Amendment to the "Electric Utility Department of the Village of Montpelier, Ohio - General Rules and Regulations" VILLAGE OF MONTPELIER ELECTRIC DEPARTMENT General Specifications for Residential Overhead and Underground Electric Services The following specifications shall supplement the Village of Montpelier Electric Department General Rules and Regulations. 1. The following describes the installation of a residential meter base positioned on the side of a dwelling. All work shall be done in accordance with the latest National Electrical Code (NEC) and any applicable local, state or federal regulations in existence at the time of installation. All work shall be in accordance with the attached specifications and drawings and shall be subject to the acceptance of the Electric Superintendent or his authorized representative of the Village of Montpelier's Electric Department. 2. All new installations and changes to an existing electrical service shall require a Residential Electric Permit from the Village of Montpelier. To obtain a Residential Electric Permit, the owner and/or electrical contractor shall hold a pre-construction meeting with the Electric Superintendent or his authorized representative of the Electric Department to determine the proper installation location and method. To schedule a meeting please call the Electric Department at 419-485-5576. 3. The owner or electrical contractor shall be responsible for calling the Ohio Utilities Protection System (OUPS) at 1-800-362-2764 before any digging or ground rods are installed. 4. The Village of Montpelier reserves the right NOT to connect the residential electric service if the Electric Superintendent or his authorized representative considers the installation not to be installed according to the required specifications. The Village of Montpelier also reserves the right to determine unsafe electric services and may terminate those services at any time. 5. All residential electric services shall be a minimum of 100 Amp. 6. For the safety of the Village of Montpelier employees and Customers, all electrical services 400 Amp and lower shall have a properly installed disconnect. 7. All meter socket bases with disconnect breaker shall be purchased from the Village of Montpelier Electric Department along with the Residential Electric Permit. 8. Meter socket bases with disconnect breaker shall be solidly secured to the side of the dwelling and shall be 4'-6" minimum to 6' maximum from final grade. 9. Meter socket bases shall NOT be installed inside porches (screened or open) or inside any carport or garage. 10. If there is more than one meter to the premises, each meter shall be permanently identified by the Customer to properly identify that portion of the

Upload: nguyenanh

Post on 06-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

Amendment to the "Electric Utility Department of the Village of Montpelier, Ohio - General Rules and Regulations"

VILLAGE OF MONTPELIER ELECTRIC DEPARTMENT

General Specifications for Residential Overhead and Underground Electric Services

The following specifications shall supplement the Village of Montpelier ElectricDepartment General Rules and Regulations.

1. The following describes the installation of a residential meter base positionedon the side of a dwelling. All work shall be done in accordance with the latestNational Electrical Code (NEC) and any applicable local, state or federalregulations in existence at the time of installation. All work shall be inaccordance with the attached specifications and drawings and shall besubject to the acceptance of the Electric Superintendent or his authorizedrepresentative of the Village of Montpelier's Electric Department.

2. All new installations and changes to an existing electrical service shall requirea Residential Electric Permit from the Village of Montpelier. To obtain aResidential Electric Permit, the owner and/or electrical contractor shall hold apre-construction meeting with the Electric Superintendent or his authorizedrepresentative of the Electric Department to determine the proper installationlocation and method. To schedule a meeting please call the ElectricDepartment at 419-485-5576.

3. The owner or electrical contractor shall be responsible for calling the OhioUtilities Protection System (OUPS) at 1-800-362-2764 before any digging orground rods are installed.

4. The Village of Montpelier reserves the right NOT to connect the residentialelectric service if the Electric Superintendent or his authorized representativeconsiders the installation not to be installed according to the requiredspecifications. The Village of Montpelier also reserves the right to determineunsafe electric services and may terminate those services at any time.

5. All residential electric services shall be a minimum of 100 Amp.6. For the safety of the Village of Montpelier employees and Customers, all

electrical services 400 Amp and lower shall have a properly installeddisconnect.

7. All meter socket bases with disconnect breaker shall be purchased from theVillage of Montpelier Electric Department along with the Residential ElectricPermit.

8. Meter socket bases with disconnect breaker shall be solidly secured to theside of the dwelling and shall be 4'-6" minimum to 6' maximum from finalgrade.

9. Meter socket bases shall NOT be installed inside porches (screened or open)or inside any carport or garage.

10. If there is more than one meter to the premises, each meter shall bepermanently identified by the Customer to properly identify that portion of the

Page 2: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

premises being served. Metal stamping or a metal tag is required. Paintedidentification is NOT acceptable.

11. Overhead and underground meter socket base locations and theunderground trench paths shall be specified by the Electric Superintendent orhis authorized representative.

12. The Customer shall install, own and maintain the service entrance equipmentin accordance with applicable rules and requirements.

13. The Village of Montpelier's service drop will terminate at the first point ofcontact on the building or structure supporting the service equipment. Thepoint of service drop attachment on the building shall be located on theexterior wall facing the direction determined by the Electric Superintendent orhis authorized representative.

14. Drip loop or point of attachment (whichever is lowest) shall be at least 13'0"from the final grade on overhead services.

15. Customer's point of attachment must be strong enough to support the servicedrop (typically 600 pounds tension) and high enough to provide NESC Codeclearance for the service drop and drip loop above the underlying area,including the roof.

16. Customer shall install a house knob (provided by utility) at the pointof attachment.

17. No foreign attachments such as cable TV wire, phone wire, fiber wire, etc.shall be permitted on a service riser conduit.

18. Conduit shall be installed on the entire entrance conductor from the meterbase into the dwelling, including an entrance sleeve through the wall of thedwelling. All fittings or hardware shall be of weather/corrosion resistantmaterials, and must be in good condition.

19. Customer shall leave a minimum of 36" of wire from the weather head, andthe neutral shall be marked with white tape to differentiate it from othercurrent carrying conductors.

20. Two ground rods of copper weld 5/8" x 8' shall both be driven into the groundto a point where the ground rod clamps are below surface grade. Galvanizedground rods are NOT permissible.

21. The grounding conductor to the ground rods shall be determined by size ofservice. The conductor shall be continuous from the ground lug of the meterto the ground rods. The conductor shall be securely strapped or stapled tothe building to protect it from mechanical injury. Otherwise it shall be installedin %" conduit and securely fastened to the wall.

Approved by Motion by the Village of Montpelier Council

Page 3: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

Outdoor Mbo.se firMlinsto.lled 0.

by custOMleo.st 3' 0.

doors,corwindows

MontpelierUnderground ElectricoJ

Electric Dept,Service lr s to.l.lction

The locateon of the service must be approved bythe Utility before work is started. Allmeters/disconnects shall be located so as to beexposed and accessible from the outside.

* Pleo.se give 24 to 48 hours notices unless itis o.n el""lergency,

I I II I I

I I Ieterynd wireder. o.t ,...,.wo.y froM <, ,r-r

"l

ners Be r-,I---

'!..

[QJ D""--.J--.J-r::3 f--•...

w..,zz

DISCONNECT CIw

G~oJnd~lr~,-l '"II ' I ,

I 'i IS_

o.x to 4"6' nlr I

~2' --1...,..condult,7

" II .--

! - .- f--

1}3' : : \~8 r---------------]

At leust 6' betweenrods-----

6' M

l' MlnPuss Drip Line of House

Service Co.poclt y (AMP)100 AMP 200 AMP

Copper \.,lire #2 3/0Alul'linul'l wir-e #2 4/0Ground \.,lire #6 #4

Contractor must follow the latestedition of the National Electric Code(NEC).

Note: Neutro.l W'ire ShO,ll beindentified by W'hite To.pe onEo.ch End,

3-W'ire f r on utility source to I""leterbo.se s.ho.tt be insto'lled in on electrico'lconduit4-W'ire f r on disconnect to houseelectrico'l ponel

* All MO,terio'l co.n be quoted O,ndpurchO,sed froM Electric Depo.r tnerrt

Page 4: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

Alterno.teloco.tionforserviceequlpnerrt

Montpelier Electric Dept.Dverheo.d Electrico.l Service Irrs t ol!c tion

InsulOoteclHouse Knobprovlclecl byutility

Serviceequlpne rrt100AMiniMuM

The location of the service must be approved bythe Utility before work is started. Allmeters/disconnects shall be located so as to beexposed and accessible from the outside.

lIE Pl e c s e give 24 to 48 hours notices unlessit is o.n erv1ergency,

Service Co.po.city (AMP)

Copper 'Wire

#4

100 AMP 200 AMP

4/0

Service wire sho.llproject 3 feetMiniMuM+r onweotherheo.d

Vo.tertightr connection

I ~Outdoor Meterbo.se firMlyInsto.lled Oondwiredby cus+oner-, Meter0.t leo.st 3' froMcloors/corners Qnawindows

13' MiniMuM

GroundVire

l' MIN PASS-l l-DRIPLINE OFHOUSE

Stro.p'i=/------t----'- Mo.xlMUM

of 12Stro.p .-}----~}------r-rlnchesMoxlMUM Fr-onof 36 weo.therheo.d.incheso.po.rt, ~+-----w

StrOopMo.xlMUMof 24 '1..----inchesfroMMeterbo s e,

Must be Electricpve Condul t

6' MAX TO 4'6' MIN

#2 3/0Alurv1inurv1 'Wire #2

#6Ground 'Wire

Contractor must follow the latestedition of the National Electric Code(NEe).

Note: Neutro.l wire Sho.ll beinolentifieol by 'White To.pe onEo.ch Enol,

3-'Wire frorv1 weo.therheo.~ to rv1eterbo.se4-'Wire Fr-on oIisconnect to houseelectrico.l po.nel

* All no terio.l co.n be quoteoi o.nolpurcho.seol Fr-or- Electric Depo.r+ne rrt

Page 5: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

Montpelier Electric De~Dverhe(H~ ElectricoJ Service Irrs t c uotion

The location of the service must be approved bythe Utility before work is started. Allmeters/disconnects shall be located so as to beexposed and accessible from the outside.

* Plea.se give 24 to 48 hours notices unless itis o.n er"lergency,

Meter bo.se to be 3' nln wo.y Fr-on: doors,corners s, windows

6' Mo.xto 4' 16' Min

1111

RigidCondiutMustextend 18inchesFr-on roof,but noMore tho.n36 incheswithoutguying,

Service wire sho.ll project0. t leos t 3 feet MiniMUMfrOM weo.therheo.d

Insulo.tedClevis providedby utility

ReccoMendedroof flo.shingprovided bycus toner-.

S=:==*====~:::::jll1

~o.dd 2-stro.ps nln to-""'>'<'='--'---'- 1 secure conduit to house

V/eo.thertlght 1connection 1

1 13 feet nlnServiceEqulpnerrt100Anlnlnun

~~ ------T Outdoor Meterbo.se f ir nlylns t o.lled ond wiredby cus t oner-.

.... -

Groundwire(onecontinuouswire.>

I--+-------L--IL _

-----lAt Ieost 6 feet between

l' MIN PASS DRIP LINE OF HOUSE

DverhecH)j Conduit Size100A I 21 Rigid steel200A I 21 Rigid steel

Service Co.po.cl t y (AMP)100 AMP 200 AMP

Copper \Jire #2 3/0AluMinuM \Jire #2 4/0Ground \Jire #6 #4

Contractor must follow the latestedition of the National Electric Code(NEC).

Note: Neutro.l wire Sho.ll beindentified by 'vv'hite To.pe onEo.ch End,

3-'vv'ire frOM weo.therheo.d to Meterbo.se4-'vv'ire Fr-om disconnect to houseelectrico.l po nel

rods

* All no t er-lo t co.n be quoted onopurchosed frOM Electric Depo.r t ne nt

Page 6: VILLAGE OF MONTPELIER ELECTRIC DEPARTMENTmontpelieroh.net/pdf/Residential_Electric_Instructions.pdf · All meter socket bases with disconnect breaker shall be purchased from the Village

Address:Date:Legal Owner:Add ress (if different than above):

Electrical Contractor:Address:

Telephone Number:Size of New Service (amps):

Location of New Service:

Additional Notes/Information:

RESIDENTIAL ELECTRIC PERMIT (REP)Vii/age of Montpelier

211 North Jonesville Street, P.O. Box 148

Montpelier, OH 43543

Phone: 419-485-5543 Fax: 419-485-4947

Web Page http://www.montpe/ieroh.netJ

Village Residential Wiring Permit Fee:1-----1100 Amp Meter Base w/Disconnect :

I------i

200 Amp Meter Base w/Disconnect:1-----1Temporary Electric Service Hook Up:

I------i

Initial Service Connection:1...-_---1(Location, Inspection of Service Entrance, Etc.)

r----IUnderground Electric Service($100.00 Base Fee plus $1.75/foot Trenching Fee)

TOTAL FEE COSTS:

ADDITIONAL MATERIAL COST (see attached):

TOTAL:

$20,00 1------1$140.00

f-----I

$140.00 1------1$100.00

f-----I

$50.00 L...-_---l

(Please note all prices are subject to change without notice.)

PLEASE MAKE CHECKS PAYABLE TO: VILLAGE OF MONTPELIERFor 400 amp and Multiple Meter Sets see Electric Superintendent for pricin .

VOM Approval Signature Customer/Contractor Signature

(Office Use Only)

Account Number: Engineering/ElecDoc Wirina Permit 2011.xls 1/13/2012