ashrae houston standard 90.1 / city of houston energy …ashrae houston standard 90.1 / city of...
TRANSCRIPT
ASHRAE HOUSTON Standard 90.1 / City of Houston
Energy Code Seminar www.ashraehouston.org
www.ashrae.org http://documents.publicworks.houstontx.gov/d
ocument-center/houston-amendments-and-code-related-documents/ashrae-90.1-2007-
houston-amendments/details.htm
ASHRAE HOUSTON Standard 90.1 / City of Houston
Energy Code Seminar 9:00 Introduction Keith Reihl 9:15 90.1 MEP Keith Reihl 10:30 Break 10:45 Appendix G David McClain 11:15 Lunch 12:30 City of Houston Forms and
Implementation Lisa Brown
ASHRAE HOUSTON Standard 90.1 / City of Houston
Energy Code Seminar 1:00 90.1 Building Envelope Lisa Rosenow 2:30 90.1 2007 vs 90.1 2010 Keith Reihl 3:00 Closing and questions
SURVEY LINK http://67.225.150.43/survey.php
ASHRAE HOUSTON Standard 90.1 / City of Houston
Energy Code Seminar The Energy code allows you to follow:
ASHRAE 90.1 2007 - Or -
IECC 2009 Since IECC 2009 is based upon ASHRAE 90.1 2007 we are only
presenting 90.1 today.
90.1 Historical Timeline
90.1-2001 minor revisions
90.1-2004 updates, reorganization
90.1-1999 major rewrite
90.1-1989 updated
90.1-1975 first issued
90.1-1980 updated
1990 2000 2010 1970 1980
90.1-2007 updates
ASHRAE Standard 90.1
Purpose
“… Provide minimum requirements for the energy-efficient design of buildings except low-rise residential buildings”
ASHRAE Standard 90.1 and
Model Codes ASHRAE Standard 90.1 is adopted by:
– National Fire Protection Association – International Code Council
(International Energy Conservation Code) • IECC–Chapter 8 adopts 90.1-2007 by reference • IECC–Chapter 7 describes an alternate path for
compliance
ASHRAE Standard 90.1 and
LEED®-NC Version 2.2 • EAp2: Minimum energy performance
• Mandatory provisions of 90.1-2004 and • Prescriptive requirements of 90.1-2004 or Energy
Cost Budget method of 90.1-2004
• EAc1: Optimize energy performance • Awards points for improving performance rating of
the design building vs. baseline building per 90.1-2004
• Minimum 14% improvement (2 credit points) is required
ASHRAE Standard 90.1 and
LEED®-2009 • EAp2: Minimum energy performance
• Mandatory provisions of 90.1-2007 and • Prescriptive requirements of 90.1-2007 or Energy
Cost Budget method of 90.1-2007 and • 10% improvement over 90.1-2007
• EAc1: Optimize energy performance • 1 point for 12% savings • 3 points for 16% savings… • Up to 19 points (out of 100)
ASHRAE Standard 90.1
Scope
• New buildings and their systems
• New portions of buildings and their systems
• New systems and equipment in existing buildings
ASHRAE Standard 90.1
Exclusions • Low-rise residential buildings
– ASHRAE Standard 90.2 covers low-rise (3 stories or less)
• Buildings that do not use either electricity or fossil fuel
• Equipment and portions of building systems that use energy to primarily to provide for industrial, manufacturing, or commercial processes
Standard 90.1
• Under continuous maintenance • Latest Published 90.1 2010 • 90.1-2007 plus addenda
– Will highlight a few of the significant addenda
90.1 2010 is 30% stricter than 2004
Standard 90.1 Section 6 HVAC • Equipment - New equipment shall meet the
minimum efficiency requirements • Cooling systems
– New cooling systems installed to serve previously uncooled spaces shall comply with this section
– Alterations to existing cooling systems shall not decrease economizer capacity (unless economizer tradeoff is used)
• Ductwork - New and replacement ductwork shall comply with applicable requirements
• Piping - New and replacement piping shall comply with applicable requirements
Standard 90.1 Section 6 HVAC • Alterations to the building HVAC system
shall comply with the requirements of Section 6 – Exceptions that are allowed:
• Equipment being modified or repaired (not replaced) – provided such modifications will not result in an increase
in the annual energy consumption • Equipment being replaced or altered which requires
extensive revisions to other systems and such replaced or altered equipment is a like-for-like replacement
• Refrigerant change of existing equipment • Relocation of existing equipment • Ducts and pipes where there is insufficient space or
access to meet these requirements
Standard 90.1 Section 6 HVAC • Section 6.2 • You have to follow Sections
– 6.1 General, – 6.7 Submittals, and – 6.8 Minimum Equipment Efficiency,
• And then you can follow either – Section 6.3 Simplified Approach OR – Sections 6.4 Mandatory Provisions and 6.5
Prescriptive Path Alternatively, you can follow Section 11 (ECB),
in which case Section 6.4 is mandatory
Standard 90.1 Section 6 HVAC • Simplified Approach is limited to…
– Buildings with 1 or 2 stories – Buildings < 25,000 ft2
– Single-zone systems (unitary or split) – Air-cooled or evaporatively cooled
Simplified Approach Option (cont’d)
Table 6.3.2
• For 2010 (not right now for climate zone 2a) The system shall have an economizer, unless the economizer Trade-off Option is used – Limited to unitary systems – Requires higher minimum
cooling efficiency (EER) – Trade-off EER by
• System size • Climate zone
Simplified Approach Option (cont’d)
• Manual changeover or dual set-point thermostat
• Heat pump supplementary control • No reheat or simultaneous heating and cooling
for humidity control (RESERVED IN COH) • Time clocks (except hotel/motel guest rooms
and systems requiring continuous operation) • Piping and ductwork insulated per Mech Code
20
Simplified Approach Option (cont’d)
• Balancing of ducted systems by NEBB, AABC or ASHRAE 111
• Interlocked t-stats for separate heating & cooling • Exhaust : gravity or motorized dampers unless
operated continuously • System > 10,000 cfm: optimum start controls • Outside air intakes shall have motorized dampers
with leakage rate not to exceed 4 cfm at 1.0 in. w.g. cfm per ft2 of damper area. Outside air dampers and exhaust fans shall be interlocked to close the damper and turn off the fan when the supply air system is de-energized.
21
HVAC Mandatory Provisions
• Minimum Equipment Efficiency (Section 6.4.1)
• Load Calculations (Section 6.4.2) • Controls (Section 6.4.3) • HVAC System Construction and Insulation
(Section 6.4.4) • Completion Requirements (Section 6.4.5)
22
Equipment Covered
• Package air conditioners and condensing units
• Heat pumps (air, water, and ground source) • Packaged terminal and room air conditioners • Chillers including absorption chillers • Furnaces and unit heaters • Boilers • Heat rejection equipment
23
Mechanical Equipment Efficiency • Tables 6.8.1A – 6.8.1G
• Tables 6.8.1H-6.8.1J used for water cooled centrifugal chillers that operate at non-standard rating conditions
• Combination HVAC and water heating systems to meet all requirements for appropriate space heating or cooling category
• Gas-fired and oil-fired forced air furnaces with input ratings ≥ 225,000 Btu/h to have intermittent or interrupted ignition device and have either power venting or a flue damper
• All furnaces with input ratings ≥ 225,000 Btu/h, including electric furnaces, not located in conditioned space, to have jacket losses ≤ 0.75% of the input rating
24
Verification of Equipment Efficiencies
Equipment efficiency information from manufacturers verified as follows:
• EPACT equipment – to comply with DOE certification requirements
• If certification program exists for covered product and includes provisions for verification and challenge of equipment efficiency ratings, product listed in program OR
• If product not listed in program, ratings verified by an independent laboratory test report OR
• If no certification program exists, equipment efficiency ratings supported by data furnished by manufacturer OR
• Where components from different manufacturers are used, system designer specifies components whose combined efficiency meets Section .4.1
• Products in Table 6.8.1G shall have efficiency ratings supported by data furnished by manufacturer.
25
Labeling • Mechanical equipment (6.4.1.5.1) – equipment not
covered by NAECA shall carry a permanent label stating equipment complies with 90.1
• Packaged terminal air conditioners (6.4.1.5.2) – packaged terminal air conditioners and heat pumps with sleeve sizes < 16 in. high and 42 in. wide shall be factory labeled as follows:
– Manufactured for replacement applications only: not to be installed in new construction projects
26
Load Calculations • Must calculate
heating and cooling system design loads
• Must base calculations on generally accepted engineering standards and handbooks
• Appendix G
27
Controls – Zone Thermostatic and Dead Band
• Required for each zone – Perimeter can be treated differently
• Dead band controls – Thermostats must have at least a 5°F dead band – Exceptions
• Thermostats that require manual changeover between heating and cooling modes
• Special occupancy or applications where wide temperature ranges aren’t acceptable (e.g., retirement homes) and approved by adopting authority
28
Controls – Setpoint Overlap Restriction
• If limit switches, mechanical stops, or software programming for DDC systems are used – means will be provided to prevent the heating
setpoint from exceeding the cooling setpoint minus any applicable proportional band
29
Controls – Off-Hour
• Automatic shutdown • Setback controls • Optimum start • Zone isolation • Exceptions, HVAC systems
– with heating/cooling capacity < 15,000 Btu/h
– intended to operate continuously
30
Controls - Automatic Shutdown
• Automatic 7-day/week time clock with 10-hour battery backup – Exception: 2-day/week thermostat for residential
applications • Each control to have
– Occupant sensor, OR – Manually-operated timer with maximum two hour duration,
OR – Security system interlock
• Exception – Residential occupancies allowed to operate with only 2
different time schedules/wk
31
Controls - Setback
• Climate Zones 2-8 – Lower heating setpoint to 55ºF or less
• Climate Zones 1b, 2b, 3b (hot/dry) – Automatically restart, temporarily operate
• Raise cooling setpoint to 90ºF or higher OR
• Prevent high space humidity levels
32
Controls - Optimum Start
• Individual heating and cooling air distribution systems with – Total design supply air capacity >
10,000 cfm – Served by one or more supply fans
• Control algorithm to at least be a function of – Difference between space
temperature and occupied setpoint and amount of time prior to scheduled occupancy
33
Controls - Zone Isolation
• Applies to – Each floor in a multistory building – Maximum 25,000 ft2 zone on one floor
• Requirements – Isolation devices to shut off outdoor and
exhaust airflow when > 5,000 cfm – Central systems shall be capable of
stable operation with one isolation zone Capable of separate time schedules for
each isolation zone
34
Controls – Ventilation System (cont’d)
Stair and Shaft Vents
• Motorized dampers – Can be automatically closed during normal building
operation – Interlocked to open as required by fire and smoke
detection systems
35
Gravity Hoods, Vents, and Ventilators
• Motorized dampers to automatically shut when spaces served are not in use are not required since we are in Climate zone 2, Gravity is OK.
• Not required if non air conditioned space or prohibited by the mech. code.
36
Controls - Shutoff Damper • Motorized dampers for outdoor air supply and
exhaust systems not required in our climate zone, gravity dampers are OK.
• Ventilation outside air dampers to be capable of automatically shutting off during – Preoccupancy building warm up, cool down, and
setback (Except when ventilation reduces energy costs or when ventilation must
be supplied to meet code requirements)
Table 6.4.3.3.4 provides maximum leakage rates for outdoor air supply and exhaust dampers
37
Dampers
• Where OA supply and exhaust air dampers are required by Section 6.4.3.4 – They shall have a maximum leakage rate when
tested in accordance with AMCA Standard 500 as indicated in Table 6.4.3.4.4
– DELETED LEAKAGE AND REFERENCED MECH CODE!
38
Ventilation Fan Controls • Fans with motors > 0.75 hp shall have
automatic controls complying with Section 6.4.3.3.1 that are capable of shutting off fans when not required
• Exception – HVAC systems intended to operate
continuously
39
Heat Pump Auxiliary Heat Control
• Controls to prevent supplementary heat when heat pump can handle the load
• Exception – Heat pumps
• With minimum efficiency regulated by NAECA • With HSPF rating meeting Table 6.8.1B (Includes all usage of internal electric resistance heating)
40
Controls - Humidifier Preheat
• Automatic valve to shut off preheat when humidification isn’t required
41
Controls - Humidification and Dehumidification
• Provide means to prevent simultaneous operation of humidification and dehumidification equipment – Limit switches, mechanical stops, or software
programming (DDC systems) • Exceptions
– Zones served by desiccant systems, used with direct evaporative cooling in series
– Systems serving zones where specific humidity levels are required and approved by jurisdiction
• Museums and hospitals
42
Controls - Freeze Protection and Snow/Ice
• Automatic controls for – Freeze protection systems
• outside air temperatures > 40°F or when conditions of protected fluid will prevent freezing
– Snow- and ice-melting systems • pavement temperature > 50°F and no precipitation is
falling and outdoor temperature > 40°F
OK, Your asleep if your not questioning this one..
43
Ventilation Controls for High-
Occupancy Areas • DCV must be provided for each zone with a
area > 500 ft² and the design occupancy > 40 people/1000 ft² where the HVAC system has: – An air-side economizer, – Automatic modulating control of the OSA
dampers, or – A design outdoor airflow > 3,000 cfm
Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy.
44
Ventilation: High Occupancy Exceptions
Exceptions: Systems with exhaust-air energy recovery
complying with Section 6.5.6.1 Multiple zone systems without DDC to the zone
level Systems with a design OA airflow <1,200 cfm Spaces where supply-exhaust <1,200 cfm
45
HVAC System Construction and Insulation
• Insulation installed in accordance with industry-accepted standards
• Insulation protection • Duct and plenum insulation • Piping insulation • Duct sealing • Duct leakage tests • IN ACCORDANCE WITH MECH CODE!!
46
General
• Insulation installed in accordance with industry-accepted standards
• Insulation – Protected from damage due to sunlight, moisture,
equipment maintenance, and wind – Exposed to weather to be suitable for outdoor service – Covering chilled water piping, refrigerant suction
piping, or cooling ducts located outside the conditioned space to include a vapor retardant located outside the insulation, all penetrations and joints of which to be sealed
47
Duct and Plenum Insulation • All supply and return ducts and plenums to be insulated per
Tables 6.8.2A and 6.8.2B • Exceptions
– Factory-installed plenums, casings, or ductwork furnished as part of HVAC equipment
– Ducts located in heated, semi-heated, or cooled spaces – For runouts < 10 ft in length to air terminals or
air outlets, the R-value need not exceed R-3.5 – Backs of air outlets and outlet plenums exposed
to unconditioned or indirectly conditioned spaces with face areas > 5 ft2 need not exceed R-2; those ≤ 5 ft2 need not be insulated
48
Piping Insulation • Table 6.8.3 • Exceptions
– Factory-installed – Piping conveying fluids
• design operating temperature range between 60°F-105°F, inclusive
• that haven’t been heated or cooled through the use of nonrenewable energy or where heat gain or heat loss will not increase energy usage
– Hot water piping between shut off valve and coil, not > 4 ft in length, when located in conditioned spaces
– Pipe unions in heating systems (steam, steam condensate, and hot water)
49
Duct Sealing • Table 6.4.4.2A • Requirements of
6.4.4.2 • Based on
standard industry practice and definitions
• IN ACCORDANCE WITH MECH CODE!!
Table 6.4.4.2A
Minimum Duct Seal Level
See Table 6.4.4.2B definition of Seal Level. Duct design static pressure classification. Includes indirectly conditioned spaces such as return air plenums.
50
Duct Leakage Tests
• Designed > 3 in. w.c. – Leak tested – Representative sections
≥ 25% of the total installed duct area shall be tested
– Ratings > 3 in. w.c. to be identified on drawings
– Maximum permitted duct leakage
• Lmax = CLP0.65
Where Lmax = maximum permitted leakage in cfm/100 ft2 duct surface area
51
Completion Requirements
• Refers to Section 6.7 for Submittal and Completion Requirements including – Record drawings – Operating and maintenance manuals – System balancing
– System commissioning
52
Prescriptive Requirements
Simplified Approach
Option (§6.3)
proposed HVAC design
90.1-compliant HVAC system
prescriptive requirements
(§6.5)
Simplified Approach
Option (§6.3)
Energy Cost Budget Method
(ECB, §11)
(small buildings only)
mandatory provisions
(§6.4)
53
HVAC Prescriptive Path
• Economizers (Section 6.5.1) Coming in 2010!!! • Simultaneous Heating and Cooling Limitation
(Section 6.5.2) • Air System Design and Control (Section 6.5.3) • Hydronic System Design and Control (Section 6.5.4) • Heat Rejection Equipment (Section 6.5.5) • Energy Recovery (Section 6.5.6) • Exhaust Hoods (Section 6.5.7) • Radiant Heating Systems (Section 6.5.8) • Hot Gas Bypass Limitation (Section 6.5.9)
54
Zone Controls • Capable of operating in sequence the
supply of heating and cooling energy to the zone
• Controls prevent – Reheating – Recooling – Mixing or simultaneously supplying air
previously heated or cooled – Other simultaneous operation of heating and
cooling systems to the same zone
55
Zone Controls - Exceptions • Zones for which volume of air that is reheated, recooled, or
mixed is no greater than the larger of the following – Volume of outside air to meet 6.2 of ASHRAE 62 for the zone – 0.4 cfm/ft2 of zone conditioned floor area – 30% of zone design peak supply – 300 cfm for zones whose peak flow rate totals no more than 10% of the
total fan system flow rate – Any higher rate that can be demonstrated to jurisdiction to reduce
overall system annual energy usage • Zones where special pressurization relationships, cross-
contamination requirements, or code-required minimum circulation rates are such that the variable air volume systems are impractical
56
Hydronic System Controls
• Limit heating and cooling of fluids previously heated or cooled mechanically per 6.5.2.2.1 through 6.5.2.2.3
No common return system for both hot and chilled water
Three-Pipe System
57
Two-Pipe Changeover System
• SHALL NOT BE USED!! • Common distribution system acceptable if
– Deadband from one mode to another is ≥ 15°F outside air temperature
– Controls to allow operation of ≥ 4 hours before changing over
– Reset controls so heating and cooling supply temperatures at changeover point no more than 30°F apart
58
Hydronic (Water Loop) Heat Pump Systems
• Controls to provide heat pump water supply temperature deadband of at least 20°F between initiation of heat rejection and heat addition by central devices
• Cooling tower bypass or cooling tower isolation dampers • A two-position valve at each hydronic heat pump for
hydronic systems having a total pump system power > 10 hp • Exception
– If system loop temperature optimization controller is used, deadband < 20°F is allowed
59
Dehumidification
• Humidistatic controls to prevent – Reheating – Mixing of hot and cold air
streams – Heating and cooling of
same air stream
60
Dehumidification Exceptions
• FOR THE PURPOSES OF HUMIDITY CONTROL!!
• Systems capable of reducing supply air flow to 50%, or to minimum ventilation
• Systems under 6.67 tons that can unload at least 50%
• Systems smaller than 3.3 tons • Process applications • 75% of reheat or recool energy is recovered or
solar
61
Humidification
• Systems with hydronic cooling and humidification systems designed to maintain inside humidity at > 35°F dewpoint temperature shall use a water economizer if required by 6.5.1
Condenser
Chiller
Evaporator
OutOut
In
In
CoolingTower
CWP
PrimaryCHWP Secondary
CHWPWith
VariableSpeed Drive
HeadPressureControlValve
Economizer CWP
HeatExchanger
CHWS CHWR
TypicalCoolingCoil
CoolingCoilWithTertiaryPump
ValveClosesInEconomizerMode
2-WayValve
62
Air System Design and Control
• RESEVED!! • HVAC systems with total fan system
power > 5 hp to meet 6.5.3.1 through 6.5.3.2 – Fan Power Limitation – VAV Fan Control
• Part Load Fan Power Limitation • Static Pressure Sensor location • Set Point Reset
63
Fan Power Limitation • RESEVED!! • Table 6.5.3.1 • Allowable fan system power may be adjusted
if – Air systems require air treatment or filtering
systems with pressure drops > 1 in. w.c. when filters are clean, or heat recovery coils or devices, or direct evaporative humidifiers/coolers, or other devices to serve process loads in the airstream
– design room temperature – supply air temp at cooling design condition = > 20°F, allowable fan system power may be adjusted
• Exceptions
64
Motor Nameplate Horsepower • Selected fan motor to be no larger than first
available motor size greater than bhp • Fan bhp on design documents • Exceptions
– Fans < 6 bhp, where first available motor larger than bhp has nameplate rating within 50% of bhp, next larger nameplate motor size may be selected
– Fans ≥ 6 bhp, where first available motor larger than bhp has nameplate rating within 30% of bhp, next larger nameplate motor size may be selected
65
Part-Load Fan Power Limitation
• Individual VAV fans with motors ≥ 5 hp reduced from 10 hp. – Must have either:
• Variable Speed Drive • Vane axial fan with variable-pitch fan blades • Other controls and devices to result in fan motor
demand ≤ 30% of design wattage at 50% of design air volume when static pressure set point = 1/3 of total design static pressure, based on manufacturer’s certified fan data
66
Static Pressure Sensor Location
• REPLACED with requirement for ECM’s except parallel flow boxes with little fan operation
• Placed so controller set point is ≤ 1/3 the total design fan static pressure – Except for digital control systems with zone reset
capabilities where it may be at the fan discharge • Install multiple sensors in each major branch
if sensor would be located downstream of a major duct split
67
Set Point Reset
• For systems with direct digital control of individual zone boxes reporting to the central control panel – Static pressure set point reset based on zone
requiring the most pressure
68
Hydronic System Design and Control
• HVAC hydronic systems with total pump system power > 10 hp shall meet 6.5.4.1 – 6.5.4.4 – Hydronic Variable Flow Systems – Pump Isolation – Chilled and Hot Water Temperature Reset – Hydronic (water-loop) Heat Pump Systems
69
Hydronic Variable Flow
• HVAC pumping systems to include control valves – Designed to modulate or step open and close as a function of load – Designed for variable fluid flow – Capable of reducing flow rates to ≤ 50% of design flow rate
• Individual pumps serving variable flow systems with a pump head > 100 ft and motor > 50 hp – Have controls and/or devices resulting in pump motor demand
≤ 30% of design wattage at 50% of design water flow
70
Hydronic Variable Flow - Exceptions
• Systems where – Minimum flow is < minimum flow required
by equipment manufacturer for proper operation of equipment served by the system
– REMOVED Total pump system power ≤ 75 hp
• Systems that include ≤ 3 control valves
71
Pump Isolation
• If chilled water plant has more than one chiller or boiler plant has more than one boiler – Provide for flow reduction when chiller or boiler
is shut down
72
Chilled and Hot Water Temperature Reset Controls
• Affects systems with design capacity > 300,000 Btu/h – To include controls to automatically reset supply
water temperatures by representative building loads (including return water temperature) or by outside air temperature
• Exceptions – If controls would result in improper operation – Hydronic systems with variable flow
73
Hydronic Heat Pump
• For heat pump loops with total pump system power > 10 hp – Two-position valves at each hydronic heat pump
must be provided and interlocked to shut off water flow to the heat pump when the compressor is off
• This basically converts the system into a variable flow system. As such, these systems must also comply with 6.3.4.1
74
Heat Rejection Equipment
• RESERVED!! • Applies to heat rejection equipment used in
comfort cooling systems such as – Air-cooled condensers – Open cooling towers – Closed-circuit cooling towers – Evaporative condensers
• Exceptions – Heat rejection devices included as an integral part
of equipment listed devices whose energy usage is included in Tables 6.8.1A-6.8.1D
75
Fan Speed Control
• RESERVED!!! • Each fan powered by a motor ≥ 7.5 hp
– Have capability to operate fan at ≤ 2/3 full speed – Have controls to automatically change the fan speed to control the
leaving fluid temperature or condensing temperature/pressure of the heat rejection device
• Exceptions – Condenser fans serving multiple refrigerant circuits or flooded
condensers – Installations located in climates zones 1 and 2 – 1/3 of the fans on a multiple fan application speed controlled
76
Exhaust Air Energy Recovery
• Incorporate exhaust air energy recovery in systems with – ≥ 70% outside air and ≥ 5000 cfm total – DELETED -50% energy recovery effectiveness
77
Exhaust Air Energy Recovery Exceptions
• Lab fume hood systems and biological safety cabinets • Systems serving uncooled spaces that are heated to < 60°F • Systems exhausting toxic, flammable, paint or corrosive fumes or
dust • Commercial kitchen hoods used for collecting grease or smoke • Where > 60% of outdoor heating energy is provided from site-
recovered or site solar energy • Heating systems in climate zones 1 through 3 2 • Cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7, and 8 • Where largest exhaust source is < 75% of the design outdoor
airflow • Systems requiring dehumidification that employ energy recovery
in series with the cooling coil
78
Heat Recovery for Service Water Heating
• DELETED!! • Condenser recovery required if
– 24 hrs per day and – Heat rejection > 6,000,000 Btu/h and – SWH load > 1,000,000 Btu/h
• Exceptions
79
Kitchen Hoods (Exhaust) • RESERVED! • Hoods > 5,000 cfm to be provided with
makeup air sized for at least 50% of exhaust air volume that is a) unheated or heated to more than 60°F and b) uncooled or cooled without the use of mechanical cooling
• Exceptions – Where hoods are used to exhaust ventilation air
that would otherwise exfiltrate or be exhausted by other fan systems
– Certified grease extractor hoods that require a face velocity no greater than 60 fpm
80
Fume Hoods
• RESERVED!! • Hood systems with a total
exhaust rate > 15,000 cfm to have ONE of the following features – Operation to < 50% design
flow OR – Direct make up at least 75%
of exhaust rate at specified conditions OR
– Heat recovery for make-up air
81
Radiant Heating Systems
• Required for unenclosed spaces except loading docks with air curtains
• “Radiant heating systems that are used as primary or supplemental enclosed space heating must be in conformance with the governing provisions of the standard”
82
Hot Gas Bypass Limitation
• Not used (including other evaporator pressure control systems) unless system is designed with multiple steps of unloading or continuous capacity modulation
• Exception – Unitary packaged systems with cooling capacities
≤ 90,000 Btu/h
83
Submittals
• Record drawings • Operating and maintenance manuals • System balancing - Each supply
outlet and zone terminal device shall be equiped with means for air balancing!!
• System commissioning – BOTH Building Envelope and Systems Commissioning is required by COH!!
84
Drawings
• Record drawings of actual installation to building owner within 90 days of system acceptance and include, as a minimum – Location and performance data on each piece of
equipment – General configuration of duct and pipe
distribution system including sizes – Terminal air or water design flow rates
85
Manuals
• Operating and maintenance manuals to building owner within 90 days of system acceptance and include several items
86
System Balancing
• Systems shall be balanced in accordance with accepted engineering standards
• NEBB, AABC, ASHRAE 111 • Written report for conditioned spaces > 5000 ft2
• Minimize throttling losses • For fans with system power > 1 hp
– Adjust fan speed to meet design flow conditions
87
Hydronic System Balancing
• Proportionately balanced to minimize throttling losses • Pump impeller trimmed or pump speed adjusted to meet
design flow conditions • Each system to have either the ability to measure differential
pressure increase across the pump or have test ports at each side of the pump
• Exceptions – Pumps with pump motors ≤ 10 hp – When throttling results in < 5% of the nameplate hp draw, or 3 hp,
whichever is greater, above that required if the impeller was trimmed
88
System Commissioning
• Control elements are calibrated, adjusted, and in proper working condition
• > 50,000 ft2 conditioned area – Except warehouses and semiheated spaces – Requires commissioning instructions
89
Minimum Equipment Efficiency Tables
• Equipment efficiency tables 6.8.1A to 6.8.1J • Duct Insulation Tables 6.8.2A and 6.8.2B • Pipe Insulation Table 6.8.3
90
Mandatory Provisions (required for most
compliance options)
Building System Compliance Options
Energy Code Compliance
Prescriptive Option
Energy Cost Budget
Trade Off Option
Simplified
Envelope
HVAC
Lighting
SWH
Power
SWH Compliance
Other
91
Section 7 - Service Water Heating • General (Section 7.1) • Compliance Path(s) (Section 7.2) • Mandatory Provisions (Section 7.4)
– Load calculations – Equipment efficiency – Service hot water piping insulation – System controls – Pools – Heat traps
• Prescriptive Path (Section 7.5) – Space heating and water heating – Service water heating equipment
• Submittals (Section 7.7)
92
SWH Alterations
• SWH equipment installed as a direct replacement shall meet these requirements unless there is not sufficient space or access to meet these requirements
93
SWH Compliance Paths
• Section 7.2 • You have to follow Sections
– 7.1, – 7.4, – 7.5, – 7.7, and – 7.8
• Alternatively, you can follow Section 11 (ECB), in which case Section 7.4 is mandatory
94
Load Calculations
• In accordance with manufacturer’s published sizing guidelines or generally accepted engineering standards and handbooks
95
Equipment Efficiency
• Section 7.4.2 refers to Table 7.8 for equipment efficiencies • Equipment not listed in Table 7.8 has no minimum
performance requirements • Exception
– Water heaters and hot water supply boilers > 140 gal storage capacity don’t have to meet standby loss requirements when
• Tank surface is thermally insulated to R-12.5, and • A standing pilot light isn’t installed, and • Gas- or oil-fired water heaters have a flue damper or fan-assisted combustion
96
Service Hot Water Piping Insulation
• Table 6.8.3, Section 6 • Circulating water heater
– Recirculating system piping, including supply and return piping
• Nonrecirculating storage system – ALL Piping!! First 8 ft of outlet piping – Inlet pipe between storage tank and
heat trap
• Externally-heated pipes (heat trace or impedance heating)
97
Service Water Heating System Controls
• Temperature Controls • Temperature Maintenance Controls • Outlet Temperature Controls • Circulating Pump Controls
98
Temperature Controls
• To allow for storage temperature adjustment from 120°F or lower to a maximum temperature compatible with the intended use
• Exception – If manufacturer’s installation instructions
specify a higher minimum thermostat setting to minimize condensation and resulting corrosion
99
Temperature Maintenance Controls
• Automatic time switches or other controls – Set to switch off usage temperature
maintenance system during extended periods when hot water is not required
100
Outlet Temperature Controls
• Controls provided – To limit maximum temperature of water delivered
from lavatory faucets in public facility restrooms to 110°F
101
Circulating Pump Controls
• To limit operation to a period from the start of the heating cycle to a maximum of five minutes after the end of the heating cycle
102
Pools
• Pool heaters to have readily accessible on-off switch
• Pool heaters fired by natural gas can NOT have continuously burning pilot lights
• Vapor retardant pool covers required (unless recovered or solar heat)
• Time switches required
103
Heat Traps • Noncirculating systems to have heat traps
on both the inlet and outlet piping as close as practical to storage tank (if no integral heat traps) – Either a device specifically designed
for this purpose or
– Arrangement of tubing that forms a loop of 360° or piping that from the point of connection to the water heater includes a length of piping directed downward before connection to the vertical piping of the supply water or hot water distribution system, as applicable
104
Space Heating and Water Heating • Gas- or oil-fired space heating boiler system (complying with
Section 6) is allowed to provide total space heating and water heating when ONE of the following conditions is met – Single boiler or component that is heating the service water has a
standby loss in Btu/h not exceeding • (13.3 x pmd + 400) / n; where pmd is probable maximum demand in gal/h
and n is the fraction of the year when outdoor daily mean temperature is > 64.9°F
– Jurisdiction agrees use of a single heat source will consume less energy than separate units
– Energy input of the combined boiler and water heater system is < 150,000 Btu/h
• Instructions for determining standby loss are included in this Section
105
Service Water Heating Equipment
• Equipment used to provide the additional function of space heating as part of a combination (integrated) system shall satisfy all requirements for service water heating equipment
106
Service Water Heating Submittals
• Authority having jurisdiction may require submittal of compliance documentation and supplemental information in accord with Section 4.2.2 of this standard
107
Mandatory Provisions (required for most
compliance options)
Building System Compliance Options
Energy Code Compliance
Prescriptive Option
Energy Cost Budget
Trade Off Option
Simplified
Envelope
HVAC
Lighting
SWH
Power
Power Compliance
Other
109
Voltage Drop • Two types of conductors
– Feeder conductors • Connect service equipment to the branch circuit
breaker panels • 2% maximum voltage drop allowed at design load
– Branch circuit conductors • Run from the final circuit breaker to the outlet or
load • 3% maximum voltage drop allowed at design load
– These are more stringent than non-enforceable requirements
in the National Electric Code (NEC)
110
Power Submittals
• Owner gets information about the building’s electrical system – Record drawings of actual installation within 30 days
• Single-line diagram of electrical distribution system • Floor plans showing location and areas served for all
distribution – Manuals
• Submittal data stating equipment rating • O&M manuals for equipment • Qualified service agency • Complete narrative of system as it’s normally intended to
operate
111
Mandatory Provisions (required for most
compliance options)
Building System Compliance Options
Energy Code Compliance
Prescriptive Option
Energy Cost Budget
Trade Off Option
Simplified
Envelope
HVAC
Lighting
SWH
Power
Lighting Compliance
112
Section 9 - Lighting • General Application (Section 9.1)
– Scope – Lighting Alterations – Installed Interior Lighting Power – Luminaire Wattage
• Compliance Path(s) (Section 9.2) • Mandatory Provisions (Section 9.4)
– Lighting control – Tandem wiring – Exit signs – Exterior building grounds lighting – Exterior building lighting power
• Building Area Method Compliance Path (Section 9.5)
• Alternative Compliance Path: Space-by-Space Method (Section 9.6)
113
Lighting General • Scope
– Interior spaces of buildings – Exterior building features – Exterior grounds lighting powered through building – Exceptions
• Emergency lighting • Lighting required by life safety statute • Lighting within dwelling units of buildings • Decorative gas lighting
• Lighting Alterations – New lighting and lighting controls must comply with this section, unless an alteration replaces less than 50% of luminaires in a space and that alteration does not increase the installed lighting power
114
Lighting General
• Installed Interior Lighting Power shall include all power used by the luminaires, including lamps, ballasts, transformers, and controls – Exception: in the case where there are two
independently operated lighting systems that are controlled to prevent simultaneous operation
• Include only the higher wattage system
• Luminaire Wattage for various systems shall determined in accordance with details in Section 9.1.4
115
Exemptions
Basic Lighting Requirements
Mandatory Requirements (Interior and
Exterior)
Controls
Switching
Interior Lighting Power
Limits
Whole Building
Additional Allowances
+
Efficiency
Space-by-Space
Exemptions
Exterior Lighting
Power Limits +
Total Connected
Power
Interior Lighting Power
Allowance <
OR
Tradable
Non-Tradable
Total Connected
Power
Exterior Lighting Power
Allowance <
116
Luminaire Wattage
• Standard incandescent = max. labeled wattage of the luminaire • Luminaires with ballasts or transformers = wattage of the
maximum lamp/ballast combination OR max. labeled wattage of the luminaire
• Line voltage track = actual wattage with a min. 30 W per foot OR wattage limit of system’s circuit breaker OR wattage limit of other permanent-current-limiting device(s) on the system
• Low voltage track = transformer wattage • All others as specified on equipment
117
Mandatory: Individual Space Control
At least one for each room or space enclosed by ceiling-height partitions in spaces ≤ 10,000 ft2, each
control serves 2500 ft2 maximum and in spaces > 10,000 ft2, serves 10,000 ft2 maximum
Readily accessible to occupants Remote location is allowed to
accommodate areas where safety or security is a concern
118
Mandatory: Additional Space Controls
Hotel/motel guest room lighting must
be controlled at room entry
Occupancy sensors are required in: Classrooms (except shop, lab, K-12) Conference/meeting rooms Employee lunch/break rooms
119
Mandatory: Individual Space Control
Additional control required for: Display/accent lighting Case lighting Task lighting Nonvisual lighting Demonstration lighting
120
Mandatory: Automatic Shutoff
Automatic lighting shutoff control device required in all buildings larger than 5,000 ft2 Override of automatic shutoff required for
not more than 4 hours Exceptions to automatic shutoff: Lighting for 24-hour operation Patient care spaces Areas with safety or security concerns
• Exception to 9.4.1.2a: Classrooms, conference/meeting rooms, and employee lunch and break rooms with bi-level switching.
121
Mandatory: Automatic Shutoff • 9.4.1.2.1 Additional controls. Each area that is required to
have a manual control shall have additional controls that meet the requirements of Sections 9.4.1.2.2.2 and 9.4.1.2.2.3.
• 9.4.1.2.2 Light reduction controls. Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern by at least 50 percent. Lighting reduction shall be achieved by one of the following or other approved method:
• a. Controlling all lamps or luminaires; • b. Dual switching of alternate rows of luminaires, alternate
luminaires or alternate lamps;
122
Mandatory: Automatic Shutoff • c. Switching the middle lamp luminaires independently of
the outer lamps; or • d. Switching each luminaire or each lamp. • Exceptions: • a. Areas that have only one luminaire. • b. Areas that are controlled by an occupant-sensing device. • c. Corridors, storerooms, restrooms or public lobbies. • d. Sleeping unit (see Section 505.2.3). • d. Spaces that use less than 0.6 watts per square foot (6.5
W/m2). • 9.4.1.2.3 Automatic lighting shutoff. Buildings larger than
5,000 square feet (465m2) shall be equipped with an automatic control device to shut off lighting in those areas.
123
Mandatory: Automatic Shutoff • This automatic control device shall function on either: • a. A scheduled basis, using time-of-day, with an
independent program schedule that controls the • interior lighting in areas that do not exceed 25,000 ft2 and
are not more than one floor; or • b. An occupant sensor that shall turn lighting off within 30
minutes of an occupant leaving a space; or • c. A signal from another control or alarm system that
indicates the area is unoccupied. • Exception: The following shall not require an automatic
control device: • a. Sleeping unit (see Section 505.2.3).
124
Mandatory: Automatic Shutoff • b. Lighting in spaces where patient care is directly
provided. • c. Spaces where an automatic shutoff would endanger
occupant safety or security. • 9.4.1.2.4 Occupant override. Where an automatic time
switch control device is installed • to comply with Section 9.4.1.2.2.3, Item 1, it shall
incorporate an override switching device that: • a. Is readily accessible. • b. Is located so that a person using the device can see the
lights or the area controlled by that switch, or • so that the area being lit is annunciated. • c. Is manually operated.
125
Mandatory: Automatic Shutoff • d. Allows the lighting to remain on for no more than 2
hours when an override is initiated. • e. Controls an area not exceeding 5,000 square feet (465
m2). • Exceptions: • a. In malls and arcades, auditoriums, single-tenant retail
spaces, industrial facilities and arenas, • where captive-key override is utilized, override time shall
be permitted to exceed 2 hours. • b. In malls and arcades, auditoriums, single-tenant retail
spaces, industrial facilities and arenas, the • area controlled shall not exceed 20,000 square feet (1860
m2).
126
Mandatory: Automatic Shutoff • 9.4.1.2.5 Holiday scheduling. If an automatic time switch
control device is installed in • accordance with Section 505.2.2.2, Item 1, it shall
incorporate an automatic holiday scheduling feature • that turns off all loads for at least 24 hours, then resumes
the normally scheduled operation. • Exception: Retail stores and associated malls, restaurants,
grocery stores, places of religious worship and • theaters. • 9.4.1.2.6 Daylight zone control. Daylight zones, as defined
by this code, shall be provided • with individual controls that control the lights independent
of general area lighting. Contiguous daylight
127
Mandatory: Automatic Shutoff • zones adjacent to vertical fenestration are allowed to be
controlled by a single controlling device provided • that they do not include zones facing more than two
adjacent cardinal orientations (i.e., north, east, south, • west). Daylight zones under skylights more than 15 feet
(4572 mm) from the perimeter shall be controlled • separately from daylight zones adjacent to vertical
fenestration. • 34 • Exception: Daylight spaces enclosed by walls or ceiling
height partitions and containing two or fewer • light fixtures are not required to have a separate switch for
general area lighting.
128
Mandatory: Automatic Shutoff • 9.4.1.2.7 Sleeping unit controls. Sleeping units in hotels,
motels, boarding houses or • similar buildings shall have at least one master switch at
the main entry door that controls all permanently • wired luminaires and switched receptacles, except those in
the bathroom(s). Suites shall have a control • meeting these requirements at the entry to each room or at
the primary entry to the suite.
129
Automatic Shutoff – Compliance options: – Control lights on a scheduled basis
(automatic time switch) • Time-of-day controller • Controls ≤ 25,000 ft2 and not more
than one floor – Occupant sensor
• Turn lights off within 30 minutes of occupant leaving the space
– Signal from another control or alarm that indicates the area is unoccupied
130
Application of Automatic Shutoff
Intent is to apply to business entities or structures where whole building control is practical
Example application:
– Strip mall – individual business unit
131
Exterior Lighting Control • For dusk-to-dawn lighting: astronomical time
switch or photosensor • For all other: astronomical time switch OR
photosensor + time switch [REVISED!] • All time switches must have 10 hour battery
backup • Exceptions:
– Covered vehicle entrances – Exits from buildings or parking structures – (where required for safety, security, or eye
adaptation)
132
Additional Control
• Many special lighting applications must be controlled separately – Display/accent lighting – Case lighting – Hotel/motel guest room lighting – Task lighting – Nonvisual lighting – Demonstration lighting
134
Tandem Wiring Exceptions
• Separated surface or pendant luminaires • Recessed luminaires more than 10 ft apart • Other luminaires
– With three-lamp ballasts – On emergency lighting circuits – With no available pair – With one lamp, high frequency, electronic ballast
136
Exterior Lighting Power Building grounds lighting luminaires over 100
watts must have lamp efficacy of at least 60 lumen/Watt Exterior Building Lighting Power must meet
prescribed wattage limits. Exterior applications divided into 2 categories: Tradable: allowed wattage may be traded among these applications Non-Tradable: allowed wattage cannot be traded
between surfaces or with other exterior lighting
137
Efficacy
• The ratio of light output to watts input – lumens per watt
• The higher the efficacy, the more efficient the light source – 40 watt incandescent = 480 lumens – 40 watt fluorescent = 2640 lumens
139
Exterior Building Lighting Power
• The total exterior lighting power allowance is the sum of the individual lighting power densities [LPD]….
• ….plus an additional unrestricted allowance of 5% of that sum. Trade-offs are allowed only among “Tradable Surfaces” applications.
• Some exemptions apply
140
Exterior Building Lighting Power
• Lighting used for the following exterior applications is exempt when equipped with a control device independent of the control of the nonexempt lighting:
– specialized signal, directional, and marker lighting associated with transportation; – lighting that is integral to advertising signage or directional signage; – lighting that is integral to equipment or instrumentation and is installed by its
manufacturer; – lighting for theatrical purposes, including performance, stage, film, and video
production; – lighting for athletic playing areas; – temporary lighting; – lighting for industrial production, material handling, transportation sites, and
associated storage areas; – theme elements in theme/amusement parks; – lighting used to highlight features of public monuments and registered historic
landmark structures or buildings.
141
Exterior LPDs: 90.1-2007
Applications Lighting Power Densities
Tradable Surfaces (Lighting Power Densities for open parking areas, building grounds, building entrances and exits, canopies and overhangs, and outdoor sales areas may be traded)
Uncovered Parking Areas
Parking lots and drives 0.15 W/ft2
Building Grounds
Walkways less than 10 feet wide 1.0 W/linear foot
Walkways 10 feet wide or greater, Plaza areas and Special feature areas
0.2 W/ft2
Stairways 1.0 W/ft2
142
Exterior LPDs: 90.1-2007 Applications Lighting Power Densities
More Tradable Surfaces…
Building Entrances and Exits
Main entries 30 W/linear foot of door width
Other doors 20 W/linear foot of door width
Canopies and Overhangs
Canopies (free standing & attached) and overhangs 1.25 W/ft2
Outdoor Sales
Open areas (including vehicle sales lots) 0.5 W/ft2
Street frontage for vehicle sales lots in addition to “open area” allowance
20 W/linear foot
143
Exterior LPDs: 90.1-2007 Applications Lighting Power Densities Non-Tradable Surfaces (Lighting Power Density calculations for the following applications can only be used for the specific application and cannot be traded between surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the Tradable Surfaces section of this table.)
Building facades 0.2 W/ft2 for each illuminated wall or surface or 5.0 W/linear foot for each illuminated wall or surface length
Automated teller machines & night depositories 270 W per location plus 90 watts per additional ATM per location
Entrances and gatehouse inspection stations at guarded facilities
1.25 W/ft2 of uncovered area (covered areas are included in the Canopies and Overhangs section of Tradable Surfaces)
144
Exterior LPDs: 90.1-2007
Applications Lighting Power Densities
Non-Tradable Surfaces
Loading areas for law enforcement, fire, ambulance and other emergency service vehicles
0.5 W/ft2 of uncovered area (covered areas are included in the Canopies and Overhangs section of Tradable Surfaces)
Drive-up windows at fast food restaurants 400 W per drive through
Parking near 24-hour retail entrances 800 W per main entry
145
Interior Lighting Power
• Lots of exemptions • Calculation methods
– Building area – Space-by-space – Trade-offs of interior lighting power allowance
among portions of the building for which a different calculation method has been used is not permitted
146
Lighting Power Allowance Exemptions
• Theatrical, stage, film, and video production
• Medical and dental procedures • Exhibit displays for museums,
monuments, and galleries • Plant growth or maintenance • Integral to equipment or
instrumentation installed by manufacturer
• Integral to both open and glass-enclosed refrigerator and freezer cases
• Retail display windows, provided the display is enclosed by ceiling-height partitions
• Food warming and food preparation equipment
• Interior spaces specifically designated as registered interior historic landmarks
• Integral part of advertising or directional signage
• Exit signs • Sale or lighting educational
demonstration systems • Lighting for television broadcasting in
sporting activity areas • Casino gaming areas • Furniture-mounted supplemental task
lighting controlled by automatic shutoff and complying with 9.4.1.4(d)
• For use in areas specifically designed for occupants with special needs
148
Building Area Method of Calculating Interior
Lighting Power Allowance
• Used for projects involving – An entire building – A single, independent, and separate occupancy in a multi-occupancy
building • Gross lighted area is multiplied by allowance from Table
9.5.1 • Limitations
– Insensitive to specific space functions and room configurations – Generally is more restrictive – Does not apply to all building types - but “selection of a reasonably
equivalent type” is permitted
149
Gross Lighted Area
• Sum of total lighted area of a building – Measured from the exterior faces
of the exterior walls or from the centerline of walls separating buildings, but excluding a long list of areas. (See Standard).
• Used in the building area method of determining interior lighting power allowance
150
Building Area Allowances
• Table 9.5.1
• • •
• • •
1.0 Exercise Center 1.0 Dormitory 1.6 Dining: Family 1.4 Dining: Cafeteria/Fast Food 1.3 Dining: Bar Lounge/Leisure 1.2 Court House 1.2 Convention Center 0.9 Automotive Facility
Lighting Power Density (W/ft2) Building Type
151
Space-by-Space Method of Calculating Interior
Lighting Power Allowance
• Identify different building types in your project • Divide gross lighted area of the building into each of the
space types • Calculate lighting power allowance by multiplying area
of space type by lighting power density for that specific space type
• Sum all the allowances • Advantages
– More flexible – Applicable to all building types – Accounts for room geometry (e.g., lighting needs of enclosed
office vs. open office)
152
Additional Interior Lighting Power
• An increase in the ILPA is allowed for specific space functions when using the space-by-space method. Applications must be automatically controlled, separately from the general lighting, to be turned off during non-business hours – Decorative in addition to general lighting – 1.0
W/ft2 in space used – Retail display lighting
153
Retail Display Lighting Additional Interior Lighting Power Allowance = 1000 watts + (Retail Area 1 x 1.0 W/ft2) + (Retail Area 2 x 1.7 W/ft2) + (Retail Area 3 x 2.6 W/ft2) + (Retail Area 4 x 4.2 W/ft2),
Where: Retail Area 1 = the floor area for all products not listed in Retail Area 2, 3 or 4. Retail Area 2 = the floor area used for the sale of vehicles, sporting goods and small
electronics. Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics and
artwork. Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china. Exception: Other merchandise categories may be included in Retail Areas 2
through 4 above, provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction.
155
Mandatory Provisions (required for most
compliance options)
Building System Compliance Options
Energy Code Compliance
Prescriptive Option
Energy Cost Budget
Trade Off Option
Simplified
Envelope
HVAC
Lighting
SWH
Power
Other Compliance
Other
156
Section 10 - Other Equipment
• Motor efficiency levels correspond to Energy Policy Act of 1992 manufacturing standards
• Mandatory provisions are for General Purpose Design A and Design B motors only
• Motors in new buildings, additions to existing buildings, and alterations to existing buildings must comply – Relocated or reused existing motors do not have to meet these
requirements • No small building option, no prescriptive compliance path,
no alternative compliance paths, no submittals
157
Section 11 - Energy Cost Budget Method
• The ultimate trade-off method allowing you to trade-off across building systems through the use of annual, hourly simulation tools and a baseline building
• The only real way to deal with unique designs, renewables, high-efficiency equipment, etc.
• The basis of the energy portion of the LEED rating
• Limits allowable energy costs of the design to those of a building meeting the Standard
• Buildings must still meet all mandatory requirements (Section X.4)
158
Section 11 - Energy Cost Budget Method
• Tradeoff limited to building permit • You have to have an approved building
envelope design prior to ECB submittal • You must meet all the X.4 sections AND
the design energy cost cannot exceed the energy cost budget AND the energy efficiency level of components must meet or exceed the levels used to calculate the design energy cost
• You must document all this in great detail
159
Section 11 - Energy Cost Budget Method
• Use a good and approved simulation program
• Use appropriate and approved climate data • Use appropriate and approved purchased
energy rates • Use the same simulation program, climate
data, and purchased energy rates for both the design energy cost and energy cost budget
• Get approval to deal with exceptional calculations that aren’t covered in the simulation program
160
Section 11 - Energy Cost Budget Method
• Develop your proposed building design and budget building design in accordance with Table 11.3.1 – This table “locks down” a number of building
design parameters • Choose your budget building HVAC system
from Figure 11.3.2 and Table 11.3.2A
161
Section 11 - Energy Cost Budget Method
• If you are attempting to show that your building goes “above code” (say, for instance, for LEED energy points) as opposed to simply using ECB as a very flexible and complex code compliance tradeoff option, – be sure to see Informative Appendix G, which
contains many of the same elements as Section 11, but with modifications to accommodate the needs of “above code” programs
162
Section 12 - Normative References
• Normative (read “mandatory”) reference documents
• Includes test methods, rating procedures, and other standards
163
Rated R-Value of Insulation and Assembly U-Factor, C-Factor, and F-Factor Determinations
• Includes pre-calculated U-factors, C-factors, and F-factors – Above-grade walls – Below-grade walls – Floors – Slab-on-grade floors – Opaque doors – Fenestration
164
Building Envelope Climate Criteria
• Defines which of the envelope criteria tables (Tables 5.5-X) to use for your location
• General • Climate Zone Map • U.S. Climate Zones (by County) • Canadian Climatic Zones (by City) • International Climate Zone (by City)
• Major Climate Type Definitions (for use with non-U.S. locations)
165
Methodology for Building Envelope Trade-Off Option in Subsection 5.6
• The details of how the envelope trade-off option referenced in Section 5.6 is implemented
• This methodology is implemented in the ENVSTD software distributed with the 90.1 Users Manual
166
Climate Data
• Climatic data for a number of US, Canadian, and international locations – HDD65 and CDD50 – Heating and cooling design temperatures – “number of hours between 8 am and 4 pm with
Tdb between 55 and 69” • Used exclusively for HVAC calculations
167
Informative References
• Other useful references that are not mandatory, but are useful as examples for the user of Standard 90.1-2007
• In general, these are not consensus documents so ASHRAE procedures do not allow them to be mandatory references
168
Addenda Description Information
• Information on addenda to ANSI/ASHRAE/IENSA Standard 90.1-2004 (the predecessor to Standard 90.1-2007)
• ASHRAE issued 44 addenda to Standard 90.1-2004
• Standard 90.1-2004 plus these addenda forms the basis of Standard 90.1-2007
169
Performance Rating Method
• Instructions for using the ANSI/ASHRAE/IESNA Standard 90.1-2007 Energy Cost Budget Method in conjunction with the U.S. Green Buildings Council (USGBC) Leadership in Energy and Environmental Design (LEED) program
172
Economizers
• Climate and size dependent (Table 6.5.1) • There are LOTS of exceptions • Can use air economizers
– 100% of design supply air – Sequenced with mechanical cooling equipment – High limit shutoff – Dampers
• Can use water economizers – 100% of expected system cooling load at 50°F DB, 45°F WB – Maximum pressure drop limitation
173
Economizer Exceptions • Exceptions:
• Cooling capacity - Table 6.5.1 • Systems with gas phase air cleaning per Standard
62 • Where >25% of the air must be humidified
>35°Fdp • Systems with condenser heat recovery per 6.5.6.2 • Residential systems <5X limits in Table 6.5.1 • Systems with a balance point <=60°F • Systems expected to operate < 20hrs/wk • Systems serving zones with refrigerated casework • Where cooling efficiency exceeds Table 6 3 2
174
Cooling capacity for which an economizer is required
Economizers (Table 6.5.1)
Climate zone
1a, 1b, 2a, 3a, 4a Economizer unnecessary (Miami, St. Louis, Charlotte)
2b, 5a, 6a, 7, 8 ≥ 135,000 Btu/h (Yuma, Chicago, Edmonton)
3b, 3c, 4b, 4c, 5b, 5c, 6b ≥ 65,000 Btu/h (Denver, Lubbock, Vancouver)
175
Design Capacity – Air Economizers
• System capable of modulating outside air and return air dampers to provide up to 100% of the design supply air quantity as outside air for cooling
176
Control Signal
• Dampers capable of being sequenced with the mechanical cooling equipment and shall not be controlled by only mixed air temperature
• Exception – Systems controlled from space temperature (such
as single-zone systems)
177
High Limit Shutoff
• Automatically reduce outdoor air intake to minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage
• Control types for specific climates from Table 6.5.1.1.3A
• Settings from Table 6.5.1.1.3B
179
Relief of Excess Outside Air
• Means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building
• Outlet located to avoid recirculation into the building
180
Design Capacity – Water Economizers
• System capable of cooling supply air by indirect evaporation and providing up to 100% of expected system cooling load at outside air temperatures of 50°F dry bulb/45°F wet bulb and below
• Exception – You can also meet this requirement if your design
can meet 100% of expected cooling load at 45°F dry bulb/40°F wet bulb
181
Maximum Pressure Drop
• Precooling coils and water-to-water heat exchangers to have either – Water-side
pressure drop of < 15 ft of water OR
– Bypassed when not in use
Condenser
Chiller
Evaporator
OutOut
In
In
CoolingTower
CWP
PrimaryCHWP Secondary
CHWPWith
VariableSpeed Drive
HeadPressureControlValve
Economizer CWP
HeatExchanger
CHWS CHWR
TypicalCoolingCoil
CoolingCoilWithTertiaryPump
ValveClosesInEconomizerMode
2-WayValve
Figure 6-O from 90.1 User’s Manual
182
Integrated Economizer Control
• Economizers must be integrated with mechanical cooling systems and be capable of providing partial cooling even when additional mechanical cooling is required
• Some exceptions to this