li-wen yip breakout session 4.4 v2

14
How we assess new PV connections Li-Wen Yip

Upload: li-wen-yip

Post on 13-Apr-2017

65 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Li-Wen Yip Breakout Session 4.4 v2

How we assess new PV connectionsLi-Wen Yip

Page 2: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Context

2008 2009 2010 2011 2012 2013 2014 20150

50

100

150

200

250

300

350

UKPN G83 PV Connections

SPNLPNEPN

Year

Cum

ulati

ve M

W C

onne

cted

Page 3: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Improving how we assess new PV connections

Research(LV network monitoring)

Design assumptions

(derating, diversity, min load, no-load volts, harmonics)

Voltage rise assessment tools

(simple spreadsheet vs spreadsheet tool)

Records of existing generation(G83, FiT registers)

Page 4: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

LV network monitoring

Source: “Validation of Photovoltaic (PV) Connection Assessment Tool – Closedown Report” bit.ly/ukpn-pvtool-cdr

Generation CT

Data Logger(1min intervals)

Net Export CT

PV Inverter

Research

Page 5: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Derating: efficiency / insolation

Source: “Validation of Photovoltaic (PV) Connection Assessment Tool – Closedown Report” bit.ly/ukpn-pvtool-cdr

Design Assumptions

Worst case for thermal constraints

Worst case for voltage constraints

SpikeSpike

Page 6: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Diversity: panel orientation

Source: “Validation of Photovoltaic (PV) Connection Assessment Tool – Closedown Report” bit.ly/ukpn-pvtool-cdr

4kW panels and inverter

4kW panels / 3.5kW inverter(flat 6 hour peak)

Design Assumptions

Page 7: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Diversity: panel orientation

Source: “Validation of Photovoltaic (PV) Connection Assessment Tool – Closedown Report” bit.ly/ukpn-pvtool-cdr

Design Assumptions

No diversity despite varying

panel orientations

Page 8: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Derating: on-site consumption

Source: “Residential consumer responsiveness to time-varying pricing: Low Carbon London Learning Lab Report A3”,

Figure 5.29, http://bit.ly/1Lhllf0

Design Assumptions

Minimum load200W

Page 9: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Other Assumptions

Source: “Residential consumer responsiveness to time-varying pricing: Low Carbon London Learning Lab Report A3”,

Figure 5.29, http://bit.ly/1Lhllf0

Design Assumptions

Condition Assumption if unknown

No-load voltage 248V

Unbalance – Urban 1.43 : 1 : 1

Unbalance – Rural 2 : 1 : 1

Harmonics Ignored

Page 10: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Simple Spreadsheet

𝐼= 𝑃√3𝑉

∆𝑉=𝐼𝑍

Voltage rise assessment tools

Page 11: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Spreadsheet Tool – Live DemoVoltage rise assessment tools

EDP 08-0160 Distributed Generation Voltag

Page 12: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

FiT vs G83 Registers: ≤4kW

Sources: FiT Installation Register Aug 2015, UKPN G83 Register Oct 2015

Records of existing generation

Missing

Registered in Both

UKPN G83 Register

Ofgem FiT Register(UKPN MPANs)

0 50 100 150 200 250 300 350 400 450

163 MW

205 MW

225 MW

369 MW

Total capacity of ≤4kW installations (MW)

Only 41% have same rating (within 0.1kW)

Page 13: Li-Wen Yip Breakout Session 4.4 v2

2015 UK Power Networks. All rights reserved

Conclusions

Derating due to efficiency / insolation

For thermal constraints: possibly yesFor voltage constraints: possibly not

Diversity due to varying panel orientations

Potentially reduced or eliminated because of undersized inverters

Derating due to on-site consumption Allow 200W per customer

Voltage rise assessment tool Ask me for a demonstration / copy

Records of existing generation

G83 is incomplete and inaccurate.DNOs can request Ofgem’s FiT data with full MPANs.

Page 14: Li-Wen Yip Breakout Session 4.4 v2

Thank You

[email protected]/in/liwenyipLCNF T1 Closedown report: bit.ly/ukpn-pvtool-cdr