valvetop d-series d2-ff foundation fieldbus iom (for ... · calibration of target / feedback...
TRANSCRIPT
™
™ Valvetop D-Series with FF Option FOUNDATION Fieldbus Installation, Operation & Maintenance Manual
Table of Contents 2 Introduction 2 Quick Installation Guide 4 Installation 4 Storage 5 Pneumatic Connection 6 Electrical Connection 8 FF Operation 10 Troubleshooting and Maintenance 16 Appendix A: FF Technology 18 Appendix B: Resource Block 20 Resource Block DD Menu Structure 21 Appendix C: Transducer Block 26 Transducer Block DD Menu Structure 27 Appendix D: Discrete Output (DO) Block 29 Appendix E: Discrete Input (DI) Block 31 Appendix F: Dimension & Assembly Drawings 35 Appendix G: Specifications & Reference Data
™
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
2
Introduction This manual is intended to provide instruction for Installing, Operating and Maintaining the TopWorx Model DXP/DXS-FF Discrete Valve Controller with FOUNDATION™ Fieldbus.
Warnings and Precautions that require special instructions or considerations are noted by this symbol.
DXP Quick Start Installation Guide Step 1 - Mount DXP/DXS-FF (Fig. 1)
a) Connect bolts firmly between switchbox and bracket b) Connect bolts loosely between actuator and bracket c) Cycle actuator to limits in both directions 3 times to center shaft d) Tighten the bolts between the actuator and bracket
Step 2 - Secure pneumatic connections
a) Refer to Figure 2 for details b) Use of Locktite 567 is recommended
Step 3 - Make electrical connections
a) Attach fieldbus wiring to FF terminals (Fig. 2) b) FOUNDATION Fieldbus wiring is polarity insensitive
Step 4 - Calibrate switches
a) Move the valve to the CLOSE position, push and rotate lower cam to activate the Red LED
b) Move the valve to the OPEN position, push and rotate upper cam to activate the Green LED
c) Verify calibration by actuating valve open and closed several times NOTE: Switches can be set using calibration switch without FF connection by using any 9-32VDC power source. Step 5 - Commission DXP-FF
a) Connect single DO to Channel 5 • No DI needed - Readback_D provides the actual valve position
b) Set the Mode to AUTO (Automatic) in the Transducer Block
Mounting - Figure 1
FLASH RESET
CLOSE
FF
AUX
OPEN
- V2 + - V1 +
WrtPrt
FF Sim
SCM-FF
Calibration Switch
Auxilliary InputTerminals(Dry contacts only)
FoundationFieldbus LoopTerminals
Piezo PilotTerminals
Single PilotDual Pilot
Std Operation Jumper Location
+ = Orange- = Black
NOTE: TopWorx has pre-configured modules and faceplates available for
DeltaV control systems. Contact TopWorx factory for more
information.
Wiring - Figure 2
www.topworx.com
3
TM
Installation on Actuator Orientations, Normal and Reverse Acting Normal acting is full CW when the process valve is closed and CCW when the process valve is open. Reverse acting is full CW when the process valve is open and CCW when the process valve is closed. 90° indicator dome assemblies are design to accommodate any mounting arrangement and can be adjusted up to 9° off axis if needed. 45° indicator dome assemblies can only accommodate normal acting applications that are mounted parallel ±9°. Consult your local distributor or factory representative for 45° reverse acting or mounted perpendicular applications.
Illustration #1:
The image to the left shows a Valvetop unit mounted parallel to the process valve in the closed position. The green arrow at the top shows the “normal acting” direction of travel to open the valve. This is the standard orientation and your unit unless otherwise specified will be factory set to operate in this fashion.
Illustration #2: The image to the right shows a Valvetop mounted perpendicular to the process valve in the closed position. The green arrow at the top shows the “normal acting” direction of travel to open the valve. Notice that the indicator dome has been rotated 90° compared to the unit above.
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
4
Installation on Actuator (continued) Mounting TopWorx has numerous mounting bracket kits available to meet your specific application, whether rotary or linear. Consult your local distributor or factory representative for ordering information. The illustration shows a direct Namur mount on a quarter turn valve. Refer to your mounting kit documentation for specific mounting instructions. Storage Until conduit, conduit plugs, and any applicable spool valve port connections are properly installed, the ValveTop unit will not support its IP/NEMA rating as the unit ships with temporary covers. Ensure that it is stored in a dry environment with a relative humidity range between 10%-95% and a temperature ranging from -40ºF (-40ºC) to 160ºF (71ºC). Once properly installed, the temperature range listed on the nameplate will supersede this storage temperature range.
Illustration #3: Mounting Assembly
Installation Notes 1. Use caution not to allow undue axial (thrust) load on the shaft.
2. Cycle the valve a couple of times prior to final tightening of the
mounting kit hardware. This allows the shaft to self-center in the pinion slot, or coupler. Refer to the dimensions and materials section of this document for appropriate tightening torque.
3. Always use sound mechanical practices when torquing down any-hardware or making pneumatic connections. Refer to the Integrated Pneumatic Control Valves section for detailed information on pneumatic connections.
4. This product comes shipped with conduit covers in the conduit entries in an effort to protect the internal components from debris during shipment and handling. It is the responsibility of the receiving and/or installing personnel to provide appropriate permanent sealing devices to prevent the intrusion of debris, or moisture, when stored outdoors or when installed. It is the responsibility of the installer, or end user, to install this product in accordance with the National Electrical Code (NFPA 70) or any other national or regional code defining proper practices.
www.topworx.com
5
TM
Pneumatic Hookup Procedures Prior to connecting the supply air to the spool valve, flush the system to remove any debris or contaminates. Galva-nized pipe can easily flake and contaminate the system and therefore is not recommended. A 40 micron point of use filter at every device is recommended. 4-Way Spool Valves The TopWorx spool valve is a 5 port, 4-way valve driven by an internally mounted pilot. The spool valve supply port and work ports are marked as follows:
***Never Plug, Block or Restrict Port 5***
Supply
Port to OpenPort to Close
Always install ventsor speed controls Supply
DOUBLE ACTING ACTUATORS SPRING RETURN ACTUATORS
1 35
24
1 35
24
Port to OpenPlug /Close
Supply
Always install ventsor speed controls
Highly Recommended TopWorx highly recommends Locktite 567 brand thread sealant. Do not use a hard setting pipe compound. If Teflon thread seal tape is used, start the wrap on the second thread from the leading thread of the fitting. This will pre-vent tape shreds from contaminating the spool valve seals. Breathers (AL-M31) should be installed in the exhaust ports to keep debris from falling into the spool valve and damaging the seals. This must be addressed prior to instal-lation, or storage. A flow control may be used in Port 3, but should NEVER BE USED in Port 5. Any blockage or restriction may cause an internal pressure build-up inside the enclosure and pose a safety issue.
Spool Valve Specifications Medium Dried, filtered air (40 micron)
Max Operating Pressure 100psi (0.69 MPa) (6.89Bar)
Min. Operating Pressure 30psi (0.21 MPa) (2.07Bar)
Ambient Temperature Range Refer to Product Nameplate Marking
Flow Coefficient 1.2Cv or 3.0Cv
Environment Rating Type 4, 4X, IP67
Port Size 1/2” NPT for 3.0Cv valve 1/4" NPT for 1.2Cv valve
Manual Override Available in Latching/Non-Latching Push Type & Palm Actuator Type
Valve Body Available in Hardcoat Anodized Aluminum, 304, or 316 Stainless Steel
Valve Seals Spool Seals: Buna-N Valve Body Seals available in Buna-N, Silicone, EPDM & Viton.
Max Consumption Rate 600 cc/min @ 80psi
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
6
Electrical / FF Connections The FOUNDATION Fieldbus Sensor Communications Module (SCM-FF) combines integral switch relays for position sensing with FOUNDATION Fieldbus communications and pilot valve output drivers.
Pilot Valve Wiring Single Pilot Valve
· The Orange (or Red) lead is terminated on V1+. (+ = Orange) · The Black lead is terminated on V1-. (- = Black)
Dual Pilot Valve · The open valve wiring to the V1 terminal (+ = Orange) · The close valve wiring to the V2 terminal (- = Black)
FOUNDATION Fieldbus Wiring The Fieldbus Segment Wiring is connected to the FF Terminals on the SCM. These terminals are NOT polarity sensitive.
It is strongly recommended that FF wiring leads are not daisy-chained together and each drop provides short-circuit protection.
Auxiliary Dry Contact Attach dry contact wiring to the AUX terminals.
FLASH RESET
CLOSE
FF
AUX
OPEN
- V2 + - V1 +
WrtPrt
FF Sim
SCM-FF
Calibration Switch
Auxilliary InputTerminals(Dry contacts only)
FoundationFieldbus LoopTerminals
Piezo PilotTerminals
Single PilotDual Pilot
Std Operation Jumper Location
+ = Orange- = Black
Flash Reset Button When there is an active device alarm, the LEDs will blink. The Flash Reset Button will stop the flashing indications.
For testing of the pneumatics and calibration of the target assembly, a 9 to 32 VDC power supply can be used with the calibration switch to open and close the valve without a fieldbus loop attached.
Illustration #4: Mounting Assembly
www.topworx.com
7
TM
Calibration of Target / Feedback Calibration of the FOUNDATION Fieldbus SCM-FF Never perform calibration procedure unless area is known to be safe.
· For Intrinsically Safe models, unit must be wired in accordance with Control Drawing S-K088A, or I.S.
components may be damaged. · For standard explosion-proof models: The OPEN and CLOSED limit switches encapsulated within the
SCM-FF may be calibrated using a DC power supply set between 9-32V, or calibrated once connected to the Fieldbus network.
Step 1 Connect the power supply, or Fieldbus wires, to the FF terminals. The terminals are not polarity sensitive. With power applied to the FF terminals, the valve may be manually stroked using the Calibration Switch on the SCM-FF. Step 2 Place calibration switch to the CLOSE position. Valve should move to CLOSE position. If it does not, consult troubleshooting section of page 11. Step 3 Disengage the bottom Cam from the splined hub and rotate the bottom Cam clockwise until the Red LED lights. Release the Cam to re-engage the splined hub. Step 4 Slide the calibration switch to the OPEN position. Valve should move to OPEN position. If it does not, consult troubleshooting section on page 11. Step 5 Disengage the top Cam from the splined hub and rotate the top Cam counter-clockwise until the Green LED lights. Release the Cam to re-engage the splined hub. Step 6 Cycle the valve CLOSED and OPEN a few times using the calibration switch to verify both limit switches are maintaining their set points. Step 7 Place calibration switch in the FF position. If using a power supply to calibrate, disconnect leads to the supply, and connect the Fieldbus loop when ready to put into service. Step 8 Manipulate the transducer parameters via the control system as necessary for desired mode of operation. NOTE: If using a reverse acting actuator, re-calibrate switches using Steps 3-6, but rotate counter-clockwise for close and clockwise for open. Reverse Action must be set in the Transducer Block (see “Transducer Block Initialization, Single-Dual Action”).
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
8
Section 2: Operation This section of the manual provides operational information for configuring the SCM-FF device on the FOUNDATION Fieldbus Host Control System. This section includes both required Control Configuration and optional Monitoring Configuration information.
Control Configuration (Required)
The TopWorx FOUNDATION Fieldbus products should be configured for operation using a single Discrete Output (DO) Function Block with Channel Parameter assignment of 5. This module configuration will provide a multi-value DO Block that will fully control a single or a dual output device. The Readback_D parameter will provide actual valve position based on the Open / Closed Limit Switches in the device. Discrete Input (DI) Blocks are neither required nor desired for feedback function.
The values of these parameters are as follows: Figure 4
NOTE: TopWorx has pre-configured modules and faceplates available for DeltaV control systems. Contact the TopWorx factory or www.topworx.com for more information.
The Transducer Block is shipped from the factory in the OOS (Out of Service) Mode to allow field installation/testing using the SCM calibration switch. Once the installation and the configuration above are complete, The Transducer Block must be placed in the AUTO (Automatic) Mode for device operation. The complete device control algorithm should be as depicted below:
DO ChannelAssignment
Definition Readback_DValves
Control Method
5 Open/Close/StopOutputs
0 - Closed1 - Open2 - Stopped3 - Opening4 - Closing
Single Block,Dual Action
Readback_D Parameter
Discrete Control
Function Block
Discrete Output (DO)
Function Block
DO
www.topworx.com
9
TM
DI ChannelAssignment
Definition OUT_D Values
13 Device Alarms 0x00 - No Alarm0x01 - Cycle Count0x02 - Time to Open0x04 - Time to Close0x08 - Time Board Temp Hi0x10 - Board Temp Lo
Alarm Configuration (Optional)
Discrete Input (DI) Block may be configured for monitoring internal Device Alarms within the Control Strategy of the Host System. The Internal Device Alarms can be monitored using a Discrete Input (DI) Block with the Channel Parameter assignment of 13. All alarms that are activated (checked in the Transducer Block) can be read by this single DI block in a masked fashion. See Appendix C for Transducer Block parameter settings.
Multiple active alarms are depicted by a HEX value representing the sum of all active alarms OUT_D Val-ues. For example, a device with a Cycle Count Alarm and a Time to Close Alarm both active would have an OUT_D Value of 0x05.
Auxiliary Input Configuration (Optional)
The AUX Input terminal may be monitored using a Discrete Input (DI) Block with the Channel Parameter assignment of 9.
DI ChannelAssignment
Definition OUT_D Values
9 Aux Input 0 - Aux Dry Contact Closed1 - Aux Dry Contact Open
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
10
Section 3: Maintenance This Section provides information on Troubleshooting and Component Replacement for the DXP-FF.
Troubleshooting
Description of Problem Possible Cause Possible Solution
Red or green LED does not illuminate whenthe valve is either in closed or open position
Target not calibrated properly Use calibration procedure on page 7
LED's do not operate, regardless of valveposition
Power not connected to FF terminals
LED's not enabled
Make sure at least 9 VDC connected to FF terminals
Transducer block parameter "LED_ENABLE" set to ENABLE
Calibration switch will not operate Transducer Block in incorrect mode
Power not connected to FF terminals
Piezo and spool valve is not pressurized
Set transducer block actual model to "Out of Service"
Make sure at least 9VDC connected to FF terminals
Verify proper air pressure. Reference mechanicaltroubleshooting chart
LEDs flash from red to green after valve hasshifted
Time to open/close alarm has triggered Target not calibrated properly. Recalibrate using theprocedure on page 7
LEDs flash from red to green as soon as unitstarts moving during a setpoint change
Operational setpoints do not match limit switch positions(i.e. the closed switch is made when the unit has an opensetpoint)
Set Transducer Block Action_Element setting according tochart
Module goes "unattached" from the segment Power dropped below 9V
Excessive noise on the segment
Check voltage to ensure that it is consistently above 9VCheck for loose wire connections
Verify that the segment has a terminating resistor at eachend
Using a Fieldbus Monitor, verify that peak and averagenoise levels are <11db
Valve will not shift See mechanical troubleshooting flowchart on page 12
No response from operator interface DO Block and/or DO Channel not correctly assignedTransducer Block Out of ServiceConfiguration/DO Block NOT downloaded
Follow troubleshooting chart, (pg. 11) then continue withmechanical troubleshooting chart (pg. 12). If problempersists contact the factory
Bad Status on FeedBack Signal and/or NoFeedback signal
Transducer Block mode is Out of Service Place Transducer Block in Auto Mode
www.topworx.com
11
TM
DO
DO
DO
DO DO DO
DO
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
12
www.topworx.com
13
TM
Component Replacement
RED UrethaneTubing (Supply)
YELLOWUrethane
Tubing (Work)
10-32 Nylon PlugUsed in Fail ClosedApplications
10-32 NylonBarb Fitting
PiezoelectricPilot Device
O-rings,Buna
Manifold
Inserts
Bracket
4-40x.25 (x2)
Orangeto V+
Blackto V -
M4x35
Flame arrestor O-ring(x5)
Spool Valve with No Manual Override
Spool Valve with Single Palm Actuator Override
Spool Valve with Dual Palm Actuator Override
Push-button Style Override
M5 x 25mm SHCS (x4)(4mm hex wrench)
Fail Closed Spool Valve Replacement Assemblies
AV-BFCVA20 Std Alum Spool Valve Assy w/Buna seals
AV-BFCVS20 Std 304SS Spool Valve Assy w/Buna seals
AV-BFCV620 Std 316SS Spool Valve Assy w/Buna seals
Fail Last Position Spool Valve Replacement Assemblies
AV-BFLPVA20 Std Alum Spool Valve Assy w/Buna seals
AV-BFLPVS20 Std 304SS Spool Valve Assy w/Buna seals
AV-BFLPV620 Std 316SS Spool Valve Assy w/Buna seals
Block-Center Spool Valve Replacement Assemblies
AV-BBCVA20 Std Alum Spool Valve Assy w/Buna seals
AV-BBCVS20 Std 304SS Spool Valve Assy w/Buna seals
AV-BBCV620 Std 316SS Spool Valve Assy w/Buna seals
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
14
Indicator / Dome Replacement
Color-coded Indicator isavailable in severalcoordinating rotations andforms for various valvetypes, such as 90deg, 180degand Thru-divert applications.
O-ringAvailable in Buna-N,
Silicone, EPDM, Viton
10-32 Captive screws,Stainless (x4)
Indicator Dome, 5 adjustable
Polycarbonate with keyed mask.
Several rotation and form options.
+ O
Shaft Replacement NAMUR Shaft,Stainless
Standard 0.25” DD Shaft,Stainless
LubricationAreas
1
2
3
4mm
0.375 [9.53mm]
0.375 [9.53mm]
0.25 in
For more shaft dimensiondetails, see Page 1.
Indicator / Dome Replacement Kits
AV-GB002 90º, Green/Open, Red/Closed, Buna O-Ring
AV-YB002 90º, Yellow/Open, Black/Closed, Buna O-Ring
AV-TB002 90º, Green/Thru, Red/Divert, Buna O-Ring
AV-4B002 90º, Green/Open, Red/Closed, Buna O-Ring
NAMUR Shaft Replacement Kits SCM’s with (2) Reed Switches
AV-NSB202 NAMUR Shaft w/Buna-N O-Rings & (2) Cam Assembly with Installation Hardware
Standard Shaft Replacement Kits SCM’s with (2) Reed Switches
AV-SSB202 Standard Shaft w/Buna-N O-Rings & (2) Cam Assembly with Installation Hardware
www.topworx.com
15
TM
Sensor Communications Module (SCM-FF) Replacement
Resetting Factory Defaults in SCM There are five restart options available for the Resource Block Restart parameter in the TopWorx DXP/DXS-FF. The fifth parameter is Reset with Factory Defaults and will be implemented by writing 0x05 to the RESTART parameter. This restart is used to reset the device to factory default initial values.
After Conducting a Reset of Factory Defaults the Device Tag Information will be lost, all DI & DO Functions Blocks will be assigned to Channel 0 and The Transducer Block will be placed in Out Of Service.
Do not power down the device for 40 seconds after you execute a “Restart with Factory Defaults.” Non-Volatile Random Access Memory (NVRAM) is being written and must complete before device loses power. The device condition is unpredictable if an early power cycle is executed.
FLASH RESET
CLOSE
FF
AUX
OPEN
- V2 + - V1 +
WrtPrt
FF Sim
SCM-FF
Calibration Switch
Auxilliary InputTerminals(Dry contacts only)
FoundationFieldbus LoopTerminals
Piezo PilotTerminals
Single PilotDual Pilot
Std Operation Jumper Location
+ = Orange- = Black
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
16
InputFunction
Block
CalculationOr ControlFunction
Block
OutputFunction
Block
InputFunction
Block
CalculationOr ControlFunction
Block
OutputFunction
Block
Channels
ResourceBlock
TransducerBlock
Process Sensors
Process Actuators
FunctionBlock
FunctionBlockChannels
ResourceBlock
TransducerBlock
Process Sensors
Process Actuators
FunctionBlock
FunctionBlock
Appendix A: FOUNDATION Fieldbus Technology Blocks and the User Application The Fieldbus Foundation has defined a standard for building user applications. The Foundation standard is built around “Blocks.” Blocks are used to represent different types of functions that the device performs and provide a way of grouping different parameters and functionality together in an easy to understand framework. A Fieldbus Foundation device has a Resource Block, Transducer Block, and Function Blocks. Once the hardware of the TopWorx Sensor-Communication Module (hereafter known as SCM-FF) is set up, fieldbus communication is used to set the transducer parameters to get the functionality desired. The desired transducer func-tionality is associated with a function block. The host system is then used to link the function blocks together, and the application is downloaded to all of the devices in the loop. Resource Block The Resource Block describes characteristics of the fieldbus device such as the device name, manufacturer, and se-rial number. There is only one resource block per device. Transducer Blocks Transducer Blocks are the connection of Function Blocks to the real world. Many of the settings unique to a Fieldbus Device are defined in the transducer block parameters. The Function Blocks are typically standard between devices, so that they may be linked together to form easily con-structed, interoperable applications. The Channels of a transducer block can be attached to a function block for use in the application. Function Blocks Function Blocks provide the control system behavior. The input and output parameters of Function Blocks can be linked over the fieldbus. The execution of each Function Block is precisely scheduled. There can be many function blocks in a single user application. The SCM-FF provides 5 Discrete Input (DI) and 3 Discrete Output (DO) function blocks. Configuration of all these blocks is NOT required for full device operation. Process Instrument and its Blocks An application is built by linking together function blocks.
www.topworx.com
17
TM
FOUNDATION Fieldbus Topology
General Purpose
ControlSystem
Power Supply w/ Terminator “ON”to power (1) Fieldbus segment
Terminator “ON”T
T = Fieldbus Terminator
T
Intrinsically Safe
ControlSystem
Power Supply w/ Terminator “ON”to power (1) Fieldbus segment
Repeaters
Terminator “ON”
Isolators w/ Terminators “ON”
T
TTT
T
T T
T
T = Fieldbus Terminator
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
18
Appendix B: Resource Block The resource block contains the hardware specific characteristics associated with a device. It has no input or output parameters. This block of contained parameters includes such things as Manufacturer’s ID and revision information. Below is a complete listing of the SCM-FF Resource Block Parameters.
Complete Resource Block Parameter Listing ST_REV The revision level of the static data associated with the function block. To support tracking changes
in static parameter attributes, the associated block's static revision parameter will be incremented each time a static parameter attribute is written but the value is not changed.
TAG_DESC The user description of the intended application of the block.
STRATEGY The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
ALERT_KEY The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
MODE_BLK The actual, target, permitted, and normal modes of the block.
BLOCK_ERR This parameter reflects the error status associated with the hardware of software components associated with a block. It is a bit string, so that multiple errors may be shown.
RESOURCE STATE State of the function block application state machine.
TEST READ WRITE Read/write test parameters - used only for conformance testing.
DD_RESOURCE String identifying the tag of the resource which contains the Device Description for this resource.
MANUFAC_ID Manufacturer identification number - used by an interface device to locate the DD file for the resource.
DEVICE TYPE Manufacturer's model number associated with the resource - used by interface devices to location the DD file for the resource.
DD REVISION Revision of the DD associated with the resource - used by an interface device to locate the DD file for the resource.
GRANT_DENY Options for controlling access of host computer and local control panels to operating, tuning and alarm parameters of the block.
HARD_TYPES The types of hardware available as channel numbers.
RESTART Allows a manual restart to be initiated. Several degrees of restart are possible. They are 1: Run, 2: Restart resource, 3: Restart with defaults, 4: Restart processor; and 5: Restart with factory defaults.
FEATURES Used to show supported resource block options.
FEATURE SELECTION Used to select resource block options. Enable 0 x 32 bit to allow readbacks from function blocks.
CYCLE_TYPEIdentifies the block execution methods available for this resource.
CYCLE SELECTION Used to select the block execution method for this resource.
MINIMUM CYCLE TIME Time duration of the shortest cycle interval of which the resource is capable.
FREE_SPACE Percent of memory available for further configuration. Zero in a preconfigured resource.
FREE_TIME Percent of the block processing time that is free to process additional blocks.
SHED REMOTE CASCASE Time duration at which to give up on computer writes to function block RCAS locations. Shed from RCAS shall never happen when SHED REMOTE CASCASE = 0.
www.topworx.com
19
TM
Complete Resource Block Parameter Listing (cont’d) SHED REMOTE OUT Time duration at which to give up on computer writes to function block Rout locations. Shed from
Rout shall never happen when SHED REMOTE OUT = 0.FAULT_STATE Condition set by loss of communication to an output block, fault promoted to an output block or a
physical contact. When Fault State condition is set, then output function blocks will perform their FSTATE actions.
SET FAULT STATEAllows the Fault State condition to be manually initiated by selecting Set.
CLEAR FAULT STATE Writing a Clear to this parameter will clear the device fault state if the field condition, if any, has cleared.
MAXIMUM NOTIFYMaximum number of unconfirmed alert notify message possible.
LIMIT NOTIFY Maximum number of unconfirmed alert notify messages allowed.
CONFIRM_TIME The time the resource will wait for confirmation of receipt of a report before trying again. Retry shall not happen when CONFIRM_TIME = 0.
WRITE_LOCK If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs will continue to be updated.
UPDATE_EVT This alert is generated by any change to the static data.
BLOCK_ALM The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the alert is entered in the subcode field. The first alert to become active will set the Active status in the Status attribute. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be reported without clearing the Active status, if the subcode has changed.
ALARM SUMMARY The current alert status, unacknowledged states, unreported states, and disabled states of the alarms associated with the function block.
ACKNOWLEDGE OPTION Selection of whether alarms associated with the block will be automatically acknowledged.
WRITE PRIORITY Priority of the alarm generated by clearing the write lock.
WR_ALM This alert is generated if the write lock parameter is cleared.
ITK_VER Major revision number of the interoperability test case used in certifying this device as interoperable. The format and range of the version number is defined and controlled by the Fieldbus Foundation. Note: The value of this parameter will be zero (0) if the device has not been registered as interoperable by the FF.
DETAILED BLOCK ERRORS Provides list of all active block alarms in the block.
SUPPORTED_MODES The modes supported by this particular block.
IKEY TopWorx revision control.
REVISION_IDTopWorx revision control.
REVISION_DATETopWorx revision control.
DEVICE REVISION Manufacturer revision number associated with the resource. Used by an interface device to locate the DD file for the resource.
CHARACTERISTICS: BLOCK_TAG Defined to be unique throughout the control system at one plant site. The Tag may be changed using the FB_TAG service.
MEMORY SIZE Available configuration memory in the emptry resource. To be checked before attempting download.
NONVOLATILE CYCLE TIMEInterval between writing copies of NV parameters to non-volatile memory. Zero means never.
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
20
MO
DE_R
ES_BLK
_MEN
U
RESO
UR
CE B
LOC
K
SETUP_M
ENU
ALM_M
ENU
DEV_ID
_MEN
U
STRATEG
YALER
T_KEY
RESO
UR
CE STATE
GR
ANT_D
ENY_M
ENU
SHED
REM
OTE C
ASCAD
ESH
ED R
EMO
TE OU
TFEATU
RES
FEATU
RE SELEC
TION
**FAU
LT_STATESET FA
ULT STA
TE **C
LEAR
FAU
LT STATE **
WR
ITE LOC
K
MA
X_NO
TIFY **LIM
IT NO
TIFY**C
ON
FIRM
TIME
ALARM
_SUM
_MEN
UA
cknowledge O
ption **W
rite Priority**
ST_REV
HAR
D TYPES
MIN
IMU
M C
YCLE TIM
EM
EMO
RY SIZE
NO
NVO
LATILE CYC
LE TIME
FREE SPAC
EFR
EE TIME
DD
RESO
UR
CE
REVISIO
N ID
REVISIO
N D
ATE
CYC
LE TYPEC
YCLE SELEC
TION
BLO
CK
_ERR
Test Read W
rite: Test Boolean
Test Read W
rite: Test Integer8Test R
ead Write: Test Integer16
Test Read W
rite: Test Integer32Test R
ead Write: Test U
nsigned8Test R
ead Write: Test U
nsigned16Test R
ead Write: Test U
nsigned32Test R
ead Write: Test Float
Test Read W
rite: Test Visible StringTest R
ead Write: Test O
ctet StringTest R
ead Write: Test D
ateTest R
ead Write: Test Tim
eTest R
ead Write: Test Tim
e Difference
Test Read W
rite: Test Bit String
Test Read W
rite: Test Data Link Layer Tim
e
MO
DE_B
LK:TA
RG
ET_MO
DE
**M
OD
E_BLK
:ACTU
AL_MO
DE
MO
DE_B
LK: PER
MITTED
_MO
DE **
MO
DE: N
ormal_M
OD
E
RESTA
RT **
BLO
CK
_OPTIO
N_M
ENU
DISPLAY_R
ES_MEN
U
BLO
CK
_EXEC_M
ENU
Detailed B
lock ErrorsB
LOC
K_ALM
_MEN
U
BLO
CK
_ALM: U
nacknowledged
BLO
CK
_ALM: Alarm
StateB
LOC
K_ALM
: Time Stam
pB
LOC
K_ALM
: SubcodeB
LOC
K_ALM
: Value
BLO
CK
_PARM
_MEN
USU
PPOR
TED_M
OD
ESK
ey
STAT_PARM
_MEN
U
EVT: Unacknow
ledgedEVT: U
pdate StateEVT: Tim
e Stamp
EVT: Static Rev
EVT: Relative Index
TEST_PARM
_MEN
U MAN
UF_ID
DEVIC
E TYPED
EVICE R
EVISION
DD
REVISIO
NTA
G_D
ESC **
Characteristics: B
LOC
K_TA
G**
DEV_IN
FO_M
ENU
DEVIC
E_MEN
U
BLO
CK
_MEN
U
PARAM
_MEN
U
** Denotes W
ritable Fields
GR
ANT D
ENY: G
RAN
TG
RAN
T DEN
Y: DEN
Y
Alarm Sum
mary: C
urrentAlarm
Summ
ary: Unacknow
ledgedAlarm
Summ
ary: Unreported
Alarm Sum
mary: D
isabled
UPD
ATE_EVT_MEN
UW
RITE_ALM
_MEN
U
WR
_ALM: U
nacknowledged
WR
_ALM: Alarm
StateW
R_ALM
: Time Stam
pW
R_ALM
: SubcodeW
R_ALM
: Discrete Value
TopWorx S
CM
-FF M
enu Structure -
For Handheld D
evices and H
ost System
s that Support D
D M
enus
www.topworx.com
21
TM
Appendix C: Transducer Block Transducer Block Initialization There are several settings in the transducer block that should be set before commissioning of the SCM-FF. Through these parameters, a user can configure a wide range of diagnostics and alarms. These include cycle timers, and counters, as well as temperature monitoring. The alarm conditions can be configured through a transducer channel in one DI Block. Also, the user may configure the SCM-FF for use in Single or Dual pilot valves for Direct or Reverse Acting applications, all through convenient Transducer settings. (a) Diagnostics & Alarming There will be 5 limit parameters that must be set during calibration. These parameters will vary with the type of valve the device is operating. The alarm priorities must also be set, depending on the application. By simply changing the settings in the transducer, all the diagnostic limits and functional settings can be set by the end user.
1. Cycle Times Set the Cycle Time Open Limit (LIM_CYC_OPEN_TIME) and the
Cycle Time Close Limit (LIM_CYC_CLOSE_TIME) parameters to the maximum amount of time in seconds the valve is allowed to complete its stroke before an alarm condition is invoked. If the LEDs are enabled, they will blink for local notification of the time limit alarms. If the Cycle Time Open Limit is exceeded, the green LED will flash. If the Cycle Time Close Limit is exceeded, the red LED will flash. Pushing the Alarm Reset Pushbutton on the board will stop the flashing.
The default setting for both the Cycle Time Open and Cycle Time
Closed Time Limit is 10 seconds. 2. Cycle Count Set the Cycle Count Limit (LIM_CYC_COUNT) parameter to the
maximum number of valve cycles allowed before a Cycle Count Alarm condition is activated.
The default setting for the Cycle Count Limit is 50000 cycles.
3. Temperature The Temperature High Limit (HI_LIM_BOARD_TEMP) parameter
should be set to alarm when the temperature sensor reads above a user specified value and the Temperature Low Limit (LO_LIM_BOARD_TEMP) will be set to alarm when the temperature sensor reads below a user specified value.
The default setting for the Temperature High Limit is 50°C. The default setting for the Temperature Low Limit is -10°C.
(b) Functional Settings
1. Single-Dual Action The ACTION_ELEMENT parameter is used to determine what
direction the actuator goes when energized. The 2 settings of the ACTION_ELEMENT parameter are Direct and Reverse Acting. “Reverse Acting” is to be used when the energized state is to close the valve.
The Default setting for Action Element is DIRECT Action.
2. Channel 13 Channel 13 is a user configurable input channel. The user can
define the functionality of a DI block associated with Channel 13 by selecting the appropriate bits in the CHAN_13_MASK parameter. One of several alarms can be used to trigger a DI including cycle count, over stroke timer, temperature or any combination of these. The unit is shipped with Channel 13 set up for over/under tempera-ture indication.
The following is a list of bit selections for Channel 13. Simply select the appropriate bit to activate the desired functionality.
0x00, No Selection 0x01, Cycle Count 0x02, Time to Open 0x04, Time to Close 0x08, Board Temp Hi 0x10, Board Temp Lo
(c) Calibration Switch Functionality The SCM-FF is shipped in a mode where the calibration switch is active. A 9 to 32 VDC power supply can be used to activate and deactivate the device, to open and close the valve, and set the target. In order to enable the calibration switch in a safe manner, three conditions are required to be true simultaneously. These are:
1. CAL_SW_ARM parameter is TRUE/Armed. The operator may consider this like a calibration switch lock out parameter when disabled.
2. The calibration switch on the SCM-FF must be in the FF position. This allows smooth transition to the manual control condition.
3. Transducer block must be in the Out Of Service (OOS) mode. This sets all of the connected output parameters to a BAD status, allowing upstream controllers to recognize the device is not controlled by the control scheme.
The CAL_SW_STATE parameter transitions to Enabled when all three conditions have been met simultaneously. This parameter will transition to the disabled state when the Transducer Block is placed into service or the CAL_SW_ARM is set to disabled. NOTE When the transducer mode changes from OOS mode, the valve will go to the FF position calculated at the time regardless of the current position of the valve or the Calibration switch. Transducer Special Diagnostic Features During installation, a special diagnostic parameter called ACTIVE _BLOCK_ALMS can be used to alert the user of configura-tion errors specific to the device. This block is used to conveniently identify some of the issues that may arise with installing the SCM-FF. The values returned are explained below:
a. None Active - No active block alarms are active. b. Invalid Mode - The computed actual mode for the block is
not supported the block’s actual mode will go to out of service.
c. Mode Error - The mode calculator detected an error. d. Both Contacts Closed - Both contacts are closed. e. Conflicting Channels Assigned - Conflicting output
channels have been assigned. (See DO Block Section for a description of the correct configuration of output channels).
f. Open without Close - An ‘Open’ output channel has been assigned without a ‘Close’ channel.
g. No Output Channels - No output channels have been assigned.
h. Out Of Service - Transducer block is out of service. i. Invalid Input - The target position is not valid for the
current device configuration. Check the target setting to insure that it is in the correct position.
Stroke Valve Method The method allows the user to simply invoke the method, receive appropriate warnings of using an operating process and then allow the user to repeatedly open/close the valve while viewing the actual feedback from the valve on the screen. This method automatically makes the necessary transducer block mode changes to enter the method and automatically reinstate the previous transducer block mode when the method exits. This prevents the user from uninten-tionally rendering the device unusable from the host control system.
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
22
Transducer Parameters to be set before an application is configured. For a complete list of transducer parameters, refer to Page 24.
*The timer accuracy for stroke time open and stroke time closed is 60mS minimum.
www.topworx.com
23
TM
Fieldbus Foundation Transducer Channel Architecture The SCM-FF has one transducer block with 13 channels. The 5 DI and 3 DO function blocks will link to these trans-ducer channels through the standard channel selection capability. (See Function Blocks) The 13 Transducer Channels are listed below. Transducer Channels
Notes on Channels Channels 1 and 5 These are Multi-value DO blocks standard with Fieldbus Foundation. Channel 1 is intended for use with a single control signal, while Channel 5 is to be used with a dual control signal. Channels 2, 3 and 4 Channels 2, 3 and 4 use 0 = false and 1 = true for open, close, and stop. This gives a more comfortable interface for users more familiar with ladder logic. In the situation where Open and Close are both true (or false) at the same time, the last input is rejected as invalid. Readback signals are 0 = false and 1 = true for is-opened, is-closed or is-stopped. Channels 2, 3 and 4 cannot be used simultaneously with channels 1 or 5. Channels 4 and 5 Available with a Dual-Control Pneumatic valve. Channels 6, 7 and 8 Echoes the Readback information from channels 1, 2 and 3. Channel 9 Reflects the input from a dry contact type of input wired into the Auxiliary input screw terminals and uses 0 = closed, 1 = opened reflecting the contact condition.
Channels 10, 11 and 12 Reflects alarm conditions in the valve. When something needs to happen in response to these error conditions, a DI should be used to publish the state of the alarm condition. These channels use 0 = false (no alarm), 1 = true (alarm condition exists). CTOA, CTCA, and CCA are transducer channels that allow alarms to be scheduled into the system. These alarms are:
Cycle Time Open Alarm (CTOA – Channel 10) Cycle Time Closed Alarm (CTCA – Channel 11) Cycle Count Alarm (CCA – Channel 12)
Above inputs are used in preventative maintenance and indicate when a valve is operating outside of acceptable times. These channels exist so that some action on the loop can be scheduled in critical applications. Cycle times may increase with an increase in valve stiction, and/or a loss of air pressure. The times and counts used as alarm limits are user settable (see Appendix 2). Regardless of whether these alarms are linked to function blocks, these FF standard alarms are always reported to the alarm handling host when one of these conditions exists and the corresponding priority is set to greater than 1. Channel 13 Stimulates activity when a set of alarm conditions exist. This channel uses a user-settable mask to allow any of five alarm conditions to cause the linkable DI parameter to become true. Channel 13 is a masked OR function. It includes the previous alarms, as well as a Temperature High (TMPH), and Temperature Low (TMPL) alerts. For TMPH and TMPL, a sensor is used to sense the temperature of the circuit board. The user can select which of these alerts on Channel 13 are to be used by masking out the undesired ones.
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
24
Complete Transducer Parameter Listing
www.topworx.com
25
TM
Complete Transducer Parameter Listing (cont.)
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
26
MO
DE_TR
ANS_B
LK_M
ENU
TRAN
SDU
CER
BLO
CK
CO
NTR
OL_PAR
AM_
MEN
U
STRA
TEGY **
ALERT K
EYM
OD
E_BLK
:TAR
GET_M
OD
E**M
OD
E_BLK
: ACTU
AL_MO
DE
MO
DE_B
LK: PER
MITTED
_MO
DE**
MO
DE_B
LK: N
OR
MAL_M
OD
E
PRI_C
YC_C
LOSE_TIM
E **LIM
_CYC
_CLO
SE_TIME **
CYC
LE_CLO
SE_TIME_ALM
_MEN
U
DEV_ALM
_MEN
U
PRI_C
YC_C
OU
NT **
LIM_C
YC_C
OU
NT **
CYC
LE_CO
UN
T_ALM_M
ENU
PRI_C
YC_O
PEN_TIM
E **LIM
_CYC
_OPEN
_TIME **
CYC
LE_OPEN
_TIME_ALM
_MEN
U
PRI_B
OA
RD
_TEMP **
HI_LIM
_BO
AR
D_TEM
P **LO
_LIM_B
OA
RD
_TEMP **
BO
ARD
_TEMP_ALM
_MEN
U
AC
TION
_ELEMEN
T **LED
_ENA
BLE **
FAU
LT_STATE **
CA
L_SW_A
RM
**C
AL_SW_PO
SITION
CAL_SW
_STATEC
LR_C
YC_C
OU
NT **
CH
AN
_13_MA
SK **
CYC
_CO
UN
T_ALM
_MEN
U
CYC
_OPEN
_ALM_M
ENU
CYC
_CLO
SE_ALM
_MEN
U
BO
ARD
_TEMP
_HI_LO
_ALM_
MEN
U
DEV_SETU
P_M
ENU
DISPLAY_TR
ANS_M
ENU
ALM_VAR
_MEN
U
LAST_OPEN
_TIME
LAST_CLO
SE_TIME
CYC
LE CO
UN
TALER
T_KEY
BLK
_ALM_M
ENU
ACTIVE_B
LOC
K_AL
MS
UN
ACK
_BLO
CK
_ALMS
ALM_STATE_B
LOC
K_ALM
TIME_STAM
P_BLO
CK
_ALMSU
BC
OD
E_BLO
CK
_ALMVALU
E_BLO
CK
_ALM
DEV_VAR
FINAL_VALU
E_D_M
ENU
SP_D_M
ENU
FINAL_PO
S_VAL_D_M
ENU
DISC
_STATE
BLK
_PARAM
_M
ENU
SUPPO
RTED
_MO
DES
TAG
_DESC **
Characteristics
: Block Tag
ALERT K
EYFAC
TOR
Y_CAL
STATUS_M
ENU
BLO
CK
_ERR
ST_REV
UPD
ATE_EVT_MEN
U
STRO
KE_VALVE_
MEN
UStroke Valve M
ethod
** Denotes W
ritable Fields
CYC
_CO
UN
T_ALM: U
nacknowledged
CYC
_CO
UN
T_ALM: Alarm
StateC
YC_C
OU
NT_ALM
: Time Stam
pC
YC_C
OU
NT_ALM
: SubcodeC
YC_C
OU
NT_ALM
: Float Valve
CYC
LE_OPEN
_TIME_ALM
: Unacknow
ledgedC
YCLE_O
PEN_TIM
E_ALM: Alarm
StateC
YCLE_O
PEN_TIM
E_ALM: Tim
e Stamp
CYC
LE_OPEN
_TIME_ALM
: SubcodeC
YCLE_O
PEN_TIM
E_ALM: Float Valve
CYC
LE_CLO
SE_TIME_ALM
: Unacknow
ledgedC
YCLE_C
LOSE_TIM
E_ALM: Alarm
StateC
YCLE_C
LOSE_TIM
E_ALM: Tim
e Stamp
CYC
LE_CLO
SE_TIME_ALM
: SubcodeC
YCLE_C
LOSE_TIM
E_ALM: Float Valve
BO
ARD
_TEMP_ALM
: U
nacknowledged
BO
ARD
_TEMP_ALM
: Alarm State
BO
ARD
_TEMP_ALM
: Time Stam
pB
OAR
D_TEM
P_ALM: Subcode
BO
ARD
_TEMP_ALM
: Float Valve
UPD
_EVT: Unacknow
ledgedU
PD_EVT: U
pdate SetU
PD_EVT: Tim
e Stamp
UPD
_EVT: Static Rev
UPD
_EVT: Relative Index
FINAL_VAL_D
: DSC
_CO
N_FV
FINAL_VAL_D
: Status
SP_D: D
SC_C
ON
_SP**SP_D
: Status**
FINAL_PO
S_VAL_D: D
SC_C
ON
_FVFIN
AL_POS_VAL_D
: Status
TopWorx SC
M-FF
Menu Structure -
For Handheld D
evices and H
ost Systems that Support
DD
Menus
www.topworx.com
27
TM
Appendix D: Discrete Output (DO) Discrete OUTPUT Blocks (DO Block) There are 3 FOUNDATION Fieldbus standard DO blocks and 5 output channels. The DO blocks take discrete control data and translate it to actuation in the field. These blocks are used to open and close the valve. There are 4 different strate-gies provided to open and close a valve, depending on the system being used, and whether a single or dual action pilot valve is being used. Single Block Control Method, Single Action (Default) Set the Channel Parameter of DO1 to 1(Open/Close Output), and DO2 and DO3 to 0 (No Connection). The valve is now controlled by the wiring going to the V1 terminals. By writing a 0 or a 1 to this DO block will now open and close the valve. Single Block Control Method, Dual Action Set the Channel Parameter of DO1 to 5 (Open/Close/Stop Output), and DO2 and DO3 to 0. The valve is now controlled by the wiring going to the V1 termi-nals and V2 terminals. By writing a 0 or a 1 to this DO block will now open and close the valve. Writing a 2 to the DO block will de-energize both the V1 and V2 terminals, stopping a valve using a block center type of pneumatic valve. Dual Block Control Method, Single Action Set the Channel Parameter of DO1 to 2 (Open), DO2 to 3 (Close), and DO3 to 0. Now by writing a 1 to DO1, the valve will Open. Changing this value back to 0, and writing a 1 to DO2 will cause the valve to close. Three Block Control Method, Dual Action Set the Channel Parameter of DO1 to 2 (Open) , DO2 to 3 (Close), and DO3 to 4 (Stop). Now by writing a 1 to DO1, the valve will Open. Changing this value back to 0, and writing a 1 to DO2 will cause the valve to close. Changing this value back to 0, and writing a 1 to DO3 will cause the outputs to terminals V1 and V2 to turn off, stopping an actuator using a block center pneumatic valve. Note on Energize to Close To energize to close (also called Reverse Acting), the ACTION_ELEMENT parameter must be reset to Reverse Acting. See the Transducer section for more details.
To use the READBACK_D values for the BACK CALCULATION OUTPUT DISCRETE parameter of the DO block, the following two options must be selected: 1. In the Resource Block the “Output Readback” option should be selected. 2. In the DO Block under IO_OPTS, select the “Use PV for BKCAL_OUT” option.
Configuration Error Handling In order to minimize configuration errors, several write checking features have been added to the SCM-FF. Write checks to the CHANNEL parameter of the DO blocks should prevent illegal configurations. These illegal configurations are:
1. If the two-state Channel 1 Open-Close has been assigned, an attempt to assign Channel 2 Open, Channel 3 Close or the Channel 5 Open/Close/Stop channels will be rejected with a write check.
2. If the three-state Channel 5 Open-Close-Stop has been assigned, an attempt to assign the Channel 2 Open, the Channel 3 Close or the Chan-nel 1 Open/Close channels will be rejected with a write check.
3. If the channel you are trying to assign has already been assigned to an-other Function Block, the write will be rejected with a write check.
4. If the Open channel has been assigned and the Close channel has not, an ‘Open without Close’ block alarm is generated by the block. NO OTH-ER LOCK-OUTS ARE IMPLEMENTED (no write-check). This becomes an open only valve. Without the close signal, the last position will be maintained.
5. If the Close channel has been assigned and the Open channel has not, a ‘Conflicting Channels Assigned’ block alarm is generated by the block. NO OTHER LOCK-OUTS ARE IMPLEMENTED (no write-check). This becomes a close only valve.
Error handling for the configuration of channels has been modified as well. The Transducer Block has a special BLOCK_ALARMS_ACTIVE parameter which may be used to diagnose a configuration problem. The configuration errors are listed in Table 2.
Table 1. Discrete Output Channel Assignments
Table 2. Transducer Block’s BLOCK_ALARMS_ACTIVE Parameter
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
28
Complete Discrete Output Block Parameter Listing
www.topworx.com
29
TM
Appendix E: Discrete Input (DI) Block
Discrete INPUT Blocks (DI Block) There are 5 Discrete Input Blocks available on the SCM-FF. The DI block takes the manufacturer’s discrete input data, selected by channel number, and makes it available to other function blocks at its output. These DI blocks become available to the user when linked to one of the Transducer Channels available for inputs. A host may retrieve internal information at any time and alarms are reported as they occur. To make a light come on or another valve close requires a DI to publish the information on the bus. Channels The 5 DI Function Blocks in the device are associated to the real world by setting the CHANNEL parameter to the desired Transducer Channel. Illustration 11 shows the relationship between Transducer channels and the DI assigned channels. The output of the DI block (viewed in the OUT_D parameter) is defined by the DI block’s CHANNEL assignment. The valid settings for the CHAN-NEL parameters are listed in Table 7. By resetting a DI CHANNEL parameter to a different transducer channel number (0, 6-13, see Table 1) an end user may customize the functionality of the SCM-FF to fit a particular application requiring DI’s on temperature limits and cycle counts instead of the defaults.
Illustration 11. Channel Assignment for DI Function Blocks
Channels
Valve is Opened/ Valve is Closed 6Valve is Opened 7Valve is Closed 8Auxillary Limit Switch.input 9Cycle Time Open Alarm (CTOA) 10Cycle Time Closed Alarm (CTCA) 11Cycle Count Alarm (CCA) 12CTOA | CTCA | CCA| TMPH|TMPL 13
Transducer DI Function Block
Channel = 6
OUT_D
Is Closed Is Opened Is Stopped Is Opening Is Closing
PV_D
1 2 3 4 5
Channels
Valve is Opened/ Valve is Closed 6Valve is Opened 7Valve is Closed 8Auxillary Limit Switch.input 9Cycle Time Open Alarm (CTOA) 10Cycle Time Closed Alarm (CTCA) 11Cycle Count Alarm (CCA) 12CTOA | CTCA | CCA| TMPH|TMPL 13
Transducer DI Function Block
Channel = 6
OUT_D
Is Closed Is Opened Is Stopped Is Opening Is Closing
PV_D
Channels
Valve is Opened/ Valve is Closed 6Valve is Opened 7Valve is Closed 8Auxillary Limit Switch.input 9Cycle Time Open Alarm (CTOA) 10Cycle Time Closed Alarm (CTCA) 11Cycle Count Alarm (CCA) 12CTOA | CTCA | CCA| TMPH|TMPL 13
Transducer DI Function Block
Channel = 6
OUT_D
Is Closed Is Opened Is Stopped Is Opening Is Closing
PV_D
1 2 3 4 5
Table 1: DI Channel Parameter Settings List
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
30
Complete Discrete Input Block Parameter Listing
www.topworx.com
31
TM
Appendix F: Dimension and Assembly Drawings
Valvetop DXP
MOUNTING SURFACE
.85 2.10
4.52
6.21
MINIMUM 2.5" REQUIRED CLEARANCE IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
SHAFT TYPE OPTIONALSEE SHAFT DETAIL
SECTION
2.13
6.65
6.76
3.85
2.25
2.25 5/16-18 UNC - 2B .44 DEEP
VALVE TYPE OPTIONALSEE INTEGRATED PNEUMATICCONTROL VALVES SECTION
2.19
OPTIONAL CONDUIT ENTRIESUSED ONLY WHEN 4 ENTRIESARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
MATERIALS OF CONSTRUCTION
Enclosure Cast A360 aluminum with dichro-mate conversion coating inside & out, epoxy coated exterior rated for 250 hrs salt spray per ASTM B117
Fasteners 304 Stainless Steel standard 316 Stainless Steel optional
Shaft 304 Stainless Steel standard 316 Stainless Steel optional
Shaft Bushing Oilite Bronze
Indicator Dome Polycarbonate, UV F1 rated
Seals O-ring seals available in: Buna, Silicone, EPDM & Viton
Maximum Fastener Torque Specifications Enclosure Housing Bolts 8 ft-lbs [10.8 N·m]
Indicator Dome Screws 20 in-oz [141 mN·m]
Bottom Mounting Holes 10 ft-lbs [13.6 N·m]
Illustration #4
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
32
Valvetop DXP - IIC
MATERIALS OF CONSTRUCTION
Enclosure Cast A360 aluminum with dichro-mate conversion coating inside & out, epoxy coated exterior rated for 250 hrs salt spray per ASTM B117
Fasteners 304 Stainless Steel standard 316 Stainless Steel optional
Shaft 304 Stainless Steel standard 316 Stainless Steel optional
Shaft Bushing Oilite Bronze
Indicator Dome Polycarbonate, UV F1 rated
Seals O-ring seals available in: Buna, Silicone, EPDM & Viton
Maximum Fastener Torque Specifications
Enclosure Housing Bolts 8 ft-lbs [10.8 N·m]
Indicator Dome Screws 20 in-oz [141 mN·m]
Bottom Mounting Holes 10 ft-lbs [13.6 N·m]
Illustration #5
www.topworx.com
33
TM
Valvetop DXS
MOUNTING SURFACE
.85 2.10
4.52
6.21
MINIMUM 2.5" REQUIRED CLEARANCE IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
SHAFT TYPE OPTIONALSEE SHAFT DETAIL
SECTION
2.13
6.65
6.76
3.85
2.25
2.25 5/16-18 UNC - 2B .44 DEEP
VALVE TYPE OPTIONALSEE INTEGRATED PNEUMATICCONTROL VALVES SECTION
2.19
OPTIONAL CONDUIT ENTRIESUSED ONLY WHEN 4 ENTRIESARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
MATERIALS OF CONSTRUCTION
Enclosure Cast 316 Stainless Steel
Fasteners 304 Stainless Steel standard 316 Stainless Steel optional
Shaft 304 Stainless Steel standard 316 Stainless Steel optional
Shaft Bushing N/A
Indicator Dome Polycarbonate, UV F1 rated
Seals O-ring seals available in: Buna, Silicone, EPDM & Viton
Maximum Fastener Torque Specifications Enclosure Housing Bolts 8 ft-lbs [10.8 N·m]
Indicator Dome Screws 20 in-oz [141 mN·m]
Bottom Mounting Holes 10 ft-lbs [13.6 N·m]
Illustration #6
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
34
SHAFT TYPE OPTIONALSEE SHAFT DETAIL
SECTION
2.00
1.10
2.10
4.51
6.21
MINIMUM 2.5" REQUIRED CLEARANCEIN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
2.25
2.25
5.03
3.66
6.10
2.14
VALVE TYPE OPTIONALSEE INTEGRATED PNEUMATIC
CONTROL VALVES SECTION
5/16-18 UNC - 2B.44DP
MOUNTING SURFACE
OPTIONAL CONDUIT ENTRIESUSED ONLY WHEN 4 ENTRIESARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
Valvetop DXR
MATERIALS OF CONSTRUCTION
Enclosure Valox® 364
Fasteners 304 Stainless Steel standard 316 Stainless Steel optional
Shaft 304 Stainless Steel standard 316 Stainless Steel optional
Shaft Bushing Delrin® 500P white
Indicator Dome Polycarbonate, UV F1 rated
Seals O-ring seals available in: Buna, Silicone, EPDM & Viton
Maximum Fastener Torque Specifications Enclosure Housing Bolts 10 in-lbs [903 mN·m]
Indicator Dome Screws 20 in-oz [141 mN·m]
Bottom Mounting Holes 8 ft-lbs [13.6 N·m]
Illustration #7
www.topworx.com
35
TM
Safe Use
Special Conditions of Safe Use (All installations) Clean only with a damp cloth to prevent possibility of electrostatic discharge. For Explosion Proof installations, the internal ground connection shall be used and the external ground connection, if supplied in addition, is supplemental bonding allowed where local authorities permit, or is required. When installing with a third party listed nipple-mount solenoid, it is the responsibility of the installer to provide fittings, and apparatus, suitable for the area classification in accordance with the National Electrical Code. All cable entry devices or conduit stopping boxes shall be certified in type of explosion protection ‘d’, suitable for the conditions of use and correctly installed. The IIC enclosures are excluded from use in carbon disulphide atmospheres. The air pressure to the valve block, when fitted, shall not exceed 7bar.
Preventative Maintenance The TopWorx Valvetop is designed to operate for one million cycles without servicing. Call TopWorx when you are approaching this milestone for a preventative maintenance kit and instructions.
Appendix G: Specifications and Reference Data
Table 1. Intrinsically Safe Entity Parameters
Table 2. Electrical Specifications
Table 3. Fieldbus Specifications
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
36
Certifications & Approvals
0518 AREA CERTIFICATION
DXP
0
Ex ia IIC T4 –40°C ≤ Tamb ≤ 80°C, IP67 DEMKO 02ATEX0223499X Ui:24Vdc, Ii:250mA, Pi:1,2W, Ci:2.5nF, Li:129µH Class I Div 1&2 Groups A,B,C,D; T4; Type 4, 4X Intrinsically Safe / Securite Intrinsique Electrical Rating: 9-32Vdc, 20mA
1
Class I Div 1 Groups C,D; Class 1 Div 2 Groups A,B,C,D Type 4, 4X Ex d IIB+H2 T6 –40°C ≤ Tamb ≤ 60°C, IP67 SIRA 07ATEX1273X IECEx SIR 07.0093X Electrical Rating: 9-32Vdc, 20mA
2 Class I Div 2 Groups A,B,C,D; Type 4, 4X Ex nC IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67 Electrical Rating: 9-32Vdc, 20mA
C
Ex d IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67 SIRA 07ATEX1273X IECEx SIR 06.0093X Max Current 500mA @ Max Voltage 25V
W NEMA 4, 4X
DXS
0
Ex ia IIC T4 –40°C ≤ Tamb ≤ 80°C, IP67 DEMKO 02ATEX0223499X Ui:24Vdc, Ii:250mA, Pi:1,2W, Ci:2.5nF, Li:129µH Class I Div 1&2 Groups A,B,C,D; T4; Type 4, 4X Intrinsically Safe / Securite Intrinsique Electrical Rating: 9-32Vdc, 20mA
1
Class I Div 1 Groups C,D; Class 1 Div 2 Groups A,B,C,D Type 4, 4X Ex d IIB+H2 T6 –40°C ≤ Tamb ≤ 60°C, IP67 SIRA 07ATEX1273X IECEx SIR 07.0093X Max Current 500mA @ Max Voltage 25V
2 Class I Div 2 Groups A,B,C,D; Type 4, 4X Ex nC IIC T6 –40°C ≤ Tamb ≤ 60°C, IP67 Electrical Rating: 9-32Vdc, 20mA
W NEMA 4, 4X
DXR G Type 4, 4X
Electrical Rating: 9-32Vdc, 20mA
W Type 4, 4X Electrical Rating: 9-32Vdc, 20mA
www.topworx.com
37
TM
Warranty
D-Series with FF Option Installation, Operation & Maintenance 502.969.8000
38
NOTES:
www.topworx.com
39
TM
NOTES:
S-K131 R13
Visit www.topworx.com for comprehensive information on our company, capabilities, and products — including model numbers, data sheets, specifications, dimensions, and certifications. [email protected]
www.topworx.com
™
™
The Emerson logo is a trademark and a service mark of Emerson Electric Co. ©2014 Emerson Electric Co. ©2014 TopWorx™, All rights reserved.TopWorx, Valvetop, and GO Switch are trademarks of TopWorx™. All other marks used in this document are the property of their respective owners. Information contained herein - including product specifications is subject to change without notice.
GLOBAL SUPPORT OFFICES
North America 3300 Fern Valley Road Louisville, Kentucky 40213 USA +1 502 969 8000 [email protected] Middle East P.O. Box 17033 Jebel Ali Free Zone —South 2 Dubai 17033 United Arab Emirates +9714 8118283 [email protected]
Asia-Pacific 1 Pandan Crescent Singapore 128461 +65 6891 7550 [email protected] Africa 24 Angus Crescent Longmeadow Business Estate East Modderfontein Gauteng South Africa +27 011 451 3700 [email protected]
Europe Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU UK +44 0161 406 5155 [email protected]