bs 5308 part 1 type 2 multipairs instrumentation cables

12
ADDISON Caledonian 2 PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC PVC Outer Sheath Galvanized Steel Wire Armour Plain Annealed Copper PE Insulation AL/HDPE Tape Aluminium/polyester Tape Tinned Copper Drain Wire PVC Inner Sheath APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission. STANDARDS Basic design to BS 5308 Part 1 Type 2 FIRE PERFORMANCE Flame Retardance (Single Vertical Wire Test)** EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)** EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design. VOLTAGE RATING 300/500V CABLE CONSTRUCTION Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228. Insulation: PE compound.

Upload: caledonian-tech

Post on 28-Mar-2016

262 views

Category:

Documents


3 download

DESCRIPTION

PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC PVC Outer Sheath Galvanized Steel Wire Armour Plain Annealed Copper PE Insulation AL/HDPE Tape Aluminium/polyester Tape Tinned Copper Drain Wire PVC Inner Sheath APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission. STANDARDS Basic design to BS 5308 Part 1 Type 2

TRANSCRIPT

Page 1: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian2

PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair)

RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

PVC Outer Sheath

Galvanized Steel Wire Armour

Plain Annealed CopperPE Insulation

AL/HDPE Tape

Aluminium/polyester Tape

Tinned Copper Drain Wire

PVC Inner Sheath

APPLICATION

The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.

STANDARDS

Basic design to BS 5308 Part 1 Type 2

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**

EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228.Insulation: PE compound.

Page 2: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

3ADDISON

NON-IS & IS Instrumentation Cables

Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmBinder tape: PETP transparent tapeOverall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compoundAmouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour: See Technical InformationOuter Sheath: NON-IS Cable: Black IS Cable: Blue

PHYSICAL AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter

ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5

Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67

Conductor Resistance Max ohm/km 18.2 12.3 7.58

Insulation Resistance Min MΩ/km 500 500 500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250

Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)

pF/m 75 85 85

Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65

Test VoltageCore To Core V 1000Core To Screen V 1000

Rated Voltage Max V 300/500 300/500 300/500

Page 3: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian4

CONSTRUCTION PARAMETERS

Cable Code

RE-2Y(St)MSYSWAY

Nominal Insulation Thickness

Nominal Inner

SheathThickness

Nominal Outer

SheathThickness

Nominal Overall

Diameter

Approx. Weight

mm mm mm mm kg/km RE-2Y(St)MSYSWAY 1×2×1.0 0.6RE-2Y(St)MSYSWAY 1×2×1.5 0.6RE-2Y(St)MSYSWAY 1×2×2.5 0.6RE-2Y(St)MSYSWAY 2×2×1.0 0.6RE-2Y(St)MSYSWAY 2×2×1.5 0.6RE-2Y(St)MSYSWAY 5×2×1.0 0.6RE-2Y(St)MSYSWAY 5×2×2.5 0.6RE-2Y(St)MSYSWAY 10×2×1.0 0.6RE-2Y(St)MSYSWAY 10×2×2.5 0.6RE-2Y(St)MSYSWAY 12×2×1.0 0.6RE-2Y(St)MSYSWAY 12×2×2.5 0.6RE-2Y(St)MSYSWAY 20×2×1.0 0.6RE-2Y(St)MSYSWAY 20×2×2.5 0.6

Note : Other conductor sizes & core configurations are available upon request.

Rated Voltage

300/500V

NStandard

BS 5308

Flame Retardancy**NF C32-070-2.1(C2)

IEC60332-1-2/EN50265-2-1

Reduced Fire Propagation**NF C32-070-2.2(C1)

IEC60332-3-24/EN50266-2-4

Page 4: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

5ADDISON

NON-IS & IS Instrumentation Cables

PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple)

RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

PVC Outer Sheath

Galvanized Steel Wire Armour

Plain Annealed CopperPE Insulation

AL/HDPE Tape

Aluminium/polyester Tape

Tinned Copper Drain Wire

PVC Inner Sheath

APPLICATION

The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.

STANDARDS

Basic design to BS 5308 Part 1 Type 2

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**

EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228.Insulation: PE compound.

Page 5: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian6

Triple: Three conductors twisted to form a triple. Binder tape: PETP transparent tapeOverall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compoundAmouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour: See Technical InformationOuter Sheath: NON-IS Cable: Black IS Cable: Blue

PHYSICAL AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter

ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5

Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67

Conductor Resistance Max ohm/km 18.2 12.3 7.58

Insulation Resistance Min MΩ/km 500 500 500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250

Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)

pF/m 75 85 85

Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65

Test VoltageCore To Core V 1000Core To Screen V 1000

Rated Voltage Max V 300/500 300/500 300/500

Page 6: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

7ADDISON

NON-IS & IS Instrumentation Cables

CONSTRUCTION PARAMETERS

Cable Code

RE-2Y(St)MSYSWAY

Nominal Insulation Thickness

Nominal Inner

SheathThickness

Nominal Outer

SheathThickness

Nominal Overall

Diameter

Approx. Weight

mm mm mm mm kg/km RE-2Y(St)MSYSWAY 7×3×1.0 0.6RE-2Y(St)MSYSWAY 10×3×1.5 0.6RE-2Y(St)MSYSWAY 20×3×2.5 0.6

Note : Other conductor sizes & core configurations are available upon request.

Rated Voltage

300/500V

NStandard

BS 5308

Flame Retardancy**NF C32-070-2.1(C2)

IEC60332-1-2/EN50265-2-1

Reduced Fire Propagation**NF C32-070-2.2(C1)

IEC60332-3-24/EN50266-2-4

Page 7: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian8

Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipairs)

RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

Galvanized Steel Wire Armour

Plain Annealed Copper

PVC Outer Sheath

PVC Inner Sheath

Mica Tape+PE Insulation

Aluminum/Polyester Tape With Tinned Copper Drain Wire

AL/HDPE Tape

APPLICATION

The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.

STANDARDS

Basic design to BS 5308

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

Circuit Integrity with mechanical shock

EN 50200(PH30); CEI 20-36/4-0

Circuit Integrity with mechanical shock & water spray

EN 50200 annex E

System Circuit Integrity DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

Page 8: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

9ADDISON

NON-IS & IS Instrumentation Cables

No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard.

CABLE CONSTRUCTIONConductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2.Insulation: Mica glass tape covered by PE compound.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmOverall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire.Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound.Armouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

VOLTAGE RATING 300/500 V

COLOUR CODEInsulation Colour: See Technical InformationOuter Sheath: Orange (other colours on request)

PHYSICAL AND THERMAL PROPERTIESTemperature range during operation (fixed state): -30°C – +90°CTemperature range during installation (mobile state): -20°C – +50°CMinimum bending radius: 10 x Overall Diameter

ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5 4.0

Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67 7 x 0.85

Conductor Resistance Max ohm/km 18.2 12.3 7.58

Insulation Resistance Min MΩ/km 500 500 500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250

Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)

pF/m 75 85 85

Page 9: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian10

Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65

Test VoltageCore To Core V 1000Core To Screen V 1000

Rated Voltage Max V 300/500 300/500 300/500 300/500

CONSTRUCTION PARAMETERS

Cable Code

RE-m2Y(St)MSYSWAY

Nominal Insulation Thickness

Nominal Inner

SheathThickness

Nominal Outer

SheathThickness

Nominal Overall

Diameter

Approx. Weight

mm mm mm mm kg/km RE-m2Y(St)MSYSWAY 5×2×1.0 0.6RE-m2Y(St)MSYSWAY 5×2×1.5 0.6RE-m2Y(St)MSYSWAY 5×2×2.5 0.6RE-m2Y(St)MSYSWAY 5×2×4.0 0.6RE-m2Y(St)MSYSWAY 10×2×1.5 0.6RE-m2Y(St)MSYSWAY 10×2×2.5 0.6RE-m2Y(St)MSYSWAY 10×2×4.0 0.6RE-m2Y(St)MSYSWAY 20×2×1.5 0.6

Note : Other conductor sizes & core configurations are available upon request.

Rated Voltage

300/500V

NStandard

BS 5308

Circuit IntegrityIEC 60331/BS 6387

EN 50200NF C32-070-2.3(CR1)

W E

Reduced Fire PropagationNF C32-070-2.2(C1)

IEC60332-3-24/EN50266-2-4

Flame RetardancyNF C32-070-2.1(C2)

IEC60332-1-2/EN50265-2-1

Low ToxicityNES 02-713/NF C 20-454

Low CorrosivityIEC60754-2

EN50267-2-2/3NF C 32-074

Low Smoke EmissionIEC 61034-1&2

EN 50268-1&2/NF C32-073

Zero

Halogen FreeIEC60754-1

EN50267-2-1

W E

DIN 4102-12Functional Integrity

Page 10: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

11ADDISON

NON-IS & IS Instrumentation Cables

Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple)

RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC

Galvanized Steel Wire Armour

Plain Annealed Copper

PVC Outer Sheath

PVC Inner Sheath

Mica Tape+PE Insulation

Aluminum/Polyester Tape With Tinned Copper Drain Wire

AL/HDPE Tape

APPLICATION

The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.

STANDARDS

Basic design to BS 5308

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)

Circuit Integrity with mechanical shock

EN 50200(PH30); CEI 20-36/4-0

Circuit Integrity with mechanical shock & water spray

EN 50200 annex E

System Circuit Integrity DIN 4102-12, E30 depending on lay system

Flame Retardance (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

Page 11: BS 5308 Part 1 Type 2 multipairs instrumentation cables

ADDISON

Caledonian12

No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard.

CABLE CONSTRUCTIONConductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2.Insulation: Mica glass tape covered by PE compound.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmOverall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire.Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound.Armouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

VOLTAGE RATING 300/500 V

COLOUR CODEInsulation Colour: See Technical InformationOuter Sheath: Orange (other colours on request)

PHYSICAL AND THERMAL PROPERTIESTemperature range during operation (fixed state): -30°C – +90°CTemperature range during installation (mobile state): -20°C – +50°CMinimum bending radius: 10 x Overall Diameter

ELECTRICAL PROPERTIES

Conductor Area Size mm2 1.0 1.5 2.5 4.0

Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67 7 x 0.85

Conductor Resistance Max ohm/km 18.2 12.3 7.58

Insulation Resistance Min MΩ/km 500 500 500

Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250

Page 12: BS 5308 Part 1 Type 2 multipairs instrumentation cables

www.caledonian-cables.co.uk www.caledonian-tech.net

Caledonian

13ADDISON

NON-IS & IS Instrumentation Cables

Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)

pF/m 75 85 85

Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120

Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65

Test VoltageCore To Core V 1000Core To Screen V 1000

Rated Voltage Max V 300/500 300/500 300/500 300/500

CONSTRUCTION PARAMETERS

Cable Code

RE-m2Y(St)MSYSWAY

Nominal Insulation Thickness

Nominal Inner

SheathThickness

Nominal Outer

SheathThickness

Nominal Overall

Diameter

Approx. Weight

mm mm mm mm kg/km RE-m2Y(St)MSYSWAY 1×3×1.5 0.6RE-m2Y(St)MSYSWAY 1×3×2.5 0.6RE-m2Y(St)MSYSWAY 7×3×1.5 0.6RE-m2Y(St)MSYSWAY 7×3×2.5 0.6RE-m2Y(St)MSYSWAY 12×3×1.5 0.6

Note : Other conductor sizes & core configurations are available upon request.

Rated Voltage

300/500V

NStandard

BS 5308

Circuit IntegrityIEC 60331/BS 6387

EN 50200NF C32-070-2.3(CR1)

W E

Reduced Fire PropagationNF C32-070-2.2(C1)

IEC60332-3-24/EN50266-2-4

Flame RetardancyNF C32-070-2.1(C2)

IEC60332-1-2/EN50265-2-1

Low ToxicityNES 02-713/NF C 20-454

Low CorrosivityIEC60754-2

EN50267-2-2/3NF C 32-074

Low Smoke EmissionIEC 61034-1&2

EN 50268-1&2/NF C32-073

Zero

Halogen FreeIEC60754-1

EN50267-2-1

W E

DIN 4102-12Functional Integrity