connection need help?

2
Technical Specifications Inputs & Outputs 8 digital inputs 6 ... 24VDC (PELV) 8 digital outputs (relays) - 250VAC 10A* at cos=1 - 30VDC 10A* 4 analogue inputs 0-10V (Ri=10k), when used as digital inputs threshold approx. 1V • Link (connection with Extensions, up to 30 devices) • Tree (connection with Tree Products, up to 50 devices) LAN (100 Mbps) Power Consumption typ. 1.85W, max. 3W (all relays on) Ambient temperature 0 ... 50°C / 32 ... 122°F Safety Rating IP20 Operation Typ 1 (IEC 60730-1, UL 60730-1) Rated surge voltage of digital outputs 2.5kV (UL 60730-1, max. altitude 2.000m) Connection Push Terminal Wire Conductor cross-section 0.25 ... 0.8mm 2 / AWG23 ... AWG18 Push-In-Technology To make connection, insert wire; to remove the wire, twist and pull at the same time. Stripping Length 5mm / 0.2” Total Power Loss max. 6.7W Power Supply 19.2 ... 30VDC PELV Loxone Electronics GmbH Smart Home 1 4154 Kollerschlag Austria loxone.com Need Help? loxone.com/support Part No: 100335 Miniserver V221119 Humidity max. 95% r. H. (non condensing) Maintenance & Cleaning The device is free of maintenance and may only be cleaned with a dry cloth. Dimensions 157x88x57mm / 6.18x3.46x2.24” (LxWxH) Technical Specifications Connection Screw Terminal Torque of Terminal Blocks min. 0.5Nm; max. 0.6Nm Wire Conductor cross-section 0.05 ... 2.5mm 2 / AWG30 ... AWG13 Temperature Resistance Wire must have a min temperature rating of 70°C / 158°F for IEC Stripping Length 6 ... 7.5mm / 0.23 ... 0.29” Degree of pollution 2

Upload: others

Post on 13-Feb-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Technical Specifications

Inputs & Outputs • 8 digital inputs 6 ... 24VDC(PELV)

• 8 digital outputs (relays)- 250VAC 10A* at cosᵠ =1- 30VDC 10A*

• 4 analogue inputs 0-10V(Ri=10k), when used as digitalinputs threshold approx. 1V

• Link (connection withExtensions, up to 30 devices)

• Tree (connection with TreeProducts, up to 50 devices)

• LAN (100 Mbps)

Power Consumption typ. 1.85W, max. 3W (all relays on)

Ambient temperature 0 ... 50°C / 32 ... 122°F

Safety Rating IP20

Operation Typ 1 (IEC 60730-1, UL 60730-1)

Rated surge voltage of digital outputs

2.5kV (UL 60730-1, max. altitude 2.000m)

Connection Push Terminal

Wire Conductor cross-section 0.25 ... 0.8mm2 / AWG23 ... AWG18

Push-In-Technology To make connection, insert wire; to remove the wire, twist and pull at the same time.

Stripping Length 5mm / 0.2”

Total Power Loss max. 6.7W

Power Supply 19.2 ... 30VDC PELV

Loxone Electronics GmbHSmart Home 14154 KollerschlagAustria

loxone.com

Need Help?loxone.com/support

Part No: 100335

Miniserver

V22

1119

Humidity max. 95% r. H. (non condensing)

Maintenance & Cleaning The device is free of maintenance and may only be cleaned with a dry cloth.

Dimensions 157x88x57mm / 6.18x3.46x2.24” (LxWxH)

Technical Specifications

Connection Screw Terminal

Torque of Terminal Blocks min. 0.5Nm; max. 0.6Nm

Wire Conductor cross-section 0.05 ... 2.5mm2 / AWG30 ... AWG13

Temperature Resistance Wire must have a min temperature rating of 70°C / 158°F for IEC

Stripping Length 6 ... 7.5mm / 0.23 ... 0.29”

Degree of pollution 2

About the productThe Loxone Miniserver is a device for automatic control and management of home & building automation and similar non-safety critical applications.

Installation & electrical connectionThis device must be mounted on a DIN rail in an electrical distribution housing (standard distribution) and may only be installed by qualified personnel.

Protection against electrical contact and fire protection must be provided in the final installation by the use of a standards compliant/approved housing.

To turn the unit on/off during installation and in case of failure, a separator (disconnecting device) must be present. These must be easily accessible and visible.

If the unit is used in a non-conforming manner as specified by the manufacturer the product included safeguards will be impaired.

Please use the 120 Ohm resistor at the last Extension which is connected to the Loxone Link.* High loads at the digital outputs result in heat development, which can influence the lifetime in the long run. We recommend using coupling relays with loads greater than 5A.

For additional information, declaration of confirmity, visit www.loxone.com/help/miniserver

LAN

AI1AI2AI3AI4

I2I3I4I5I6I7I8

AI2

AI4

I2

I6

I4

I8

AI1

AI3

I1

I5

I3

I7

AnalogueInputs

Digital

Inputs

Digital O

utputs(Relays)

Q2

Q3

Q4

Q5

Q6

Q7

Q8

Q2

Q4

Q1

Q3

Q6

Q8

Q5

Q7

This folder is a part of the product!

I1

Micro

SD

WH

GN

WH

Q1

BU

TreeLink

Power

Supply

OG

WH