Perforated Shear Wall Deflection
Vertical elongation
• Nail slip
• Device elongation
• Rod elongation
Bending
Apparent shear stiffness
• Nail slip
• Panel shear deformation
Deflection of perforated shear wall
4.3-1
4.3.2.1 Deflection of Perforated Shear Walls: The deflection
of a perforated shear wall shall be calculated in
accordance with 4.3.2, where v in equation 4.3-1 is
equal to vmax obtained in equation 4.3-9 and b is
taken as ∑Li.
∆𝑺𝑾=𝟖𝒗𝒉𝟑
𝑬𝑨𝒃+
𝒗𝒉
𝟏𝟎𝟎𝟎𝑮𝒂+ 𝒉∆𝒂
𝒃
vmax ∑Li
Open’g
Hdr
Max. o
pen
ing
heig
ht
vmax
V
Wall
segment
Wall
segment
h m
ax
=20 f
t
Li (typ)Li (typ)
∆𝑺𝑾
3’ 6’ 5.5’
14.5’
4’
3’
2’
1 2
A
B
3
C
D
4
9’
4500 lb
w=200 plf
(See recent Testing-APA Form M410 and SR-105)
Tie straps full
length of wall
per SDPWS
section 4.3.5.2
Anchor bolts
or nails
(Typical boundary
Member)
Typical boundary
member
2’ min. per SDPWS
Section 4.3.5.2
(2008 requirement)
Many examples
ignore gravity loads
FTAO Shear Walls
Cont. Rim joist
Strut/collector
Shear panels
or blocking
(b) Force Transfer Around Opening
Wall
pier
Wall
pier
Wall
pier
Wall
pier Wall
pier
Wall P
ier
heig
ht
Wall p
ier
heig
ht
Wall
pier
width
Cle
ar
heig
ht
Wall p
ier
heig
ht
Overall width
AWC SDPWS Figure 4E
Dr.
Wall
pier
width
Boundary
members
Collector (typ.)
Foundation wall
Allowable Shear Wall Aspect Ratios For FTAO Shear Walls
Note: Not
shown as
having to
comply w/
A/R
Wd.
Wd.
• Sections exceeding 3.5:1 aspect
ratio shall not be considered a
part of the wall.
• The aspect ratio limitations of
Table 4.3.4 shall apply to the
overall wall and the pier sections
on each side of the openings
• Minimum pier width=2’-0”.
• A full height pier section shall be
located at each end of the wall.
• Where a horizontal offset occurs,
portions on each side of the
offset shall be considered as
separate FTAO walls.
• Collectors for shear transfer shall
be provided through the full
length of the wall.
Limitations:
4500
C
Tie strap/blocking
full width
Blocking
Point of inflection is assumed
to occur at mid-length (Typ.)
MM
V
V
V
V
M
M
1 2
A
B
3
C
D
4
C
A B
D
F
E
HG
I
L
J
K
T
V
V
M
M
MM
V
V
F=0 lb
F=0 lbF=0 lb
M
F=0
MF=0
Force Transfer Methodology (Diekmann)-Vierendeel Truss/Frame
F=0 lb
F
F
Gravity loads
to wall
1343.1 4243.1
w=200 plf
N.A.
4500 lb
4’
14.5’
208.62 lb
208.62 lb
991.38 lb
587.08 lb
F1B.5
VB.5
1 2
A
B
3
A
B
4
2’
2’
4500 lb
200 plf
200 plf
0M
0M
B.5
B.5
2691.38 lb
F4B.5
3912.92 lb
VB.5
BA
C
A
I
G
B
H
C
V2.53’
3’
Free-body of Upper Half and Upper Left Section
Point of
inflection
I
H
A
C
D
B
F
587.08
VB=587.08
VB.5=587.08
(587.08)
Vc=587.08
587.08
V2
.5
15
51
.7
V2
(1343.1)
3’
3’
F2b(V)
391.39
F2C(v)
391.399
91
.38
V2
39
1.3
9
(208.62)
F2A
F2B(H)
1381
1037.1
1160.3
F2C(H)
F1B
600
F1C
182.77
E
(0)
(0)
573.23
2’
2’
2’
1 2
0M
0M0M
0M
0M
0M
Units are in lb
Corner tie
strap force
Corner tie
strap force
HG
J
I
KL
15
91
.38
(99
1.3
8)
V3
268.8
1937.1
15
51
.7
15
51
.7
236.17
3676.6
V3
(4243.1)
(2691.38)VB.5=3912.92
VB=3912.92
3912.92
(3912.92)
VC=3912.92
3912.92
(0)
5.5’
3’
2’
2’
2’
F3(V)
1422.88
F3B(V)
1422.9
F4B
1268.5
F4C
4114.3F3C(H)
F3B(H)
F3A A
B
3
C
D
4
0M
0M
0M
3’ 3’
3’ 3’
2.5
B.5B.5
2124.9
1551.7
(4500)
(4500)
F2.5A
1274.9
(xxx) Shears and forces determined
in previous step.
0M
0M 0M
200 plf 200 plf 200 plf 200 plf
F2.5C
Resultant Forces on Wall Segments
0V
0H
0V
0V
0V0V
0H
0V
0H
1551.7
1706.9931931931
(0)
(See recent Testing-APA Form M410)
Advancements in FTAO Shear Wall Analysis
Basis of APA System Report
SR-105 (in development)
SEAOC Convention 2015
Proceedings
Advancements in Force Transfer Around
Openings for Wood Framed Shear Walls
APA System Report SR-105
(Report pending)
Refine rational design methodologies
to match test results
Used test results from full-scale
wall configurations
Analytical results from a computer
model
Allows asymmetric piers and
multiple openings.
20’-0”
L
5’-0”
L1
4’-0”
L22’-6”
L3
6’-0”
LO1
2’-6”
LO2
2’-
8”
ho
8’-
0”
H
V=4000 lbs.
1’-
4”
ha
4’-
0”
hb
1600
1600
Calculate O/T forces:
𝑭𝑶/𝑻=𝟒𝟎𝟎𝟎(𝟖)
𝟐𝟎= 1600 lbs.
Pier 1 Pier 2 Pier 3
Example Problem
(Note: No dead loads)
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6”
2’-
8”
1600
1600
1’-
4”
4’-
0”
Calculate:
• Aspect ratios of pier sections
𝑷𝒊𝒆𝒓 𝟏 =𝒉
𝒅=𝟐.𝟔𝟕
𝟓= 0.534 < 2:1
𝑷𝒊𝒆𝒓 𝟐 =𝟐.𝟔𝟕
𝟒= 0.668 < 2:1
𝑷𝒊𝒆𝒓 𝟑 =𝟐.𝟔𝟕
𝟐.𝟓= 1.07 < 2:1
𝑯𝒆𝒂𝒅𝒆𝒓 𝟏 =𝟔
𝟏.𝟑𝟑= 4.51 > 3.5:1
𝑯𝒆𝒂𝒅𝒆𝒓 𝟐 =𝟐.𝟓
𝟏.𝟑𝟑= 1.88 < 2:1
𝑺𝒊𝒍𝒍 𝟏 =𝟔
𝟒= 1.5 < 2:1
𝑺𝒊𝒍𝒍 𝟐 =𝟐.𝟓
𝟒= 0.625 < 2:1
.534:1 .668:1 1.07:1
4.51:1 1.88:1
.625:11.5:1
Pier 1 Pier 2 Pier 3
V=4000
20’-0”
5’-0” 4’-0” 2’-6”6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
300 p
lf
400
300 p
lf
1200
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
𝑽𝒉𝒅𝒓𝟏 =𝑭𝒐/𝒕(𝒉𝒂)
(𝒉𝒂+𝒉𝒃)=𝟏𝟔𝟎𝟎(𝟏.𝟑𝟑𝟑)
𝟓.𝟑𝟑
= 400 lbs.
vhdr2 = 𝟒𝟎𝟎
𝟏.𝟑𝟑= 300 plf
𝑽𝒔𝒊𝒍𝒍𝟏 =𝟏𝟔𝟎𝟎(𝟒)
𝟓.𝟑𝟑= 1200 lbs.
vsill2 = 𝟏𝟐𝟎𝟎
𝟒= 300 plf
Method assumes the unit shear above
and below opening are equivalent
V=4000
FLo1=1800
5’-0” 4’-0” 2’-6”6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
Vhdr = 300 plf
FLo2=750
Vhdr=300
20’-0”
The total boundary force above and below the
opening = the unit shear above and below the
opening multiplied by the opening length
Bottom force
same
FLo1 = 300(6) = 1800 lbs.
FLo2 = 300(2.5) = 750 lbs.
1800 750
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
𝑭𝟏 =𝑭𝑳𝒐𝟏(𝑳𝟏)
(𝑳𝟏+𝑳𝟐)=𝟏𝟖𝟎𝟎(𝟓)
(𝟓+𝟒)= 1000 lbs.
𝑭𝟐 =𝟏𝟖𝟎𝟎(𝟒)
(𝟓+𝟒)= 800 lbs.
𝑭𝟑 =𝟕𝟓𝟎(𝟒)
(𝟒+𝟐.𝟓)= 461.50 lbs.
𝑭𝟒 =𝟕𝟓𝟎(𝟐.𝟓)
(𝟒+𝟐.𝟓)= 288.5 lbs.
F4=288.5F1=1000 F3=461.5F2=800
Corner forces are based on the boundary forces
above and below the opening and only the pier
sections adjacent to that opening
Bottom force
same
FLo1=1800 FLo2=750
F4=288.5F1=1000 F3=461.5F2=800
V=4000
20’-0”
L1=5’-0” L2=4’-0” L3=2’-6”
Lo1=6’-0” Lo2=2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
𝑻𝟏 =𝑳𝟏(𝑳𝒐𝟏)
(𝑳𝟏+𝑳𝟐)=𝟓(𝟔)
(𝟓+𝟒)= 3.33’
𝑻𝟐 =𝟒(𝟔)
(𝟓+𝟒)= 2.67’
𝑻𝟑 =𝟒(𝟐.𝟓)
(𝟒+𝟐.𝟓)= 1.54’
𝑻𝟒 =𝟐.𝟓(𝟐.𝟓)
(𝟒+𝟐.𝟓)= 0.96’
0.96’1.54’2.67’3.33’
The tributary length of the opening is the ratio
of the pier length multiplied by the opening
length divided by the sum of the lengths of the
piers on each side of the opening
T4T3T2T1
0.96’1.54’2.67’3.33’
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
Vtop=200 plf
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
• Unit shear in piers
𝑽𝟏 =𝒗𝒕𝒐𝒑(𝑳𝟏+𝑻𝟏)
𝑳𝟏=𝟐𝟎𝟎(𝟓+𝟑.𝟑𝟑)
(𝟓)
= 333.2 plf
𝑽𝟐 =𝟐𝟎𝟎(𝟐.𝟔𝟕+𝟒+𝟏.𝟓𝟒)
(𝟒)= 410.5 plf
𝑽𝟑 =𝟐𝟎𝟎(𝟎.𝟗𝟔+𝟐.𝟓)
(𝟐.𝟓)= 276.8 plf
V3=276.8 plfV2=410.5 plfV1=333.2 plf
The pier shear is equal to the unit shear at the
top of the wall multiplied by the pier length +
the tributary length adjacent to the pier divided
by the length of the pier
0.96’1.54’2.67’3.33’
T4T3T2T1
276.8410.5333.2
𝑽𝒕𝒐𝒑 =𝑽
𝑳=𝟒𝟎𝟎𝟎
𝟐𝟎= 200 plf
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6” 8’-
0”
1600
1600
200 plf
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
• Unit shear in piers
• Resisting forces
R1=v1L1=333.2(5)=1666 lbs.
4000 lbs.
R3=692R2=1642R1=1666
The resisting forces of the piers equal to the
pier unit shear multiplied by the pier length
69216421666
R2=v2L2=410.5(4)=1642 lbs.
R3=v3L3=276.8(2.5)=692 lbs.
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6” 8’-
0”
1600
1600
200 plf
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
• Unit shear in piers
• Resistance forces
• Pier collector forces
F4=288.5F1=1000 F2+F3=800+461.5
R3=692
(403.5)
R2=1642
(380.5)
R1=1666
(Net=666)
R1-F1=1666-1000=666 lbs.
The net collector force at the corners of the
Opening is equal to the pier resisting force
minus the opening corner force
288.51000 1261.5(403.5)(380.5)(Net=666)
69216421666
R2-F2=1642-(800+461.5)
=380.5 lbs.
R3-F4=692-288.5=403.5 lbs.
V=4000
20’-0”
5’-0” 4’-0” 2’-6”
6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
200 plf
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
• Unit shear in piers
• Resistance forces
• Pier collector forces
• Unit shears at corner zones
Va2=(R2-F2-F3)/L2=380.5/4 = 95.1 plf
161.4 plf95.1 plf133.2 plf
The corner zone unit shear is equal to the net
collector force divided by the pier length
161.495.1133.2
Va3=(R3-F4)/L3=403.5/2.5 =161.4 plf
Va1=(R1-F1)/L1=666/5 = 133.2 plf
V=403.5 lbs.
netV=380.5 lbs.
net
V=666 lbs.
net
V=4000
20’-0”
5’-0” 4’-0” 2’-6”6’-0” 2’-6”
2’-
8”
8’-
0”
1600
1600
1’-
4”
4’-
0”
300
300
200 plf
Calculate:
• Aspect ratios of pier sections
• Unit shear above and below
opening
• Total boundary force above
and below opening
• Corner forces
• Tributary length of openings
• Unit shear in piers
• Resistance forces
• Pier collector forces
• Unit shears at corner zones
• Verify design
∑H=V, 333.2(5)+410.5(4)+276.8(2.5) =4000 lbs. o.k.
133.2
333.2
Grid 1=va1(ha+hb)+v1(ho)=Fo/t, 133.2(4+1.33)+333.2(2.67)=1600 o.k.
Grid 2=va(ha+hb)-va1(ha+hb)-v1(ho)=0, 300(4+1.33)-133.2(4+1.33)-333.2(2.67)=0 o.k.
Grid 3=va2(ha+hb)+v2(ho)-va(ha+hb)=0, 95.1(5.33)+410.5(2.67)-300(5.33)=0 o.k.
Grid 4=va2(ha+hb)+v2(ho)-va(ha+hb)=0, -95.1(5.33)-410.5(2.67)+300(5.33)=0 o.k.
Grid 5=va(ha+hb)-va3(ha+hb)-v3(ho)=0, -300(5.33)+161.4(5.33)+276.8(2.67)=0 o.k.
Grid 6=va3(ha+hb)+v3(ho)=Fo/t, 161.4(5.33)+276.8(2.67)=1600 o.k.
654321
133.2
133.2
333.2
133.2
300
300
161.495.1
276.8
95.1 161.4
410.5410.5
300
300
300
300
95.1
95.1
𝜮𝑽 = 𝟎 𝒂𝒕 𝒂𝒍𝒍 𝒈𝒓𝒊𝒅 𝒍𝒊𝒏𝒆𝒔
20’-0”
L
5’-0”
L1
4’-0”
L22’-6”
L3
6’-0”
LO1
2’-6”
LO2
4’-
8”
ho
2
8’-
0”
H
4000 lbs.
V
1’-
4”
ha
2’-
0”
hb
2
1600
1600
2’-
8”
ho
14’-
0”
hb
1
TD
Multi-story walls?
Tall shear walls?
• The deflection of the wall is the average of
the deflection of the piers as shown (acting
both ways combined) using the 4 term eq.
Single opening
∆𝑨𝒗𝒆𝒓.= (∆𝒑𝒊𝒆𝒓 𝟏+∆𝒑𝒊𝒆𝒓 𝟐)+(∆𝒑𝒊𝒆𝒓 𝟏+∆𝒑𝒊𝒆𝒓 𝟐)
𝟒
• The remainder of the terms are identical to
the traditional equation.
• Deflections for a wall with multiple
openings is similar.
∆𝑨𝒗𝒆𝒓.=(∆𝒑𝒊𝒆𝒓 𝟏+∆𝒑𝒊𝒆𝒓 𝟐+∆𝒑𝒊𝒆𝒓 𝟑)+(∆𝒑𝒊𝒆𝒓 𝟏+∆𝒑𝒊𝒆𝒓 𝟐+∆𝒑𝒊𝒆𝒓 𝟑)
𝟔...
Hdr
Opening
Wall
Pier 2
Wall
Pier 1
Sill
∆𝑺𝑾=𝟖𝒗𝒉𝟑
𝑬𝑨𝒃+𝒗𝒉
𝑮𝒗𝒕𝒗+𝟎. 𝟕𝟓𝒉𝒆𝒏+
𝒉∆𝒂
𝒃
Traditional 4 term deflection equation
∆𝑷𝒊𝒆𝒓 𝟏 ∆𝑷𝒊𝒆𝒓 𝟐
Reference APA SR-105
Loads Loads
∆𝑷𝒊𝒆𝒓 𝟏 ∆𝑷𝒊𝒆𝒓 𝟐
2015 SDPWS
Shear Wall Capacity and Load Distribution
Allowable values shown in tables
are nominal shear values
Design values:
LRFD (Strength) = 0.8 x Vn
ASD = Vn/2
SheathingMaterial
MinimumNominal
PanelThickness
(in.)
MinimumFastener
PenetrationIn Framing
Member or Blocking
(in.)
FastenerType & Size
ASeismic
Panel Edge Fastener Spacing (in.)
Table 4.3A Nominal Unit Shear Capacities for Wood-Framed Shear Walls
6 4 3 2 6 4 3 2
Vs Ga Vs Ga Vs Ga Vs Ga Vw Vw Vw Vw
1,3,6,7
5/16 1-1/4 6d 400 13 10 600 18 13 780 23 16 1020 35 22 560 840 1090 1430
BWind
Panel Edge Fastener Spacing (in.)
Wood Based Panels4
(plf) (kips/in.) (plf) (kips/in.)(plf) (kips/in.)(plf) (kips/in.) (plf) (plf) (plf) (plf)
Nail (common orGalvanized box)
Wood Structural Panels-Structural 1
Use Table 4.3B for WSP over ½” or 5/8” GWB or Gyp-sheathing Board
Use Table 4.3C for Gypsum and Portland Cement Plaster
Use Table 4.3D for Lumber Shear Walls
OSB PLY OSB PLY OSB PLY OSB PLY4,5
3/8 460 19 14 720 24 17 920 30 20 1220 43 24 645 1010 1290 17107/16 1-3/8 8d 510 16 13 790 21 16 1010 27 19 1340 40 24 715 1105 1415 1875 15/32 560 14 11 860 18 14 1100 24 17 1460 37 23 785 1205 1540 2045
15/32 1-1/2 10d 680 22 16 1020 29 20 1330 36 22 1740 51 28 950 1430 1860 2435
Increased 40%*
Blocked
Shear Wall Capacity-Wood Based Panels
*40% Increase based on reducing the load factor from 2.8, which was originally used to develop shear
capacities down to 2.0 for wind resistance. (2006 IBC commentary)
Supported Edges
Unblocked
Table 4.3.3.3.2 Unblocked Shear Wall Adjustment Factor, Cub
Intermediate Framing
Stud Spacing (in.)
12 16 20 24
6 12 0.8 0.6 0.5 0.4
6 6 1.0 0.8 0.6 0.5
vub= vb Cub Eq. 4.3-2
vub = Nominal unit shear value for unblocked shear wall
vb = Use nominal shear values from Table 4.3A for blocked WSP shear walls with stud spacing at 24” o.c. and 6” o.c nailing
Shear Wall Capacity-Wood Based Panels
Summing Shear Capacities-4.3.3.3
Same material, construction
and same capacities
Dissimilar materials
(Not cumulative)
Dissimilar materials
Vallow = largest
Vallow=2x
Vallow =2x smaller or
largest, greater of.
VS1
VS2Same material, construction
on both sides, different capacities
Side 1
Vsc
Side 2
𝐆𝐚𝐜 = 𝐆𝐚𝟏 + 𝐆𝐚𝟐
𝐯𝐒𝐂 = 𝐊𝐦𝐢𝐧𝐆𝐚𝐜 Combined apparent shear wall shear
capacity (seismic)
𝐊𝐦𝐢𝐧 =𝐯𝐒𝟏
𝐆𝐚𝟏𝐨𝐫𝐯𝐒𝟐
𝐆𝐚𝟐Minimum of
Where:
(Exception-for wind,
add capacities)
Gac= Combined apparent shear wall shear
stiffness
Ga1= Apparent shear wall shear stiffness side 1
(Ga2 side 2)-from SDPW table
vS1=Nominal unit shear capacity of side 1
(vS2 side 2)
VS1
VS2
VS1
Vsc or Vwc
Vsc or Vwc
Vsc or Vwc
Vsc = combined nominal unit shear capacity seismic
Vwc = combined nominal unit shear capacity wind
The shear wall deflection shall be calculated using the
combined apparent shear wall shear stiffness, Gac and
the combined nominal unit shear capacity, vsc, using the
following equations:
2 layers WSP 1 side of wall
When two layers of WSP sheathing are applied to
the same side of a conventional wood-frame wall,
the shear capacity for a single-sided shear wall of
the same sheathing-type, thickness, and attachment
may be doubled provided that the wall assembly
meets all of the following requirements:
• Panel joints between layers shall be staggered
• Framing members located where two panels
abut shall be a minimum of 3 x framing.
• Special sheathing attachment requirements
• Special retrofit construction requirements
• Double 2x end studs, if used, shall be stitch-
nailed together based on the uplift capacity of
the double-sheathed shear wall.
Distribution of lateral forces to In-line Shear Walls
• All walls are of same materials and
construction
1. Where Vn of all WSP shear walls having
A/R>2:1 are multiplied by 2b/h, shear
distribution to individual full-height wall
segments is permitted to be taken as
proportional to design shear capacities of
individual full height wall segments.
(traditional method)
Where multiplied by 2b/h the Vn need not be
reduced by Aspect Ratio Factor (WSP)=
1.25-0.125h/b per Section 4.3.4.2.
Exception:
Section 4.3.4.2-Limitation of section
Same materials in same wall line
Summing
is allowed
Dissimilar materials in same wall line
Section 4.3.4.2
does not apply
Equal wall deflection∆𝒘𝒂𝒍𝒍
2. Where Vn x 0.1+0.9b/h of all structural
fiberboard shear walls with A/R>1:1, shear
distribution to individual full-height wall
segments shall be permitted to be taken as
proportional to design shear capacities.
Where Vn x 0.1+0.9b/h, the nominal shear
capacities need not be reduced by 1.09-0.09h/b
• Shear distribution to individual SW’s
shall provide same calculated deflection
in each shear wall (Default Method)
per 2015 SDPWS)
Distribution of lateral forces to In-line Shear Walls
• All walls are of same materials and
construction
Section 4.3.3.4-Limitation of section
Method 1-Simplified Approach
Traditional Method
b1 b2
SW1 SW2h
Example Calculation per Commentary
(assumes same unit shear capacity)
SW1 and SW2
• Determine ASD unit shear capacity
• Check aspect ratio-adjust per SDPWS 4.3.4.1 (and/or exception), Aspect ratios
> 2:1 use reduction factor 𝟐𝒃𝒔
𝒉(further reductions in 4.3.4.2 are not required)
• Sum design strengths = vsw1 x b1 + vsw2 x b2
for line strength
• Will produce similar results to equal deflection method
Distribution of lateral forces to In-line Shear Walls
Method 2-Equal Deflection
∆𝑺𝑾𝟏 ∆𝑺𝑾𝟐
b1 b2
SW1 SW2h
Method of Analysis
SW1 and SW2
• Determine ASD unit shear capacity
• Check aspect ratio-adjust per SDPWS
4.3.4.2
• Determine Ga and EA values
• Calculate deflection of larger SW (SW2)
𝒗𝒔𝒘𝟏 =∆𝒔𝒘𝟐−
𝒉∆𝒂𝒃
𝟖𝒉𝟑
𝑬𝑨𝒃+𝒉
𝟏𝟎𝟎𝟎𝑮𝒂
• Sum design strengths
= vsw1 x b1 + vsw2 x b2 for line strength
Example Calculation per Commentary
(assumes same unit shear capacity)
• Determine unit shear in smaller SW (SW1)
that will produce same deflection
3000
2500
2000
1500
1000
Lo
ad
lb
s.
500
Deflection, in.
0.3
5
0.3
0.2
5
0.2
0.1
5
0.1
0.0
5
ASD strength and
deflection of shear
wall line
ASD strength and
deflection of SW2
ASD strength and
deflection of SW1
at SW2 defl. limit
ASD strength
of SW1 Per
SDPWS 4.3.4.2
Presentation Topics
• Shear Wall Types
• Shear wall Anchorage
• SDPWS Code Requirements
• Complete Load Paths
• Offset Shear Walls and Relevant Code
Requirements
• Mid-rise Diaphragms and Tall Shear Walls
Typical Floor Plan
Typical
Unit
Transverse walls
typical
Longitudinal
exterior walls
typicalCorridor walls
typical
26’
StrutSW1
SW2
35’ maximum if open front
(i.e. No ext. wall)
Wind loading
Seismic
loading
Co
rrid
or
6’
8’
12’
4’
4’
27’
11.5’
3’
23’
Unit 1 of 6
3’
11.5’
SW
3
Typical Offset Exterior Walls - Plan Layout
Let’s look at
exterior offset
walls
TD3
TD1
TD2
SW4
SW3
SW5
SW2
SW1
Diaphragm stiffness changes
Multi Story, Multi-family
Wood Structure
1
2
3
Loads
I1 I2 I3
Higher shears
and nailing
requirements
I1 I2
SW
SW4
SW3
SW5
SW1
1
2
3Transfer Area
Higher shears
and nailing
Reqmts.
Collector
(typ.)
Higher shears
and nailing
Reqmts.
SW2
Co
llecto
r
Str
ut/
ch
ord
Be
am
TD2
TD1
Str
ut
Main diaphragm
becomes TD3
Optional Framing
Layouts
Collector
(typ.)
Framing and Transfer Diaphragm Layout Options
Loads
Co
lle
cto
r
collectors
Corridor
walls
Jst. Jst.
2x6/2x8Tie straps at
all Joints (typ.)
Typical Corridor Section
Mech.
Co
lle
cto
r
Co
lle
cto
r
Co
lle
cto
r
Layout 1 Layout 3Layout 2
Section
Special nailing of the sheathing to the
collector is required the full length of the
collector (typ.)
Common Transverse Wall Layouts
Corridor
wallsCo
lle
cto
r
SW
SW
SWSW
SW
Layout 4
Co
lle
cto
r
Co
lle
cto
r
SW
SW
Layout 5
Transfer
Area (typ.)
Co
lle
cto
r
Co
lle
cto
r
SW
SW
Layout 6
Co
lle
cto
r
Tying Shear Walls Across the Corridor or Diaphragm??
3. Collectors for shear transfer
to individual full-height wall
segments shall be provided.
SDPWS 4.3.5.1
Diaphragm 1 Diaphragm 2
SW
1S
W2
1 2
B
3
C
A
D
W=200 plf
78’ 122’
6’
22’
22’
50’
7800 # Sum=20000 # 12200 #
156
156 244
244
RL=RR=200(78/2)=7800 #
vR=7800/50=156 plfRL=RR=200(122/2)=12200 #
vR=12200/50=244 plf
Sum=40000 #
=200 plf(200’)
vSW=454.55 plf
vNet=54.55 plf
1200
1200
Layout 1-Full length walls aligned
Diaphragm 1 Diaphragm 2
SW
1
SW
2
SW3
1 2
B
3
C
A
D
4
SW4
11
2 p
lf8
8 p
lf
88
plf
11
2 p
lf
24 p
lf
W=200 plf
78’ 122’
82’
4’
118’
6’
22’
22’
50’
Sum=7976 # Sum=20048 # Sum=11976 #
156
156
164 236
236
244
244
164
8 8
RL=RR=112(78/2)=4368 #
vR=4368/28=156 plf
4368 #
RL=RR=88(82/2)=3608 #
vR=3608/22=164 plf
RL=RR=88(122/2)=5368 #
vR=5368/28=244 plf
RL=RR=112(118/2)=6608 #
vR=6608/28=236 plf
3608 #
Transfer Area
RL=RR=24(4/2)=48 #
vL=vR=48/6=8 plf
Sum=40000 #
=200 plf(200’)
5368 #
6608 #
Case 1-Full length offset walls
Example 1-Offset Shear Walls -Layout 6
SW
1
SW
2
SW3
2
B
3
C
A
D
SW4
156
156
164 236
244
244
164
8
160
160240
240
Total load to grid lines 2 & 3
R23=4368+3608+48+5368+6608+48=20048 # O.K.
LSW=22+22=44’
VSW=20048 #
vSW=20048/44=455.64 plf
vnet SW1=455.64-156-244=55.64 plf
vnet SW2=455.64-164-236=55.64 plf Checks, they
should be equal
SW1
F2AB=55.64(22)=1224 #
F2BC=(156+8)6=984 #
F2C=1224-984=240 #
SW2
F3CD=55.64(22)=1224 #
F3CB=(236+8)6=1464 #
F3B=1224-1464= -240 #
FB23=FC23=240(4)/6=160 #
Shear at transfer area=240/6+8=48 plf
Sum=20048 #
1224
1224984
1464
8 236
Summing V=0
Summing V=0
All forces in lb., all shears in plf
O.K.
Case 1-Smaller resulting forces at corridor
Diaphragm 1 Diaphragm 2S
W1
SW
2
SW3
1 2
B
3
C
A
D
4
SW4
11
2 p
lf8
8 p
lf
88
plf
11
2 p
lf
24 p
lf
W=200 plf
78’ 122’
82’
4’
118’
6’
22’
22’
50’
Sum=7976 # Sum=20048 # Sum=11976 #
156
156
164 236
236
244
244
164
8 8
RL=RR=112(78/2)=4368 #
vR=4368/28=156 plf
4368 #
RL=RR=88(82/2)=3608 #
vR=3608/22=164 plf
RL=RR=88(122/2)=5368 #
vR=5368/28=244 plf
RL=RR=112(118/2)=6608 #
vR=6608/28=236 plf
3608 #
Transfer Area
RL=RR=24(4/2)=48 #
vL=vR=48/6=8 plf
Sum=40000 #
=200 plf(200’)
5368 #
6608 #
Case 2-Full length plus partial length offset shear walls
10’
12’
SW
1
SW
2
SW3
2
B
3
C
A
D
SW4
156
156
164 236
244
244
164
8
2125.49
2125.493188.2
4
3188.2
4
Total load to grid lines 2 & 3
R23=4368+3608+48+5368+6608+48=20048 # O.K.
LSW=22+12=34’
VSW=20048 #
vSW=20048/34=589.65 plf
vnet SW1=589.65-156-244=189.65 plf
vnet SW2=589.65-164-236=189.65 plf Checks, they
should be equal
SW1
F2AB=189.65(22)=4172.24 #
F2BC=(156+8)6=984 #
F2C=4172.24-984=3188.24 #
SW2
FSW2 =189.65(12)=2275.76 #
FSW2 to 3B=(236+8)6+(236+164)10=5464 #
F3B=2275.76-5464= -3188.24 #
FB23=FC23=3188.24(4)/6=2125.49 #
Shear at transfer area=3188.24/6+8=539.37 plf
Sum=20048 #
4172.24
2275.76
3188.24
3188.24
8
236
Summing V=0
Summing V=0
All forces in lb., all shears in plf
Case 2-Larger resulting forces at corridor
O.K.
22’
10’
12’
6’
Total load to grid lines 2 & 3
R23=4368+3608+48+5368+6608+48=20048 # O.K.
LSW=12+10=22’
VSW=20048 #
vSW=20048/22=911.27 plf
vnet SW1=911.27-156-244=511.27 plf
vnet SW2=911.27-164-236=511.27 plf Checks, they
should be equal
SW1
FSW1=511.27(10)=5112.7 #
FSW1 to 2B=(156+244)12=4800 #
F2BC=(156+8)6=984 #
F2C=5112.7-4800-984=-671.3 #
SW2
FSW2=511.27(12)=6135.24 #
FSW2 to 3C=(236+8)6+(236+164)10=5464 #
F3B=6135.24-5464= 671.24 #
FB23=FC23=671.3(4)/6=120 #
Shear at transfer area=671.3/6+8=119.9 plf
SW
2
SW3
2
B
3
C
A
D
SW4
156
156
164 236
244
244
164
8
Sum=20048 #
671.24
8
236
Summing V=0
Summing V=0
All forces in lb., all shears in plf
Case 3-Smaller resulting forces at corridor
O.K.
10’
12’
6’
120
120671.2
4
671.3
5112.7
6135.24
12’S
W1
10’
671.3
Potential buckling
problem w/ supporting
columns and beams
A
B3
2
1
A.75
A.33
The deflection equation must
be adjusted to account for the
uniformly distributed load plus
the transfer force.
Elements requiring
over-strength load
combinations
Transfer diaphragm grid line
1 to 3 See Section 12.10.1.1
ASCE 7 Table 12.3-2
Type 4 vertical irregularity-in-
plane offset discontinuity12.3.3.3 Discont. Walls SDC B-F
12.3.3.4 25% incr. SDC D-F
ASCE 7 Table 12.3-1
Type 4 horizontal irregularity-out-of-
plane offset discontinuity in the LFRS12.3.3.3 Discont. Walls SDC B-F
12.3.3.4 25% incr. SDC D-FASCE 7 Table 12.3-2
Type 4 vertical irregularity- in-
plane offset discontinuity in
the LFRS (if no H.D. at A.25) 12.3.3.3 Discont. Walls SDC B-F
12.3.3.4 25% incr. SDC D-F
Relevant Irregularities Per ASCE 7-10 Tables 12.3-1 and 12.3-2
A.25
Diaphragm 1
Shear wall is not continuous to
foundation. Type 4 horizontal
and vertical irregularity
Chord
Co
llecto
r
Str
ut
Str
ut
Chord
Str
ut
Design supporting collector and
columns for over-strength factor
per ASCE 7-10 Section 12.3.3.3
SDC B-F and 12.10.2.1 SDC C-F.
Type 4 Horizontal Offset Irregularity-Seismic
SW
1
SW
2
SW
3
Type 4 horizontal irregularity-Out-of-plane offset irregularity occurs where there is a discontinuity in
lateral force resistance path. Out-of-plane offset of at least one of the vertical lateral force resisting
elements.
ASCE 7-10 Section 12.3.3.3 (SDC B-F)-Elements supporting discontinuous walls or frames. Type 4
horizontal or vertical irregularity.
• Beams, columns, slabs, walls or trusses.
• Requires over-strength factor of Section 12.4.3
1
2
B
3
C
A
Type 2 and Type 4 Irregularity SDC D-F(Interior collector similar)
Blocking
Continuous member
Alt. Collector/ strut
Connection
ASCE 7-10 Section 12.3.3.3Type 4 Irregularity (SDC B-F)
Elements supporting discont.
Walls:
•Beams, columns, slabs,
walls or trusses.
•Requires over-strength
factor of Section 12.4.3
(also see 12.10.2.1 SDC C-F
for collector requirements).
Diaphragm 1
Shear wall is not continuous to
foundation. Type 4 horizontal
and vertical irregularity
Chord
Co
llecto
r
Str
ut
Str
ut
Chord
Str
ut
Type 4 Horizontal Offset Irregularity-Seismic
SW
1
SW
2
SW
3
ASCE 7-10 Section 12.3.3.4 (SDC D-F) -Type 4 Horizontal irregularity or Type 4 vertical irregularity
requires a 25% increase in the diaphragm (inertial) design forces determined from 12.10.1.1 (Fpx) for
the following elements:
• Connections of diaphragm to vertical elements and collectors.
• Collectors and their connections to vertical elements.
1
2
B
3
C
A
Collectors and their connections
to vertical elements per ASCE 7-10
Section 12.3.3.4. (Grid lines 1, 2
and 3)
• Diaphragm shears
are not required to
be increased 25%.
• The transfer force
(SW) in SDC D-F
must be increased
by rho, per 12.10.1.1.
See 12.10.2 & 12.10.2.1
for collectors
Exception: Forces using the seismic load effects including the over-strength factor
of Section 12.4.3 need not be increased.
Diaphragm 1
Shear wall is not continuous to
foundation. Type 4 horizontal
and vertical irregularity
Chord
Co
llecto
r
Str
ut
Str
ut
Chord
Str
ut
Type 4 Horizontal Offset Irregularity-Seismic
SW
1
SW
2
SW
3
ASCE 7-10 Section 12.3.3.4 (SDC D-F) -Type 4 Horizontal irregularity or Type 4 vertical irregularity
requires a 25% increase in the diaphragm (inertial) design forces determined from 12.10.1.1 (Fpx) for
the following elements:
• Connections of diaphragm to vertical elements and collectors.
1
2
B
3
C
A
Design diaphragm connections to
SW and struts using 25% increase
per ASCE 7-10 Section 12.3.3.4.
(Grid lines 1, 2 and 3)
Type 2 and Type 4 Irregularity SDC D-F(Interior collector similar)
ASCE 7-10 Section 12.3.3.4 (SDC D-F)
Horizontal Type 2 Irreg.-Re-entrant corner,
horizontal and vertical Type 4 irregularity:
Requires a 25% increase in the diaphragm
design forces determined from 12.10.1.1 (Fpx)
for the following elements:
Exception: Forces using the seismic load
effects including the over-strength factor of
Section 12.4.3 need not be increased.
Blocking
Continuous member
Alt. Collector/
strut Connection
• Connections of diaphragm to
vertical elements and collectors.
CollectorShear Wall
• Collectors and their connections,
including their connections to
vertical elements.
Ftg.
Strut/Collector
Strut/Collector
SW1
Vr
V2
Dhr
Dh2
Ftg.
Su
pp
ort
co
lum
n
A BA.25
SW2
Shear wall system at grid line 1
In-plane Offset of Wall
Su
pp
ort
co
lum
n
ASCE 7 Table 12.3-2-Type 4 vertical
irregularity- In-plane offset
discontinuity in the LFRS
Wall element is designed for
standard load combinations of
ASCE 7-10 Sections 2.3 or 2.4.
Shear wall anchorage
is designed for
standard load
combinations of
Sections 2.3 or 2.4.
Column elements
are designed for
standard load
combinations 2.3
or 2.4.
Wall designed for
over-strength per
ASCE 7-10 Section
12.3.3.3 (SDC B-F)
And/or 12.3.3.4 (SDC
D-F)
Shear wall anchorage is
designed for standard load
combinations of Sections
2.3 or 2.4.
Co
llecto
r
Assuming no
hold down
See struts and collectors
Ftg.
Support beam/collector
Collector
SW3
Vr
V2
Su
pp
ort
co
lum
n
Ftg.
Su
pp
ort
co
lum
n
A BA.33
Shear wall system at grid line 2
Out-of-Plane Offset
Footings are not
required to be
designed for
over-strength.
Dhr
Dh2
Dv
ASCE 7 Table 12.3-1-Type 4 horizontal
irregularity- out of-plane offset
discontinuity in the LFRS
Wall element is designed for
standard load combinations
of ASCE 7-10 Sections 2.3 or
2.4.
Shear wall hold downs
and connections are
designed for standard
load combinations of
ASCE 7-10 Sections 2.3
or 2.4.
Elements supporting discontinuous
walls or frames require over-strength
Factor of Section 12.4.3.
Collector and columns shall
be designed in accordance
with ASCE 7-10 section: 12.3.3.3
Connection is
designed for
standard load
combinations of
Sections 2.3 or 2.4.
See struts and collectors
Grade beamFtg.
Support beam/collector
Collector
SW4
SW5
Vr
V2S
up
po
rt c
olu
mn
Gr. Bm.
DL
Ftg.
Su
pp
ort
co
lum
n
AB A.75 A.33
Shear wall system at grid line 3-In-plane Offset
Footings are not required
to be designed for over-
strength.
ASCE 7 Table 12.3-2-Type 4 vertical
irregularity- In-plane offset discontinuity
in the LFRS
Wall element, hold downs,
and connections are
designed for standard
load combinations of
ASCE 7-10 Sections 2.3
or 2.4.
Elements supporting discontinuous walls or
frames require over-strength factor of Section 12.4.3.
Collector and columns shall be designed in
accordance with ASCE 7-10 section: 12.3.3.3
Connections are
designed for standard
load combinations of
Sections 2.3 or 2.4.
Dhr
Dh2
Connections are
designed for standard
load combinations of
ASCE 7-10 Sections
2.3 or 2.4.
Wall element
designed for
standard load
combinations of
Sections 2.3 or 2.4.
See struts and collectors
Struts and Collectors
Possible struts:
• Truss or rim joist
over wall
• Double top plate
• Beam/header
12.10.2 SDC B - Collectors can be designed w/o over-strength
but not if they support discontinuous walls or frames.
12.10.2.1 SDC C thru F- Collectors and their connections, including connections to the vertical resisting
elements require the over-strength factor of Section 12.4.3, except as noted:
Shall be the maximum of:
𝛀𝒐𝑭𝒙 - Forces determined by ELF Section 12.8 or Modal Response Spectrum Analysis
procedure 12.9
𝛀𝒐 𝑭𝒑𝒙 - Forces determined by Diaphragm Design Forces (Fpx), Eq. 12.10-1 or
𝑭𝒑𝒙 𝒎𝒊𝒏= 𝟎. 𝟐𝑺𝑫𝑺𝑰𝒆𝒘𝒑𝒙 - Lower bound seismic diaphragm design forces determined by
Eq. 12.10-2 (Fpxmin) using the Seismic Load Combinations of section
12.4.2.3 (w/o over-strength)-do not require the over-strength factor.
Struts / collectors and their connections shall be designed in
accordance with ASCE 7-10 sections:
Exception:
1. In structures (or portions of structures) braced entirely by light framed shear walls, collector
elements and their connections, including connections to vertical elements need only be designed
to resist forces using the standard seismic force load combinations of Section 12.4.2.3 with forces
determined in accordance with Section 12.10.1.1 (Diaphragm inertial Design Forces, 𝑭𝒑𝒙).
Struts and Collectors-Seismic
𝑭𝒑𝒙 𝒎𝒂𝒙= 𝟎. 𝟒𝑺𝑫𝑺𝑰𝒆𝒘𝒑𝒙- Upper bound seismic diaphragm design forces determined by
Eq. 12.10-2 (Fpxmax) using the Seismic Load Combinations of section
12.4.2.3 (w/o over-strength)-do not require the over-strength factor.
Presentation Topics
• Shear Wall Types
• Shear wall Anchorage
• SDPWS Code Requirements
• Complete Load Paths
• Offset Shear Walls and Relevant Code
Requirements
• Mid-rise Diaphragms and Tall Shear Walls
Mid-rise Diaphragms and Shear Walls
Crescent Terminus building- credit: Richard Lubrant.
Important Design considerations: Continuous load paths
Vertical/horizontal irregularities
Diaphragm stiffnesses and flexibility
Shear wall stiffness and the effects of tall walls
Horizontal distribution of forces within the diaphragm and
shear walls
The effects of offset diaphragms and shear walls
• ASCE 7-10 Section 12.3.1.1- (c), Light framed construction, meeting all conditions:
Longitudinal-Allowed to be idealized as flexible, provided exterior shear walls
exist. However, diaphragm can be semi-rigid or open front, even if exterior walls
exist.
Transverse-Traditionally assumed to be flexible diaphragm.
If token or questionable wall stiffness at exterior, use semi-rigid analysis
envelope method-(conservative), or semi-rigid, or idealize as rigid.
Non-open front
Open Front Structures:
• SDPWS 4.2.5.2 :
Loading parallel to open side - Model as semi-rigid (min.), shall include shear
and bending deformation of the diaphragm, or idealized as rigid.
Loading perpendicular to open side-traditionally assumed to be flexible.
Drift at edges of the structure ≤ the ASCE 7 allowable story drift ratio when
subject to seismic design forces including torsion, and accidental torsion
(strength, multiplied by Cd). Drift check not required for wind.
Includes flexible and rigid analysis
Typical Floor Plan
Typical
Unit
Open Front / Cantilever Diaphragm-Corridor Shear Walls Only
Transverse
shear walls
typical
No exterior
shear walls
typicalCorridor walls
typical
26’
StrutSW1
SW2
35’ Maximum
(2015 SDPWS)
Wind loading
Seismic
loading
Co
rrid
or 6’
8’
12’
4’
4’
27’
11.5’
3’
23’
Unit 1 of 6
3’
11.5’
Shear panels are
required over
corridor walls
W’
L’
Limit= 35’
Example-Open Front Diaphragms
Side wall
End wall
Side wall S
tru
t
Strut
Strut Strut
Str
ut
SW1
SW2
Str
ut/
ch
ord
W’
Side wall
Side wall
End wall or
Corridor wall
Str
ut
Strut
Strut Strut
Str
ut
SW1
SW2
Location of strut/chord
depends on framing
orientation
L’
Limit= 35’
Wind loading
Seismic
loading
4.2.6.1 Framing requirements:
• Diaphragm boundary elements shall be provided to transmit design
tension, compression and shear forces.
• Diaphragm Sheathing shall not be used to splice boundary elements.
Co
rrid
or
Corridor only shear walls
..
Check drift at edges
(extreme corners)
including torsion
plus accidental
torsion (Deflection-
strength level x Cd. )
w
∆𝒔𝒘
∆𝑫𝒊𝒂𝒑𝒉
W’
L’
Shear
Defl.Nail
sliprotation End shear
wall lateral
translation
Example-Simple Open Front Diaphragm Deflection (APA)
End wall
Side wall
∆𝑨=𝑽𝒎𝒂𝒙 𝑳
𝟐𝑮𝒕+ 0.376L’𝒆𝒏 +
𝟐∆𝒔𝒘𝑳
𝒃+ ∆𝒆𝒘
∆𝒔𝒘𝟏
∆𝒔𝒘𝟐
∆𝑨
∆𝒔𝒊𝒅𝒆𝒘𝒂𝒍𝒍
𝜽
𝜽
Note:
If there are splices in the struts, chord slip must
be added to the deflection equation
Str
ut
Strut
Strut Strut
Str
ut
SW1
SW2
Str
ut
/ ch
ord
Bending term required if
chords cont. across corridor
Rotation term needs to be
adjusted if different end
wall lengths
∆𝒔𝒘
∆𝒔𝒘∆𝑨
𝜽
∆𝑬𝒘
b
L
En
d w
all
Side wall
APA Figure
Open
end
w
Boundary element not
restrained for bending
e
V
F
F
Side wall
Relevant 2015 SPDWS Sections-Open Front Structures
New definitions added:
• Open front structures
• Notation for L’ and W’ for
cantilever Diaphragms
• Collectors
Relevant Revised sections:
• 4.2.5- Horizontal Distribution
of Shears
• 4.2.5.1-Torsional Irregularity
• 4.2.5.2- Open Front Structures
(a)
L’
W’
Force
Cantilever Diaphragm
Plan
Open front
SW
SW
L’
Cantilever
DiaphragmPlan
W’
Open front
SW
SW
SW
ForceL’
W’
Open front
SW
SWForce
Cantilever
Diaphragm
Figure 4A Examples of Open Front Structures
(d)
L’
W’
Open front
SW
SW
Force
Cantilever
Diaphragm
SW
SWL’
Cantilever
Diaphragm
(c)(b)
Open front
4.2.5 Horizontal Distribution of Shear (Revised)
Distribution of shear to vertical resisting elements shall be based on:
• Analysis where the diaphragm is modeled as :o Idealized as flexible-based on tributary area.
o Idealized as rigid
Distribution based on relative lateral stiffnesses of vertical-resisting elements of the
story below.
Can be idealize as rigid when the computed maximum in-plane deflection of the
diaphragm is less than or equal to two times the average deflection of adjoining
vertical elements of the LFRS under equivalent tributary lateral load.
o Modelled as semi-rigid.
Not idealized as rigid or flexible
Distributed to the vertical resisting elements based on the relative stiffnesses of the
diaphragm and the vertical resisting elements accounting for both shear and flexural
deformations.
It shall be permitted to use an enveloped analysis -Larger of the shear forces resulting
from analyses where idealized as flexible and idealized as rigid (Minimum analysis).
Average drift
of walls
Maximum diaphragm deflection
(MDD) >2x average story drift of
vertical elements, using the ELF
Procedure of Section 12.8.
Maximum
diaphragm
deflection
Calculated as Flexible
• More accurately distributes lateral forces
to corridor, exterior and party walls
• Allows better determination of building drift
• Can under-estimate forces distributed to the corridor walls
(long walls) and over-estimate forces distributed to the
exterior walls (short walls)
• Can inaccurately estimate diaphragm shear forces
Note:
Offsets in diaphragms can also
affect the distribution of shear
in the diaphragm due to changes
in the diaphragm stiffness.
4.2.5.2 Open Front Structures: (Figure 4A)
For resistance to seismic loads, wood-frame diaphragms in open front structures shall comply with all
of the following requirements:
1. The diaphragm conforms to:
a. WSP-L’/W’ ratio ≤ 1.5:1 4.2.7.1
b. Single layer-Diag. sht. Lumber- L’/W’ ratio ≤ 1:1 4.2.7.2
c. Double layer-Diag. sht. Lumber- L’/W’ ratio ≤ 1:1 4.2.7.3
2. The drift at edges shall not exceed the ASCE 7 allowable story drift ratio when subject to
seismic design forces including torsion, and accidental torsion (Deflection-strength level
amplified by Cd. ).
3. For open-front-structures that are also torsionally irregular as defined in 4.2.5.1, the L’/W’
ratio shall not exceed 0.67:1 for structures over one story in height, and 1:1 for structures
one story in height.
4. For loading parallel to open side:
a. Model as semi-rigid (min.), shall include shear and bending deformation of the diaphragm,
or idealized as rigid.
b. Drift at edges of the structure ≤ the ASCE 7 allowable story drift ratio when
subject to seismic design forces including torsion, and accidental torsion. Torsion
(Deflection-strength level amplified by Cd. )
5. The diaphragm length, L’, (normal to the open side) does not exceed 35 feet.
Exception:
Where the diaph. edge cantilevers no more than 6’ beyond the nearest line of vertical
elements of the LRFS.
4.2.5.2.1 For open front structures of 1 story, where L’≤25’ and L’/W’ ≤1:1, the diaphragm shall be
permitted to be idealized as rigid for the purposes of distributing shear forces through torsion.
• Idealized as Flexible
• Idealized as Rigid
ASCE7-10 Section 12.3-Diaphragm Flexibility
or…..
12.3.1 Diaphragm Flexibility- The structural Analysis shall consider the relative
stiffnesses of the diaphragm and the vertical elements of the seismic force-
resisting system. Unless a diaphragm can be idealized as either flexible or rigid,
the structural analysis shall explicitly include consideration of the stiffness of the
diaphragm (i.e. semi-rigid modeling assumption).
• You can model it as Semi-rigid
Average drift
of walls
Is maximum diaphragm
deflection (MDD) >2x average
story drift of vertical elements,
using the Equivalent Force
Procedure of Section 12.8?
Maximum diaphragm
deflection
Semi-rigid (Envelope Method)
Is diaphragm
untopped steel
decking or Wood
Structural Panels
Idealize
as
flexible
Is span to depth ratio ≤ 3
and having no horizontal
irregularities ?
Is diaphragm concrete
slab or concrete filled
steel deck ?
Structural analysis must
explicitly include consideration
of the stiffness of the diaphragm
(i.e. semi-rigid modeling).
Is any of the following true?
1 & 2 family Vertical elements one Light framed construction
Dwelling of the following : where all of the following are
met:
1. Steel braced frames 1. Topping of concrete or
2. Composite steel and similar material is not
concrete braced frames placed over wood structural
3. Concrete, masonry, steel SW panel diaphragms except
or composite concrete and for non-structural topping
steel shear walls. not greater than 1 ½” thick.
2. Each line of vertical
elements of the seismic
force-resisting system
complies with the allowable
story drift of Table 12.12-1.
Idealize
as rigid
Idealize as
flexible
Yes
YesYes
No
No
No
No
No
Sta
rtASCE7-10 Section 12.3 Diaphragm Flexibility Seismic
Yes
Yes
Section 12.3.1- The structural analysis shall consider the relative stiffnesses of diaphragms and the
vertical elements of the lateral force resisting system.
(Could apply to CLT or Heavy timber diaphragms)
Is diaphragm untopped steel
decking , concrete filled steel
decks or concrete slabs, each
having a span-to-depth ratio
of two or less?
Yes
Yes
No
Diaphragm can
be idealized as
flexible
Is diaphragm of
Wood Structural
Panels ?
Diaphragm can
be idealized as
rigid
No
Is diaphragm untopped steel
decking , concrete filled steel
decks or concrete slabs, each
having a span-to-depth ratio
greater than two ?
Yes Calculate as
flexible or
semi-rigid
ASCE7-10, Section 26.2 Diaphragm Flexibility Wind
Start
Tall Shear Walls
Marselle Condominiums 5 stories of wood over 6 stories concrete Structural
Engineer engineer: Yu & Trochalakis, PLLC (podium) 2 above grade
Photographer: Matt Todd Photographer
Tall FTAO walls
or open front
structure???
∆𝑺𝑾=𝟖𝒗𝒉𝟑
𝑬𝑨𝒃+
𝒗𝒉
𝟏𝟎𝟎𝟎𝑮𝒂+ 𝒉∆𝒂
𝒃
A/R
h/d ≤ 2:1
Methods Used:
• Shiotani/Hohbach Method
• Thompson Method
• FPInnovations Method
• Computer models (Cashew)
A/R
h/d ≤ 3.5:1
Tall Shear Walls
+
+
Traditional Method
• Traditional Method good for 3 stories or less
(w/ exception)
• Tall walls greater than 3 stories require
consideration of flexure and wall rotation.
VR
V3
V2T
rad
itio
na
l
Me
tho
d
Ta
ll W
all
Me
tho
d
∆𝑻= ∆𝒔𝒘𝟏+∆𝒔𝒘𝟐 + ∆𝒔𝒘𝟑
Testing shows that the traditional deflection
equation cannot be used for walls with
aspect ratios higher than 2:1, because
deflections can not be adequately predicted.(Dolan)
Walls assumed
to be pinned at
top and bottom
at each floor-Rigid
wall sections
∆𝟑.𝟓:𝟏∆𝟐:𝟏
Tall Wall
A/R, Stiffness of Shear Walls
Diaphragm
out-of-plane
stiffness=Flexible
Analyze as
tall wall
Diaphragm
out-of-plane
stiffness=Rigid
Analyze as
floor to floor
Doesn’t account for multi-story shear wall effects
FPInnovations-Deflections of Stacked Multi-story Shear Walls”A Mechanics-Based Approach for Determining Deflections of Stacked Multi-Storey Wood-Based Shear
Walls”, Newfield (metric units)
• Mechanics based approach
• Uses 5 part deflection equation
∆𝒊= ∆𝒃,𝒊 + ∆𝒔,𝒊 + ∆𝒏,𝒊 + ∆𝒂,𝒊 + ∆𝒓,𝒊
𝑴𝒐 =
𝒊
𝒏
𝑽𝒊𝑯𝒊
𝑽𝒐 =
𝒊
𝒏
𝑽𝒊
Ls
Lc
ytr
∆𝒏
Where
∆𝒃,𝒊= 𝑽𝒊𝑯𝒊𝟑
𝟑 𝑬𝑰 𝒊+ 𝑴𝒊𝑯𝒊𝟐
𝟐 𝑬𝑰 𝒊
∆𝒔,𝒊= 𝑽𝒊𝑯𝒊
𝑳𝒊𝑩𝒗,𝒊
∆𝒏,𝒊= 0.0025𝑯𝒊𝒆𝒏,𝒊
∆𝒂,𝒊= 𝑯𝒊
𝑳𝒊𝒅𝒂,𝒊 (Includes affects of rod elongation
and crushing)
∆𝒓,𝒊= 𝑯𝒊 ∑𝒋−𝟏𝒊−𝟏 𝑽𝒋𝑯𝒋
𝟐
𝟐 𝑬𝑰 𝒋+𝑴𝒋𝑯𝒋
𝑬𝑰 𝒋+𝑯𝒊 ∑𝒋−𝟏
𝒊−𝟏 𝒅𝒂,𝒋
𝑳𝒋
∆𝒂,𝒊
Bending
Panel
Shear
Nail slip
Anchor
Elongation
Wall
Rotation
5 part deflection equation
Rotational deflection
∆𝒃,𝒊
𝜃𝒊
𝒋=𝟏
𝒊−𝟏
𝜽𝒋
𝒊
𝒋
𝒊−𝟏
α𝒋
𝑯𝒊𝜶𝟏 + 𝜶𝟐 +…𝜶𝒊−𝟏
𝑯𝒊 𝜽𝟏 + 𝜽𝟐 +⋯𝜽𝒊−𝟏
𝑯𝒊
Level i
Level i-1
𝑰𝒕𝒓=𝑨𝒕,𝒕𝒓 . 𝒚𝒕𝒓𝟐 +𝑨𝒄 . 𝑳𝒄 − 𝒚𝒕𝒓
𝟐
Uses transformed composite section
(transformed bending stiffness)
where continuous tie down (ATS)
∆𝒃,𝒊
𝑰=𝑨 . 𝑳𝟐/2 if discrete hold down
(wood chord members used)
(cont. hold down used)
∆=𝟓𝐯𝑳𝟑
𝟖𝑬𝑨𝒃+𝒗𝑳
𝟒𝑮𝒕+ 𝟎. 𝟏𝟖𝟖𝐋𝒆𝒏 +
𝚺 𝜟𝑪𝑿
𝟐𝒃𝐈𝐁𝐂 𝐄𝐪. 𝟐𝟑 − 𝟏
I1 I2 I3Rigid or spring
Support ??
Exte
rio
r
sh
ear
walls
Typical Multi-residential Mid-rise unit
Rigid support or
Partial support
Support Support
TD1
TD2 No
Support
TD1
TD2
I1I2I3
No support
(Full cantilever)
Adjust terms of the equation for support
condition, stiffness and loading conditions
Wind Loads as applicableSeismic Loads
Support Support
Full support
(SW rigid)
Partial support
(Decreasing
SW stiffness)
No SW
support
If flexible
diaphragm
Corridor only SW
Condition B
Condition ACondition C
Longitudinal Loading
No exterior
Shear walls ??
Drift by semi-rigid or
rigid analysis only
Calculation of drift at corners is
required for all open front or
cantilever diaphragms (seismic only)
including torsion and accidental
torsion (Deflection-strength level
amplified by Cd. )
Determination of Open Front Diaphragm Flexibility
26’
StrutSW1
SW2
35’
Wind loading
Seismic
loading
Areas of non-clarity:• Determination of diaphragm flexibility if open front
• Effects/requirements of blocking
• Wind requirements for open front diaphragms
• Exterior wall contribution, ignore? Model as non-resisting?
Corr
idor
Corridor only shear walls
.
∆𝒔𝒘
∆𝑫𝒊𝒂𝒑𝒉 I1I2I3
Computer Model
6’
8’
12’
4’
4’
27’
11.5’
3’
M
V
23’
Unit 1 of 6
156’
Sym.
C.L.
3’
11.5’
Spring
Support
(SW stiff.) K1
Full depth
Wind
Seismic
Bending ∆
Does not
include
rotational
effects
∑ Kdiaph.
Shear Deflection per
USDA Research Note
FPL-0210
Location of strut/chord
depends on framing
orientation
26’
StrutSW1
SW2
Wind loading
Seismic
loading
Co
rrid
or
∆𝒔𝒘𝒄𝒐𝒓𝒓.
6’
8’
12’
4’
4’
27’
11.5’
3’
11.5’
Unit 1 of 6
Determination of Diaphragm Flexibility and Shear Distribution With
Exterior Shear Walls
Narrow Exterior shear wallsFlr. / Flr. hgt.= 10’-0”
∆𝒔𝒘 𝒆𝒙𝒕
Spring
Support
(SW stiff.)
I1I2I3
Computer Model
SW
3
Tall or
narrow
SW
Full depth
M
V
35’
156’
Sym.
C.L.
3’
23’
Spring
Support
(SW stiff.)K1 K2
Not considered open front because of ext. SW-However, ?????
1K
2.5K
5K
Wind
Seismic
10KNo stiff. or
support
Low stiff.
Moderately
stiff.
Rigid
support
. .Positive
moments
100% 97.5%95.2%91% 0%
2.5%4.8%9%
Place holders
∑ Kdiaph.
.Shear Deflection per
USDA Research Note
FPL-0210
∆𝑫𝒊𝒂𝒑𝒉
∆ 𝑺𝑾𝑨𝒗𝒆𝒓.
2D Computer Model-Longitudinal Loading
Spring support
if Shear walls = SW stiffness
Drift by semi-rigid or
rigid analysis only
+Same
as
=23’11.5’
Calculation of drift at corners is required for all open front or
cantilever diaphragms (seismic only) including torsion and
accidental torsion (Deflection-strength level amplified by Cd. )
Drift by semi-rigid
or rigid analysis
only
Spring support
If Shear walls
+
Same as
=
2D Computer Model-Transverse Loading
Calculation of drift at
corners is required for all
open front or cantilever
diaphragms (seismic only)
including torsion and
accidental torsion
(Deflection-strength level
amplified by Cd. )
Model asModel as
Note: Rigid diaphragm
analysis can cause
torsional irregularity even
if uniform distribution of
transverse walls
Reference Materials
http://www.woodworks.org/publications-media/solution-papers/
http://www.woodworks.org/wp-content/uploads/Irregular-
Diaphragms_Paper1.pdf
• The Analysis of Irregular Shaped Structures: Diaphragms and Shear Walls-Malone,
Rice-Book published by McGraw-Hill, ICC
• Woodworks-The Analysis of Irregular Shaped Diaphragms (paper)
• Woodworks Webinar-Offset Diaphragms-Part 1
• Woodworks Presentation Slide Archives-Workshop-Advanced Diaphragm Analysis
• Woodworks Webinar-Offset Shear Walls- Part 2-Coming on December 16
• NEHRP (NIST) Seismic Design Technical Brief No. 10-Seismic Design of Wood
Light-Frame Structural Diaphragm Systems: A Guide for Practicing Engineers
• SEAOC Seismic Design Manual, Volume 2
Woodworks-The Analysis of Irregular Shaped
Diaphragms (paper). Complete Example with narrative and
calculations.