04. chapter - ii.pdf
TRANSCRIPT
REVIEW OF LITERATURE
9
CHAPTER 2
REVIEW OF LITERATURE
2.1 Introduction
A detailed review of literature on the performance of different types of concrete
specimens that were exposed to higher temperature is reported in this chapter.
Shape of specimen, size of specimen, magnitude of temperature load applied on the
specimen, duration of heating, time temperature curve, rate of heating, rate of
cooling, time taken for hot test after curing period, time taken for load test after
heating, stressed/unstressed test on hot members, type of cooling adopted on heated
specimens etc are the parameters that influence the test results. To completely
understand the behavior of concrete under elevated temperature, it is necessary to
consider all the key factors involved while designing the experimental setup. Grade
of concrete, type of cement, type of admixture, type of aggregate, water cement
ratio, density of concrete, reinforcement percentage, cover to the reinforcement etc
are some of the important factors that influence the performance of concrete at
elevated temperature. However it is difficult to carry out experimental
investigations considering all the parameters that influence the performance of
concrete exposed to elevated temperatures. Hence different researchers considered
different sets of parameters. This chapter summarizes the salient features of the
experimental and analytical investigations reported in the literature. The analysis of
the data indicates that the behaviors of Normal Compacting Concrete and Self
Compacting Concrete are different. The effects of elevated temperatures on the
properties of concrete such as compressive strength, tensile strength, flexural
strength and spalling reported in the literature are summarized.
A review of methods used by various investigators for testing concrete at elevated
temperature indicates that, the tests can be categorized into three types namely
stressed test, unstressed test and unstressed residual strength test. In stressed tests, a
preload is applied to the specimen prior to heating and the load is sustained during
the heating period. Heat is applied at a constant rate until a target temperature is
reached, and this temperature is maintained for a time until a thermal steady state is
10
achieved. Load is then increased at a prescribed rate until the specimen fails. In the
unstressed test, the specimen is heated, without preload at a constant rate to the
target temperature, which is maintained until a thermal steady state is achieved.
Load is then applied at a prescribed rate until failure occurs. In unstressed residual
strength test, the specimen is heated without preload at a prescribed rate to the
target temperature, which is maintained until a thermal steady state is reached
within the specimen. The specimen is then allowed to cool, following a prescribed
rate to room temperature. Load is applied on the specimen at room temperature until
the specimen fails. The first two types of test are suitable for accessing the strength
of concrete during high temperatures, while the later is excellent for finding the
residual properties after the high temperature. It is reported by Abrams [1973]1 that
the last method gives the lowest strength and is therefore more suitable for getting
the limiting values of strength.
2.2 Review of Literature
2.2.1 Development of Self Compacting Concrete
Bertil Persson (2001)10
carried out an experimental and numerical study on
mechanical properties, such as strength, elastic modulus, creep and shrinkage of self
compacting concrete and the corresponding properties of normal compacting
concrete. The study included eight mix proportions of sealed or air cured specimens
with water binder ratio (w/b) varying between 0.24 and 0.80. Fifty percent of the
mixes were SCC and rests were NCC. The age at loading of the concretes in the
creep studies varied between 2 and 90 days. Strength and relative humidity were
also found. The results indicated that elastic modulus, creep and shrinkage of SCC
did not differ significantly from the corresponding properties of NCC.
Nan Su et al (2001)73
proposed a new mix design method for self compacting
concrete. First, the amount of aggregates required was determined, and the paste of
binders was then filled into the voids of aggregates to ensure that the concrete thus
obtained has flowability, self compacting ability and other desired SCC properties.
The amount of aggregates, binders and mixing water, as well as type and dosage of
super plasticizer to be used are the major factors influencing the properties of SCC.
11
Slump flow, V-funnel, L-flow, U-box and compressive strength tests were carried
out to examine the performance of SCC, and the results indicated that the proposed
method could be used to produce successfully SCC of high quality. Compared to
the method developed by the Japanese Ready Mixed Concrete Association
(JRMCA), this method is simpler, easier for implementation and less time
consuming and requires a smaller amount of binders and saves cost.
Bouzoubaa and Lachemi (2001)12
carried out an experimental investigation to
evaluate the performance of SCC made with high volumes of FlyAsh (FA). Nine
SCC mixtures and one control concrete were made during the study. The content of
the cementitious materials was maintained constant (400kg/m3), while the
water/cementitious material ratios ranged from 0.35 to 0.45. The self compacting
mixtures had a cement replacement of 40%, 50%, and 60% by Class F flyash. Tests
were carried out on all mixtures to obtain the properties of fresh concrete in terms
of viscosity and stability. The mechanical properties of hardened concrete such as
compressive strength and drying shrinkage were also determined. The SCC mixes
developed a 28 day compressive strength ranging from 26 to 48 MPa. They reported
that economical SCC mixes could be successfully developed by incorporating high
volumes of Class F flyash.
Sri Ravindrarajah et al (2003)89
made an attempt to increase the stability of fresh
concrete (cohesiveness) using increased amount of fine materials in the mixes. They
reported about the development of self compacting concrete with reduced
segregation potential. The systematic experimental approach showed that partial
replacement of coarse and fine aggregate with finer materials could produce self
compacting concrete with low segregation potential as assessed by the V-Funnel
test. The results of bleeding test and strength development with age were
highlighted by them. The results showed that flyash could be used successfully in
producing self compacting high strength concrete with reduced segregation
potential. It was also reported that flyash in self compacting concrete helps in
improving the strength beyond 28 days.
12
Hajime Okamura and Masahiro Ouchi (2003)30
addressed the two major issues
faced by the international community in using SCC, namely the absence of a proper
mix design method and jovial testing method. They proposed a mix design method
for SCC based on paste and mortar studies for super plasticizer compatibility
followed by trail mixes. However, it was emphasized that the need to test the final
product for passing ability, filling ability, flowability and segregation resistance was
more relevant.
Mohammed Sonebi (2004)67
developed medium strength self compacting concrete
(MS-SCC) by using pulverised fuel ash (PFA) with a minimum amount of super
plasticizer. A factorial design was carried out to mathematically model the influence
of key parameters on filling ability, passing ability, segregation resistance and
compressive strength, which are important for the successful development of
medium strength self compacting concrete incorporating PFA. The parameters
considered in the study were the contents of cement and PFA, water to powder
(cement + PFA) ratio (w/p) and dosage of SP. The responses of the derived
statistical models are slump flow, fluidity loss, Orimet time, V-funnel time, L-box,
rheological parameters, segregation resistance and compressive strength at 7, 28 and
90 days. Twenty one mixes were prepared to derive the statistical models, and five
were used for the verification and the accuracy of the developed models. The
models are valid for mixes made with 0.38 to 0.72 w/p, 60 to 216 kg/m3 of cement
content, 183 to 317 kg/m3 of PFA and 0% to 1% of SP, by mass of powder. The
influences of w/p, cement and PFA contents, and the dosage of SP were
characterised and analysed using polynomial regression equations, which can
identify the primary factors and their interactions on the measured properties. The
results showed that MS-SCC can be achieved with a 28 day compressive strength of
30 to 35 MPa by using up to 210 kg/m3 of PFA.
Mustafa Sahmaran et al (2006)71
evaluated the effectiveness of various mineral
additives and chemical admixtures in producing Self Compacting Mortars (SCM).
For this purpose, four mineral additives (flyash, brick powder, limestone powder
and kaolinite), three super plasticizers and two viscosity modifying admixtures were
13
used. Within the scope of the experimental program, 43 mixtures of SCM were
prepared keeping the amount of mixing water and total powder content (portland
cement and mineral additives) constant. Workability of the fresh mortar was
determined using mini V-Funnel and mini slump flow tests. The setting time of the
mortars, was also determined. The hardened properties that were determined
included ultrasonic pulse velocity and strength at 28th
and 56th
days. It was
concluded that among the mineral additives used, flyash and limestone powder
significantly increased the workability of SCMs. On the other hand, especially
flyash significantly increased the setting time of the mortars, which can be
eliminated through the use of ternary mixtures, such as mixing flyash with
limestone powder. The two polycarboxyl based SPs yield approximately the same
workability and the melamine formaldehyde based SP was not as effective as the
other two.
Mustafa Sahmaran and Ozgur Yaman (2007)72
studied the fresh and mechanical
properties of a fiber reinforced self compacting concrete incorporating high volume
flyash that does not meet the fineness requirements of ASTM C 618. A poly
carboxylic based super plasticizer was used in combination with a viscosity
modifying admixture. In mixtures containing flyash, 50% of cement by weight was
replaced with flyash. Two different types of steel fibers were used in combination,
keeping the total fiber content constant at 60 kg/m3. Slump flow time and diameter,
V-funnel, and air content were found to assess the fresh properties of the concrete.
Compressive strength, splitting tensile strength, and ultrasonic pulse velocity were
determined for the hardened concrete. The results indicated that high volume coarse
flyash can be used to produce fiber reinforced self compacting concrete, even
though there is some reduction in the strength because of the use of high volume
coarse flyash.
Burak Felekoglu et al (2007)14
made an investigation on five self compacting
concrete mixtures with different combinations of water/cement ratio and super
plasticizer dosage levels. Slump flow, V-funnel and L-box tests were carried out to
determine the optimum parameters for the self compactibility of mixtures.
14
Compressive strength development, modulus of elasticity and splitting tensile
strength of mixtures were also studied. It was reported that optimum water/cement
ratio for producing SCC was in the range of 0.84 to 1.07 by volume. The ratios
above and below this range may cause blocking or segregation of the mixture. The
Splitting tensile strengths of the SCC mixes were found to be higher and the values
of Modulus of elasticity were found to be lower than those of NCC.
Binu Sukumar et al (2007)11
replaced high volume flyash in the powder, based on
a rational mix design method to develop self compacting concrete. High flyash
content necessitated the study on the development of strength at early ages of curing
which is a significant factor for the removal of formwork. Rate of gain of strength at
different periods of curing such as 12 h, 18 h, 1 day, 3 days, 7 days, 21 days and 28
days were studied for various grades of different SCC mixes and suitable relations
were established for the gain in strength at the early ages in comparison to the
Conventional Concrete (CC) of same grades. Relations were also formulated for the
compressive strength and the split tensile strength for different grades of SCC
mixes. It was observed that the rate of gain in strength for different grades of SCC
was slightly more than the expected strength of conventional concrete of the same
grades.
Burak Felekoglu and Hasan Sarıkahya (2007)13
synthesized three Poly
Carboxylate (PC) based super plasticizers by using radical polymerisation
techniques. The effect of these admixtures on setting time of cement pastes, time
dependent workability and strength development of SCC was investigated. Test
results showed that, from the viewpoint of chemical structure, workability retention
performance of PC based super plasticizers could be manipulated by modifying the
bond structure between main backbone and side chain of copolymer. PC based SPs
with ester bonding were found to be ineffective in maintaining the workability of
fresh concrete workability due to the alkali attack vulnerability of this bond
structure. It was also reported that, by directly bonding the polyoxyethylene side
chain to the backbone of copolymer, the workability of fresh concrete can be
effectively maintained at least for a period of 2 h. It was found that, in addition to
15
the types of SP, water/powder ratio of SCC mixtures were also responsible for the
long workability retention performances. Best results were derived from mixtures
incorporating 2.3 weight % of SP.
Ahmadi et al (2007)2 studied the development of Mechanical properties up to 180
days of self compacting and ordinary concrete mixes with rice husk ash (RHA),
from a rice paddy milling industry. Two different replacement percentages of
cement by RHA, 10%, and 20%, and two different water/cementitious material
ratios (0.40 and 0.35) were used for both of self compacting and normal concrete
specimens. The results were compared with those of the self compacting concrete
without RHA. SCC mixes show higher compressive and flexural strength and lower
modulus of elasticity rather than the normal concrete. Replacement up to 20% of
cement with rice husk ash in matrix caused reduction in utilization of cement and
expenditures, and also improved the quality of concrete at the age of more than 60
days. It was concluded that RHA provides a positive effect on the Mechanical
properties after 60 days.
Halit Yazici (2007)31
developed self compacting concrete by replacing cement with
a Class C FA in various proportions from 30% to 60%. Durability properties of
various self compacting concrete mixtures such as, freezing and thawing, and
chloride penetration resistance were found. Similar tests were carried out with the
incorporation of 10% Silica Fume (SF) to the same mixtures. Test results indicated
that SCC could be obtained with a high volume FA. Addition of 10% SF to the
system improved both the fresh and hardened properties of high performance high-
volume FA SCC. These mixtures had good mechanical properties, freeze thaw and
chloride penetration resistance. Moreover, these mixtures also had great
environmental and economical benefits. The heat of hydration and shrinkage of
these mixtures were lower than those of the SCC mixtures made with high volume
Portland cement.
Khatib (2008)52
investigated the influence of including flyash on the properties of
self compacting concrete. Portland cement was partially replaced with 0–80% FA.
The water to binder ratio was maintained at 0.36 for all mixes. Properties like
16
workability, compressive strength, ultrasonic pulse velocity, absorption and
shrinkage were found. The results indicated that high volume FA can be used to
produce high strength and low shrinkage SCC. Replacing 40% of Portland cement
with FA resulted in a strength of more than 65 N/mm2
at 56 days. High absorption
values were obtained with increasing amount of FA. There is a systematic reduction
in shrinkage as the FA content increases and at 80% FA content, the shrinkage at 56
days reduced by two third compared with the control. A linear relationship existed
between the 56th
day shrinkage and FA content. Increasing the admixture content
beyond a certain level led to a reduction in strength and increase in absorption. The
correlation between strength and absorption indicated a sharp decrease in strength
as absorption increased from 1 to 2%. Beyond 2% absorption, the reduction in the
strength was found to be at a slower rate.
Shazim Ali Memon et al (2008)90
studied the use of Rice Husk Ash (RHA) to
increase the amount of fines and hence achieving self compacting concrete in an
economical way. They compared the properties of fresh SCC containing varying
amounts of RHA with that containing commercially available viscosity modifying
admixture. The comparison was done at different dosages of super plasticizer
keeping cement, water, coarse aggregate, and fine aggregate contents constant. Test
results substantiate the feasibility to develop low cost SCC using RHA. Cost
analysis showed that the cost of ingredients of specific SCC mix is 42.47 percent
less than that of control concrete.
Paratibha Aggarwal et al (2008)80
presented a procedure for the design of self
compacting concrete mixes based on an experimental investigation. At the
water/powder ratio of 1.180 to 1.215, slump flow test, V-funnel test and L-box test
results were found to be satisfactory, i.e. passing ability, filling ability and
segregation resistance are well within the limits. SCC was developed without using
VMA in this study. Further, compressive strength at the ages of 7, 28, and 90 days
was also determined. By using the Ordinary Portland Cement (OPC) 43 grade,
normal strength of 25 MPa to 33 MPa at 28 days was obtained, keeping the cement
content around 350 kg/m3 to 414 kg/m
3.
17
Seshadri Sekhar and Srinivasa Rao (2008)86
studied the properties like
compressive strength, split tensile strength and flexural strength of SCC mix
proportions ranging from M30 to M65 grades of concrete. An attempt was made to
obtain a relationship among the splitting tensile strength, flexural strength and
compressive strength from the test results. The increase in the compressive strength
for all the grades of SCC mixes compared with the 28th
day compressive strength
varied between 20 and 30%. The increase in flexural strength for all the grades of
SCC mixes compared with the 28th
day flexural strength varied between 15 and
25%. The increase in split tensile strength for all the grades of SCC mixes
compared with the 28th
day split tensile strength varied between 15 and 25%.
Al-Feel and Al-Saffar (2009)3 carried out an experimental investigation to study
the effect of curing methods on the compressive, splitting, and flexural strengths
(modulus of rupture) of self compacting concrete and compared the same with that
of normal concrete. The self compacting concrete was made with Portland cement,
limestone powder, sand, gravel and super plasticizer. The specimens were cured in
the air and water, for the period of 7, 14, and 28 days. Three specimens were tested
for each point of each property. It is reported that the compressive strength, splitting
tensile strength and flexural strength of the water cured specimens were 11%, 10%
and 11% respectively more than those of the specimens cured in air. From the failed
specimens it was found that there was no segregation and the bond between
aggregate and matrix was good.
Kursat Esat Alyamac and Ragip Ince (2009)61
studied the relationship between
properties of the fresh SCC and the hardened SCC containing marble powder. For
this purpose, the mix design approach based on monogram developed by Monteiro
and co-workers for normal vibrated concrete was adapted to SCC mixes. In order to
obtain this monogram, a series of SCC mixes with different water/cement ratios and
water/powder ratios were prepared. Several tests such as slump-flow, T50 time, L-
box, V-Funnel and sieve segregation resistance were applied for fresh concrete and
tests such as compressive strength and split tension strength at 7,28 and 90 days
18
were performed for hardened concrete. They reported that the mix design method
based on monogram can be used for preliminary design of SCC mixes.
Ilker Bekir Topcu et al (2009)39
developed self compacting concrete, using waste
Marble Dust (MD) as a filler material. MD was used directly without any additional
processing. MD was used to replace the binder of SCC in proportions of 0, 50, 100,
150, 200, 250 and 300 kg/m3. Slump flow test, L-box test and V-funnel test were
carried out on the fresh concrete. Compressive strength, flexural strength, ultrasonic
velocity, porosity and compactness were also determined at 28 days. The effect of
waste MD usage as filler material on capillarity properties of SCC was also
investigated. It was concluded that the workability of fresh SCC has not been
affected up to 200 kg/m3 MD content. However, the mechanical properties of
hardened SCC were found to decrease while using MD, especially when the content
of MD was more than 200 kg/m3.
Hemant Sood et al (2009)35
highlighted the use of European standards for testing
self compacting concrete in Indian conditions. They carried out an experimental
investigation of self compacting concrete using flyash and Rice husk ash as mineral
admixtures and testing rheological properties as per European Standards. Addition
of flyash in SCC increased the filling and passing ability of concrete, whereas rice
husk ash imparted viscosity to concrete improving segregation resistance of
concrete mix. From this experimental study it was inferred that flyash and RHA
blend improved the overall workability, which is the prime important characteristic
of SCC. Increase in Rice husk ash content increased the water demand and reduced
the compressive strength of concrete.
Girish et al (2010)28
presented the results of an experimental investigation carried
out to find out the influence of paste and powder content on self compacting
concrete mixtures. Tests were conducted on 63 mixes with water content varying
from 175 l/m3 to 210 l/m
3 with three different paste contents. Slump flow, V-funnel
and J-ring tests were carried out to examine the performance of SCC. The results
indicated that the flow properties of SCC increased with increase in the paste
volume. As powder content of SCC increased, slump flow of fresh SCC increased
19
almost linearly and in a significant manner. They concluded that paste plays an
important role in the flow properties of fresh SCC in addition to water content. The
passing ability as indicated by J-ring improved as the paste content increased.
Nicolas Ali Libre et al (2010)76
studied the effect of chemical and mineral
admixtures, including super plasticizer, viscosity modifying agent, limestone
powder and flyash with different w/c ratios on fluidity, viscosity, and stability of
self consolidating mortar. The results indicated that w/c is the most significant
parameter influencing the rheological properties of cementitious mixtures, specially
their stability. Furthermore, the maximum allowable w/c ratio for preventing
inhomogeneity could not be a fixed value for all the mixtures and should be
adjusted for the target fluidity. They reported that addition of VMA was an effective
method for stabilizing self consolidating mortars and preventing any kinds of
instability. Limestone powder and flyash mainly affected bleeding and aggregate
blockage. Besides, these mineral admixtures improved the fluidity of the mixtures
to some extent.
Venkateswara Rao et al (2010)94
developed standard and high strength self
compacting concrete with different sizes of aggregate based on Nansu’s mix design
procedure. The results indicated that Self Compacting Concrete can be developed
with all sizes of graded aggregate satisfying the SCC characteristics. The
mechanical properties such as compressive strength, flexural strength and split
tensile strengths were found at the end of 3, 7 and 28 days for standard and high
strength SCC with different sizes of aggregate. The optimum size of aggregate was
found to be 10mm for standard self compacting concrete (M30), while it was 16mm
for high strength self compacting concrete (M70) though all other sizes also could
develop properties satisfying the criteria for SCC. A comparison of M30 and M70
grade concrete confirmed that the filling ability, passing ability and segregation
resistance were better for higher grade concrete for the same size of aggregate. This
is due to the higher fines content in M70 concrete. It was noted that 10mm size
aggregate and 52% flyash resulted in highest mechanical properties in standard
20
SCC, whereas 16 mm size aggregate with 31% flyash content resulted in highest
strength in case of high strength SCC.
Mucteba Uysal and Kemalettin Yilmaz (2011)69
studied the benefits of using
limestone powder (LP), basalt powder (BP) and marble powder (MP) as partial
replacement of Portland cement to develop the self compacting concrete.
Furthermore, LP, BP and MP were used directly without any additional processing
in the production of self compacting concrete. The water to binder ratio was
maintained at 0.33 for all mixtures. The examined properties include workability,
air content, compressive strength, ultrasonic pulse velocity, static and dynamic
elastic moduli. Workability of the fresh concrete was determined by using both the
slump flow test and the L-box test. The results proved that it is possible to
successfully utilize waste LP, BP and MP as mineral admixtures in producing SCC.
It was reported that the employment of waste mineral admixtures improved the
economical feasibility of SCC production.
2.2.2 Experimental Investigations on the Behaviour of Concrete Materials
Under Elevated Temperatures
Abrams.M.S (1973)1 determined the compressive strength of 7.5x15cm cylindrical
specimens that were heated for short duration to temperatures of 200 to 1600° F (93
to 871°C). Carbonate, siliceous, and lightweight aggregates were used in the
experiment. Three different types of tests (heated without load and tested hot,
heated with load and tested hot, and tested cool after heating) were carried out on
the specimens. Carbonate aggregate concrete and lightweight concrete specimens
when tested hot without prior loading retained about 75 percent of their original
strength (strength prior to heating) at 1200°F (649°C). Above that temperature,
reduction in the strength was observed. Specimens heated while loaded had the
highest strengths, while the strength of specimens heated, cooled, and then tested
were the lowest throughout the temperature range. Original strength of concrete had
little effect on the percentage of strength retained at high temperatures. The
lightweight concrete had strength characteristics at high temperatures similar to
those of carbonate concrete. At temperatures above 800°F (427°C), the siliceous
21
aggregate concrete had lower strength than the other concretes. The salient features
of the test are shown in Table 2.1.
Table 2.1 Salient Features of Test Carried out by Abrams M.S
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.076 x
0.152)
21 to 871oC
Peak
temperature
maintained
for 3 to 4
hours
Furnace
temperature
curve
- -
Stressed,
Unstressed,
Un stressed
residual
strength
test
Moetaz M. El-Hawaryet al (1996)65
studied the effect of fire on the flexural
behaviour of Reinforced Concrete (RC) beams. Four groups of RC beams were cast,
exposed to fire at 650°C for time durations of 0, 30, 60 and 120 min and then
cooled by water. Reduction in ultimate load, increase in deflection, increase in both
compressive and tensile strains and reduction in concrete compressive strength were
observed for the heated specimens. The salient features of the test are shown in
Table 2.2.
Table 2.2 Salient Features of Test Carried out by Moetaz M. El-Hawary et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(1.8x0.12
x0.2)
650°C
Peak
temperature
maintained
for 30min,
60min,
120min
Furnace
temperature
curve
-
Sprayed
with water
immediately
Un
stressed
residual
strength
test
Moetaz M. El-Hawary and Sameer A. Hamoush (1996)66
carried out an
experimental investigation to determine the effect of high temperature on the
interfacial bond shear modulus between concrete and reinforcement. Steel bars of
different diameters were embedded in concrete cylinders for a depth less than that
required for total development to assure failure by loss of bond. Specimens were
then kept in an oven for different time durations and different temperatures.
22
Specimens were then cooled by either keeping cylinders at room temperature or
immersing them in water. The interfacial bond shear modulus between concrete and
steel reinforcement was calculated using an experimental analytical technique. The
pull out test was applied, and loads and displacements were recorded. Results from
the pull out test were then used along with an analytical model to calculate the bond
shear modulus. The analytical model was based on the physical representation of
the pull out test, assuming linear elastic behavior of both steel and concrete. The
effects of temperature, duration of heating, size of steel bar and the method of
cooling on the bond shear modulus were investigated. The bond shear modulus was
found to be independent of the diameter of the reinforcing bars and was found to be
much lower for concrete cooled by water than for concrete cooled gradually in air.
Specimens heated to about 100°C for short durations and cooled in air experienced
an increase in the bond shear modulus. For all other specimens, a reduction in the
bond shear modulus was noticed. The reduction increased with the increase of the
heating temperature or duration of heating. The salient features of the test are shown
in Table 2.3.
Table 2.3 Salient Features of Test Carried out by Moetaz M. El-Hawary and
Sameer A. Hamoush
Size of
the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.1 x
0.2)
100,300
500oC
Peak
temperature
maintained
for 2,4 & 8
hours
Furnace
temperature
curve
-
Natural
cooling by
air,
immersion
in water
Un
stressed
residual
strength
test
Moetaz M. El-Hawary et al (1997)22
studied the effect of duration of fire exposure
and the concrete cover thickness on the behaviour of RC beams subjected to fire in
shear zone and cooled by water. Investigation was carried out on eight reinforced
concrete beams of size 1800 x 200 x 120 mm. The beams were divided into two
groups. Group (1) consisted of four beams with a cover thickness of 20 mm and
group (2) consisted of four beams with a cover thickness of 40 mm. Each group was
subjected to a temperature of 650°C for different periods of time, i.e. 0, 30, 60. 120
23
min. The compressive strength of the beams was determined non-destructively
using a Schmidt hammer on the next day after exposure to fire. The beams were
tested by applying two transverse loads incrementally. Strains and deformations
were measured at each load increment. Cracking loads, crack propagation and
ultimate loads were recorded for each beam. The behaviour of the beams exposed to
fire in the shear zone was found to be highly affected by the fire exposure time and
the change of the cover thickness. The salient features of the test are shown in Table
2.4.
Table 2.4 Salient Features of Test Carried out by Moetaz M. El-Hawary et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(1.8x0.2
x0.12)
650°C
Peak
temperature
maintained
for 30min,
60min,
120min
Furnace
temperature
curve
-
Sprayed
with water
immediately
Un
stressed
residual
strength
test
Y.N.Chan et al (1999)17
carried out an investigation on the fire resistance of
Normal Strength Concrete (NSC) and High Strength Concrete (HSC), with
compressive strengths of 39, 76 and 94 MPa respectively. After exposure to
temperatures upto 1200°C, compressive strength and tensile splitting strength were
determined. The pore structure in HSC and in NSC was also investigated. Results
indicated that HSC lost its mechanical strength in a manner similar to that of NSC.
The range between 400 and 800°C was found to be critical to the strength loss.
High temperatures had a coarsening effect on the microstructure of both HSC and
NSC. On the whole, HSC and NSC suffered damage to almost the same degree,
although HSC appeared to suffer a greater worsening of the permeability related
durability. The salient features of the test are shown in Table 2.5.
24
Table 2.5 Salient Features of Test Carried out by Y.N.Chan et al
Size of
the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1
x0.1)
20, 400,
600, 800,
1000 &
1200°C
Peak
temperature
maintained
for
1 hour
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Y.N.Chan et al (2000)16
carried out an experimental investigation to study the
mechanical properties and pore structure of high performance concrete and normal
strength concrete after exposure to high temperature. After the concrete specimens
were subjected to a temperature of 800°C, their residual compressive strength was
measured. The porosity and pore size distribution of the concrete were investigated
using mercury intrusion porosimetry. Test results indicated that HPC had higher
residual strength than the normal strength concrete after exposure to high
temperature. It was reported that the changes in pore structure could be used to
indicate the degradation of mechanical property of HPC subjected to high
temperature. The salient features of the test are shown in Table 2.6.
Table 2.6 Salient Features of Test Carried out by Y.N.Chan et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1x0.1)
800°C
Peak
temperature
maintained
for
1 hour
Furnace
temperature
curve
5 to
7°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Chi-Sun Poon et al (2001)18
investigated the strength and durability performance
of normal and high strength pozzolanic concrete incorporating silica fume, flyash
and blast furnace slag at elevated temperatures up to 800ºC. The strength properties
were determined using an unstressed residual compressive strength test, while
durability was investigated by rapid chloride diffusion test and crack pattern
25
observations. It was found that pozzolanic concrete containing flyash and blast
furnace slag gave the best performance particularly at temperatures below 600ºC as
compared to the pure cement concrete. Explosive spalling occurred in high strength
concrete containing silica fume. A distributed network of fine cracks was observed
in all flyash and blast furnace slag concrete, but no spalling or splitting occurred.
The high strength pozzolanic concrete resulted in a severe loss in permeability
related durability than the loss in the compressive strength. Thirty percent
replacement of cement by flyash in HSC and 40% replacement of cement by blast
furnace slag in normal strength concrete were found to be optimal to retain
maximum strength and durability after high temperatures. The salient features of the
test are shown in Table 2.7.
Table 2.7 Salient Features of Test Carried out by Chi-Sun Poon et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1x0.1)
(0.1x0.05)
200°C,
400°C,
600°C&
800°C
Peak
temperature
maintained
for 1 hour
Furnace
temperature
curve
2.5°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Chi-Sun Poon et al (2003)19
carried out an experimental investigation to evaluate
the performance of Metakaolin (MK) concrete at elevated temperatures up to
800°C. Eight normal and high strength concrete mixes incorporating 0%, 5%, 10%
and 20% MK were prepared. The residual compressive strength, chloride-ion
penetration, porosity and average pore sizes were measured and compared with
silica fume, flyash and pure ordinary portland cement concretes. It was found that
after an increase in compressive strength at 200°C, the MK concrete suffered a
more severe loss of compressive strength and permeability related durability than
the corresponding SF, FA and OPC concretes at higher temperatures. Explosive
spalling was observed in both normal and high strength MK concretes and the rate
of spalling increased with higher MK contents. The salient features of the test are
shown in Table 2.8.
26
Table 2.8 Salient Features of Test Carried out by Chi-Sun Poon et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1x0.1)
Cylinder
(0.1x0.2)
200°C,
400°C,
600°C&
800°C
Peak
temperature
maintained
for 1 hour
Furnace
temperature
curve
2.5°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Kumar A and Kumar V (2003)60
carried out an investigation to find the residual
strength of reinforced cement concrete beams exposed to higher temperature for a
long duration. Six Reinforced Cement Concrete (RCC) beams were cast with same
reinforcement, length, grade of concrete and clear cover. Four beams were exposed
to fire for durations of 1 h, 1.5 h, 2 h and 2.5 h. These beams exposed to fire for
2.5 h and tested at room temperature failed in serviceability criteria. The reduction
in stiffness was found to increase with the increase in the duration of fire exposure.
The following conclusions were drawn by the authors from the test carried out on
RCC beams. RCC beam of grade M20 with 25 mm clear cover was unable to resist
a fire exposure of about 2.5h as it failed in serviceability criterion. Spalling of
concrete was observed at many places, which increased further with the time. Even
2 h fire duration was found to be critical as the beam was able to take only about
50% load of the companion beam. The behavior of M20 RCC beam exposed to fire
of 1 h duration was found to be satisfactory as its strength was found to be about
83% of the companion beam. The salient features of the test are shown in Table 2.9.
Table 2.9 Salient Features of Test Carried out by Kumar A and Kumar V
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(3.96x0.2
x0.3)
1000ºC
1hr,1.5hr,2hr,
2.5hr
(IS 3809-
1979)
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Fu-Ping Cheng et al (2004)26
investigated the effects of high temperature on the
strength and stress-strain relationship of high strength concrete. Stress-strain curve
27
tests were conducted at various temperatures (20, 100, 200, 400, 600 and 800°C) for
four types of HSC. The variables considered in the experimental study included
concrete strength, type of aggregate, and the addition of steel fibers. From the
results of stress-strain curve tests it was found that plain HSC exhibited brittle
properties below 600°C, and ductility above 600°C. HSC with steel fibers exhibited
ductility above 400°C. The compressive strength of HSC decreased by about a
quarter of its room temperature strength within the range of 100 to 400°C, the
strength further decreased with the increase of temperature and reached about a
quarter of its initial strength at 800°C. The strain at peak load also increased with
temperature, from 0.003 at room temperature to 0.02 at 800°C. Further, the increase
in strains for carbonate aggregate HSC was found to be more than that of the
siliceous aggregate HSC. The salient features of the test are shown in Table 2.10.
Table 2.10 Salient Features of Test Carried out by Fu-Ping Cheng et al
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.1x0.2)
20,100,200,
400,600&
800oC
Peak
temperature
maintained for
1 hour
Furnace
temperature
curve
2°C/min -
Un
stressed
residual
strength
test
Min Li et al (2004)64
investigated the effect of temperature exposure on
compressive strength, splitting tensile strength and flexural strength of normal and
high strength concrete. Oil furnace was used in this study for heating the specimens.
The temperature time curve was close to the standard curve, which conforms to
Chinese standard GB/T 9978-1999. After being heated to temperatures of 200, 400,
600, 800 and 1000°C respectively, the mechanical properties of HSC were found.
The influence of temperature, water content, specimen size, strength grade and
temperature profiles on mechanical properties of HSC were discussed. They
concluded that the larger the specimen size, the lesser the strength loss. The salient
features of the test are shown in Table 2.11.
28
Table 2.11 Salient Features of Test Carried out by Min Li et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.415x0.1x0.1)
Cube
(0.1x0.1x0.1)
Cube
(0.15x0.15x0.15)
200, 400,
600, 800&
1000°C
90min
Furnace
temperature
curve
(GB/T
9978-1999)
-
Natural
cooling
by air
Un
stressed
residual
strength
test
B.Persson (2004)82
made a comparison between the performance of vibrated
concrete and that of self consolidating concrete under elevated temperature.
Cylinders and columns were tested by compressive loading with high temperature.
Polypropylene fibers were used to avoid the spalling of concrete. Hydrocarbon and
ISO 384 fire curves were used. Rate of heating was maintained at 240°C and 480°C
per hour. Specimens were heated in the temperature range of 20 to 800°C and
specimens were slowly cooled upto room temperature and tested. It was observed
from the test results that explosive spalling took place for columns with SCC but
not for columns with vibrated concrete, even through the vibrated concrete columns
were cured exactly as SCC columns. It was reported that spalling mainly depended
on the stress in the concrete, cement powder ratio and w/c ratio. Lower elastic
modulus at fire temperature was observed in SCC than that in vibrated concrete.
The salient features of the test are shown in Table 2.12.
Table 2.12 Salient Features of Test Carried out by B.Persson
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.1x0.2)
Prestressed
column
(2x0.2x0.2)
20, 200, 400,
600 & 800°C 2hours
ISO 384 &
modified
hydro carbon
fire curve
240°C/hr&
480°C/hr
60°C/hr
Un
stressed
residual
strength
test
Xudong Shi et al (2004)97
carried out an experimental investigation on flexural
members exposed to fire load to understand the effect of cover thickness on the
resistance of members. They varied the cover from 10mm to 30mm. The bottom
29
surface and the two lateral surface of the specimen were heated. They reported that
the bottom concrete cover had significant influence on the ultimate loading capacity
of the specimens, but the extent of this influence decreased with an increase in the
concrete cover thickness. It was found that, it is improper to excessively increase
the bottom concrete cover thickness to improve the fire resistance of the specimens.
Also the beneficial effect of the lateral concrete cover was found to be lower than
that of the bottom concrete cover. The salient features of the test are shown in Table
2.13.
Table 2.13 Salient Features of Test Carried out by Xudong Shi et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type
of
test
Beam
(1.3x0.1x0.18
1.3x0.1x0.19
1.3x0.1x0.20)
900°C 150 min
Furnace
temperature
curve
- - -
A.Ferhat Bingol and Rustem Gul (2004)25
investigated the effect of high
temperature on compressive strength of concrete with the aim to produce a fire
resistant concrete. Concrete was made by replacing ordinary aggregate with pumice
in the ratios of 25, 50, 75 and 100% in volume. The temperature values were chosen
as 150, 300,450,600 and 750°C. The effect of heating duration over the
compressive strength was also examined and different types of concrete mixtures
were heated for durations of one hour, three hours and five hours for each of
temperature values. It was observed that the quality of concrete deteriorated at
150°C and specimen began to lose some strength at this temperature. Though the
considerable strength loss was not noticed from 150 to 300°C, all types of concrete
mixtures continued to lose their compressive strength after 300°C. Every concrete
mixture lost a significant part of their initial strength when the temperature reached
750°C. It was reported that the heating duration did not affect the strength loss
significantly but a high temperature was found to be a significant parameter on the
strength loss. The salient features of the test are shown in Table 2.14.
30
Table 2.14 Salient Features of Test Carried out by A.FerhatBingol and RustemGul
Size of
the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.1 x 0.2)
150,
300,450,600
and 750°C
Peak
temperature
maintained
for 1,3 and 5
hours
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Gai-FeiPeng et al (2006)27
carried out an investigation to explore the relationship
between occurrence of explosive spalling and residual mechanical properties of
fiber toughened high performance concrete exposed to high temperatures. The
residual mechanical properties measured were compressive strength, tensile
splitting strength and fracture energy. A series of concretes were prepared using
ordinary Portland cement and crushed limestone. Steel fiber, polypropylene fiber,
and hybrid fiber (polypropylene fiber and steel fiber) were added to enhance the
fracture energy of the concrete. After exposure to high temperatures ranged from
200 to 800 °C, the residual mechanical properties of fiber toughened high
performance concrete were investigated. For fiber concrete, although residual
strength was decreased by exposure to high temperatures over 400 °C, residual
fracture energy was significantly higher than that before heating. Incorporating
hybrid fiber seems to be a promising way to enhance the resistance of concrete to
explosive spalling. The salient features of the test are shown in Table 2.15.
Table 2.15 Salient Features of Test Carried out by Gai-FeiPeng et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1
x0.1)
Beam
(0.3x0.1x0.1)
200, 400,
600 &
800°C
Peak
temperature
maintained
for 1 hour
Furnace
temperature
curve
10°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
Metin husem (2006)63
examined the variation of compressive and flexural
strengths of ordinary and high performance micro concrete at high temperature.
31
Compressive and flexural strengths of ordinary and high performance micro
concrete which were exposed to high temperatures (200, 400, 600, 800 and 1000°C)
and cooled differently (in air and water) were obtained. Compressive and flexural
strengths of these concrete samples were compared with each other and then
compared with the samples which had not been heated. Strength loss curves of these
concrete samples were compared with the strength loss curves given in the codes.
The results indicate that strength of concrete decreases with increasing temperature
and the decrease in the strength of ordinary concrete was more than that of the high
performance concrete. The type of cooling was found to affect the residual
compressive and flexural strength, the effect being more pronounced as the
temperature increases. Strength loss curves obtained from this study were found to
be in agreement with the strength loss curves given in the Finnish Code. The salient
features of the test are shown in Table 2.16.
Table 2.16 Salient Features of Test Carried out by Metin husem
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.15x0.3)
Beam
(0.04x0.04
x0.16)
200, 400,
600, 800&
1000°C
-
Furnace
temperature
curve
5.5&
6.67°C/min
Air and
water
Un
stressed
residual
strength
test
A.Noumowe et al (2006)77
carried out an investigation to understand the behavior
of conventional vibrated high strength concrete and self compacting high strength
concrete at high temperature. Based on the results they concluded that, the residual
mechanical properties of self compacting high strength concretes were similar to
those of conventional high strength concrete. The risk of spalling for self
compacting high strength concrete was greater than that of conventional high
strength concrete. The tests showed that severe spalling could occur with self
compacting high strength concrete even at a heating rate as low as 0.5°C/min. The
salient features of the test are shown in Table 2.17.
32
Table 2.17 Salient Features of Test Carried out by A.Noumowe et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate
of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.16x0.32)
Beam
(0.4x0.1x0.1)
400, 600°C -
Furnace
temperature
curve
0.5°C/
min
Cooling
as per
(RILEM
TC-129)
Un
stressed
residual
strength
test
Y.F.Chang et al (2006)15
carried out an investigation to obtain complete
compressive stress–strain relationship for concrete after heating to temperatures of
100 to 800°C. All concrete specimens were standard cylinders of diameter 150 mm
and height 300 mm, made with siliceous aggregate. The heated specimens were
tested at 1 month after they were cooled to room temperature. From the results of
108 specimens with two original unheated strengths, a single equation for the
complete stress–strain curves of heated concrete was developed. Through the
regression analysis, the relationships of the mechanical properties with temperature
were proposed to fit the test results, including the residual compressive strength,
peak strain and elastic modulus. The equation proposed is applicable to unheated
and heated concrete specimens at different temperatures. In addition, the split
cylinder tests of 54 specimens were also found and a relationship between splitting
tensile strength and temperature was established. The salient features of the test are
shown in Table 2.18.
Table 2.18 Salient Features of Test Carried out by Y.F.Chang et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.15x0.3)
100,200,300,
400,500,600,
700& 800°C
Peak
temperature
maintained
for 1.5 to 2.5
hours
Furnace
temperature
curve
1 to
4.5°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Kosmas K. Sideris (2007)58
carried out an investigation on the mechanical
properties of self consolidating concrete subjected to elevated temperatures up to
700°C. Eight different concretes (four self consolidating and four conventional)
33
having different strength categories were produced. At the age of 120 days,
specimens were placed in an electrical furnace and heated at a rate of 5°C/min until
the desired temperature was reached. Temperatures of 100, 300, 500, and 700°C
were maintained for 1 h. Specimens were then allowed to cool in the furnace and
tested for compressive strength, splitting tensile strength, and ultrasonic pulse
velocity. Similar tests were also performed at room temperature (20°C) for the
reference specimens. Residual strengths of both SCC and Conventional concrete
were reduced almost in a similar manner upto the maximum temperature reached.
Explosive spalling occurred in both SCC and CC of the highest strength category at
temperatures greater than 380°C. The residual compressive strength of SCC
mixtures was higher than the one of CC mixtures for the same strength class. The
tentative spalling behaviors of SCC and CC were the same and depended only on
the strength category. The salient features of the test are shown in Table 2.19.
Table 2.19 Salient Features of Test Carried out by Kosmas K. Sideris
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1
&0.15x0.15)
Cylinder
(0.15x0.3)
100,300,
500 &
700oC
Peak
temperature
maintained
for 1hour
Furnace
temperature
curve
5°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Esref Unluoglu et al (2007)23
investigated the mechanical properties of structural
reinforcement after the exposure to high temperatures. Plain steel and reinforcing
steel bars embedded into mortar and plain mortar specimens were prepared and
exposed to 20, 100, 200, 300, 500, 800 and 950 °C temperature for 3 hours
individually. The S420 deformed steel bars with diameters of B10, B16 and B20
were used. The tension tests on reinforcements taken from cooled specimens and
the variations in yield strength, ultimate strength and in resilience of three different
dimensioned reinforcements were determined. For the temperatures upto 500°C, the
reinforcing steel specimens with cover had the same yield strength and tensile
strength with that of the reinforcing steels without high temperature exposure.
34
However, when the temperature exceeded 500°C, the reinforcing steel with cover
was found to lose the strength. It was observed that 25 mm cover thickness was not
sufficient to protect the mechanical properties of reinforcing steel when the
structure is exposed to temperatures over 500°C. It is required to provide sufficient
concrete cover thickness to protect reinforcements from fire reaching the
temperatures over 500°C. The salient features of the test are shown in Table 2.20.
Table 2.20 Salient Features of Test Carried out by Esref Unluoglu et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Mortar
(0.06x0.06x0.3
0.066x0.066x0.3
0.07x0.07x0.37)
20°C,
100°C,
200°C,
300°C,
500°C,
800°C&
950°C
Peak
temperature
maintained
3 hours
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Omer Arioz (2007)78
presented the effects of elevated temperatures on the physical
and mechanical properties of various concrete mixtures prepared using ordinary
Portland cement, crushed limestone, and river gravel. Specimens were subjected to
elevated temperatures ranging from 200 to 1200ºC. After exposure, weight losses
and the compressive strength were found out. Test results indicated that weight of
the specimens significantly reduced with an increase in temperature. This reduction
was very sharp beyond 800ºC. The effects of water/cement ratio and type of
aggregate on losses in weight were not found to be significant. The results also
revealed that the relative strength of concrete decreased as the exposure temperature
increased. The salient features of the test are shown in Table 2.21.
Table 2.21 Salient Features of Test Carried out by Omer Arioz
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.07x0.07x0.07)
200°C to
1200°C 2 hours
Furnace
temperature
curve
20°C/min
2°C/min
Un
stressed
residual
strength
test
35
Serdar Aydin and Bulent Baradan (2007)85
investigated the effects of high
temperature on the mechanical properties of cement based mortars containing
pumice and flyash. Four different mortar mixtures with varying amounts of flyash
were exposed to high temperatures of 300, 600, and 900°C for 3 h. The residual
strength of these specimens was determined after cooling by water or air.
Microstructure formations were investigated by X-ray and SEM analyse. The
pumice mortar incorporating 60% flyash was found to have the best performance
particularly at 900°C. This mixture did not show any loss in compressive strength at
all test temperatures when cooled in air. The superior performance of 60% FA
mortar may be attributed to the strong aggregate cement paste interfacial transition
zone and ceramic bond formation at 900°C. However, all mortar specimens were
found to have severe losses in terms of flexural strength. Furthermore, specimens
cooled in water showed greater strength loss than the air cooled specimens.
Nevertheless, the developed pumice, flyash and cement based mortars seemed to be
a promising material in reducing high temperature hazards. The salient features of
the test are shown in Table 2.22.
Table 2.22 Salient Features of Test Carried out by Serdar Aydin and Bulent Baradan
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
0.04x0.04x1.6
300°C,
600°C&
900°C
Peak
temperature
maintained
for three
hours
Furnace
temperature
curve
10°C/min
Water
soaking
&Air
cooling
Un
stressed
residual
strength
test
Ilker Bekir Topcu and Cenk Karakurt (2008)38
carried out an experiment on hot
rolled S220 and S420 reinforcement steel rebars that were subjected to high
temperatures and subsequently cooled to room temperature to understand the
behaviour of these materials under fire. The deterioration of the mechanical
properties of yield strength and modulus of elasticity is considered as the primary
element affecting the performance of steel structures under fire. It was aimed to
determine the residual mechanical properties of steel rebars after exposing them to
36
elevated temperatures. Steel bars were subjected to 20, 100, 200, 300, 500, 800 and
950oC temperatures for 3 hours and tensile tests were carried out. Effects of
temperature on mechanical properties of S220 and S420 were determined. All
mechanical properties of the steel rebars were reduced due to the temperature
increase. It is seen that mechanical properties of S420 steel were affected more than
those of S220 steel at elevated temperatures. The authors suggest that the protective
cover thickness should be higher for increasing the fire safety of reinforced concrete
members. The salient features of the test are shown in Table 2.23.
Table 2.23 Salient Features of Test Carried out by Ilker Bekir Topcu
and Cenk Karakurt
Size of the
specimen (m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
S220 and
S420 Steel
Rebars
(10mm and
16mm dia&
200mm
Length)
20,100,200,
300,500,800
&
950oC
Peak
temperature
maintained for
three hours
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
M.C.Alonso et al (2008)4 carried out an experimental investigation on Self
Compacting Concrete reinforced with polymeric fibers (Polypropylene fibers, PPF).
First, the mechanical and micro structural characterization was determined. Further
the influence of the presence of the PPF in the SCC durability properties of the
material was studied at laboratory, using different indicators. Finally, the response
of both types of material with respect to resistance at high temperature was
evaluated through micro structural analysis. The results indicated that porosity,
capillary suction, transport of chloride and depth of carbonation for the self
compacting concrete with and without fibers are very similar. The salient features
of the test are shown in Table 2.24.
37
Table 2.24 Salient Features of Test Carried out by M.C.Alonso et al
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
SCC Beams
(0.4 x 0.1 x
0.1)
Cylinder
(0.075 x
0.1)
20,200,300,
500 &
700oC
Peak
temperature
maintained
for two hours
Furnace
temperature
curve
2oC/min
<1oC/min
Natural
cooling
by air
Un
stressed
residual
strength
test
R.H. Haddad et al (2008)29
evaluated the bond behavior between fiber reinforced
concrete and 20mm reinforcing steel rebars under elevated temperatures. Fifty
modified pullout specimens (100x100x400 mm) were prepared using high strength
concrete with basalt aggregate and different volumetric mixtures of three types of
fibers, namely brass coated steel fibers, hooked steel fibers, and high modulus
polypropylene fibers. Specimens, designated for heat treatment, were then subjected
to elevated temperatures, ranging from 350 to 700oC, whereas unheated (control)
ones were kept in the laboratory. The overall response of control and heat damaged
specimens, cracking extent and the continuity were described. Standard cubes
(100x100x100) were cast, cured, and heat treated under similar conditions and then
tested to evaluate the compressive and splitting tensile strengths. The results
indicated significant reduction in the residual compressive, splitting and steel–
concrete bond under high temperatures with dramatic changes in bond stress free
end slip trend behavior. Use of fibers minimized the damage in steel–concrete bond
under elevated temperatures and hence the reduction in bond strength. Specimens
which incorporated hooked steel fibers attained the highest bond resistance against
elevated temperatures followed, in sequence, by those prepared with the mixture of
hooked and brass coated steel, the mixture of hooked steel and polypropylene, and
brass coated steel fibers. Statistical models were developed to describe the
relationship between the bond strength and exposure temperature. The salient
features of the test are shown in Table 2.25.
38
Table 2.25 Salient Features of Test Carried out by R.H. Haddad et al
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.4x0.1x0.1)
Cube
(0.1x0.1x0.1)
350, 500,
600&700oC
Peak
temperature
maintained
for two hours
Furnace
temperature
Curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Ilker Bekir Topcu and Burak IsIkdag (2008)37
studied the mechanical properties
of structural rebars after exposure to elevated temperatures. The mortar was
prepared with CEM I 42.5N cement and fired clay. The S420a, B16 mm ribbed
steel bars were used to prepare the specimens with the covers of 20, 30, 40 and 50
mm against elevated temperatures up to 800°C. The rebars were embedded in
mortars and then specimens were exposed to 20, 100, 200, 300, 500 and 800°C
temperatures for 3 h, individually. The mechanical tests were conducted on cooled
specimens, and the ultimate tensile strength, yield strength and elongation of mortar
specimens at various temperatures were also determined at the end of the
experiments. It was observed that 20–30–40–50 mm cover thickness was not
sufficient to protect the mechanical properties of rebars when exposed to above
500°C temperature. Therefore required cover thickness of concrete must be
calculated regarding protection of reinforcement up to peak temperatures. The
salient features of the test are shown in Table 2.26.
Table 2.26 Salient Features of Test Carried out by Ilker Bekir Topcu
and Burak IsIkdag
Size of the
specimen (m)
temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.056x0.056
x0.29
0.076x0.076
x0.31
0.096x0.096
x0.33
0.116x0.116
x0.35)
20°C,
100°C
200°C,
300°C,
500°C&
800°C
Peak
temperature
maintained
for 3 hours
Furnace
temperature
Curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
39
Anagnostopoulos et al (2009)5 carried out an investigation to determine the
influence of different fillers on the properties of SCC of different strength classes
when exposed to high temperatures. They reported that explosive spalling occurred
in both the cases of SCC and NCC when the oven peak temperature of 600°C is
maintained. SCC was found to spall more compared to NCC due to lower
permeability and higher moisture content. SCC with ladle furnace slag in its
composition was found to have higher compressive strength at the age of 28 days
due to slag’s cementitious behavior, but was more susceptible to spalling effects
after fire exposure compared to other mixtures. SCC produced with glass filler had
greater rheological characteristics at fresh state condition, but did not perform well
after exposure to high temperatures. SCC produced with limestone filler was found
to have better performance compared to mixtures prepared with different filler
materials. The salient features of the test are shown in Table 2.27.
Table 2.27 Salient Features of Test Carried out by Anagnostopoulos et al
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1
x0.1)
Cylinder
(0.15x0.3)
300& 600°C
Peak
temperature
maintained for
one hour
Furnace
temperature
curve
10°C
/min
Natural
cooling
by air
(24 hrs)
Un
stressed
residual
strength
test
Udaya kumar et al (2009)92
carried out an investigation to generate experimental
data on residual flexural strength of heated RCC beams and their strengthening
using various repair techniques. A total of 25 RCC beams were cast with similar
cross sectional details, length, grade of concrete and clear cover. Twenty beams
were tested after fire exposure and the remaining five were used as companion
beams. The beams were heated in two stages. In the first stage, two beams were
kept at each temperature for 3 h between 100°C and 1000°C, in increments of
100°C. Beams exposed to temperature ranging between 100 and 500°C were
repaired by applying paint. The beams exposed to temperature ranging between 600
and 1000°C were repaired for spalling. In the second stage, all repaired specimens
40
were again heated. These test specimens were tested for flexural strength after
bringing them to room temperature. The variation of flexural strength of repaired
RCC beams with increase in temperature was studied and the flexural strength of
beams before and after the repair was compared. The salient features of the test are
shown in Table 2.28.
Table 2.28 Salient Features of Test Carried out by Udayakumar et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(1.2x0.112x0.24)
100 to
1000°C
Peak
temperature
maintained
for three
hour
ISO 834
fire curve -
Natural
cooling
by air
Un
stressed
residual
strength
test
Tayfun Uygunoglu and Ilker Bekir Topcu (2009)91
Studied the effects of
aggregate type on the coefficient of thermal expansion of self consolidating
concrete produced with normal and lightweight aggregate at elevated temperature.
Two types of aggregates namely crushed limestone and pumice were used.
Different combinations of water/powder ratio and super plasticizer dosage levels
were prepared for the SCC and Self Consolidating Lightweight Concrete (SCLC)
mixtures. The total powder content (cement and mineral additives) was constant in
the experiments. Thermal test was performed to accurately characterize the
Coefficient of Thermal Expansion (CTE) of SCC and SCLC aged 28 days using the
dilatometer. The CTEs of SCC and SCLC were defined by measuring the linear
change in length of concrete specimens subjected to a range of temperatures. Test
temperatures were varied from 20 to 1000°C at a heating rate of 5°C/min. The
results, in general, showed that SCC has higher CTE than normal weight concrete
and that lightweight aggregate reduced the CTE of SCC due to their porous
structure. The aggregate type has significant influence on the thermal expansion of
SCC. The salient features of the test are shown in Table 2.29.
41
Table 2.29 Salient Features of Test Carried out by Tayfun Uygunoglu
and Ilker Bekir Topcu
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type
of
test
Cube
(0.07x0.07x0.07)
Cylinder
(0.15x0.3)
20 to 1000°C -
Furnace
temperature
curve
5°C
/min - -
Hanaa Fares et al (2009)32
carried out an experimental study on the performance
of self consolidating concrete subjected to high temperature. Two SCC mixtures
and one vibrated concrete were tested. Mechanical and micro structural properties
were studied at ambient temperature and after heating. Compressive strength,
flexural strength, bulk modulus of elasticity, porosity and permeability of these
concretes were found. For each test, the specimens were heated at a rate of 1 °C/
min upto desired target temperatures (150, 300, 450 and 600°C). In order to ensure
a uniform temperature throughout the specimen, the temperature was held constant
at the target temperature for 1 h before cooling. In addition, the specimen mass was
measured before and after heating in order to determine the loss of water during the
test. The salient features of the test are shown in Table 2.30.
Table 2.30 Salient Features of Test Carried out by Hanaa Fares et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.16×0.32)
Prism
(0.1x0.1x0.4)
150, 300,
450 &
600oC
Peak
temperature
maintained
for one hour
Furnace
temperature
curve
1°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
Jin Tao et al (2010)51
reported the results of laboratory investigations carried out to
study the effects of high temperatures ranging from room temperature to 800°C on
the compressive strength of SCC and HSC. It was reported that the hot compressive
strength of SCC decreased with increase in temperature. It was found that grade of
concrete had an effect on the strength loss of concrete, especially in the temperature
range below 400°C. Higher grades of SCC resulted in higher loss of strength. But
42
this difference was found to be less in the permanent strength loss stage. Compared
with normal strength SCC, high strength SCC was found to possess a larger
compressive strength when exposed to high temperature. It was also reported that
addition of polypropylene fibers decreased the strength .However the addition
reduced the probability of explosive spalling. The salient features of the test are
shown in Table 2.31.
Table 2.31 Salient Features of Test Carried out by Jin Tao et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.15x0.3)
200 to
800°C -
Furnace
temperature
curve
5°C/min &
30°C/min
above
500°C
-
Un
stressed
residual
strength
test
Sivaraja (2010)87
studied the effect of high temperature on mechanical strength
properties of five different self compacting concrete mixes. Initially five different
SCC mixes such as normal concrete, SCC (Self Compacting Concrete) with flyash,
SCC with silica fume, SCC with rice husk ash and SCC with 20% quarry sand were
designed. The fresh concrete properties such as filling ability and passing ability
were ascertained. Specimens were subjected to high temperature up to 500°C and
1000°C for 1 hour in hot furnace. Mechanical properties such as compressive
strength, split tensile strength and modulus of rupture were obtained by conducting
respective tests as per Indian Standards. Results of specimens subjected to high
temperature were compared with those of conventional specimens. The salient
features of the test are shown in Table 2.32.
Table 2.32 Salient Features of Test Carried out by Sivaraja
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.15x0.15
x0.15)
Cylinder
(0.15X0.3)
Beam
(0.5x0.1x0.1)
500 and
1000°C
Peak
temperature
maintained
for one
hour
Furnace
temperature
curve
5°C
/min
Natural
cooling
by air
Un
stressed
residual
strength
test
43
Subhash C. Yaragal et al (2010)88
tested the cube samples subjected to elevated
temperatures ranging from 100oC to 800
oC, in steps of 100
oC with a retention
period of 2 hours. After exposure, weight losses and the residual compressive
strength retention characteristics were studied. Test results indicated that weight and
strength significantly reduced with an increase in temperature. As the exposed
temperature increased, loss in weight of specimen increased, above 200oC. With
increase in grade of concrete, there was a decrease in loss of weight of specimen
after subjecting it to elevated temperatures. In general there was a substantial loss
(74%) in strength from 100oC to 800
oC for M20, M25 & M30 grades of concretes.
However for M35, M40 & M45 grades, strength loss was 80%. The observed
minimum residual strength was 18% for M45 at 800oC. Residual compressive
strength prediction equations for two ranges of temperature were derived for normal
strength concretes. The salient features of the test are shown in Table 2.33.
Table 2.33 Salient Features of Test Carried out by Subash C. Yaragal et al
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15
x0.15x0.15)
100oC to
800oC
Peak
temperature
maintained
for two hour
Furnace
temperature
curve
2oC/min
Natural
cooling
by air
Un
stressed
residual
strength
test
I.K. Fang et al (2010)24
designed three full scale beam exterior column sub
assemblage specimens, according to ACI 318 seismic provisions and these
specimens were subjected to ISO 834 fire test to check the fire resistance. Two
specimens were made of self compacting concrete and one was made of Normal
Concrete (NC). Analysis based on thermal properties of materials suggested in
Eurocode 2 and ANSYS software was carried out to predict the temperature
distribution of specimens. The specimens performed satisfactorily after subjecting
them to three hours of fire as per ISO 834 fire curve. The significant explosive
spalling occurred in about 25 minutes after heating. The beam deflection at the end
of heating was approximately 10 times that before heating. Most of the concrete
44
spalling occurred along the bottom edge of beams and corner of lower column
during the early twenty five minutes of heating. Relatively more spalling was
observed at bottom of the beam for the normal concrete specimen. Most of the
vertical displacements in the beam occurred in the first thirty minutes of heating,
and then the increase of vertical displacement decreased during the thirty to sixty
minutes due to the low temperature rise in beam. The normal and self compacting
concrete specimens behaved quite closely in their load displacement relationships at
load in the residual strength test. Two specimens failed in ductile flexural mode and
one specimen failed in unfavorable diagonal shear after exhibiting significant yield
behavior in beams. The salient features of the test are shown in Table 2.34.
Table 2.34 Salient Features of Test Carried out by I.K. Fang et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Column
(0.5 x 0.5 x
2.86)
Beam
(7.68x 0.4 x 0.5)
1193oC 180 min
ISO 834
Standard
Temperature
Curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Bahar Demirel and Oguzhan Kelestemur (2010)6 investigated the effect of
elevated temperature on the mechanical and physical properties of concrete
specimens obtained by substituting cement with Finely Ground Pumice (FGP) at
proportions of 5%, 10%, 15% and 20% by weight. To determine the effect of silica
fume on the mechanical and physical properties of concrete containing FGP, SF
was added to all specimens except the control specimen. The specimens were
heated in an electric furnace up to 400, 600 and 800°C and kept at these
temperatures for one hour. After the specimens were cooled, Ultrasonic Pulse
Velocity (UPV), compressive strength and weight loss values were determined. The
results demonstrated that addition of the mineral admixtures to concrete decreased
both unit weight and compressive strength. It was also found that elevating the
temperature above 600°C affected the compressive strength to a larger extent. The
weight loss of concrete was more pronounced for concrete mixtures containing both
45
FGP and SF. SEM investigations conducted on the specimens confirmed the
deformation of well-developed Ca(OH)2 crystals and the C-S-H gel at temperatures
beyond 600°C. This study demonstrates that the critical temperature for concrete
specimens containing FGP or FGP and SF was 600°C, because all the hydrated
phases including C-S-H and Ca(OH)2 appeared to have amorphous structures at this
temperature instead of their characteristic crystal structures. The salient features of
the test are shown in Table 2.35.
Table 2.35 Salient Features of Test Carried out by Bahar Demirel and
Oguzhan Kelestemur
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1 x 0.1 x
0.1)
20,400,600,
800oC
Peak
temperature
maintained
for one
hour
Furnace
temperature
curve
2.5oC/min
Natural
cooling
by air
Un
stressed
residual
strength
test
Hanaa Fares et al (2010)33
carried out an experimental study on the properties of
self compacting concrete subjected to high temperature. Two SCC mixtures and one
vibrated concrete mixture were tested. These specimens were heated at a rate of
1°C/min upto temperatures of 150, 300, 450 and 600°C. In order to ensure a
uniform temperature distribution throughout the specimens, the temperature was
held constant at the maximum temperature for 1h before cooling. Physicochemical
properties and the micro structural characteristics were studied. Thermo gravimetric
analysis, thermo differential analysis, X-ray diffraction and SEM observations were
made. It was observed from the results that the residual compressive strength
increased between 150 and 300°C. The salient features of the test are shown in
Table 2.36.
Table 2.36 Salient Features of Test Carried out by Hanaa Fares et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cylinder
(0.16×0.32)
Prism
(0.1x0.1x0.4)
150, 300,
450 &
600oC
Peak
temperature
maintained
for one hour
Furnace
temperature
curve
1°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
46
Ilker Bekir Topcu et al (2011)36
studied the effect of high temperatures on the
mechanical properties of the reinforcement bars placed between 3 and 5 cm covers
inside the mortar specimens. These reinforced mortar specimens were exposed to
20, 100, 200, 300, 500 and 800°C temperatures. Then these bars were taken out of
these mortar specimens and the mechanical properties were found. The results of
the study indicated that larger covers gave better protection to the steel bars against
high temperatures. The salient features of the test are shown in Table 2.37.
Table 2.37 Salient Features of Test Carried out by Ilker Bekir Topcu et al
Size of
the specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.076x0.076
x0.31
0.116x0.116
x0.35)
20°C,
100°C,
200°C,
300°C,
500°C&
800°C
Peak
temperature
maintained
for three
hour
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
S. Bakhtiyari et al (2011)9 evaluated the fire resistance of self compacting concrete
(SCC) containing limestone and quartz powders, with two different compressive
strengths, and compared with normal concrete. The residual mechanical strength of
the mixes at different temperatures was measured. The changes in the phase
composition of the cement pastes at high temperatures were examined with thermal
analysis and X-ray diffractometry methods. The SCC mixes showed a higher
susceptibility to spalling at high temperatures but the NC mixes suffered a higher
strength loss. Both the powder types and the compressive strength notably
influenced the fire behavior of the SCC. The quartz powder accelerated the
hydration of the SCC cement paste at high temperatures, up to 500°C. However, the
quartz contained SCC showed the highest risk of spalling among all the mixes. The
results showed that the thermal analysis could be a useful device for evaluating the
fire behavior of building materials. The salient features of the test are shown in
Table 2.38.
47
Table 2.38 Salient Features of Test Carried out by S. Bakhtiyari et al
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15
x0.15)
Cylinder
(0.15x0.3)
150°C,
500°C,
750°C&
1000°C
Peak
temperature
maintained
for two
hour
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
S. Bakhtiyari et al (2011)8 developed self compacting concrete specimens with
limestone (L) and quartz (Q) powder. The influence of this type of the powder on
the properties of fresh and hardened concrete was evaluated. Dense packing theories
were used for the mix design of samples. The equation of Fuller and Thompson for
Particle Size Distribution (PSD) of aggregates was modified considering fine
particles and a proper PSD curve was obtained for SCC. Experimental results
showed that this method needs use of less powder content and results in higher
strength/cement ratio compared to traditional mixing methods. No significant
difference was observed between the compressive strengths of specimens
containing limestone (L-specimens) and quartz (Q-specimens) powder, with similar
proportions of materials. The residual compressive strength of specimens was
examined at 500°C and contradictory behavior was observed. The type of powder
played an important role in the behavior of SCC at high temperatures. The use of
the quartz powder accelerated the hydration process and led to the development of
strength at high temperatures, around 500°C. The reason for this phenomenon is the
partial pozzolanic effect of the quartz, at an internal autoclaved condition produced
at these temperatures. Therefore, the porosity of concrete decreased and
consequently the pore pressure increased, which in turn increased the tendency of
spalling of concrete. However, as the mechanical strength of sample also increased
with development of hydration, it might overcome the produced pore pressure. In
this situation, if tensile strength of the concrete prevails over the pore pressure and
thermal stresses, spalling will not occur and the compressive strength of the
concrete will considerably increase. Such a behavior can be also seen for concretes
48
containing silica fume, because of its high pozollanic activity. The SCC containing
limestone powder has a lower risk for spalling, but its mechanical strength is
decreased with increasing temperature. About 15% reduction of the compressive
strength can be expected at temperatures around 500°C. The salient features of the
test are shown in Table 2.39.
Table 2.39 Salient Features of Test Carried out by S. Bakhtiyari et al
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15
x0.15)
Cylinder
(0.15x0.30)
500°C
Peak
temperature
maintained
for two hour
Furnace
temperature
curve
10°C/
min
Natural
cooling
by air
(24 hrs)
Un
stressed
residual
strength
test
Wasim Khaliq and Venkatesh Kodur (2011)95
presented the effect of temperature
on thermal and mechanical properties of self consolidating concrete and Fiber
Reinforced SCC (FRSCC). Specific heat, thermal conductivity and thermal
expansion of the specimens were measured. Compressive strength, tensile strength
and elastic modulus were found in the temperature range of 20–800°C. Four SCC
mixes, plain SCC, steel, polypropylene and hybrid fiber reinforced SCC were
considered in the test program. Temperature was found to have a significant
influence on thermal conductivity, specific heat and thermal expansion of SCC and
FRSCC. The thermal conductivity generally decreased with temperature, while the
thermal expansion increased with temperature up to 800°C. However, specific heat
remained almost constant up to about 400°C, and then increased with presence of
steel fibers. Data from mechanical property tests indicated that the presence of steel
fibers increased the high temperature splitting tensile strength and elastic modulus
of SCC. Thermal expansion of FRSCC was found to be slightly higher than that of
SCC in 20–1000°C range. Data generated from these tests were utilized to develop
simplified relations for expressing thermal and mechanical properties of SCC and
FRSCC as a function of temperature. The salient features of the test are shown in
Table 2.40.
49
Table 2.40 Salient Features of Test Carried out by Wasim Khaliq
and Venkatesh Kodur
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cylinder
(0.1x0.2
0.075x0.15)
Prism
(0.10x0.10
x0.30)
20°C to
800°C
Peak
temperature
maintained
for two
hour
RILEM
Technical
committee
TC-129
(Furnace)
5°C/
min &
2°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
Manolia Abed Al-Wahab Ali (2011)62
investigated the residual mechanical
properties (compressive strength, modulus of rupture and dynamic modulus of
elasticity) of self compacting concrete exposed to elevated temperatures ranging
from 100-800oC. Also he studied the influence of High Reactivity Metakaolin
(HRM), as a partial replacement of cement, for improving the mechanical properties
before and after exposure to elevated temperatures. The concrete specimens were
subjected to a temperature of 100, 200, 400, 600 and 800°C with exposure duration
of 2 hours. The performance of SCC containing HRM was found to be better than
that of SCC without HRM. The residual compressive strength of SCC with HRM
after an exposure to a temperature of 800oC was found to be 73.2% while for the
normal SCC the residual strength was only 65% of the original strength. At the
same exposure temperature of 800oC, the reduction in the modulus of rupture was
found to be more than that of compressive strength, the difference being in the
range 2% - 12.4%. The reduction in the dynamic modulus of elasticity was found to
be higher than that of the compressive strength and modulus of rupture. The salient
features of the test are shown in Table 2.41.
Table 2.41 Salient Features of Test Carried out by Manolia Abed Al-Wahab Ali
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15x0.15)
Prism
(0.10x0.10x0.5)
100°C,200°C,
400°C,
600°C&
800°C
2 hr
Furnace
temperature
curve
2°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
50
J.E. Park et al (2011)81
investigated the behavior of high strength concrete
columns at elevated temperatures including temperature distributions and spalling.
Seven short HSC columns having different design parameters were fabricated and
placed in a heating chamber for fire tests. The design parameters are cross sectional
areas, cover thicknesses, and arrangements of reinforced bars. The columns were
heated using temperature control system following ISO 834 time temperature curve.
Temperature distributions were obtained from temperature gauges located inside the
columns during the fire tests, and the spalling depths of the columns were measured
after the fire tests in order to examine the reduction in the cross sectional area due to
spalling. They reported that cross sectional area, cover thickness, and reinforcement
arrangements, affected the temperature distribution and spalling of HSC columns.
The column with the larger cross sectional area and thinner concrete cover showed
the higher temperature distributions. Even with a same reinforcement ratio, the
more distributed arrangement of reinforcing bars resulted in the higher temperature
distributions of the HSC column. Spalling of the HSC column was found to be
highly related to the temperature distribution; that is the HSC column showing the
higher temperature distributions resulted in the larger spalling. However, the effect
of cross sectional area of the column on area loss was not significant. The salient
features of the test are shown in Table 2.42.
Table 2.42 Salient Features of Test Carried out by J.E. Park et al
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type
of
test
HSC Column
1.5x0.35x0.35
1.5x0.45x0.45
1.5x0.55x0.55
1193oC 160 min
ISO 834
Standard
Temperature
Curve
-
- -
Jayasree.G et al (2011)50
carried out an investigation to determine the residual
characteristics of RC beams subjected to elevated temperature under unstressed and
stressed conditions. The RC beams were of size120mmx120mmx1500mm and
designed with single and double reinforcement and designated as Type I and Type
II respectively. M20 grade of concrete was used. The temperatures were kept as
51
100°C, 200°C, 300°C, 400°C and 500°C and the duration of exposure was 4 hours.
The specimens were cooled in air and the residual properties were tested by
conducting two point bending test on RC beams and their behavioral parameters
were compared with those of the reference specimens. The extent of damage
suffered was measured by the damage factor and was found to be around 32 % for
Type I beams and 48% for the Type II beams when tested under unstressed test
condition and exposed to 500°C. The damage factor was around 33% for Type I
beams and 49% for Type II beams in stressed test condition for the same exposed
temperature. The degradation in stiffness at 50% of ultimate load was nearly 36%
and 35% for Type I and Type II beams in unstressed test and 49% and 76.6%
respectively for stressed test when exposed to 500°C. The ultimate load of RC
beams tested in stressed condition was only 5% lower than that of the beams under
unstressed test condition. The salient features of the test are shown in Table 2.43.
Table 2.43 Salient Features of Test Carried out by Jayasree.G et al
Size of the
Specimen
(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling
/Coolant
Type of test
Beam
(1.5x0.12
0.12)
100oC,
200oC,
300oC, 400
oC
& 500oC
4 Hours
Furnace
temperature
curve
-
Natural
cooling
by air
Stressed &
Un stressed
residual
strength test
Krishna Rao M.V et al (2011)59
investigated the effect of sustained elevated
temperature on the properties of ordinary concrete of M40 grade containing
different types of cements and cured by two different methods. The specimens were
heated to150°C, 300°C and 450°C for 1 hour duration in a muffle furnace.
Compressive strength of the specimens was found after air cooling to the room
temperature. The variables considered in the study were types of cementing
material, temperature and method of curing. Results indicated the losses of strength
due to high temperature exposure and the presence of 10% silica fume as a cement
replacement seemed to have no significant effect. The compressive strength of
concrete and the weight of concrete decreased with increasing temperature.
52
Specimens subjected to conventional water curing performed relatively better than
those of membrane curing. The salient features of the test are shown in Table 2.44.
Table 2.44 Salient Features of Test Carried out by Krishna Rao M.V et al
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.15x0.15x0.15)
150°C,
300°C&
450°C
Peak
temperature
maintained
for one
hour
Furnace
temperature
curve
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Yining Ding et al (2011)98
analyzed the effect of various fibres on the residual
compressive strength, the ultimate load, flexural toughness, the failure pattern and
the fracture energy of Self Compacting High Performance Concrete (SCHPC) after
exposure to various high temperatures. The micro Polypropylene Fibre (PP fibre)
could mitigate the spalling of SCHPC member significantly, but did not show clear
effect on the mechanic properties of concrete. The macro steel fibre reinforced
SCHPC showed higher flexural toughness and ultimate load before and after high
temperatures. The mechanical properties of Hybrid Fibre reinforced concrete
SCHPC (HFSCHPC) were better than those of mono fibre reinforced SCHPC after
exposure to higher temperature. The failure mode changed from pull out of steel
fibres at lower temperature to breaking down of steel fibres at higher temperature.
The use of hybrid fibre can be effective in providing the residual strength and in
improving the toughness and fracture energy of SCHPC after high temperature. The
combination of steel fibres and PP fibres resulted in positive composite effect on the
post peak behaviour of SCHPC materials before and after exposure to high
temperature. During the high temperature, PP fibre can mitigate or prevent the
explosive spalling, enhance the residual strength and fracture energy, but does not
increase the toughness of SCHPC. Steel fibres were found to improve the residual
compressive strength, enhance the ductility of SCHPC subjected to different high
temperatures, but it was not able to mitigate the spalling of concrete at high
temperature. This observation supports the use of fibre cocktail in SCHPC as a fire
53
resistant material. They concluded that the use of fibre cocktail reinforced SCHPC
material can be very effective in reducing thermal stress and in improving
composite effect of hybrid fibres on the post crack behaviour during heating process
at high temperature. The salient features of the test are shown in Table 2.45.
Table 2.45 Salient Features of Test Carried out by Yining Ding et al
Size of the
specimen
(m)
Temperature
range Time duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1x
0.1)
Beam
(0.1x0.1x
0.4)
300,600,
900°C
Peak
temperature
maintained for
three hour
Furnace
temperature
curve
6°C/min
Natural
cooling
by air
Un
stressed
residual
strength
test
S. Bakhtiyari et al (2011)7 investigated the influence of permanently expanded
polystyrene formwork on the fire resistance of self compacting concrete. SCC was
produced and cured by two different conditions, one by the traditional method and
the other inside expanded polystyrene forms. Normal vibrated concrete with similar
characteristic strength was also produced and cured under the same conditions for
comparison. The specimens were exposed to different high temperatures. The
residual mechanical strengths, phase composition and porosity changes at high
temperatures were investigated. The SCC was found to be more susceptible to
spalling than the normal vibrated concrete. This is due to more packing of the SCC,
giving rise to higher pore pressure at high temperatures. The insulating permanent
forms raised the risk of spalling of concretes and had significant influence on the
residual mechanical strengths of the concrete. The relative residual strength of the
SCC was higher than that of the NC at high temperatures. Hence, if the spalling can
be controlled, for example using polypropylene fibers, the fire resistance of the SCC
can be higher than that of the NC. The loss of residual strength of concrete was not
very significant until 500°C. The relative residual strength of the SCC was
considerably increased around 500°C. It was due to acceleration of hydration at
medium high temperatures, which was confirmed with XRD and porosimetry tests.
The salient features of the test are shown in Table 2.46.
54
Table 2.46 Salient Features of Test Carried out by S. Bakhtiyari et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.15 x 0.15
x 0.15)
Cylinder
(0.15 x 0.30)
150,500,
750 &
1000°C
Peak
temperature
maintained
for two
hour
Furnace
temperature
curve
-
Natural
cooling
by air
(24 hrs)
Un
stressed
residual
strength
test
E.G. Choi and Y.S. Shin (2011)20
investigated the effects of concrete compressive
strength and cover thickness on the structural behavior of reinforced concrete beams
under fire. For this purpose, four normal strength and high strength concrete beams
were fabricated and tested under the ISO 834 standard fire curve to point of the
failure. The test setup was designed to evaluate the heat distribution and
displacement changes of simply supported beams subjected to sustained loads under
fire. Test results for normal strength and high strength concrete beams were
compared for each of the test variables. The test results indicated that the
relationships between time and temperature distributions in the beam sections are
very similar and are unrelated to the strength of the concrete, with the exception of
the upper part of the beam section. It was also found that the rate of increase in the
deflection for both normal strength and high strength concrete beams were very
similar before spalling but became remarkably high for high strength concrete
beams after spalling. A simplified model was proposed to determine the effect of
spalling on the temperature gradient of a high strength concrete beam. The results of
Finite Difference Method (FDM) analysis using this proposed model indicated
temperature gradient that was similar to that of the test results. The salient features
of the test are shown in Table 2.47.
Table 2.47 Salient Features of Test Carried out by E.G. Choi and Y.S. Shin
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.25 x 0.4 x
4.7)
- -
ISO 384
Time
Temperature
Curve
- - Stressed
test
55
Kiang Hwee Tan and Yuqian Zhou (2011)53
investigated the flexural behavior of
Fiber Reinforced Polymer (FRP) strengthened beams after exposure to elevated
temperatures. Twenty five specimens making up un-strengthened beams and FRP
strengthened beams were fabricated. Glass and basalt FRP systems were used with
and without protective systems, which included a cement mortar overlay and two
types of commercially available intumescent coatings. Typical temperature time
histories at the surface of FRP laminates, FRP concrete interface, internal steel bars
and center of beams were monitored by using two specimens. The other specimens
were tested to failure under three point bending after subjecting them to elevated
temperatures. Test results indicated a general decrease in the initial stiffness and
ultimate strength of the specimens with an increase in the exposed temperature. The
protective systems appeared to preserve the structural integrity of glass FRP
systems when the elevated temperature was less around 700°C. Basalt FRP
strengthened beams exhibited less deterioration in ultimate strength than glass FRP
strengthened beams. The salient features of the test are shown in Table 2.48.
Table 2.48 Salient Features of Test Carried out by Kiang Hwee Tan
and Yuqian Zhou
Size of the
specimen (m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.4x0.1x0.1)
950oC
Peak
temperature
obtained
after one
hour
ASTM
E119
(Furnace)
-
Natural
cooling
by air
Un
stressed
residual
strength
test
Neelam Pathak and Rafat Siddique (2012)75
studied the properties of self
compacting concrete such as compressive strength, splitting tensile strength, rapid
chloride permeability, porosity, and mass loss when exposed to elevated
temperatures. Mixes were prepared with three percentages of class F flyash ranging
from 30% to 50% and for comparison; one controlled mixture without flyash
was also produced. The specimens were heated to 20oC, 100
oC, 200
oC, and 300
oC.
Ordinary Portland cement was used for making SCC mixes. The 28th
day
compressive strength ranged between 21.43 and 40.68 MPa and splitting tensile
56
strength ranged from 1.35 to 3.60 MPa. Test results clearly show that there is little
improvement in compressive strength within temperature range of 200–300oC as
compared to 20–200oC but there is little reduction in splitting tensile strength
ranging from 20 to 300oC with the increase in percentage of flyash. The salient
features of the test are shown in Table 2.49.
Table 2.49 Salient Features of Test Carried out by Neelam Pathak
and Rafat Siddique
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15
x0.15)
Cylinder
(0.15x0.3
0.1x0.05)
20°C
100°C,
200°C&
300°C
Peak
temperature
maintained
for one
hour
RILEM
Technical
committee
TC-129 (39)
1°C/min
Natural
cooling
by air
(24hrs)
Un
stressed
residual
strength
test
Neelam Pathak and Rafat Siddique (2012)74
studied the use of foundry sand and
flyash on the properties of self compacting concrete such as compressive strength,
splitting tensile strength, modulus of elasticity, rapid chloride permeability, porosity
and mass loss when exposed to elevated temperatures. The influence of flyash as
partial replacement of cement and foundry sand as partial replacement of sand on
the properties of SCC was investigated. Mixes were prepared with three percentages
of flyash ranging from 30% to 50% and one controlled mix without flyash was also
prepared for comparison. Fine aggregate was replaced with 10% of foundry sand.
The specimens were heated up to 27oC, 100
oC, 200
oC, and 300
oC and in order to
ensure a uniform temperature distribution throughout the specimens, the
temperature was kept constant for a period of 1 h before cooling. Using ordinary
portland cement, an increase of about24–25% in compressive strength, 18–22% in
splitting tensile strength was observed at 28 days when flyash content was
decreased from 50% to 30%. Also test results clearly show that there is little
improvement in compressive strength within the temperature range of 200–300oC as
compared to 27–200oC. But the rate of splitting tensile strength and modulus of
elasticity loss were found to be higher than those of the compressive strength loss at
elevated temperatures. The salient features of the test are shown in Table 2.50.
57
Table 2.50 Salient Features of Test Carried out by Neelam Pathak
and Rafat Siddique
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15
x0.15)
Cylinder
(0.15x0.3
0.1x0.05)
27°C
100°C,
200°C&
300°C
Peak
temperature
maintained
for one
hour
RILEM
Technical
committee
TC-129
1°C/min
Natural
cooling
by air
(24hrs)
Un
stressed
residual
strength
test
Ozge Andic-Cakır and Selim Hizal (2012)79
prepared Self Consolidating
Lightweight Concrete (SCLWC) mixtures using two different lightweight coarse
aggregates and by replacing normal weight crushed coarse limestone aggregate at a
constant water/powder ratio. One of the SCLWC mixtures was also prepared at a
different water/powder ratio. All the mixtures were exposed to 300, 600 and 900°C,
respectively. Type of lightweight aggregate and water/powder ratio were found to
affect the water transport characteristics and resistance of the mixtures subjected to
elevated temperatures. Compressive strength and modulus of elasticity of the
mixtures were found to be affected by the type of the aggregate and w/c (or w/p)
ratio, while splitting tensile strength was mainly affected by the type of the
aggregate alone. Type and porosity of the aggregates and w/c (or w/p) ratio of the
mixtures were the main factors that affect the porosity and thus, the water
absorption capacity of self consolidating lightweight concrete samples. The porosity
of concrete was found to adversely affect the resistance of self consolidating
lightweight concrete subjected to elevated temperatures. Even though the specimens
were pre dried at 105oC for 24 h before the exposure to elevated temperature, the
pores in hardened concrete still acting as water reservoirs during exposure was
attributed to be the main reason for this behaviour. Such exposure cracks were
observed in the micro structural analysis of deteriorated pumice containing
specimens after exposure to elevated temperatures. For a given lightweight
aggregate type, the decrease in w/c (or w/p) ratio decreased the permeability of
concrete which is expected to have an adverse effect during exposure to elevated
temperatures; however, this serves as a protection against high temperature by
58
decreasing the moisture content of specimens. The salient features of the test are
shown in Table 2.51.
Table 2.51 Salient Features of Test Carried out by Ozge Andic-Cakır and Selim Hizal
Size of the
Specimen
(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
(0.15x0.15
x0.15)
(0.05x0.05
x0.05)
20°C
300°C,
600°C&900°C
Peak
temperature
maintained
for two
hour
Furnace
temperature
curve
15°C/
min&
5°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
Mucteba Uysal (2012)68
carried out an experiment to evaluate the performance of
self compacting concrete subjected to elevated temperatures. For this purpose,
Portland cement (PC) was replaced with Limestone Powder (LP), Basalt Powder
(BP) and Marble Powder (MP) in various proportions. Polypropylene (PP) fibers
were added to 50% of the specimens to understand the effect of PP fibers on the
behavior of SCCs subjected to high temperatures. SCC mixtures were prepared with
water to cement ratio of 0.33 and polypropylene fibers content was 2 kg/m3 for the
mixtures containing polypropylene fibers. Specimens were heated up to
temperatures of 200, 400, 600 and 800oC. Tests were conducted to determine loss in
weight and compressive strength. Ultrasonic pulse velocity was determined and
surface crack observations were made after being exposed to elevated temperatures.
Experimental results indicated that a severe strength loss was observed for all of the
SCC mixtures after exposure to 600oC, particularly the specimens containing
polypropylene fibers though they reduce and eliminate the risk of the explosive
spalling. At higher replacement levels of LP, BP and MP, further lower residual
strength was observed. In terms of percent residual properties, control specimens
performed better than filler additive specimens for all heating cycles. The salient
features of the test are shown in Table 2.52.
59
Table 2.52 Salient Features of Test Carried out by Mucteba Uysal
Size of the
Specimen(m)
Temperature
Range
Time
Duration
Time-
Temperature
Curve
Rate of
Heating
Rate of
Cooling/
Coolant
Type of
test
Cube
0.10x0.10
x0.10)
200°C,
400°C,
600°C,
800°C
Peak
temperature
maintained
for three
hour
RILEM
Technical
committee
TC-129
(Furnace)
1°C/
min
Natural
cooling
by air
Un
stressed
residual
strength
test
Rahul P. Chadha et al (2012)84
carried out an experiment investigation to find out
the effect of fire on flexural strength of reinforced concrete beams. After heating,
the specimens were allowed to reach the room temperature and some samples were
quenched with water for rapid cooling. Flexural strength was determined after
cooling. Simultaneously, theoretical investigation of various parameters in relation
to fire was carried out. The flexural strengths of the beams exposed to fire at 550°C
& 750°C for 60 and 120 minutes were found to be less than those of the reference
beam by about 34.84% and 44.37% respectively. When the beams were exposed at
950°C there was a significant decrease in flexural strength and the reduction was
found to be 61.99% and 64.24% respectively. The reduction in strength for beams
exposed to fire with a cover thickness of 25mm & 30mm was around 35 % less than
that for the reference beam at 550°C. The reduction in strength for beams exposed
to fire with a cover thickness of 25mm & 30mm was found to be 60% and 47%
when compared with the reference beam at 750°C. The reduction was 64% and
61% respectively for beams exposed to 950°C. Spalling of concrete was observed in
the beam exposed to fire for 2 hr at 950°C at the time of removal from furnace,
which increased with time under normal weathering conditions. The salient features
of the test are shown in Table 2.53.
Table 2.53 Salient Features of Test Carried out by Rahul P. Chadha et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Beam
(0.15 x
0.15x 0.7)
550,750
950oC
1 hour,
2 hour
Furnace
temperature
Curve
-
Natural
cooling &
Water
quenching
Un stressed
residual
strength
test
60
Mucteba Uysal et al (2012)70
carried out an experimental investigation on the
performance of self compacting concrete subjected to high temperatures. For this
purpose, Portland cement was replaced with flyash and Granulated Blast Furnace
Slag (GBFS) in various proportions with and without polypropylene fibers. The PP
fiber content was 2 kg/m3 for the mixtures that contained fibers. When the
specimens were 56 days old, they were heated to elevated temperatures (200, 400,
600 or 800°C). Tests were conducted to determine the weight loss and the
compressive strength. The change in the ultrasonic pulse velocity was measured and
observations for surface cracks were made after the specimens were exposed to
elevated temperatures. A severe strength loss was observed for all of the specimens
after 600°C, particularly for the specimens that contained PP fibers; however, the
fibers reduced and eliminated the risk of explosive spalling. Based on the test
results, it was concluded that the performance of FA concrete is better than that of
the GBFS concrete. The salient features of the test are shown in Table 2.54.
Table 2.54 Salient Features of Test Carried out by Mucteba Uysal et al
Size of the
specimen
(m)
Temperature
range
Time
duration
Time-
temperature
curve
Rate of
heating
Rate of
cooling/
coolant
Type of
test
Cube
(0.1x0.1x0.1)
200, 400,
600&800oC
Peak
temperature
maintained
for three
hour
Furnace
temperature
curve
1°C/
min
Natural
cooling
by air
0.4ºC/min
Un
stressed
residual
strength
test
2.2.3 Analytical Investigations on the Behaviour of Concrete Materials Under
Elevated Temperatures
Kodur and Phan (2007)57
discussed about the material, structural detailing and fire
characteristics that influence the performance of HSC under fire conditions. Data
from earlier experimental and numerical studies were used to illustrate the impact of
the concrete mix design and the structural detailing on fire performance of HSC
systems. The fire characteristics, concrete mix properties and structural design
features were found to have an influence on the fire performance of HSC columns.
The intensity of fire, size of fire, heat output, and rate of heating were found to
61
influence the degree of spalling and the fire endurance duration of HSC members.
The main parameters that influence fire performance of HSC at material level were
found to be strength of concrete, silica fume content, concrete moisture content,
density of concrete, % of fibre reinforcement and type of aggregate. At the
structural level, tie spacing, confinement, tie configuration, load levels and size of
the members were found to play an important role in determining the fire
endurance. They reported that by adopting proper guidelines, both at material and
structural level, spalling in HSC members can be minimized to a significant level
and fire endurance can be enhanced. Adding polypropylene fibres to concrete mix
was found to be effective in minimizing the spalling in HSC under hydrocarbon
fires.
Kodur and Dwaikat (2008)54
developed a macroscopic finite element model to
investigate the effect of fire induced spalling on the response of reinforced concrete
beams. Spalling is accounted for in the model through pore pressure calculations in
concrete. The principles of mechanics and thermodynamics were applied to
compute the temperature induced pore pressure in the concrete structures as a
function of fire exposure time. The computed pore pressure was checked against the
temperature dependent tensile strength of concrete to determine the extent of
spalling. Using the model, case studies were conducted to investigate the influence
of concrete permeability, fire scenario and axial restraint on the fire induced
spalling and also on the response of RC beams. Results from the analysis indicate
that the fire induced spalling, fire scenario, and axial restraint have significant
influence on the fire response of RC beams. It was also shown that permeability of
concrete has a substantial effect on the fire induced spalling and thus on the fire
response of concrete beams. The fire resistance of high strength concrete beams can
be lower than that of normal strength concrete beams due to fire induced spalling
resulting from the low permeability of high strength concrete.
Kodur and Dwaikat (2008)55
presented a numerical model, in the form of a
computer program, for tracing the behavior of reinforced concrete beams exposed to
fire. The three stages associated with the numerical procedure for evaluating fire
62
resistance of RC beams were namely, fire temperature calculation, thermal analysis
and strength analysis. A simplified approach to account for spalling under fire
conditions was also incorporated in the model. The use of the computer program for
tracing the response of RC beams from the initial pre loading stage to collapse
stage, due to the combined effect of fire and loading, was demonstrated. The
validity of the numerical model was established by comparing the predictions from
the computer program with the results from full scale fire resistance tests. Through
the results of numerical study, it was shown that the type of failure criterion has
significant influence on predicting the fire resistance of RC beams.
Wu and Lu (2009)96
developed a beam element model to analyse reinforced
concrete beams at elevated temperature using the principle of virtual work. After
validating the model with the results of an available experimental program, a RC
beam with elastic axial and rotational restraints at beam ends was selected for
numerical parametric study. The parameters investigated included different spans,
different levels of applied load, different types of loads and different levels of axial
and rotational stiffness at beam ends. Through the parametric analysis, it was found
that axial restraint induced axially compressive force and increased the mid span
deflection when temperature was increased. The effect of the rotational restraint on
the generated axial force was found to be less.
R.A. Hawileh et al (2009)34
investigated the fire performance of Carbon Fiber
Reinforced Polymer (CFRP) strengthened members subjected to various
environmental exposure factors and their resistance to heat transfer. A detailed
finite element model of a CFRP strengthened reinforced concrete T-beam was
developed. The model accounts for the variation in the thermal and mechanical
parameters of the constituent materials with temperature, including CFRP and
insulation materials. Nonlinear time domain transient thermal stress finite element
analysis was performed using the commercial software ANSYS to study the heat
transfer mechanism and deformation within the beam for fire conditions initiating
from the bottom of the beam. To relate the simulation to an actual case, a reinforced
concrete T-beam strengthened with CFRP and fire tested by other investigators was
63
modeled. The progression of temperature in the beam, CFRP, reinforcing steel, and
along the CFRP concrete interface was compared with the observed fire test data.
The predicted results were found to be in good agreement with the measured ones.
In addition, the mid span deflection was found to increase nonlinearly during the
fire exposure time due to the increase in the total strain on the tension side of the
beams and due to concrete cracking.
Kodur et al (2009)93
developed a numerical model for tracing the response of Fiber
Reinforced Polymer (FRP) strengthened reinforced concrete beams under fire
conditions. The model was based on a macroscopic finite element approach and
utilized moment curvature relationships to trace the response of insulated FRP
strengthened RC beams from linear elastic stage to collapse under any given fire
exposure and loading scenarios. In the analysis, high temperature material
properties, load and restraint conditions, material and geometric nonlinearity were
accounted for, and a realistic failure criterion was applied to determine the failure of
beams. The model was validated against fire test data on FRP strengthened RC
beams and was applied to study the effect of FRP strengthening, insulation scheme
and failure criterion on the fire response of FRP strengthened RC beams. Results
from the model indicated that the fire behavior of FRP strengthened RC beams,
provided with supplemental fire insulation, was as good as that of unstrengthened
RC beams. A case study was also presented to illustrate the application of the model
for optimizing the fire insulation scheme to achieve required fire resistance in FRP
strengthened concrete beams.
Zhaohui Huang (2010)99
developed a nonlinear procedure to model the bond
characteristic between concrete and reinforcing steel for reinforced concrete
structures subjected to fire load. The accuracy and reliability of the model were
demonstrated by the analysis of one pull out test and one beam test at ambient
temperature. Four full scale beams were tested under two fire conditions. The model
was found to predict the response of reinforced concrete members and structures in
a fire with acceptable accuracy. It was reported that the bond condition between the
concrete and reinforcing steel bar has an important influence on the fire resistance
64
of reinforced concrete structures, especially when the temperature of the reinforcing
steel bar is high (more than 500°C).
Kodur and Dwaikat (2011)56
proposed an approach for evaluating the fire
resistance of reinforced concrete beams. A macroscopic finite element model was
applied to study the influence of various parameters on the fire resistance of RC
beams. Data from parametric studies were utilized to develop a simplified
expression for evaluating the fire resistance of an RC beam as a function of
influencing parameters. The validity of the proposed approach was established by
comparing the fire resistance predictions with those obtained from finite element
studies as well as from fire resistance tests. Predictions from the proposed equation
were also compared with fire resistance estimates from current codes of practice.
The applicability of the approach to design situations was illustrated through a
numerical example. The proposed rational approach expressed fire resistance in
terms of conventional structural and material design parameters, and thus facilitates
easy evaluation of fire resistance. The proposed approach yielded better estimates
than those from current codes of practice and thus can be used to evaluate the fire
resistance of RC beams with an accuracy that will be adequate for design purposes.
2.3 Conclusions Based on Review of Literature
Inspite of a few investigations carried out on fire resistance of SCC, further studies
on fire resistance of self compacting concrete elements are needed. Special attention
has to be paid to the material properties for analysis and evaluation of the residual
strength of structural elements exposed to fire. The considerable reduction in
compressive strength, tensile strength, flexural strength and Young’s modulus has
been observed for concrete specimens exposed to elevated temperatures. Since SCC
contains mineral and chemical admixtures, the behavior of SCC specimens
subjected to high temperatures may be different from that of Normal compacting
concrete and High performance concrete. The effect of grade of SCC, reinforcement
percentage, cover, type of cooling, rate of heating etc have to be clearly understood.
Hence an attempt has been made to understand the influence of the key parameters
that will affect the performance of SCC under elevated temperatures.