kva mva - ge grid · pdf filekva mva mip mig mgc g60 ... 100% stator ground fault protec-tion...
TRANSCRIPT
GENERATOR Selector Guide
PR
OT
EC
TIO
NC
ON
TR
OL
MO
NIT
OR
ING
489 DGP
KVA MVA
MGCMIGMIP G60
FEATURES DEVICE 489 DGP G60 LPS-O MGC MIG MIP
Overspeed 14
Distance, Phase 21P
Overexcitation, Volts/Hertz 24
Synchronism Check or Synchronizing 25
Undervoltage, Phase 27P
Reverse Power 32
Undercurrent 37
Loss of Field 40
Reverse-Phase or Current Unbalance 46
Reverse Phase Sequence Voltage 47
Thermal Image 49
Breaker Failure 50BF
IOC, Ground/Neutral/Phase 50G/N/P G/N/P G/N/P P G/PTOC, Ground/Neutral/Phase 51G/N/P G/N/P G/N G/N/P N/P G/PTOC, Voltage Restrained 51V
Overvoltage, Neutral/Phase 59N/P N/P P N/P N/P100% Stator Ground 64 27TN
Current Directional, Neutral/Phase 67/N/P N/P N/P
Loss of Mains 78Over and Underfrequency 81O/U O/U O/U O/U O/UDifferential, Stator 87S
Voltage Transformer Fuse Failure VTFF
Accidental Energization
Sequential Trip Logic
Power Supply, AC or DC AC/DC DC AC/DC DC AC/DC AC/DC AC/DCRedundant Power Supplies
CT Inputs 5A/1A 5/1 5/1Self-Test Failure Contact
Settings Groups 2 1 8 4 2
Flash Memory
Contact Inputs (Fixed) – up to 2 6Contact Inputs (Programmable) – up to 7 3 48 12 2 2Contact Outputs (Fixed) – up to 1 8 4 5 2 2Contact Outputs (Programmable) – up to 5 19 48 24 4 4Virtual Inputs 32Virtual Outputs 64Display
Keypad
Trip/Coil Supervision T 22Programmable Logic
User-Programmable LEDs
Timers
Digital Counters
Digital Elements
IRIG-B Input
Analog Outputs 4Current – RMS
Current – Phasor
Current – Demand
Voltage – RMS
Voltage – Phasor Phase-Phase
Power Factor
Symmetrical Components
MW, MVA, Mvar
MW, MVA, Mvar Demand
Energy Metering
Frequency
Analog Inputs 4Fault Report
Event Recorder
Oscillography (Waveform Capture)
Data Logger
Interface Program
RS232 Port 1 2 1 3 1 1RS485 Port 2 1/2 2 1 1Baud Rate 19.2k 115k 9.6k 19.2k 19.2k10 BaseF Port 1/2/3ModBus® Protocol
ModBus® User Map
DNP3 Protocol
UCA2/MMS Protocol
TCP/IP
CO
MM
UN
ICA
TIO
NS
LPS-O
28 www.GEindustrial.com/Multilin
3
29
3
COMINGSOON
Versatile relay for the
protection of AC generators.
UR Generator Management RelayTM
Features and Benefits
FlexLogic™ and distributed FlexLogic™
Virtual and expandable I/Os to reducehardware costs
User-programmable LEDs
User-definable display messages
Flash memory for field upgrades
Common drawout modules to reducespare parts costs
Multiple settings groups
Applications
Any size of AC generator driven bysteam, gas and hydraulic turbine
Stand-alone or component in automatedsubstation control system
enerVista.com compatible (see page 275)
Protection and Control
100% stator ground differential
Loss of excitation
Reverse and low forward power
Current unbalance
Overexcitation
FlexElement™ universal comparators
Distance backup
Monitoring and Metering
Current, voltage, power, power factor,frequency, energy
Contact input and output status
User Interfaces
URPC software for setting, monitoring
RS232, RS485 and Ethernet ports
GE Multilin
ProtectionThe G60, a digital GeneratorManagement Relay, is designedspecifically for AC generators ofany size, driven by steam, gas orhydraulic turbine.
As part of the Universal RelayFamily, the G60 provides superiorprotection which includes:
100% Stator Ground
100% stator ground fault protec-tion is provided by an adaptivevoltage differential featureresponding to the unbalance ofthe third harmonic at the machineterminals and at the neutral point.The protection could be supple-mented or replaced by a thirdharmonic undervoltage functionresponding to the voltage at theneutral side of the machine.
Loss of Excitation
Impedance based two-stageprotection responds to positivesequence voltage and current.
Sensitive Directional Power
Available for reverse power andlow forward power protection.
Current Unbalance
Meets ANSI standards to mini-mize risk of heat damage causedby unbalance in the generator.
Overcurrent Protection
IOC and TOC functions availablefor phase, ground, and neutral.Time curves provided includethree IEEE, four IEC, four GE IAC,I2t, definite time and two user-programmable curves. Phase TOCfunctions use voltage restraint.
Overexcitation Protection
Provided through a Volts/Hertzfunction with programmableinverse time characteristic.
Frequency Protection
Over and underfrequency protec-tion available.
Voltage Protection
Over and undervoltage protectionprovided.
Out-of-Step Tripping
Integrated out-of-step tripping andpower swing blocking functions useeither two or three characteristics totrace the positive sequence imped-ance trajectory to detect an out-of-step condition. Programmable tripaction (instantaneous or delayed).
Synchronism Check
Two independent synchronismcheck elements monitor differ-ences in voltage magnitudes,phase angles and frequencies.
User-Definable Protection
Functions
The G60 relay includes 16 universal comparators calledFlexElements™ that can be pro-grammed to respond to changesin any measured value.
G60 UR Generator Management RelayTM
www.GEindustrial.com/Multilin30
3
830710A6.CDR
32 50/27 50P40
50G 51G
64TN
50N 51P 51N 46 67P 67N 68 78
24 59P 59N 81U27P 59_2 81O
Metering
TRIP
CLOSE
27TN 59Aux27Aux
G60 Generator Management Relay
G
52
R
87S
25
Functional Block Diagram
Typical Wiring
G60 UR Generator Management RelayTM
www.GEindustrial.com/Multilin 31
3
830700AP.CDR
1
PowerSupply
9
CPU
MODULE ARRANGEMENT (Rear View)JU MX LW KV BHT DN GS P FR
No. 10AWGMinimum
GROUND BUS
AC or DC
DC
( D
C O
NLY
)
Groundat Remote Device
Shieldedtwisted pairs
Co-axial
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXDRXD TXD
SGND SGND
1 832
20764522
25 PINCONNECTOR
9 PINCONNECTOR
2 23 34 45 56 67 78 89 9
CONTACTS SHOWNWITH NO
CONTROL POWER
6
I/O
8
VT/CT
8
CT
TC
TC
2
1
VO
LTA
GE
SU
PV
.V
OLT
&C
UR
RE
NT
SU
PV
.
G60UR GeneratorManagement Relay
GE Multilin
CONTACT IN 5aCONTACT IN 5cCONTACT IN 6aCONTACT IN 6c
COMMON 5b
CONTACT IN 7aCONTACT IN 7cCONTACT IN 8aCONTACT IN 8c
COMMON 7b
SURGE
6a
8a
5b
7b
8b
5aH
H
H
H
H
H
H
H
H
H
H
HHHHH
HHHHH
H
HH
H
H
H
H
H
H
H
H
H
H
H
H
H
7a
6c
8c
5c
7c
1a
2b
1c
1b
2c
2a
4a
4c
3b
3a
4b
3c
1
2
3
4
DIGITAL I/O 6G I
V
I
V
I
V
I
V
CRITICALFAILURE
48 VDCOUTPUT
CONTROLPOWER
HILO
PO
WE
R S
UP
PLY
1
FILTERSURGE
3a
1b
8a
6b
8b
6a
B
B
B
B
B
B
B
B
B
B
3b
1a
2b
5b
9A
COM
COM
C
PU
D3b
D4b
D5b
D2a
D3a
D4a
D5a
D6a
D7b
RS485COM 1
RS485COM 2
IRIG-B
SURGE
1c
4a
FF FFFFFFFFFFFFFFFFFF
8c
8a
3c
5a
5c
7c
CURRENT INPUTS6
a
7a
6c
2c
VX
VA
VB
VC
4c
1a
4b
1b
2a
3a
2b
3b
VOLTAGE INPUTS8A / 8B
VX
VA
VB
VC
F FFFFF
5a
5c
7c
6a
7a
6c
VA
VB
VC
VOLTAGE INPUTS
VA
VB
VC IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
TYPICAL CONFIGURATIONTHE AC SIGNAL PATH IS CONFIGURABLE
POSITIVE WATTSOPEN DELTAVT CONNECTION (ABC)
3c
4c
4b
4a
1c
1a
MMMMMMMMMMMM
1b
3b
CURRENT INPUTS8E / 8F
2a
3a
2b
2c
IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
ABC
R
MODULES MUST BEGROUNDED IF TERMINAL IS
PROVIDED
G60 UR Generator Management RelayTM
www.GEindustrial.com/Multilin32
3
Ordering
G60 * 00 HC * F** H** M** P** U** W** For full sized horizontal mountG60 * 00 VF * F** H** M** P** For reduced size vertical mountG60 Base unit
A RS485 + RS485 CPU C RS485 + 10BaseF (MMS/UCA2 and ModBus® TCP/IP) CPUD RS485 + redundant 10BaseF (MMS/UCA2 and ModBus® TCP/IP) CPU
00 No software optionsHC Horizontal mountVF Faceplate with keypad and display
H 125/250V AC/DC power supplyL 24/48V (DC only)
8A 8A Standard 4CT/4VT8B 8B Sensitive Ground 4CT/4VT8C 8C Standard 8CT8D 8D Sensitive Ground 8CT
XX XX XX XX No module6A 6A 6A 6A 6A 2 Form A (voltage w/opt current) and 2 Form C outputs, 8 digital inputs6B 6B 6B 6B 6B 2 Form A (voltage w/opt current) and 4 Form C outputs, 4 digital inputs6C 6C 6C 6C 6C 8 Form C outputs6D 6D 6D 6D 6D 16 digital inputs6E 6E 6E 6E 6E 4 Form C outputs, 8 digital inputs6F 6F 6F 6F 6F 8 Fast Form C outputs6G 6G 6G 6G 6G 4 Form A (voltage w/opt current) outputs, 8 digital inputs6H 6H 6H 6H 6H 6 Form A (voltage w/opt current) outputs, 4 digital inputs6K 6K 6K 6K 6K 4 Form C and 4 Fast Form C outputs6L 6L 6L 6L 6L 2 Form A (current w/ opt voltage) and 2 Form C outputs, 8 digital inputs
6M 6M 6M 6M 6M 2 Form A (current w/ opt voltage) and 4 Form C outputs, 4 digital inputs6N 6N 6N 6N 6N 4 Form A (current w/ opt voltage) outputs, 8 digital inputs6P 6P 6P 6P 6P 6 Form A (current w/ opt voltage) outputs, 4 digital inputs6R 6R 6R 6R 6R 2 Form A (no monitoring) and 2 Form C outputs, 8 digital inputs6S 6S 6S 6S 6S 2 Form A (no monitoring) and 4 Form C outputs, 4 digital inputs6T 6T 6T 6T 6T 4 Form A (no monitoring) outputs, 8 digital inputs6U 6U 6U 6U 6U 6 Form A (no monitoring) outputs, 4 digital inputs5C 5C 5C 5C 5C 8 RTD inputs5E 5E 5E 5E 5E 4 DCmA inputs, 4 RTD inputs select a maximum of 45F 5F 5F 5F 5F 8 DCmA inputs
™Generator Management Relay is a trademark of GE Multilin.
G60 GuideformSpecificationsFor an electronic version of the G60guideform specifications, pleasevisit: www.GEindustrial.com/Multilin/specs, fax your request to 905-201-2098 or email to [email protected].
Monitoring andMeteringAdvanced metering functions arecommon across the UR platform(see page 7). The G60 providesadditional specific monitoringand metering that includes:
Metering
Voltage phasors (both magnitudeand phase angle), voltagesymmetrical components, currentphasors, current symmetricalcomponents, current true one-cycle RMS value, active, reactive,
apparent power, power factor (allpower values per phase and total)energy, and frequency are meas-ured. These signals are availablefor local or remote display usingcommunications, and can bestored in the oscillography recordor data logger.
www.enerVista.com
enerVista enabledenerVista enabled See page 275.Accessories
Interactive UR Training CD-ROM available. Visitwww.GEindustrial.com/multilin/trainingcd to order.
33
3
Economical protection, monitoring
and metering for generators.
SR Generator Management RelayTM
Features and Benefits
Configurable analog output channels
Digital inputs for protection, control ordiagnostic functions
Data communications from 300 to19,200 bps
Multiple communications ports
Event recording (40 events)
Oscillography (64 cycles)
Drawout construction
Applications
25, 50 or 60 Hz synchronous or inductiongenerators
Primary, backup and co-generatorapplications
enerVista.com compatible (see page 275)
Protection and Control
Phase differential
100% stator ground
Overcurrent, over and undervoltage
Monitoring and Metering
RMS and negative sequence current,voltage
Three-phase power and temperature
User Interfaces
40 character display with full keypad
RS232 and RS485 ports
URPC functionality
GE Multilin
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin34
3
808783E6.cdr
87G
27TN59GN
49
50
46
86
49
12
38
50BF
Outputrelays
Trip CoilSupervision
RS485RS485
Analoginputs
Analogoutputs
Outputrelays
489
RS232
+
+
-
-4
4
6
52
GENERATOR
41
39
76
50/51GN
60FL
51V
50/27
32
21
40
40Q
24
59
810
81U
27
47
67
ProtectionThe 489 Generator ManagementRelay is an economical choice forprotection, metering and monitor-ing of synchronous or inductiongenerators of 25, 50 or 60 Hz. Itcan be used in primary, backupand co-generation applications.Protection features include:
Machine Fault Protection
A dual slope percentage differen-tial element and an IOC elementprotect against machine faultsduring operation and throughstartup respectively.
Functional Block Diagram
Dual slope percentage differential.
Stator Ground Protection
In addition to a ground overcur-rent element, the 489 comparesthe machine neutral voltage andground current to determine ifground directional faults arewithin or outside the generator.100% stator ground fault protec-
tion is provided through an over-voltage element and an adaptiveelement.
Stator Thermal Protection
The stator RTDs are monitored toprovide stator thermal protectionduring running overload condi-tions. Additionally, the RTDs votefor high reliability. The thermalmodel overload curve may bebiased by the current unbalanceand/or the hottest stator RTD.Machine cooling is simulatedusing exponential decay of thethermal capacity used register. Thethermal overload curve may alsobe used to provide start-up protec-tion for an induction generator.
OverspeedDistanceVolts/HzUndervoltageInadvertent generator energizationReverse power/low forward powerBearing overtemperature (RTD)Bearing vibration (analog inputs)Loss of excitation (impedence)Loss of field (reactive power)Negative sequence overcurrent (I2t)Voltage phase reversalStator thermal (RTD/thermal model)High-set phase overcurrentBreaker failure detectionOffline overcurrentGround overcurrentVoltage restrained phase overcurrent Overvoltage100% stator groundVT fuse failure Ground directionalOverexcitation (analog input)Overfrequency/underfrequencyElectrical lockoutPercentage differentialSequential tripping logicTrip coil supervision
12212427
50/2732383940
40Q46474950
50BF50
50/51GN51V59
59GN/27TN60FL67768186
87G
Sync
hron
ous
Indu
ctio
n
489 Application
OPERATEREGION
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
00 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
I OP
ER
AT
E (
mu
ltip
les
of
CT
)
I RESTRAINT (multiples of CT) 808790A2.cdr
Slope 1 = 10%
Slope 2 = 20%
Minimum Pickup = 0.10 x CT
Bearing Protection
Any of the 12 RTD inputs may beconfigured to monitor and protectagainst bearing overtemperatureconditions. Two RTDs can vote togive higher reliability. Additionally,four analog inputs can be config-ured to monitor bearing vibrationtransducers. This provides alarmor trip functions perfect for smallermachines.
Excitation System
Protection elements includeoverexcitation, over and under-voltage. Alarm or trip functionsmay be activated by definite orinverse time curves. Loss of fieldprotection is provided via loss ofexcitation and reactive power.
Rotor Thermal Protection
A definite time alarm and inverseTOC curve trip protect the gener-ator rotor from overheatingcaused by negative sequencecurrents. The rating for bothcontinuous and short time opera-tion is defined by the equation:K=I2t. A variable reset rateprovides a thermal memory ofprevious unbalance conditions.
Negative sequence inverse TOC.
System Backup Protection
Three voltage restrained overcur-rent elements provide backupprotection for system faults. Thepickup level for the inverse timecurves are adjusted in conjunc-tion with the measured phase tophase voltage.
Voltage restraint characteristic.
High-set phase overcurrentprovides backup protection for onor offline elements. If any individ-ual phase current exceeds thepickup level, a trip will occur.
Distance protection uses two zonesof mho phase to phase protection(total of six elements), which isintended as a backup for primaryline protection against internal andunit transformer faults.
Sequential Tripping Logic
During routine shutdown, and forless critical trips, the sequentialtrip function can be used toprevent overspeed. Turbine valvestatus is monitored via digitalinput. When the valve is closed,either low forward power orreverse power will trip the breakeronce the generator output hasfallen below the programmed level.
Abnormal Frequency
Alarm functions for over andunderfrequency are included. Ifoperator action is not taken tocorrect the situation, a trip willoccur if conditions persist orbecome more severe.
Operational Failures
On a total or partial loss of theprime mover (if the power gener-ated is less than the no-loadlosses of the machine), realpower will start flowing back intothe generator. The reverse powerfunction can be set to trip thegenerator when it begins motor-ing. Accidental energizationprotection limits damage if thegenerator is accidentally placedonline while it is shutdown.
Overspeed
Twenty-four VDC power is provid-ed for mounting a probe orsensor near the shaft key orkeyway, with an assignable digi-tal input configured as atachometer to monitor the probeoutput signal.
The 489 can monitor speed via an assignableinput.
Monitoring Protection
With breaker failure enabledwhen the 489 initiates a trip andgenerator current does not dropto zero after the pre-set timedelay, a breaker failure alarm willoccur. When the breaker is closed,the trip coil circuit monitors itselffor a break in continuity, whichtriggers a trip coil monitor alarm.VT fuse failure triggers an alarmand disables features that usevoltage measurements.
Monitoring andMeteringThe 489 features advancedmetering and event recordingfunctions which include:
Metering Functions:
Complete monitoring functionsinclude:
Current Voltage Power: kW kvar kVA Energy use: MWh Mvarh Power factor Frequency Four analog inputs
Demand and peak demand func-tions include:
Current Power: kW kvar kVA
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin 35
3
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
00 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Cu
rve
Pic
kup
Mu
ltip
lier
Phase-Phase Voltage / Rated Phase-Phase Voltage 808792A2.cdr
SENSOR
ROTATING SHAFT
808755E2.dwg
TO 489DIGITAL
INPUT
0.1
1
10
100
1000
0.01 0.1 1 10 100
K=1.0 4.0 15 40 100
Tim
e (S
eco
nd
s)
Negative Sequence Current / Rated Current808791A2.cdr
Communications
A front panel RS232 port and tworear panel RS485 ports supportModBus® RTU and DNP 3.0 proto-col. The RS232 port can transmitdata at 9600 bps, while the twoRS485 ports are variable from300 to 19,200 bps. Data may beaccessed from all three portssimultaneously and independently.All measured values are alsoavailable via the four analogoutputs.
A typical communications setupcould include a programmablelogic controller (PLC) using thefour analog outputs for controlfunctions. The front panel RS232port could be used for local inter-rogation and troubleshooting.One of the 485 ports could beused to connect a DCS or SCADAsystem, for continuous onlinemonitoring by the operationspersonnel. The second RS485port could be wired to a modem,which would be used for off-siteinterrogation of the 489 by engi-neering personnel.
Data is available from the 489 via threecommunications ports and four analog inputs.
808766E4.cdr
MODEM
SCADA/DCS
PLC
4 ANALOGOUTPUTS
AUXILIARYRS485
FRONT RS232
COMPUTERRS485
489 PC
489 PC489 Generator Management Relay™
489 IN SERVICE BREAKER OPEN R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
SETPOINT ACCESS BREAKER CLOSED
COMPUTER RS232 HOT STATOR
MESSAGE
VT FAILURE
BREAKER FAILURE
PROGRAM PORTSETPOINT 7 8 9
4 5 6
1 2 3
. 0 HELP
MESSAGE
VALUE
ACTUAL
ESCAPE
ENTER
RESET
NEXT
RESETPOSSIBLE
COMPUTER RS485
AUXILIARY RS485
ALT. SETPOINTS
489 STATUS GENERATOR STATUS OUTPUT RELAYS
NEG. SEQUENCE
GROUND
LOSS OF FIELD
A = 0 C = 0B = 0 AMPS
All measured quantities can beviewed on the front panel display,through the communicationsports, or through one of the fouranalog outputs.
Event Recording
The 489 records and timestampsthe last 40 events, their cause andlast measured parameters. Alltripping functions are classed asevents. Alarm functions may beselectively chosen as events. Allof the 489 event data may beaccessed via the three communi-cations ports or viewed on thefront panel display to help withtroubleshooting.
Oscillography
The 489 samples the current andvoltage inputs at a rate of 12times per cycle. These samplesare stored in a configurable bufferup to 64 cycles long. The triggerposition setpoint allows the userto define how much of the buffercycles are pre and post trigger.
The trace memory may beextracted from the relay throughthe communications ports. It maybe displayed using the 489PCsoftware provided with the relay.This allows the user to examinemagnitudes and phase relation-ships of the measured signalswhen troubleshooting.
Oscillography data can be displayed usingthe 489PC program.
Self-Test
The 489 initiates a self-test atpower up and continues in thebackground during operation. Aself-test failure triggers an alarm.
Inputs and OutputsThe 489 offers a multitude ofconnections for analog and digi-tal input and output.
Analog I/Os
The four input channels monitoredby the 489 can be used for func-tions such as the protection andmonitoring of bearing vibration.The four output channels can beconfigured to any measuredparameter.
Digital Inputs
Seven assignable digital inputscan be used for functions such asa tachometer for overspeedcontrol.
RTD Inputs
Twelve RTD inputs allow the userto monitor both stator and bear-ing temperature. A voting featureallows two RTDs monitoring the same device to vote for highreliability.
Output Relays
The 489 has six output relays: onetrip, three auxiliary, one alarm,and one self-test relay. LEDs onthe front panel show the status ofeach output.
User InterfacesThe 489 allows users ease ofaccess through:
Keypad and Display
The front panel features a 40character display and a keypadthat includes full numeric keysand control keys.
LED Indicators
The front panel features 22 LEDindicators. Eight of these indicate489 status, eight indicate genera-tor status, and six indicate theoutput relay status.
IRIG-B Input
An IRIG-B input is provided fortime synchronization via satellitesignal.
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin36
3
489 IN SERVICE BREAKER OPEN R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
SETPOINT ACCESS BREAKER CLOSED
COMPUTER RS232 HOT STATOR
MESSAGE
VT FAILURE
BREAKER FAILURE
PROGRAM PORTSETPOINT 7 8 9
4 5 6
1 2 3
. 0 HELP
MESSAGE
VALUE
ACTUAL
ESCAPE
ENTER
RESET
NEXT
RESETPOSSIBLE
COMPUTER RS485
AUXILIARY RS485
ALT. SETPOINTS
489 STATUS GENERATOR STATUS OUTPUT RELAYS
NEG. SEQUENCE
GROUND
LOSS OF FIELD
EFGH
1
LOWER
ELOWER
EUPPER
FUPPER
F
UPPER
GUPPER
G
LOWER
HLOWER
H
R1 TRIP NC
R1 TRIP NO
R2 AUX COM
R3 AUX NC
R3 AUX NO
R4 AUX.COM
R5 ALARMNC
R5 ALARMNO
R6 SERVICECOM
NUETRALVT COM
NUETRALVT
TRIP COIL SUPERVISION+
IRIG-B+
IRIG-B-R1 TRIP COM
R2 AUX NO
R2 AUX NC
R3 AUX COM
R4 AUXNO
R4 AUX.NC
R5 ALARMCOM
R5 SERVICE NO
R6 SERVICENC
TRIP COILSUPERVISION-
PHASE VT COM
PHASE A VT
Ia NEUTRALCT
Ib NEUTRALCT
Ic NEUTRALCT
IA OUT CT
IB OUT CT
IC OUT CT
Ia NEUTRALCT
Ib NEUTRALCT
Ic NEUTRALCT
IA OUT CT
IB OUT CT
IC OUT CT
1A GROUNDCT
1A GROUNDCT
GROUND(HGF)CT
GROUND(HGF)CT
FILTERGROUND
SAFETYGROUND
PHASE B VT
PHASE C VT
CONTROLPOWER -
CONTROLPOWER +
2 3 4 5 6 7 8 9 10 11 12
A1
B1
B2
B3
B4
RTDSHD
COM
-
+AUX.RS485
A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 -COM
-COMANSHOANALOG OUTPUTS ANALOG INPUTS
+ - COM#1 #2 #3 #4 #5 #6 #7SW com
+24Vdc
#1+ #2+ #3+ #4+ #1+#2+#3+#4+
COMP RS485ASSIGNABLE INPUTS
+24Vdc
A18 A19 A20 A21 A22 A23 A24 A25 A26 A27
C1+
+
C2ACCESS
BREAKER STATUS
-
-
C3
C4
D27D26D25D24D23D22D21D20D19D18D17D16
RTD6RTD5RTD4RTD3RTD2RTD1
RTD7 RTD8 RTD9 RTD10 RTD11 RTD12
D15D14D13D12D11D10D9D8D7D6D5D4D3D2D1
LOW VOLTAGE INPUTS, DO NOT HI-POT!
489GENERATOR MANAGEMENT RELAYTM
808784E9.cdr
DISPLAYForty character LCD display for setpoint programming, monitoring, status, and fault diagnostics.Up to twenty scrolling messagesmay be defined as the default display.
OUTPUT RELAYSIndicates any operation of the489 output relays.
GENERATOR STATUSIndicates if the generator is online or offline. Also indicates pickups of several protective features.
TRIP COIL SUPERVISIONMonitors the trip circuit for continuitywhen the generator is online andalarms if that continuity is broken.
KEYPADNumeric keys allow for simpleentry of setpoint values.Control keys allow simplenavigation through setpointand actual value messagestructures.Help key provides contextsensitive help messages.
ANALOG SIGNALSFour isolated 4-20 mA analog outputsmay be used to replace costlytransducers. They may be fieldprogrammed to reflect any measured parameter.Four 0-1 or 4-20 mA analog inputs maybe used to monitor any transducersignal. Possible applications includevibration and field current monitoring.
DIGITAL INPUTSAccess jumper input providessetpoint programming security.Breaker status input tells 489 ifthe generator is online or offline.Seven assignable digital inputs maybe field programmed for a variety offunctions including tachometer.
GROUNDSeparate safety and filter ground.All inputs meet C37.90 EMI, SWC,RFI interference immunity.
CT INPUTSSeven CT inputs provide three-phase output, three-phase neutral and ground current sensing.
AC/DC CONTROL POWERUniversal power supply90-300 VDC 70-265 VAC
PROGRAM PORTThe front panel RS232 port may be connected to a PC for localinterrogation, downloadingsetpoint files, and upgradingproduct firmware.
489 STATUSIndicates when the 489 is inservice, if setpoint access isallowed, any communicationport activity, if alternate setpointsare in use, if any latched alarm ortrip may be reset, and if Nextkey should be pressed to displaydiagnostic messages.
OPERATOR KEYSOnce the 489 is programmed,normal operation requires onlytwo keys. The Reset key is used toreset latched trips or alarms. TheNext key is used to scroll throughdiagnostic messages in the eventof an alarm or trip.
RTD INPUTSTwelve RTD inputs are individually field programmable to measure platinum, nickel, or copper type RTDs.
OUTPUT RELAYSSix, trip duty, form C output relaysmay be assigned to trip, alarmand control functions.
VT INPUTSFour VT inputs provide wye or opendelta system voltage sensing as well as neutral voltage sensing.
RS485 COMMUNICATIONSTwo independent RS485communication ports may beaccessed simultaneously usingModbus® RTU and DNP 3.0 protocolat baud rates up to 19200 bps.
489 Generator Management Relay™
A = 0 C = 0B = 0 AMPS
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin 37
3
Features
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin38
3
Typical Wiring
OUTPUT CT's
PHASE A
PHASE B
PHASE C
EXCITERAND
AUTOMATICVOLTAGE
REGULATOR
FIELD
DCAmps
mA
OPTIONALTRANSDUCER
TO 4-20 mA INPUT FOROVEREXCITATION
PHASE a
PHASE b
PHASE c
GENERATOR
C(B)
B(C)
A
WYE VOLTAGETRANSFORMERCONNECTION
UNITCIRCUIT
BREAKER
OPEN DELTA VOLTAGETRANSFORMERCONNECTION
UNITCIRCUIT
BREAKER
LOADLOAD
INDUCTIVE/HALLEFFECT SENSORFOR TACHOMETER
+ 24
KEYSWITCHFOR SETPOINTACCESS
UNITBREAKER STATUS
(52a)DCS
GROUND COMMUNICATION PORTS ONLY AT MASTER DEVICE
RS485PORT
COMMON COMMON
4 –20mAANALOG
INPUTPLCor
COMPUTER
WATTS
VARS
STATOR RTDs
BEARING RTDs
#1+
#2+
#3+
#4+
SELF POWEREDBEARING VIBRATION
TRANSDUCERS
489PC
PERSONALCOMPUTER RS232
9 W
IRE
RS
232
ALARM ANNUNCIATOR
OUTPUT CONTACTSSHOWN WITH NOCONTROL POWER
SELF TEST ANNUNCIATOR
UNITSHUTDOWN
CIRCUIT
UNITTRIPCOIL52a
UNIT BREAKERTRIP CONTROL
GROUNDBUS
CONTROLPOWER
489POWERSUPPLY
F10 G9 H9 G10 H10 G3 H3 G4 H4 G5 H5 G6
H12
H11
G12
G11
E12
F12
E11F11
E2F1E1F2E3F3E5F4E4F5E6F6E8F7E7F8E9F9
H6 G7 H7 G8 H8 G2 H1 H2 G1
A27A26A25A24A23A22A21A20A19A18A17A16B4B3B2D27D26D25
C4C3C2C1
D24D23D22D21D20D19D18D17D16
D4D5D6D7D8D9
D10D11D12D13D14D15
A14A15D1D2D3
A9A10A11A12A13
A4A5A6A7A8
B1A1A2A3
cbaNEUTRAL END CT's
HG
F
E10
AUTOMATICCT SHORTINGTERMINALS
GROUND INPUTS
VNEUTRAL
1A
1A / 5A
1A / 5A
1A / 5A
1A / 5A
CO
M
CO
M
CO
M
CO
M
CO
M
1A / 5A
CO
M
1A / 5A
CO
M
Va Vb
Vc
Vco
m
CO
MRTD RETURN
RTD RETURN
RTD RETURN
COMPENSATION
COMPENSATION
COMPENSATION
COMPENSATION
COMPENSATION
HOT
HOTHOT
HOTHOT
COMPENSATION
COMPENSATION
HOTHOT
RTD RETURN
RTD RETURN
COMPENSATION
COMPENSATION
HOTHOT
COMPENSATION
COMPENSATION
HOT
RTD RETURNCOMPENSATIONHOT
HOT
RTD SHIELD
RTD #1
RTD #2
RTD #3
RTD #4
RTD #5
RTD #6
RTD #7
RTD #8
RTD #9
RTD #10
RTD #11
RTD #12
ASSIGNABLE INPUT 1ASSIGNABLE INPUT 2ASSIGNABLE INPUT 3ASSIGNABLE INPUT 4ASSIGNABLE INPUT 5ASSIGNABLE INPUT 6ASSIGNABLE INPUT 7COMMONSWITCH + 24Vdc
ACCESS
BREAKER STATUS
DIG
ITAL IN
PUTS
COMPUTERRS485
AUXILIARYRS485
COM COM COMCOM
ANALOG OUTPUTS ANALOG INPUTS
ANALOG I/O
1 2 3 4 1 2 3 424
Vdc
SHIELD
FRONT PANEL LOCALPROGRAMMING PORT R
S23
2
R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
TRIP COILSUPERVISION
CONTROL POWER
SAFETY GROUND
FILTER GROUND
PHASEVOLTAGE INPUTS
PHASE A PHASE B PHASE CPHASE PHASE PHASE
G2 H1 H2 G1
Va Vb
Vc
Vco
m
PHASEVOLTAGE INPUTS
IRIG-B
CHECK VOLTAGE RATINGOF THE UNIT
BEFORE APPLYING POWER.(SEE Pgs.2-8)
CAUTION
DO NOT INJECTVOLTAGES TO
DIGITAL INPUTS(DRY CONTACT
CONNECTIONS ONLY)
CAUTION
120Ω
1nF
120Ω
1nF
120Ω
1nF
120Ω 1nF
808752EH.dwg
RS232 INTERFACE
RELAY COMPUTER
9 PINCONNECTOR
25 PINCONNECTOR
TXDTXDRXDRXD
SGND SGND
1234567
20
2289
12
233
4
4
5
5
6 67
7
8
8
9
489 SR GeneratorManagement Relay
GE Multilin
DO NOT INJECT OVER RATED CURRENTON G10 & H10.(See pg. 2 - 10)
CAUTION
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin 39
3
PROTECTIONGROUND CURRENT INPUTSCT ratio: 10000:1 for 1 A/5 A secondary,
50:0.025 for HGFCT secondary: 1 A/5 A, 2.5 mA for HGFBurden: Less than 0.2 VA at rated load for 1 A/5 A
Less than 0.02 VA at rated load for HGFConversion range: 0.02 – 20 x CT for 1 A/5 A
0.0 – 100 A primary for HGFAccuracy: at <2 x CT: ±0.5% of 2 x CT for 1 A/5 A
at ≥2 x CT: ±1% of 20 x CT for 1 A/5 AHGF: at <10 A: ± 0.1 A/5 A
at ≥10 – 100 A: ±1.0 A150 mA continuous
CT withstand: 1 sec @ 80 times rated current for 1 A/5 A2 sec @ 40 times rated current for 1 A/5 Acontinuous @ 3 times rated current for 1 A/5 A
METERINGPHASE AND DIFFERENTIAL CURRENT INPUTSCT primary: 10 – 50000 ACT secondary: 1 A or 5 A (must be specified with order)Burden: <0.2 VA at rated loadConversion range: 0.02 – 20 x CTAccuracy: at <2 x CT: ±0.5% of 2 x CT
at ≥2 x CT: ±1% of 20 x CTCT withstand: 1 sec @ 80 times rated current
2 sec @ 40 times rated currentcontinuous @ 3 times rated current
489 Technical SpecificationsTERMINALS
Low voltage (A, B, C, D terminals):12 AWG max
High voltage (E, F, G, H terminals):#8 ring lug, 10 AWG wire standard
INPUTSPHASE VOLTAGE INPUTSVT ratio: 1.00 – 240.00:1 in steps of 0.01VT secondary: 200 VAC (full scale) Conversion range: 0.02 – 1.00 x full scaleAccuracy: ±0.5% of full scaleMax continuous: 280 VACNEUTRAL VOLTAGE INPUTVT ratio: 1.00 – 240.00:1 in steps of 0.01VT secondary: 100 VAC (full scale) Conversion range: 0.005 – 1.00 x full scaleAccuracy: ±0.5% of full scaleMax continuous: 280 VACDIGITAL INPUTSInputs: 9 opto-isolated inputsExternal switch: dry contact <800 Ω or
open collector NPN transistor from sensor6 mA sinking from internal 4 K pullup @ 24 VDC with Vce <4 VDC
489 sensor supply: +24 VDC @ 20 mA max RTD INPUTSRTDs: 3 wire type 100 Ω Platinum (DIN.43760)
100 Ω Nickel field120 Ω Nickel programmable10 Ω Copper
RTD sensing current: 5 mAIsolation: 36 Vpk (isolated with analog inputs and
outputs)Range: -50 to +250° CAccuracy: ±2° C for Pt and Ni, ±5° C for CuLead resistance: 25 Ω Max per leadNo sensor: >1000 ΩShort/low alarm: <-50° C ANALOG CURRENT INPUTSCurrent inputs: 0 – 1 mA, 0 – 20 mA or 4 – 20 mA (setpoint)Input impedance: 226 Ω ± 10%Conversion range: 0 – 21 mAAccuracy: ±1% of full scaleType: passiveAnalog input supply: +24 VDC @ 100 mA max
POWER SUPPLYCONTROL POWEROptions: LO/HI (must be specified when ordering)Range:
LO: DC: 20 – 60 VDCAC: 20 – 48 VAC @ 48 – 62 Hz
HI: DC: 90 – 300 VDCAC: 70 – 265 VAC @ 48 – 62 Hz
Power: 45 VA (max), 25 VA typicalVoltage loss-ride through time:
30 ms
*Specifications subject to change without notice.
MONITORINGTRIP COIL SUPERVISIONApplicable voltage: 20 – 300 VDC/VACTrickle current: 2 – 5 mA
COMMUNICATIONSCOMMUNICATIONS PORTSRS232 port: 1, front panel, non-isolatedRS485 ports: 2, isolated together @ 36 VpkBaud rates: RS485: 300, 1200, 2400, 4800, 9600, 19200 bps
RS232: 9600 bpsParity: None, odd, evenProtocol: ModBus® RTU/half duplex, DNP 3.0
OUTPUTSANALOG CURRENT OUTPUTType: ActiveRange: 4 – 20 mA, 0 – 1 mA (must be specified
with order)Accuracy: ±1% of full scale4 – 20 mA maximum load:
1200 Ω0 – 1 mA maximum load: 10 kΩIsolation: 36 Vpk (isolated with RTDs and analog
inputs)4 assignable outputs: phase A, B, C output current, 3-phase
average current, negative sequence,generator load, hottest stator RTD,hottest bearing RTD, hottest other RTD,RTD # 1-12, phase AB voltage, phaseBC voltage, phase CA voltage, 3average phase-phase voltage, V/Hz,frequency, 3rd harmonic neutralvoltage, Power factor, 3-phase realpower (kW), 3-phase apparent power(kVA), 3-phase reactive power (kvar),analog inputs 1 – 4, current demand, kvardemand, kW demand, kVA demand,thermal capacity used, tachometer
OUTPUT RELAYSConfiguration: 6 electromechanical Form CContact material: silver alloyOperate time: 10 ms
Max ratings for 100000 operations
VOLTAGE MAKE/CARRY MAKE/CARRY BREAK MAXCONTINUOUS 0.2 sec LOAD
DC Resistive 30 VDC 10 A 30 A 10 A 300 W125 VDC 10 A 30 A 0.5 A 62.5 W250 VDC 10 A 30 A 0.3 A 75 W
DC Inductive 30 VDC 10 A 30 A 5 A 150 W125 VDC 10 A 30 A 0.25 A 31.3 W
(L/R = 40 ms) 250 VDC 10 A 30 A 0.15 A 37.5 WAC Resistive 120 VAC 10 A 30 A 10 A 2770 VA
250 VAC 10 A 30 A 10 A 2770 VAAC Inductive 120 VAC 10 A 30 A 4 A 480 VAPF=0.4 250 VAC 10 A 30 A 3 A 750 VA
PRODUCTION TESTS
Thermal cycling: Operational test at ambient, reducing to-40° C and then increasing to 60° C
Dielectric strength: 2.0 kV for 1 min from relays, CTs, VTs,power supply to safety ground DO NOT CONNECT FILTER GROUND TOSAFETY GROUND DURING TEST
ENVIRONMENTAL
Ambient operating temperature: -40° C to +60° CAmbient storage temperature: -40° C to +80° CHumidity: Up to 90%, noncondensingAltitude: Up to 2000 mPollution degree: 2NOTE: It is recommended that the 489 be powered up at least
once per year to prevent deterioration of electrolyticcapacitors in the power supply.
LCD contrast impaired below -20°C
TYPE TESTS
Dielectric strength: Per IEC 255-5 and ANSI/IEEE C37.902.0 kV for 1 min from relays, CTs, VTs,power supply to safety ground DO NOT CONNECT FILTER GROUND TOSAFETY GROUND DURING TEST
Insulation resistance: IEC255-5 500 VDC, from relays, CTs, VTs,power supply to safety ground DO NOT CONNECT FILTER GROUND TOSAFETY GROUND DURING TEST
Transients: ANSI C37.90.1 oscillatory (2.5 kV/1 MHz)ANSI C37.90.1 fast rise (5k V/10 ns)Ontario Hydro A-28M-82IEC255-4 impulse/high frequency disturbanceClass III level
Impulse test: IEC 255-5 0.5 J 5 kVRFI: 50 MHz/15 W transmitterEMI: C37.90.2 electromagnetic interference
@ 150 MHz and 450 MHz, 10 V/mStatic: IEC 801-2 static dischargeEnvironment: IEC 68-2-38 temperature/humidity cycleVibration: Sinusoidal vibration 8.0 g for 72 hrs
PACKAGING
Shipping box: 12" W x 11" H x 10" D(30.5 cm x 27.9 cm x 25.4 cm)
Shipping weight: 17 lbs max (7.7 kg)
CASE
Fully drawout (automatic CT shorts)Seal provisionDust tight doorPanel or 19" rack mountIP class: IP20-X
APPROVALS
ISO: Manufactured under an ISO9001 registered system.UL: UL approvedCSA: CSA approved
: Conforms to EN 55011/CISPR 11, EN 50082-2, Conforms to IEC 947-1, 1010-1
489 SR Generator Management RelayTM
www.GEindustrial.com/Multilin40
3
489 * * *489 Base unit generator management relay
P1 Current transformer inputs: 1 A CT secondaries
P5 Current transformer inputs: 5 A CT secondaries
LO Control power: DC: 20 – 60 V; AC: 20 – 48 V @ 48 – 62 Hz
HI Control power: DC: 90 – 300 V; AC: 70 – 265 V @ 48 – 62 Hz
A1 0 – 1 mA analog outputs
A20 4 – 20 mA analog outputs
Accessories
489PC Software: Shipped free with 489DEMO: Metal carry case in which 489 unit may be mounted19-1 PANEL: Single cutout for 19" panel19-2 PANEL: Double cutout for 19" panelSCI MODULE: RS232 to RS485 converter box, designed for harsh industrial
environmentsPhase CT: 50, 75, 100, 150, 200, 250, 300, 350, 400, 500, 600, 750, 1000HGF3, HGF5, HGF8: For sensitive ground detection on high resistance grounded
systems1 3/8" Collar: For shallow switchgear, reduces the depth of the relay by 1 3/8"3" Collar: For shallow switchgear, reduces the depth of the relay by 3"IP54 Collar
Dual mounting available with the 19-2 panel
NOTE: For dimensions see SR Family brochure.
Ordering
808785E3.cdr
7 8 9
4 5 6
1 2 3
. 0
7 8 9
4 5 6
1 2 3
. 0
Software
The 489PC software is a robust,Windows®-based application.Information can be accessedlocally through the keypad anddisplay, or via PC. The 489PCsoftware can display actualvalues over time in a graphicalformat, which may be useful introubleshooting situations.
489 setpoint files may be saved to a disk,printed, and downloaded to the 489.
The intuitive click and point softwaresimplifies setpoint programmingand relay interrogation. Setpoint
files for each generator may bestored, printed for verification, anddownloaded to the 489 for error freesetpoint entry.
The entire 489 manual is conve-niently included in the 489PCprogram’s help file, allowing theuser to easily access informationwhile programming the relay. Thedocumentation and illustrationscan be printed or pasted intoother Windows® applications.
URPC Program
The 489 is supported by theWindows®-based URPC program,allowing the use of advancedfunctions including creatingsingle-line diagrams, annunciatorpanel viewing, metering andsimple programming changes.Additionally, the user can accessmultiple 489s or other devices formetering in real time.
Product Upgrades
Flash memory technology allowsproduct upgrades without unitremoval. Firmware upgrades maybe downloaded to the unit via theRS232 ports.
489 GuideformSpecificationsFor an electronic version of the 489guideform specifications, pleasevisit: www.GEindustrial.com/Multilin/specs, fax your request to 905-201-2098 or email to [email protected].
489 Generator Management Relay™
489 IN SERVICE BREAKER OPEN R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
SETPOINT ACCESS BREAKER CLOSED
COMPUTER RS232 HOT STATOR
MESSAGE
VT FAILURE
BREAKER FAILURE
PROGRAM PORTSETPOINT 7 8 9
4 5 6
1 2 3
. 0 HELP
MESSAGE
VALUE
ACTUAL
ESCAPE
ENTER
RESET
NEXT
RESET
POSSIBLE
COMPUTER RS485
AUXILIARY RS485
ALT. SETPOINTS
489 STATUS GENERATOR STATUS OUTPUT RELAYS
NEG. SEQUENCE
GROUND
LOSS OF FIELD
A = 0 C = 0
B = 0 AMPS
808765E4.cdr
489 SETTINGS
send to 489
saveondisk
489 Windows Application-489
ForHelp,pressF1
Actual-ChartRecorder
489 IN SERVICE BREAKER OPEN R1 TRIP
R2 AUXILIARY
R3 AUXILIARY
R4 AUXILIARY
R5 ALARM
R6 SERVICE
SETPOINT ACCESS BREAKER CLOSED
COMPUTER RS232 HOT STATOR
MESSAGE
VT FAILURE
BREAKER FAILURE
PROGRAM PORT SETPOINT 7 8 9
4 5 6
1 2 3
. 0 HELP
MESSAGE
VALUE
ACTUAL
ESCAPE
ENTER
RESET
NEXT
RESET
POSSIBLE
COMPUTER RS485
AUXILIARY RS485
ALT. SETPOINTS
489 STATUS GENERATOR STATUS OUTPUT RELAYS
NEG. SEQUENCE
GROUND
LOSS OF FIELD
A = 0 C = 0
B = 0 AMPS
www.GEindustrial.com/Multilin
Order online –Order online –save timesave time
www.enerVista.comenerVista enabledenerVista enabled See page 275.
™Generator Management Relay is a trademark of GE Multilin.
41
3
Digital Generator Protection
Features and Benefits
High dependability and security
Extensive self-diagnostic routines
Redundant power supply
Adaptive sampling frequency for betterprotection during startup
Extensive recording capabilities (last 100 events, three fault reports)
Oscillography (120 cycles)
Compact to reduce space requirements
Modular construction for easymaintenance
Applications
Any size AC generators driven by steam,gas and hydraulic turbine
Protection and Control
Stator differential
100% stator ground faults
Current unbalance
Monitoring and Metering
Negative sequence current
Third harmonic voltages
User Interfaces
16 character LED display, 20 buttonkeypad
Two RS232 ports
Protection, control, monitoring and recording
functions for AC generators in a single compact package.
GE Multilin
Protection andControlThe DGP is a Digital GeneratorProtection system for any size ofAC generator driven by steam,gas or hydraulic turbine. A highdegree of security is provided viaextensive self-diagnostics and anoptional redundant power supply.Protection features include:
Current Unbalance
The DGP protects the generatorfrom heating caused by currentunbalance, using a formula basedon the negative sequence compo-nent of the stator current. A linearreset allows the machine to cooldown, and an alarm function isoperated by the negative sequencecomponent.
Stator Differential
High-speed protection during inter-nal phase-to-phase faults andthree-phase faults is provided. Thisfunction can provide high-speedphase-to-ground protection provid-ed the neutral of the machine isgrounded or another machineoperating in parallel is grounded.
Anti-Motoring
The DGP includes a one or two-step anti-motoring reverse powerfunction with individual time delayadjustments. One step can beused for sequential tripping of thegenerator, in which the turbine istripped first. This step is enabledwhen closing of turbine inletvalves is indicated by digital input.The trip sequence is then contin-ued when its delay time elapses.The second step is intended toprovide backup to the sequentialtrip. If the sequential trip is notenabled, the two devices can beused as two-step reverse powerfunctions with independent timers.
Ground Overcurrent
This inverse overcurrent functioncan be used to detect stator groundfaults in a high or low resistancegrounded generator system.
Time Overcurrent with Voltage
Restraint
Protection against prolongedgenerator contribution to a fault onthe system is provided through atime-overcurrent function withvoltage restraint, as part of thesystem backup protection. Thisfunction is controlled by a faultdetector and a Voltage TransformerFuse Failure (VTFF) condition.
Stator Ground
Two overlapping zones providestator ground fault detection in ahigh impedance grounded gener-ator system.
Zone 1 uses a fundamentalfrequency neutral overvoltage tocover about 95% of the statorwinding, based on the pickupvoltage setting.
Zone 2 is based on comparing thethird harmonic voltage at thegenerator neutral with the totalthird harmonic voltage generated.This function is designed to cover15% of the neutral end of thestator windings, and is controlledby fundamental and thirdharmonic voltage thresholds.Together the two zones cover100% of the stator windings.
Alternatively, Zone 1 can be usedas a generator-bus ground detector in a high-impedancegrounded or ungrounded system.
The DGP uses two overlapping zones todetect stator ground faults.
Loss of Excitation
When a synchronous generatorloses excitation, it acts as aninduction generator: runningabove normal speed, operating at
DGP Digital Generator Protection
www.GEindustrial.com/Multilin42
3
Functional BlockDiagram
704750A8.CDR
To MODEM
To LAPTOPPC
TRIP
ALARM
52G
GSU Transf.
TOPOWERSYSTEM
GEN.
51GN
64G1
64G2
27TN
RS
23
2
46
87G
40
32
51V
VTFF
RS
23
2
64G2
24
32 40
27 59
81
VTFF
DGP
51V
87S Generator differential46 Current unbalance40 Loss of excitation32 Anti-motoring51V TOC with voltage restraint64G 100% stator ground51GNP Stator ground overcurrent27TN 3rd harmonic neutral undervoltage24 Overexcitation59 Overvoltage27P Undervoltage81 Over and underfrequency50/27 Accidental energizationVTFF Voltage transformer fuse failure
DEVICE PROTECTION
95%
15%
704757A3.CDR
Neutral end
Terminal end
Zone 1
(64G1)
Zone 2
(64G2)
reduced power, and receiving itsexcitation (vars) from the system.The DGP’s loss of excitation func-tion includes two mho character-istics featuring individuallyadjustable reach, offset, and timedelay. The DGP will block thisfunction if it detects a negativesequence voltage, which wouldindicate a VTFF, or an externalVTFF signal.
The first zone mho function can beset to detect severe cases of excita-tion failure with a short time delay.The second zone mho function canbe set to detect all the excitationfailure cases with a longer timedelay setting. This permits systemsecurity during stable powersystem swing conditions.
Overexcitation Protection
Provided through a Volts/Hertzfunction with inverse and instanta-neous time delay characteristics.The overexcitation protectionincludes trip and alarm functionscomputed for each of the three-phase voltages. The trip functionincorporates a user-configurablelinear reset characteristic to mimicmachine cooling.
Over and Undervoltage
The undervoltage functionconsists of a positive sequenceundervoltage with a user-selectable inverse or definite timecharacteristic. The overvoltagefunction consists of a positivesequence overvoltage with aninverse characteristic. A linearreset characteristic is incor-porated for both functions. Theovervoltage function can be usedas a backup to the overexcitation.The undervoltage function alsoprovides voltage phase reversalprotection.
Over and Underfrequency
Up to four steps of protection areincluded, each with an adjustabletime delay. The steps arecontrolled by an adjustable posi-tive sequence voltage level.
Voltage Transformer Fuse Failure
(VTFF)
When a fuse failure is detected,the DGP will block tripping by theloss of excitation and TOC withvoltage restraint functions, asthey may continue operating witha loss of AC.
Accidental Energization
The DGP system uses internallogic to detect accidental ener-gization of the generator.
Configurable I/Os
Two general purpose contactconverter inputs allow easyconnection of external trip oralarm contacts, permitting use ofthe event log and configurableoutputs of the DGP. An optionalinput can be configured to disableall protections functions.
Eight configurable output relays,four trip and four alarm, allow theuser to select any desired combi-nation of the functions. Outputrelays can be controlled remotelyor locally through a securedauthorization or hardwire jumper.
The control functions of the DGP can operateoutput relays locally or remotely.
Configurable Logic
The DGP allows strategic modifi-cation of internal logic to favoreither security or dependability.This can be accomplished eitherby software settings or automati-cally by a "Generator Offline"contact input. This feature allowsdisabling of selected functionswhen the generator is offline andmodification of the AccidentalEnergization logic.
Contact Expansion Unit
The DEC 1000 unit is an intelligentcontact expansion unit thatprovides an additional 11 outputrelays, five with contacts in ‘C’
configuration, and six with nor-mally open contacts. Eleven LEDsindicate operation of contacts, anda reset button tests and resets theunit. Available for “CA“ model only.
The DEC 1000 expands the number ofoutputs controlled by the DGP.
Monitoring andMeteringThe DGP features advancedmetering and event recordingfunctions which include:
Self-Tests and Diagnostics
Self-test routines are performedduring power-up and continue torun in the background duringservice. Failures are categorizedas either a critical or non-criticalalarm. Appropriate protectivefunctions are automaticallydisabled during a critical alarm,helping to maintain the high secu-rity of the DGP.
The DGP also has a RELAY TESTmenu which facilitates installationby allowing testing of individualprotective functions and outputrelays for the protection system.
Trip Circuit Monitor
This function consists of the TripVoltage Monitor (TVM) and theTrip Current Monitor (TCM) for upto four trip output contacts. TheTVM detects any discontinuity inthe external trip circuit andproduces a non-critical alarm.The TCM confirms energizing ofthe trip circuit when a trip isissued by the DGP. To protect theoutput contacts the TCM may beused to seal-in the trip output aslong as trip current is flowing.
Metering
The DGP provides the followingmetering values:
Currents (Ia, Ib, Ic) Voltages (Va, Vb, Vc, or Vab, Vbc, Vca)
DGP Digital Generator Protection
www.GEindustrial.com/Multilin 43
3
Angles of I and V Negative sequence current (%I2) Third harmonic voltages
(phase/neutral) Watts (three-phase) Vars (three-phase) Frequency Contact inputs (status)
The currents, voltages, watts, andvars can be metered as eitherprimary or secondary values toan accuracy of 3%.
Event Recording
The last 100 events are time taggedin milliseconds and stored in theDGP's memory. Event data is avail-able via the RS232 ports and theoptional printer port for analysis.
The DGP stores the last 100 events.
Fault Reports
The DGP stores the last threefault reports in its memory. Afault report is generated by anyprotective function trip or by anexternally triggered input.
Oscillography
The DGP can capture and store120 cycles of oscillography datawhich can be divided into one,two, or three partitions. Up to 20prefault cycles can be captured.In addition to 12 analog wave-forms (currents and voltages) theDGP captures internal logic flagsand contact I/O status. The DGPsettings at time of capture arealso stored as part of the data,along with the fault report.
User InterfacesThe 489 allows users ease ofaccess through:
Keypad and Display
A 20 button keypad and a 16character LED display allow theuser easy access to settings anddata. Two distinct security pass-words limit tampering.
A keypad and display are provided for localuser interface.
LED Indicators
Over eighteen LEDs on the frontpanel provide easy and immedi-ate indication of the phase andfault type. A two-color LED (redand green) is also provided toindicate the relay status.
Communications
Two RS232 serial ports are provid-ed on the DGP, one on the frontand one on the rear. The port onthe front allows easy local userinterface via a laptop computer.The rear port can be used to inter-face with a remote computer viamodem. There are three levels ofsecurity password provided forremote communications. Foradded security, hardwire jumperscan disable setting changes andcontrol actions from a computer.
For remote link communications,DGP offers a choice of **GE-MODEM or *ModBus® protocol,each supplied with a copy of GE-LINK remote communicationsoftware. In addition to the GE-LINK, a copy of the DGP-DATAsoftware is also supplied with therelay for oscillography dataanalysis of DGP data. * ModBus® available with “CA” model
only. Requires an optional RS485 toRS232 converter.
** New Windows® version of GE-LINKfor ModBus® protocol.
Time Synchronization
An IRIG-B input is provided for timesynchronization via satellite signal.
Drawout Construction
The drawout construction of theDGP case allows for all internalcomponents to be withdrawnfrom the front of the relay.
DGP Digital Generator Protection
www.GEindustrial.com/Multilin44
3
File
Quit
Graphs Reports Setup eXit F1=Help
TEST_LOF.OSC:
LEFT RIGHTSAMPLE: 136 231 ELAPSED TIME: 132.7 MS (59.68 HZ)
VALUE: IAS +004.79IBS -010.05ICS +005.50VA -0035.9VB +0020.7VC +0016.4
-000.96 -001.41 +002.19-0048.8 +0035.2 +0014.1
DIFF: +005.75+008.64+003.31+0012.9+0014.5+0002.3
SEC AMPS
SEC VOLTS
20.0 AMPS
IAS
-20.0 AMPS
IBS
ICS
100.0 VOLTS
VA
-100.0 VOLTS
VB
VC
704755A1.CDR
704756A1.CDR
94G TRIP CIRCUIT OPEN ALARM OFF94G TRIP CIRCUIT OPEN ALARM ON94G2 TRIP SIGNAL RESET32-1 OFF32-2 OFF32-1 ONTURBINE INLET VALVE CLOSEDGENERATOR OFF-LINE94G2 TRIP SIGNAL ON32-2 ONGENERATOR ON-LINETURBINE INLET VALVE OPEN94G3 TRIP SIGNAL RESET64G1 OFFTURBINE INLET VALVE CLOSEDGENERATOR OFF-LINE94G3 TRIP SIGNAL ON64G1 ONGENERATOR ON-LINETURBINE INLET VALVE OPENREMOTE - SETTINGS CHANGE DONEREMOTE - SETTINGS CHANGE STARTED
GEN Simulator DGP
Station ID:MALVERN
Generator ID:MODEL GENERATOR
10/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/29/9310/28/9010/28/93
14:40:42.27614:39:54.97114:33:35.66114:33:35.66014:33:35.63914:33:34.39614:33:31.99714:33:28.42314:33:26.45214:33:26.45114:27:09.87814:27:04.96814:26:54.26314:26:54.26214:26:50.91114:26:47.58414:26:42.60414:26:42.60314:25:44.44414:25:38.20216:32:31.64216:32:30.882
Events
The DGP can store 120 cycles of oscillography.
DGP Digital Generator Protection
www.GEindustrial.com/Multilin 45
3
MAN MACHINE INTERFACE MODULE (MMI) 16 character alpha-numeric LED display for fault report,
metering values, alarm messages, setting parameters etc. Keypad includes 20 buttons for user-friendly
local interface with the DGP Dual color LED indicates relay status RS232 port facilitates connection of lap-top PC
MODULESSystem Procesor (SSP),Analog Interface (ANI),Data Acquisition (DAP), &Digital Signal Processor(DSP) modules are plug-intype for ease of maintenanceand trouble-shooting.DIGITAL INPUT & TARGET
MODULE (DIT) LED targetsindicate ALL the functionsthat operated during atrip event.
POWER SUPPLY MODULES are located behind the cover plate. Module PS2 is optional.
OUTPUT RELAY CONTACTS 8 configurable relays 8 predefined relays
CONTROL POWERDC control power input
CT INPUTS 6 phase CT inputs 1 residual CT input 1 residual/neutral CT input
VT INPUTS: 3 phase VT inputs,
wye or delta 1 neutral VT input
RS232 PLUG (PL-1) provides connection to modem for remote communications or an interface to stationintegration system.
OPTIONAL SERIAL PORT (PL-2)Can be used to connect aprinter for automatic/manualprintout of data or a ContactExpansion Unit DEC1000.
OPTIONAL PLUG (PL-3) Available for IRIG-B signal input to synchronize the DGP internal clock to a common reference clock e.g. GPS receiver.
704752A8.CDR
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
DIGITAL INPUTS: 3 configurable contact
inputs 3 predefined contact
inputsAE
AF
AG
AH
BE
BF
BG
BH
SSP301 ANI301 DAP201 DSP401
SSP301MMI301
MGM781
DIT101
DIT101 MMI301
ANI301
PL-2PL-1 PL-3
DAP201 DSP401
MMI301
MGM781 TPM2
1
2
15
16
17
1
2
15
16
17
11
12
13
14
27
28
11
12
13
14
27
28
INVNFREQ
5 AMP100/140 VOLTS50/60 Hz
RATINGSINVNFREQ
5 AMP100/140 VOLTS50/60 Hz
RATINGS
PS2
VTFF
PS1
PS2PS1
TPM1
46
59
32
81-U 81-O
64G1 64G2
40G1 40G2
24A 24B 24C
51V-A 51V-B 51V-C
57A 57B 57C
MAGNETIC MODULES (MGM) Two identical modules contain CT’s, VT’s, output relays, etc. and areinterchangeable.
OPTIONAL TEST BLOCKSfacilitate injection of analog input signals and monitoring of DGP outputs for test purpose without disturbing field wiring.
Features
Front View
Rear View
DGP Digital Generator Protection
www.GEindustrial.com/Multilin46
3
Typical Wiring
GROUNDBUS
A
B
C
AH1
BG8
TRIP A (DRY)
TRIP B (DRY)
TRIP C (DRY)
TRIP D (DRY)
ALARM A
ALARM B
ALARM C
ALARM D
VT FUSE FAIL
TEST PICKUP
TEST TRIP
SPARE
SELF TESTNON CRITICAL
SELF-TESTCRITICAL
POWERSUPPLY
ALARM 1
POWERSUPPLYALARM 2
94G
94G1
94G2
94G3
74A
74B
74C
74D
74FF
DOR 12
DOR 13
DOR 9
74 NC
74 CR
TRIP A
TRIP B
TRIP C
TRIP D
704753A8.CDR
GENERATOROFF LINE
TURBINEINLET VALVE
LIMIT SWITCH
EXTERNALTRIP 1
INP
UT
S
OU
TP
UT
S
EXTERNALTRIP 2
OSCILLOGRAPHTRIGGER
EXT. VTFF/DISABLE PROT.
BG7
BG6
BG5
BG4
BG3
BG2
BE4
BE2
BG1
BE3
BE1
AH12
AG1 CONTROL
POWERAG2
BH14
BH1
BH9
AH2
AH11
BH2
BH10
AH3
BH3
BH11
AH4
BH4
BH12
AH5
BH5
AH9
AH6
BH6
AH10
AH7
BH7
AH8
BH8
IARGNDVOLT
IAS VAIBR IBS VBICR ICS VC
VOLTAGE
INPUTS
CURRENT
INR INS
AC(B)
B(C)
DB25
DB9
DB25
RS-232
DEC1000
or
ContactExpansion
Unit
IRIG-B
RS-232
PRINTER
(REAR)PL1
(FRONT)
(REAR)PL2
(REAR)PL3
BF5
AE7
BE5
BE6
BF6
BE10
BE9
BE8
BE14
BE13
BF10
BF9
BF14
BF13
BE7
AG13
AG12
AG11
AG10
AG6
AG5
AG9
AG8
AG7
BE12
AE13
AE12
AE10
AE6
AE5
AE9
AE8
BF8
BF7
AF14
AF13
AF11
AF10
AF6
AF5
AF9
AF8
AF7
BF12
BF11
AG14
BE11
AE14
AF12
AE11
(-)
(+)
(-)
(+)
(-)
(+)
(-)
(+)
PRINTER
DGPDigital Generator Protection
GE Multilin
DGP Digital Generator Protection
www.GEindustrial.com/Multilin 47
3
Dimensions
704751A3 DWG
CUTOUT
8 REQ'D.0.28" Dia.
(7)
*3.375"(86)
17.25"(438) 18.38"
(467)
13.94"(354)
4.00"(102)
4.00"(102)
2.94"(75)
1.50"(38)
1.0"(25)
13.03"(331)
0.31"(8)
13.88"(352)
* minimum to remove cable when req'd.
PLUG
TERMINALBLOCKS
19.00"(483)
SIDE VIEW PANEL CUTOUTFRONT VIEW
LATCH
Inches(mm)
DEC1000 Mounting
FRONT VIEW SIDE VIEW
CUTOUT & DRILLING PATTERN
19.00"(483)
3.40"(87)
8.1"(206) 1.20"
(30.4)
0.28" Dia.(7) 4 Pl.
18.32"(465)
17.35"(441)
3.54"(90)
3.00"(76)
0.26"(7)
INCHES(mm)
704759A2.dwg
CUTOUT
APPROVALSUL file no. E57838
PACKAGINGNet weight: 51 lbs (23 kg)Dimensions:
Height: 14" (352 mm) 8 rack unitsWidth: 19" (484 mm) standard 19" rackDepth: 14" (356 mm)
TYPE TESTSInsulation test voltage: 2kV 50/60 Hz, one min
2.8k VDC, one minImpulse voltage withstand: 5 kV peak, 1.2/50 µsec, 0.5 JInterference test withstand: SWC, per ANSI C37.90.1 &
IEC 255-5Vibration test withstand: IEC255-21-1
ENVIRONMENTALAmbient temperature range:
Storage: -30° C to +70° COperation: -20° C to +55° C
Humidity: 95% without condensation
OUTPUTSCONTACT DATATrip outputs (4 programmable relays, 2 contacts each)Trip contacts: Continuous rating = 3 A
Make and carry 30 A per ANSI C37.90Interrupting = 60 VA inductive,maximum 250 V or 0.5 A
Alarm outputs(4 programmable & 5 predefined relays, 1 contact each)Alarm contacts: Continuous rating = 3 A
Make and carry 5 A for 30 secInterrupting = 60 VA inductive,maximum 250 V or 0.5 A
Trip current monitor sensitivity:150 mA
Trip voltage monitor: 38 – 300 VDCDigital inputs: 38 – 300 VDC, 1 – 3 mA
COMMUNICATIONSINTERFACE DATASystem interface: DB25, RS232 port – rear panel
DB9, RS232 port – front panelIRIG-B port – rear panel (optional)Printer port – rear panel (optional)
INPUTSBURDENSCurrent circuits: 0.022 Ω, 5° for In = 5 A
0.12 Ω, 30° for In = 1 A@ 60 Hz 0.0507 < 4.738
Voltage circuits: 0.30 VA, 60 Hz0.40 VA, 50 Hz
DC battery:Power supply: 19 W with 1 supply
25 W with 2 suppliesFor contact converters: 2.5 mA at rated voltage
POWER SUPPLYDC control voltage:
48 VDC 38.5 – 60 VDC110/125 VDC 88 – 150 VDC220/250 VDC 176 – 300 VDC
METERINGRATINGSNominal frequency: 50 or 60 HzFrequency tracking: 30 – 80 HzNominal voltage (phase-phase): 100 – 210 VACRated current: In = 1 or 5 AMaximum permissible current:
Continuous 2 x InThree sec 50 x InOne sec 100 x In
Maximum permissible AC voltage:Continuous 280 VACOne min (once per hour) 490 VAC
ACCURACYRMS measurements: ± 3%Phase angle measurements: ± 1°Frequency measurements: ± 0.01 HzTimers: ± 3% of settingData time tag resolution: ± 1 ms
PROTECTIONIn = 1 A In = 5 A
General differential (87G):Differential current pickup: 0.04 – 0.2 A 0.2 – 1.0 A% slope factor: 1 – 10 1 – 10
Current unbalance (46A, 46T):Neg. seq. current pickup: 0.01 – 0.60 A 0.5 – 2.99 AMachine constant (46T): 1 – 45 1 – 45Alarm time delay (46A): 1 – 9 sec 1 – 9 sec
Loss of field (40):Zone 1 and Zone 2 center: 12.5 – 300 Ω 2.5 – 60 ΩZone 1 and Zone 2 radius: 12.5 –300 Ω 2.5 – 60 ΩZone 1 and Zone 2 timer: 0.01 – 9.99 sec 0.01 – 9.99 sec
Anti-motoring (32-1 & optional 32-2):Reverse power: 0.1 – 20.0 W 0.5 – 99.9 WTime delay: 1 – 120 sec
Stator ground (64G1 & optional 64G2):Neutral OV pickup: 4 – 40 VTime delay (for 64G1): 0.1 – 9.9 secTime delay (for 64G2): 0.1 – 9.9 sec
3rd harmonic neutral undervoltage (27TN):U/V setpoint: 0.1 – 9.9 VTime delay: 0.5 – 99.9 sec
Overexcitation, (24T, 24I, 24A):V/Hz pickup: 1 – 1.99 PUTime factor (24T-inverse): 0.1 – 99.99Time delay (instantaneous): 0 – 9.9 secTime delay (24A-alarm): 0 – 9.9 secRate of reset: 0 – 999 sec
Undervoltage, optional (27):U/V set point: 40 – 120 VTime factor: 0.1 – 99.99 secCurve select: Inverse/definite time
Overvoltage (59):O/V set point: 100 – 225 VTime factor: 0.1 – 99.99 sec
Over and underfrequency, up to four steps (81):O/F set point (each step): 45 –0 79.9 HzU/F set point (each step): 40 – 65 HzTime delay (each step): 0.05 – 99.99 secTime delay (U/F step 1): 0.1 – 999.9 sec
System Backup (51V):Overcurrent pickup: 0.1 – 3.2 A 0.5 – 16 ATime factor: 0.1 – 99.99 sec 0.1 – 99.99 sec
DGP Technical Specifications
*Specifications subject to change without notice.
DGP Digital Generator Protection
www.GEindustrial.com/Multilin48
3
DGP * * * * * *DGP Digital Generator Protection
1 1 A rated5 5 A rated
0 One power supply, 48 VDC1 One power supply, 110/125 VDC2 One power supply, 220/250 VDC3 Two power supplies, 48 VDC4 Two power supplies, 110/125 VDC
A With test blocks, gray caseB Without test blocks, gray case
A GE-MODEM communication protocolB ModBus® communication protocol
(not available with Function Group A/B)A Function Group A See DGP B Function Group B Selection Guide*C Function Group C on the right
A Revision level
Optional RS485 to RS232 converter available for use with ModBus® version
Ordering Note that the DGP relay with special configuration of printer port is required for the DEC1000 to function properly.
*DGP Selection Guide FUNCTION GROUPFUNCTIONS AND FEATURES A B CStator differential 87G X X XCurrent unbalance 46 X X XLoss of excitation 40-1, -2 X X XOC – voltage restraint 51V X X XStator ground 64G1 (fundamental OV) X X XOverexcitation 24 (Volts/Hz) X X XOvervoltage 59 X X XAccidental energization logic X X XSequential trip logic X X XVT fuse failure X X XOscillography capture X X XIRIG-B input X X XAnti-motoring 32 2 setpoints 1 setpoint 2 setpointsStator ground 64G2 (3rd Harm. UV) X — XNeutral OC 51GN — X XUndervoltage 27 — X XStator GND 27TN — X XUnderfrequency 81-U 4 setpoints 2 setpoints 4 setpointsOverfrequency 81-0 4 setpoints 2 setpoints 2 setpointsPrinter output X — XDEC1000 compatible — — XCommunication ports 2-RS232 2-RS232 2-RS232
DEC 1000A *** * 00CDEC
*** Select the three digit code from the DEC SelectionGuide† on the right or fill in desired functionassignment for the DEC1000 output relays R1-R11using Table 1 and submit with the order. Codes 001to 005 are already assigned and are available asdescribed. Any protection function available in thecompanion DGP relay can be selected for the DECoutput relay assignment
F Vps = 24 – 48 VDC
H Vps = 110 – 250 VDC
Example: DGP54BBCA – DGP rated 5 A, 50/60 Hz, 110/125 VDC redundant power supplies, no built-in testblocks, ModBus® protocol, function group C, revision A.
The following special DGP™ systems are also available. Refer to factory for other special requirements.DGP***AAA-0101 – Similar to "AAA" except single voltage-rated digital inputs, special logic for function51V and separate terminals for power supply inputs.
†DEC Selection GuideCODE R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 R11001 32-2 59 81O1 81-2 81U1 81U2 40 46-2 46-1 32-1 —002 32-1 64G2 46-1 32-2 64G1 40-1 87G-A 87G-B 87G-C 46-2 40-2003 87G➀ 64G➁ 32-2 51GN 24➀ 87G➀ 64G➁ 32-2 51GN 24➀ 32-1004 46T 51V➀ 59 81O1 81U1 46T 51V➀ 59 81O1 81U1 40-1005 46T 51V➀ 59 64G1 87G➀ DI3 DI4 32-1 — — —➂➂
➀ Indicates any phase – A, B, or C ➁ Indicates any zone – 1 or 2 ➂ Code assigned by GE
DGP GuideformSpecificationsFor an electronic version of the DGPguideform specifications, pleasevisit: www.GEindustrial.com/Multilin/specs, fax your request to 905-201-2098 or email to [email protected].
www.GEindustrial.com/Multilin
Faster ordersFaster ordersvia the webvia the web
49
3
Generator Backup Protection
Features and Benefits
Waveform sampling of current andvoltage inputs
High-resolution oscillography andplayback
Four zones of phase and ground mhodistance functions
Out-of-step blocking and trippingavailable
Phase and ground overcurrentinstantaneous backup
Ground time overcurrent backup
User-configurable I/Os
Integrated RMS metering
Horizontal and vertical models
Applications
Backup protection for generators ortransmission lines
Three-phase tripping applications
enerVista.com compatible (see page 275)
Protection and Control
Out-of-step tripping
Over and undervoltage functions
Monitoring and Metering
Fault location, event and fault recording
Currents, voltages, watts, vars andfrequency
User Interfaces
LCD and keypad
RS232 and RS485 serial ports
System backup for generators
and transmission lines.
GE Multilin
Protection andControlThe LPS-O provides backup pro-tection for generators andtransmission lines. Advancedprotection functions include:
Distance
Four zones of phase step distanceprotection are provided. Functionsare positive sequence voltage po-larized mho characteristics. Thereach of the three forward lookingzones can be compensated for adelta-wye transformer.
Zone 4 is reversed and disregardsany transformer between the relayand the fault in the forward direc-tion. Zones 1, 2, 3, and 4 eachinclude independent timers forphase step distance protection.
Out-of-step blocking monitorsswing condition and blocks trip-ping. Out-of-step tripping logic isprovided with a choice of two orthree mho type characteristicswith adjustable shapes.
Forward and reverse share acommon maximum reach angle.Loss of synchronism or a powerswing between two areas of thepower system is detected bymeasuring the positive sequenceimpedance seen by the relay overa period of time as the powerswing develops.
Directional Ground Overcurrent
The ground directional functionsare forward and reverse negativesequence current and voltage op-erated. The ground instantaneousand TOC functions can be inde-pendently set with directionalcontrol.
Overcurrent Backup
The LPS-O provides instanta-neous phase and groundovercurrent functions. The phasebackup consists of an instanta-neous function. Groundovercurrent backup consists ofIOC and TOC functions. The TOCfunction includes four selectableand one programmable curve.
The ground overcurrent functionscan be controlled by the direc-tional functions. Both IOC andTOC functions can be set as non-directional or directional.
The LPS-O provides an adaptivesensitive current disturbance de-tector (fault detector) and anunbalanced current alarm to de-tect open or shorted CT leads.
Voltage
Three single-phase under andovervoltage detectors and a posi-tive sequence overvoltage detectorare provided.
Fuse failure logic detects a full orpartial loss of AC potential andblocks tripping of distance and directional functions. The LPS-Ohas a three-wire voltage inputsuitable for either delta or wyeconnected VTs.
Scheme Logic
The LPS-O provides user-programmable logic with up to40 gates and eight timers.
Manual Breaker Control
Manual circuit breaker tripping orclosing can be done locally or re-motely.
Multiple Settings Groups
Two separate groups of protec-tion settings may be stored in theLPS-O non-volatile memory. Theactive settings group can be se-lected by the user.
Configurable I/Os
All 12 contact converter inputsand 20 contact outputs (exceptfor alarms) are user-configurable.SCR tripping outputs are avail-able for high speed operation.
Monitoring andMeteringThe LPS-O provides sophisticatedmonitoring and metering func-tions that include:
Trip Circuit Monitor
DC battery voltage is monitoredacross each open trip contact. Analarm triggers when the voltagebecomes virtually zero. A currentsensor in series with each tripcontact is provided, to log anevent message on the DC tripcurrent status following the trip.
Metering
The LPS-O provides the followingRMS metering values:
Current (Ia, Ib, Ic, In) Voltage (Vab, Vbc, Vca) Watts (three-phase) Vars (three-phase) Frequency
The currents are calculated foreach phase, and voltages are cal-culated between phases. Theaccuracy is 1% of rated currentand voltage. The phasor value(magnitude and angle) of thephase currents and voltages arealso displayed.
LPS-O™ Generator Backup Protection
www.GEindustrial.com/Multilin50
3
lpso_fbd.ai
LPS-O
67P7821P 67N50P50/51G
Metering
5927
G
Functional Block Diagram
Event Recording
The LPS-O stores up to 150 eventswith the date and time stamped tothe nearest millisecond. This aidsthe user with determining the se-quence of events, facilitatingdiagnosis and recovery.
Oscillography
The LPS-O captures current andvoltage waveforms and selectedinternal logic signals at 64 samplesper cycle. The unit can store fromsix events of 72 cycles each to 36events of 12 cycles each. The time,date, active settings, and fault re-port are stored with the datacapture. Prefault data can be setfrom one to eight cycles.
Oscillography can be triggered byinternal or external signals.Internal signals include trip out-puts or a programmable logicsignal. The supplied out-of-steptrip logic features a three secondoscillography data file consistingof phasor values of the currentsand voltages captured at a rate ofone per cycle. The LPS-O has thecapability to store the oscillo-graphy files in Comtrade format.
The LPS-O relay can playbackstored waveform files throughthe relays processor, allowing theuser to playback faults with dif-ferent settings.
Breaker Health
The breaker health threshold isset by the user to achieve “just intime” maintenance. When the cu-mulative value of the three-phasecurrents exceeds the threshold,an alarm occurs. The user can ad-just the threshold for breakerswith previous duty.
Self-Test Diagnostics
Self-test routines are performedduring power up and continue inthe background during service.Failures are categorized as eithercritical or non-critical alarm andrecorded in the event log.
LPS-O™ Generator Backup Protection
www.GEindustrial.com/Multilin 51
3
B(C)
C(B)
A
A1 A8A17 A2
A3
D2
D6
D10
D4
D8
D12
D3
D7
D11
D5
D9
D13
D1
A5
A7
A4
A6
A8
B11
B29
A9
A10
A11
A12
A13
B1
A14
B2
A15
B3
A16
B4
B5
B23
B8
B26
D16
B14
B32
T1
CC1
CC5
CC9
CC3
CC7
CC11
CC2
CC6
CC10
CC4
CC8
CC12
UNMODULATEDIRIG-B
PL2A(REAR)
RS-232
RS-232
RS-485
RS-485
RS232
4 WIRE / 2 WIRE
PL3(REAR)
OPTIONAL
OPTIONAL SINGLE POLE MODEL
PL2B(REAR)
PL1(FRONT)
T3
T5
T2
T4
T6
C1
C2
A1
A2
A3
A4
A5
A9
A6
A10
A7
A11
A8
A12
KT1
KT2
KT3
KT4
CRITICALALARM
POWERSUPPLYALARM
FAULTLOCATION
I/V
A19
D18
D22
D26
D20
D24
D28
D19
D23
D27
D21
D25
D29
D17
A21
A23
A20
A22
A24
B27
B12
B28
B13
A25
A26
A27
A28
A29
B17
A30
B18
A31
B19
B21
B6
B24
B9
A32
B20
B22
B7
B25
B10
B30
B15
D32
B31
B16
730750A3.CDR
C1
IAC2
IARC3
IBC4
IBRC5 C13 C9 C11
Vs Va VcVs Vb VnICC6 C14 C10 C12
ICR
A B C
CURRENT INPUTS VOLTAGE INPUTS
CO
NFI
GU
RA
BLE
(S
HO
WN
WIT
H D
EFA
ULT
SE
TT
ING
S)
CO
NFI
GU
RA
BLE
(38
.5 T
O 3
00 V
DC
)
INP
UT
S
FIX
ED
OU
TP
UT
S
CONTROLPOWER G
RO
UN
DS
UR
GE
CONTROLPOWERSUPPLY
CONNECTIONAS REQUIRED
GROUNDBUS
TRIPPING DIRECTION
52
DB-25
DB-25
DB-9
LPSLine Protection System
GE Multilin
Typical Wiring
LPS-O™ Generator Backup Protection
www.GEindustrial.com/Multilin52
3
LPS-O Technical Specifications
*Specifications subject to change without notice.
TYPE TESTSInsulation test voltage: 2 kV, 50/60 Hz, 1 min
(high-pot) ANSI C37.90IEC 255-5
Impulse voltage withstand fast transient:5 kV peak, 1.2/50 µs, 0.5 JIEC 255-4ANSI C37.90.1
Surge withstand capability (SWC):ANSI C37.90.1IEC 255-22-1
Radio frequency interference withstand (RFI):ANSI C37.90.2IEC 255-22-3
Electrostatic discharge (ESD): IEC 255-22-2
ENVIRONMENTALAmbient temperature range:
Storage: -30° C to +75° COperation: -20° C to +60° C
Humidity: 95% without condensation
INSTRUCTION BOOKSingle-pole GEK 106202Three-pole GEK 106159
COMMUNICATIONSProtocol: ASCII, GE-MODEMPorts: Front: 1 DB9, RS232
Rear: 1 DB25, RS232 and 4 pin Phoenix, RS485 (standard): 1 DB25, RS232 or RS485 optional
Display: 4 line liquid crystal display standardKeypad: Full numeric keypad standard
POWER SUPPLYControl voltage: Range:
48 VDC 38.5 – 60.0 VDC110/125 VDC 88 – 150 VDC220/250 VDC 176 – 300 VDC
OUTPUTSCONTACT RATINGSTrip contact (T1 – T6): Continuous = 5 A
Make & carry = 30 A per ANSI C37.90Interrupting: 25 VAPickup <4 ms
Trip SCR (T1 – T6): Continuous = 5 AMake & Carry = 30 A per ANSI C37.90
Auxiliary(A1 – A12): Continuous = 5 A(C1, C2): Make & carry = 30 A
Interrupting: 25 VAPickup <8 ms
High speed (KT1 – KT4): Continuous = 0.5 AMax voltage = 280 VDC =Pickup <0.5 ms
INPUTSContact converter inputs: 5 – 300 VDC (jumper selectable)BURDENSCurrent circuits: In = 1 0.02 Ω at 5°
In = 5 0.12 Ω at 30°Voltage circuits: 50 Hz 0.20 VA
60 Hz 0.15 VADC battery:
Power supply: <20 WContact converters: 2.5 mA each
MONITORINGRecords: 6 – 36Record length: 72 – 12 cyclesPre-fault cycles: 1 – 8Samples per cycle: 64
METERINGFrequency: 50 or 60 HzVoltage (ph-ph): 100 – 120 VACCurrent (In): 1 or 5 AMaximum permissible current:
Continuous: 3 A for In = 1 A15 A for In = 5 A
Three sec: 50 x InOne sec: 100 x In
Maximum permissible AC voltage:Continuous: 138 VAC (ph-n)One minute: 3.5 x rated
PROTECTIONIn = 1 In = 5
Positive sequence angle: 45 – 90° 45 – 90°Zero sequence angle: 45 – 90° 45 – 90°Zero sequence current :Compensation (K0): 1.00 – 7.00 1.00 – 7.00
Zone 1, 2, 3 and 4 reach: 0.05 – 250 Ω 0.01 – 50 ΩZone 4 offset reach: 0.00 – 0.40 0.00 – 0.40
(Zone 4 is reversible)Zone 2 timer: 0.10 – 3.00 sec 0.10 – 3.00 secZone 3 and 4 timers: 0.10 – 10.0 sec 0.10 – 10.0 secPhase instantaneous OC: 0.4 – 32 A 2.0 – 160.0 AGround instantaneous OC: 0.1 – 16.0 A 0.5 – 80.0 AGround TOC: 0.04 – 3.00 A 0.20 – 15.00 ATOC curves: Inverse, very inverse, extremely
inverse, definite and custom
RECLOSURE (OPTIONAL)Reclose attempts: 4Synchronism check: Optional
Ordering
Accessories:
158D7358P1 L2 Flange for vertical mounting158D7359P1 KD Flange for vertical mounting
NOTE: For dimensions see ALPSbrochure.
LPS * * * * * * * * * * * *LPS Line protection system
O Phase distance relay with out-of-step tripping (system phase backup)
B Revision level B3 Three-phase tripping logic
5 5 A rated currentU For applications without series capacitors
0 48 VDC battery voltage1 110/125 VDC battery voltage2 220/250 VDC battery voltage
1 SCR trip outputs and contact channel interface2 Contact trip outputs and contact channel interface
3 Front RS232 com port and 2 selectable RS232/RS485 rear port(GE-MODEM/ASCII)
H Horizontal mountingV Vertical mounting
E Extended oscillography memory1 With out-of-step tripping
N No reclosure
Time Synchronization
An IRIG-B input is provided for timesynchronization via satellite signal.
Security
There are separate remote pass-words which permit view only,view and settings changes, or view,settings, and control capability.
Software
Windows®-based software pack-ages are included in the LPS-Oinstruction book.
LPS-O LINK – allows communi-cation with the relay using GEprotocol
XPRESSION BUILDER™ – allowsthe user to graphically designprogrammable logic settings andI/O assignments
The user may also obtain GE-DATAor GE-OSC to analyze oscillo-graphy data.
LPS-O GuideformSpecificationsFor an electronic version of the LPS-Oguideform specifications, pleasevisit: www.GEindustrial.com/Multilin/specs, fax your request to 905-201-2098 or email to [email protected].
™LPS-O is a trademark of GE Multilin.
www.enerVista.comenerVista enabledenerVista enabled See page 275.
55
3
M Family Digital Machine Protection Relay
Features and Benefits
Advanced 16-bit microprocessor
Configurable logic, curves, digital I/Osand LEDs
Flash memory for field upgrades
Two settings groups
Drawout case for easy maintenance
AC/DC power supply
Access via front panel keypad or commu-nication links
Compatible with M Family systems inhalf or full 19" racks
Applications
Protection and control for generators,motors, and transformers
enerVista.com compatible (see page 275)
Protection and Control
Thermal image protection
Unbalance
Overcurrent and undercurrent
Monitoring and metering
Analog/digital oscillography
24 event recording
Restricted ground fault
User Interfaces
M+PC software for setting and monitoring
Front RS232 and rear RS485 ports usingModBus® RTU protocol up to 19,200 bps
Three-phase protection
for electrical machines.
GE Multilin
ProtectionThe MIG Digital Machine ProtectionRelay is designed specifically forsmall generators and motors. Aspart of the M Family, the MIGprovides superior protection whichincludes:
Thermal Image Unit
The thermal image algorithmprotects the machine from nega-tive sequence components thatcan cause overheating in the statorand rotor, as well as overload.
Unbalance
Protection against rotor damageis provided through definite timeor time curve models, to minimizeheating caused by the negativesequence current generated bysupply voltage unbalance.
Three-Phase TOC
This protection can be set from0.1 to 2.4 times In. Four separateANSI or IEC TOC curves can beselected including definite time,normal inverse, very inverse, andextremely inverse. Additionally, a user configurable curve is avail-able. Different time multipliersmay be set for each curve, opti-mizing curve selection for coordi-nation with fuses, machines,motors, transformers, or otherequipment.
Phase IOC Units
Adjustable phase IOC allows thepickup setpoint to be set from 0.1to 30 times In and a time delayfrom 0 to 100 seconds.
Ground TOC
This feature has the same curveselection choices and settings asthe phase TOC unit. The groundsignal is normally derived as theresidual sum of the three-phaseCTs eliminating the need for
MIG M Family Digital Machine Protection Relay
www.GEindustrial.com/Multilin56
3
Functional Block Diagrams
MIGDigital Machine Protection
GENERATOR APPLICATION
MOTOR APPLICATION
52G
METERING
OSCILLOGRAPHY
EVENT RECORDING
CONFIGURABLE I/O
CONFIGURABLE LEDS
CONFIGURABLE LOGIC
50P
MIGDigital Machine Protection
37 66
3
52M
742751A2.ai
METERING
OSCILLOGRAPHY
EVENT RECORDING
CONFIGURABLE I/O
CONFIGURABLE LEDS
CONFIGURABLE LOGIC
GEN
50G 51G
50G 51G
M
49 46 51P 50P
49 46 51P
MIG
TRANSFORMER APPLICATION52
3
1
METERING
OSCILLOGRAPHY
EVENT RECORDING
CONFIGURABLE I/O
CONFIGURABLE LEDS
CONFIGURABLE LOGIC
742752A2.ai
50G 51G 87R
49 46 51P 50P
an additional ground sensor.Alternatively, for more sensitivedetection, an additional corebalance (zero sequence) groundsensor encircling the three-phaseconductors can be used.
Ground IOC Units
This protection has the samesettings and features as the phaseIOC unit.
Undercurrent
This function is used in motorapplications to detect a decreasein machine current caused byload decrease. The unit can beset as an alarm or trip.
Starts/Hour and Time To Restart
This feature counts the number ofmachine starts during a timewindow to ensure they do not
normal inverse IEC Avery inverse IEC Bextremely inverse IEC Cdefinite time definite time
ANSI IEC/BS142
TRIPCOIL
PHASE ACT
PHASE BCT
PHASE CCT
ZERO SEQUENCEGROUND CT
ZERO SEQUENCE 20 A MAXCIRCUIT BREAKERLOCATED BEFORE
POWER INPUT
GROUND SENSING CONNECTION
>>
>>
>>
<<
<<
>>
A
B
C
LINE
<<
<<52a 52a
CIRCUIT
AC or DC
BREAKER
TRIP COIL
Terminals B12, A12 and B11 must be connected to SELV(safety extra-low voltage) parts (on the PLC). They arenot to be tested for hipot test under any circumstance.
In basic model, inputs and outputs are configured as follows: INPUTSCC1: Disable 50P FunctionCC2: Disable 50N Function
CONTROLPOWER
GROUNDBUS
-
+
PROGRAMMABLECONTROLLER
A
B
GROUND
INPUT
INPUT
OUTPUTSOUT1: Phase TripOUT2: Ground TripOUT3: 50 TripOUT4: 49 Alarm
CAUTION: Fork or ring terminals must be used on the termainal block.NOTE: Suitable disconnect devices (switch or circuit breaker) recommended located near the relay.OVERVOLTAGE CATEGORY: II(*)
(**)
Internally fused1A/250V fast blow
NOTE: 14 AWG wiringrecommended (2.5 mm2)
742750A2.ai
C1
A5
A1 A2
A6
A8
A9
A7
A10B10
B9
B8
B7
B11(*)
A12(*)
B12(*)SDA
SDB
GND
GND
RS232
JXCC1
CC2
COM
C2 C3 C4 C5 C6 C7 C8
POWER
+/L -/NI N N N N
CURRENT INPUTS
SAFETYGROUND
TR
IP
B5
B6 RE
AD
Y
CO
MO
UT
4O
UT
3O
UT
1
RS
48
5
OU
T1/2
DIG
ITA
L O
UT
PU
TS
(**
)
DIG
ITA
LIN
TP
UT
S(*
*)
A IB IC IG
PHASE ACT
PHASE BCT
PHASE CCT
ALTERNATIVE CT WIRING FORRESIDUAL GROUND SENSING
A
B
C
C1 C2 C3 C4 C5 C6 C7 C8
I N N N N
CURRENT INPUTS
A IB IC IG
MIGDigital GeneratorProtection
GE Multilin
MIG M Family Digital Machine Protection Relay
www.GEindustrial.com/Multilin 57
3
Typical Wiring Note: Only for reference. For particular connections for any MIG model, please refer to its externalconnections drawing.
exceed the number programmedby the user. If the number isexceeded, the unit blocks any newattempts and keeps the trip contactclosed during the restart block time.
Locked Rotor
The MIG provides protectionduring extra-long start-ups whereexcessive overcurrent conditionscan damage rotors. This protectionis critical for power applicationswhere the motor drives the gener-ator into service.
Restricted Ground Fault
Restricted Ground Fault (RGF)protection provides sensitiveground fault detection for lowmagnitude fault currents thatmay not be detected by otherprotection functions. This protec-tion is often applied to machinesand transformers having imped-ance grounded wye windings.
Inputs and Outputs
The factory configuration of MIGinputs and outputs can be easilymodified using M+PC software.Two digital inputs and six relayoutputs are provided, four of themprogrammable. These config-urable outputs can be assignedeither to a set of pre-configuredvalues, or to an OR/NOT combina-tion of the same values.
MIG GuideformSpecificationsFor an electronic version of the MIGguideform specifications, pleasevisit: www.GEindustrial.com/Multilin/specs, fax your request to 905-201-2098 or email to [email protected].
Ordering
MIG P * * * E O 00 * 00 *MIG Digital machine protection relay
P Three-phase + ground relayA ANSI curvesI IEC curves
1 Phase CT In = 1A (pickup range: 0.1 – 2.4 A)5 Phase CT In = 5A (pickup range: 0.5 – 12 A)
1 Ground CT In = 1A (pickup range: 0.1 – 2.4 A)5 Ground CT In = 5A (pickup range: 0.5 – 12 A)N Sensitive ground CT In = 1 A
(pickup range: 0.005 – 0.12 A)F 24 – 48 VDC auxiliary voltage (range: 19 – 58 VDC)H 110 – 250 VDC (range: 88 – 300 VDC) and
110 – 230 VAC (range: 88 – 264 VAC)C Individual relayS Mounted in an M+ system†
† If relays are to be mounted in an M+ system, then either an M050 half 19” rack or M100 full 19” rack case must beordered. The M050 and M100 racks are provided at no additional cost based on the number of relays ordered.
Accessories
B1315P1 Depth reducing collar, reduces the mounting depth by 63 mm
www.enerVista.comenerVista enabledenerVista enabled See page 275.
GE Multilin 58
MGCMGCDigital Generator Protection
Three phase protection for small
generators.
Features and Benefits
I1, I2, I0 metering and last trip data
Part of a modular system
Independent 4" modules
1/4 standard 19" rack cases available
3 digit display and reset button
Applications
Small generators
Component for bigger generator packages
Protection and Control
Unbalance or current reversal
Thermal protection
Phase and ground faults
59 www.GEindustrial.com/Multilin
MGC Digital Generator Protection
DescriptionThe MGC1000 are microproces-sor based, digital type, generatorprotection relays which providethermal protection for threephase generators, phase fault,ground fault, and unbalancedcurrent protection.
ApplicationsThe basic functions performed bythe MGC are:
46-protection against unbalancedcurrent or current reversal (nega-tive sequence)
49-thermal protection51-protection against phase faults51G-protection against ground
faults
The thermal image unit alsoprovides protection againstexcessive starts, given that oncea trip has been produced, thethermal unit does not reset untilthe temperature of the generatordecreases below a given value.
Construction accurate and reliable, with low
power consumption
Typical Wiring
rack mounting (case is 1/4 of arack wide, or 6.33")
LED indicators for Pick-Up, Trip,and System Availability
three digit display, where thefollowing information isdisplayed:F0. present state of the equip-mentF1. thermal state (%)F2. positive sequence current(xIs)F3. negative sequence current(xIs)F4. zero sequence current(xInGRN)F5. last trip (cause)F6. positive sequence currentduring the tripF7. negative sequence currentduring the tripF8. zero sequence currentduring the trip
anti-shock, flame resistant,sealed plastic cover, whichallows the trip indicator to bereset from outside the cover
elevated anti-seismic waveformresponse of the output relays
high reliability, solid statecomponents
microprocessor system
Standard Functions
Thermal Image Unit
Adjustable between 0.55 and 1.3times In in steps of 0.05 times In,through microswitches locatedon the front of the relay.
Selectable operating curves as afunction of the time constant (t1),adjustable between 1 and 20 minin steps of one min.
Negative Sequence compensa-tion (K1), adjustable from 1 to 6.
Cold time constant (t2) adjustablefrom 1 to 6 times the warm timeconstant.
Positive Sequence Unit (I1)
Adjustable between 1 and 8 timesthe value selected for the thermalimage unit.
Time delay of 0.05 to 10 sec in0.05 sec steps.
Negative Sequence Unit (I2)
The unit can operate either as aninstantaneous (adjustable timedelay) or according to an inversetime curve; where the operatingmode can be selected by theuser.
Instantaneous Mode (adjustabletime delay): 0.5-8 x Is in steps of0.1 x Is with time delay of 0.05 to10 sec in 0.05 sec steps.
Inverse Time Mode: Per the familyof curves in Fig. 3, truncated forselectable pick up settingsbetween 0.1-1.0 x Is in steps of0.1 x Is.
Zero Sequence Unit (I0)
Adjustable between 0.06 and 0.24x InGRN in steps of 0.01 x InGRN (InGRN = 5, 1 or 0.02 A).
Time Delay: 0.05 - 10 sec,adjustable in steps of 0.05 sec.
B10
B1
B9
B6
B3
B5
B4
B8
B7
720754A5.CDR
( - )
(+)
MANUALTRIP
MANUALCLOSE
SYST
EM
READ
YTR
IPTH
ERM
AL A
LARM 52/b
52/a
52/TC 52/CC
52
A
B
C
A9
A6
A8
A11
A12
A10
A7
A5
A3
A4
A2
A1
A
BC
GE Power Management
MGCDigital GeneratorProtection Relay
POWER SUPPLY
Auxiliary Voltage: 24-48 VDC/VAC, 48-125 VDC/VAC, 110-240 VDC/110-220 VAC (three models)
TYPE TESTS
Insulation:Between Each Terminal and the Chassis:
2000 VAC for one min at industrial freq.Between Independent Circuits:
2000 VAC for one min at industrial freq.Between Terminals of Each Output Circuit:
1000 VAC for one min at industrial freq.Interference Test: 2.5 kV longitudinal, 1 kV transversal,
class 111, per IEC 255-4Impulse Test: 5 kV peak, 1.2/50 ms, 0.5 J, per IEC 255-4Electrostatic Discharge: Per IEC 801-2, class IIIRadio Interference: Per IEC 801-3, class III
METERING
ACCURACYOperating Value: 5%Operating Time: 5% or 0.025 sec, whichever isgreaterClass E Error Index, Per BS142 for Current and OperatingTimes: Class E-5
ContactCharacteristicsMGC relays have two tripcontacts, one is normally open,and the other, electrically sepa-rate, is normally closed. Therelays incorporate two pre alarmtemperature contacts, electricallyseparate and with the same char-acteristics as the trip contacts.They also include a normallyclosed contact for equipmentalarm.
Trip Contacts
Closing: 3000 W resistive for 0.2sec with a max of 30 A and 300VDC.
Opening: 50 W resistive, with amax of 2 A and 300 VDC.
Continuous: 5 A.
Alarm Contacts
Closing: 5 A DC for 30 sec, at 250VDC maximum. Opening: 25 Winductive and 250 VDC max.
Continuous: 3 A.
SettingsWith the exception of the currenttap Is, the rest of the settings canbe made through three pushbuttons located on the front ofthe relay: ENTER; +; -; the select-ed setting value can be seen onthe display. A feature common toall the units is the possibility forthe user to disable them.
www.GEindustrial.com/Multilin
5
MGC Digital Generator Protection
60
APPROVALS
Compliant
PACKAGING
Approximate Weight:Net: 8.8 lbs (4 kg)Shipping: 11 lbs (5 kg)
ENVIRONMENTAL
Temperature:Operating: -10 to +55°CStorage: -40 to +70°C
Relative Humidity: to 95% without condensing
INPUTS
BURDENSBurden: Less than 1.5 W at all voltagesTHERMAL CAPACITY OF THE CURRENT CIRCUITSCurrent Capacity:
Continuous: 2 x In3 Sec: 50 x In1 Sec: 100 x In
Burdens:For Models: In = 5 A: 0.3 VA
In = 1 A: 0.3 VAIn = 0.2 A: 0.08 VA
MONITORINGREPEATABILITYOperating Value: 1%Operating Time: 2% or 0.025 sec, whichever isgreater
RATINGSNominal Frequency: 50 or 60 Hz, selectable by the userNominal Phase Current (In):
1 A or 5 ANominal Ground Current (InGRN):
5, 1 or 0.02 A (This last setting is recommended when used with toroidal current transformers)
MGC Technical Specifications
MGC10 * 0D010 * 00 *MGC10 Three-pole tripping; 8 rack unit case
0 5 phase sec, 5 ground sec1 5 phase sec, 1 ground sec2 5 phase sec, 0.02 ground sec*3 1 phase sec, 1 ground sec*
F 24 - 48 VDC/VAC place auxiliary voltageG 48 -125 VDC/VAC place auxiliary voltageH 110 - 240 VDC/110-220 VAC place auxiliary voltage
C Individual drawout housingS As part of a MID† drawout system
* This model should be used only with toroidal current transformers for theneutral current signal. For more details, refer to the instruction book.
† Modular Industrial Protection SystemExample: Microprocessor generator protection relay, with nominal phase currentof In = 5 A, ground current InGRN = 1 A, standard type, with thermal alarm contact,and auxiliary voltage of 48-125 V.
OrderingTo order select the basic model and the desired features from the Selection Guide below.
*Specifications subject to change without notice.
www.GEindustrial.com/pm
Order online –Order online –save timesave time