2016 ashrae 90.1 summary of important changes ashrae 90.1 i… · · 2017-08-242 overview...
TRANSCRIPT
1
2016 ASHRAE 90.1
Summary of Important Changes
2
Overview
ANSI/ASHRAE/IES Standard 90.1-2016, Energy Efficiency Standard for Buildings Except Low-Rise Residential Buildings,
incorporates more than 120 updates to the 2013 version of the standard. During its development, BOMA International’s codes
team worked to ensure the interests and concerns of the commercial real estate industry were heard and that the updates
would maximize energy efficiency without excessively increasing cost. The new edition is estimated to provide an 8.3 percent
increase in energy savings over the 2013 edition (PNNL modeling results).
To help commercial building owners and managers better understand the changes that were made, BOMA International has
compiled the following list of critical changes and their cost implications. Changes are organized by section number in the
standard. Some significant changes include:
• Building Thermal Envelope: Though very few modifications were made to the building thermal envelope, the insulation
requirements for metal buildings, doors and windows have been increased.
• Mechanical Systems: Major changes to mechanical system requirements include more stringent efficiency
requirements for energy recovery systems. Although not yet mandated, dedicated outdoor air system (DOAS) efficiency
and rating requirements are now included if such a system is used, and there is a new metering requirement for chilled
water plants.
• Power and Lighting: With the significant reduction in cost and increased usage of LED lighting, both exterior and interior
lighting allowances have been reduced to reflect the lower power consumption of LEDs. New control requirements were
added for emergency lighting and parking lot occupancy sensors. Hotel/motel guest room controls were expanded, and
the standard now regulates lighting in dwelling units within commercial buildings.
• Alternate Compliance Path: Appendix G, previously only used to rate LEED buildings, is now able to be used as a stand-
alone compliance path, offering more options to designers.
Although every effort has been made to ensure that the summary overviews all changes within the body of the standard,
developers and designers need to consult the 2016 edition of ASHRAE 90.1 to determine how changes may impact a specific
project.
3
Section(s) and
Issue(s)
Type of
Change
Cost
Implication
Comments
Table 3.2, Heated
Space Criteria
Revision Increase The heating output threshold (in BTU/h-ft2) has been reduced in all
climate zones except for CZs 1 & 2. Criteria for CZ 0 has been added,
areas of which previously fell into CZ 1.
CZ 2013 2016
0 n/a 5
1 5
2 5
3A; 3B 10 9
3C 10 7
4A; 4B 15 10
4C 15 8
5 15 12
6 20 14
7 20 16
8 25 19
4.2.4 Inspections Revision Unknown The list of items for inspection have been deleted. Inspection
procedures are now to be specified by the Building Official.
4.2.5 Verification and
Commissioning
Reporting
4.2.5.1
Nonconformance
New Sections Increase The new section specifies reporting requirements for conformance and
nonconformance inspection findings to the building official and outlines
the documentation requirements through correction.
4
5.1.2.3, Space
Conditioning
Categories
(Exception)
Revision Increase Approval is required from the Building Official in all CZs for a space to
be designated as semiheated or unconditioned. Previously, Climate
Zones 1 & 2 did not require approval.
5.1.4.1, Climate -
United States
Locations
5.1.4.2, Climate -
International
Locations
Revision None The Code User is referred to ASHRAE Standard 169 to determine
climate zones. U.S., Canada and international climate zone tables from
Standard 169 have been reproduced in Annex 1.
Section 5.2.1
Compliance
New Section Increase Section 5.9, Inspection and Verification, is now mandatory.
5.4.3.1.3, Testing,
Acceptable Materials,
and Assemblies
New Section None A whole building pressurization test (0.40 cfm/ft2) has been added as
an alternative compliance option to the material and assembly air
barrier specifications. Exceptions permit buildings over 50,000 ft2 to
take representative sections for testing. Another exception permits the
use of a diagnostic evaluation (e.g., smoke tracing or IR imaging) if the
leakage rate exceeds 0.40 but not 0.60 cfm/ft2.
5.4.3.1.3 Testing,
Acceptable Materials,
and Assemblies
Revision Decrease Single-ply roof membrane no longer has to be fully adhered to be
deemed an air barrier.
5.4.3.2 Fenestration
and Doors
Revision Increase Glazed power-operated sliding and folding entrance doors have been
included in the air leakage requirements for glazed swinging entrance
doors (1.0 cfm/ft2).
Exception to 5.4.3.2 Revision Increase Metal coiling doors in semiheated spaces in CZs 6 and under are no
longer fully exempt from the air leakage requirements. The new
minimum threshold set is 1.0 cfm/ft2.
5
Table 5.5-0 Building
Envelope
Requirements for
Climate Zone 0 (A,B)*
New Increase The insulation requirements in new Climate Zone 0 have been set at a
level higher than what had been permitted for buildings in these
locations when they fell into Climate Zone 1.
Tables 5.5-1 through
8, Building Envelope
Requirements for
Climate Zones 1 – 8
Revision Increase The insulation requirements were made more stringent for metal
building roofs and walls, fenestration and opaque doors.
5.5.3.6 Opaque Doors
(Exceptions)
New Exceptions Decrease Nonswinging, horizontally hinged sectional doors with a single row of
fenestration (between 14% and 25% of total door area) are permitted
an increased u-factor.
5.5.4.1 General
(Fenestration)
New Exception
#2
Decrease Clarifies how area-weight averaging of vertical fenestration U-factor,
SHGC, VT/SHGC, or LSG are permitted.
5.5.4.4.1 SHGC of
Vertical Fenestration
Table 5.5.4.4.1 SHGC
Multipliers for
Permanent Projections
Revision to
Exceptions
Increase Exceptions to the SHGC requirements where permanent shading
devices are used have been rewritten (Exceptions 1 & 2). Table
5.5.4.4.1 no longer includes a column for multipliers for North-facing
fenestration.
Exception 5 no longer permits north-oriented fenestration to have a
SHGC 0.05 greater than that specified in Tables 5.5.1 – 5.5.8. The
exception now permits north-oriented fenestration to have an SHGC
equal to or less than the area-weighted average SHGC of fenestration in
the S, E and W orientations before reductions are made for the
permanent projections in exceptions 1 & 2.
5.5.4.5 Fenestration
Orientation
New equation
for CZs 4-8
Deleted
Exception
Increase When SHGCs are factored into the fenestration orientation (Option B),
the fenestration area on the E and W facades in CZs 4-8 are further
limited.
Deleted Exception 2, which exempts buildings from the vertical
fenestration orientation requirements where there is existing
permanent infrastructure to the south.
6
5.8.2.3 U-Factor
(Fenestration & Door
Products)
Clarification
Minor
None Exception 4, which permits labeling in accordance with
ANSI/DASMA105, clarifies “garage doors” as “sectional garage doors
and metal coiling doors.”
5.9 Inspection and
Verification
New Sections Increase New Section 5.9.1, Inspections, specifies components to be inspected,
including fenestration & doors, loading dock weatherseals, and the
opaque building envelope.
New subsection 5.9.2.2, Air Leakage Verification, specifies periodic
inspection and reporting requirements or the option of a whole-building
air leakage test.
6.3.2 Criteria
(Simplified Approach
Option for HVAC
Systems)
Revision Increase Criteria d has added Section 6.4.3.12, Economizer Fault Detection and
Diagnostics, as mandatory requirement for air economizers.
New Criteria k was added, which requires systems serving hotel/motel
guest rooms to comply with new Section 6.4.3.3.5, Automatic Control of
HVAC in Hotel/Motel Guest Rooms.
Criteria r has added the ventilation design requirements of Section
6.5.3.7.
6.4.1.2.1 Water-
Cooled Centrifugal
Chilling Packages
Revision None Design conditions were modified based on AHRI Standard 550/590
test conditions.
When 550/590 test conditions are not the basis of design, a maximum
evaporating leaving temperature of 60 °F is specified for the given
equations to be applicable.
Example (Section
6.4.1.2.1)
Correction/
Clarification
None Calculations were modified slightly for clarification and to correct
significant digits.
7
6.4.3.3.5 Automatic
Control of HVAC in
Hotel/Motel
Guest Rooms
New Section Increase New section and subsections specifying the automatic controls for
HVAC equipment required in hotels and motels with greater than 50
guest rooms. Requirements include temperature setbacks and the
discontinuation of outdoor air ventilation during unoccupied periods.
Captive key card systems may be used to comply (subsection
6.4.3.3.5.2).
6.4.3.9 Heated or
Cooled Heating in
Vestibules
Revision
New Exception
None The section now limits cooling in vestibules to a minimum of 85 °F. The
existing exception is still valid for vestibules tempered with transfer air,
and an exemption for systems where the heating or cooling is provided
by site-recovered energy have been added.
6.4.3.11 Chilled-Water
Plant Monitoring
New Section Increase New electric-motor-driven chilled-water plants greater than specified
thresholds are required to have a monitoring system to measure the
energy use and efficiency, have a graphically displayed recording and
reporting system and include economizer fault detection & diagnostics
(where an economizer is provided).
Size Thresholds
1000 tons (1500 tons in CZs 3C, 4C, & 5-8) for water-cooled
plants
570 tons (860 tons in CZs 3C, 4C, & 5-8) for water-cooled plants
6.5.1 Economizers Revision Decrease The section now applies to all cooling systems regardless of whether or
not they have a fan. A new exception (#2) has been added to exempt
chilled water cooling systems without a fan that use induced airflow
with total system capacities less than certain thresholds (1MM Btu/h in
CZ 0-4 & 1.4MM Btu/h in CZs 5-8). Systems in CZ 1A are fully exempt
regardless of size.
Table 6.5.1-1
Minimum Fan-Cooling
Unit Size for which an
Economizer Is
Required
Revision Increase Table 6.5.1-1 was previously only for comfort cooling but now applies to
cooling for computer rooms, too.
Previous Table 6.5.1-2, which specified the size threshold for fan-
cooling units serving computer rooms that required economizers, was
deleted. CZs 2a, 3a and 4a had previously been exempt from
8
economizer requirements, and the threshold for other CZs were greater
than what is now permitted by Table 6.5.1.1, under which they are now
governed.
6.5.2.1 Zone Controls
(for Simultaneous
Heating and Cooling
Limitations)
New
Equipment
Covered in
Exception
Decrease An exception for systems with DDC has been added where the volume
of air that is reheated, recooled or mixed is less than 20% of the zone
design peak supply. (Other systems remain at 30%.)
6.5.2.6 Ventilation Air
Heating Control
New Section Increase New requirement for units that provide ventilation air to multiple zones
and operate in conjunction with zone heating and cooling systems
stating that they may not use heating or heat recovery to warm supply
air above 60°F when representative building loads or outdoor air
temperature indicate that the majority of zones require cooling.
6.5.3.1.2 Motor
Nameplate
Horsepower
New Exception Decrease New exception #4 to the maximum selected fan motor size is for fans
with a motor nameplate horsepower of less than 1.
Table 6.5.3.1-2 Fan
Power Limitation
Pressure Drop
Adjustment
Revision None The first line, which provides the drop adjustment for fully ducted return
and/or exhaust air, is now only applicable when the exhaust systems
are required by code to be fully ducted. Systems required to maintain
air pressure differentials between adjacent rooms are also provided
with the same adjustment credit.
6.5.3.2.3 VAV Set-
Point Reset
Revision Decrease Clarification was added that this requirement is for multiple-zone VAV
systems. The requirements now only apply to systems with a total fan
system motor nameplate rating exceeding 5 hp.
6.5.3.2.4 Return and
Relief Fan Control
New Section Increase New section adds control requirements for the relief of excess air when
it is required by Section 6.5.1.1.5 during air economizer operation.
Exceptions exist for fans ≤ 0.5 hp and for staged relief fans.
6.5.3.4 Parallel-Flow
Fan-Powered VAV Air
Terminal Control
New Section Increase The new section adds new automatic control requirements for parallel-
flow fan-powered VAV air terminals.
9
6.5.3.7 Ventilation
Design
New Section Increase The new section provides two options to limit the design minimum
system outdoor air (design or with dampers) or requires exhaust air
energy recovery.
6.5.4.2 Hydronic
Variable Flow Systems
Table 6.5.4.2 Pump
Flow Control
Requirements
Revision
New Table
6.5.4.2
Increase ▪ The nomenclature was changed from “HVAC pumping systems” to
“chilled- and hot-water distribution systems”
▪ The threshold for applicability is no longer a pump system power
exceeding 10 hp
▪ The exception for systems with fewer than three control valves was
moved into the main paragraph.
▪ Variable fluid flow must be capable of reducing flowrates to 25% or
less of the design flowrate or minimum required (previously 50%).
▪ Refers the user to new Table 6.5.4.2 for the motor nameplate hp
rating threshold by climate zone that require controls that will result
in pump motor demand of no more than 30% of design wattage at
50% of design water flow.
▪ The two existing exceptions were moved into the main paragraph,
and five new exceptions were added for a number of specific
systems.
6.5.4.4, Chilled- and
Hot-Water
Temperature Reset
Controls
Revision
New Exceptions
Deleted
Exceptions
Increase ▪ Separate setpoint resets are specified for DDC control valves.
▪ Three new exceptions were added for thermal energy storage
systems, process equipment, and for boiler turn-down.
▪ The existing two exceptions for hydronic systems and infeasibility
were deleted.
6.5.4.7, Chilled-Water
Coil Selection
New Section Increase The new section requires chilled-water cooling coils to provide a 15 °F
or higher temperature difference between leaving and entering water
temperatures and a minimum of 57 °F leaving water temperature at
design conditions. Seven exceptions exist for specific equipment.
6.5.5.2, Fan Speed
Control
Revision Increase ▪ The section has been clarified that it applies to fans on heat-
rejection devices.
▪ The threshold of applicability was lowered from 7.5 hp to 5 hp.
10
▪ Control requirements were changed from requiring the fan speed to
be lowered by 33% to a specified power demand (30% of design
wattage) at 50% airflow.
▪ CZs 1 & 2 are no longer exempt.
Table 6.5.6.1-1
Exhaust Air Energy
Recovery
Requirements
for Ventilation
Systems Operating
Less than 8000 Hours
per Year
Table 6.5.6.1-2
Exhaust Air Energy
Recovery
Requirements
for Ventilation
Systems Operating
Greater than or Equal
to 8000 Hours per
Year
Revision Decrease Design supply airflow rates have been increased for a number of
climate zones and percent-outdoor-air combinations. This permits
smaller exhaust systems to be designed and installed without energy
recovery.
6.5.7.1 Transfer Air Revision Increase ▪ The section scope has been expanded from kitchen hood makeup
air to cover any makeup air. The list of maximum air supply that is
permitted has been slightly modified by referring to external sources.
Available transfer air is now calculated from conditioned space
within 15 feet as opposed to “adjacent spaces.”
▪ Four exceptions were added for laboratories, vivariums, spaces
required to maintain positive pressure, and for spaces with a
required negative pressure relationship.
Table 6.6.1 Power
Usage Effectiveness
(PUE) Maximum
Revision Decrease Maximum PUEs for CZs 0A & 0B have been added to the table. They
are slightly higher than those permitted by CZs 1A & 1B.
11
Tables 6.8.1-1 through
6.8.1-13
(Mechanical Efficiency
Requirements)
Revision
minor
None Efficiencies for obsolete effective dates have been removed.
Footnotes that previously referred to NAECA now refer to 10 CFR 430.
An informative note directs the code user to Appendix F for federal
minimum efficiencies of single-phase air conditioners.
Table 6.8.1-14,
“Vapor-Compression-
Based Indoor Pool
Dehumidifiers—
Minimum Efficiency
Requirements”
Table 6.8.1-15,
“Electrically Operated
DX-DOAS Units, Single-
Package and Remote
Condenser, without
Energy Recovery—
Minimum Efficiency
Requirements”
Table 6.8.1-16,
“Electrically Operated
DX-DOAS Units, Single-
Package and Remote
Condenser, with
Energy Recovery—
Minimum
Efficiency
Requirements”
New Tables Increase New efficiency tables have been added for indoor pool dehumidifiers
and dedicated outdoor air system (DOAS) units.
7.4.3, Service Hot-
Water Piping
Insulation
Revision Increase New requirement (c) requires the first 8 ft of branch piping connecting
to recirculated, heat-traced, or impedance heated piping to be
insulated.
12
Table 7.8,
Performance
Requirements for
Water-Heating
Equipment—Minimum
Efficiency
Requirements
Modifications None Performance requirements in the table that contain Energy Factors (EF)
have been deleted and instead refer the Code User to footnote (g),
which refers to 10 CFR 430.
8.4.1, Voltage Drop Revision Increase Feeder conductors and branch circuits combined now must be sized for
a 5% voltage drop total as opposed to a 2% and 3% drop, respectively.
Circuits dedicated to emergency services are no longer exempt.
8.4.3.2 Recording and
Reporting
Revision None Requires collected data to be transmitted to DDC controls, including
graphical display, in buildings with DDC controls (Section 6.4.3.10)
Table 8.4.4 Minimum
Nominal Efficiency
Levels for Low-Voltage
Dry-Type Distribution
Transformers
Revision Increase Minimum efficiencies for three-phase transformers have increased.
9.1.1, Scope (Lighting) Revision Decrease
Increase
▪ The scope of the chapter now only includes exterior lighting that is
powered through the building’s electrical service.
▪ Lighting within dwelling units is no longer exempt.
9.1.2, Lighting
Alterations
Revision Decrease Wording was modified for clarity to refer the Code User to specific
sections that are applicable to alterations. The exception was modified
to allow up to 20% of the lighting load (previously 10%) to undergo an
alteration before triggering code requirements. Two new exceptions
were added for maintenance/repair due to the deletion of the
exemptions from the main paragraph.
9.1.5 Climate New Section None Added for congruency with other sections—simply refers the Code User
to Section 5.1.4 to determine the Climate Zone.
13
Exception to 9.4.1.1(c)
(Interior Lighting
Controls)
New Exemption None Lighting in open-plan office spaces are permitted to turn on
automatically to more than 50% if controlled in zones no greater than
600 ft2. This permits the effective use of occupancy sensors.
9.4.1.1(e) (Interior
Lighting Controls)
Revision None Calibration adjustment for automatic sidelight daylight controls are no
longer required to be readily accessible but must be located within 11
ft. above the finished floor level and may not require the physical
presence of a person at the sensor.
9.4.1.1(e) & (f)
(Interior Lighting
Controls)
Revision None Calibration adjustment for automatic toplight and sidelight daylight
controls may not require the physical presence of a person at the
sensor.
Exception to 9.4.1.1(f)
(Interior Lighting
Controls)
Revision None Exception 2 to the required automatic controls under toplight daylight
zones is now dependent on a maximum effective aperture as opposed
to a maximum visual transmittance.
Exceptions to
9.4.1.1(g) and (i)
(Interior Lighting
Controls)
New Exceptions
#4 (in each
section)
None Lighting loads (in W) up to 2% of the gross area building area (in ft2) are
exempt from the automatic off (g) and scheduled off (i) requirements.
This permits emergency egress lighting to remain lit.
9.4.1.1(h) & (i)
(Interior Lighting
Controls)
Revision Increase Lighting connected to emergency circuits has been explicitly called out
as applicable to automatic full off (h) and scheduled shutoff (i) controls.
9.4.1.2, Parking
Garage Lighting
Control
Revision
Deleted
Exception
Increase ▪ The exception for daylight transition zones and ramps without
parking from the parking garage lighting control requirements has
been deleted.
▪ Requirement (d) for garage perimeter lighting controlled by
photosensors now specifies a minimum of 50% reduction in power
in response to daylight.
9.4.1.4, Exterior
Lighting Control
Modified Increase ▪ Requirement (c), which applies to lighting other than grounds and
façade lighting, including signage, must have controls that can
reduce lighting power by 50% (previously 30%).
▪ New requirement (d) was added to require motion sensors that
reduce parking lot lighting by 50% after 15 minutes of no activity.
14
The requirement is applicable to lighting greater than 78 W with a
mounting height ≤ 24 ft.
9.4.2, Exterior
Building Lighting
Power
New Exemption Decrease Exemption (1)(e) has been expanded to include public art displays as
exempt from the exterior lighting power requirements when equipped
with an independent control.
Table 9.4.2-2,
Individual Lighting
Power Allowances for
Building Exteriors
Revision Increase ▪ Lighting power allowances have been reduced throughout the table.
Lighting power allowances for main entries and other doors have
been combined as “pedestrian and vehicular entrances and exits.”
▪ The table now states “uncovered” entrances and loading areas to
make it clear that if they were covered, they would be within the
scope of the interior lighting requirements.
9.4.4, Dwelling Units New Section
with exemption
Increase New section requires at least 75% of lights within dwelling units to be
high-efficacy unless they are controlled with dimmers or automatic
controls.
9.6.2, Additional
Interior Lighting Power
Revision Increase ▪ The permitted increase in LPD for decorative lighting or lighting that
highlights art has been reduced from 1 W/ft2 to 0.75 W/ft2.
▪ The additional interior lighting power allowance for retail areas has
also been reduced by about 33%. The 1000 W base allowance has
not been reduced.
Tables 9.5.1 & 9.6.1,
Lighting Power Density
Allowances
Revision Increase Lighting power density allowances have been reduced by about 10% for
nearly all building area and space types
10.4.1, Electric Motors Revision None The section was modified to no longer refer to the Energy Independence
and Security Act of 2007 but instead to NEMA Design motors. Five
exceptions to the section’s requirements have been added for:
1. Air-over electric motors.
2. Component sets of an electric motor.
3. Liquid-cooled electric motors.
4. Submersible electric motors.
5. Inverter-only electric motors.
15
10.4.3.4, Design
Documents
New Section None The new section requires design documents to list the usage category
and energy efficiency class of elevators.
Normative Appendix A,
Rated R-Value of
Insulation and
Assembly U-Factor, C-
Factor, and F-Factor
Determinations
Revised None Appendix A provides pre-calculated heat transfer values for materials
and also provides methods for calculating those values. Major
modifications to the appendix include the following:
▪ Values for Section A3.2.2 were expanded for single-layer and
double-layer insulation in metal walls.
▪ Unlabeled insulated double-layer metal coiling doors were given a U-
factor of 1.00 in Section A7.1.
▪ For Metal Building U-Factor Equations, new section A9.4.6.3, Single-
Layer in Cavity and Double-Layer Walls, was added.
Appendix B, Building
Envelope Climate
Criteria
Deleted n/a Appendix B was deleted, however Annex 1 was added – Reference
Standard Reproduction Annex from ASHRAE 169.
Appendix C,
Methodology for
Building Envelope
Trade-Off Option in
Section 5.6
Revised None Appendix C provides simulation requirements when using the Building
Envelope Tradeoff Option in Section 5.6. Modifications to the appendix
include:
▪ Section C3.5.5.3, Air Leakage, was modified for clarity
▪ Required HVAC characteristics for electrically-provided cooling with
constant COP (b) and fans (f) have been modified (Section C3.5.8)
Appendix D
“Climatic Data”
Deleted n/a Appendix D was deleted, however Annex 1 was added – Reference
Standard Reproduction Annex from ASHRAE 169.
Informative Appendix
F, U.S. Department of
Energy Minimum
Energy Efficiency
Requirements
New Appendix None This new appendix provides the federal efficiency standards for
residential products, which are found in the U.S. Code of Federal
Regulations, 10 CFR Part 430 Subpart C, Section 430.32.
Normative Appendix
G, Performance Rating
Method
Revision None Appendix G now can be used as a path for compliance with the
standard in addition to being able to rate “beyond code” performance of
buildings. Other modifications to include: elevator, motor and
16
refrigeration baselines; changes to the baseline for existing building
projects; and specific opaque assemblies for the baseline envelope
model.
Table 4.2.1.1, Building Performance Factor (BPF)
The Performance Cost Index calculated using Appendix G is required to
be less than a Performance Cost Index Target. An equation is provided
to calculate the PCIt, which is a function of the baseline building energy
cost, the building use, and the climate zone.
4.2.1.3 Alterations of Existing Buildings
The option to utilize Appendix G is provided for additions and
alterations. Two exceptions have been deleted from alterations:
1. where the standard required compliance with a provision that results
in the increase in energy use (within Section 4.2.1.3)
2. The option to show that the entire altered building uses less annual
energy than a substantially identical design (previously exception 2 to
Section 4.2.1.3)
Annex 1 New None This annex reproduces ASHRAE Standard 169 Material so that climate
zones can be determined.