Floor Standing Split Air Conditioner

TRANSCRIPT

  • 1

    MFS

  • 2

    PAGE

    1. CONTENTS 2

    2. NOMENCLATURE 3

    3. NAMES AND FUNCTION OF PART 4

    4. TECHNICAL SPECIFICATION 5

    5. OUTLINES AND DIMENSIONS 6

    6. WIRING DIAGRAM 8

    7. INSTALLATION (INDOOR) 9

    CONTENTS

  • 3

    M F S 30

    A

    Generation

    Capacity 30, 40, 50, 60

    Standing Fan Coil

    Floor

    McQuay

    Easy Maintenance The simple design concept has maintenance and servicing in mind. Access to the internal parts of the unit

    can be from front or back of the unit by removing a few screws

    Filter Rack The fan coil unit has a filter rack to hold the air filter. This ensure the air flow is clean and the filter is easily

    accessible for maintenance and cleaning

    Three Speed Motor The unit has 3-speed direct driven centrifugal fan and operate very silently to give whisper comfort condition. The speed of the fan can be adjusted through the electric controller. (See below).

    Easy and Flexible Installation The easy is highly compact and therefore it is very easy to select a location to install the unit such that only small space is required.

    Electric Controller

    Electric Controller can display cool, dry and fan mode with auto, high, medium and low fan speed. The temperature settings range from 16 OC and 30 OC.

    NOMENCLATURE

  • 4

    CONTROL PANEL

    REMOTE CONTROL

    AUTO mode

    COOL mode

    DRT mode

    FAN mode

    HEAT mode

    SLEEP operation

    SWING operation

    NAMES AND FUNCTIONS OF PART

    CLOCK Button Set desired Timed time

    Fan Running Display Simulate the running

    condition of ran

    TIMER Button Select timed

    starting or stopping

    ON/OFF Button Start or stop

    operation

    SLEEP Button Set or cancel

    sleep operation

    TEMPERATURE SET Button

    Set desired temperature

    FAN SPEED Button

    Set fan speed or indoor unit

    SWING Button Set the flow in a fixed direction or

    swing left

    MODE Button Select the

    operation mode

    Clock button

    Reset button

    Batteries

    ON/OFF button

    Mode button

    Swing button

    Sleep button

    Fan Speed button

    Fan speed and sleep operation

    display

    Mode Display

    Signal transmitting section

    Set temperature display

    Swing display

    Time display

    Temperature set button

    On timer button

    Off timer button

  • 5

    TECHNICAL SPECIFICATION

    MODEL INDOOR UNIT MFS 30A MFS 40A MFS 50A MFS 60A

    OUTDOOR UNIT MLC 30C MLC 40C MLC 50C MLC 61C

    NOMINAL COOLING CAPACITY Btu/h 29,000 39,000 49,000 58,000

    REFRIGERANT / CONTROL R22 / THERMAL EXPANSION VALVE

    IND

    OO

    R

    BLO

    WER

    & M

    OTO

    R

    POWER SOURCE V/ph/Hz 240 / 1 / 50

    TYPE CENTRIFUGAL / DIRECT DRIVEN

    QUANTITY 1 1 1 1

    NOMINAL AIR FLOW CFM 850 1,150 1,450 1,750

    OUTLET VELOCITY m/s 3.1 4.2 5.3 6.4

    MOTOR OUTPUT W 50 90 110 110

    CAPACITOR SIZE f 3.5 6 5 5

    RATED RUNNING CURRENT (EACH) Amps 0.85 1.3 1.6 1.6

    FAN MOTOR POLES 4 Poles; IP55; Class B

    EXTERNAL STATIC PRESSURE inWG 0.4 0.4 0.4 0.4

    CO

    IL

    TUB

    E MATERIAL COPPER

    DIAMETER mm 9.52

    THICKNESS mm 0.3

    FIN

    MATERIAL ALUMINIUM

    THICKNESS mm/in 0.11

    TUBE HEIGHT 29 36 36 36

    ROWS

    2 2 3 3

    FIN PER INCH 14 14 14 16

    FACE AREA m2 0.34 0.43 0.43 0.43

    FIN LENGTH mm 480 480 480 480

    AIR VELOCITY FPM 154 206 260 314

    CASING MATERIAL PLASTIC FRONT PANEL

    DIMENSION

    HEIGHT mm 1900 1900 1900 1900

    WIDTH mm 600 600 600 600

    DEPTH mm 280 360 360 360

    WEIGHT kg 42 65 65 65

    CONTROL ROOM TEMPERATURE CAPILLARY TUBE

    PIPING CONNECTION

    GAS mm 15.88 19.05 19.05 19.05

    LIQUID mm 9.52 9.52 9.52 12.7

    CONDENSATE DRAIN SIZE FLEXIBLE HOSE

    FILT

    ER TYPE WASHABLE SARANET FILTER

    SIZE WIDTH x HEIGHT mm 500 x 690

    THICKNESS mm 5

    QUANTITY 1

    PACKING DIMENSION

    HEIGHT mm 1970 1970

    WIDTH mm 390 440

    DEPTH mm 680 680

    OU

    TD

    OO

    R

    CO

    MP

    TYPE SCROLL

    POWER SOURCE V/Ph/Hz 220-240/1/50 415 / 3 /50

    PROTECTION DEVICE OVERLOAD PROTECTION AND AUTO RESET HIGH/LOW PRESSURE SWITCH

    FAN

    FAN TYPE / DRIVE PROPELLER / DIRECT

    BLADE MATERIAL ACRLY STYRENE RESIN

    DIAMETER mm/in 609.6 / 24.0

    POWER SOURCE V/Ph/Hz 240 / 1 / 50

    CO

    IL

    TUB

    E MATERIAL SEAMLESS COPPER

    DIAMETER mm 9.52

    THICKNESS mm 0.3

    FIN

    MATERIAL ALUMINIUM

    THICKNESS mm 0.11

    NUMBER x ROWS 1 x 1 1 x 2 1 x 2 1 x 3

    FIN PER INCH 16 14 16 16

    FACE AREA m2 0.89 0.85 0.87 1.23

    DIMENSION

    HEIGHT mm 850

    WIDTH mm 1,030

    DEPTH mm 400 460

    WEIGHT kg 95 100 105 108

    CASING MATERIAL ELECTRO-GALVANISED MILD STEEL

    FINISH EPOXY POLYSTER POWDER COATING

    SOUND PRESSURE LEVEL dBA 58 58 58 61

    PIPING CONNECTION

    GAS mm 15.88 19.05 19.05 19.05

    LIQUID mm 9.52 9.52 9.52 12.7

  • 6

    INDOOR UNIT MODEL: MFS 30A

    MODEL: MFS 40A/50A/60A

    OUTLINES AND DIMENSIONS

    R

    R

  • 7

    OUTDOOR UNIT MODEL: MLC 30C, 40C, 50C, 61C

    Model A B C D E F G H J K L M N P

    MLC 30C/40C/50C 1030 850 400 390 414 827 72 196 91 488 448 141.5 746.5 82

    MLC 61C 1030 850 480 390 414 827 72 196 91 488 448 141.5 746.5 82

  • 8

    INDOOR - OUTDOOR UNIT MODEL: MFS 30A/40A/50A/60A MLC 30C/40C/50C/61C

    WIRING DIAGRAM

    PP

    LP

    HP

    CRANKCASE

    HEATER

    L2

    COMPRESSOR

    WH

    ITE

    RE

    D

    L1

    BLA

    CK

    BLU

    E

    L3

    BLA

    CK

    3L2

    4T2

    1L1

    2T1

    5L3

    RED

    6T3

    R S T N

    GR

    EE

    N/Y

    ELLO

    W

    OUTDOOR UNIT

    FAN

    MOTOR

    L N

    U

    V W

    R S T N

    NO

    RED

    A1

    A2

    NC

    NC

    GREEN/YELLOW

    RE

    D

    WH

    ITE

    BLU

    E

    DT

    FU -

    -

    -

    -

    -

    - DISCHARGE TERMOSTAT

    AUTO RESET HP SWITCH

    AUTO RESET LP PRESSURE

    PHASE PROTECTOR

    CONTACTOR

    FUSE

    BLUE

    BLUE

    RED

    WHITE

    BLUE

    RELAY

    PP

    C

    COM

    WHITE

    BLACK

    BLACK

    HP

    BLUE BLUE BLUE

    LP

    BLACK BLACK

    GREEN/YELLOW

    FU

    7ARED

    OPERATING

    BOARD

    8 4

    TC

    BROW

    BROW

    RE

    D

    BLU

    E

    1L1

    2T1

    (NO)

    (NO)

    BLA

    CK

    RED

    RE

    D

    BLU

    E

    WH

    ITE

    WH

    ITE

    DT

    C

  • 9

    Preliminary Site Survey a) Electrical supply and installation is to confirm to local authoritys (e.g. National Electricity Board) codes

    and regulations. b) Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be

    independent of welding transformers which can cause supply fluctuation. c) Ensure that the location is convenient for wiring and piping.

    Piping Do not use contaminated or damaged copper tubing. If piping, evaporator or condenser are exposed or had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do not remove plastic/rubber plugs/caps from fittings, tubing and coils until ready to connect suction or liquid line into fittings.

    Operational Check After all electrical wiring is completed and system is charged with refrigerant, make sure unit is operating properly. Check that: a) Condenser fans are running, with warm air blowing off the condenser coil. b) Evaporator blowers are running and discharging cool air. c) Suction line inside condensing unit feels cool. d) Liquid line inside condensing unit feels warm.

    Electrical Connection As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for field wiring regulations and ensure that these are complied with. Besides, observe the following general precautions: a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing

    wiring work. b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit

    breaker for over-current protection should be provided in the exclusive line. c) The unit must be GROUNDED to prevent possible hazard due to insulation failure. d) All wiring must be firmly connected. e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan

    motors.

    INSTALLATION (INDOOR)

  • 10

    Maximum Pipe Length And Maximum Number Of Bends When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability drops as a result. As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity and the compressor may become defective. If the height difference between the evaporator and the condenser is excessive, the cooling capacity drops, the lubricating oil return is retarded, affecting the compressor efficiency adversely. Always choose the shortest piping path and follow the recommendations as shown below:

    Model Max. Elevation,

    m (ft)

    Max. Length,

    m (ft)

    Max. Total Length, m (ft)

    Max. of

    Bends

    MLC 30C 25 (82.0) 20 (65.6) 45 (147.6) 8

    MLC 40C 25 (82.0) 20 (65.6) 45 (147.6) 8

    MLC 50C 25 (82.0) 20 (65.6) 45 (147.6) 8

    MLC 61C 25 (82.0) 20 (65.6) 45 (147.6) 8

    COUTION: 1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length

    and/or the number of bends of the refrigerant piping system installed is beyond the limit above. 2) Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far

    as possible.

    Maximum Allowable Piping Length & Elevation Difference

  • 11