user manual ibs s5 sl lb um e - phoenix contact

46
5004C INTERBUS User Manual Communication Interface Board for Siemens S5 Designation: Revision: Order No.: This manual is valid for: IBS S5 SL LB Order No.: 28 06 94 3 © Phoenix Contact 02/1997 IBS S5 SL LB UM E C 27 53 74 0

Upload: others

Post on 23-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

5004C

INTERBUSUser Manual

Communication Interface Board for Siemens S5

Designation:

Revision:

Order No.:

This manual is valid for:

IBS S5 SL LB Order No.: 28 06 94 3

© Phoenix Contact 02/1997

IBS S5 SL LB UM E

C

27 53 74 0

Page 2: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT
Page 3: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

5004C

INTERBUS

Please Observe the Following:

In order to guarantee that your use of this manual is as straightforward as pos-sible and that hardware is used safely in the installation, operation and mainte-nance phases, we request that you carefully read and observe the following notes:

Explanation of Symbols Used

The attention symbol refers to erroneous handling which could lead to damage to the hardware or software, or in indirect connection with dangerous process peripherals, to personal injury. This symbol is always located to the left of the tagged text.

The hand symbol gives you tips and advice on the efficient use of hardware and on software optimization. In addition, text marked in this way informs you of sys-tem-related conditions that must absolutely be observed to achieve error-free operation. The hand is also found in front of clarifications of terms.

The text symbol refers to detailed sources of information (manuals, data sheets, literature, etc.) on the subject matter, product, etc. This text also provides helpful information for the orientation, reading order, etc. in the manual.

We Are Interested in Your Opinion

We are constantly attempting to improve the quality of our manuals. Should you have any suggestions or recommendations for improvement of the contents and layout of our manuals, we would appreciate it if you would send us your com-ments.

Statement of Legal Authority

This manual, including all illustrations contained herein, is copyright protected. Use of this manual by any third party in departure from the copyright provision is forbidden. Reproduction, translation, or electronic or photographic archiving or alteration requires the express written consent of Phoe-nix Contact. Violations are liable for damages. Phoenix Contact reserves the right to make any technical changes that serve for the purpose of technical progress. Phoenix Contact reserves all rights in the case of patent award or listing of a registered design. External products are always named without reference to patent rights. The existence of such rights shall not be excluded. The use of products described in this manual is oriented exclusively to qualified who are familiar with the safety concepts of automation technology, the use and effects of INTERBUS-specific commands and messages as well with applicable national standards.Phoenix Contact assumes no liability for erroneous handling or damage to Phoenix Contact or ex-ternal products resulting from disregard of information contained in this manual.

Page 4: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

5004C

INTERBUS

Page 5: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSIBS S5 SL LB UM E

i5004C

Table of Contents

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

1.1 Short Description . . . . . . . . . . . . . . . . . . 1-3

1.1.1 IBS S5 SL LB Communication Interface Board . . . . . . . 1-3

1.2 Definitions . . . . . . . . . . . . . . . . . . . . . 1-4

2 Addressing the Board Within the Slave System. . . . . . . . . . . . . . . 2-3

2.1 Switch Meanings and Settings . . . . . . . . . . . . . 2-3

2.1.1 Number of Communication Registers. . . . . . . . . . . 2-3

2.1.2 Communication Register Addressing . . . . . . . . . . . 2-3

3 Addressing Within the INTERBUS Master System. . . . . . . . . . . . . . 3-3

3.1 INTERBUS I/O Representations . . . . . . . . . . . . 3-5

4 Detecting Error States - With Communication Register 0 . . . . . . . . . . . 4-3

5 Configuration of the IBS S5 SL LB Board . . . . . . . . . . . . . . . . . 5-3

5.1 Jumpers Locations and Setting Positions . . . . . . . . . 5-3

5.2 Jumper Settings . . . . . . . . . . . . . . . . . . . 5-3

5.2.1 Master System Failure . . . . . . . . . . . . . . . . 5-4

5.2.2 Slave System Failure . . . . . . . . . . . . . . . . . 5-4

5.2.3 Swapping Bytes in the Word (SWAP) . . . . . . . . . . 5-5

5.2.4 Bus Master Information on Active BASP Signal or PLC Voltage Failure . . . . . . . . . . . . . . . . . 5-6

5.2.5 Operation in the Central Controller/Controller Expansion Unit . 5-6

6 Slots in SIMATIC S5 Systems . . . . . . . . . . . . . . . . . . . . . . 6-3

7 INTERBUS Connection and Diagnstic LEDs . . . . . . . . . . . . . . . . 7-3

7.1 INTERBUS Connection . . . . . . . . . . . . . . . . 7-3

7.2 Diagnostic LEDs. . . . . . . . . . . . . . . . . . . 7-4

Page 6: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSIBS S5 SL LB UM E

5004Cii 5004C

Page 7: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

1-15004C

Introduction

This section provides information on

- the basic function of the communication interface bord in the INTERBUS system

- the locations and functions of hardware switches and connectors- the meanings of certain terms used in this manual

Section 1

1.1 Short Description . . . . . . . . . . . . . . . . . . 1-31.1.1 IBS S5 SL LB Communication Interface Board . . . . . . . 1-31.2 Definitions . . . . . . . . . . . . . . . . . . . . . 1-4

Page 8: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

1-2 5004C

Page 9: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSIntroduction

1-35004C

1 Introduction

1.1 Short Description

With the IBS S5 SL LB communication interface board, the INTERBUS systemcan directly transfer data from a host computer to a subordinate control systemor vice versa. For this purpose the commmunication interface includes up to 16bidirectional registers. In case of a system failure or bus malfunctions the masteror slave system can respond to the error.

The user determines the behavior of the communication interface board. To this effect there are seven switches (S2, switch field: S1.3 through S1.8; Figure 1-1) and seven jumpers (X3-X5, X7-X11; Figure 1-1). The switch and jumper func-tions will be explained in the following sections.

1.1.1 IBS S5 SL LB Communication Interface Board

The IBS S5/SL-LB communication interface board is an element of the local busand behaves essentially like a module with digital inputs and outputs.The advantage is that defined groups can be disabled; i.e. a local bus branchcan be disabled while the rest of the INTERBUS system remains active.The user determines the behavior of the IBS I/O communication interface board.To this effect a switch field (S1.3 through S 1-8; Figure 1-1) is provided, whichis used to configure the following:

- Setting of the base address- Locations of the registers in the Q or P area of the PLC.

Jumpers X3 and X4 (Figure 1-1) can be used to respond to slave and mastersystem errors.In addition, there are also the jumpers X5, X7, X8, X9, X10 and X11 which willbe explained further below.

The switch functions will be explained in Section 2, the jumper functions in Section 5.

Page 10: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSIntroduction

1-4 5004C

1.2 Defintions

The IBS S5 SL LB board is operated in an INTERBUS system. The board hasthe identification no. 171 (hex: AB). The INTERBUS controller board controls thedata transfer from or to the communication interface board. For this reason twosystems have to be distinguished in the following: - the master system (with the INTERBUS controller board) and - the slave system (with the communication interface board).

For this INTERBUS configuration, the master does not have to be of the sametype as the slave system. All control systems and computers for which there areINTERBUS controller boards can be used as a master system:

In order to look at things in the same way the following will be agreed upon.The definition of the data direction uses the master system as the point of refer-ence.This means:

- OUT data is written by the master system to the IBS I/O communication inter-face registers,

- IN data is transferred by the slave system to the master.

In programming terms, the term "address" refers to a byte-by-byte access. Ofcourse, the PLC programmer can also access the communication register byteson a bit-by-bit basis.

The term "communication register" is not equivalent to the same term used inthe host controller board manuals. The latter refers to reserved register locationsbelow the settable windows in the P and Q areas. The term used in this manual only refers to the settable I/O area of the commmu-nication interface board.

Page 11: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSDefintions

1-55004C

Figure 1-1: Front plate as well as locations of switches and jumpers on the communication interface board

5004B101

System connectorS5

S1.1

S1.8

X10 X9

X8 X7

X4

X3LEDs

X5

SWAPX11

ERR

BASPRES

4W

8WIN

OUT

8163264

128Q

S2

Error

Us

Error

US

Local In

Local Out

INTERBUS-S

INT

ER

BU

S IB

S S

5/S

L-L

B

Page 12: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSIntroduction

1-6 5004C

Page 13: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

2-15004C

Addressing the Board Within the Slave System

This section provides information on

- the address adaptation of the communication interface board to the slave system

- the meanings of the switches for setting the system addresses- examples for setting certain address areas

Section 2

2.1 Switch Meanings and Settings . . . . . . . . . . . . . 2-32.1.1 Number of Communication Registers. . . . . . . . . . . 2-32.1.2 Communication Register Addressing . . . . . . . . . . . 2-3

Page 14: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

2-2 5004C

Page 15: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing the Board Within the Slave System

2-35004C

2 Addressing the Board Within the Slave System

2.1 Switch Meanings and Settings

2.1.1 Number of Communication Registers

16 bidirectional, one-byte (eight-bit) communication registers (COM_REG_0 to COM_REG_15) are the heart of a communication interface board. The user can make full use of these registers.To offload both the slave system and the master system from invalid data, the user can limit the length of the communication in-terface board to eight bidirectional registers. The number of registers can be changed with S2 (Figure 1-1, 8 W (=words) = 16 bytes; 4 W (=words) = 8 bytes).

2.1.2 Communication Register Addressing

The switch setting of S1.3 determines whether the communication registers ofthe board appear in the P and Q area of the Siemens slave system. (Figure 2-1)The slave system addresses the communication registers to be set via theswitches S1.3 through S1.8 (Figure 2-1). The start address is the lowest addressat which the slave system writes to a communication register, or from which itreads. The start address is obtained by adding up the values that are assignedto the switches S1.4 through S1.8 (see Table 2-1). However, only the values ofthe switches in "ON" position are added up. Depending on the set length (withS2), seven or 15 further address above the start address are additionally occu-pied for the communication registers.

Page 16: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing the Board Within the Slave System

2-4 5004C

Figure 2-1: Address switch meaning

The address switch field is located on the lower right of the board. (Figure 1-1).

ON

OFF 1 2 3 4 5 6 7 8

Registers are in theP area of the PLC

0000

0

S1.1 to S1.8Default setting

Registers are in theQ area of the PLC

22

2

2

2

3

4

5

7

6

(only with 8 communicationregisters)

=128

=64=32

=16

Reserved

Reserved

5004A201

Reserved

Reserved

Page 17: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSCommunication Register Addressing

2-55004C

Table 2-1: Significance of the address switches

Figure 2-2 shows the switch settings in two examples:- Example 1 is true for 16 communication registers in the P area of the slave PLCoccupying the addresses 176 to 191;

- For the second example the communication interface board is operated witheight communication registers in the Q area of the slave system occupyingregister addresses from 56 to 63.

Since the communication interface board occupies a minimum of eight bytes in the address area of the slave system, the address lines A0 through A2 (with the associated values 20 = 1, 21 = 2 and 22 = 4) are always directly evaluated on the board. If the board is operated with 16 communication registers, A3 (with the val-ue 23 = 8) is also directly evaluated on the board.

This has two important consequences for the user:- If the board is operated with eight communication registers, the user can only choose a start address that can be divided by eight. Starting from the set ad-dress, the comunication board also occupies the following seven addresses.

- If the board is operated with 16 communication registers, the user can only choose a start address that can be divided by 16. Starting from the set address, the communication board also occupies the following 15 addresses.

Switch Value Comment

S1.8 23 = 8 This value is only considered when the start address is calcu-lated and the communication board is operated with a length of eight bidirectional registers. If the board is operated with 16 communication registers, this switch must be in the "OFF" po-sition.

S1.7 24 = 16

S1.6 25 = 32

S1.5 26 = 64

S1.4 27 = 128

S1.3 This switch determines whether the communication registers of the board appear in the P or Q area of the Siemens slave system.

Page 18: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing the Board Within the Slave System

2-6 5004C

Figure 2-2: Examples for setting switches S1.3 to S1.8

ON

OFF

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8

0

+ 16

+ 32

+ 0+ 128

in the P area

= 176

Example 1

ON

OFF

+ 16

+ 32

+ 0 + 0

in the Q area

= 56

Example 2

5004A202

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8

8

Page 19: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

3-15004C

Addressing Within the INTERBUS Master System

This section provides information on

- the address positions of the communication registers in the INTERBUS address field of the master system

- the basic possibilities with logical addressing- a configuration example for an INTERBUS system with a communication

interface board.

Section 3

3.1 INTERBUS I/O Representations . . . . . . . . . . . . 3-5

Page 20: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

3-2 5004C

Page 21: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing Within the INTERBUS Master System

3-35004C

3 Addressing Within the INTERBUS Master System

The addressing within the INTERBUS master system depends on the host con-troller board used. The addressing differs slightly between the various possiblemaster systems. For detailed information on the addressing refer to the user ma-nuals for the different host controller boards. At this point a configuration example (Figure 3-1) is used to show in principle theaddress locations for the communication registers in the INTERBUS addressarea of the master system.The number of communication registers is set with S2 (Figure 1-1; see also Section. 2, "Adressing Within the Slave System").

With logical addressing, the INTERBUS system allows the user to assign thesame address to IN and OUT data communication registers within the mastersystem. When logical addressing is used, the address of each module can be freely sel-ected within the used address window (in the master). Note that the communi-cation interface board requires 8 or 16 bytes (4 or 8 data words), which must betaken into account when the addresses are allocated.Please refer to the host controller board user manuals for a detailed descriptionof logical addressing.

There is no relationship between the base address of the communication inter-face board and the host controller board address window set in the host system(master). Both can be freely selected; i.e. they may even be identical.

Page 22: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing Within the INTERBUS Master System

3-4 5004C

Figure 3-1: Configuration example

Communicationinterface board

Local bus 1

Local bus 2

INTERBUS master system

PLC slave system

Remote bus

Remote bus

5004B301

Page 23: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSINTERBUS I/O Representations

3-55004C

3.1 INTERBUS I/O Representations

Owing to the different types of handling and representation of data structures,which are due to the use of different processors (e.g. Intel, Motorola), there is nostandard location of the data bytes at the INTERBUS I/O modules in connectionwith the different PLC and computer makes. Figure 3-2 shows the locations ofthe data bytes depending on the PLC or computer system.

Figure 3-2: INTERBUS I/O representations

* The representation for IBM PCs is only valid for the word-oriented access to pro-cess data. For the IBS PC CB/.../I-T controller boards it applies only when the macros for data conversion are used.

15 8 7 0 15 8 7 0

Byte n Byte n+1

1st word 2nd word

Byte n Byte n+1

a) IBS S5 DAB, IBS S5 DCB/ I-T

15 8 7 0 15 8 7 0

Byte n+1 Byte n+1Byte n Byte n

1st word 2nd word

b) IBS BA AT

15 8 7 0 15 8 7 0

Byte n Byte n+1

1st word 2nd word

Byte n Byte n+1

1st word 2nd word

1st word 2nd word

16 8 16 8

Byte n+1 Byte n+1Byte n Byte n

9 9 1

c) IBS VME CB/ I-T

d) IBS A25 DCB/ I-T

e) IBS PC AT-T, IBS PC CB/ .../ I-T *

15 8 7 0 15 8 7 0

Byte n+1 Byte n+1Byte n Byte n

5004B302

Page 24: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSAddressing Within the INTERBUS Master System

3-6 5004C

Page 25: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

4-15004C

Detecting Error Conditions -with Communication Register 0

This section provides information on

- the possibility of responding to error conditions in the slave or master system- the location of communication register 0

Section 4

Page 26: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

4-2 5004C

Page 27: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSDetecting Error Conditions With Communication Register 0

4-35004C

4 Detecting Error ConditionsWith Communication Register 0

Scanning communication register 0 gives the user the opportunity to respond to error conditions in the slave or master system.

A feature of the communication register 0 on the communication interface board is that it is cleared in a direction-dependent manner should slave or master er-rors occur. This is due to the fact that bit 7 can be used in both directions for sig-naling the error conditions.

Figure 4-1 shows the location of the communication register 0 in the data word. You can see that bits 8 to 15 of the first data word are assigned to this register.

Figure 4-1: Representation of registers 0 and 1 in the first data word

Bit 7 of the communication register is assigned to bit 15 of the data word. This applies, according to the signaling direction, to the input and output area of the S5 system.

As has been mentioned in Section 3, the arrangement of the bytes in the data word may vary depending on the controller board used.

MSB 1st data word LSB

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

7 Com_Reg0 0 7 Com_Reg1 0

Byte n Byte n+1

Error condition bit 7 5004A401

Page 28: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSDetecting Error Conditions With Communication Register 0

4-4 5004C

Page 29: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

5-15004C

Configuration of the IBS S5 SL LB Board

This section informs you on

- the locations of the jumpers on the communication interface board- the necessary jumper positions and the analysis of those jumper positions in

the event ofa) a master system failureb) a slave system failure

- the adaptation of the board to different master systems with regard to the order of bytes using jumper X5- the requirements when the board is operated in a SIMATIC expansion unit

Section 5

5.1 Jumpers Locations and Setting Positions . . . . . . . . . 5-35.2 Jumper Settings . . . . . . . . . . . . . . . . . . . 5-35.2.1 Master System Failure . . . . . . . . . . . . . . . . 5-45.2.2 Slave System Failure . . . . . . . . . . . . . . . . . 5-45.2.3 Swapping Bytes in the Word (SWAP) . . . . . . . . . . 5-55.2.4 Bus Master Information on Active BASP Signal or

PLC Voltage Failure . . . . . . . . . . . . . . . . . 5-65.2.5 Operation in the Central Controller/Controller Expansion Unit . 5-6

Page 30: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

5-2 5004C

Page 31: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSConfiguration of the IBS S5 SL LB Board

5-35004C

5 Configuration of the IBS S5 SL LB Board

5.1 Jumper Locations and Setting Positions

The locations of the jumpers (jumpers X3 to X5 and X7 to X11) are shown in Fig-ure 5-1.

Figure 5-1: Locations of the jumpers on the communication interface board

5.2 Jumper Settings

The jumpers allow the user to respond to fault conditions in the slave or in themaster system. As a result there are two message directions:

- Fault conditions in the slave system which can be reported to the master sys-tem

- Fault conditions in the master system, including the associated INTERBUS, to which the slave system can respond.

System connector S5

X10 X9

X8 X7

X4

X3

LEDs

LOCALBUS

X5X11

4W

8W

IN

OUT

8163264128Q

S2

Error

Us

123

3 2 1

3 2 1

3 2 1 3 2 1

5004C501

SWAPERR

RES

BASP

S1.1

S1.8

Page 32: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSConfiguration of the IBS S5 SL LB Board

5-4 5004C

5.2.1 Master System Failure

When the INTERBUS system fails or a remote or local bus is reset, all commu-nication registers are reset. For bit 7 of the communication register 0 this is only true if the jumper X4 (Figure 5-2) is in position 2-3.

Figure 5-2: Jumper X4 (Default position 2-3: In this position all communication registers are reset)

When the user puts jumper X4 in position 1-2, bit 7 of the communication regis-ter 0 shows a "1" during an active bus reset. If the slave system is to respond to a malfunction of the master, the user mustset X4 to position 1-2, and scan bit 7 of the communication register 0 in the slaveinput area.If this bit is to be used for data transfer as well, jumper X4 must remain in posi-tion 2-3 (default state). If jumper X4 is in position 2-3 and a master system failure occurs, the slave sys-tem receives on all bits the output value of the master system.When the master sytem fails, most host controller boards set the OUT data to"0". This is also true for the communication register data. Thus, the user is ableto recognize a master system failure (see description of communication register0).

5.2.2 Slave System Failure

In case of an S5 failure, the signal BASP at the control sytem is activated. In theslave system all digital outputs are set to the state "0". In addition, every statechange of the BASP signal results in a module status error when jumper X11 isin position 1-2 (see Section 5.2.4). The user cannot manipulate this behavior of the communication interface boardand the INTERBUS system.

When the voltage of the slave PLC fails, the words 5 to 8 transferred by the mas-ter system are returned by the slave as IN data!

3 2 1 5004B502

RES

Page 33: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSSwapping Bytes in the Word (SWAP)

5-55004C

The master system can respond in different ways to the module status error re-ported by the slave board:- If the master system is switched to the "STOP" state after an error, further in-

formation is not required.- However, if the master system is to continue to operate, the current BASP

signal state of the slave system must be transmitted. Bit 7 in the communication register 0 is used to indicate the BASP signal.

Jumper X3 allows to use bit 7 for data transfer (position 2-3 of X3) or for over-laying the BASP signal (position 1-2 of X3) If jumper X3 is in position 2-3, alleight bits of the communication register 0 can be used for data transfer. (Figure 5-3)

Figure 5-3: Jumper X3 (Default position 1-2: Mapping in the BASP signal)

5.2.3 Swapping Bytes in the Word (SWAP)

As the different master systems interpret the order of bytes in the data word dif-ferently, (Section 3), an adaptation to the master system is essential. This isnecessary, for example, with the Bosch PLC or with a PC that functions as amaster. The conversion is effected with jumper X5 (Figure 5-4).In position 1-2, no bytes in the word are swapped. The order of writing/readingis first high-byte, then low-byte.

Figure 5-4: Jumper X5 (Default position 1-2: Bytes in the word are not swapped )

Accordingly, position 2-3 means a reversed order of reading/writing.

3 2 1 5004A506

BASP

3 2 1 5004B503

SWAP

Page 34: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSConfiguration of the IBS S5 SL LB Board

5-6 5004C

5.2.4 Bus Master Information on Active BASP Signal or PLC Voltage Failure

When X11 is in position 2-3 (Figure 5-5), an active BASP signal or a PLC voltagefailure is indicated as a module status error to the bus master. The error LED islit.

Figure 5-5: Jumper X11 (Information of the bus master on an active BASP signal or PLC voltage failure)

Position 1-2 disables this function.

5.2.5 Operation in the Central Controller/Central Expansion Unit

It is possible to connect an expansion unit to the SIMATIC® S5 system. As thecommunication interface board can be operated in the basic unit as well as inthe expansion unit, the address lines A8 to A11 must be dealt with separately.When the communication interface board is installed in the basic unit, the jump-ers X7 to X10 (Figure 5-6) must be set to position 1-2. Therewith, the lines areconnected 1:1 with the SIMATIC® S5 bus.

Figure 5-6: Jumpers X7-X10

When the communication interface board is installed in the central expansion unit, place the jumpers X7 to X10 in position 2-3. Here, the address lines are not used and are connected to ground.

3 2 1 5004B505

ERR

1

2

3

1

2

3

1

2

3

X10 X9

X8 X7

1

2

3

5004A504

Page 35: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

6-15004C

Slots in SIMATIC S5 Systems

Section 6

Page 36: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

6-2 5004C

Page 37: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSSlots in SIMATIC S5 Systems

6-35004C

6 Slots in SIMATIC S5 Systems

Switch off the operating voltage of the PLC before you install or remove the com-munication interface board!

Figure 6-1: Permissible slots (marked in gray) in SIMATIC® S5 130WB, 135 U, 150 U, 155 U PLCs

Figure 6-2: Permissible slots (marked in gray) in SIMATIC®-Steuerungssyste-men S5 115 U, 135 U

S5-155U

S5-150Umode

S5-155Umode

Slot designation

Installation possible.

3 11 19 27 35 43 51 59 67 75 83 91 99 107

115

123

131

139

147

155

163

S5-150U

Slot designation 3 11 19 27 35 43 51 59 69 79 89 99 107

115

123

131

139

147

155

163

S5-130WB

Slot designation 3 27 35 43 51 69 79 89 97 105

113

121

129

137

145

153

163

Installation possible if the BR7 bridge is installedin the rear panel of the rack.(see Siemens S5 155 U Manual)

5114B017

S5-135U

with interrupt

processing

Slot designation

Softwareused

S5-115U

CR 700-0 LA 12 rack

Slot designation

CR 700-0 LB 11 rack

CR 700-1 LA 12 rack

CR 700-2 LA 12 rack

CR 700-3 LA12 rack

Installation possible

PS

CP

U

0 1 2 3 4 5 6 IM

3 11 19 27 35 43 51 59 67 75 83 91 99 107

115

123

131

139

147

155

163

5114B016

without inter-

rupt processing

Page 38: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSSlots in SIMATIC S5 Systems

6-4 5004C

Page 39: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

7-15004C

INTERBUS Connection and Diagnostic LEDs

This section provides information on

- the physical connection of the communication interface board in theINTERBUS system

- the pin assignment of the local bus cable- diagnostics through the LEDs on the board

Section 7

7.1 INTERBUS Connection . . . . . . . . . . . . . . . . 7-37.2 Diagnostic LEDs. . . . . . . . . . . . . . . . . . . 7-4

Page 40: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

7-2 5004C

Page 41: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSINTERBUS Connection and Diagnostic LEDs

7-35004C

7 INTERBUS Connection and Diagnostic LEDs

7.1 INTERBUS Connection

In the INTERBUS system, the IBS S5 SL LB communication interface board isconnected as a local bus module. The local bus cable is connected directly tothe board.The logic circuitries both on the bus side and on the PLC side are electrically iso-lated from one another.

For connecting the incoming local bus cable, the communication interface boardfeatures a 15-position male D-SUB connector (LOCAL IN), and for the outgoingcable a 15-position female D-SUB connector (LOCAL OUT). Preassembled ca-bles are available in the following lengths: 10 cm, 20 cm, 50 cm, 100 cm and150 cm .

Table 7-1: Preassembled cables

- Length of the local bus: 10 m- Length of each local bus cable: max. 1.5 m- Up to 8 modules in a local bus branch together with the IBS S5 SL LB board

Length Designation Order No.

10 cm IBS PBC 10 27 84 17 5

20 cm IBS PBC 20 28 06 31 2

50 cm IBS PBC 50 27 59 43 0

100 cm IBS PBC 100 27 84 18 8

150 cm IBS PBC 150 27 84 19 1

Page 42: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

INTERBUSINTERBUS Connection and Diagnostic LEDs

7-4 5004C

7.2 Diagnostic LEDs

Two light-emitting diodes, called "Error" and "Us" indicate the operating mode ofthe communication interface board. These four LEDs have the following mean-ings:

Us:The green LED is on when the logic voltage is applied to the communication in-terface board.

Error:It depends on the position of the jumper X11 whether this display appears. When an S5 system fails, the BASP signal of the PLC is activated. When BASPis active, this is indicated by the "Error" LED. The the same is true in the eventof a voltage drop at the PLC.Both is only the case in position 2-3 (see also Section 5.2.4).

If the jumper X11 is in the position 1-2, neither the STOP state of the PLC nor aPLC voltage failure is indicated to the master sytem. The "Error" LED is not lit.

Page 43: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

A-15004C

Index

Appendix A

AAddressing the board within the master system3-3

BBase address 3-3Bus maste rinformation 5-6Byte-by-byte access 1-4

CCentral controller/central expansion unit 5-6Central expansion unit 5-6Changing the register number 2-3Communication interface board 2-5Communication register 1-4, 2-3Configuration of the S5/SL-LB board 5-3

DDiagnostic LEDs 7-4

EError states in the slave or master system 1-3

IIBS S5 SL LB board 1-6Identification no. 171 1-4Installing or removing the board 6-3INTERBUS connection 7-3INTERBUS connection and diagnostic LEDs 7-3INTERBUS controller board 1-4

JJumper locations and setting positions 5-3Jumper settings 5-3Jumper X3 5-5Jumper X3 and X4 1-3Jumper X5 5-5Jumper X5, X7, X8, X9, X10 und X11 1-3

Jumpers X7 to X10 5-6

LLocal bus branch 1-5, 7-3Local bus module 7-3LOCAL IN 7-3LOCAL OUT 7-3Logical addressing, 3-3

MMaster system 1-4Master system failure 5-4

SSettable I/O area 1-4Setting of the base address 1-5Setting the base address 1-3Significance of the address switches 2-5Slave and master system errors 1-3Slave system failure 5-4Slots in SIMATIC S5 systems 6-3Start address 2-3Swapping bytes in the word (SWAP) 5-5

Page 44: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

A-2 5004C

Page 45: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

We Are Interested in Your Opinion!We would like to hear your suggestions, wishes and criticisms concerning this InterBus manual.Therefore, we would appreciate your answers to the questionnaire overleaf. No matter how small yourcontribution, we will deal with any hint or comment.

This reply can be sent as a fax, in an envelope, or directly, after folding (1. / 2.) and sticking it together(with adhesive tape).

Thanking you for your cooperation !

...............................................................................................................................................................................1. ...............

Phoenix Contact GmbH & Co.Produktmarketing InterBus/ME-DOKFlachsmarktstraße 8 - 2832825 BlombergGermany

................................................................................................................................................................................2. ...............

Page 46: User Manual IBS S5 SL LB UM E - PHOENIX CONTACT

FAX-NO.: *49-(0)5235-331199

FAX Reply Date: ..............................Phoenix Contact GmbH & Co.Produktmarketing InterBus/ME-DOK No. of pages: ....................

Sender:

Company: ............................................................................. Contact: ................................................................................

............................................................................. Dept.: ................................................................................

Address: ............................................................................. Title: ................................................................................

City, ZIP code:............................................................................. Telephone: ............................... / ..............................................

Country: ............................................................................. Fax: ............................... / ..............................................

Manual data:

Type: ................................................................... Revision: ............. Order No: ....................

My Opinion on the Manual

Form Yes In part No

Is the Table of Contents clearly arranged? r r rAre the figures/diagrams easy to understand/meaningful? r r rDoes the page layout make it easy to locate the required information? r r rIs the chapter overview detailed enough? r r rDo the corresponding explanations of the figures suffice? r r rDoes the quality of the figures (clear/self-explaining) meet yourexpectations/requirements?

r r r

Do the index entries guide you to the relevant information? r r r

Contents Yes In part No

Are the technical terms easy to understand/meaningful? r r rIs the wording always easy to understand/meaningful? r r rAre the index entries easy to understand/meaningful? r r rWhich reference list (Table of Contents, Figures, Tables, Index) do you usemost when you search for information ?.............................................................................................................Is any important information missing?If so, which?..............................................................................................................................................................................................................................................................

r r r

Are the examples practice-oriented? r r rIs the manual easy to handle? r r rDo you wish more space for your own notes? r r r

I have the following suggestion(s)/comment(s):............................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................

DNR 2533

.......................................................................................................................................

.......................................................................................................................................

5050CF17