    ICON® Instrumentation Cable

    PLTC/ITC and TC Types

  • 8/20/2019 Icon en Instrumentation Cables

    2/76

    www.leoni-industrial-projects.com2

    The product program “Instrumentation Cable ICON®“ covers products

    which are based on the European standard EN 50288-7 and the US-

    American standards UL 13, UL 2250 and UL 1277. This product program

    gives extensive coverage to the requirements of the different Installation

    and Safety Regulations which are applied for measurement, control andmonitoring systems in industrial plants. As a result the user has a product

    program at his disposal for applications world wide.

    On the solid basis of many years of experience in international

    business (either project-oriented or geared to the site requirements

    of the customers), we have defined a very wide produc t range

    designed to meet all your field-driven product requirements.

    We have selected and elaborated a product program designed to

    cover all usual applications. The diversity of the environmental,

    electrical, mechanical, installation and safet y requirements produces

    a need for an extensive range of products.

    In this catalog you will find a product guide showing the complete

    UL instrumentation product range of LEONI Industrial Projects and

    data sheets of the most common types.

    The Quality Connection

    ■ Telecommunication cables

    ■ Data- and Bus cables (copper and fiber optic)

    ■ Mining cables

    ■ Cables for special applications

    ■  Instrumentation- and control cables

    ■ Thermocouple extension and compensating cables

    ■ Power cables (low and medium voltage)

    Product range

    Content Page

    Introduction   5

    Produc t Guide UL 13, UL 2250 and UL 1277 6

    Instrumentation Cable PLTC / ITC 300 V 6Instrumentation Cable TC 600 V 10

    DATASHEETS

    Instrumentation Cable 300 V 

    PVC jacket unshielded

    RE-YwYw-fl  

    Single-pair  22

    Single-triple  23

    PVC-jacket, shielded

    RE-Yw(St)Yw-fl

    Single- & multi-pair, collective shield 24

    Multi-pair, individual & collective shield (PiMF) 26

    Single- & multi-triple, collective shield 28

    Multi-triple, individual & collective shield (TiMF) 30

    Armor, PVC jacket

    RE-Yw(St)YwSWAYw-fl

    Single- & multi-pair, collective shield 32

    Multi-pair, individual & collective shield (PiMF) 34Single- & multi-triple, collective shield 36

    Multi-triple, individual & collective shield (TiMF) 38

  • 8/20/2019 Icon en Instrumentation Cables

    3/76

    www.leoni-industrial-projects.com 3

    AL-laminated jacket

    RE-Yw(St)Yw(L)Yw-fl

    Single- & multi-pair, collective shield 40

    Multi-pair, individual & collective shield (PiMF) 42

    Single- & multi-triple, collective shield 44Multi-triple, individual & collec tive shield (TiMF) 4 6

    AL-laminated jacket, armor, PVC-jacket

    RE-Yw(St)Yw(L)YwSWAYw-fl

    Single- & multi-pair, collective shield 48

    Multi-pair, individual & collective shield (PiMF) 50

    Single- & multi-triple, collective shield 52

    Multi-triple, individual & collective shield (TiMF) 54

    Instrumentation Cables 600 V

    PVC jacket, shielded

    RE-Yw(St)Yw-fl

    Single- & multi-pair, collective shield 56

    Multi-pair, individual & collective shield (PiMF) 58

    Single- & multi-triple, collective shield 60

    Multi-triple, individual & collective shield (TiMF) 62

    Instrumentation & Control Cables 300 V

    PVC jacket, shielded

    RE-Yw(St)Yw-flMulti-cores, collective shield, PVC jacket 64

    Armor, PVC jacket

    RE-Yw(St)YwSWAYw-fl

    Multi-cores, collective shield, armor, PVC jacket 66

     

    Instrumentation & Control Cables 600 V

    PVC jacket, shielded

    RE-Yw(St)Yw-fl

    Multi-cores, collective shield, PVC jacket 68

    Content

    LEONI Kerpen GmbH can not be held responsible in any form whatsover for any

    information provided by this publication. Printing errors excepted. Subject to altera-

    tions. Issue 20110208 - replaces issue 20081022

    General

    General units 71

    Conductors AWG and metric values by comparison 72

    Color codes 73

    Type designatio n 74

    Abbreviation code 75

  • 8/20/2019 Icon en Instrumentation Cables

    4/76

    www.leoni-industrial-projects.com4

    Please visit our website

    www.leoni-industrial-projects.com

    Table of Contents

    LEONI is one of the leading suppliers of standardized and

    customer-specific special cables and pre-assembled cable

    systems worldwide.

    The Business Unit Industrial Projects allows us to give our custom-

    ers access to the entire competence of a worldwide corporation,

    focused to meet the needs of industrial applications. We supply

    our products and solutions wherever everything depends on

    maximum reliability, quality and durability, such as in oil and gas

    extract ion and processing as well as in the petrochemical and

    energy production industries. LEONI products are to be found in

    many other applications such as the pulp and pap er, cement and

    pharmaceutical industries and in waste management, in which

    processes have to run in a controlled way via sensors and actua -

    tors.

    For us reliability doesn’t just mean keeping the right product avail-

    able for you as a standard produc t or developing a project solution

    for you – it also means supplying it precisely at the agreed time.

    Safety, availability and reliability are vital in industrial

    plant engineering and energy provision. This is b ecause these are

    fields in which unexpec ted breakdowns are very expensive and have

    critical effects on the environment.

    Companies are asking for solutions which are perfectly tailored to

    meet the application in question as well as the plant its elf. 70 %

    of the cables leaving our company are developed, manufactured

    and assembled according to customer specifications. We produce

    quantities depending on the requirements of the projects and sup-

    ply according to cable drumming schedules. We are also equipped

    to provide project quantities in a considerable two-digit million euro

    range. We take into account company-specific standards as well as

    all important industrial and environmental standards on the national

    and international level.

    LEONI

    Industrial Projects –

    your expert for a market that

    requires maximum reliability

  • 8/20/2019 Icon en Instrumentation Cables

    5/76

    www.leoni-industrial-projects.com 5Table of Contents

    The product range of

    instrumentation cables acc. to UL

    ICON®

    UL Program

    UL 13, UL 2250 and UL 1277

    Instrumentation, Control and Thermocouple extension cables according

    to above standards have to be applied in those systems, where “Installa-

    tion and Safety regulations“ are based on the “National Electrical Code“

    (NEC).

    The NEC Handbook is published by the “National Fire Protection

    Association“ a leading US standardization for safety, particularly for fire

    protection. As installation guide it is mandatory in the USA, however, it

    is also practiced in some other countries.

    Instrumentation, Control and Thermocouple extension cables

    will thereby meet the following standards and types:

    ■ e300 V “Power Limited Tray Cable” (PLTC) acc. to UL 13

    “Instrumentation Tray Cable”(ITC) acc. to UL 2250

    ■ 600 V “Tray Cable” (TC) acc. to UL 1277 ib

  • 8/20/2019 Icon en Instrumentation Cables

    6/76

    www.leoni-industrial-projects.com6 The Standard Types Instrumentation Cable

    Instrumentation Cable

    Common types

    armoredunarmored(L) shieldarmored(L) shield

    PLTC / ITC (UL 13 / UL 2250)

    300 V

    plain stranded copper conductors,pairs or triples,

    individual and/or overall static shield

    PVCw-insulation or XLPE-insulation

    PVCw-jacket

    ICON® Instrumentation Cable

    TC (UL 1277)

    600 V

    plain stranded copper conductors,pairs or triples,

    individual and/or overall static shield

    PVCwNC-insulation, PVCw-insulation or XLPE-insulation,

    PVCw-jacket

    unarmored

  • 8/20/2019 Icon en Instrumentation Cables

    7/76

    www.leoni-industrial-projects.com 7The Standard Types Instrumentation Cable

    Technical data

    Type of insulation/jacket PVCw/PVCw XLPE/PVCw

    Type of cabling elements Pair, Triple, PiMF, TiMF

    No. of cabling elements 1, 2, 4, 6, 8, 10, 12, 16, 24, 36

    Conductor sizes AWG 20/7, AWG 18/7, AWG 16/7, AWG 14/7

    1. Unarmored types RE-Yw(St)Yw-fl RE-2X(St)Yw-fl

    Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial  2)

    Bending radius 7.5 x cable diameter

    2. Armored types RE-Yw(St)YwSWAYw-fl RE-2X(St)YwSWAYw-fl

    Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial  2)

    Bending radius 10 x cable diameter

    3. (L) shielded type RE-Yw(St)Yw(L)Yw-fl RE-2X(St)Yw(L)Yw-fl

    Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial

    Bending radius 15 x cable diameter

    4. (L) shielded type, armored RE-Yw(St)Yw(L)YwSWAYw-fl RE-2X(St)Yw(L)YwSWAYw-fl

    Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial

    Bending radius 15 x cable diameter

    Reaction to fire

     Flame propagation

    a) Test on single cable

    b) Test on bunched cables

    UL 13 VW-1 test, IEC 60332-1

    UL 1685, IEC 60332-3 part 24 (Cat.C)

    Temperature range during operation

      during installat ion

     –40 °C up to 105 °C

     –5 °C up to 50 °C

     –40 °C up to 90 °C

     –5 °C up to 50 °C

    Sunlight resistance UL 1581 Section 1200

    Oil resistance ICEA S-72-532

    Application For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article

    725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC

    502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply

    1)  Color code of cabling elements see general. 2)

    if applicable.

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored

    ■ armored

    ■ (L) shielded

    ■ (L) shielded, armored

    300 V

  • 8/20/2019 Icon en Instrumentation Cables

    8/76

    www.leoni-industrial-projects.com8 The Standard Types Instrumentation Cable

    Construction

    Product types Unarmored types Armored types (L) shielded types L() shielded types, armored

    Conductor Plain annealed copper; 7 stranded according to UL 13

    size AWG

    Conductor design mm

    AWG 20/7

    7 x 0.320

    AWG 18/7

    7 x 0.404

    AWG 16/7

    7 x 0.490

    AWG 14/7

    7 x 0.620

    Insulation materialsCross linked polyethylene XLPE or

    Polyvinyl chloride heat resistant PVCw

    Cabling element 1) 

    without individual shield Pair, Triple

    with individual shield PiMF, TiMF

    Individual shield Aluminum/plastic-tape over solid tinned copper drain wire, plastic-tape under and above shield

    Wrapping at least one plastic tape above cable core

    Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire

    Inner jackets — PVCw, black

    L() shield — — Laminated aluminium tape

    Armoring —

    Galvanized steel wire armor;

    wire diameter depending on

    cable diameter under armoring,

    at least 0.9 mm

    Galvanized steel wire armor;

    wire diameter depending on

    cable diameter under armoring,

    at least 0.9 mm

    Outer jacket PVCw

    Color black or blue for intrinsically safe systems

    Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL TYPE OF SHIELD UL

    TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET

      1)  Color code of cabling elements see general. 2) if applicable.

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored

    ■ armored

    ■ (L) shielded

    ■ (L) shielded, armored

    300 V

  • 8/20/2019 Icon en Instrumentation Cables

    9/76

    www.leoni-industrial-projects.com 9The Standard Types Instrumentation Cable

    Electrical Data at 20 °C 300 V

    Conductor sizes nom. AWG AWG 20/7 AWG 18/7 AWG 16/7 AWG 14/7

    Conductor resistance max.   Ω/km 35.8 22.8 14.3 9.0

    Insulation resistance at 15.6 °C PVCw-insulation min. MΩxkm 30.5

      XLPE-insulation min. MΩxkm 30.5

    Inductance max. mH/km 1 (0.75 for (L) shielded types)

    Mutual capacitance

    PVCw-insulation Pair, Triple 1) 2)

      PiMF, TiMFmax. nF/km

    200

    200

    XLPE-insulation Pair, Triple 1) 2)

      PiMF, TiMFmax. nF/km

    125

    125

    Test voltage Core/core (Urms

    )

      Core/shield (Urms

    ) V

    1500

    1500

    Operating voltage (Urms

    ) max. V 300

    1)  Values for cables with 1 element correspond to those for PiMF and TiMF resp. 2)  Values for cables with >1 element -30 %.

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket■ unarmored

    ■ armored

    ■ (L) shielded

    ■ (L) shielded, armored

    300 V

  • 8/20/2019 Icon en Instrumentation Cables

    10/76

    www.leoni-industrial-projects.com10 The Standard Types Instrumentation Cable

    Instrumentation Cable

    Common types

    PLTC / ITC (UL 13 / UL 2250)

    300 V

    plain stranded copper conductors,

    pairs or triples,

    individual and/or overall static shield

    PVCw-insulation or XLPE-insulation

    PVCw-jacket

    ICON® Instrumentation Cable

    armored

    TC (UL 1277)

    600 V

    plain stranded copper conductors,

    pairs or triples,

    individual and/or overall static shield

    PVCwNC-insulation, PVCw-insulation or XLPE-insulation,

    PVCw-jacket

    unarmoredunarmored (L) shieldarmored(L) shield

  • 8/20/2019 Icon en Instrumentation Cables

    11/76

    www.leoni-industrial-projects.com 11The Standard Types Instrumentation Cable

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 V

    ICON® Instrumentation Cable according to UL 1277

    Common types

    Single & Multi pair and Single & Multi triple, indiv idual and/or overall shield, PVC-jacket

    ■ unarmored

    600 V

    Technical data

    Type of insulation/jacket PVCw/PVCw PVCwNC/PVCw XLPE/PVCw

    Type of cabling elements Pair, Triple, PiMF, TiMF

    No. of cabling elements 1, 2, 4, 6, 8, 10,12, 16, 24, 36

    Conductor sizes AWG 18/7, AWG 16/7, AWG 14/7

    1. Unarmored types RE-Yw(St)Yw-fl RE-Yw4Y(St)Yw-fl RE-2X(St)Yw-fl

    Laying Recommended for indoor and outdoor installation,

    on racks, trays, in conduits, in dry and wet locations,

    for direct burial

    Bending radius 7.5 x cable diameter 10 x cable diameter 7.5 x cable diameter

    Reaction to fire

     Flame propagation

    a) Test on single cable

    b) Test on bunched cables

    UL 13 VW-1 test, IEC 60332-1

    UL 1685, IEC 60332-3 part 24 (Cat.C)

    Temperature range during operation

      during installation

     –40 °C up to 90 °C

     –5 °C up to 50 °C

    Sunlight resistance UL 1581 Section 1200

    Oil resistance ICEA S-73-532

    Application For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance

    with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and

    NEC 502.10(B), not allowed for direct connection to l ow impedance sources, e.g. public mains electrici ty supply

  • 8/20/2019 Icon en Instrumentation Cables

    12/76

    www.leoni-industrial-projects.com12 The Standard Types Instrumentation Cable

    Construction

    Product types Unarmored types

    Conductor Plain annealed copper; 7 stranded

    size AWG

    Conductor design mm

    AWG 18/7

    7 x 0.404

    AWG 16/7

    7 x 0.490

    AWG 14/7

    7 x 0.620

    Insulation materials Polyvinylchloride PVC heat resistant PVCw or

    Polyvinylchloride PVC heat resistant PVCw with nylon coating NC or

    Cross linked polyethylene XLPE

    Cabling element 1) 

    without individual shield Pair, Triple

    with individual shield PiMF, TiMF

    Individual shield Aluminum/plastic-tape over stranded tinned copper drain wire, plastic-tape under and above shield

    Wrapping at least one plastic tape above cable core

    Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire

    Outer jacket PVCw

    Color black or blue for intrinsically safe systems

    Marking LEONI KERPEN ICON TC SIZE MATERIAL T YPE OF SHIELD UL RATED VOLTAGE

    TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET

    1)  Color code of cabling elements see general .

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 VICON® Instrumentation Cable according to UL 1277

    Common types

     Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    600 V

  • 8/20/2019 Icon en Instrumentation Cables

    13/76

    www.leoni-industrial-projects.com 13The Standard Types Instrumentation Cable

    Electrical Data at 20 °C 600 V

    Conductor sizes nom. AWG AWG 18/7 AWG 16/7 AWG 14/7

    Conductor resistance max.   Ω/km 22.8 14.3 9.0

    Insulation resistance at 15°C PVCw-insulation min. MΩxkm 175

      XLPE-insulation min. MΩxkm 810

    Inductance max. mH/km 0.7

    Mutual capacitance

    PVCw-insulation Pair, Triple 1) 2)

      PiMF, TiMFmax. nF/km

    170

    170

    XLPE-insulation Pair, Triple 1) 2)

      PiMF, TiMFmax. nF/km

    120

    120

    Test voltage Core/core (Urms

    )

      Core/shield (Urms

    ) V

    2000, PVCw insulation / 3000, XLPE insulation

    2000, PVCw insulation / 3000, XLPE insulation

    Operating voltage (Urms) max. V 600

    1)  Values for cables with 1 element correspond to those for PiMF and TiMF resp. 2)  Values for cables with > 1 element -30 %.

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 VICON® Instrumentation Cable according to UL 1277

    Common types

    Single & Multi pair and Single & Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    600 V

  • 8/20/2019 Icon en Instrumentation Cables

    14/76

    www.leoni-industrial-projects.com14 The Standard Types Instrumentation Cable

    Instrumentation Control Cable

    Common types

    ICON® Instrumentation Control Cable

    TC (UL 1277)

    600 V

    plain stranded copper conductors,

    cores,

    overall static shield

    PLTC / ITC (UL 13 / UL 2250)

    300 V

    plain stranded copper conductors,

    cores,

    overall static shield

    PVCw-insulation or XLPE-insulation

    PVCw-jacket

    armoredunarmored (L) shieldarmored(L) shield

    PVCwNC-insulation, PVCw-insulation,or XLPE-insulation,

    PVCw-jacket

    unarmored

  • 8/20/2019 Icon en Instrumentation Cables

    15/76

    www.leoni-industrial-projects.com 15The Standard Types Instrumentation Cable

    Technical data

    Type of insulation/jacket PVCw/PVCw XLPE/PVCw

    Type of cabling elements Cores

    No. of cabling elements 2, 4, 6, 8, 10, 12, 16, 24, 36

    Conductor sizes AWG 20/7, AWG 18/7, AWG 16/7, AWG 14/7

    1. Unarmored types RE-Yw(St)Yw-fl RE-2X(St)Yw-fl

    Laying Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct

    burial 2)

    Bending radius 7.5 x cable diameter

    2. Armored types RE-Yw(St)YwSWAYw-fl RE-2X(St)YwSWAYw-fl

    Laying Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct burial1)

    Bending radius 7.5 x cable diameter

    Reaction to fire

     Flame propagation

    a) Test on single cable

    b) Test on bunched cables

    UL 13 VW-1 test, IEC 60332-1

    UL 1685, IEC 60332-3 part 24 (Cat.C)

    Temperature range during operation

      during installat ion

     –40 °C up to 105 °C

     –5 °C up to 50 °C

     –40 °C up to 90 °C

     –5 °C up to 50 °C

    Sunlight resistance UL 1581 Section 1200

    Oil resistance ICEA S-72-532

    Application For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article

    725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC

    502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply

    1) if applicable

    ICON® Instrumentation Control Cable according to UL 13 / 2250

    Common types

    Multi core, overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 V

  • 8/20/2019 Icon en Instrumentation Cables

    16/76

    www.leoni-industrial-projects.com16 The Standard Types Instrumentation Cable

    Construction

    Product types Unarmored types Armored types

    Conductor Plain annealed copper; 7 stranded according to UL 13

    size AWG

    Conductor design mm

    AWG 20/7

    7 x 0.320

    AWG 18/7

    7 x 0.404

    AWG 16/7

    7 x 0.490

    AWG 14/7

    7 x 0.620

    Insulation materialsCross linked polyethylene XLPE or

    Polyvinyl chloride heat resistant PVCw

    Cabling element 1) 

    without individual shield Core

    Wrapping at least one plastic tape above cable core

    Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire

    Inner jacket — PVCw, black

    Armoring

    Galvanized steel wire a rmor; wire diameter depending on

    cable diameter under armoring, at least 0.9 mm

    Outer jacket PVCw

    Color black or blue for intrinsically safe systems

    Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL T YPE OF SHIELD UL

    TEMPERATURE RATING SUN RES DIR BUR 2) PRODUCTION LOT CODE LENGTH MARKING IN FEET

    1)  Color code of cabling elements see general . 2) if applicable

    ICON® Instrumentation Control Cable according to UL 13 / 2250

    Common types

    Multi core, overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 V

  • 8/20/2019 Icon en Instrumentation Cables

    17/76

    www.leoni-industrial-projects.com 17The Standard Types Instrumentation Cable

    Electrical Data at 20 °C 300 V

    Conductor sizes nom. AWG AWG 20/7 AWG 18/7 AWG 16/7 AWG 14/7

    Conductor resistance max.   Ω/km 35.8 22.8 14.3 9.0

    Insulation resistance at 15.6 °C PVCw-insulation min. MΩxkm 30.5

      XLPE-insulation min. MΩxkm 30.5

    Inductance max. mH/km 1

    Mutual capacitance

    PVCw-insulation CORE max. nF/km 200

    XLPE-insulation CORE max. nF/km 125

    Test voltage Core/core (Urms

    )

      Core/shield (Urms

    ) V

    1500

    1500

    Operating voltage (Urms

    ) max. V 300

    ICON® Instrumentation Control Cable according to UL 13 /2250

    Common types

    Multi core, overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 V300 V

  • 8/20/2019 Icon en Instrumentation Cables

    18/76

    www.leoni-industrial-projects.com18 The Standard Types Instrumentation Cable

    Instrumentation Control Cable to UL 1277

    Common types

    ICON® Instrumentation Control Cable

    TC (to UL 1277)

    600 V

    plain stranded copper conductors,

    cores,

    overall static shield

    PLTC / ITC (UL 13 / UL 2250)

    300 V

    plain stranded copper conductors,

    cores,

    overall static shield

    PVCw-insulation or, XLPE-insulation

    PVCw-jacket

    armoredunarmored (L) shieldarmored(L) shield

    PVCwNC-insulation, PVCw-insulation, XLPE-insulation,

    PVCw-jacket

    unarmored

  • 8/20/2019 Icon en Instrumentation Cables

    19/76

    www.leoni-industrial-projects.com 19The Standard Types Instrumentation Cable

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 VICON® Instrumentation Control Cable according to UL 1277

    Common types

    Multi Core, overall shield, PVC-jacket

    ■ unarmored

    600 V

    Technical data

    Type of insulation/jacket PVCw/PVCw PVCwNC/PVCw XLPE/PVCw

    Type of cabling elements Core

    No. of cabling elements 2, 4, 6, 8, 10, 12, 16, 24, 36

    Conductor sizes AWG 18/7, AWG 16/7, AWG 14/7

    1. Unarmored types RE-Yw(St)Yw-fl RE-Yw4Y(St)Yw-fl RE-2X(St)Yw-fl

    Laying Recommended for indoor and outdoor installation,

    on racks, trays, in conduits, in dry and wet locations,

    for direct burial

    Bending radius 7.5 x cable diameter 10 x cable diameter 7.5 x cable diameter

    Reaction to fire

    Flame propagation

    a) Test on single cable

    b) Test on bunched cables

    UL 13 VW-1 test, IEC 60332-1

    UL 1685, IEC 60332-3 part 24 (Cat.C)

    Temperature range during operation

      during installation

     –40 °C up to 90 °C

     –5 °C up to 50 °C

    Sunlight resistance UL 1581 Section 1200

    Oil resistance ICEA S-73-532

    Application For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance

    with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and

    NEC 502.10(B), not allowed for direct connection to l ow impedance sources, e.g. public mains electrici ty supply

  • 8/20/2019 Icon en Instrumentation Cables

    20/76

    www.leoni-industrial-projects.com20 The Standard Types Instrumentation Cable

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 VICON® Instrumentation Control Cable according to UL 1277

    Common types

    Multi core, overall shield, PVC-jacket

    ■ unarmored

    Construction

    Product types Unarmored types

    Conductor Plain annealed copper; 7 stranded

    size

    Conductor design mm

    AWG 18/7

    7 x 0.320

    AWG 16/7

    7 x 0.404

    AWG 14/7

    7 x 0.620

    Insulation materials Polyvinylchloride PVC heat resistant PVCw or

    Polyvinylchloride PVC heat resistant PVCw with nylon jacket NC or

    Cross linked polyethylene XLPE

    Cabling element 1)  Core

    Wrapping at least one plastic tape above cable core

    Overall shield Aluminum/plastic-tape over stranded tinned copper drain wire

    Outer jacket PVCw

    Color black or blue for intrinsically safe systems

    Marking LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL TYPE OF SHIELD UL RATED VOLTAGE

    TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET

    1)  Color code of cabling elements see page 71 .

    600 V

  • 8/20/2019 Icon en Instrumentation Cables

    21/76

    www.leoni-industrial-projects.com 21The Standard Types Instrumentation Cable

    ICON® Instrumentation Cable according to UL 13 / 2250

    Common types

    Single & Multi pair and Multi triple, individual and/or overall shield, PVC-jacket

    ■ unarmored

    ■ armored

    300 V

    ICON® Instrumentation Control Cable according to UL 1277

    Common types

    Multi core, overall shield, PVC-jacket

    ■ unarmored

    600 V

    Electrical Data at 20 °C 600 V

    Conductor sizes nom. mm² AWG 18/7 AWG 16/7 AWG 14/7

    Conductor resistance max.   Ω/km 35.8 22.8 14.3

    Insulation resistance at 15 °C PVCw-insulation min. MΩxkm 175

      XLPE-insulation min. MΩxkm 810

    Inductance max. mH/km 1

    Mutual capacitance

    PVCw-insulation Core max. nF/km 187

    XLPE-insulation Core max. nF/km 120

    Test voltage Core/core (Urms

    )

      Core/shield (Urms

    ) V

    2000, PVCw insulation / 3000, XLPE insulation

    2000, PVCw insulation / 3000, XLPE insulation

    Operating voltage (Urms

    ) max. V 600

    600 V

  • 8/20/2019 Icon en Instrumentation Cables

    22/76

    www.leoni-industrial-projects.com22 The Standard Types Instrumentation Cable

    Instrumentation Cable   UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single-Pair, PVC-Insulation, PVC Jacket

     

    RE-YwYw-flApplication

    Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC

    501.10(B) and NEC 502.10(B).

    Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 °C SUN

    RES PRODUCTION LOT CODE LENGTH MARKING IN FEET

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)

    Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

     

    Geometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 14 /7

    1 0.51 / 20 1.02 / 40 8.0 / 0.32 88 / 60 79030013

    AWG 16 /7

    1 0.38 / 15 0.89 / 35 6.5 / 0.26 66 / 50 79030012

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.0 / 0.24 55 / 40 79030011

    AWG 20 /7

    1 0.30 / 12 0.89 / 35 5.2 / 0.20 40 / 30 79030010

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    23/76

    www.leoni-industrial-projects.com 23The Standard Types Instrumentation Cable

    Instrumentation Cable   UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single-Triple, PVC-Insulation, PVC Jacket

     

    RE-YwYw-flApplication

    Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC

    501.10(B) and NEC 502.10(B).

    Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 °C SUN

    RES PRODUCTION LOT CODE LENGTH MARKING IN FEET

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)

    Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance

    single element:

    2 to 4 elements:

    above 4 elements:

    nom. nF/km /

    nF/1000ft

     

    187 / 57

     

    187 / 57

     

    187 / 57

     

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

     

    Geometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 16 /7

    1 0.38 / 15 0.89 / 35 6.8 / 0.27 80 / 55 79030016

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.3 / 0.25 65 / 45 79030015

    AWG 20 /7

    1 0.30 / 12 0.89 / 35 5.4 / 0.21 45 / 35 79030014

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    24/76

    www.leoni-industrial-projects.com24 The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Pair, PVC-Insulation, Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-flApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireCommunication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/

    PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET*) single element design without com wire

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)-5°C up to +50°C(during installation)

    Min. bending radius - repeated

    bending

    7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    (St)collective shield

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance

    single element:

    2 to 4 elements:

    above 4 elements:

    nom. nF/km /

    nF/1000ft

     

    200 / 61

    190 / 58

    150 / 46

     

    200 / 61

    190 / 58

    150 / 46

     

    200 / 61

    180 / 55

    150 / 46

     

    200 / 61

    180 / 55

    150 / 46

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

  • 8/20/2019 Icon en Instrumentation Cables

    25/76

    www.leoni-industrial-projects.com 25The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Pair, PVC-Insulation, Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-flGeometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 14 /7

    1 0.51 / 20 1.02 / 40 8.2 / 0.32 109 / 75 79960628

    2 0.51 / 20 1.27 / 50 12.6 / 0.50 207 / 140 79960629

    4 0.51 / 20 1.27 / 50 14.6 / 0.57 318 / 215 79960630

    6 0.51 / 20 1.52 / 60 18.0 / 0.71 492 / 325 79960631

    8 0.51 / 20 1.52 / 60 19.1 / 0.75 578 / 390 79960632

    10 0.51 / 20 1.52 / 60 21.7 / 0.85 705 / 475 79960633

    12 0.51 / 20 1.78 / 70 23.3 / 0.92 851 / 575 79960634

    16 0.51 / 20 1.78 / 70 26.4 / 1.04 1095 / 740 79960635

    24 0.51 / 20 1.78 / 70 31.4 / 1.24 1548 / 1040 79960636

    36 0.51 / 20 2.03 / 80 38.6 / 1.52 2299 / 1545 79960637

    AWG 16 /7

    1 0.38 / 15 0.89 / 35 6.7 / 0.26 69 / 55 79960000

    2 0.38 / 15 1.27 / 50 10.8 / 0.43 146 / 95 79960001

    4 0.38 / 15 1.27 / 50 12.5 / 0.50 217 / 145 79960002

    6 0.38 / 15 1.27 / 50 14.8 / 0.58 297 / 195 79960254

    8 0.38 / 15 1.52 / 60 16.1 / 0.64 384 / 260 79960003

    10 0.38 / 15 1.52 / 60 18.2 / 0.72 460 / 310 79960255

    12 0.38 / 15 1.52 / 60 18.8 / 0.74 533 / 355 79960004

    16 0.38 / 15 1.52 / 60 21.1 / 0.83 680 / 455 79960005

    24 0.38 / 15 1.78 / 70 25.4 / 1.01 1002 / 670 79960006

    36 0.38 / 15 1.78 / 70 30.3 / 1.20 1433 / 955 79960007

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.2 / 0.24 54 / 45 79960008

    2 0.38 / 15 1.02 / 40 9.3 / 0.37 105 / 75 79960009

    4 0.38 / 15 1.27 / 50 11.4 / 0.45 171 / 115 79960010

    6 0.38 / 15 1.27 / 50 13.5 / 0.53 230 / 155 79960252

    8 0.38 / 15 1.27 / 50 14.1 / 0.56 280 / 185 79960011

    10 0.38 / 15 1.52 / 60 16.5 / 0.65 350 / 240 79960253

    12 0.38 / 15 1.52 / 60 17.0 / 0.67 409 / 275 79960012

    16 0.38 / 15 1.52 / 60 19.0 / 0.75 518 / 350 7996001324 0.38 / 15 1.78 / 70 23.1 / 0.91 776 / 505 79960014

    36 0.38 / 15 1.78 / 70 28.6 / 1.07 1086 / 720 79960015

     

    AWG 20 /7

    1 0.30 / 12 0.89 / 35 5.3 / 0.21 39 / 35 79960016

    2 0.30 / 12 1.02 / 40 8.0 / 0.31 76 / 55 79960017

    4 0.30 / 12 1.02 / 40 8.8 / 0.36 109 / 75 79960018

    6 0.30 / 12 1.27 / 50 11.3 / 0.44 160 / 110 79960250

    8 0.30 / 12 1.27 / 50 11.8 / 0.47 194 / 130 79960019

    10 0.30 / 12 1.27 / 50 13.3 / 0.52 225 / 155 79960251

    12 0.30 / 12 1.27 / 50 13.7 / 0.54 263 / 175 79960020

    16 0.30 / 12 1.52 / 60 15.8 / 0.63 355 / 240 79960021

    24 0.30 / 12 1.52 / 60 18.6 / 0.73 488 / 325 79960022

    36 0.30 / 12 1.52 / 60 21.8 / 0.86 693 / 460 79960023

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    26/76

    www.leoni-industrial-projects.com26 The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Pair, PVC-Insulation, Individual & Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-fl PiMFApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC

    SPOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending

    7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    PiMF pair in metal foil

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance nom. nF/km /

    nF/1000ft

    200 / 61 200 / 61 200 / 61 200 / 61

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

  • 8/20/2019 Icon en Instrumentation Cables

    27/76

    www.leoni-industrial-projects.com 27The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Pair, PVC-Insulation, Individual & Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-fl PiMFGeometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 14 /7

    2 0.51 / 20 1.27 / 50 13.9 / 0.55 238 / 160 79960638

    4 0.51 / 20 1.52 / 60 16.7 / 0.66 387 / 260 79960639

    6 0.51 / 20 1.52 / 60 20.0 / 0.79 552 / 375 79960640

    8 0.51 / 20 1.52 / 60 21.3 / 0.84 687 / 465 79960641

    10 0.51 / 20 1.78 / 70 24.7 / 0.97 857 / 580 79960642

    12 0.51 / 20 1.78 / 70 26.4 / 1.04 987 / 665 79960643

    16 0.51 / 20 1.78 / 70 29.7 / 1.17 1271 / 855 79960644

    24 0.51 / 20 2.03 / 80 36.0 / 1.42 1871 / 1285 79960645

    36 0.51 / 20 2.29 / 90 43.4 / 1.71 2911 / 1960 79960646

    AWG 16 /7

    2 0.38 / 15 1.27 / 50 12.1 / 0.48 170 / 115 79960024

    4 0.38 / 15 1.27 / 50 14.2 / 0.56 259 / 170 79960025

    6 0.38 / 15 1.52 / 60 17.3 / 0.69 388 / 255 79960260

    8 0.38 / 15 1.52 / 60 18.4 / 0.72 470 / 310 79960026

    10 0.38 / 15 1.52 / 60 20.8 / 0.82 570 / 370 79960261

    12 0.38 / 15 1.52 / 60 21.6 / 0.85 641 / 420 79960027

    16 0.38 / 15 1.78 / 70 24.8 / 0.98 861 / 565 79960028

    24 0.38 / 15 1.78 / 70 29.4 / 1.16 1208 / 800 79960029

    36 0.38 / 15 2.03 / 80 35.4 / 1.40 1792 / 1175 79960030

    AWG 18 /7

    2 0.38 / 15 1.27 / 50 11.4 / 0.44 144 / 100 79960031

    4 0.38 / 15 1.27 / 50 13.1 / 0.52 210 / 145 79960032

    6 0.38 / 15 1.52 / 60 16.0 / 0.63 305 / 205 79960258

    8 0.38 / 15 1.52 / 60 17.0 / 0.67 381 / 250 79960033

    10 0.38 / 15 1.52 / 60 19.1 / 0.75 450 / 305 79960259

    12 0.38 / 15 1.52 / 60 19.8 / 0.78 514 / 340 79960034

    16 0.38 / 15 1.78 / 70 22.7 / 0.90 687 / 455 79960035

    24 0.38 / 15 1.78 / 70 26.9 / 1.06 968 / 640 79960036

    36 0.38 / 15 2.03 / 80 32.4 / 1.28 1411 / 935 79960037

    AWG 20 /72 0.30 / 12 1.02 / 40 8.9 / 0.36 94 / 65 79960038

    4 0.30 / 12 1.27 / 50 11.2 / 0.44 152 / 345 79960039

    6 0.30 / 12 1.27 / 50 13.1 / 0.52 209 / 135 79960256

    8 0.30 / 12 1.27 / 50 13.7 / 0.54 253 / 165 79960040

    10 0.30 / 12 1.52 / 60 16.0 / 0.63 310 / 210 79960257

    12 0.30 / 12 1.52 / 60 16.6 / 0.65 357 / 240 79960041

    16 0.30 / 12 1.52 / 60 18.5 / 0.73 455 / 300 79960042

    24 0.30 / 12 1.52 / 60 21.8 / 0.86 662 / 415 79960043

    36 0.30 / 12 1.78 / 70 26.4 / 1.04 936 / 615 79960044

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    28/76

    www.leoni-industrial-projects.com28 The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Triple, PVC-Insulation, Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-flApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireCommunication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/

    PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET*) single element design without com wire

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending

    7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance

    single element:

    2 to 4 elements:

    above 4 elements:

    nom. nF/km /

    nF/1000ft

     

    200 / 61

    190 / 58

    150 / 46

     

    200 / 61

    190 / 58

    150 / 46

     

    200 / 61

    180 / 55

    150 / 46

     

    200 / 61

    180 / 55

    150 / 46

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

  • 8/20/2019 Icon en Instrumentation Cables

    29/76

    www.leoni-industrial-projects.com 29The Standard Types Instrumentation Cable

     

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Triple, PVC-Insulation, Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-flGeometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 14 /7

    1 0.51 / 20 1.02 / 40 8.6 / 0.35 134 / 90 79960647

    2 0.51 / 20 1.27 / 50 14.0 / 0.55 275 / 185 79960648

    4 0.51 / 20 1.52 / 60 16.5 / 0.65 454 / 305 79960649

    6 0.51 / 20 1.52 / 60 21.2 / 0.84 663 / 450 79960650

    8 0.51 / 20 1.78 / 70 23.2 / 0.91 848 / 570 79960651

    10 0.51 / 20 1.78 / 70 24.1 / 0.95 1010 / 680 79960652

    12 0.51 / 20 1.78 / 70 26.8 / 1.05 1191 / 805 7996065316 0.51 / 20 1.78 / 70 30.2 / 1.19 1546 / 1040 79960654

    24 0.51 / 20 2.03 / 80 36.5 / 1.44 2274 / 1530 79960655

    36 0.51 / 20 2.29 / 90 44.0 / 1.73 3349 / 2250 79960656

    AWG 16 /7

    1 0.38 / 15 1.02 / 40 7.2 / 0.28 90 / 65 79960045

    2 0.38 / 15 1.27 / 50 11.9 / 0.47 180 / 125 79960046

    4 0.38 / 15 1.27 / 50 13.7 / 0.54 288 / 195 79960047

    6 0.38 / 15 1.52 / 60 17.3 / 0.68 420 / 285 79960266

    8 0.38 / 15 1.52 / 60 18.4 / 0.72 525 / 355 79960048

    10 0.38 / 15 1.52 / 60 20.6 / 0.81 647 / 430 79960267

    12 0.38 / 15 1.52 / 60 21.2 / 0.83 749 / 495 79960049

    16 0.38 / 15 1.78 / 70 24.3 / 0.96 995 / 660 79960050

    24 0.38 / 15 1.78 / 70 28.9 / 1.14 1400 / 945 79960051

    36 0.38 / 15 2.03 / 80 34.9 / 1.37 2060 / 1385 79960052

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.5 / 0.26 66 / 50 79960053

    2 0.38 / 15 1.27 / 50 10.8 / 0.43 170 / 115 79960054

    4 0.38 / 15 1.27 / 50 12.4 / 0.49 223 / 150 79960055

    6 0.38 / 15 1.27 / 50 15.2 / 0.60 315 / 215 79960264

    8 0.38 / 15 1.52 / 60 16.7 / 0.66 413 / 270 79960056

    10 0.38 / 15 1.52 / 60 18.6 / 0.74 492 / 330 79960265

    12 0.38 / 15 1.52 / 60 19.2 / 0.76 564 / 380 79960057

    16 0.38 / 15 1.52 / 60 21.5 / 0.85 722 / 485 7996005824 0.38 / 15 1.78 / 70 26.1 / 1.03 1055 / 710 79960059

    36 0.38 / 15 1.78 / 70 30.8 / 1.22 1518 / 1015 79960060

  • 8/20/2019 Icon en Instrumentation Cables

    30/76

    www.leoni-industrial-projects.com30 The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Triple, PVC-Insulation, Individual & Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-fl TiMFApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC

    STOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET

    Technical data Abbreviations

    Flame propagation

    - Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range

    -40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending

    7.5 x cable diameter 

    RE- Instrumentation Cable

    Yw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    TiMF triple in metal foil

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92

    Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance nom. nF/km /

    nF/1000ft

    200 / 61 200 / 61 200 / 61 200 / 61

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

  • 8/20/2019 Icon en Instrumentation Cables

    31/76

    www.leoni-industrial-projects.com 31The Standard Types Instrumentation Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Triple, PVC-Insulation, Individual & Collective Shield, PVC Jacket

     

    RE-Yw(St)Yw-fl TiMFGeometrical data

    No. of elements RT of insulation RT outer jacket Outer dia. Weight Part number  

    nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (kg/km / lbs/1000ft) black

    AWG 14 /7

    2 0.51 / 20 1.52 / 60 16.5 / 0.65 324 / 220 79960657

    4 0.51 / 20 1.52 / 60 18.9 / 0.75 513 / 345 79960658

    6 0.51 / 20 1.78 / 70 24.0 / 0.94 773 / 520 79960659

    8 0.51 / 20 1.78 / 70 25.0 / 0.98 959 / 645 79960660

    10 0.51 / 20 1.78 / 70 28.2 / 1.11 1162 / 785 79960661

    12 0.51 / 20 1.78 / 70 29.2 / 1.15 1327 / 895 79960662

    16 0.51 / 20 2.03 / 80 33.6 / 1.32 1766 / 1190 79960663

    24 0.51 / 20 2.03 / 80 40.1 / 1.58 2550 / 1715 79960664

    36 0.51 / 20 2.29 / 90 48.7 / 1.96 3756 / 2525 79960665

    AWG 16 /7

    2 0.38 / 15 1.27 / 50 13.3 / 0.52 215 / 145 79960069

    4 0.38 / 15 1.52 / 60 15.9 / 0.63 350 / 230 79960070

    6 0.38 / 15 1.52 / 60 19.6 / 0.77 490 / 330 79960272

    8 0.38 / 15 1.52 / 60 20.9 / 0.82 610 / 410 79960071

    10 0.38 / 15 1.78 / 70 24.1 / 0.95 791 / 520 79960273

    12 0.38 / 15 1.78 / 70 24.7 / 0.97 891 / 585 79960072

    16 0.38 / 15 1.78 / 70 27.7 / 1.09 1145 / 755 79960073

    24 0.38 / 15 2.03 / 80 33.5 / 1.32 1650 / 1110 79960074

    36 0.38 / 15 2.03 / 80 39.8 / 1.57 2365 / 1590 79960075

    AWG 18 /7

    2 0.38 / 15 1.27 / 50 12.3 / 0.48 172 / 115 79960076

    4 0.38 / 15 1.27 / 50 14.2 / 0.56 260 / 175 79960077

    6 0.38 / 15 1.52 / 60 18.0 / 0.71 395 / 270 79960270

    8 0.38 / 15 1.52 / 60 19.1 / 0.75 491 / 325 79960078

    10 0.38 / 15 1.52 / 60 21.5 / 0.85 585 / 395 79960271

    12 0.38 / 15 1.78 / 70 22.7 / 0.89 702 / 465 79960079

    16 0.38 / 15 1.78 / 70 25.3 / 1.00 898 / 595 79960080

    24 0.38 / 15 1.78 / 70 30.1 / 1.19 1268 / 845 79960081

    36 0.38 / 15 2.03 / 80 36.3 / 1.43 1840 / 1240 79960082

    AWG 20 /72 0.30 / 12 1.27 / 50 10.4 / 0.41 120 / 85 79960083

    4 0.30 / 12 1.27 / 50 12.0 / 0.47 180 / 125 79960084

    6 0.30 / 12 1.27 / 50 14.6 / 0.57 250 / 170 79960268

    8 0.30 / 12 1.52 / 60 16.1 / 0.63 335 / 230 79960085

    10 0.30 / 12 1.52 / 60 17.9 / 0.70 400 / 270 79960269

    12 0.30 / 12 1.52 / 60 18.4 / 0.72 450 / 305 79960086

    16 0.30 / 12 1.52 / 60 20.6 / 0.81 628 / 385 79960087

    24 0.30 / 12 1.78 / 70 25.0 / 0.98 835 / 565 79960088

    36 0.30 / 12 1.78 / 70 29.6 / 1.17 1190 / 800 79960089

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    32/76

    www.leoni-industrial-projects.com32 The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Pair, PVC-Insulation, Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-flApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireInner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black

     Armor....................................... galvanized round steel wires

    Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/

    PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET*) single element design without com wire

    Technical data Abbreviations

    Flame propagation- Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)

    Gas/vapor tightness outer  jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range-40°C up to +105°C(during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending

    10 x cable diameter 

    RE-Instrumentation Cable

    Yw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC inner jacket, heat resistant

    SWA steel wire armor 

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance

    single element:2 to 4 elements:

    above 4 elements:

    nom. nF/km /

    nF/1000ft

     

    200 / 61190 / 58

    160 / 49

     

    200 / 61190 / 58

    160 / 49

     

    200 / 61180 / 55

    150 / 46

     

    200 / 61180 / 55

    150 / 46

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    O eratin volta e V 300

  • 8/20/2019 Icon en Instrumentation Cables

    33/76

    www.leoni-industrial-projects.com 33The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Pair, PVC-Insulation, Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-flGeometrical data

    No. of 

    elements

    RT of 

    insulation

    RT of inner 

     jacket 1

    Dia. over 

    inner jacket 1

    Dia. of 

    armor wire

    RT outer jacket Outer dia. Weight Part number  

    nom. nom. nom. nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /

    lbs/1000ft)

    black

    AWG 14 /7

    1 0.51 / 20 1.02 / 40 8.1 / 0.32 0.9 1.27 / 50 12.5 / 0.49 319 / 215 79840471

    2 0.51 / 20 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.5 / 0.69 540 / 365 79840472

    4 0.51 / 20 1.27 / 50 14.6 / 0.58 0.9 1.52 / 60 19.5 / 0.77 700 / 475 79840473

    6 0.51 / 20 1.52 / 60 18.0 / 0.71 1.25 1.78 / 70 24.1 / 0.95 1097 / 740 79840474

    8 0.51 / 20 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1234 / 830 7984047510 0.51 / 20 1.52 / 60 21.7 / 0.86 1.25 1.78 / 70 27.8 / 1.09 1440 / 970 79840476

    12 0.51 / 20 1.78 / 70 23.3 / 0.92 1.25 1.78 / 70 29.3 / 1.15 1649 / 1100 79840477

    16 0.51 / 20 1.78 / 70 26.4 / 1.04 1.6 2.03 / 80 33.6 / 1.32 2213 / 1490 79840478

    24 0.51 / 20 1.78 / 70 31.4 / 1.23 1.6 2.03 / 80 38.6 / 1.52 2845 / 1915 79840479

    36 0.51 / 20 2.03 / 80 38.6 / 1.52 2 2.29 / 90 47.1 / 1.85 4256 / 2860 79840480

    AWG 16 /7

    1 0.38 / 15 0.89 / 35 6.7 / 0.26 0.9 1.27 / 50 11.0 / 0.43 248 / 175 79840000

    2 0.38 / 15 1.27 / 50 10.6 / 0.43 0.9 1.27 / 50 15.0 / 0.59 414 / 285 79840001

    4 0.38 / 15 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.4 / 0.69 555 / 375 79840002

    6 0.38 / 15 1.27 / 50 14.8 / 0.58 0.9 1.52 / 60 19.7 / 0.77 694 / 470 79840254

    8 0.38 / 15 1.52 / 60 16.2 / 0.64 1.25 1.52 / 60 21.8 / 0.85 924 / 620 79840003

    10 0.38 / 15 1.52 / 60 18.2 / 0.72 1.25 1.78 / 70 24.3 / 0.96 1097 / 740 79840255

    12 0.38 / 15 1.52 / 60 18.9 / 0.74 1.25 1.78 / 70 25.0 / 0.98 1222 / 800 79840004

    16 0.38 / 15 1.52 / 60 21.2 / 0.83 1.25 1.78 / 70 27.3 / 1.07 1402 / 945 79840005

    24 0.38 / 15 1.78 / 70 25.6 / 1.01 1.6 2.03 / 80 32.8 / 1.30 2080 / 1400 79840006

    36 0.38 / 15 1.78 / 70 30.4 / 1.20 1.6 2.03 / 80 37.6 / 1.48 2696 / 1815 79840007

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.1 / 0.24 0.9 1.27 / 50 10.4 / 0.41 235 / 160 79840008

    2 0.38 / 15 1.02 / 40 9.4 / 0.37 0.9 1.27 / 50 13.8 / 0.54 343 / 235 79840009

    4 0.38 / 15 1.27 / 50 11.3 / 0.45 0.9 1.52 / 60 16.2 / 0.64 474 / 330 79840010

    6 0.38 / 15 1.27 / 50 13.4 / 0.53 0.9 1.52 / 60 18.3 / 0.72 597 / 400 79840252

    8 0.38 / 15 1.27 / 50 14.2 / 0.56 0.9 1.52 / 60 19.1 / 0.75 654 / 445 79840011

    10 0.38 / 15 1.52 / 60 16.5 / 0.65 1.25 1.52 / 60 22.1 / 0.87 905 / 615 7984025312 0.38 / 15 1.52 / 60 17.1 / 0.67 1.25 1.78 / 70 23.2 / 0.91 1000 / 680 79840012

    16 0.38 / 15 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1174 / 790 79840013

    24 0.38 / 15 1.78 / 70 23.1 / 0.91 1.25 1.78 / 70 29.1 / 1.15 1542 / 1040 79840014

    36 0.38 / 15 1.78 / 70 27.3 / 1.07 1.6 2.03 / 80 34.5 / 1.36 2218 / 1520 79840015

     

    AWG 20 /7

    1 0.30 / 12 0.89 / 35 5.3 / 0.21 0.9 1.02 / 40 9.1 / 0.36 185 / 125 79840016

    2 0.30 / 12 1.02 / 40 8.0 / 0.31 0.9 1.27 / 50 12.4 / 0.48 285 / 195 79840017

    4 0.30 / 12 1.02 / 40 9.2 / 0.36 0.9 1.27 / 50 13.6 / 0.53 348 / 240 79840018

    6 0.30 / 12 1.27 / 50 11.3 / 0.44 0.9 1.52 / 60 16.2 / 0.63 470 / 320 79840250

    8 0.30 / 12 1.27 / 50 11.9 / 0.47 0.9 1.52 / 60 16.8 / 0.66 513 / 350 79840019

    10 0.30 / 12 1.27 / 50 13.3 / 0.52 0.9 1.52 / 60 18.2 / 0.71 585 / 395 79840251

    12 0.30 / 12 1.27 / 50 13.8 / 0.54 0.9 1.52 / 60 18.7 / 0.73 626 / 455 79840020

    16 0.30 / 12 1.52 / 60 15.9 / 0.63 1.25 1.78 / 70 22.0 / 0.84 879 / 595 79840021

    24 0.30 / 12 1.52 / 60 18.6 / 0.73 1.25 1.78 / 70 24.7 / 0.97 1130 / 760 79840022

    36 0.30 / 12 1.52 / 60 21.9 / 0.86 1.25 1.78 / 70 28.0 / 1.10 1439 / 970 79840023

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    34/76

    www.leoni-industrial-projects.com34 The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Pair, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-fl PiMFApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG

    18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Wrapping.................................. at least 1 layer of plastic tapeCollective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire

    Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black

     Armor....................................... galvanized round steel wires

    Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsically

    safe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC

    SPOS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET

    Technical data Abbreviations

    Flame propagation- Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)

    Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range-40°C up to +105°C

    (during operation)

    -5°C up to +50°C

    (during installation)

    Min. bending radius - repeated

    bending

    10 x cable diameter 

    RE-

    Instrumentation CableYw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC inner jacket, heat resistant

    SWA steel wire armor 

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    PiMF pair in metal foil

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance nom. nF/km /

    nF/1000ft

    200 / 61 200 / 61 200 / 61 200 / 61

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    Operating voltage V 300

  • 8/20/2019 Icon en Instrumentation Cables

    35/76

    www.leoni-industrial-projects.com 35The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Pair, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-fl PiMFGeometrical data

    No. of 

    elements

    RT of 

    insulation

    RT of inner 

     jacket 1

    Dia. over 

    inner jacket 1

    Dia. of 

    armor wire

    RT outer jacket Outer dia. Weight Part number  

    nom. nom. nom. nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /

    lbs/1000ft)

    black

    AWG 14 /7

    2 0.51 / 20 1.27 / 50 14.1 / 0.56 0.9 1.52 / 60 19.0 / 0.75 605 / 410 79840124

    4 0.51 / 20 1.52 / 60 16.7 / 0.66 1.25 1.78 / 70 22.8 / 0.90 965 / 650 79840482

    6 0.51 / 20 1.52 / 60 20.0 / 0.79 1.25 1.78 / 70 26.1 / 1.03 1234 / 830 79840483

    8 0.51 / 20 1.52 / 60 21.3 / 0.84 1.25 1.78 / 70 27.4 / 1.08 1417 / 955 79840484

    10 0.51 / 20 1.78 / 70 24.7 / 0.97 1.25 1.78 / 70 30.7 / 1.21 1692 / 1140 7984048512 0.51 / 20 1.78 / 70 26.4 / 1.04 1.6 2.03 / 80 33.6 / 1.32 2106 / 1415 79840486

    16 0.51 / 20 1.78 / 70 29.7 / 1.17 1.6 2.03 / 80 36.9 / 1.45 2518 / 1695 79840487

    24 0.51 / 20 2.03 / 80 36.0 / 1.42 2 2.29 / 90 44.5 / 1.75 3763 / 2530 79840488

    36 0.51 / 20 2.29 / 90 43.4 / 1.71 2 2.54 / 100 52.5 / 2.06 5166 / 3475 79840490

    AWG 16 /7

    2 0.38 / 15 1.27 / 50 12.2 / 0.48 0.9 1.52 / 60 17.0 / 0.67 495 / 335 79840024

    4 0.38 / 15 1.27 / 50 14.3 / 0.56 0.9 1.52 / 60 19.2 / 0.75 633 / 430 79840025

    6 0.38 / 15 1.52 / 60 17.3 / 0.69 1.25 1.78 / 70 23.4 / 0.93 1014 / 665 79840260

    8 0.38 / 15 1.52 / 60 18.4 / 0.72 1.25 1.78 / 70 24.5 / 0.96 1097 / 740 79840026

    10 0.38 / 15 1.52 / 60 20.8 / 0.82 1.25 1.78 / 70 26.9 / 1.06 1272 / 860 79840261

    12 0.38 / 15 1.52 / 60 21.6 / 0.85 1.25 1.78 / 70 27.7 / 1.09 1375 / 930 79840027

    16 0.38 / 15 1.78 / 70 24.9 / 0.98 1.25 1.78 / 70 30.9 / 1.22 1692 / 1140 79840028

    24 0.38 / 15 1.78 / 70 29.4 / 1.16 1.6 2.03 / 80 36.6 / 1.44 2422 / 1630 79840029

    36 0.38 / 15 2.03 / 80 36.5 / 1.40 2 2.29 / 90 45.0 / 1.74 3645 / 2450 79840030

    AWG 18 /7

    2 0.38 / 15 1.27 / 50 11.3 / 0.44 0.9 1.52 / 60 16.2 / 0.63 446 / 305 79840031

    4 0.38 / 15 1.27 / 50 13.1 / 0.52 0.9 1.52 / 60 18.0 / 0.71 557 / 380 79840032

    6 0.38 / 15 1.52 / 60 16.0 / 0.63 1.25 1.52 / 60 21.6 / 0.85 853 / 575 79840258

    8 0.38 / 15 1.52 / 60 17.0 / 0.67 1.25 1.78 / 70 23.1 / 0.91 974 / 660 79840033

    10 0.38 / 15 1.52 / 60 19.1 / 0.75 1.25 1.78 / 70 25.2 / 0.99 1117 / 755 79840259

    12 0.38 / 15 1.52 / 60 19.8 / 0.78 1.25 1.78 / 70 25.9 / 1.02 1194 / 805 79840034

    16 0.38 / 15 1.78 / 70 22.8 / 0.90 1.25 1.78 / 70 28.8 / 1.14 1454 / 980 79840035

    24 0.38 / 15 1.78 / 70 26.9 / 1.06 1.6 2.03 / 80 34.1 / 1.35 2086 / 1405 7984003636 0.38 / 15 2.03 / 80 32.4 / 1.28 1.6 2.03 / 80 39.6 / 1.56 2749 / 1855 79840037

    AWG 20 /7

    2 0.30 / 12 1.02 / 40 9.2 / 0.36 0.9 1.27 / 50 13.6 / 0.53 332 / 230 79840038

    4 0.30 / 12 1.27 / 50 11.2 / 0.44 0.9 1.52 / 60 16.1 / 0.63 455 / 310 79840039

    6 0.30 / 12 1.27 / 50 13.1 / 0.52 0.9 1.52 / 60 18.0 / 0.70 556 / 380 79840256

    8 0.30 / 12 1.27 / 50 13.8 / 0.54 0.9 1.52 / 60 18.7 / 0.73 615 / 415 79840040

    10 0.30 / 12 1.52 / 60 16.0 / 0.63 1.25 1.52 / 60 21.6 / 0.85 854 / 575 79840257

    12 0.30 / 12 1.52 / 60 16.6 / 0.65 1.25 1.78 / 70 22.7 / 0.89 934 / 630 79840041

    16 0.30 / 12 1.52 / 60 18.6 / 0.73 1.25 1.78 / 70 24.7 / 0.97 1093 / 685 79840042

    24 0.30 / 12 1.52 / 60 21.8 / 0.86 1.25 1.78 / 70 27.9 / 1.10 1383 / 935 79840043

    36 0.30 / 12 1.78 / 70 26.8 / 1.04 1.6 2.03 / 80 34.0 / 1.33 2047 / 1380 79840044

    RT = Radial Thickness

  • 8/20/2019 Icon en Instrumentation Cables

    36/76

    www.leoni-industrial-projects.com36 The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Triple, PVC-Insulation, Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-flApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.

    Construction

    Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG18 , AWG 20

    Insulation.................................. heat resistant polyvinyl chloride PVC (105 °C)

    Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multi-

    element

    Wrapping.................................. at least 1 layer of plastic tape

    Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wireInner jacket 1........................... heat resistant polyvinyl chloride PVC (105 °C), black

     Armor....................................... galvanized round steel wires

    Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,

    colored orange

    Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 °C), black, blue for intrinsicallysafe systems

    Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/

    PVC*) OS (UL) 105 °C SUN RES PRODUCTION LOT CODE LENGTH

    MARKING IN FEET*) single element design without com wire

    Technical data Abbreviations

    Flame propagation- Test on single cable UL13 (VW-1)

    - Test on bunched cables UL 1685 (vertical tray)

    Gas/vapor tightness outer 

     jacket

    NEC 501.15 (D) and (E)

    Limiting Oxygen Index (LOI)  ASTM D 2863 (min. 30 %)

    Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 °C)

    Oil resistance ICEA S-73-532

    Sunlight resistance UL 1581 section 1200

    Temperature range-40°C up to +105°C

    (during operation)

    -5°C up to +50°C(during installation)

    Min. bending radius - repeated

    bending

    10 x cable diameter 

    RE- Instrumentation CableYw PVC insulation, heat resistant

    (St) collective shield

    Yw PVC inner jacket, heat resistant

    SWA steel wire armor 

    Yw PVC outer jacket, heat resistant

    -fl reduced flame propagation

    Electrical Properties at 20 °C

    Conductor cross-section (AWG)  AWG 14 AWG 16 AWG 18 AWG 20

    Conductor resistance max. Ω/km / Ω/1000ft 8.9 / 2.72 14.3 / 4.36 22.8 / 6.93 35.8 / 10.92Insulation resistance min. MΩ x km /

    MΩ x 1000ft

    30.5 / 100 (at 15.6 °C)

    Mutual capacitance

    single element:

    2 to 4 elements:

    above 4 elements:

    nom. nF/km /

    nF/1000ft

     

    200 / 61

    190 / 58

    160 / 49

     

    200 / 61

    190 / 58

    160 / 49

     

    200 / 61

    180 / 55

    150 / 46

     

    200 / 61

    180 / 55

    150 / 46

    Inductance max. mH/km 1

    L/R ratio max. max. µH/Ω 60 40 25

    Test voltage Urms (core : core) V 1500

    Test voltage Urms (core : shield) V 1500

    O eratin volta e V 300

  • 8/20/2019 Icon en Instrumentation Cables

    37/76

    www.leoni-industrial-projects.com 37The Standard Types Instrumentation & Control Cable

     

    AWG 20 /7

    1 0.30 / 12 0.89 / 35 5.6 / 0.22 0.9 1.02 / 40 9.4 / 0.37 194 / 135 79840061

    2 0.30 / 12 1.02 / 40 8.8 / 0.34 0.9 1.27 / 50 13.2 / 0.51 319 / 215 79840062

    4 0.30 / 12 1.27 / 50 10.4 / 0.41 0.9 1.27 / 50 14.8 / 0.58 421 / 290 79840063

    6 0.30 / 12 1.27 / 50 12.6 / 0.50 0.9 1.52 / 60 17.5 / 0.69 560 / 380 79840262

    8 0.30 / 12 1.27 / 50 13.4 / 0.53 0.9 1.52 / 60 18.3 / 0.72 616 / 415 79840064

    10 0.30 / 12 1.27 / 50 14.9 / 0.59 0.9 1.52 / 60 19.8 / 0.78 706 / 475 79840263

    12 0.30 / 12 1.52 / 60 15.9 / 0.63 1.25 1.52 / 60 21.4 / 0.84 910 / 615 7984006516 0.30 / 12 1.52 / 60 17.7 / 0.70 1.25 1.78 / 70 23.8 / 0.94 1099 / 740 79840066

    24 0.30 / 12 1.52 / 60 20.8 / 0.82 1.25 1.78 / 70 26.9 / 1.06 1388 / 945 79840067

    36 0.30 / 12 1.78 / 70 25.2 / 1.00 1.6 2.03 / 80 32.4 / 1.28 2070 / 1420 79840068

    RT = Radial Thickness

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Single & Multi-Triple, PVC-Insulation, Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-flGeometrical data

    No. of 

    elements

    RT of 

    insulation

    RT of inner 

     jacket 1

    Dia. over 

    inner jacket 1

    Dia. of 

    armor wire

    RT outer jacket Outer dia. Weight Part number  

    nom. nom. nom. nom. nom. approx. approx. Color  

    (mm / mils) (mm / mils) (mm / in) (mm) (mm / mils) (mm / in) (kg/km /

    lbs/1000ft)

    black

    AWG 14 /7

    1 0.51 / 20 1.02 / 40 8.8 / 0.35 0.9 1.27 / 50 13.2 / 0.52 356 / 240 79840491

    2 0.51 / 20 1.27 / 50 14.0 / 0.55 0.9 1.52 / 60 18.9 / 0.74 643 / 435 79840492

    4 0.51 / 20 1.52 / 60 16.5 / 0.65 1.25 1.52 / 60 22.1 / 0.87 1000 / 675 79840493

    6 0.51 / 20 1.52 / 60 21.2 / 0.84 1.25 1.78 / 70 27.3 / 1.07 1383 / 930 79840494

    8 0.51 / 20 1.78 / 70 23.2 / 0.91 1.25 1.78 / 70 29.2 / 1.15 1632 / 1100 7984049510 0.51 / 20 1.78 / 70 24.1 / 0.95 1.25 1.78 / 70 30.1 / 1.18 1820 / 1225 79840496

    12 0.51 / 20 1.78 / 70 26.8 / 1.05 1.6 2.03 / 80 34.0 / 1.34 2330 / 1570 79840497

    16 0.51 / 20 1.78 / 70 30.2 / 1.19 1.6 2.03 / 80 37.4 / 1.47 2814 / 1895 79840498

    24 0.51 / 20 2.03 / 80 36.5 / 1.44 2 2.29 / 90 45.0 / 1.77 4131 / 2780 79840499

    36 0.51 / 20 2.29 / 90 44.0 / 1.73 2 2.54 / 100 53.1 / 2.09 7265 / 4885 79840500

    AWG 16 /7

    1 0.38 / 15 1.02 / 40 7.2 / 0.28 0.9 1.27 / 50 11.6 / 0.45 289 / 195 79840045

    2 0.38 / 15 1.27 / 50 12.0 / 0.47 0.9 1.52 / 60 16.9 / 0.66 505 / 340 79840046

    4 0.38 / 15 1.27 / 50 13.6 / 0.54 0.9 1.52 / 60 18.5 / 0.73 647 / 440 79840047

    6 0.38 / 15 1.52 / 60 17.2 / 0.68 1.25 1.78 / 70 23.3 / 0.92 1043 / 705 79840266

    8 0.38 / 15 1.52 / 60 18.4 / 0.72 1.25 1.78 / 70 24.5 / 0.96 1165 / 785 79840048

    10 0.38 / 15 1.52 / 60 20.6 / 0.81 1.25 1.78 / 70 26.7 / 1.06 1354 / 915 79840267

    12 0.38 / 15 1.52 / 60 21.1 / 0.83 1.25 1.78 / 70 27.2 / 1.07 1466 / 990 79840049

    16 0.38 / 15 1.78 / 70 24.4 / 0.96 1.25 1.78 / 70 30.4 / 1.20 1823 / 1225 79840050

    24 0.38 / 15 1.78 / 70 28.8 / 1.14 1.6 2.03 / 80 36.0 / 1.43 2626 / 1770 79840051

    36 0.38 / 15 2.03 / 80 34.8 / 1.37 1.6 2.29 / 90 42.5 / 1.68 3569 / 2430 79840052

    AWG 18 /7

    1 0.38 / 15 0.89 / 35 6.5 / 0.26 0.9 1.27 / 50 10.9 / 0.43 248 / 170 79840053

    2 0.38 / 15 1.27 / 50 10.9 / 0.43 0.9 1.27 / 50 15.3 / 0.59 425 / 285 79840054

    4 0.38 / 15 1.27 / 50 12.4 / 0.49 0.9 1.52 / 60 17.3 / 0.68 554 / 380 79840055

    6 0.38 / 15 1.27 / 50 15.1 / 0.60 1.25 1.52 / 60 20.7 / 0.81 820 / 565 79840264

    8 0.38 / 15 1.52 / 60 16.6 / 0.66 1.25 1.78 / 70 22.7 / 0.90 984 / 670 79840056

    10 0.38 / 15 1.52 / 60 18.7 / 0.74 1.25 1.78 / 70 24.8 / 0.98 1140 / 770 79840265

    12 0.38 / 15 1.52 / 60 19.2 / 0.76 1.25 1.78 / 70 25.3 / 1.00 1225 / 825 79840057

    16 0.38 / 15 1.52 / 60 21.4 / 0.85 1.25 1.78 / 70 27.5 / 1.09 1453 / 1005 79840058

    24 0.38 / 15 1.78 / 70 26.0 / 1.03 1.6 2.03 / 80 33.2 / 1.31 2156 / 1455 79840059

    36 0.38 / 15 1.78 / 70 30.8 / 1.22 1.6 2.03 / 80 38.0 / 1.50 2800 / 1925 79840060

  • 8/20/2019 Icon en Instrumentation Cables

    38/76

    www.leoni-industrial-projects.com38 The Standard Types Instrumentation & Control Cable

    Instrumentation Cable UL 13 / UL 2250

    Flame Retardant, Sunlight Resistant

    PLTC/ITC

    105 °C / 300 V

    Multi-Triple, PVC-Insulation, Individual & Collective Shield, Armor, PVC Jacket

     

    RE-Yw(St)YwSWAYw-fl TiMFApplication

    UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to

    NEC 501.10(B) and NEC 502.10(B).

    For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.

    Construction

    Conductor.........