hvdc systems for - usaid sari/energy integration · pdf file• stray losses in...

33
Converter Transformer

Upload: doandan

Post on 30-Jan-2018

225 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer

Page 2: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

HVDC Systems for…

• Energy Transmission over long distances

• Asynchronous coupling between AC Regional networks

Power Electronic circuits are used to convert AC to DC (Rectifier circuits) or

convert DC to AC (Inverter Circuits). Both of these circuits are also called

converter circuits.

A transformer that has one of its windings connected to one of these

circuits, as a dedicated transformer, is a Converter Transformer

Page 3: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer in HVDC system….

•Supply of AC voltages into two separate circuits feeding the

rectifier bridges with a phase shift of 30 electrical degrees for

reduction of low order harmonics esp. 5th & 7th harmonics.

•As a galvanic barrier between AC and DC systems to prevent

DC potential entering into the AC system

•Reactive Impedance in the AC supply to reduce short circuit

currents and to control the rate of rise in valve current during

commutation.

Page 4: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformers for 12 pulse rectification….

Primary: Star 400 kV AC

Secondary: Two windings connected to converter (Thyristors)

connected in series to build up required level of DC voltage

Page 5: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

– transport restrictions (dimensions and weight)

– number of necessary spare transformers

– technical possible solutions for core and windings

Choice of transformer design is mainly ruled by….

Page 6: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformers for 12 pulse rectification

Type of Connections No. of design X No. of units

Spares required

3 Phase Star-Delta & Star-Star

2 X 2 2

Single phase 2 winding 2 X 6 2

Singe phase 3 winding 2 x 3 1

Extended delta-connection

2 X 2 1

3 Phase 3 winding 2 X 2 1

Page 7: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer....

Design

active part

Valve Winding (D)Valve Winding (Y)

Line Winding

Tap Winding

HV-Terminal

Neutral-Terminal

Simplified connection of

line windings and tap windings

Winding and core arrangement

Page 8: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Xmer & Normal AC Xmer…..

• Polarity Reversal

• Voltage Distribution in Oil Barrier System

• Impedance variation influence

• On load Tap Changer

• Harmonic Currents

• Losses

• DC Magnetisation

• Short Circuit Forces

• DC Bushings

Page 9: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Beginning voltage stress distributions capacitive – Oil is stressed

more than PB

• Successively change over to Resistive distribution – PB is

stressed more (almost all stress across solid insulation)

• PD stresses under DC – Sporadic pulses at random intervals

-Discharges in oil gaps under rapid changes in voltage

-Discharges in cellulose insulation due to imperfections in

insulation

-Discharges at the oil-cellulose interface

……. To meet above, special oil-barrier insulation system is required

Under Polarity Reversal…..

Page 10: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Voltage Distribution in Oil-Barrier System...

Page 11: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Main duct in HVDC transformers require more PB barriers than normal AC transformers as DC voltage is taken mainly by PB. Voltage distribution is by resistivity in steady state.

- Transient DC voltages:

• Start up of converter when full DC potential from bridges is developed almost instantaneously

- DC Voltage Polarity Reversal:• When direction of power flow is changed in HVDC system, current

direction remains the same while polarity of the voltage will be reversed. • This is done within a few number of power cycles.• A sudden change in DC voltage is capacitive. • Time constant for the transition from capacitive to resistive distribution

is about an hour.

Voltage Distribution in Oil-Barrier System...

Page 12: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

AC DC

Voltage Distribution in Oil-Barrier System...

Page 13: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current
Page 14: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Valve windings to withstand AC voltages, superimposed DC

voltages on AC voltages, DC Voltage Polarity Reversal

• Composite insulation of Pressboard or Paper (Solid) and

oil (liquid)

• Voltage distribution between paper & oil under AC conditions

� depends on inverse ratio of dielectric constants of

PB/ Oil (2:1)

• Voltage distribution between oil & paper under steady state

DC voltage � depends on direct ratio of resistivities (1:10 ~ 500),

depends on oil quality, moisture content and temperature

Insulation Design

Page 15: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Closer Tolerance in Impedance is required between three phases and also between upper & lower bridges (star-star, star-delta circuits)

• (± 6% on special tolerance and 2-3% variation between units • (Normal transformers ± 10%)

The above is necessary :• To reduce distortion in DC voltage wave form• To reduce non-characteristic harmonics, thereby cost of AC filters • To reduce residual currents between three phases, which can act

as DC magnetization on the core.

To achieve close tolerance on impedance variation• Close dimensional tolerances in windings• Proper stabilization of windings before assembly• Better insulating material• Good winding machines

Influence of Impedance variation…

Page 16: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Large voltage control requirements at converter & inverter ends.

Tapping range is large (25 ~ 30%) with small steps to give

necessary adjustments in supply voltage.

• High frequency of operation – Mechanical aspects of OLTC

should be reviewed to ensure a robust design (Contacts wear,

linkages, motor, relays, contactors, interlocks). Derating

necessary compared to normal transformer applications.

• Small step voltage permit small variation in DC voltage, valve

firing angles and reactive power demand

On Load Tap Changer….

Page 17: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• There is need to compensate for the reactive voltage drop in the conversion between AC & DC by changing taps.

• In OLTC, switchover from one tap to another is carried out by the diverter switch.

• When changing over from one tap to next, the current in the leavingtap has to be broken during the normal current zero passage.

• In star-star connected windings, the current is zero for a long time and the change over is smooth.

• But in star-delta connected windings, the current change from positive to negative is abrupt with very little time at zero current.

• This puts strain on diverter switch.

On Load Tap Changer…

Page 18: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current
Page 19: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Additional losses due to harmonic currents in valve windings

• Stray flux from harmonic currents can heat up structural members like Yoke Clamps, Tank

• Yoke shunts are used to contain and direct the above leakageflux to core

• Harmonic stray flux can induce larger currents than power frequency stray flux

Higher Harmonic Currents….

Page 20: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current
Page 21: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• No-Load losses – Depends on applied AC voltage, same as normal transformer

• Load Losses – I2R + Stray loss from circulating currents in windings & metallic parts

from leakage flux

• Circulating current depend on rate of change in winding current and thus leakage

flux.

• With stepwise change in load current during commutation from one valve to

another, the induced voltages will be fairly high to create circulating currents. So

stray losses are increased compared to conventional power transformers.

• Stray losses in windings – Increase as square of harmonic number

• At 150 Hz, Stray losses (150/50)2 more than at 50 Hz current

• Stray losses in metal- varies as 0.8 of harmonic number

• High percentage of harmonic currents in the load current causes higher load losses

compared to normal transformers

Losses….

Page 22: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• Due to inaccuracies in valve firing.

• Results in a small residual DC current oscillating around zero.

• DC components in magnetizing current lead to core saturation, which

results in -

�high levels of vibration

�increased sound level in transformers

�marginal increase in no-load loss.

DC Magnetization….

Page 23: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• A short circuit across a valve or phase to ground on a valve side terminal

can result in a completely asymmetrical current for a few cycles.

• Resulting forces on the winding can be larger than for the normal power

transformers where the asymmetry decays rapidly.

Short Circuit Forces….

Page 24: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Mechanical forces during a short circuit may reach critical values

An inner winding buckles under radial forces

Page 25: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Excessive axial force in winding will cause tilting of conductor

Page 26: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

• DC withstand voltage of contaminated insulator is 20 ~ 30% of that of AC.

• To meet this, bushings creepage used are 40 mm/kV or more (Normal

bushings are with 25mm / kV of service maximum voltage)

• To avoid chances of phase to ground short circuits, valve side bushings are

located inside the valve hall. This also reduces the pollution related

flashovers and consequent short circuit.

• IEC & IEEE standards for the DC bushings.

DC Bushing….

Page 27: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer

Design

Interface: DC bushings (Basslink)

Page 28: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer

• Few Formula…..

dd I L3

cos35.1U ωπ

α −••= U

)I L3

cos35.1(U dd ωπ

γ −••−= U

Rectifier mode

Inverter mode

Overlap

U

IL2cos)cos( dω

αµα −=+

πγµα =++

Page 29: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer

Testsrequired acc. to IEC 60076-1, ~-3, IEC61378-2

routine tests

meas of DC wind. res. IEC 60076-1, 10.2 meas. of voltage ratio and check of phase displacement

IEC 60076-1, 10.3

meas. of s/c imp. and load loss IEC 60076-1, 10.4 meas. of no load loss and current at fr and Ur IEC 60076-1, 10.5 dielectric routine tests (for Um>300kV)

IEC 60076-3

LI (for line & neutral, principal and extr. taps)

neg. Ut IEC 60076-3, cl.13 & 14

SI IEC 60076-3, cl.15 ACLD (AC long duration), sine wave>>fr,

100%Utrms(60s) IEC 60076-3, cl.12.4

seperate source AC (applied potential test)

IEC 60076-3, cl.11

seperate source DC volt. withstand incl PD meas.

IEC 601378-2, cl.10

polarity reversal test IEC 601378-2, cl.10 (aux.wiring IEC60076-3, cl.10: 2kV rms) tests on on-load tap- changer (where appropriate) IEC 60076-1, 10.8 meas. insulation resistance IEC 601378-2, cl.10 test of magn. circuit insulation and associated ins. IEC 601378-2, cl.10

Page 30: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Converter Transformer

Tests type tests

temp.rise test

IEC 60076-2, also 5.2.3

dielectric type tests n.a., all tests are routine tests

IEC 60076-3

sound power level

IEC 60076-10

sound power level of cooling equipment

IEC 60076-10

special tests

dielectric special tests (for Um>300kV) (to be agreed about)

see routine tests IEC 60076-3

ACSD (AC short duration), 1ph transformer: ph- gr only, 100%Utest for 60s

1-ph.: U2=1.5*Um/Wurzel(3)

IEC 60076-3, cl.12.2 & 12.3

det.of cap. windings-to-earth and between windings det. of transient volt. transfer characteristics

meas. of zero-seq. imp. on 3-ph. transformers

IEC 60076-1, 10.7

s/c withstand test (test or calc.) calc.: 4.1.2...4.1.5 IEC 60076-5 det. of sound levels IEC 60551 meas. of harmonics of the no load current

IEC 60076-1, 10.6

meas of power taken by fan and oil pump motors

meas. of ins. res. to earth of windings

meas of tan(delta) of the ins. sys. capacitances

losses and imp.(other taps) IEC 60076-1, 10.4+10.5, IEC 61378-1

load current test

IEC 601378-2, cl.10

Page 31: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Standards:

1) IEC 61378-1 (1.0) 1997-09 Converter Transformers –Part I Transformers for Industrial Applications

2) IEC 61378-2 (1.0) 2001-02 Converter Transformers –Part 2 Transformers for HVDC Applications.

3) IEC 61378-3 (under issue) Converter Transformers –Part 3 Application Guide for Converter Transformers

4) IEC 62199: 2004-05 Bushings for DC Application

5) IEEE Std. C57.129-1999 General Requirements and Test code for Oil Immersed HVDC Converter Transformers.

Page 32: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

Standards:

6) IEEE Std. 1158-1991 (R 1996) Recommended Practice for Determination of Power losses in HVDC converter stations.

7) IEEE Std. C57.19.03 - 1996 Standard Requirements, Terminology and Test Code for Bushings for DC applications.

Page 33: HVDC Systems for - USAID SARI/Energy Integration · PDF file• Stray losses in metal-varies as 0.8 of harmonic number • High percentage of harmonic currents in the load current

THANK YOU