Xtralis VESDA VFT-15Sales and TechnicalSales and Technical Presentation
Extending the VESDA Range
The Xtralis VESDA VFT-15 is a unique and versatile high sensitivity ASD that can pinpoint the source of an incipient smoke incident
– Minimises business disruption and downtime
– Speeds response
– Enhances investigation
Two variants are available
– VFT-15 (0.01 – 20% Obs/m or 0.003 – 6.10% Obs/ft)
– VFT-15-C(1 – 20% Obs/m or 0.3 – 6.10% Obs/ft)
VESDA VFT-15 Value Proposition
The only ASD product available on today’s market to provide:
Pinpoint location of the source and location of an incipient smoke incident, therefore minimising investigation and downtime
Intelligent addressability to identify up 15 protected areas respectively via microbore air sampling tubesrespectively, via microbore air sampling tubes
High sensitivity ranging from 0.01 to 20 % obs/m (0.003 –6.10% obs/ft)
Optional CO gas sensor
The VFT-15 is complementary to the existing range and provides pinpoint addressability at a more compelling price than multiple VLS units with single hole pipes.
2
Product Positioning
Area
Sensitivity
400m2 800m2 1200m2 1600m2 2000m2
High
(EN54-20 Class A)
VFT-15
(VEW)
Enhanced
(EN54-20 Class B)
(EW)
Normal
(EN54-20 Class C)
VLPVLS
VLF250
VLF500
VLC
VFT-15-C
Matching Models With EnvironmentsEnvironment VLP VLS VLC VLF VFT-15
Aircraft Hangars x xAtria xAuditorium xCable Tunnels/Trays x x xCasinos x xClean Rooms x x x x xCold Rooms x xComputer Rooms x x x x xControl Rooms x x x x xDormitories x x xEDP Environments x x x x xElect/Switching Cabinets x x xElect/Switching Cabinets x x xEquipment Cabinets x x xHistorical Buildings x x x x xHospitals x x x x xHotels x x x x xLaboratories x x x x xLibraries/Archival Storage x x x xManufacturing Facilities x xMuseums/Art Galleries x x xOffices x x x xPrison cells x x x xSchools x xStorage Areas x x xSubstations x x xTelecommunications x x x x xTheatres x x
Transportation x x x
Site conditions and pipe network design will determine the final choice of detector.
Principle of Operation
Actively draws air from the protected area through a network of flexible pipes
Filters and conditions the air where necessary
Analyses the air for low levels of smoke
Id tifi th i hi h th Identifies the pipe on which the incident occurred
Sets alarms on four programmable thresholds
Reports the alarm via relay outputs or communication network
3
Detection Principle VFT
Sensitivity from 0.01% - 20% obs/m (0.003 – 6.10% obs/ft) for VFT-15 or 1% -20% obs/m (0.3 – 6.10% obs/ft) for VFT-15-C
A laser illuminates smoke particles in an optical chamber with 360 degree lightoptical chamber with 360 degree light guide collector
Unique field serviceable optical chamber separates optics from sampled air
Removable chamber includes particle filter
6 mm micro bore air sampling High or normal sensitivity laser
detection 15 pipes 50 m pipe length each pipe 4 Alarms - Alert, Action, Fire 1, Fire 2 Powerful suction rotary vane vacuum
0 7 B ith iti i fl
VFT- 15 Micro Bore 15 Pipe Detector
pump – 0.7 Bar with sensitive airflow monitor
Large, clear display panel Onboard Modbus RS232 and RS485 TCP/IP Ethernet Modular relay output units PSU, battery charger and battery
optional
What’s inside VFT-15?
15 Sector inputs
Display/
Programmer
0.7 Bar Vacuum pump
Battery Compartment
Power Supply (if required)
I/O modules when the display is lowered
4
Sampling Components
Powerful 0.7 Bar suction rotary vane vacuum pump.
15 way rotary valve incorporating pressure sensor.– Trace mode of operation: samples overall from all pipes
• 30 sec to detection
– Selection mode: Scans sectors when smoke detected
• +/ 9 sec/pipe• +/- 9 sec/pipe
– Self test mode: every 20 min
• 1/1 dilution (no dilution of smoke sample)
VFT-15 Microbore Sampling
The VFT-15 requires microbore, which is 6 mm OD and 4mm ID flexible nylon tube.
All lengths should be equal with a maximum allowable length of 50 m per tube.
Other materials may be used such as Stainless Steel with suitable adaptors for harsh environments.
Never glue to the inlets of the detector.
Unused inputs should be looped to one another using short lengths of microbore.
VFT-15 - Accessories
Part Number Description
VFT-15 Xtralis VESDA VFT‐15, 24v DC with Display & TCP/IP
VFT-15-C Xtralis VESDA VFT‐15, 24v DC with Display & TCP/IP ‐ Class C Sensitivity
01-E921-15 Remote Display
01-EP02-02 Mains PSU/Battery Charger 230VAC
01-E606-01 Relay Module 4 Channel FT series
01-E624 Re‐Transmission Module 8 Channel 4‐20mA
01-E922-01 Mini RDU RS485 ‐ 19" rack mount
5
Power Supply
Optional 230V AC supply and battery charger (EN54)
2 x 12V (18 AH) batteries inside housing or 2 x 12 V (40 AH) batteries outside the housing
I/O Modules
Optional I/O modules
– 4 Channel relays
– 8 Channel 4-20 mA Analogue Out
VFT Series Display Panel
Display may be used to program the detector
6
Remote Display Options
Remote Display Panel– Remote display & keypad
– One per detector up to 1km away
– RS485 connected.
Rack Mounted Remote Display Unit– 19” rack mount - 12 per rack
– Accept / reset / isolate
– Bar graph, alarms and faults
– RS485 connected via CN6 on i602 board (Termination Board)
– Up to 16 per detector– Up to 16 per detector
VSC Configuration andcontrol of all Xtralis VESDAdevices
Sophisticated but intuitive support tools
Supporting Software
VSM4 Remote monitoringand control of multipledevice networks in fullgraphical context, includingemail/SMS messaging andfire policy prompts
Remote Access & Networking
7
Typical VFT-15 Applications
Electronic data processing equipment
High sensitivity
Micro bore pipes forMicro bore pipes for individual cabinet identification
Unaffected by high air speeds
Optional integral hydrogen monitoring of UPS rooms
A highly addressable solution for fully-enclosed cabinets
Extending the VLP-VLS solution
Typically a VLP would be used to protect the open environment of the modern high density data centre.
Addressability to a particular area might be possible by using a VLS pipe per isle or per grille but this can be economically challenging
Extending the VLP/VLS solution
The application of VFT-15 provides fully addressable coverage of the mission critical cabinets while the VLP detects less critical environments such as across the return air grille and hot isles.
8
Typical VFT-15 Applications
Mines and Electrical Substations
Operates in dusty environments
Individual protection of high-voltage switchgear cabinetsvoltage switchgear cabinets
HV cabinets are bolted and cannot be opened easily
PLC and control rooms
Electrical substations
Extending the VLP-VLS solution
The current solution for protecting low heat load vented cabinets is to sample at the top of the cabinet using capillary tubes placed into the various cabinets from a main branch pipe.
The disadvantage is that only aThe disadvantage is that only a global alarm will be generated, requiring visual inspection of each cabinet to determine the source
Use of a VLS provides enhanced addressability per main branch pipe but still does not provide individual cabinet identification
Extending the VLP-VLS solution
The VFT-15 offers an extremely competitive and more elegant solution for identifying up to 15 individual cabinets.
9
Typical VFT-15-C Applications
Prisons and Correctional Institutions
Tamper proof air sampling
Individual monitoring of up to 15 cells
High speed reaction time High speed reaction time
Central maintenance facility
Typical VFT-15-C Applications
Exclusive Residences, Shops & Apartments
Aesthetic, invisible
Unique low profile stainlessUnique low profile stainless steel sampling point!
– Only Ø 33 mm x 4 mm height
Programming Tools
VSC/VSM4
VFT Display Panel
10
Programming with VFT Display
Programming Keys
Log on to the DetectorUsing the Admin Code 693
1. Alert 0.08%2. Action 0.14%3. Fire 1 0.2%4. Fire 2 1.5%
5. Set the fan speed to 76. Normalize the Detector7. Set the High Flow to 135%8. Set the low flow to 75%
Menus Available1. Faults2. Operator3. Engineering4. Configure5. Sector Alarms6. Time + Date7. Web8. Setup9. Laser Cal10. Load Defaults11. Maintenance12. Test Outputs
Basic Programming Exercise
VFT RS485 Communications
Three Options:
– Up to 30 Detectors communicate to a PC
– 1 Detector communicates with one Remote Display Panel
– Up to 16 Detectors communicate 16 R t Di l U itRemote Display Units
Cannot combine any of the three options.
VFT RS485 Communications
Connect shielded twisted pair to CN6
Ensure length doesn’t exceed 1km
CN6 CN6 CN6 CN6
Set Jumper to “End” for End of Line Detectors
11
VFT RS485 Communications
Connect a Remote Display Panel using connector under the Display Panel.
Ensure length doesn’t exceed 1km
Note: The configuration of the detector needs to be changed to expect the Remote Display Panel.
VFT Relays
On-board Relays Relay Modules
VFT Relay Assignments
12
VFT Faults
General Fault
Mains Fault
Flow Fault
Battery Fault y
Aspirator Fault
Detector Fault
Comms Fault
If faults not rectified on site when referring to trouble shooting guide contact Xtralis
VFT Spare Parts List
Part Number DescriptionVFT-15 Xtralis VESDA VFT‐15, 24v DC with Display & TCP/IP
VFT-15-C Xtralis VESDA VFT‐15, 24v DC with Display & TCP/IP ‐ Class C Sensitivity
01-E921-15 Remote Display
01-EP02-02 Mains PSU/Battery Charger 230VAC
01-E606-01 Relay Module 4 Channel
01-E624 Re‐Transmission Module 8 Channel 4‐20mA , FT series
01-E922-01 Mini RDU RS485 ‐ 19" rack mount
01-E922-99 19” sub rack for 12 Mini RDU
01-E922-00 Blind plate for sub rack
02-2001-30 Micro Bore 6mm sampling tube ‐ 30m reel
02-2002-01P Straight Union for Micro Bore 6mm Tube (Pack of 10)
02-2003-01P Tee Union for Micro Bore 6mm Tube (Pack of 10)
02-3000-06 Stainless steel sampling point 6mm