Seismic Detailing of Special Shear Walls and

Coupling Beams Date: 16 June 2021

URP S-09 Training Module S12

Dr. S. K. GhoshPresident, S. K. Ghosh Associates LLC

Detailing by BNBC-2020

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 1

Page 2: S12 Detailing of Shear Walls

Basis of Concrete Design Provisions of BNBC-2020

Updates of ACI 318-08

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 2

Page 3: S12 Detailing of Shear Walls

Basis

ACI 318-08 Chapter 21; rest applies except where modifiedBNBC-2017 Part 6: STRUCTURAL DESIGNChapter 8: DETAILING OF REINFORCEMENT IN CONCRETE STRUCTURESSection 8.3: EARTHQUAKE-RESISTANT DESIGN PROVISIONSChapter 6: STRENGTH DESIGN OF REINFORCED CONCRETE STRUCTURES applies except where modified

Section Numbers

All section numbers that are not in blue are from ACI 318-08

All section numbers in blue are from BNBC-2020 Part 6, Chapter 8 or Chapter 6, unless otherwise noted.

ACI 318-14 changes are indicated in green.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 3

Page 4: S12 Detailing of Shear Walls

Seismic DesignSeismic design, in its very essence, is an exercise in trade-off between strength and inelastic deformation capacity.

Inelastic deformation capacity is the ability of a structure to continue to carry full factored gravity loads as it deforms beyond the stage of elastic response.

Inelastic deformation capacity comes from proper detailing of the structural members and the joints.

Seismic Design by the IBC/ BNBC-2020Chapter 16 (Part 6, Section 2.5) sets the design force level or strength.Detailing rules are given in the materialschapters: 19 (Pt 2, Ch 8) for concrete, 21 (Pt 2, Ch 7) for masonry, 22 (Pt 2, Ch 10) for steel, 23 (Pt 2, Ch11) for wood. The materials chapters reference materials standards: ACI 318 for concrete.Three levels of detailing are defined: ordinary, intermediate, special.R-value provides the link between design force level and level of detailing.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 4

Page 5: S12 Detailing of Shear Walls

Seismic Design by the IBC/ BNBC-2020

SDC A: No seismic design required

SDC B: Unrestricted trade-off between strength and inelastic deformability.

SDC C: Intermediate detailing required as a minimum.

SDC D, E, or F: Special detailing required as a minimum. [E or F does not exist in Bangladesh]

EARTHQUAKE FORCE-RESISTING STRUCTURAL SYSTEMS OF CONCRETE —

ASCE 7-05 (BNBC-2020 Table 6.2.19)

BASIC SEISMIC FORCERESISTING SYSTEM

DETAILING REF.SECTION R o Cd

SYSTEM LIMITATIONS AND BUILDINGHEIGHT LIMITATIONS (m) BY SEISMIC

DESIGN CATEGORY

B C D E F

Bearing Wall Systems

Special reinforced concrete shear walls 14.2 and14.2.3.6 5 21/2 5 NL NL 50 50 30

Ordinary reinforced concrete shear walls 14.2 and14.2.3.4 4 21/2 4 NL NL NP NP NP

Detailed plain concrete shear walls 14.2 and14.2.3.2 2 21/2 2 NL NP NP NP NP

Ordinary plain concrete shear walls 14.2 and14.2.3.1 11/2 21/2 11/2 NL NP NP NP NP

Intermediate precast shear walls 14.2 and14.2.3.5 4 21/2 4 NL NL 121 121 121

Ordinary precast shear walls 14.2 and14.2.3.3 3 21/2 3 NL NP NP NP NP

1Increase in height to 14 m is permitted for single-story storage warehouse facilities.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 5

Page 6: S12 Detailing of Shear Walls

EARTHQUAKE FORCE-RESISTING STRUCTURAL SYSTEMS OF CONCRETE —

ASCE 7-05 (BNBC-2020 Table 6.2.19)

BASIC SEISMIC FORCERESISTING SYSTEM

DETAILINGREF. SECTION R o Cd

SYSTEM LIMITATIONS AND BUILDINGHEIGHT LIMITATIONS (m) BY SEISMIC

DESIGN CATEGORY

B C D E F

Building Frame Systems

Special reinforced concrete shear walls 14.2 and14.2.3.6 6 21/2 5 NL NL 15 15 9

Ordinary reinforced concrete shear walls 14.2 and14.2.3.4 5 21/2 41/2 NL NL NP NP NP

Detailed plain concrete shear walls 14.2 and14.2.3.2 2 21/2 2 NL NP NP NP NP

Ordinary plain concrete shear walls 14.2 and14.2.3.1 11/2 21/2 11/2 NL NP NP NP NP

Intermediate precast shear walls 14.2 and14.2.3.5 5 21/2 41/2 NL NL 41 41 41

Ordinary precast shear walls 14.2 and14.2.3.3 4 21/2 4 NL NP NP NP NP

1Increase in height to 14 m is permitted for single-story storage warehouse facilities.

EARTHQUAKE FORCE-RESISTING STRUCTURAL SYSTEMS OF CONCRETE —

ASCE 7-05 (BNBC-2020 Table 6.2.19)

BASIC SEISMIC FORCERESISTING SYSTEM

DETAILINGREF. SECTION R o Cd

SYSTEM LIMITATIONS AND BUILDINGHEIGHT LIMITATIONS (m) BY SEISMIC

DESIGN CATEGORY

B C D E F

Dual Systems with Special Moment Frames

Special reinforced concrete shear walls 14.2 7 21/2 51/2 NL NL NL NL NL

Ordinary reinforced concrete shear walls 14.2 6 21/2 5 NL NL NP NP NP

Dual Systems with Intermediate Moment Frames

Special reinforced concrete shear walls 14.2 61/2 21/2 5 NL NL 15 9 9

Ordinary reinforced concrete shear walls 14.2 51/2 21/2 41/2 NL NL NP NP NP

Shear Wall Frame Interactive System withOrdinary Reinforced Concrete MomentFrames and Ordinary Reinforced ConcreteShear Walls

12.2.5.10 and14.2 41/2 21/2 4 NL NP NP NP NP

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 6

Page 7: S12 Detailing of Shear Walls

21.1.4, 21.1.5 – Materials

Concrete 8.3.3.3• Compressive strength not less than 21 MPa• Lightweight – Not greater than 35 MPa

Reinforcement 8.3.3.4(b)• Low-alloy – A706 Grade 420Alternatively,

• Billet-steel – A615 (modified) Grades 275 and 420• BDS ISO 6935-2 Grades 300, 350, 400 and 420 or ASTM

A615 Grades 275 and 420 with supplementary requirements

21.1.5 – Reinforcement

The actual yield strength based on mill tests does not exceed by more than 125 N/mm2 (retests shall not exceed this

value by more than an additional 20 N/mm2); 8.3.3.4(b)(i)

Minimum elongation in 200 mm shall be at least 14 percent for bar dia. 10 mm to 20 mm, at least 12 percent for bar dia. 22 mm through 36 mm, and at least 10 percent for bar dia. 40 mm to 60 mm. 8.3.3.4(b)(iii) Added in ACI 318-14

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 7

Page 8: S12 Detailing of Shear Walls

21.1.5 , 8.3.3.4(b)(ii) – Reinforcement

BILLET STEEL REINFORCEMENT

21.1.5 – Reinforcement

ACI 21.1.5.4, 8.3.3.4(c) — The value of fyt used to compute the amount of confinement reinforcement shall not exceed 700 MPa .

ACI 21.1.5.5, 8.3.3.4(d) — The value of fy or fyt used in design of shear reinforcement shall conform to 11.4.2, 6.4.3.2.

ACI 11.4.2, 6.4.3.2 — The values of fy and fyt used in design of shear reinforcement shall not exceed 420 MPa, except the value shall not exceed 550 MPa for welded deformed wire reinforcement.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 8

Page 9: S12 Detailing of Shear Walls

DESIGN OF SPECIAL SHEAR WALLS FOR SHEAR

18 Design of Special Shear WallsDesign requirements for special shear walls were changed in significant ways in ACI 318-14 in view of lessons learned from the Chile earthquake of 2010.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 9

Page 10: S12 Detailing of Shear Walls

Shear Design of Special Shear Walls

Vu Vn

ACI 21.9.3 (8.3.6.3)Vu is to be obtained from lateral load analysis in accordance with factored load combinations

Shear Design of Special Shear Walls

Vu Vn

ACI 9.3.4 (6.2.3.3(a))For structures that rely on special reinforced concrete structural walls to resist earthquake force effects E, for shear for any structural member that is designed to resist E is to be 0.6 if the nominal shear strength of the member is less than the shear corresponding to the development of the nominal flexural strength of the member.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 10

Page 11: S12 Detailing of Shear Walls

Vn = Acv( c f c + tfy) 0.66Acv f c

lwAcv

c varies linearly from 3.0 for hw/lw = 1.5 to 2.0 for hw/lw = 2.0

c = 2 for hw/lw > 2.0

21.9.4 (8.3.6.4)Shear Design of Special Shear Walls

21.9.4 (8.3.6.4) Shear Design of Special Shear Walls

21.9.4.2 (8.3.6.4(b))The ratio of hw/lw used for determining Vn for segments of a wall is the larger of the ratios for

a. the entire wall, and

b. the segment of wall considered

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 11

Page 12: S12 Detailing of Shear Walls

21.9.2 (8.3.6.2)Special Shear Wall Reinforcement

l 0.0025, s 450 mm.

t 0.0025, s 450 mm.

Two curtains of reinforcement required when Vu > 0.17Acv f c or when hw/lw 2.0

When hw/lw 2.0, l t

Min. reinforcement per 14.3 (11.6) when Vu 0.08Acv f c

18 Design of Special Shear Walls

R18.10.2 …The requirement for two layers of vertical reinforcement in more slender walls is to improve lateral stability of the compression zone under cyclic loads following yielding of vertical reinforcement in tension.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 12

Page 13: S12 Detailing of Shear Walls

SPECIAL SHEAR WALL DESIGN FOR FLEXURE AND AXIAL COMPRESSION

ACI 318-95

Pu

Mu

Ig

lw

2

Pu2l w

Mu

l w

Pu2

Mu

l w

lw

Mu

Boundary elements required to carry entire Pu and Mu

PuAg

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 13

Page 14: S12 Detailing of Shear Walls

ACI 318-95

Design for Flexure and Axial Load

• fc = (Pu/Ag) + (Mulw/2Ig) > 0.2f c

• Pu,boundary = (Pu/2) (Mu/l w)

ACI 318-95

Shortcomings

•Very large boundary elements with extremely large amounts of vertical reinforcement required

•Extensive amounts of required confinement reinforcement made construction very difficult

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 14

Page 15: S12 Detailing of Shear Walls

ACI 318-95

Shortcomings

•Flexural overstrength created high shear demand

•Unconservative shear design could result

Example

Seismic Zone 4

20 stories tall

Beams: 500 x 550 mm

Cols.: 500 x 500 mm

Walls: 300 mm thick

950 x 950 mm boundary elements

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 15

Page 16: S12 Detailing of Shear Walls

Example

Constructability?

21.9.5 (8.3.6.5)Design for Flexure and Axial Loads

Design for flexural and axial loads•Design in accordance with 10.2 (6.3.2) and 10.3 (6.3.3)

•10.3.7 (6.3.3.7) (slenderness effects) and nonlinear strain requirements of 10.2.2 (6.3.2.2) shall not apply

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 16

Page 17: S12 Detailing of Shear Walls

21.9.5 (8.3.6.5)Design for Flexure and Axial Loads

Effective flange width

•Effective flange width shall extend from the face of the web a distance equal to the smaller of

• 0.5 × (distance to adjacent wall web)• 0.25 × (total wall height)

21.9.6 (8.3.6.6)Boundary Elements of Special Structural Walls

Special boundary elements

•Two methods to determine need for special boundary elements•21.9.6.2 (8.3.6.6(b))•21.9.6.3 (8.3.6.6(c))

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 17

Page 18: S12 Detailing of Shear Walls

21.9.6.2 (8.3.6.6(b))Displacement-Based Approach

Applicable to walls or wall piers that are• Effectively continuous from the base of the structure to

the top of the wall

• Designed to have a single critical section for flexure and axial loads

And have hw/lw 2.0

21.9.6.2 (8.3.6.6(b))Displacement-Based Approach

Compression zones shall be reinforced with special boundary elements when

u = design displacement; total lateral displacement expected for the design-basis earthquake

clw

600(1.5 u/hw)u/hw 0.007 (0.005)

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 18

Page 19: S12 Detailing of Shear Walls

2.1 – Notation

c = distance from the extreme compression fiber to neutral axis

corresponds to the largest neutral axis depth calculated for the factored axial force and nominal moment strength consistent with the design displacement u.

R21.9.6.2 Displacement-Based Approach

The neutral axis depth c is the depth calculated corresponding to development of nominal flexural strength of the wall when displaced by u. The axial load is the factored axial load that is consistent with the design load combination that produces the displacement u.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 19

Page 20: S12 Detailing of Shear Walls

P

M

Pu

MnMu

1.2D + 0.5L + 0.2S + 1.0E Pu

0.9D + 1.0E

c corresponds to this point

R21.9.6.2 Displacement-Based Approach

21.9.6.2 (8.3.6.6(b))Displacement-Based Approach

When special boundary elements are required by the displacement-based approach, the special boundary element reinforcement needs to extend vertically above critical section a distance at least the larger of

• lw• Mu/4Vu

The same extension of the reinforcement is required below the critical section, except at the base of the wall, which is addressed in 21.9.6.4(d) (8.3.6.6(d)(iv))

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 20

Page 21: S12 Detailing of Shear Walls

21.9.6.4 (8.3.6.6(d))Special Boundary Elements

When required, special boundary element reinforcement shall extend horizontally from the extreme compression fiber a distance not less than the larger of

•c – 0.1lw•c/2

21.9.6.4 (8.3.6.6(d))Special Boundary Elements

In flanged sections, the boundary element shall include the effective flange width in compression and shall extend at least 300 mm. into the web

300 mm.

Effective flange width

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 21

Page 22: S12 Detailing of Shear Walls

21.9.6.4 (8.3.6.6(d)) Special Boundary Elements

At the wall base, the special boundary element reinforcement needs to extend into the support by

• ld, determined per 21.9.2.3 (8.3.6.2(c)) for the largest longitudinal reinforcement

• 300 mm. for footing, mat foundation or pile cap

18.10.6.4Special Boundary Elements

Width of flexural compression zone b over the horizontal distance calculated by 18.10.6.4(a), including flange if present, shall be at least hu/16;

b hu /16

Neutral Axis

hu

hu = laterally unsupported height at extreme compressionfiber of wall or wall pier

PLAN ELEVATION

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 22

Page 23: S12 Detailing of Shear Walls

18.10.6.4Special Boundary Elements

For walls or wall piers where • hw/lw 2.0, and• Effectively continuous from the base of structure to top of wall, and

• designed to have a single critical section for flexure and axial loads, and

• c/lw 3/8width of the flexural compression zone b over the length calculated in 18.10.6.4(a) shall be greater than or equal to 300 mm.

18.10.6.4Special Boundary Elements

b 300 mmIf c/lw 3/8

Neutral Axis

Larger of c 0.1lwand c/2

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 23

Page 24: S12 Detailing of Shear Walls

R18.10.6.4 Special Boundary Elements

A value of c/lw 3/8 is used to define a wall critical section that is not tension-controlled according to 21.2.2. A minimum wall thickness of 300 mm is imposed to reduce the likelihood of lateral instability of the compression zone after spalling of cover concrete.

21.9.6.4 (8.3.6.6(d)) Special Boundary Elements Transverse Reinforcement

For boundary element transverse reinforcement requirements, 21.9.6.4(c) (8.3.6.6(d)(iii)) references:

21.6.4.2 (8.3.5.4(a)(iii)) – For configuration requirements (shape, arrangement, horizontal spacing, etc.).

21.6.4.3 (8.3.5.4(b)) – For maximum spacing along height of boundary element, with one exception.

21.6.4.4 (8.3.5.4(a)(i), (ii)) – For minimum amount of transverse reinforcement, with one exception.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 24

Page 25: S12 Detailing of Shear Walls

21.9.6.4 (8.3.6.6(d)) Special Boundary Elements Transverse Reinforcement

Configuration requirements:• Transverse reinforcement to comprise of single or overlapping spirals,

circular hoops, or rectilinear hoops with or without crossties.

• Bends of rectilinear hoops and crossties to engage peripheral longitudinal reinforcing bars and to provide lateral support to them.

• Consecutive crossties to be alternated end for end along the longitudinal reinforcement and around the perimeter of the cross section.

• Reinforcement is to be arranged such that the spacing hx of legs of hoops or cross ties (longitudinal bars) laterally supported by the corner of a crosstie or hoop leg around the perimeter of the column do not exceed 350 mm. and two-thirds of the boundary element thickness.

hx = Max. value of xi on all faces 350 mm and 2/3 of boundary element thickness

xi

xi

xi xi xi

6db 75 mm 6db extension

Alternate90 deg hooks

Provide additional trans. reinf. ifthickness > 100 mm

Configuration requirements:

…The limits on hx are intended to provide more uniform spacing ofhoops and crossties for thin walls.

Up to ACI 318-11: xi = c/c spacing of consecutive ties

ACI 318-14: xi = c/c spacing of consecutive supported bars

21.9.6.4 (8.3.6.6(d)) Special Boundary ElementsTransverse Reinforcement

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 25

Page 26: S12 Detailing of Shear Walls

21.9.6.4 (8.3.6.6) Special Boundary Elements Transverse Reinforcement

Spacing along the height of the boundary element:

Spacing shall not exceed the smallest of• One-third of the minimum member dimension

• 6 times the diameter of smallest longitudinal bar

• 100 mm. so = 100 + 150 mm. (8.3.5.4) 350 – hx

3

TransverseReinforcement

Applicable expressions

Ash/sbcfor rectilinear hoop

Greater of(a) and (b)

s

for spiral or circular hoopGreater of(c) and (d)

0.3 – 1 (a)f cfyt

21.9.6.4 (18.10.6.4) Special Boundary Elements Transverse Reinforcement

Minimum amount of transverse reinforcement:

Ag

Ach

0.09 (b)f cfyt

0.45 – 1 (c)f cfyt

0.12 (b)f cfyt

Ag

Ach

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 26

Page 27: S12 Detailing of Shear Walls

R21.9.6.4 Special Boundary Elements Transverse Reinforcement

Minimum amount of transverse reinforcement:

For wall special boundary elements having rectangular cross section, Ag and Ach in expressions (a) and (c) in Table 18.10.6.4(f) are defined as Ag = lbeb and Ach = bc1bc2, where dimensions are shown in Fig. R21.9.6.4. This considers that concrete spalling is likely to occur only on the exposed faces of the confined boundary element.

21.9.6.4 Special Boundary Elements Transverse Reinforcement

Fig. R21.9.6.4(a) - Development of wall horizontal reinforcement in confined boundary element.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 27

Page 28: S12 Detailing of Shear Walls

600( u/hw)

21.9.6.2 – Displacement-Based Approach 21.9.6.4 – Special Boundary Elements

Pu

VuMu

lw

hw

cN.A.

larger ofc – 0.1lwc/2

Special boundary elementsrequired when

larger oflw

Mu /4Vu

Special boundary element transverse reinforcement per 21.6.4.2 –21.6.4.4 with 2 exceptions

u

clw

600( u/hw)

8.3.6.6(b) – Displacement-Based Approach 8.3.6.6– Special Boundary Elements

Pu

VuMu

lw

hw

cN.A.

larger ofc – 0.1lwc/2

Special boundary elementsrequired when

larger oflw

Mu /4Vu

Special boundary element trans. reinf. per Sec 8.3.5.4, 8.3.5.4b(i)

u

clw

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 28

Page 29: S12 Detailing of Shear Walls

21.9.6.3 (8.3.6.6(c))Conventional Approach

Applicable to any wall section

Special boundary elements are required where the maximum extreme compressive stress > 0.2f c

Special boundary elements may be discontinued where the calculated compressive stress < 0.15f c

Stresses calculated based on factored forces using a linearly elastic model and gross section properties

21.9.6.3 (8.3.6.6 (c))Conventional Approach

Pu

hw

Vu

Special boundary elementsrequired when(Pu/Ag) + (Mulw/2Ig) > 0.2f c

Special boundary elements may bediscontinued where compressive stress < 0.15f c

Special boundary element transverse reinforcement

cN.A. larger of

c – 0.1lwc/2

lw

Mu

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 29

Page 30: S12 Detailing of Shear Walls

21.9.6.4 (8.3.6.6)Special Boundary Elements

Ash 0.09sbcf’c/fyt , 0.3sbc (Ag/Ach -1) f’c/fyt

s 6db

min. dim./3

so

reinf. ratio 0.0025s 18”

6db, 75 mm min.

6db, 75 mm min.

6db

21.9.6.4 (8.3.6.6)Special Boundary Elements

21.9.6.4(e) [8.3.6.6(d)(v)]

150mm.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 30

Page 31: S12 Detailing of Shear Walls

21.9.6.4 (18.10.6.4)Special Boundary Elements

21.9.6.4(e) [ 8.3.6.6(d)(v)]

150mm.

21.9.6.5 (8.3.6.6(e))“Non-Special” Boundary Elements

Reinforcement details where special boundary elements are not required

If longitudinal reinforcement ratio at wall boundary > 2.8/fy, provide boundary transverse reinforcement

• That meets the geometric requirements within a cross-section per 21.6.4.2 [8.3.5.4(a)(iii), 8.3.5.4(c)], and

• That extends horizontally from the extreme compression fiber per 21.9.6.4(a) [8.3.6.6(d)(i)], and

Continued….

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 31

Page 32: S12 Detailing of Shear Walls

21.9.6.5 (8.3.6.6(e))“Non-Special” Boundary Elements

Reinforcement details where special boundary elements are not requiredIf longitudinal reinforcement ratio at wall boundary > 2.8/fy, provide boundary transverse reinforcement

• Where the maximum longitudinal spacing does not exceed (the lesser of) 200 mm (and 8db) (the lesser of 150 mm and 6db over the greater of lw and Mu/4Vu above the base).

21.9.6.5 (18.10.6.5)“Non-Special” Boundary Elements

x

x

a

bw

Acb = bw(2x + a)

bw

sb

Acb = sbbw

Asb = area of long. reinf. in Acb

= Asb/Acb > 2.8/fy

Ash @ s 200 mm and 8db (or 150 mm and 6db)

350 mm

Ash to be provided over a length of c – 0.1lw or c/2

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 32

Page 33: S12 Detailing of Shear Walls

21.9.6.5 (18.10.6.5)“Non-Special” Boundary Elements

When Vu Acv f c

• Horizontal reinforcement terminating at ends of wall shall have a standard hook engaging the edge reinforcement, or

• Edge reinforcement shall be enclosed in U-stirrups having the same size and spacing as, and spliced to, the horizontal reinforcement

R18.10.6.5“Non-Special” Boundary Elements

Fig. R18.10.6.4.2 - Summary of boundary element requirements for special walls.

(a) Wall with hw/lw 2.0 and a single critical section controlled by flexure and axial load designed using 18.10.6.2, and 18.10.6.4, and 18.10.6.5

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 33

Page 34: S12 Detailing of Shear Walls

R18.10.6.5 “Non-Special” Boundary Elements

Fig. R18.10.6.4.2 - Summary of boundary element requirements for special walls.

(b) Wall and wall pier designed using 18.10.6.3, 18.10.6.4, and 18.10.6.5

2.8

2.8

2.8

21.9.2.3(d) [8.3.6.2(c)]Reinforcement in Structural Walls

Mechanical and welded splices of longitudinal reinforcement of boundary elements shall conform to 21.1.6 and 21.1.7 (8.2), respectively

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 34

Page 35: S12 Detailing of Shear Walls

COUPLING BEAMS

High Seismic Risk – Coupling Beams (21.9.7) (8.3.6.7)

Aspect ratio ln/h 4• Satisfy requirements of 21.5 (8.3.7)

Aspect ratio ln/h 4• Permitted to be reinforced with two intersecting groups

of diagonal barsAspect ratio ln/h 2 and Vu > 0.33 f cAcw

• Must be reinforced with two intersecting groups of diagonal bars

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 35

Page 36: S12 Detailing of Shear Walls

(21.9.7) (8.3.6.7) Coupling Beams (ln /h < 4)

lnBars to be developedfor tension (typ.)

Avd = total area of bars in thegroup of bars forming onediagonal (min. 4 bars)

bw

Min. per 11.7.4.2[6.4.6.5]

Trans. reinf. per21.6.4.2, 21.6.4.4 (typ.)8.3.5.4

Min. per 11.7.4.1[6.4.6.4]

bw/2

bw/5

(21.9.7) (8.3.6.7) Coupling Beams

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 36

Page 37: S12 Detailing of Shear Walls

(21.9.7) (8.3.6.7) Coupling Beams

Source: http://nees.seas.ucla.edu/pankow

Source: http://nees.seas.ucla.edu/pankow

(21.9.7) (8.3.6.7) Coupling Beams

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 37

Page 38: S12 Detailing of Shear Walls

Source: http://nees.seas.ucla.edu/pankow

(21.9.7) (8.3.6.7) Coupling Beams

Source: http://nees.seas.ucla.edu/pankow

ACI 318-05Must have diagonal bars enclosed in transverse reinforcement

Coupling Beams

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 38

Page 39: S12 Detailing of Shear Walls

Source: http://nees.seas.ucla.edu/pankow

ACI 318-08, 318-11, 318-14Must either have diagonal bars enclosed in transverse reinforcement, orMust have entire beam cross-section enclosed in transverse reinforcement

Coupling Beams

Source: http://nees.seas.ucla.edu/pankow

ACI 318-05 Detail

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 39

Page 40: S12 Detailing of Shear Walls

Source: http://nees.seas.ucla.edu/pankow

ACI 318-08, -11, -14 Alternate Detail

21.9.8 (8.3.6.8) – Wall Piers

Door and window openings in shear walls often lead to narrow vertical wall segments, many of which have been defined as wall piers in the IBC and in the UBC before it. Wall pier provisions are now included in Section 21.9.8 of ACI 318-11 (8.3.6.8). The dimensions defining wall piers are given in Section 2.2.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 40

Page 41: S12 Detailing of Shear Walls

2.2 – Wall Piers

2.5 lwp/h 6.0hwp/lwp 2.0

hwplwp

h

21.9.8 (8.3.6.8) – Wall Piers

Shear failures of wall piers have been observed in previous earthquakes. The intent of Section 21.9.8 (8.3.6.8) is to prescribe detailing that would result in flexural failure preceding shear failure in wall piers. The provisions apply to wall piers considered part of the seismic force-resisting system (SFRS). Wall piers considered not part of the SFRS need to be designed by Section 21.13 (8.3.12).

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 41

Page 42: S12 Detailing of Shear Walls

21.9.8 (8.3.6.8) – Wall Piers

Wall piers having (lw/bw) 2.5 behave essentially as columns. Section 21.9.8.1 (8.3.6.8(a)) requires them to be detailed like columns. Alternative requirements are provided for wall piers having (lw/bw) > 2.5.

21.9.8 (8.3.6.8) – Wall Piers

Table R21.9.1 – Governing Design Provisions for Vertical Wall Segments

Clear height of verticalwall segment/length ofvertical wall segment

(hw /lw)

Length of vertical wall segment/wall thickness(lw /bw)

(lw /bw) 2.5 2.5 < (lw /bw) 6.0 (lw /bw) > 6.0

hw /lw< 2.0 Wall Wall Wall

hw /lw 2.0

Wall pier required tosatisfy specifiedcolumn design

requirements, see21.9.8.1 (18.10.8.1)

Wall pier required tosatisfy specifiedcolumn designrequirements or

alternativerequirements, see21.9.8.1 (18.10.8.1)

Wall

*hw is the clear height, lw is the horizontal length, and bw is the width of the web of the wall segment.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 42

Page 43: S12 Detailing of Shear Walls

21.9.8 (8.3.6.8) – Wall Piers

Wall piers at the edge of a wall are addressed in Section 21.9.8.2 (8.3.6.8(b)). Under in-plane shear, inclined cracks can propagate into segments of the wall directly above and below the wall pier. Shear failure within the adjacent wall segments can occur unless sufficient reinforcement is provided in those segments (Figure R21.9.8).

21.9.8 (8.3.6.8) – Wall Piers

Fig. R21.9.8 – Required horizontal reinforcement in wall segments above and below wall piers at the edge of a wall.

S. K. Ghosh Associates LLC International Code Council (ICC)

www.skghoshassociates.com 43

Page 44: S12 Detailing of Shear Walls

Questions?Thank you