GE 275 VPSXGE 275 VPMSX
USE AND MAINTENANCE MANUALSPARE PARTS CATALOGS
842779003 - GB0 2 0 9
25/05/07 84277M00preparato da UPTapprovato da DITE
The unit is composed by : a base, a tank, an engine/alternator unit fixed on the base by 4 elastic dampers,a roll-bar, with hook for an easy and sure lifting, a base complete with doors for a quick access to theengine, to the air filter and to the battery. The set is also equipped with a electrical board where there aremounted protections and measuring instruments, which are protected by a same sized cover.
DESCRIPTION OF THE MACHINE GE 275 VPSXGE 275 VPMSX
M0
© MOSA REV.1-02/09
Main Characteristics of GE 85:• Three-phase electric power (max) 220 kW / 400 V / 50 Hz.• Diesel engine VOLVO PENTA/TAD734GE• Synchronous alternator• Tank of 250l with autonomy of 6.5h• Dimensions / weight, 4000x1300x1950, 3050 Kg (GE 275 VPSX) - 3040 Kg (GE 275 VPMSX)• Noise level at 7m 72 dB(A)• Prepared for automatic start unit.• Prepared for remote start/stop.
MUFFLER
BATTERY
FILTER
EMERGENCYSTOP
CONNECTORFOR EAS ORREMOTE START
Quality systemM01
© MOSA REV.3-02/09
UNI EN ISO 9001 : 2000
10/1
0/02
M01
-GB
MOSA has certified its quality system according toUNI EN ISO 9001:2000 to ensure a constant, highquality of its products. This certification covers thedesign, production and servicing of engine drivenwelders and generating sets.
The certifying institute, ICIM, which is a member ofthe International Certification Network IQNet,awarded the official approval to MOSA after anexamination of its operations at the head office andplant in Cusago (MI), Italy.
This certification is not a point of arrival but a pledgeon the part of the entire company to maintain a levelof quality of both its products and services whichwill continue to satisfy the needs of its clients, aswell as to improve the transparency and thecommunications regarding all the company’s activesin accordance with the official procedures and inharmony with the MOSA Manual of Quality.
The advantages for MOSA clients are:
· Constant quality of products and services at thehigh level which the client expects;
· Continuous efforts to improve the products andtheir performance at competitive conditions;
· Competent support in the solution of problems;
· Information and training in the correct applicationand use of the products to assure the security ofthe operator and protect the environment;
· Regular inspections by ICIM to confirm that therequirements of the company’s quality systemand ISO 9001 are being respected.
All these advantages are guaranteed by theCERTIFICATE OF QUALITY SYSTEM No.0192issued by ICIM S.p.A. - Milano (Italy ) - www.icim.it
INDEX GE 275 VPSXGE 275 VPMSX
M1
© MOSA REV.1-05/08
25/0
5/07
842
77-G
B
M 1.01 COPYRIGHTM 1.1 NOTESM 1.4 CE MARKM 1.5 TECHNICAL DATAM 2 ... SYMBOLS AND SAFETY PRECAUTIONSM 2.5 -… ADVICEM 2.6 INSTALLATION AND ADVICEM 3 UNPACKINGM 4.2 TRANSPORT AND DISPLACEMENTSM 20 SET-UP FOR OPERATIONM 31 CONTROLSM 33.1... USE OF THE GECO CONTROL UNITM 37 -… USING THE GENERATORM 38.6 TCM 35 REMOTE CONTROLM 39.11 EARTH LEAKAGE RELAYM 40.2 TROUBLE-SHOOTINGM 43 -… MAINTENANCE OF THE MACHINEM 45 STORAGEM 46 CUST OFFM 60 ELECTRICAL SYSTEM LEGENDM 61-… ELECTRICAL SYSTEM
Copyright GE_, MS_, TS_, EASM
1.01© MOSA 1.0-10/02
ATTENTION
© All rights are reserved to said Company.
It is a property logo of MOSA division of B.C.S.S.p.A. All other possible logos contained in thedocumentation are registered by the respectiveowners.
➠ The reproduction and total or partial use, in anyform and/or with any means, of thedocumentation is allowed to nobody without awritten permission by MOSA division of B.C.S.S.p.A.
To this aim is reminded the protection of the author’sright and the rights connected to the creation anddesign for communication, as provided by the lawsin force in the matter.
In no case MOSA division of B.C.S. S.p.A. will beheld responsible for any damaga, direct or indirect,in relation with the use of the given information.
MOSA division of B.C.S. S.p.A. does not take anyresponsibility about the shown information on firmsor individuals, but keeps the right to refuse servicesor information publication which it judges discutible,unright or illegal.
10/1
0/02
M1-
01-G
B
This use and maintenance manual is an importantpart of the machines in question.The assistance and maintenance personel mustkeep said manual at disposal, as well as that forthe engine and alternator (if the machine issynchronous) and all other documentation about themachine.
We advise you to pay attention to the pagesconcerning the security (see page M1.1).
INFORMATION
Dear Customer,We wish to thank you for having bought fromMOSA a high quality set.
Our sections for Technical Service and SpareParts will work at best to help you if it werenecessary.
To this purpose we advise you, for all control andoverhaul operations, to turn to the nearestauthorized Service Centre, where you will obtaina prompt and specialized intervention.
☞ In case you do not profit on these Services andsome parts are replaced, please ask and besure that are used exclusively original MOSAparts; this to guarantee that the performancesand the initial safety prescribed by the norms inforce are re-established.
☞ The use of non original spare parts will cancelimmediately any guarantee and Technical Ser-vice obligation from MOSA.
NOTES ABOUT THE MANUALBefore actioning the machine please read thismanual attentively. Follow the instructionscontained in it, in this way you will avoidinconveniences due to negligence, mistakes orincorrect maintenance. The manual is for qualifiedpersonnel, who knows the rules: about safety andhealth, installation and use of sets movable aswell as fixed.
You must remember that, in case you havedifficulties for use or installation or others, ourTechnical Service is always at your disposal forexplanations or interventions.
The manual for Use Maintenance and Spare Partsis an integrant part of the product. It must be keptwith care during all the life of the product.In case the machine and/or the set should beyielded to another user, this manual must alsogiven to him.Do not damage it, do not take parts away, do nottear pages and keep it in places protected fromdampness and heat.
You must take into account that some figurescontained in it want only to identify the describedparts and therefore might not correspond to themachine in your possession.
INFORMATION OF GENERAL TYPE
In the envelope given together with the machineand/or set you will find: the manual for UseMaintenance and Spare Parts, the manual foruse of the engine and the tools (if included in theequipment), the guarantee (in the countries whereit is prescribed by law).
Our products have been designed for the use ofgeneration for welding, electric and hydraulicsystem; ANY OTHER DIFFERENT USE NOTINCLUDED IN THE ONE INDICATED, relievesMOSA from the risks which could happen or,anyway, from that which was agreed when sellingthe machine; MOSA excludes any responsibilityfor damages to the machine, to the things or topersons in this case.
Our products are made in conformity with thesafety norms in force, for which it is advisable touse all these devices or information so that theuse does not bring damage to persons or things.
While working it is advisable to keep to thepersonal safety norms in force in the countries towhich the product is destined (clothing, work tools,etc.).
Do not modify for any motive parts of the machine(fastenings, holes, electric or mechanical devices,others..) if not duly authorized in writing by MOSA:the responsibility coming from any potentialintervention will fall on the executioner as in facthe becomes maker of the machine.
Notes GE_, MS_, TS_, EAS_M
1-1© MOSA 1.0-10/02
☞ Notice: this manual does not engage MOSA,who keeps the faculty, apart the essentialcharacteristics of the model here described andillustrated, to bring betterments and modificationsto parts and accessories, without putting thismanual uptodate immediately.
10/1
0/02
M 1
-1 G
B
CE MARKM
1.4© MOSA REV.4-10/07
10/1
0/02
M1-
4 G
B
Any of our product is labelled with CE marking attesting its conformity to appliable directivesand also the fulfillment of safety requirements of the product itself; the list of these directives ispart of the declaration of conformity included in any machine standard equipment.Here below the adopted symbol:
CE marking is clearly readable and unerasable and it can be either part of the data-plate (A) orplaced as a sticker near the data-plate (B)
A B
Furthermore, on each model it is shown the noise level value; the symbol used is the following:
The indication is shown in a clear, readable and indeleble way on a sticker.
GE 275 VPSXGE 275 VPMSX© MOSA REV.2-02/09
M1.5Technical data
The generating set GE 275 is a unit which transforms the mechanical energy, generated by endothermic engine, into electricenergy, through an alternator.Is meant for industrial and professional use, powered by an endothermic engine; it is composed of various main parts such as:engine, alternator, electric and electronic controls, the fairing or a protective structure.The assembling is made on a steel structure, on which are provided elastic support which must damp the vibrations and alsoeliminate sounds which would produce noise.
Technical data GE 275 VPSX GE 275 VPMSXGENERATOR
Power (*stand by) 275 kVA / 400 V / 397 APower (**P.R.P.) 250 kVA / 400 V / 361 AActive power (*stand by) 220 kW / 400 V / 318 AActive power (**P.R.P.) 220 kW / 400 V / 289 AFrequency 50 HzCos ϕϕϕϕϕ 0.8
ALTERNATOR Self-excited, self-regulated with AVRtype three-phase, synchronousInsulation class H
ENGINEMake / Model VOLVO PENTA / TAD734GEType / Cooling system Diesel Turbo-common rail / LiquidCylinders / Displacement 6 on line / 7150 cm3
Power (*stand by) 241 kW (327 CV)Power (**P.R.P.) 216 kW (293 CV)Speed 1500 rpmFuel consumption 204 g/kWhCooling system capacity 32 lEngine oil capacity 24 lStarter Electric
GENERAL SPECIFICATIONSBattery 24V (2x12V - 100Ah)Tank capacity 250 lRunning time (75%) 6.5 hProtection IP 44Dimensions / max. on base Lxwxh (mm) * 4000x1300x1950Weight on base 3050 Kg 3040 KgMeasured acoustic power 97 LWA (72 db(A) - 7 m) 97 LWA (72 db(A) - 7 m)Garanteed acoustic power 97 LWA (72 db(A) - 7 m) 97 LWA (72 db(A) - 7 m)* Dimensions and weight are inclusive of all parts
25/0
5/07
842
77-G
B
OUTPUTDeclared power according to ISO 8528-1 (temperature 25°C, 30% relative humidity, altitude 100 m above sea level).(*Stand-by) = maximum available power for use at variable loads for a yearly number of hours limited at 500 h. No overload isadmitted.(**Prime power P.R.P.) = maximum available power for use at variable loads for a yearly illimited number of hours. The averagepower to be taken during a period of 24 h must not be over 80% of the P.R.P.It’s admitted overload of 10% each hour every 12 h.In an approximative way one reduces: of 1% every 100 m altitude and of 2.5% for every 5°C above 25°C.
ACOUSTIC POWER LEVELATTENTION: The concrete risk due to the machine depends on the conditions in which it is used. Therefore, it is up to the end-user and under his direct responsibility to make a correct evaluation of the same risk and to adopt specific precautions (forinstance, adopting a I.P.D. -Individual Protection Device)Acoustic Noise Level (LWA) - Measure Unit dB(A): it stands for acoustic noise released in a certain delay of time. This is notsubmitted to the distance of measurement.Acoustic Pressure (Lp) - Measure Unit dB(A): it measures the pressure originated by sound waves emission. Its valuechanges in proportion to the distance of measurement.The here below table shows examples of acoustic pressure (Lp) at different distances from a machine with Acoustic NoiseLevel (LWA) of 95 dB(A)
Lp a 1 meter = 95 dB(A) - 8 dB(A) = 87 dB(A) Lp a 7 meters = 95 dB(A) - 25 dB(A) = 70 dB(A)Lp a 4 meters = 95 dB(A) - 20 dB(A) = 75 dB(A) Lp a 10 meters = 95 dB(A) - 28 dB(A) = 67 dB(A)
PLEASE NOTE: the symbol when with acoustic noise values, indicates that the device respects noise emission limitsaccording to 2000/14/CE directive.
2000 / 14 / CE
2000 / 14 / CE
2000 / 14 / CE
SYMBOLS AND SAFETY PRECAUTIONS GE_, MS_, TS_M2
© MOSA 1.0-11/99
SYMBOLS IN THIS MANUAL
- The symbols used in this manual are designed to callyour attention to important aspects of the operation ofthe machine as well as potential hazards and dangersfor persons and things.
IMPORTANT ADVICE
- Advice to the User about the safety:
☞ N.B.: The information contained in the manual canbe changed without notice.Potential damages caused in relation to the use ofthese instructions will not be considered becausethese are only indicative.Remember that the non observance of theindications reported by us might cause damage topersons or things.It is understood, that local dispositions and/or lawsmust be respected.
WARNING
Situations of danger - no harm to personsor things
Do not use without protective devices providedRemoving or disabling protective devices on themachine is prohibited.
Do not use the machine if it is not in good technicalconditionThe machine must be in good working order beforebeing used. Defects, especially those which regardthe safety of the machine, must be repaired beforeusing the machine.
SAFETY PRECAUTIONS
This heading warns of an immediate danger for personsas well for things. Not following the advice can result inserious injury or death.
This heading warns of situations which could result ininjury for persons or damage to things.
To this advice can appear a danger for persons as well asfor things, for which can appear situations bringing mate-rial damage to things.
These headings refer to information which will assis youin the correct use of the machine and/or accessories.
ATTENTION
NOTE
IMPORTANT
CAUTION
WARNING
DANGEROUS
26/1
1/99
M2G
B
SYMBOLS AND SAFETY PRECAUTIONS GE_, MS_, TS_M
2-1© MOSA 1.1-04/03
SYMBOLS (for all MOSA models)
STOP - Read absolutely and be duly attentive
Read and pay due attention
GENERAL ADVICE - If the advice is notrespected damage can happen to persons orthings.
HIGH VOLTAGE - Attention High Voltage.Therecan be parts in voltage, dangerous to touch.The non observance of the advice implies lifedanger.
FIRE - Danger of flame or fire. If the advice isnot respected fires can happen.
HEAT - Hot surfaces. If the advice is notrespected burns or damage to things can becaused.
EXPLOSION - Explosive material or danger ofexplosion. in general. If the advice is notrespected there can be explosions.
WATER - Danger of shortcircuit. If the adviceis not respected fires or damage to personscan be caused.
SMOKING - The cigarette can cause fire orexplosion. If the advice is not respected firesor explosions can be caused.
ACIDS - Danger of corrosion. If the advice isnot respected the acids can cause corrosionswith damage to persons or things.
WRENCH - Use of the tools. If the advice isnot respected damage can be caused to thingsand even to persons.
PRESSION - Danger of burns caused by theexpulsion of hot liquids under pressure.
PROHIBITIONS No harm for persons
Use only with safety clothing -It is compulsory to use the personalprotection means given in equipment.
Use only with safety clothing -It is compulsory to use the personal protectionmeans given in equipment.
Use only with safety protections -It is a must to use protection means suitable forthe different welding works.
Use with only safety material -It is prohibited to use water to quench fires onthe electric machines.
Use only with non inserted voltage -It is prohibited to make interventions beforehaving disinserted the voltage.
No smoking -It is prohibited to smoke while filling the tankwith fuel.
No welding -It is forbidden to weld in rooms containingexplosive gases.
ADVICE No harm for persons and things
Use only with safety tools, adapted to the specificuse -It is advisable to use tools adapted to the variousmaintenance works.
Use only with safety protections, specifically suitableIt is advisable to use protections suitable forthe different welding works.
Use only with safety protections -It is advisable to use protections suitablefor the different daily checking works.
Use only with safety protections -It is advisable to use all protections whileshifting the machine.
Use only with safety protections -It is advisable to use protections suitable forthe different daily checking works.and/or ofmaintenance.
26/1
1/99
M2-
1GB
ACCES FORBIDDEN to non authorizad peaple.
INSTALLATION AND ADVICE BEFORE USE GE_, MS_, TS_M
2-5© MOSA 1.0-06/00
Stop engine when fueling
ENG
INE
CH
ECK
ING
BO
AR
D
Do not touch electric devices if youare barefoot or with wet clothes.
Always keep off leaning surfacesduring work operations
Static electricity can demage theparts on the circuit.
An electric shock can kill
The installation and the general advice concerning the operations, are finalized to the correct use of themachine, in the place where it is used as generator group and/or welder.
☞ FIRST AID. In case the operator shold be sprayed by accident, from corrosive liquids a/o hot toxic gasor whatever event which may cause serious injuries or death, predispose the first aid in accordance withthe ruling labour accident standards or of local instructions.
Skin contactEyes contactIngestionSuction of liquids fromlungsInhalation
Wash with water and soapIrrigate with plenty of water, if the irritation persists contact a specialistDo not induce vomit as to avoid the intake of vomit into the lungs, send for a doctorIf you suppose that vomit has entered the lungs (as in case of spontaneous vomit) take thesubject to the hospital with the utmost urgencyIn case of exposure to high concentration of vapours take immediately to a non polluted zonethe person involved
☞ FIRE PREVENTION. In case the working zone,for whatsoever cause goes on fire with flames liable tocause severe wounds or death, follow the first aid as described by the ruling norms or local ones.
AppropriatedNot to be usedOther indications
Particular protectionUseful warnings
Carbonate anhydride (or carbon dioxyde) powder, foam, nebulized waterAvoid the use of water jetsCover eventual shedding not on fire with foam or sand, use water jets to cool off thesurfaces close to the fireWear an autorespiratory mask when heavy smoke is presentAvoid, by appropriate means to have oil sprays over metallic hot surfaces or over electriccontacts (switches,plugs,etc.). In case of oil sprinkling from pressure circuits, keep inmind that the inflamability point is very low.
EXTINCTION MEANS
WARNING CAUTION
DANG
ERO
US
WARNINGTHE MACHINE MUST NOT BE USED IN AREAS WITH
EXPLOSIVE ATMOSPHERE
10/0
6/00
M2-
5I
Do not smoke, avoid flames, sparks or electric tools when fueling.
Unscrew the cap slowly to let out the fuel vapours.
Slowly unscrew the cooling liquid tap if the liquid must be topped up.
The vapor and the heated cooling liquid under pressure can burn face, eyes, skin.
Do not fill tank completely.Wipe up spilled fuel before starting engine.Shut off fuel of tank when moving machine (where it is assembled).Avoid spilling fuel on hot engine.Sparks may cause the explosion of battery vapours
INSTALLATION AND ADVICEM
2.6© MOSA REV.1-06/07
INSTALLATION AND ADVICE BEFORE USE
GASOLINE ENGINES■ Use in open space, air swept or vent exhaust gases,
which contain the deathly carbone oxyde, far fromthe work area.
DIESEL ENGINES■ Use in open space, air swept or vent exhaust gases
far from the work area.
POSITIONPlace the machine on a level surface at a distance of atleast 1,5 m from buildings or other plants.
Check that the air gets changed completely and the hotair sent out does not come back inside the set so as tocause a dangerous increase of the temperature.
☞ Make sure that the machine does not move duringthe work: block it possibly with tools and/or devicesmade to this purpose.
Maximum leaning of the machine (in case of dislevel)
26/1
1/99
M2-
6GB
1,5 m
1,5 m
1,5m
GAS DI SCARICO
EXHAUST OUTPUT
MOVES OF THE MACHINE☞ At any move check that the engine is off, that there
are no connections with cables which impede themoves.
PLACE OF THE MACHINE
ATTENTIONFor a safer use from the operator DO NOTfit the machine in locations with high risk offlood.Please do not use the machine in weatherconditions which are beyond IP protectionshown both in the data plate and on pagenamed "technical data" in this same manual.
InstallazioneInstallationInstallation
LuftzirkulationInstalación GE 275 VPSX
GE 275 VPMSX
M2.7
© MOSA REV.1-04/08
25/0
5/07
842
77-I
M1.4
M1.4 B
UNPACKING GE_, MS_, TS_M3
© MOSA 1.1-02/04
NOTE
☞ Be sure that the lifting devices are: correctly mounted,adequate for the weight of the machine with it’spackaging, and conforms to local rules and regula-tions.When receiving the goods make sure that the prod-uct has not suffered damage during the transport,that there has not been rough handling or takingaway of parts contained inside the packing or in theset.In case you find damages, rough handling or ab-sence of parts (envelopes, manuals, etc.), we ad-vise you to inform immediately our Technical Ser-vice.
For eliminating the packing materials, the Usermust keep to the norms in force in his country.
1) Take the machine (C) out of the shipment packing.Take out of the envelope (A) the user’s manual (B).
2) Read: the user’s manual (B), the plates fixed on themachine, the data plate.
30/0
3/00
M3G
B
TRANSPORT AND DISPLACEMENTS COVERED UNITS AND SKID GE_, MS_, TS_M
4-2© MOSA 1.0-03/00
NOTEIn case you should transport or move the machine, keep to the instructions as per the figures.Make the transportation when the machine has no petrol in its tank, no oil in the engine and and electrolyte in thebattery.Be sure that the lifting devices are: correctly mounted, adequate for the weight of the machine with it’s packaging, andconform to local rules and regulations.Only authorized persons involved in the transport of the machine should be in the area of movement.
DO NOT LOAD OTHER PARTS WHICH CAN MODIFY WEIGHT AND BARICENTER POSITION.IT IS STRICTLY FORBIDDEN TO DRAG THE MACHINE MANUALLY OR TOW IT BY ANY VEHICLE (model with noCTL accessory).If you did not keep to the instructions, you could damage the structure of the machine.
30/0
3/00
M4G
B
Set-up for operation TS_,DSP_,GEWater cooled systems
M20
© MOSA 1.1-09/05
12/0
6/03
M20
-R-H
O2-
GB
LUBRICANT
RECOMMENDED OILMOSA recommends selecting AGIP engine oil.Refer to the label on the motor for the recommendedproducts.
REFUELLING AND CONTROL:Carry out refuelling and controls with motor at levelposition.1. Remove the oil-fill tap (24)2. Pour oil and replace the tap3. Check the oil level using the dipstick (23); the oil
level must be comprised between the minimumand maximum indicators.
Please refer to the motor operating manual for therecommended viscosity.
AIR FILTER
Check that the dry air filter is correctly installed andthat there are no leaks around the filter which couldlead to infiltrations of non-filtered air to the inside ofthe motor.
It is dangerous to fill the motor with too much oil,as its combustion can provoke a sudden increasein rotation speed.
ATTENTION
BATTERY WITHOUT MAINTENANCE
Connect the cable + (positive)to the pole + (positive) of thebattery (after having takenaway the protection), byproperly tightening the clamp.
Check the state of the batteryfrom the colour of the warning light which is in theupper part.
- Green colour: battery OK- Black colour: battery to be recharged- White colour: battery to be replacedDO NOT OPEN THE BATTERY.
FUEL
Do not smoke or use open flames duringrefuelling operations, in order to avoidexplosions or fire hazards.Fuel fumes are highly toxic; carry outoperations outdoors only, or in a well-ventilated environment.Avoid accidentally spilling fuel. Cleanany eventual leaks before starting upmotor.
ATTENTION
Refill the tank with good quality diesel fuel, such asautomobile type diesel fuel, for example.
For further details on the type of diesel fuel to use,see the motor operating manual supplied.
Do not fill the tank completely; leave a space ofapprox. 10 mm between the fuel level and the wallof the tank to allow for expansion.
In rigid environmental temperature conditions, usespecial winterized diesel fuels or specific additivesin order to avoid the formation of paraffin.
Set-up for operation TS_,DSP_,GEWater cooled systems
M20.1
© MOSA 1.0-06/03
12/0
6/03
M20
-R-H
O2-
GB
COOLING LIQUID
Remove the tap and pour the liquid coolant into theradiator; the quantity and composition of the liquidcoolant are indicated in the motor operating manual.Replace the tap, ensuring it is perfectly closed.After refilling operations, allow the motor to run fora brief time and check the level, as it may havediminished due to air bubbles present in the coolingcircuit; restore the level with water.To replace the liquid coolant, follow the operationsdescribed in the motor operating manual.
Do not remove the radiator tap with themotor in operation or still hot, as the liquidcoolant may spurt out and cause seriousburns. Remove the tap very carefully.
GROUNDING CONNECTION
The grounding connection to an earthed installationis obligatory for all models equipped with adifferential switch (circuit breaker). In these groupsthe generator star point is generally connected tothe machine’s earthing; by employing the TN or TTdistribution system, the differential switchguarantees protection against indirect contacts.In the case of powering complex installationsrequiring or employing additional electrical protectiondevices, the coordination between the protectiondevices must be verified.For the grounding connection, use the terminal(12); comply to local and/or current regulations inforce for electrical installations and safety.
ATTENTION
ComandiControlsCommandes
GE 275 VPSXGE 275 VPMSX
M31
© MOSA REV.0-06/07
Pos. Descrizione Description DescriptionQ3R3L5D6A7
C7E7N7S7
MuffolaAvvisatore acusticoPulsante stop emergenzaConnettore PACSelettore travaso pompa AUT-0-MANControllo gruppo elettr. “GECO”Potenz. regolatore di tensioneSelettore OFF-ON-DIAGN.Spina 230V monofase
Planche à bornes prélèv. puissanceAvertisseur sonoreBouton d’urgenceConnecteur PACSélecteur transvasement pompe AUT-0-MANContrôle groupe électrogene "GECO"Potentiomètre régulateur de tensionSélecteur OFF-ON DIAGNFiche 230V monophasée
DescripciónTerminal obtención potenciaSirenaPulsador emergenciaConector PACSelector trasvase bomba AUTO/0/MANControl grupo electrógeno "GECO"Potenc. regulador de tensiónSelector OFF-ON DIAGNEnchufe 230V monofásico
Mandos
Output power unitElectric sirenEmergency stop buttonConnector, PACTransfer pump selector AUT-0-MAN“GECO” generating set testVoltmeter regulatorOFF-ON-DIAGN. selectorPlug 230V singlephase
25/0
5/07
842
77-I
N7C7
A7 (Option)
(Option)
E7
TEST AUT MAN RESET
START STOP
HELP
MAINS GEN
ENTER EXIT
GECO
SWITCH BOARDONOFF DIAGN.
AUT MAN
0
FUEL PUMP
Volt
MANUAL VERSIONAUTOMATIC VERSION
Q3 R3 L5 D6 (Option) S7
USE GE 225 - 275 VPS - VPSXM33
© MOSA 1.0-09/02
INTRODUCTION
The “GECO” equipment entails a control unit for absolutelymodern generators. Its strong holds are the following:
- Large-size graphical display (95x45 mm) to be able to displayall the electrical parameters at the same time (with charactersof 10mm).
- The membrane keyboard has built-in keys with relativeindicator LEDs. It also offers a high degree of reliability andideal touch-sensitive keys.
- The HELP key with relative LED that flashes to point out thata message is to be read
- The use of the dater clock to set the weekly TEST and todisplay all the events that occur and that may be shown onthe Display.
- The control of 4 different mains/generator line systems:• N-L1-L2-L3• L1-L2-L3• L1-N-L2 (AMERICAN market)• N-L1
- Operational temperature range from -20 to + 60°C- Protection rating IP64- 5 possible languages: Italian-English-French-German-
Spanish- Generator protection against OVERLOADS and SHORT-
CIRCUITS with setting of the rated current of the generator,setting of the short-circuit current in percentage of the ratedcurrent value of the generator and a tripping delay timing ofthe protection device in tenths of a second.
Parameters Displayed
The LCD shows data and information in graphic andalphanumeric forms. Press the “⇓⇓⇓⇓⇓” or “⇑⇑⇑⇑⇑” keys to view the datapages. Press the “–” or “+” keys to see alternative data on thesame page.N.B. on the display it appears MAINS or GENERATOR forshowing to whom the measure are referred.
The measure on the display are the followings:
- Battery voltage- Mains and phase generator voltages, between the lines
and of the system- Phase currents- Phase and total active, reactive and apparent powers.- Active, reactive and apparent energy.- P.F. - Power factor of each phase.- Energy contact maker- Frequency of the generator.- Oil pressure instrument- Water temperature instrument- Fuel level instrument- Engine RPM- Number of successful starting attempts- Number of failed starting attempts- Number of total starting attempts- Total hours of use- Partial hours of use- Hours left to maintenance
KEYBOARD
HELP key – The illuminated LED means a help message isavailable. By pressing the key, a help message concerning thecurrent operation is displayed.ENTER and EXIT keys - Press ENTER to confirm operationsor to enter the menu. Press EXIT to refuse an operation or toexit a menu and help message.“⇓⇓⇓⇓⇓” and “⇑⇑⇑⇑⇑” arrow keys – Press these keys to shift to thedifferent pages of data display or to select parameters.“–” and “+” keys – Press these keys to display alternativedata of the selected data page or to modify the parameters.OFF/RESET, MAN, AUT and TEST keys – Press these keysto select the operating mode. The illuminated LED indicatesthe selected operating mode; if it is flashing, remote control isactive.
03/0
9/02
842
75-G
B
START and STOP keys – These work in MAN operatingmode only, used to start and stop the engine. By quicklypressing the START key, one start attempt takes place; bykeeping the START key pressed, the duration of the startattempts can be extended. The flashing LED of the enginesymbol denotes engine started, with alarms inhibited; and isconstantly on at the end of the alarms inhibition time. Theengine can be stopped using the OFF/RESET key.MAINS and GEN keys – They work in MAN operating modeonly, used to switch the load from mains to generator and viceversa. The illuminated LEDs of the mains and generatorsymbols indicate the respective voltages are within presetlimits. The illuminated LEDs of the changeover symbols indicatethe actual closing of switching devices; when flashing, there isa incorrect feed-back signal for the actual closing or openingof the switching devices.
OPERATING MODE
OFF/RESET mode – The engine can not operate. If the mainsis present, the load is switched to the mains. Changing fromTEST, AUT or MAN to the OFF/RESET mode and if the engineis running, the engine is immediately stopped and eventualalarms are reset. If the cause of the alarm is still present, it cannot be reset.MAN mode – The engine can be manually started or stoppedusing the START and STOP keys only in addition to loadswitching from mains to generator and vice versa, by means ofthe MAINS and GEN keys. Always in MAN mode, at the startcommand and by keeping the key pressed, the preset startingtime can be prolonged while at the stop command and bykeeping the key pressed for more than 6 seconds, the fuelvalve is discharged for 4 minutes.AUT mode – In case of mains not present (out of the presetlimits), the engine automatically starts or stops when themains returns.TEST mode – The engine immediately starts even if themains is present. In case the mains is not present, the load isswitched to the generator. Changing to the AUT mode and ifthe mains is present, the engine will stop.
AlarmsWhen an alarm arises, the lower section of the display is usedto view it. In case of two alarms or more, they are individuallyshown in sequence. A help message is available for everyalarm, in order to locate the possible alarm source. Alarmconditions can be reset by means of the OFF/RESET key, thatprevent any unintentional engine starting at the alarm resetoperation. If the alarm does not reset, this means the cause ofthe alarm is still present. During event-log sessions and set-upoperations, no alarms are viewed.
USE GE 225 - 275 VPS - VPSXM
33.1
© MOSA 1.0-09/02
03/0
9/02
842
75-G
B
USE GE 225 - 275 VPS - VPSXM
33.2
© MOSA 1.0-09/02
LIST OF THE ALARMS GECO
A01 Engine temperature warning (analog sensor)A02 High engine temperature (analog sensor)A03 Temperature analog sensor faultA04 High engine temperature (digital sensor)A05 Oil pressure warning(analog sensor)A06 Low oil pressure (analog sensor)A07 Pressure analog sensor faultA08 Low oil pressure (digital sensor)A09 Pressure digital sensor faultA10 Fuel level warning(analog sensor)A11 Low fuel level(analog sensor)A12 Level analog sensor faultA13 Low fuel level(digital sensor)A14 High battery voltageA15 Low battery voltageA16 Inefficient batteryA17 Charger alternator failureA18 “W” signal failureA19 Low engine “W” speedA20 High engine “W” speedA21 Starting failureA22 Emergency stopA23 Unexpected stopA24 Engine stop failureA25 Low generator frequencyA26 High generator frequencyA27 Low generator voltageA28 High generator voltageA29 Generator asymmetryA30 Generator short-circuitA31 Generator overloadA32 External generator protection trippingA33 Incorrect generator phase sequenceA34 Incorrect mains phase sequenceA35 Wrong system frequency settingA36 Generator contactor failureA37 Mains contactor failureA38 Maintenance requestedA39 System errorA40 Fuel transfer emptyA41 Fuel transfer too fullA42 Rent hours exhausted
UA1 Earth leakage relay protectionUA2 User’s alarm 2UA3 User’s alarm 3UA4 User’s alarm 4
N.B.: MOSA enables the alarms and sets their intervention characteristics according to the type of generatingset.
03/0
9/02
842
75-G
B
USE GE 225 - 275 VPS - VPSXM
33.3
© MOSA 1.0-09/02
TECHNICAL CHARACTERISTICS GECO
Power supplyBattery rated voltage 12 or 24VDC indifferentlyVoltage range 9÷33VDCMinimum voltage at the starting 6,7VDCMaximum current consumption 320mA at 12VDC and
160mA at 24VDCStand-by current 150mA at 12VDC and
75mA at 24VDCMicro interruption immunity 200ms
Digital inputInput type negativeCurrent input ≤10mAInput “low” voltage ≤1,5V (typical 2,9V)Input “high” voltage ≥5,3V (typical 4,3V)Input delay ≥50ms
Speed input “W”Input type AC couplingVoltage range 5÷50VppFrequency range 40÷2000Hz
Engine running input (500rpm) for permanent magnetgeneratorVoltage range 0÷40VAC
Engine running input (500rpm) for pre-excited generatorVoltage range 0÷40VDCMaximum input current 12mAMaximum voltage at +D terminal 12 or 24VDC (battery
voltage)Pre-excitation current 170mA at 12VDC or
130mA at 24VDC
Relay output 4.1-4.2 / 4.3-4.4 terminals (voltage free)Contact type 1 NC for mains 1 NO for
generatorRated voltage 250VAC (440VAC max)Rated current at 250VAC 8A AC1 (2A AC15)
Relay output 5.3-5.4-5.5 terminals (voltage free)Contact type 1 changeoverRated voltage 250VAC maxRated current at 250VAC 8A AC1 (2A AC15)
Relay output 6.2 / 6.3 / 6.4 / 6.5 terminals (+ batteryvoltage output)Contact type 1 NORated voltage 30VDCRated current at 30VDC 5A DC1
Analog inputsPressure sensor current 20mA maxTemperature sensor current 7mA maxLevel sensor current 10mA maxAnalog ground voltage -0,5V÷+0,5V
Voltage inputsMaximum rated voltage Ue 480VAC L-L (277VAC L-
N)Measuring range 50÷620V L-L (358VAC L-
N)Frequency range 45 ÷65HzMeasuring method True RMSMeasuring input impedance >1,1MW L-L >570kW L-
NWiring mode 1, 2 or 3 phases, with or
without neutral
Current inputsRated current Ie 5AMeasuring range 0,02÷6AMeasuring method True RMSOverload capacity +20% IeOverload peak 50A for 1 secondPower consumption <0,3VA
Measuring charateristics (-10÷÷÷÷÷+45°C)Voltage ±1% ±1digitFrequency ±0,2% ±1digitCurrent ±1% ±1digitPower ±2% ±1digitEnergy ±2% ±1digit
Ambient operating conditionsOperating temperature -20÷+60°CStorage temperature -30÷+80°CRelative humidity <90%Maximum pollution degree 3
ConnectionsTerminal type Plug-inCable cross section (min e max) 0,2÷÷÷÷÷2,5 mmq (24÷÷÷÷÷12AWG)Tightening torque 0,8 Nm (7 LBin)
HousingVersion Flush mountDimensions 196,5x106,5x120mmPanel cutout 181x91mmMaterial Noryl SE100
thermoplasticDegree of protection IP64 on frontWeight 750g
03/0
9/02
842
75-G
B
Functional characteristics testHeating testElectrical tests
EMC testImunity testsSurgesfast transient/bursts
irradiated electro-magnetic fielddriver electro-magentic fieldElectrostatic discharge
Emission testsRadiofrequency driver emissionRadiofrequency irradiated emission
CollisionSinusoidal vibrationsSalty mist
Z/ABDM climatic sequence
IEC/EN 60255-6 (’94)IEC/EN 60255-6 (’94)IEC 60664-1 (’92)
IEC/EN 61000-4-5 (’95)IEC/EN 61000-4-4 (’95)
IEC/EN 61000-4-3 (’96)IEC/EN 61000-4-6 (’96)IEC/EN 60255-22-2 (’96)
IEC/EN 55011 (’98)IEC/EN 55011 (’98)IEC/EN 60255-21-2 (’95)IEC/EN 60068-2-6 (LLOYD)RINA regulation (sect. E chap. 3)or IEC/EN 60068-2-52 (’96)IEC/EN 60068-2-61 (’93)
Sect. 3, par. 13 of the standardSect. 3, par. 15 of the standard• 4 kV (1.2/50 s): 3 pulses + and 3 pul-ses – with gap of at least 1 s• 2500 (50Hz): 1 min.
2kV (CM) - 1kV (DM)2kV on power supply and output - 1 kVon controls10 V/m10V8kV (air) - 6kV (contact)
class A of the standardclass A of the standardclass 2 of the standardV1According to RINA regulation (pastedition) or level 2 of the standardTemperatures according to storage limitsand operational limits
USE GE 225 - 275 VPS - VPSXM
33.4
© MOSA 1.0-09/02
Type of test/check Reference standard /regulation
Test parameters
ACQUIRED HOMOLOGATIONS GECO
03/0
9/02
842
75-G
B
USE GE 225 - 275 VPS - VPSXM
33.5
© MOSA 1.0-09/02
Terminal board connections (seen from rear)
Overall dimensions03
/09/
02 8
4275
-GB
Using the generatorM37
© MOSA 1.1-09/05
12/0
6/03
M37
GB
_150
0G_G
E
WARNING
Access forbidden to area adjacent toelectricity-generating group for all non-authorized personnel.
It is absolutely forbidden to connect the unitto the public mains and/or another electricalpower source .
GE_Diesel engine
The electricity-generating groups are to be consideredelectrical energy producing stations.The dangers of electrical energy must be consideredtogether with those related to the presence of chemicalsubstances (fuels, oils, etc.), rotating parts and wasteproducts (fumes, discharge gases, heat, etc.).
GENERATION IN AC (ALTERNATING CURRENT)Before each work session check the efficiency of theground connection for the electricity-generating group ifthe distribution system adopted requires it, such as, forexample, the TT and TN systems.
Check that the electrical specifications for the units tobe powered - voltage, power, frequency - are compatiblewith those of the generator. Values that are too high ortoo low for voltage and frequency can damage electricalequipment irreparably.In some cases, for the powering of three-phase loads, itis necessary to ensure that the cyclic direction of thephases corresponds to the installation’s requirements.
Connect the electric devices to be powered to the ACsockets, using suitable plugs and cables in primecondition.
Before starting up the group, make certain no dangeroussituations exist on the installation to be powered.Check that the thermal-magnetic switch (Z2) is in theOFF position (input lever in downward position).
Start up the electricity-generating group, positioning thethermal-magnetic switch (Z2) and differential switch (D)to ON (input lever in upward position).Before powering on the utilities, check that the voltmeter(N) and frequency meter (E2) indicate nominal values;in addition, check on the voltmeter change-over switch(H2) (where it is assembled) that the three line voltagesare the same.☞ In the absence of a load, the values for voltage andfrequency can be greater than their nominal values.See sections on VOLTAGE and FREQUENCY.
OPERATING CONDITIONS
POWERThe electrical power expressed in kVA on an electricity-generating group is the available output power to thereference environmental conditions and nominal valuesfor: voltage, frequency, power factors (cos ϕ).
There are various types of power: PRIME POWER (PRP),STAND-BY POWER established by ISO 8528-1 and3046/1 Norms, and their definitions are listed in themanual’s TECHNICAL SPECIFICATIONS page.
☞ During the use of the electricity-generating groupNEVER EXCEED the power indications, paying carefulattention when several loads are poweredsimultaneously.
VOLTAGEGENERATORS WITH COMPOUND SETTING.In these types of generators, the no-load voltage isgenerally greater than 3–5% with respect to its nominalvalue; f.e. for nominal voltage, threephase 400Vac orsinglephase 230Vac, the no-load voltage can becomprised between 410-420V (threephase) and 235-245V(singlephase). The precision of the load voltage ismaintained within ±5% with balanced loads and with arotation speed variation of 4%. Particularly, with resistiveloads (cos ϕ = 1), a voltage over-elevation occurs which,with the machine cold and at full load, can even attain+10 %, a value which in any case is halved after the first10-15 minutes of operation.The insertion and release of the full load, under constantrotation speed, provokes a transitory voltage variationthat is less than 10%; the voltage returns to its nominalvalue within 0.1 seconds.
GENERATORS WITH ELECTRONIC SETTING(A.V.R.).In these types of generators, the voltage precision ismaintained within ±1,5%, with speed variationscomprised from -10% to +30%, and with balanced loads.The voltage is the same both with no-load and withload; the insertion and release of the full load provokesa transitory voltage variation that is less than 15%; thevoltage returns to its nominal value within 0.2–0.3seconds.
FREQUENCYThe frequency is a parameter that is directly dependenton the motor’s rotation speed. Depending on the type ofalternator, 2 or 4 pole, we will have a frequency of 50/60Hz with a rotation speed of 3000/3600 or 1500/1800revolutions per minute.The frequency, and therefore the number of motorrevolutions, is maintained constant by the motor’s speedregulation system.Generally, this regulator is of a mechanical type andpresents a droop from no-load to nominal load which isless than 5 % (static or droop), while under staticconditions precision is maintained within ±1%.Therefore,for generators at 50Hz the no-load frequency can be52–52.5 Hz, while for generators at 60Hz the no-loadfrequency can be 62.5-63Hz.
Using the generatorM
37.1
© MOSA 1.1-09/05
GE_Diesel engine
In some motors or for special requirements the speedregulator is electronic; in these cases, precision understatic operating conditions attains ±0.25%, and thefrequency is maintained constant in operation from no-load to load (isochronal operation).
POWER FACTOR - COS ϕϕϕϕϕThe power factor is a value which depends on the load’selectrical specifications; it indicates the ratio betweenthe Active Power (kW) and Apparent Power (kVA). Theapparent power is the total power necessary for the load,achieved from the sum of the active power supplied bythe motor (after the alternator has transformed themechanical power into electrical power), and the ReactivePower (kVAR) supplied by the alternator. The nominalvalue for the power factor is cos ϕ = 0,8; for differentvalues comprised between 0.8 and 1 it is importantduring usage not to exceed the declared active power(kW), so as to not overload the electricity-generatinggroup motor; the apparent power (kVA) will diminishproportionally to the increase of cos ϕ.For cos ϕ values of less than 0.8 the alternator must bedowngraded, since at equal apparent power thealternator should supply a greater reactive power. Forreduction coefficients, contact the Technical ServiceDepartment.
START-UP OF ASYNCHRONOUS MOTORSThe start-up of asynchronous motors from an electricity-generating group can prove critical because of highstart-up currents the asynchronous motor requires (Istart-up = up to 8 times the nominal current In.). Thestart-up current must not exceed the alternator’sadmissible overload current for brief periods, generallyin the order of 250–300% for 10–15 seconds.To avoid a group oversize, we recommend followingthese precautionary measures:- in the case of a start-up of several motors, subdivide
the motors into groups and set up their start-up atintervals of 30–60 seconds.
- when the operating machine coupled to the motorallows it, see to a start-up with reduced voltage, starpoint/triangle start-up or with autotransformer, or usea soft-start system.
In all cases, when the user circuit requires the start-upof an asynchronous motor, it is necessary to check thatthere are no utilities inserted into the installation, whichin the case of a voltage droop can cause more or lessserious disservices (opening of contact points, temporarylack of power to control and command systems, etc.).
SINGLE-PHASE LOADSPower to monophase utilities by means of three-phasegenerators requires some operating limitations.- In single-phase operation, the declared voltage
tolerance can no longer be maintained by the regulator(compound or electronic regulator), since the systembecomes highly unbalanced. The voltage variationon the phases not affected by the power can provedangerous; we recommend sectioning the otherloads eventually connected. 12
/06/
03 M
37G
B_1
500G
_GE
- The maximum power which can be drawn betweenNeutral and Phase (start connection) is generally 1/3of the nominal three-phase power; some types ofalternators even allow for 40%. Between two Phases(triangle connection) the maximum power cannot exceed2/3 of the declared three-phase power.
- In electricity-generating groups equipped withmonophase sockets, use these sockets for connectingthe loads. In other cases, always use the "R" phaseand Neutral.
ELECTRIC PROTECTIONS
THERMAL-MAGNETIC SWITCHThe electricity-generating group is protected against short-circuits and against overloads by a thermal-magneticswitch (Z2) situated upstream from the installation.Operating currents, both thermic and magnetic, can befixed or adjustable in relation to the switch model.☞ In models with adjustable operating current do notmodify the settings, since doing so can compromise theinstallation’s protection or the electricity-generating
group’s output characteristics. Foreventual variations, contact ourTechnical Service Department.The intervention of the protectionfeature against overloads is notinstantaneous, but follows a currentoverload/time outline; the greater theoverload the less the intervention.
Furthermore, keep in mind that the nominal operatingcurrent refers to an operating temperature of 30°C, sothat each variation of 10°C roughly corresponds to a
variation of 5% on the valueof nominal current.
In case of an intervention onthe part of the thermalmagnetic protection device,
check that the total absorption does not exceed theelectricity-generating group’s nominal current.
Using the generatorM
37.2
© MOSA 1.1-09/05
GE_Diesel engine
12/0
6/03
M37
GB
_150
0G_G
E
DIFFERENTIAL SWITCHThe differential switch or differential relay guaranteeprotection against indirect contacts due to malfunctioncurrents towards the ground. When the device detects amalfunction current that is higher than the nominal currentor the set current, itintervenes by cutting off
power to the circuit connected.In the case of an intervention by the differential switch,check that there are no sheathing defects in theinstallation: connection cables, sockets and plugs,utilities connected.☞ Before each work session, check the operation of thedifferential protection device by pressing the test key.The electricity-generating group must be in operation,and the lever on the differential switch must be in theON position.
THERMIC PROTECTIONGenerally present to protect against overloads on anindividual power socket c.a.When the nominal operating current has been exceeded,the protection device intervenes by cutting off power tothe socket.The intervention of the protection device againstoverloads is not instantaneous, but follows a currentoverload/time outline; the greater the overload the lessthe intervention.In case of an intervention, check that the currentabsorbed by the load does not exceed the protection’snominal operating current.Allow the protection to cool off for a few minutes beforeresetting by pressing the central pole.
ON OFF PRESS TORESET
Do not keep the central pole on the thermicprotection forcefully pressed to prevent itsintervention.
ATTENTION
USAGE WITH EAS AUTOMATIC START-UP PANELThe electricity-generating group in combination with theEAS automatic start-up panel forms a unit for distributingelectrical energy within a few seconds of a power failurefrom the commercial electrical power line.Below is some general operating information; refer tothe automatic panel’s specific manual for details oninstallation, command, control and signalling operations.
Perform connections on the installation in safetyconditions. Position the automatic panel in RESETor LOCKED mode.Carry out the first start-up in MANUAL mode.Check that the generator’s LOCAL START / REMOTESTART switch (I6) is in the REMOTE position.Check that the generator switches are enabled (inputlever in upward position).Position the EAS panel in manual mode by pressingMAN. key, and only after having checked that thereare no dangerous situations, press the START keyto start the electricity-generating group.During the operation of the generator, all controlsand signals from both the automatic panel and groupare enabled; it is therefore possible to control itsoperation from both positions.In case of an alarm with a shutdown of the motor(low pressure, high temperature, etc.), the automaticpanel will indicate the malfunction that has causedthe stoppage, while the generator’s front panel willbe disabled and will no longer supply any information.
T5.4
T5.1
T5.3
T5.2
T5.10
T5.6 T5.7
T5.8
T5.9
TRIPON
TESTRESET
0.25 2.5
20.5
1.51
0.02
0.1
0.2
0.5
0.3
0.4
RESET
I° (A) t (s)
RESETA M
tx10 tx1x1x10
x0.1I°I°
x10
tx10x1
I°
Mtx1
x0.1I°
A
1 c 0
1 d 0
1 b 0
1 a 0
T5.5
ENGINE PROTECTION USE EARTH LEAKAGE RELAYM
39.11© MOSA 1.1-10/05
Don not intervene on the setting of the protectionswitch. Before using the machine check the ON warninglamp lighting.
NOTE
The relay allows to select the tripping current value so asto keep values of contact voltage of the limits indicatedby the electrical security norms.
These adjustments allow to perform a tripping selecticityor either current or delay when more relays are locatedalong the same line in protection of the different startingsignals.
SW G.F.I.The SW G.F.I. switch placed inside the electric controlpanel - or inside the electric box - allows to exclude thedifferential relay in case of need from the group to befeeded.
WARNING: Have qualified personnel to exclude protectionin order to foresee other electrical safety solutions.
USE OF THE DER2 / D2B MODEL (MOSA SET UP)1) Manual reset2) Regulation of intervention time: 0.5 seconds3) Regulation of fault current: 30 mA4) Output relay: N.De or N.E. according to the model
of the machine .☞ - In order to modify the set up call the TechnicalAssistance Centres
The GFI is equipped with three tests, two of which areeffected automatically by the instrument.
1. manual test (trial push button)2. automatic test of the toroid/relay connection (guard)3. automatic test of the board electronics. In case of
fault the output relay trips and the Fault led lightswith fixed light.
It is able to work correctly even in presence of harmonicdistortion or anyway with very disturbed signals.In case the internal temperature goes over the thresholdfor a good functioning , the Fault led will twinkle.Its interruption due to a fault of the toroid (break of theconnection wire) or a fault in the internal circuits brings tothe automatic intervention of the protection
To help the user in setting up the intervention delay, thepotentiometer t(s) rotation in correspondence of a referencemark causes the Fault led to twinkle for a few seconds.
25/0
5/01
M39
GB
LEGEND:D1 Potentiometer for earthing fault current regulationD2 Potentiometer for intervention time regulationD3 Multifunction led for indication of: internal electronics
fault / internal temperature out of range/ t(s) centredcorrectly.
D4 Led indicating presence of feedingD5 Led indicating intervention of GFI relayD6 Micro-switches for setting up of the instrumentD7 Trial push-buttonD8 Push-button for the manual reset
TroubleshootingM
40.2© MOSA REV.3-07/06
28/0
1/03
M40
I_15
00G
_GE
GEDiesel engine
The motor does not startup
1) Start-up switch (I6) (where it isassembled) in incorrect position
2) Emergency button (L5) pressed3) Preheating (where it is assembled)
4) Engine control unit or starting keyfaulty.
5) Battery low
6) Battery cable terminals loose orcorroded
7) Start-up motor defective8) No fuel or air in feed circuit9) Malfunction on feed circuit: defective
pump, injector blocked, etc.10) Air filter or fuel filter clogged11) Air in the gasoil filter.12) Motor stopping device defective13) Malfunction on electrical power circuit
on generator control panel
1) Check position
2) Unblock3) Lacking or insufficient preheating
phase for sparkplugs.Malfunction in circuit: repair.
4) Replace
5) Recharge or replace.Check the battery charge circuit onmotor and automatic panel.
6) Tighten and clean. Replace ifcorroded.
7) Repair or replace.8) Refill tank, un-aerate the circuit.9) Ask for intervention of Service
Department.10) Clean or replace11) Take the air out filling the filter with gasoil.12) Replace.13) Check and repair.
Problem Possible cause Solution
The motor does notaccelerate. Inconstantspeed.
1) Air filter or fuel filter clogged.2) Malfunction on feed circuit: defective
pump, injector blocked, etc.3) Oil level too high.4) Motor speed regulator defective.
1) Clean or replace.2) Ask for intervention of Service
Department.3) Eliminate excess oil.4) Ask for intervention of Service
Department
Black smoke 1) Air filter clogged.2) Overload.
3) Injectors defective. Injection pumprequires calibration.
1) Clean or replace2) Check the load connected and
diminish.3) Ask for intervention of Service
Department.
White smoke 1) Oil level too high.2) Motor cold or in prolonged operation
with little or no load.3) Segments and/or cylinders worn out.
1) Eliminate excess oil.2) Insert load only with motor sufficiently
hot3) Ask for intervention of Service
Department.
Too little power providedby motor.
1) Air filter clogged.2) Insufficient fuel distribution, impurities
or water in feed circuit.3) Injectors dirty or defective.
1) Clean or replace.2) Check the feed circuit, clean and
refill once again.3) Ask for intervention of Service
Department.
Low oil pressure 1) Oil level insufficient2) Air filter clogged.3) Oil pump defective.
4) Alarm malfunction.
1) Reset level. Check for leaks.2) Replace filter.3) Ask for intervention of Service
Department.4) Check the sensor and electrical
circuit.
High temperature 1) Overload
2) Insufficient ventilation.
3) Insufficient coolant liquid (Only forwater cooled motors)
1) Check the load connected anddiminish.
2) Check the cooling vent and relativetransmission belts
3) Restore level. Check for leaks orbreakage in the entire cooling circuit,pipes, couplings, etc.
ENGINE
TroubleshootingM
40.2.1
© MOSA REV.3-07/06
12/0
6/03
M40
GB
_150
0G_G
E
GEDiesel engine
Problem Possible cause Solution
4) Water radiator or oil clogged (where itis assembled)
5) Water circulating pump defective (Onlyfor water cooled motors)
6) Injectors defective. Injection pumprequires calibration
7) Alarm malfunction
4) Clean cooling fins on radiator
5) Ask for intervention of ServiceDepartment
6) Ask for intervention of ServiceDepartment
7) Check the sensor and electricalcircuit
Absence of output voltage 1) Voltage switch in position 02) Voltage switch faulty
3) Protection tripped due to overload
4) Differential protection device tripped.(Differential switch, differential relay)
5) Protection devices defective6) Alternator not sparked
7) Alternator defective
1) Check position2) Check connections and working of
the switch, repair or replace3) Check the load connected and
diminish4) Check on the entire installation:
cables, connections, util it iesconnected have no defectivesheathing which may cause incorrectcurrents to ground
5) Replace6) Carry out external spark test as
indicated in alternator manual. Askfor intervention of ServiceDepartment
7) Check winding, diodes, etc. onalternator (Refer to alternatormanual)Repair or replace.Ask for intervention of ServiceDepartment
No-load voltage too low ortoo high
1) Incorrect motor running speed
2) Voltage regulating device (where it isassembled) defective or requirescalibration
3) Alternator defective
1) Regulate speed to its nominal no-load value
2) Adjust regulator device as indicatedin alternator manual, or replace
3) Check winding, diodes, etc. onalternator (Refer to alternatormanual)Repair or replaceAsk for intervention of ServiceDepartment
Corrected no-load voltagetoo low with load
1) Check the load connected anddiminish
2) Reduce or rephase load3) Check winding, diodes, etc. on
alternator (Refer to alternatormanual)Repair or replaceAsk for intervention of ServiceDepartment
1) Check electrical connections andtighten
2) Ask for intervention of ServiceDepartment
3) Check winding, diodes, etc. onalternator (Refer to alternatormanual)Repair or replaceAsk for intervention of ServiceDepartment
1) Incorrect motor running speed due tooverload
2) Load with cos ϕ less than 0.83) Alternator defective
1) Contacts malfunctioning
2) Irregular rotation of motor
3) Alternator defective
Unstable tension
ENGINE
GENERATOR
MAINTENANCEM43
© MOSA 1.0-09/05
NOTE
By maintenance at care of the utilizer we intend all theoperatios concerning the verification of mechanical parts,electrical parts and of the fluids subject to use orconsumption during the normal operation of the machine.
For what concerns the fluids we must consider asmaintenance even the periodical change and or the refillseventually necessary.
Maintenance operations also include machine cleaningoperations when carried out on a periodic basis outsideof the normal work cycle.
The repairs cannot be considered among themaintenance activities, i.e. the replacement of partssubject to occasional damages and the replacement ofelectric and mechanic components consumed in normaluse, by the Assistance Authorized Center as well as byMOSA.
The replacement of tires (for machines equipped withtrolleys) must be considered as repair since it is notdelivered as standard equipment any lifting system.
The periodic maintenance should be performed accordingto the schedule shown in the engine manual. An optionalhour counter (M) is available to simplify the determinationof the working hours.
THE ENGINE PROTECTION NOT WORK WHEN THEOIL IS OF LOW QUALITY BECAUSE NOT CHARGEDREGULARLY AT INTERVALS AS PRESCRIBED INTHE OWNER’S ENGINE MANUAL.
NOTE
IMPORTANTIn the maintenance operations avoid thatpolluting substances, liquids, exhausted oils,etc. bring damage to people or things or cancause negative effects to surroindings, healthor safety respecting completely the laws and/or dispositions in force in the place.
WARNING● Have qualified personnel do maintenance and troubleshooting work.● Stop the engine before doing any work inside the machine. If for any
reason the machine must be operated while working inside, payattention moving parts, hot parts (exhaust manifold and muffler,etc.) electrical parts which may be unprotected when the machineis open.
● Remove guards only when necessary to perform maintenance, andreplace them when the maintenance requiring their removal iscomplete.
● Use suitable tools and clothes.● Do not modify the components if not authorized.
- See pag. M1.1 -
HOT surfacecan
hurt you
MOVINGPARTS
can injure
05/0
9/05
M43
GB
ENGINE and ALTERNATORPLEASE REFER TO THE SPECIFIC MANUALSPROVIDED.
VENTILATIONMake certain there are no obstructions (rags, leaves orother) in the air inlet and outlet openings on the machine,alternator and motor.
ELECTRICAL PANELSCheck condition of cables and connections daily.Clean periodically using a vacuum cleaner, DO NOTUSE COMPRESSED AIR.
DECALS AND LABELSAll warning and decals should be checked once a yearand replaced if missing or unreadable.
STRENUOUS OPERATING CONDITIONSUnder extreme operating conditions (frequent stops andstarts, dusty environment, cold weather,extended periodsof no load operation, fuel with over 0.5% sulphur content)do maintenance more frequently.
BATTERY WITHOUT MAINTENANCEDO NOT OPEN THE BATTERY
The battery is charged automatically from the batterycharger circuit suppplied with the engine.
Check the state of the battery from the colour of thewarning light which is in the upper part.
- Green colour: battery OK- Black colour: battery to be recharged- White colour: battery to be replaced
MAINTENANCE GEM
43.1© MOSA 1.0-09/05
05/0
9/05
M43
GB
ATTENTION■ Maintenance operations on the electricity-generating group prearranged for automatic operation must be
carried out with the panel in RESET mode.■ Maintenance operations on the installation’s electrical panels must be carried out in complete safety by cutting
off all external power sources: ELECTRICAL POWER, GROUP and BATTERY.
EVERY MONTHAND/OR AFTER
INTERVENTION ONLOAD
EVERY YEAR
1. TEST or AUTOMATIC TEST cycle tokeep the generating set constantlyoperative
2. Check all levels: engine oil, fuellevel, battery electrolyte,, ifnecessary top it up.
3. Control of electrical connections andcleaning of control panel
EVERY
WEEK
NO-LOAD
X
WITH LOAD
X
X X
X X
For the electricity-generating groups prearranged for automatic operation, in addition to carrying out all periodicmaintenance operations foreseen for normal usage, various operations must be carried out that are necessary inrelation to the specific type of use. The electricity-generating group in fact must be continuously prepared foroperation, even after prolonged periods of inactivity.
MAINTENANCE GENERATING SET WITH AUTOMATIC BOARD
☞ Carry out motor oil change at least once a year, even if the requested number of hours has not beenattained.
STORAGE GE_, MS_, TS_M45
© MOSA 1.0-06/00
In case the machine should not be used for more than 30days, make sure that the room in which it is storedpresents a suitable shelter from heat sources, weatherchanges or anything which can cause rust, corrosion ordamages to the machine.
☞ Have qualified personnel prepare the machine forstorage.
GASOLINE ENGINE
Start the engine: lt will run until it stops due to the lack offuel.
Drain the oil from the engine sump and fill it with new oil(see page M25).
Pour about 10 cc of oil into the spark plug hole and screwthe spark plug, after having rotated the crankshaft severaltimes.
Rotate the crankshaft slowly until you feel a certaincompression, then leave it.
In case the battery, for the electric start, is assembled,disconnect it.
Clean the covers and all the other parts of the machinecarefully.
Protect the machine with a plastic hood and store it in odry place.
DIESEL ENGINE
For short periods of time it is advisable, about every 10days, to make the machine work with load for 15-30minutes, for a correct distribution of the lubricant, torecharge the battery and to prevent any possible blokingof the injection system.
For long periods of inactivity, turn to the after solesservice of the engine manufacturer.
Clean the covers and all the other parts of the machinecarefully.
Protect the machine with a plastic hood and store it in adry place.
In the storage operations avoid thatpolluting substances, liquids, exhaustedoils, etc. bring damage to people orthings or can cause negative effects tosurroindings, health or safety respectingcompletely the laws and/or dispositionsin force in the place.
IMPORTANT
30/0
0/00
M45
GB
In case of necessity for first aid and of fire prevention,see page. M2.5.
CUST OFF GE_, MS_, TS_M46
© MOSA 1.0-03/00
In the cust-off operations avoid thatpolluting substances, liquids, exhaustedoils, etc. bring damage to people orthings or can cause negative effects tosurroindings, health or safety respectingcompletely the laws and/or dispositionsin force in the place.
IMPORTANT
☞ Have qualified personnel disassemble themachine and dispose of the parts, including theoil, fuel, etc., in a correct manner when it is tobe taken out of service.
As cust off we intend all operations to be made, atutilizer’s care, at the end of the use of the machine.This comprises the dismantling of the machine, thesubdivision of the several components for a furtherreutilization or for getting rid of them, the eventualpacking and transportation of the eliminated partsup to their delivery to the store, or to the bureauencharged to the cust off or to the storage office,etc.
The several operations concerning the cust off,involve the manipulation of fluids potentiallydangerous such as: lubricating oil and batteryelectrolyte.
The dismantling of metallic parts liable to causeinjuries or wounds, must be made wearing heavygloves and using suitable tools.
The getting rid of the various components of themachine must be made accordingly to rules in forceof law a/o local rules.Particular attention must be paid when gettingrid of:lubricating oils, battery electrolyte, andinflamable liquids such as fuel, cooling liquid.
The machine user is responsible for the observanceof the norms concerning the environment conditionswith regard to the elimination of the machine beingcust off and of all its components.
In case the machine should be cust off without anyprevious disassembly it is however compulsory toremove:- tank fuel- engine lubricating oil- cooling liquid from the engine- battery
NOTE: MOSA is involved with custing off themachine only for the second hand ones, when notreparable.This, of course, after authorization.
In case of necessity for first aid and fire prevention,see page M2.5.
30/0
3/00
M45
GB
DimensioniDimensionsDimensions© MOSA REV.0-06/07
AbmessungenDimensiones GE 275 VPSX
GE 275 VPMSX
M53
ø
785 95
n°4 fori25
3630
190 655 372
10
01
70
0
58
08
50
600150
55 1190
1300
15
2~
13
0~
878878
25/0
5/07
842
77-I
ELECTRICAL SYSTEM LEGENDE GE_, MS_, TS_M60
© MOSA REV.6-06/08
26/0
7/04
M60
GB
A: AlternatorB: Wire connection unitC: CapacitorD: G.F.I.E: Welding PCB transformerF: FuseG: 400V 3-phase socketH: 230V 1phase socketI: 110V 1-phase socketL: Socket warning lightM: Hour-counterN: VoltmeterP: Welding arc regulatorQ: 230V 3-phase socketR: Welding control PCBS: Welding current ammeterT: Welding current regulatorU: Current transformerV: Welding voltage voltmeterZ: Welding socketsX: ShuntW: D.C. inductorY: Welding diode bridge
A1: Arc striking resistorB1: Arc striking circuitC1: 110V D.C./48V D.C. diode bridgeD1: E.P.1 engine protectionE1: Engine stop solenoidF1: Acceleration solenoidG1: Fuel level transmitterH1: Oil or water thermostatI1: 48V D.C. socketL1: Oil pressure switchM1: Fuel warning lightN1: Battery charge warning lightO1: Oil pressure warning lightP1: FuseQ1: Starter keyR1: Starter motorS1: BatteryT1: Battery charge alternatorU1: Battery charge voltage regulatorV1: Solenoid valve control PCBTZ1: Solenoid valveW1: Remote control switchX1: Remote control and/or wire feeder
socketY1: Remote control plug
A2: Remote control welding regulatorB2: E.P.2 engine protectionC2: Fuel level gaugeD2: AmmeterE2: Frequency meterF2: Battery charge trasformerG2: Battery charge PCBH2: Voltage selector switchI2: 48V a.c. socketL2: Thermal relayM2: ContactorN2: G.F.I. and circuit breakerO2: 42V EEC socketP2: G.F.I. resistorQ2: T.E.P. engine protectionR2: Solenoid control PCBTS2: Oil level transmitterT2: Engine stop push-button T.C.1U2: Engine start push-buttonT.C.1V2: 24V c.a. socketZ2: Thermal magnetic circuit breakerW2: S.C.R. protection unitX2: Remote control socketY2: Remote control plug
A3: Insulation moitoringB3: E.A.S. connectorC3: E.A.S. PCBD3: Booster socketE3: Open circuit voltage switchF3: Stop push-buttonG3: Ignition coilH3: Spark plugI3: Range switchL3: Oil shut-down buttonM3: Battery charge diodeN3: RelayO3: ResistorP3: Sparkler reactorQ3: Output power unitR3: Electric sirenS3: E.P.4 engine protectionT3: Engine control PCBU3: R.P.M. electronic regulatorV3: PTO HI control PCBZ3: PTO HI 20 l/min push-buttonW3: PTO HI 30 l/min push-buttonX3: PTO HI reset push-buttonY3: PTO HI 20 l/min indicator
A4: PTO HI 30 l/min indicatorB4: PTO HI reset indicatorC4: PTO HI 20 l/min solenoid valveD4: PTO HI 30 l/ min solenoid valveE4: Hydraulic oil pressure switchF4: Hycraulic oil level gaugeG4: Preheating glow plugsH4: Preheating gearboxI4: Preheating indicatorL4: R.C. filterM4: Heater with thermostatN4: Choke solenoidO4: Step relayP4: Circuit breakerQ4: Battery charge socketsR4: Sensor, cooling liquid temperatureS4: Sensor, air filter cloggingT4: Warning light, air filter cloggingU4: Polarity inverter remote controlV4: Polarity inverter switchZ4: Transformer 230/48VW4: Diode bridge, polarity changeX4: Base current diode bridgeY4: PCB control unit, polarity inverter
A5: Base current switchB5: Auxiliary push-button ON/OFFC5: Accelerator electronic controlD5: ActuatorE5: Pick-upF5: Warning light, high temperatureG5: Commutator auxiliary powerH5: 24V diode bridgeI5: Y/s commutatorL5: Emergency stop buttonM5: Engine protection EP5N5: Pre-heat push-buttonO5: Accelerator solenoid PCBP5: Oil pressure switchQ5: Water temperature switchR5: Water heaterS5: Engine connector 24 polesT5: Electronic GFI relaisU5: Release coil, circuit breakerV5: Oil pressure indicatorZ5: Water temperature indicatorW5: Battery voltmeterX5: Contactor, polarity changeY5: Commutator/switch, series/parallel
A6: Commutator/switchB6: Key switch, on/offC6: QEA control unitD6: Connector, PACE6: Frequency rpm regulatorF6: Arc-Force selectorG6: Device starting motorH6: Fuel electro pump 12V c.c.I6: Start Local/Remote selectorL6: Choke buttonM6: Switch CC/CVN6: Connector – wire feederO6: 420V/110V 3-phase transformerP6: Switch IDLE/RUNQ6: Hz/V/A analogic instrumentR6: EMC filterS6: Wire feeder supply switchT6: Wire feeder socketU6: DSP chopper PCBV6: Power chopper supply PCBZ6: Switch and leds PCBW6: Hall sensorX6: Water heather indicatorY6: Battery charge indicator
A7: Transfer pump selector AUT-0-MANB7: Fuel transfer pumpC7: „GECO“ generating set testD7: Flooting with level switchesE7: Voltmeter regulatorF7: WELD/AUX switchG7: Reactor, 3-phaseH7: Switch disconnectorI7: Solenoid stop timerL7: "VODIA" connectorM7: "F" EDC4 connectorN7: OFF-ON-DIAGN. selectorO7: DIAGNOSTIC push-buttonP7: DIAGNOSTIC indicatorQ7: Welding selector modeR7: VRD loadS7: 230V 1-phase plugT7: V/Hz analogic instrumentU7: Engine protection EP6V7: G.F.I. relay supply switchZ7: Radio remote control receiverW7: Radio remote control trasnsmitterX7: Isometer test push-buttonY7: Remote start socket
A8: Transfer fuel pump controlB8: Ammeter selector switchC8: 400V/230V/115V commutatorD8: 50/60 Hz switchE8: Cold start advance with temp. switchF8: START/STOP switchG8: Polarity inverter two way switchH8: Engine protection EP7I8: AUTOIDLE switchL8: AUTOIDLE PCBM8: A4E2 ECM engine PCBN8: Remote emergency stop connectorO8: V/A digital instruments and led VRD PCBP8: Water in fuelQ8:R8:S8:T8:U8:V8:Z8:W8:X8:Y8:
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE275 VPSX / VPMSXAUT.
M61.1
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Engi
neVo
lvoPe
nta
TAD7
34G
E84
277.
prg
8427
7.S.
010
Lepo
race
N.
2 Appr
ovat
o:
Esp
.Da
taDi
s.Ap
pr.
Mod
ifica
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp
.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
sirise
rva
ate
rmin
idi l
eg
ge
lap
rop
rie
ta'd
elp
rese
nte
dis
eg
no
con
div
ieto
dir
ipro
du
rlo
oco
mu
nic
arlo
ate
rzis
en
zasu
aa
uto
rizz
azi
on
e.
Y/W
GIA
LLO
/BIA
NCO
- YEL
LOW
/WHI
TE
LE
GE
ND
AC
OL
OR
IC
OL
OU
RK
EY
GR/
YG
RIG
IO/G
IALL
O- G
REY/
YELL
OW
SBNE
RO- B
LACK
RRO
SSO
- RED
R/BL
ROSS
O/B
LU- R
ED/B
LUE
GN/
WVE
RDE
- GRE
ENW
BIAN
CO- W
HITE
W/S
BBI
ANCO
/NER
O- W
HITE
/BLA
CK
M4
B
06.0
6.20
07
-+ M R1
B+W
D+
U1
T1
1314
1314
71 72
7172
711
8281
8281
8281
1
832
Y/W
GR/Y
SB
R
R/BL
GN/W
W
W/SB
2
178
109
N N
Z2
MTH
Whi
teRe
d
G1
243
S54
241
27
65
VOLV
OEM
S2
12
34
56
78
1112
POWER220-240V50-60Hz
BATTERY
ALARMOUT
L
N
-+
-
G2
55
1112
-+
S1
F10
F2A
3 3
+BATT
-BATT
+BATTSWITCHED
STOP
A
B
CANJ1939
J1708/1587
H
L
OPT
ION:
WH
VP5
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSX / VPMSXMAN.
M61.2
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Engi
neVo
lvoPe
nta
TAD7
34G
E84
278.
prg
8427
8.S.
010
Lepo
race
N.
2 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.M
odific
a
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
sirise
rva
ate
rmin
idi l
eg
ge
lap
rop
rie
ta'd
elp
rese
nte
dis
eg
no
con
div
ieto
dir
ipro
du
rlo
oco
mu
nic
arlo
ate
rzis
en
zasu
aa
uto
rizz
azi
on
e.
Y/W
GIA
LLO
/BIA
NCO
- YEL
LOW
/WHI
TE
LE
GE
ND
AC
OLO
RI
CO
LO
UR
KE
Y
GR/
YG
RIG
IO/G
IALL
O- G
REY/
YELL
OW
SBNE
RO- B
LACK
RRO
SSO
- RED
R/BL
ROSS
O/B
LU- R
ED/B
LUE
GN/
WVE
RDE
- GRE
ENW
BIAN
CO- W
HITE
W/S
BBI
ANCO
/NER
O- W
HITE
/BLA
CK
M4
B
06.0
6.20
07
-+ M R1
B+W
D+
U1
T1
1314
1314
71 72
7172 82
81
8281
8281
Y/W
GR/Y
SB
R
R/BL
GN/W
W
W/SB
178
109
N N
Z2
MTH
Whi
teRe
d
G1
243
S54
241
27
65
VOLV
OEM
S2
12
34
56
78
1112
1112
-+
S1
S7
+BATT
-BATT
+BATTSWITCHED
STOP
A
B
CANJ1939
J1708/1587
H
L
OPT
ION:
WH
VP6
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSXGE 275 VPMSX
M61.3
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Engi
neco
ntro
l car
d84
277.
prg
8427
7.S.
011
Lepo
race
N.
3 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.M
odific
a
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
sirise
rva
ate
rmin
idi l
eg
ge
lap
rop
rie
ta'd
elp
rese
nte
dis
eg
no
con
div
ieto
dir
ipro
du
rlo
oco
mu
nic
arlo
ate
rzis
en
zasu
aa
uto
rizz
azi
on
e.
+-
BATT
ERY
12/2
4Vd
c
11999
15RELA
ISO
UTPU
T(+B
)DI
GIT
ALIN
PUT
1313
1414
15
- PO
NTIC
ELLA
RESE
NON
COLL
EGAT
O
-JUM
PER
IFNO
TCO
NNEC
TED
*A
PULS
ANTE
EMER
GEN
ZAES
TERN
O.
TOEX
TERN
ALEM
ERG
ENG
YST
OP
BUTT
ON
+BATT
COM
NO
NC
RELA
ISO
UTPU
TDI
GIT
ALIN
PUT
21 21
2322
2322
3
*G
LOBA
LAL
ARM
C7
REMOTESTART
REMOTESTOP
(1)
(2)
L5
(1)
(2)
-BATT
+BATTSWITCHED
STOP
A
B
2 2
5
4417
18
1718
2
2
21
B6
7
6.6
6.5
6.4
6.3
6.2
6.1
7.2
7.1
9.1
9.2
9.3
9.4
9.5
9.6
9.7
178
5.5
5.4
5.3
5.2
5.1
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
B
F1
F8A
S524
56
06.0
6.20
07
A.1
A.2
A.3
A.4
A.10
A.11
A.12
A.13
CAN-
BUS
PCB
-+
R3
9
1112
1112
12 11
34 L
H
EMERGENCYSTOPPUSHBUTTON
EMERGENCYSTOPPUSHBUTTON
FUELLEVELGAUGE
FUELLEVELGAUGE
W
LEG
EN
DA
CO
LOR
IC
OLO
UR
KE
YW
BIAN
CO- W
HITE
BRM
ARRO
NE- B
ROW
N
BR
2 21 25422
CANJ1939
J1708/1587
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSXGE 275 VPMSX
M61.4
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Tran
sfer
fuel
pum
pkit
8427
7.pr
g
8427
7.S.
015
Lepo
race
N.
4 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.M
odific
a
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
siriserv
aa
term
inidile
gge
lapro
prieta
' delpre
sente
dis
egno
con
div
ieto
diripro
durlo
ocom
unic
arlo
ate
rzisenza
sua
auto
rizzazio
ne.
07.0
6.20
07
DIG
ITAL
INPU
T
1M
230V
8886
24Vd
c23
0Vac
88
86
51
87 8655
52
POM
PACA
RBUR
ANTE
FUEL
PUM
PVU
OTO
EMPT
YPI
ENO
FULL
TRO
PPO
PIEN
OTO
OFU
LL
C7
SWIT
CHAU
T.- 0
-MAN
.
B7
OPT
IONA
L
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
N
N
Z2M
TPK2
(A1)
(A2)
N3
Pum
p
Z1
3
2/41
7
6/8
5
A7
(5)
(9)
1920
25
1920
20
24
1924
25
1924
25
(2)
D7
(3)
(4)
(1)24
15S5
1413
RELA
ISO
UTPU
T(+B
)
6.1
6.2
6.3
6.4
6.5
6.6
7 7
2
22
2019
88
Z1
K2(1
2)
(8)
Pum
p
7 8
28
8886
3
2
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSXM
61.5© MOSA REV.0-02/09
20090-C
US
AG
O(M
I)-I
TA
LYhttp://w
ww
.mosa.it
GE
275
VP
SX
Ele
ctr
icaldia
gra
mfo
r50/6
0H
zkit
84278.p
rg
84
27
8.S
.01
6Lepora
ce
N.
5 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.Mo
difi
ca
Deno
mina
zion
e:
Macc
hina
:Da
ta:
Prog
etto
:di
n°Pa
g.n°
6
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
mina
tion
:
Mach
ine:
Modi
fica
tion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desi
gner
:
ofn°
Desi
.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
LaMOSA
siriservaaterminidi
leggela
proprieta'
delpresente
disegnocondivietodi
riprodurlo
ocomunicarloaterzisenzasuaautorizzazione.
R S T N
60
Hz
50
Hz
3G
A
NU V W
(1)(2
) (3)
(8)
(7)
(5)
D8
C50
60
60
C
VO
LTS
UF
RO
IND
ICA
TO
RL
ED
STA
BIL
ITY
TRIMDROOP
AS
440
F1
78
8Z
2
S1 S2 A1 A2
50
C6
0
1 2 3 La Lb
F2
50
32
DIG
ITA
LIN
PU
T
9.2
9.3
9.4
9.5
9.6
9.7
6 6
C7
9.1
15.0
6.2
007
OP
TIO
NA
L
2
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPMSXM
61.6© MOSA REV.0-02/09
20090-C
US
AG
O(M
I)-I
TA
LYhttp://w
ww
.mosa.it
GE
275
VP
MS
X
Ele
ctr
icaldia
gra
mfo
r50/6
0H
zkit
84272.p
rg
84
27
2.S
.01
6Lepora
ce
N.
5 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.Mo
difi
ca
Deno
mina
zion
e:
Macc
hina
:Da
ta:
Prog
etto
:di
n°Pa
g.n°
6
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
mina
tion
:
Mach
ine:
Modi
fica
tion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desi
gner
:
ofn°
Desi
.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
LaMOSA
siriserva
atermini
dilegge
laproprieta'
del
presente
disegno
con
divieto
diriprodurlo
ocomunicarlo
aterzi
senza
sua
autorizzazione.
R S T N
60
Hz
50
Hz
3G
A
NU V W
(1)(2
) (3)
(8)
(7)
(5)
D8
C50
C
50
32
DIG
ITA
LIN
PU
T
9.2
9.3
9.4
9.5
9.6
9.7
6 6
C7
9.1
OP
TIO
NA
L
2
30.1
0.2
008
60
Hz
QP
MA
RK
I
*-
TO
GLIE
RE
PO
NT
ICE
LLO
AR
AN
CIO
NE
EC
OLLE
GA
RE
CA
VI
N°
31-3
2
-R
EM
OV
EO
RA
NG
ELIN
KA
ND
CO
NN
EC
TC
AB
LE
SN
°31-3
2
*
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSXAUT.
M61.7
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Aux.
(400
T)St
amfo
rdal
ter.
8427
7.pr
g
8427
7.S.
020
Lepo
race
N.
5 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.M
odific
a
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
sirise
rva
ate
rmin
id
ile
gg
ela
pro
prie
ta' d
elp
rese
nte
dis
eg
no
co
nd
ivie
tod
irip
rod
urlo
oco
mu
nic
arlo
ate
rzise
nza
su
aa
uto
rizza
zio
ne
.
RG SG TG NG
5859
6061
6263
S1
S2
S1
S2
S1
S2
5859
6061
6263
GE
NE
RA
TO
R
L1
L2
L3
N
5157
5553
5654
52
80
7172
7476
7970
69
8070
7868
COM
NC
COM
NO
RE
LAIS
OU
TPU
TTL
RTL
GR
ET
E
L1
L2
L3
L4
7375
7771
72712 2
DIG
ITA
LIN
PU
TC
UR
RE
NT
TR
AN
SF
OR
ME
R
5254
56
4042
43
4042
*
N1
T1S1R
G SG TG NG
N1T1S1R1
41
R1
52 5144
C7
646584
8451
536564
NR
N1R1
RS
TN
RE
TE
-MA
IN
(NO
)TL
G
(NO
)TL
R
85
85-T
OG
LIER
EPO
NTIC
ELLO
ECO
LLEG
ARE
CAVI
66-6
7DE
LPO
TENZ
IOM
ETRO
- REM
OVE
LINK
AND
CONN
ECT
HAND
TRIM
MER
BYCA
BLES
66-6
7
513G
ANU V W
3.1
3.2
3.3
3.4
3.5
3.6
S1S2
U
S1S2
U
S1S2
U
2.1
2.2
2.3
2.4
78
910
43
2
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
1112
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
5D6
1
Q3
F8 2A
6
65
43
21 7
89
1011
12G.F
.I.DO
SSEN
A
12
34
TLR
TLG
Z2
F2
F2A
F3 2A
F4 2A
16
16
F9 2A
F5 2A
F6 2A
F7
F2A
RE
LAIS
OU
TP
UT
(+B
)
10
6.6
6.5
6.4
6.3
6.2
6.1
*
CW
6667 67
66
23
3
2
1
E7
1K
S522
(12)
(8)
2
3
51S1
S283
U5
07.0
6.20
07
K1(A
1)
(A2)
N3G
.F.I.
53
OPT
IONA
L:G
.F.I.
2
10
OP
TIO
NA
L:R
EV
1
VOLTS
UFRO
INDICATORLED
STABILITY
TR
IMD
RO
OP AS440
F1 7 8 8 Z2
S1
S2
A1
A2
50C 60
12
3La
Lb
F2
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPSXMAN.
M61.8
© MOSA REV.0-06/07
2009
0-C
US
AG
O(M
I)-I
TALY
http
://w
ww
.mos
a.it
GE
275
VPSX
Aux.
(400
T/23
0M)
8427
8.pr
g
8427
8.S.
020
Lepo
race
N.
5 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.M
odific
a
Deno
min
azio
ne:
Mac
chin
a:Da
ta:
Prog
etto
:di
n°Pa
g.n°
5
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
min
atio
n:
Mac
hine
:
Mod
ificat
ion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desig
ner:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
La
MO
SA
sirise
rva
ate
rmin
idi l
eg
ge
lap
rop
rie
ta' d
elp
rese
nte
dis
eg
no
con
div
ieto
di r
ipro
du
rlo
oco
mu
nic
arlo
ate
rzis
en
zasu
aa
uto
rizz
azi
on
e.
RG SG TG NG
5859
6061
6263
S1
S2
S1
S2
S1
S2
5859
6061
6263
GEN
ERAT
OR
L1
L2
L3
N
5157
5553
5654
52
COM
NC
COM
NO
RELA
ISO
UTPU
TTL
RTL
GRE
TE
L1
L2
L3
L4
DIG
ITAL
INPU
TCU
RREN
TTR
ANSF
ORM
ER
5254
56
*
N1T1S1RG SG TG NG
N1T1S1R1R1
52 5144
C7
646584
8451
536564
85
85-T
OG
LIER
EPO
NTIC
ELLO
ECO
LLEG
ARE
CAVI
66-6
7DE
LPO
TENZ
IOM
ETRO
- REM
OVE
LINK
AND
CONN
ECT
HAND
TRIM
MER
BYCA
BLES
66-6
7
513G
ANU V W
3.1
3.2
3.3
3.4
3.5
3.6
S1S2
U
S1S2
U
S1S2
U
2.1
2.2
2.3
2.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Q3
65
43
21 7
89
1011
12G.F
.I.DO
SSEN
A
12
34
Z2
F2
F2A
F3 2A
F4 2A
16
16
RELA
ISO
UTPU
T(+B
)
10
6.6
6.5
6.4
6.3
6.2
6.1
(12)
(8)
2
3
51S1
S283
07.0
6.20
07
K1(A
1)
(A2)
N3G
.F.I.
53
OP
TIO
NA
L:G
.F.I.
2
10 U5
*
CW
6667 67
66
OPT
IONA
L:RE
V1
23
3
2
1
E7
1K
S522
VOLTS
UFRO
INDICATORLED
STABILITY
TR
IMD
RO
OP
AS440
F1 7 8 8 Z2
S1
S2
A1
A2
50C 60
12
3L
aL
b
F2
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPMSXAUT.
M61.9
© MOSA REV.0-02/09
20090-C
US
AG
O(M
I)-I
TA
LYhttp://w
ww
.mosa.it
GE
275
VP
MS
X
Aux.(4
00T
)84272.p
rg
84
27
2.S
.02
0Lepora
ce
N.
6 Appr
ovat
o:
Esp.
Data
Dis.
Appr.
Modifica
Denominazione:
Macchina:
Data:
Progetto:
din°
Pag.n°
6
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
mina
tion
:
Mach
ine:
Modi
fica
tion
Date
:
DaPag.
Alla
Pag.
ToPage
From
Page
Designer:
ofn°
Desi.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Disegnatore:
LaMOSA
siriservaaterminidi
leggela
proprieta'
delpresente
disegnocondivietodi
riprodurlo
ocomunicarloaterzisenzasuaautorizzazione.
RG
SG
TG
NG
58
59
60
61
62
63
S1
S2
S1
S2
S1
S2
58
59
60
61
62
63
GE
NE
RA
TO
R
L1
L2
L3
N
51
57
55
53
56
54
52
80
71
72
74
76
79
70
69
80
70
78
68
COM
NC
COM
NO
RE
LA
ISO
UT
PU
TT
LR
TLG
RE
TE
L1
L2
L3
L4
73
75
77
71
72
71
2 2
DIG
ITA
LIN
PU
TC
UR
RE
NT
TR
AN
SF
OR
ME
R
52
54
56
40
42
43
40
42
N1
T1
S1
RG
SG
TG
NG
N1
T1
S1
R1
41
R1
52
51
44
C7
64
65
84
84
51
5365
64
NR
N1
R1
RS
TN
RE
TE
-MA
IN
(NO
)T
LG
(NO
)T
LR
85
85
51
3G
ANU V W
3.1
3.2
3.3
3.4
3.5
3.6
S1
S2
U
S1
S2
U
S1
S2
U
2.1
2.2
2.3
2.4
78
91
04
32
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
11
12
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
5D
61
Q3
F8
2A
6
65
43
21 7
89
10
111
2
G.F
.I.
DO
SS
EN
A
12
34
TL
RT
LG
Z2
F2
F
2A
F3
2A
F4
2A
16
16
F9
2A
F5
2A
F6
2A
F7
F
2A
RE
LA
ISO
UT
PU
T(+
B)
10
6.6
6.5
6.4
6.3
6.2
6.1
2
3
51
S1
S2
83
U5
K1
(A1
)
(A2
)N
3
G.F
.I.
53
OP
TIO
NA
L:
G.F
.I.
2
10
(8)
(12
)
67
66
CW
67
66
67
66
23
S5
22
60
Hz
Q
P
MA
RK
I
3
2
1
E7
10
0K
OP
TIO
NA
L:
RE
V4
30.1
0.2
008
25/0
5/07
842
77-I
Schema elettricoElectric diagramSchemas electriques
GE 275 VPMSXMAN.
M61.10
© MOSA REV.0-02/09
20090-C
US
AG
O(M
I)-I
TA
LYhttp://w
ww
.mosa.it
GE
275
VP
MS
X
Aux.(4
00T
)84273.p
rg
84
27
3.S
.02
0Lepora
ce
N.
6 Appr
ovat
o:
Esp.
Data
Dis.
Appr
.Mo
difi
ca
Deno
mina
zion
e:
Macc
hina
:Da
ta:
Prog
etto
:di
n°Pa
g.n°
6
Date
Appr
.
Appr
oved
:
Proj
ect:
Deno
mina
tion
:
Mach
ine:
Modi
fica
tion
Date
:
DaPa
g.
Alla
Pag.
ToPa
ge
From
Page
Desi
gner
:
ofn°
Desi
.
Dis.
n°:
Exp.
Page
n°
Dwg.
n°:
Dise
gnat
ore:
LaMOSA
siriserva
atermini
dilegge
laproprieta'
del
presente
disegno
con
divieto
diriprodurlo
ocomunicarlo
aterzi
senza
sua
autorizzazione.
RG
SG
TG
NG
58
59
60
61
62
63
S1
S2
S1
S2
S1
S2
58
59
60
61
62
63
GE
NE
RA
TO
R
L1
L2
L3
N
51
57
55
53
56
54
52
COM
NC
COM
NO
RE
LA
ISO
UT
PU
TT
LR
TLG
RE
TE
L1
L2
L3
L4
DIG
ITA
LIN
PU
TC
UR
RE
NT
TR
AN
SF
OR
ME
R
52
54
56
N1
T1
S1
RG
SG
TG
NG
N1
T1
S1
R1
R1
52
51
44
C7
64
65
84
84
51
5365
64
85
85
51
3G
ANU V W
3.1
3.2
3.3
3.4
3.5
3.6
S1
S2
U
S1
S2
U
S1
S2
U
2.1
2.2
2.3
2.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
Q3
65
43
21 7
89
10
111
2
G.F
.I.
DO
SS
EN
A
12
34
Z2
F2
F
2A
F3
2A
F4
2A
16
16
RE
LA
ISO
UT
PU
T(+
B)
10
6.6
6.5
6.4
6.3
6.2
6.1
2
3
51
S1
S2
83
K1
(A1
)
(A2
)N
3
G.F
.I.
53
OP
TIO
NA
L:
G.F
.I.
2
10 U
5
(8)
(12
)
67
66
CW
67
66
67
66
OP
TIO
NA
L:
RE
V4
23
S5
22
60
Hz
Q
P
MA
RK
I
3
2
1
E7
10
0K
31.1
0.2
008
SPARE PARTS LISTR1
© MOSA 1.0-03/00
MOSA guarantees that any request for spare parts will be satisfied.To keep the machine in full working order, when replacement of MOSA spare parts is required, alwaysask for genuine parts only.
When ordering the spare parts, it isrecommended to indicate:
1) ✹ serial number
2) ✹ model of welder and/or generating set
3) ◆ n. table
4) ◆ n. position
5) quantity1
4/1
2/9
86
Q1
6M
31
TAVOLA RICAMBI - SPARE PARTS - PIECES DE RECHANGE - ERSATZTEILE
ONOFF
START
*
VE
NULLEITERAUFMASSENULVERBONDENMETMASSA
NEUTROCONECTADOAMASA
NEUTRERACCORDEAUBATINEUTRALBONDEDTOFRAME
NEUTROCOLLEGATOAMASSA
*
6560
Hz A
1050
1555
500
300
V
ST
RS0
200
100
TR0
h
HOURMETER
I
0
EA1
2520
125
1-3 13 18 17 16 20-21-22 12
21-22-2314
11
8
2
19
15
4-5-6
EA1
12
50
Hz
50
Hz 3
EA1
4
12
TS 0000 GETS 0000 GE
V.le Europa,59 - 20090 CUSAGO (MI) ITALY
Tel. +39-02 90352.1 - fax +39-02 90390466
0987654321
TYPE
SERIAL N°
22/0
3/00
R1G
B
The requested data are to be found on thedata plate located on the machine structure,quite visible and easy to consult. ✹
ABBREVIATIONS AND SYMBOLS:(EV) When ordering, specify the engine type and
the auxiliary voltage(ER) Engine with recoil starter only(ES) Engine with electric starter only(VE) E.A.S version only.(QM) When ordering, specify the length in meters(VS) Special version only(SR) By request only
© MOSA REV.1-02/09
GE 275 VPSXGE 275 VPMSX
JM1E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
2
3
4
5
6
7
8
9
10
12
13
14
1516
17
18
11
5a
6
19
20
Pos. Rev. Cod. Descr. Note2 842762200 MOTORE VOLVO PENTA3 842252020 SERBATOIO CARBURANTE4 842251242 CORNICE FISS.PANNELLO IN GOMMA5 842753100 ALT. STAMFORD5a 842753100 ALT. MARELLI Da REV.1-02/09 Del.183/08 24/10/086 842251035 ANTIVIBRANTE A CAMPANA7 842231050 BASAMENTO8 842252134 PANNELLO GOMMA USC.TUBI SERBAT9 842778152 LISTELLO CHIUSURA INFERIORE RADIATORE10 764409975 SENSORE LIVELLO CARBURANTE(L=225)11 842252026 TAPPO SERB. CARBUR. BAIONETTA D8012 764409150 BATTERIA13 842759154 STAFFA FISSAGGIO BATTERIA14 842251100 ROLL BAR15 842772069 GUARNIZIONE16 842772070 TUBO SCARICO17 841452069 GUARNIZIONE SCARICO MOTORE18 842252050 SILENZIATORE DI SCARICO19 841252032 RONDELLA Da REV.1-02/09 Del.183/08 24/10/08
Versione con Alt. Marelli20 842252032 PIASTRA SPESSORE ALTERNATORE Da REV.1-02/09 Del.183/08 24/10/08
Versione con Alt. Marelli
Pos. Rev. Cod. Descr. Note2 842762200 VOLVO PENTA ENGINE3 842252020 FUEL TANK4 842251242 RUBBER FIXING FRAME5 842753100 STAMFORD ALTERNATOR5a 842753100 MARELLI ALTERNATOR From REV.1-02/09 Del.183/08 24/10/086 842251035 VIBRATION DAMPER7 842231050 BASE8 842252134 RUBBER PROTECTION FOR OUTLET PIPES9 842778152 LOCKING LISTEL FOR RADIATOR BUTTOM10 764409975 FUEL LEVEL SENSOR11 842252026 FUEL TANK, CAP12 764409150 BATTERY13 842759154 BATTERY SUPPORT BRACKET14 842251100 ROLL BAR15 842772069 GASKET16 842772070 EXHAUST PIPE17 841452069 GASKET18 842252050 MUFFLER EXHAUST19 841252032 WASHER From REV.1-02/09 Del.183/08 24/10/08
Version with Alt. Marelli20 842252032 PLATE ALTERNATOR (SPACER) From REV.1-02/09 Del.183/08 24/10/08
Version with Alt. Marelli
© MOSA REV.1-02/09
GE 275 VPSXGE 275 VPMSX
JM1.1E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
1 2 3 4 5 6
7
8
9
10
11
12
13
14
15
16
17
18
19
8
8
20
21
22 23
24
822
25
26
27
28 29
30
31
32
33
22
34
35
36373839
40
11
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM2E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
Pos. Rev. Cod. Descr. Note1 309509005 GUARNIZIONE / GASKET2 842779553 SCHEDA CANBUS / PCB CANBUS3 744507057 CHIAVE SERRATURA QUADRO ELETT. / ELECTRICAL BOARD KEY4 842259550 CONTROLLO GRUPPO ELETTROGENO / GENERATOR CONTROL “GECO”5 842257020 PANNELLO FRONTALE / FRONT PANEL6 842777236 SELETTORE A 2 POSIZIONI / TWO-WAY SWITCH7 744508112 SERRATURA PER COPERCHIO FRONT. / FRONT COVER LOCK8 1244020 CANALINA PER CAVI / CABLE CHANNEL9 1242050 TERMINALE MORSETTIERA / TERMINAL BOARD
10 1242060 TERMINALE MORSETTIERA / TERMINAL BOARD11 1243020 GUIDA PER MORSETTIERA / TERMINAL GUIDE12 842257306 TRASFORMATORE AMPEROM. / TRANSFORMER13 84278C022 CONNETTORE COMPLETO / CONNECTOR COMPLETE14 1244010 CANALINA PER CAVI / CABLE CHANNEL15 1240040 MORSETTIERA / TERMINAL BOARD16 1241010 PIASTRINA / PLATE17 1240020 MORSETTO 4mmq /TERMINAL 4mmq18 107509045 PORTAFUSIBILE / HOLDER, FUSE19 842257036 STAFFA SUPP.INTERR.MAGNETOTER. / BRACKET MAGNETO SWITCH20 842259830 UNITA’CARICA BATTERIA 2.5A / 24V/UNIT CHARGE BATTERY21 842257010 SCATOLA ELETTRICA / ELECTRIC BOX22 306418310 GUARNIZIONE (L=MT.1) / PROTECTION GASKET (L=MT.1)23 842257324 PROTEZIONE CASSETTA ALIMENTAZ. / SUPPLY BOX PROTECTION24 744507237 CONTATTO NC AGGIUNTIVOPER PULSANTE / SUPPLEMENTARY CONTACT FOR PUSH-KNOB25 842257325 INT.MAGNETOTERM.(SCAT) 4P 400A / CIRCUIT BREAKER26 842257015 COPERCHIO SCATOLA ELETTRICA / ELECTRIC BOX COVER27 842257061 SEPARATORE SCATOLA ELETTRICA / ELECTRIC BOX SEPARATOR28 842258005 CARENATURA ANTERIORE / COVER FRONT29 315507215 AVVISATORE ACUSTICO / ACOUSTIC ALARM SYSTEM30 842257170 CUSTODIA FISSA CONNETTORE 16C. / CONNECTOR HOUSING31 842257173 FRUTTO SPINA CONNETTORE 16C / CONNECTOR PLUG32 842257174 COPERCHIETTO DI CHIUSURA 16C. / BLIND PLATE33 744507219 PULSANTE STOP D’EMERGENZA / EMERGENCY PUSH BUTTON STOP34 744508112 SERRATURA PER COPERCHIO FRONT. / FRONT COVER LOCK35 744507057 CHIAVE SERRATURA QUADRO ELETT. / ELECTRICAL BOARD KEY36 842257313 COPERCHIO CHIUS.CASS.ALIMENT. / SUPPLY BOX COVER37 842258161 SCHERMO PROTETTIVO / PROTECTIVE FRAME38 842258264 PIASTRINA ISOLANTE FERMA CAVI / RUBBER WIRE PROTECTION39 842259505 PANNELLO GOMMA PROTEZIONE CAVI / RUBBER WIRE PROTECTION40 842258073 TIRANTE / TIE-ROD
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM2.1E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
1 2 3 4
56
7
8
9
10
11
12
13
14
15
16
17
2
18 19 20
21
22
23
24
25
26
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM3E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
Pos. Rev. Cod. Descr. Note1 842258004 FIANCATA CARENATURA SX2 842258464 STAFFA FERMO FONOASSORBENTE3 842258170 CAREN.SUP.LATO ALTERNATORE4 842258095 CASSONETTO ASPIRAZIONE ARIA5 842757102 SUPP.SCATOLA APPARECCH.ELETTR.6 842258003 FIANCATA CARENATURA DX7 744508090 SQUADR.FISS.SCHERMO PORTELLA8 744508089 SCHERMO PER PORTELLA9 744508136 MANIGLIA A PULSANTE
10 842258426 FIANCATA LATO STRUMENTI11 744508140 CERNIERA PER FIANCATA12 842758020 FIANCATA POSTERIORE DX13 842778215 PARETE SCARICO ARIA MOTORE14 105112270 GUARNIZIONE (L=MT.1)15 842252053 COPERCHIETTO PARAPIOGGIA D12016 842252068 FLANGIA PER TUBO SCARICO17 842778175 CAREN.SUP.LATO ALTERNATORE18 842258293 PIASTRA FISS. CASSONETTO ESP.19 842258065 GRIGLIA USCITA ARIA20 842752078 RACCORDO TUBO SCARICO21 842758025 FIANCATA POSTERIORE SX22 842772058 PROTEZIONE TERMICA23 841659358 ANELLO DOPPIO24 841659357 TIRANTE IN GOMMA25 841658361 GHIERA PER COPERCHIO ERMETICO26 841658360 COPERCHIO ERMETICO
Pos. Rev. Cod. Descr. Note1 842258004 LEFT COVER2 842258464 SOUND-PROOF MATERIAL BRACKET3 842258170 TOP COVER, ALTERNATOR SIDE4 842258095 BOX AIR INLET5 842757102 SUPPORT, ELECTRICAL EQUIPMENT6 842258003 COVER RIGHT SIDE7 744508090 FIXING BRACKET DOOR SCREEN8 744508089 GLASS COVER9 744508136 HANDLE
10 842258426 COVER COMMANDS SIDE11 744508140 LATCH12 842758020 REAR RIGHT COVER13 842778215 ENGINE AIR EXHAUST SITE14 105112270 STRIP, SEALING (L=MT.1)15 842252053 WATER CAP16 842252068 EXHAUST PIPE FLANGE17 842778175 TOP COVER, ALTERNATOR SIDE18 842258293 FIXING PLATE FOR INTAKE COVER19 842258065 AIR OUTLET GRILL20 842752078 PIPE FITTING, EXHAUST PIPE21 842758025 REAR LEFT COVER22 842772058 THERMOPROTECTION23 841659358 DOUBLE RING24 841659357 TIE ROD25 841658361 FLANGE FOR AIR-TIGHT SEALED COVER26 841658360 ERMETIC COVER
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM3.1E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
1 2
3
45678
9 10
11 12 13
16
14
15
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM4E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I
Pos. Rev. Cod. Descr.1 744508140 CERNIERA PER FIANCATA2 309509005 GUARNIZIONE3 842258163 CHIUSURA A CRICCHETTO4 105111450 MORSETTO5 842758030 FASCIA CENTRALE CAREN. SUP.6 842258460 FILO ARMONICO7 6033050 GOLFARE8 842258464 STAFFA FERMO FONOASSORBENTE9 842258137 SCARPETTA PER CHIUSURA
10 744508136 MANIGLIA A PULSANTE11 842258458 FIANCATA INTERMEDIA12 842258444 LISTELLO FERMO FONOASSORBENTE13 842258501 FONOASSORBENTE PER PORTIERA14 842258428 FIANCATA INTERMEDIA15 842258200 CASSONETTO16 842258067 FONDO CASSONETTO ESP. ARIA
Pos. Rev. Cod. Descr.1 744508140 LATCH2 309509005 GASKET3 842258163 JACK-GEAR LOCK4 105111450 TERMINAL5 842758030 TOP COVER MIDDLE FRAME6 842258460 HARMONIC WIRE7 6033050 UP-EAVING RING8 842258464 SOUND-PROOF MATERIAL BRACKET9 842258137 CLOCK LATCH
10 744508136 HANDLE11 842258458 MIDDLE COVER12 842258444 STOP LISTEL FOR SOUND-PROOF MATERIAL13 842258501 SOUND-PROOF MATERIAL FOR DOOR14 842258428 MIDDLE COVER15 842258200 CASE16 842258067 AIR OUTLET GRATE
© MOSA REV.0-05/08
GE 275 VPSXGE 275 VPMSX
JM4.1E
D
NL
RicambiSpare partsPiéces de rechanges
ErsatzteileTabla de recambios
25/0
5/07
842
77-I