bs 5308 part 1 type 2 multipairs instrumentation cables
DESCRIPTION
PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair) RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC PVC Outer Sheath Galvanized Steel Wire Armour Plain Annealed Copper PE Insulation AL/HDPE Tape Aluminium/polyester Tape Tinned Copper Drain Wire PVC Inner Sheath APPLICATION The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission. STANDARDS Basic design to BS 5308 Part 1 Type 2TRANSCRIPT
ADDISON
Caledonian2
PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipair)
RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
PVC Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperPE Insulation
AL/HDPE Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
PVC Inner Sheath
APPLICATION
The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.
STANDARDS
Basic design to BS 5308 Part 1 Type 2
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)**
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**
EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228.Insulation: PE compound.
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
3ADDISON
NON-IS & IS Instrumentation Cables
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmBinder tape: PETP transparent tapeOverall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compoundAmouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour: See Technical InformationOuter Sheath: NON-IS Cable: Black IS Cable: Blue
PHYSICAL AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter
ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5
Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67
Conductor Resistance Max ohm/km 18.2 12.3 7.58
Insulation Resistance Min MΩ/km 500 500 500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250
Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)
pF/m 75 85 85
Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65
Test VoltageCore To Core V 1000Core To Screen V 1000
Rated Voltage Max V 300/500 300/500 300/500
ADDISON
Caledonian4
CONSTRUCTION PARAMETERS
Cable Code
RE-2Y(St)MSYSWAY
Nominal Insulation Thickness
Nominal Inner
SheathThickness
Nominal Outer
SheathThickness
Nominal Overall
Diameter
Approx. Weight
mm mm mm mm kg/km RE-2Y(St)MSYSWAY 1×2×1.0 0.6RE-2Y(St)MSYSWAY 1×2×1.5 0.6RE-2Y(St)MSYSWAY 1×2×2.5 0.6RE-2Y(St)MSYSWAY 2×2×1.0 0.6RE-2Y(St)MSYSWAY 2×2×1.5 0.6RE-2Y(St)MSYSWAY 5×2×1.0 0.6RE-2Y(St)MSYSWAY 5×2×2.5 0.6RE-2Y(St)MSYSWAY 10×2×1.0 0.6RE-2Y(St)MSYSWAY 10×2×2.5 0.6RE-2Y(St)MSYSWAY 12×2×1.0 0.6RE-2Y(St)MSYSWAY 12×2×2.5 0.6RE-2Y(St)MSYSWAY 20×2×1.0 0.6RE-2Y(St)MSYSWAY 20×2×2.5 0.6
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300/500V
NStandard
BS 5308
Flame Retardancy**NF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire Propagation**NF C32-070-2.2(C1)
IEC60332-3-24/EN50266-2-4
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
5ADDISON
NON-IS & IS Instrumentation Cables
PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple)
RE-2Y(St)MSYSWAY BC/PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
PVC Outer Sheath
Galvanized Steel Wire Armour
Plain Annealed CopperPE Insulation
AL/HDPE Tape
Aluminium/polyester Tape
Tinned Copper Drain Wire
PVC Inner Sheath
APPLICATION
The armoured PVC sheathed (Part 1 Type 2) cables are generally used when the risk of mechanical damage is increased. The galvanized steel wire armour provides excellent protection. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the PVC sheath can reduce toxic smoke and fume emission.
STANDARDS
Basic design to BS 5308 Part 1 Type 2
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test)**
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**
EN 60332-3-22 (cat. A); IEC 60332-3-22; BS EN 60332-3-22; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Bare copper, sizes: 1.0 mm² solid(Class 1), 1.5mm² and 2.5mm², multistranded(Class 2) to BS6360/IEC60228.Insulation: PE compound.
ADDISON
Caledonian6
Triple: Three conductors twisted to form a triple. Binder tape: PETP transparent tapeOverall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compoundAmouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE
Insulation Colour: See Technical InformationOuter Sheath: NON-IS Cable: Black IS Cable: Blue
PHYSICAL AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C Temperature Range During Installation (Mobile State): -20°C – +50°C Minimum Bending Radius: 6 X Overall Diameter
ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5
Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67
Conductor Resistance Max ohm/km 18.2 12.3 7.58
Insulation Resistance Min MΩ/km 500 500 500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250
Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)
pF/m 75 85 85
Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65
Test VoltageCore To Core V 1000Core To Screen V 1000
Rated Voltage Max V 300/500 300/500 300/500
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
7ADDISON
NON-IS & IS Instrumentation Cables
CONSTRUCTION PARAMETERS
Cable Code
RE-2Y(St)MSYSWAY
Nominal Insulation Thickness
Nominal Inner
SheathThickness
Nominal Outer
SheathThickness
Nominal Overall
Diameter
Approx. Weight
mm mm mm mm kg/km RE-2Y(St)MSYSWAY 7×3×1.0 0.6RE-2Y(St)MSYSWAY 10×3×1.5 0.6RE-2Y(St)MSYSWAY 20×3×2.5 0.6
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300/500V
NStandard
BS 5308
Flame Retardancy**NF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Reduced Fire Propagation**NF C32-070-2.2(C1)
IEC60332-3-24/EN50266-2-4
ADDISON
Caledonian8
Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multipairs)
RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
Galvanized Steel Wire Armour
Plain Annealed Copper
PVC Outer Sheath
PVC Inner Sheath
Mica Tape+PE Insulation
Aluminum/Polyester Tape With Tinned Copper Drain Wire
AL/HDPE Tape
APPLICATION
The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
STANDARDS
Basic design to BS 5308
FIRE PERFORMANCE
Circuit IntegrityIEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)
Circuit Integrity with mechanical shock
EN 50200(PH30); CEI 20-36/4-0
Circuit Integrity with mechanical shock & water spray
EN 50200 annex E
System Circuit Integrity DIN 4102-12, E30 depending on lay system
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
9ADDISON
NON-IS & IS Instrumentation Cables
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTIONConductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2.Insulation: Mica glass tape covered by PE compound.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmOverall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire.Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound.Armouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
VOLTAGE RATING 300/500 V
COLOUR CODEInsulation Colour: See Technical InformationOuter Sheath: Orange (other colours on request)
PHYSICAL AND THERMAL PROPERTIESTemperature range during operation (fixed state): -30°C – +90°CTemperature range during installation (mobile state): -20°C – +50°CMinimum bending radius: 10 x Overall Diameter
ELECTRICAL PROPERTIESConductor Area Size mm2 1.0 1.5 2.5 4.0
Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67 7 x 0.85
Conductor Resistance Max ohm/km 18.2 12.3 7.58
Insulation Resistance Min MΩ/km 500 500 500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250
Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)
pF/m 75 85 85
ADDISON
Caledonian10
Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65
Test VoltageCore To Core V 1000Core To Screen V 1000
Rated Voltage Max V 300/500 300/500 300/500 300/500
CONSTRUCTION PARAMETERS
Cable Code
RE-m2Y(St)MSYSWAY
Nominal Insulation Thickness
Nominal Inner
SheathThickness
Nominal Outer
SheathThickness
Nominal Overall
Diameter
Approx. Weight
mm mm mm mm kg/km RE-m2Y(St)MSYSWAY 5×2×1.0 0.6RE-m2Y(St)MSYSWAY 5×2×1.5 0.6RE-m2Y(St)MSYSWAY 5×2×2.5 0.6RE-m2Y(St)MSYSWAY 5×2×4.0 0.6RE-m2Y(St)MSYSWAY 10×2×1.5 0.6RE-m2Y(St)MSYSWAY 10×2×2.5 0.6RE-m2Y(St)MSYSWAY 10×2×4.0 0.6RE-m2Y(St)MSYSWAY 20×2×1.5 0.6
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300/500V
NStandard
BS 5308
Circuit IntegrityIEC 60331/BS 6387
EN 50200NF C32-070-2.3(CR1)
W E
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24/EN50266-2-4
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
W E
DIN 4102-12Functional Integrity
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
11ADDISON
NON-IS & IS Instrumentation Cables
Mica+PE Insulated, PVC Sheathed, Overall Screened & Armoured NON-IS & IS Instrumentation Cables (Multi Triple)
RE-m2Y(St)MSYSWAY BC/Mica+PE/Aluminium mylar tape Screen/AL/HDPE/PVC/SWA/PVC
Galvanized Steel Wire Armour
Plain Annealed Copper
PVC Outer Sheath
PVC Inner Sheath
Mica Tape+PE Insulation
Aluminum/Polyester Tape With Tinned Copper Drain Wire
AL/HDPE Tape
APPLICATION
The cables are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
STANDARDS
Basic design to BS 5308
FIRE PERFORMANCE
Circuit IntegrityIEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)
Circuit Integrity with mechanical shock
EN 50200(PH30); CEI 20-36/4-0
Circuit Integrity with mechanical shock & water spray
EN 50200 annex E
System Circuit Integrity DIN 4102-12, E30 depending on lay system
Flame Retardance (Single Vertical Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
ADDISON
Caledonian12
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454Note: Asterisk * denotes superseded standard.
CABLE CONSTRUCTIONConductor: Bare copper wire, stranded according to BS6360/IEC 60228 class 2.Insulation: Mica glass tape covered by PE compound.Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mmOverall Screen: Aluminum/polyester tape with 0.5mm2 screen (7/0.3mm) with tinned copper drain wire.Moisture Barrier: A layer of AL/HDPE tape is appliedhellic with overlap over the cable core to ensure a barrier against water vapor. Inner Sheath: PVC compound.Armouring: Galvanized steel wire armourOuter Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
VOLTAGE RATING 300/500 V
COLOUR CODEInsulation Colour: See Technical InformationOuter Sheath: Orange (other colours on request)
PHYSICAL AND THERMAL PROPERTIESTemperature range during operation (fixed state): -30°C – +90°CTemperature range during installation (mobile state): -20°C – +50°CMinimum bending radius: 10 x Overall Diameter
ELECTRICAL PROPERTIES
Conductor Area Size mm2 1.0 1.5 2.5 4.0
Conductor Stranding No. x mm 1 x 1.13 7 x 0.53 7 x 0.67 7 x 0.85
Conductor Resistance Max ohm/km 18.2 12.3 7.58
Insulation Resistance Min MΩ/km 500 500 500
Capacitance Unbalance At 1 Khz(Pair to Pair Screen) pF/250m 250
www.caledonian-cables.co.uk www.caledonian-tech.net
Caledonian
13ADDISON
NON-IS & IS Instrumentation Cables
Max. Mutual Capacitance @ 1 Khz for non OS or OS Cables (Except 1 Pair and 2 Pairs)
pF/m 75 85 85
Max. Mutual Capacitance @ 1 Khz for IS/OS Cables (Include 1 Pair and 2 Pairs) pF/m 115 120 120
Max. L/R Ratio For Adjacent Cores(Inductance/Resistance) μH/ohm 25 40 65
Test VoltageCore To Core V 1000Core To Screen V 1000
Rated Voltage Max V 300/500 300/500 300/500 300/500
CONSTRUCTION PARAMETERS
Cable Code
RE-m2Y(St)MSYSWAY
Nominal Insulation Thickness
Nominal Inner
SheathThickness
Nominal Outer
SheathThickness
Nominal Overall
Diameter
Approx. Weight
mm mm mm mm kg/km RE-m2Y(St)MSYSWAY 1×3×1.5 0.6RE-m2Y(St)MSYSWAY 1×3×2.5 0.6RE-m2Y(St)MSYSWAY 7×3×1.5 0.6RE-m2Y(St)MSYSWAY 7×3×2.5 0.6RE-m2Y(St)MSYSWAY 12×3×1.5 0.6
Note : Other conductor sizes & core configurations are available upon request.
Rated Voltage
300/500V
NStandard
BS 5308
Circuit IntegrityIEC 60331/BS 6387
EN 50200NF C32-070-2.3(CR1)
W E
Reduced Fire PropagationNF C32-070-2.2(C1)
IEC60332-3-24/EN50266-2-4
Flame RetardancyNF C32-070-2.1(C2)
IEC60332-1-2/EN50265-2-1
Low ToxicityNES 02-713/NF C 20-454
Low CorrosivityIEC60754-2
EN50267-2-2/3NF C 32-074
Low Smoke EmissionIEC 61034-1&2
EN 50268-1&2/NF C32-073
Zero
Halogen FreeIEC60754-1
EN50267-2-1
W E
DIN 4102-12Functional Integrity