Honeywell Process Solutions
Pnet Remote I/F Module
2MLL-PSRA User's Guide
R200
September 2010
Release 200
Honeywell
ii Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Notices and Trademarks
Copyright 2010 by Honeywell International Sárl. Release 200 September, 2010
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Honeywell, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell International Inc.
Other brand or product names are trademarks of their respective owners.
Honeywell Process Solutions
1860 W. Rose Garden Lane
Phoenix, AZ 85027 USA
1-800 822-7673
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide iii September 2010 Honeywell
About This Document
This document describes the product specification, performance and operation method needed to use PLC system composed of Pnet remote I/F module.
Release Information
Document Name Document ID
Release Number
Publication Date
2MLL-PSRA User's Guide 200 September 2010
References The following list identifies all documents that may be source of reference for material discussed in this publication.
Document Title
SoftMaster User’s Guide
Support and Other Contacts
iv Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Support and Other Contacts
United States and Canada
Contact: Phone: Fascimile: Mail:
Honeywell Solution Support Center 1-800-822-7673 Calls are answered by dispatcher between 6:00 am and 4:00 pm Mountain Standard Time. Emergency calls outside normal working hours are received by an answering service and returned within one hour. 1-973-455-5000 Honeywell TAC, MS L17 1860 W. Garden Lane Phoenix, AZ, 85027 USA
Europe, Middle East, and Africa (EMEA)
Contact: Phone: Fascimile: Mail:
Honeywell TAC-EMEA +32-2-728-2345 +32-2-728-2696 TAC-BE02 Hermes Plaza Hermeslaan, 1H B-1831 Diegem, Belgium
Pacific
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Pacific 1300-364-822 (toll free within Australia) +61-8-9362-9559 (outside Australia) +61-8-9362-9564 Honeywell Limited Australia 5 Kitchener Way Burswood 6100, Western Australia [email protected]
India
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – India +91-20- 6603-9400 +91-20- 6603-9800 Honeywell Automation India Ltd 56 and 57, Hadapsar Industrial Estate Hadapsar, Pune –411 013, India [email protected]
Support and Other Contacts
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide v September 2010 Honeywell
Korea
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Korea +82-80-782-2255 (toll free within Korea) +82-2-792-9015 Honeywell Co., Ltd 4F, Sangam IT Tower 1590, DMC Sangam-dong, Mapo-gu Seoul, 121-835, Korea [email protected]
People’s Republic of China
Contact: Phone: Mail: Email:
Honeywell Global TAC – China +86- 21-2219-6888 800-820-0237 400-820-0386 Honeywell (China) Co., Ltd 33/F, Tower A, City Center, 100 Zunyi Rd. Shanghai 200051, People’s Republic of China [email protected]
Singapore
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – South East Asia +65-6580-3500 +65-6580-3501 +65-6445-3033 Honeywell Private Limited Honeywell Building 17, Changi Business Park Central 1 Singapore 486073 [email protected]
Taiwan
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Taiwan +886-7-536-2567 +886-7-536-2039 Honeywell Taiwan Ltd. 17F-1, No. 260, Jhongshan 2nd Road. Cianjhen District Kaohsiung, Taiwan, ROC [email protected]
Support and Other Contacts
vi Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Japan
Contact: Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Japan +81-3-6730-7160 +81-3-6730-7228 Honeywell Japan Inc. New Pier Takeshiba, South Tower Building, 20th Floor, 1-16-1 Kaigan, Minato-ku, Tokyo 105-0022, Japan [email protected]
Elsewhere
Call your nearest Honeywell office.
World Wide Web
Honeywell Solution Support Online:
http://www.honeywell.com/ps
Training Classes
Honeywell Automation College:
http://www.automationcollege.com
Symbol Definitions
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide vii September 2010 Honeywell
Symbol Definitions The following table lists the symbols used in this document to denote certain conditions.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
TIP: Identifies advice or hints for the user, often in terms of performing a task.
REFERENCE -EXTERNAL: Identifies an additional source of information outside of the bookset.
REFERENCE - INTERNAL: Identifies an additional source of information within the bookset.
CAUTION
Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.
Symbol Definitions
viii Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Symbol Definition
ESD HAZARD: Danger of an electro-static discharge to which equipment may be sensitive. Observe precautions for handling electrostatic sensitive devices.
Protective Earth (PE) terminal: Provided for connection of the protective earth (green or green/yellow) supply system conductor.
Functional earth terminal: Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements.
Earth Ground: Functional earth connection. NOTE: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide ix September 2010 Honeywell
Contents
1. INTRODUCTION .......................................................................... 15
1.1 Overview ........................................................................................................ 15
1.2 Features ......................................................................................................... 15
1.3 Product configuration ................................................................................... 17 Digital I/O module ................................................................................................................. 17 Analog I/O module ............................................................................................................... 18
2. PRODUCT SPECIFICATIONS ..................................................... 19
2.1 General specification .................................................................................... 19
2.2 Pnet remote I/F module specification ......................................................... 21
2.3 Profibus-DP cable specification .................................................................. 22 Cable specification ............................................................................................................... 22 Connector’s structure and connector wire method ............................................................... 23
2.4 Pnet Terminating ........................................................................................... 25
3. INSTALLATION AND WIRING .................................................... 27
3.1 Installation ..................................................................................................... 27 Installation environment ....................................................................................................... 27 Precautions during installation of Profibus-DP module ........................................................ 28 Precautions while handling the product ................................................................................ 29 Precautions in attaching the PLC ......................................................................................... 30
3.2 Wiring ............................................................................................................. 32 Power wiring ......................................................................................................................... 32 I/O Device Wiring ................................................................................................................. 33 Grounding Wiring ................................................................................................................. 34 Cable specification for wiring ................................................................................................ 35
4. SYSTEM CONFIGURATION ........................................................ 37
4.1 Overview ........................................................................................................ 37 Basic System Configuration ................................................................................................. 38
4.2 Part names and functions ............................................................................ 39
Contents Symbol Definitions
x Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Error type ............................................................................................................................ 40 Available Product List .......................................................................................................... 41
4.3 Example for system configuration ............................................................... 44
5. COMMUNICATION PROGRAMMING ......................................... 45
5.1 How to set master module ............................................................................ 45 High-speed Link .................................................................................................................. 45 SoftMaster-NM Link Parameter setting ............................................................................... 46 High-speed Link communication status flag information ..................................................... 48
5.2 How to register Profibus-DP remote module .............................................. 51 Creating a new project ........................................................................................................ 51 Setting I/O parameter .......................................................................................................... 52
6. PROFIBUS-DP COMMUNICATION ............................................ 57
6.1 Overview ......................................................................................................... 57
6.2 Communication Specification ...................................................................... 57
6.3 Basic Performance ........................................................................................ 58 Overview ............................................................................................................................. 58 Operation by High-speed Link ............................................................................................. 59 How to establish Pnet communication ................................................................................. 59 I/O data Communication ...................................................................................................... 61
6.4 Tool for Communication Setting .................................................................. 62 Communication setting by SyCon ....................................................................................... 62
6.5 High-speed Link setting in SoftMaster-NM ................................................. 69
6.6 How to set and download GSD .................................................................... 76
7. MAINTENANCE AND REPAIR ................................................... 77
7.1 I/O module maintenance .............................................................................. 77
7.2 Routine inspection ........................................................................................ 78
8. TROUBLESHOOTING ................................................................. 79
8.1 Introduction .................................................................................................... 79
8.2 Basic troubleshooting procedure ................................................................ 79
Contents Symbol Definitions
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide xi September 2010 Honeywell
8.3 Troubleshooting methods ............................................................................ 80 Action method when RUN LED is OFF ................................................................................ 81 Action method when ERR LED is ON .................................................................................. 82 Action method when Program Write does not work ............................................................. 83 SyCon connection error........................................................................................................ 84 SoftMaster-NM connection error .......................................................................................... 85 Communication error with slave ........................................................................................... 86
Contents Tables
xii Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Tables Table 1 – Product configuration of digital I/O module .................................................... 17 Table 2 – Product configuration of analog I/O module ................................................... 18 Table 3 – General specifications of Pnet remote I/F module ......................................... 19 Table 4 – Communication specifications of Pnet remote I/F module ............................. 21 Table 5 – Profibus-DP cable specification ..................................................................... 22 Table 6 – Cable specification for wiring ......................................................................... 35 Table 7 – LED status ...................................................................................................... 40 Table 8 – Product list ..................................................................................................... 41 Table 9 – Base list .......................................................................................................... 41 Table 10 – Digital I/O module list ................................................................................... 42 Table 11 – Analog I/O module list .................................................................................. 43 Table 12 – Pnet High-speed Link setting contents ........................................................ 46 Table 13 – Communication flag list ................................................................................ 48 Table 14 – Profibus-DP classification ............................................................................ 57 Table 15 – Operation sequence of High-speed Link ...................................................... 69
Contents Figures
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide xiii September 2010 Honeywell
Figures Figure 1 – Hot swap function ......................................................................................... 16 Figure 2 – Connector’s structure ................................................................................... 23 Figure 3 – Cable structure ............................................................................................. 24 Figure 4 – Wire connection method ............................................................................... 24 Figure 5 – Pnet termination ........................................................................................... 25 Figure 6 – Wiring the I/O line ......................................................................................... 29 Figure 7 – Installing PLC to control panel ...................................................................... 30 Figure 8 – Installing the duct ......................................................................................... 31 Figure 9 – Power wiring ................................................................................................. 32 Figure 10 – Surge absorber ........................................................................................... 33 Figure 11 – I/O device wiring ......................................................................................... 34 Figure 12 – Grounding wiring ........................................................................................ 34 Figure 13 – Wiring for DC input module ........................................................................ 37 Figure 14 – Basic system configuration ......................................................................... 38 Figure 15 – Part names and functions ........................................................................... 39 Figure 16 – Example for system configuration .............................................................. 44 Figure 17 – High-speed Link process ............................................................................ 45 Figure 18 – Error log ...................................................................................................... 52 Figure 19 – Sequence operation to establish communication ....................................... 60 Figure 20 – I/O data Communication through backplane bus ....................................... 61 Figure 21 – I/O data Communication through local USB .............................................. 62 Figure 23 – Downloading configuration information through GSD file .......................... 76
Contents Figures
xiv Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 15 September 2010 Honeywell
1. Introduction
1.1 Overview This user’s guide describes the specifications, handling, and programming of the 2MLL-PSRA Pnet remote I/F module.
1.2 Features The characteristics of Pnet remote I/F module are as follows:
Product design based on International Electrotechnical Commission (IEC 61131)
Easy support to programming device
Standard language (IEC 61131-3) provided (IL/LD/SFC)
Supports International standard communication protocol based on open network.
Communicates with the remote master module.
Sets maximum 99 stations.
Enables to save the cost for installation and maintenance.
System configuration is simple for maintenance and repair.
Compatible with third party’s product.
Easy to set the system by hardware station address setting.
Supports various I/O like:
DC input 8/16/32/64 points, TR output 16/32/64 points, Relay output 8/16 points
Combined 32 point (DC input 16 point/ TR output 16 point)
Various special modules such as AD (analog input)/DA (analog voltage)/DC (analog current output)/RTD (Resistor temperature detector)/TC (Thermocouple)
Easy to configure the system.
Provides the online network status detection function.
Detects the remote module status through High-speed Link monitor.
1. Introduction 1.2. Features
16 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Verifies diverse modules instantly.
High-speed communication.
Flexible communication relation is available as the speed is set automatically according to the speed of master.
Hot-Swap function available.
Module can be changed during the RUN mode. Operation of all I/O modules, except the module under change, is normal.
Before the module change, it communicates to BPMC about the module change using switch manipulation.
After the module change, restores the mode switch.
You can check the invalid module installation and replacement through operation of M_CHECK, M_CLO/SE at BPMC I/F program.
Figure 1 – Hot swap function
1. Introduction 1.3. Product configuration
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 17 September 2010 Honeywell
1.3 Product configuration
Digital I/O module
The following table displays the product configuration of digital I/O module.
Table 1 – Product configuration of digital I/O module
Name Model Contents
Digital input module
2MLI-D21A DC 24V input, 8 points (current source / sink input)
2MLI-D22A DC 24V input, 16 points (current source / sink input)
2MLI-D24A DC 24V input, 32 points (current source / sink input)
2MLI-D28A DC 24V input, 64 points (current source / sink input)
2MLI-D22B DC 24V input, 16 points (current source input)
2MLI-D24B DC 24V input, 32 points (current source input)
2MLI-D28B DC 24V input, 64 points (current source input)
2MLI-A12A AC 110V input, 16 points
2MLI-A21A AC 220V input, 8 points
Digital output module
2MLQ-RY1A Relay output, 8 points (2A, single COM)
2MLQ-RY2A Relay output, 16 points (2A)
2MLQ-RY2B Relay output, 16 points (2A), Varistor added
2MLQ-TR2A TR output, 16 points (0.5A, sink output)
2MLQ-TR4A TR output, 32 points (0.1A, sink output)
2MLQ-TR8A TR output, 64 points (0.1A, sink output)
2MLQ-TR2B TR output 16 points (0.5A, source output)
2MLQ-TR4B TR output 32 points (0.1A, source output)
2MLQ-TR8B TR output 64 points (0.1A, source output)
2MLQ-SS2A Triac output, 16 points (1A)
Dustproof module
2MLT-DMMA Dustproof module for unused slot
1. Introduction 1.3. Product configuration
18 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Analog I/O module
The following table displays the product configuration of analog I/O module.
Table 2 – Product configuration of analog I/O module
Name Model Contents
Specia
l mod
ule
Analog input module
2MLF-AV8A Voltage input: 8 channels
2MLF-AC8A Current input: 8 channels
2MLF-AD8A Voltage/Current input: 8 channels
2MLF-AD4S Voltage/Current input: 4 channels, Isolation between channels
2MLF-AD16A Voltage/Current input: 16 channels
Analog output module
2MLF-DV4A Voltage output: 4 channels DC 1 ~ 5V / 0 ~ 5V / 0 ~ 10V / 10 ~ +10V
2MLF-DC4A Current output: 4 channels DC 4 ~ 20mA / 0 ~ 20mA
2MLF-DC4S Current output: 4 channels, Isolation between channels
2MLF-DV8A Voltage output: 8 channels DC 1 ~ 5V / 0 ~ 5V / 0 ~ 10V / 10 ~ +10V
2MLF-DC8A Current output: 8 channels DC 4 ~ 20mA / 0 ~ 20mA
Thermocouple input
2MLF-TC4S T/C input, 4 channels, Isolation between channels
RTD input module
2MLF-RD4A RTD input, 4 channels
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 19 September 2010 Honeywell
2. Product Specifications
2.1 General specification The following lists the general specifications of Pnet remote I/F module.
Table 3 – General specifications of Pnet remote I/F module
Items Specifications Related
standards
Ambient temperature 0 ~ 55 C
Storage temperature 25 ~ 70 C
Ambient humidity
5 ~ 95%RH (Non-condensing)
Storage humidity
5 ~ 95%RH (Non-condensing)
Vibration resistance
Occasional vibration -
Frequency Acceleration Amplitude times
IEC61131-2
10 f 57Hz 0.075mm
Ten times in each directions (X, Y, and Z)
57 f 150Hz 9.8m/s2(1G)
Continuous vibration
Frequency Acceleration Amplitude
10 f 57Hz 0.035mm
57 f 150Hz 4.9m/s2(0.5G)
Shock resistance
Peak acceleration: 147 m/s2 (15G)
Duration: 11ms
Half-sine, 3 times each direction per each axis
IEC61131-2
2. Product Specifications 2.2. Pnet remote I/F module specification
20 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Items Specifications Related
standards
Noise resistance
Square wave Impulse noise 1,500 V
Honeywell standard
Electrostatic discharge
4kV (Contact discharge) IEC61131-2, IEC61000-4-2
Radiated electromagnetic field noise
80 ~ 1,000 MHz, 10V/m IEC61131-2, IEC61000-4-3
Fast transient/bust noise
Segment Power supply module
Digital/analog input/output communication interface
IEC61131-2, IEC61000-4-4
Voltage 2kV 1kV
Environment Free from corrosive gasses and excessive dust
Altitude Up to 2,000 ms
Pollution degree
2 or less
Cooling Air-cooling
ATTENTION
IEC (International Electrotechnical Commission): An international non-governmental organization, which promotes internationally accepted standardization in electric/electronic field, publishes international standards, and manages applicable estimation system.
Pollution degree: An index indicating pollution degree of the operating environment, which decides the Isolation performance of the devices. For instance, Pollution degree 2 indicates the state generally that only non-conductive pollution occurs. However, due to the dew produced, this state contains temporary conduction.
2. Product Specifications 2.2. Pnet remote I/F module specification
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 21 September 2010 Honeywell
2.2 Pnet remote I/F module specification The following table lists the communication specifications of Pnet remote I/F module.
Table 4 – Communication specifications of Pnet remote I/F module
Items Specifications
Standard EN50170 / DIN 19245
Interface RS-485 (electric)
Media access Polling
Topology Bus method
Amplitude method NRZ
Communication interface Auto baud rate
Master/Slave Slave
Maximum station count per network 100 stations (including master and repeater)
Maximum station count per segment 32 stations (including master and repeater)
Cable Twisted shielded cable
Maximum communication data size TX/RX each 244 byte
I/O parameter setting After writing I/O parameter using expansion adapter, download through USB
Communication speed and distance
Speed (kbps) 9.6 19.2 93.75 187.5 500
Distance (m) 1200 1200 1200 1000 400
Speed (kbps) 1500 3000 6000 12000 -
Distance (m) 200 100 100 100 -
Maximum node count 100 stations (setting range: 0 ~ 99 )
Maximum expansion module installation count
12 modules
2. Product Specifications 2.3. Profibus-DP cable specification
22 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Items Specifications
Maximum digital I/O points
768 points
(Input Maximum 768 points/output Maximum 768 points, 64-point module x 12 slots)
Maximum analog I/O channels
Input max 122 channels (Maximum TRX 244 byte/2) Output Maximum 96 channels (8 channels X 12 slots) - 1 word per channel
Internal consumption current (mA) 600
Weight (g) 114
ATTENTION
For more information on how to write the parameter of special module and I/O module through expansion adapter, refer to SoftMaster and special module manual.
2.3 Profibus-DP cable specification
Cable specification
The following table lists the Profibus-DP cable specification.
Table 5 – Profibus-DP cable specification
Classification Contents
Cable
BELDEN cable:
Product name : 3077F, 3079A
Tomas cable:
Product name : Profibus-DP UNITRONIC-BUS L2/FIP/BUS
AWG 22
Type BC (Bare copper)
Isolation PE (Polyethylene)
Isolation intensity 0.035 (inch)
2. Product Specifications 2.3. Profibus-DP cable specification
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 23 September 2010 Honeywell
Classification Contents
Shield Aluminum Foil-Polyester Tape /Braid Shield
Capacity 8500/ft
Characteristic impedance
150 Ω
Core count 2 Core
Connector’s structure and connector wire method
Input wire: green wire is connected to A1; red wire is connected to B1.
Output wire: green wire is connected to A2; red wire is connected to B2.
Shield is connected to connector’s clamp.
When installing the connector in terminal, connect the cable to A1 and B1.
The following figure displays the connector’s structure.
Figure 2 – Connector’s structure
2. Product Specifications 2.3. Profibus-DP cable specification
24 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
The following figure displays the cable structure.
Figure 3 – Cable structure
The following figure displays the wire connection method.
Figure 4 – Wire connection method
2. Product Specifications 2.4. Pnet Terminating
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 25 September 2010 Honeywell
2.4 Pnet Terminating The following figure displays Pnet termination.
Figure 5 – Pnet termination
2. Product Specifications 2.4. Pnet Terminating
26 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 27 September 2010 Honeywell
3. Installation and wiring
3.1 Installation
Installation environment
The 2MLL-PSRA module has high reliability regardless of their installation environment. The following factors ensure the system reliability and stability.
1. Environmental prerequisites Avoid installing the module in places where it is subjected or exposed to:
a) Water leakage and dust.
b) Continuous shocks or vibrations.
c) Direct sunlight.
d) Dew condensation due to rapid temperature change.
e) Temperature outside the range of 0 to 55C.
f) Relative humidity outside the range of 5 ~ 95%.
g) Corrosive gas or combustible gas.
2. Installation guidelines
a) Ensure that no external materials like wire scraps enter the upper part of the PLC during drilling or wiring.
b) Ensure to install PLC in a location where it is easy for monitoring and use.
c) Ensure that PLC is not located on the same panel where high voltage equipment is located.
d) Ensure that the distance from the walls of duct to external equipment is 50mm or more.
e) Ensure that the PLC is properly grounded to the locations that have good ambient noise immunity.
3. Installation and wiring 3.1. Installation
28 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Precautions during installation of Profibus-DP module
Profibus-DP Smart I/O module can set maximum 126 stations (including master). However, for 2MLL-PSRA, station number 0~99 is available.
The following precautions must be taken during the installation of the 2MLL-PSRA module.
1. Verify the basic factors necessary for the system configuration and select the proper communication module.
2. Prepare the cable and accessories such as tab, terminal resistance, and so on to be used for this communication.
3. The station number of all other stations including this module should be different. If it is connected with more than one station number, it may cause the communication error.
4. In case of operating with normal communication, the mode switch of master module should be at RUN mode.
5. For communication cable, the designated standard cable should be used. If not, it may cause significant communication obstacle.
6. Before installation, verify if the communication cable is cut off or short-circuited.
7. Tighten the communication cable connector completely and fix the cable connection tightly. If the cable connection is not complete, it may cause significant communication obstacle.
8. If the communication cable is twisted or if the cable is not connected properly, it may cause communication error.
9. In case of connecting the long distance communication cable, the wiring should be far from the power line or inductive noise.
10. Do not remove the PCB from its case. It can result in damage or an abnormal operation.
11. If LED action is abnormal, refer to section Troubleshooting for causes.
12. Install the Profibus-DP module when the status of PLC power is ‘OFF’.
3. Installation and wiring 3.1. Installation
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 29 September 2010 Honeywell
Precautions while handling the product
The following precautions must be taken while handling the product.
1. Recheck the I/O standard specification: Apply input voltage and output voltage as per standard specification. If the voltage exceeds the maximum capacity, it may cause failure, breakage, and fire.
2. Selection of wire: Select the wire considering the ambient temperature and allowable current. The minimum cable specification of the wire should be AWG24 (0.18mm²).
3. Environment: If the I/O wiring is close to a heat generating machine or material, or if the wiring is in direct contact with oil for a long time, it may cause short-circuit, breakage, and failure.
4. Polarity: Check the polarity before applying power to the terminal block. Do not wire the AC input power to the 24V DC external power supply terminal that is located on the edge of the basic unit input part. In case of DeviceNet, if you provide 24V power to the communication cable, then it is not necessary to wire separately.
5. Wiring
a) When wiring the I/O line with high voltage cable and the power cable together, induction obstacle occurs, and it may cause the failure and malfunction.
b) Do not pass the cable in front of I/O action indication part (LED). (Because it prevents from distinguishing the I/O indication.)
c) In case the inductive load is connected to the output part, connect the surge killer or diode to the load in parallel. Connect the cathode of the diode to the ‘+’ side of the power.
Figure 6 – Wiring the I/O line
3. Installation and wiring 3.1. Installation
30 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
6. Terminal block: Ensure that no external materials like wire scraps enter the upper part of the PLC while wiring the terminal block or while drilling a screw hole. It may cause malfunction and failure.
Precautions in attaching the PLC
The following precautions must be taken in attaching the PLC to the control panel.
1. Sufficient distance is required between well-ventilated room and PLC. It facilitates the exchange of the basic unit and the extended module. Maintain a distance of 100mm between the left side of the basic unit and the control panel. This distance is necessary for the exchange of battery, which is done once in three year.
2. To maximize the radiation effect, install PLC to the control panel as shown in the following figure.
Figure 7 – Installing PLC to control panel
3. Use a different panel for large sized electronic contactor or the vibration source such as no-fuse breaker and install PLC separately.
3. Installation and wiring 3.2. Wiring
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 31 September 2010 Honeywell
4. Install the duct for wiring if necessary. But, if the distance between upper part or lower part of PLC and duct is smaller than the below figure, then you should consider the following:
Figure 8 – Installing the duct
a) In case of installing on the upper PLC, the height of wiring duct should be less than 80mm for good ventilation.
b) In case of installing on the lower PLC, consider minimum radius of the cable.
5. In case the equipment is installed in front of the PLC (inside the door) to avoid the effect of radiant noise or the heat, separate it from the PLC of distance more than 100mm.
3. Installation and wiring 3.2. Wiring
32 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
3.2 Wiring This section describes the precautions to be taken for wiring.
Power wiring
1. You must use 24V DC power supply.
2. If the power variation is more than the regular range, you must connect a constant voltage transformer.
3. To prevent noise from the power cable, twist the power cable as densely as possible and connect within the shortest distance.
Figure 9 – Power wiring
4. Provide the power where the noise is lesser. (If there is much noise, connect the Isolation transformer.)
5. For PLC, I/O machine and power machine, it is required to divide the power as follows.
Where T1, T2: Constant voltage transformer
6. Use 2mm² thick power cable to reduce the voltage fluctuation.
3. Installation and wiring 3.2. Wiring
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 33 September 2010 Honeywell
7. Do not place the 24V DC power cable close to the main circuit or to the I/O signal cable. They should be placed atleast 80mm away from each other.
8. Use the surge absorber to prevent the lightning as shown in the figure below.
Figure 10 – Surge absorber
ATTENTION
Separate the earth (E1) of the surge absorber for lightning and the earth (E2) of PLC.
Select the surge absorber for lightning so that it does not exceed maximum allowable voltage of the absorber even when the power voltage is raising maximum.
9. Use the insulated transformer or the noise filter.
10. In case of the wiring, each input resource, the wiring of the insulated transformer or the noise filter is not allowed to pass the wiring duct.
I/O Device Wiring
1. For I/O wiring, it is recommended to use 0.5mm² cable, even though the specification is 0.18~2 mm².
2. Input cable and output cable should be separated for wiring.
3. While wiring, maintain a distance of 80mm between the I/O signal cable and the high-voltage, high-current main circuit cable.
4. To separate the main circuit cable and the power cable, you should use the shielded cable, and earth the PLC.
3. Installation and wiring 3.2. Wiring
34 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Figure 11 – I/O device wiring
5. Separate the 24V DC output cable from 110V AC cable and 220V AC cable.
6. In the cases where wiring is longer than 200m, error occurs depends upon the leakage current that is caused by interline capacity.
Grounding Wiring
If there is more noise, you have to use PLC with grounding. During grounding, refer to the following notices.
1. During grounding, use the exclusive grounding if possible. For the grounding construction, use the 3rd class grounding (grounding resistance less than 80Ω).
2. If the exclusive grounding is not possible to use, you can use the common grounding as shown on the figure (B).
Figure 12 – Grounding wiring
(A): exclusive grounding: Excellent
(B): common grounding: Good
(C): common grounding: Bad
3. For grounding, use the electric wire that is more than 2mm² of thickness. Place the grounding point near this PLC if possible and shorten the length of the grounding cable.
3. Installation and wiring 3.2. Wiring
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 35 September 2010 Honeywell
a) When connecting the extended base, connect the extended connector accurately.
b) Do not remove the PCB from the module case and do not modify the module.
c) When attaching/removing the module, the power should be OFF.
d) Use the cellular phone or radiophone 30mm away from the product.
e) I/O signal cable and communication cable should be at least 100mm apart from the high voltage cable or the power cable to avoid the effect caused by the noise or the change of magnetic filed.
Cable specification for wiring
The cable specification to be used for the wiring is as follows:
Table 6 – Cable specification for wiring
External connection type Cable specification (mm²)
Low limit High limit
Digital input 0.18 (AWG24) 1.5 (AWG16)
Digital output 0.18 (AWG24) 2.0 (AWG14)
Analog I/O 0.18 (AWG24) 1.5 (AWG16)
Communication 0.18 (AWG24) 1.5 (AWG16)
Main power resource 1.5 (AWG16) 2.5 (AWG12)
Protection grounding 1.5 (AWG16) 2.5 (AWG12)
For the power and I/O wiring of Smart I/O, it is required to use the compressed terminal.
Use ‘M3’ type screw for the terminal.
Tighten the terminal screw with 6~9 kgcm torque.
Use the fork type screw for the compressed terminal.
The following figure is an example of the proper compressed terminal (fork type).
3. Installation and wiring 3.2. Wiring
36 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 37 September 2010 Honeywell
4. System Configuration
4.1 Overview This chapter describes the system configuration method and its characteristics. Consider the following factors while selecting the digital I/O module, which is used for Remote I/O.
1. Digital input types contain the current sink input and current source input. In case of DC input module, the wiring method is as follows:
a) Connect the sink type external connection machine to the source type DC input module as shown below.
Figure 13 – Wiring for DC input module
External connection machine is located between the DC power and the (-) terminal of DC input module terminal.
Hence, when the power is ON, the current flows from the DC input module terminal to the external connection machine.
b) Connect the source type external connection machine to the sink type DC input module as shown below.
External connection machine is located between the DC power and the (+) terminal of DC input module terminal.
Hence, when the power is ON, the current flows from external connection machine to DC input module terminal.
4. System Configuration 4.1. Overview
38 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
2. In case the open/close frequency is high or module is used to open/close the conductive load, use the transistor output module.
Basic System Configuration
The 2MLL-PSRA communicates with master and controls expansion I/O module through Backplane Bus.
Figure 14 – Basic system configuration
4. System Configuration 4.2. Part names and functions
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 39 September 2010 Honeywell
4.2 Part names and functions The following figure illustrates the part names and functions of Pnet remote I/F module.
Figure 15 – Part names and functions
LED RUN: Power ON P-RUN: normal communication (ON) STATUS: I/O synchronization (ON) ERR: error (ON)
Station number switch
USB port
- I/O parameter and OS download
Module change switch
Pnet communication connector
4. System Configuration 4.2. Part names and functions
40 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
The following table indicates the LED status.
Table 7 – LED status
Item Name Normal Abnormal LED indication
1 RUN
On - Module normal
(Normal operation of system O/S)
- Off O/S is not operating
(O/S operation error by H/W error)
2 P-RUN
On Pnet communication normal
- Off Not connected with master or not communicating with master
3 STATUS
On - System configuration of master is same as I/O configuration of slave, so communication is normal.
- Off System configuration of master is not same as I/O configuration of slave, so communication is not normal.
4 ERR - On Refer to section Error type.
Off - No error
Error type
1. Module detachment error: Module is detached from base while M.XCHG switch is off.
2. Invalid module is attached: Invalid module such as communication module, High Speed Counter module, and so on is attached at Base.
3. Out of I/O points: I/O module configuration is exceeding maximum data size (244 byte) or no I/O data.
4. System Configuration 4.2. Part names and functions
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 41 September 2010 Honeywell
4. I/O parameter error: I/O parameter set by user is different with actual I/O configuration.
When different parameter is downloaded during communication, ERR LED is OFF.
When different parameter is downloaded during not communicating, ERR LED is ON.
Available Product List
The following table displays the power module list.
Table 8 – Product list
Model Specification
2MLP-ACF1 AC100V - AC240V, 3A
2MLP-ACF2 AC100V - AC240V, 6A
2MLP-AC23 AC200V - AC240V, 8.5A
2MLP-DC42 DC24V, 6A
The following table displays the base list.
Table 9 – Base list
Model Specification Remark
2MLB-M04A 4-slot main base
Up to 12 slots are available and expansion base through expansion cable is not supported.
2MLB-M06A 6-slot main base
2MLB-M08A 8-slot main base
2MLB-M12A 12-slot main base
4. System Configuration 4.2. Part names and functions
42 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
The following table displays the digital I/O module list.
Table 10 – Digital I/O module list
Model Specification
Input module
2MLI-A12A AC110V, 16 point
2MLI -A21A AC220V, 8 point
2MLI -D21A DC24V, 8 point
2MLI -D22A DC24V, 16 point, sink/source
2MLI -D22B DC24V, 16 point, sink
2MLI -D24A DC24V, 32 point, sink/source
2MLI -D24B DC24V, 32 point, sink
2MLI -D28A DC24V, 64 point, sink/source
2MLI -D28B DC24V, 64 point, sink
Output module
2MLQ-RY1A Relay, 8 point
2MLQ -RY2A Relay, 16 point
2MLQ -RY2B Relay, 16 point, Built-in surge killer
2MLQ -SS2A Triac, 16 point
2MLQ -TR2A TR, 16 point, sink
2MLQ -TR2B TR, 16 point, source
2MLQ -TR4A TR, 32 point, sink
2MLQ -TR4B TR, 32 point, source
2MLQ -TR8A TR, 64 point, sink
2MLQ -TR8B TR, 64 point, source
I/O module
2MLH-DT4A DC24V, 16 point input / TR 16 point, sink
4. System Configuration 4.2. Part names and functions
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 43 September 2010 Honeywell
ATTENTION
For more information on specification of I/O module, refer to 2MLI-CPU user guide.
The following table displays the Analog I/O module list.
Table 11 – Analog I/O module list
Model Specification
Analog input
2MLF-AV8A Voltage input: 8 channels
2MLF-AC8A Current input: 8 channels
2MLF-AD8A Voltage/current input: 8 channels
2MLF-AD4S Voltage/current input: 4 channels, Isolation between channels
2MLF-AD16A Voltage/current input: 16 channels
Analog output
2MLF-DV4A Voltage output type, 4 channels
2MLF-DC4A Current output type, 4 channels
2MLF-DV8A Voltage output type, 8 channels
2MLF-DC8A Current output type, 8 channels
2MLF-DC4S Current output type, 4 channels, Isolation type
Temp. conversion 2MLF-TC4S
Thermocouple input, 4 channels, Isolation type
2MLF-RD4A RTD input, 4 channels
ATTENTION
For more information on specification of analog I/O module, refer to respective product’s user manual.
4. System Configuration 4.3. Example for system configuration
44 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
4.3 Example for system configuration
Figure 16 – Example for system configuration
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 45 September 2010 Honeywell
5. Communication Programming
5.1 How to set master module This section describes how to set master module to use Pnet remote I/F module.
High-speed Link
High-speed Link is used when other station’s data or information is periodically exchanged at specific interval. By referring to the data exchange of its own station or other station periodically, utilize the data effectively. It communicates the data by setting the simple parameter.
The setting method is to designate its own area and the area of other station, data size, and station number (for 2MLT in SoftMaster-NM) and then communicate. Data size is from minimum 1 byte (8 bits) to maximum 244 byte and communication period is from minimum 10ms to maximum 10s according to communication contents.
As it is possible to communicate with other station by simple parameter setting, it is easy to use High-speed Link. The High-speed Link process of internal data enables periodic, simultaneous processing of huge data.
Figure 17 – High-speed Link process
5. Communication Programming 5.1. How to set master module
46 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
SoftMaster-NM Link Parameter setting
When using Pnet master module, it is easy to set device region and data size to communicate between CPU module and communication module (Master module and Slave module) by using SoftMaster-NM.
The following table describes Pnet High-speed Link setting contents.
Table 12 – Pnet High-speed Link setting contents
Contents High-speed Link
Communication module setting
Communication module setting
Module Type
Select Pnet
Base No.Maximum: 0 ~ 7, Setting range differ according to CPU module.
Slot No. Maximum: 0 ~ 11, Setting rage differ according to base Type.
Communication period setting (Period Type)
Select among 10ms, 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s, 10s -default is 10ms.
Output data setting when emergency
CPU Error
Latch Maintain previous output status.
Clear Clear all output.
CPU Stop
Latch Maintain previous output status.
Clear Clear all output.
Mode Sending: transfers data from Master module to Slave module.
Receiving: transfers data from Slave module to Master module.
Station Number Slave Station Number (Range: 1 ~ 99)
Communication type
Indicate communication type between Master and Slave. (Poll, Bit-Strobe, COS, Cyclic)
Read area (Master module Slave module)
Addressfirst device of TX devices
Refer to ML200R User’s Guide for memory address.
Size (Byte)
Indicate I/O point into Byte.
- Consider less than 8 bit I/O module as 1 Byte
5. Communication Programming 5.1. How to set master module
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 47 September 2010 Honeywell
Contents High-speed Link
Save area (Slave module
Master module)
Addressfirst device of RX devices
Refer to ML200R User’s Guide for memory address.
Size (Byte)
Indicate Slave module’s I/O point into Byte.
- Consider less than 8 bit I/O module as 1 Byte
PLC connection CPU module’s RS-232C or USB port
Control condition Control is available regardless of location (RUN, STOP) of mode switch of CPU module.
Maximum communication point TX 28,672 point, RX 28,672 point each 3584 byte
Maximum Block Number 126 (0~125)
Maximum point per block 244
High-speed Link setting count Maximum 12
ATTENTION
1. The above category is not set in SoftMaster-NM.
2. This data is the uploaded value from Pnet, which is set in SyCon.
When you change High-speed Link contents, you should download the parameter again.
It is possible to set and use only one High-speed Link per communication module.
Written parameter (basic, High-speed Link, P2P) is stored in the CPU module.
When changing the CPU module, download backup parameter set in SoftMaster-NM and write it to the new CPU module.
3. For more details on SyCon, refer to section Profibus-DP Communication.
5. Communication Programming 5.1. How to set master module
48 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
To use SoftMaster-NM for Pnet remote I/F module, perform the following steps.
Step Action
1 Execute SoftMaster-NM.
2 Click Online > Read IO Information or click .
You can read the I/O information of the Pnet remote I/F module.
3 Connect Pnet remote I/F module to read I/O information from High-speed Link.
4 Designate device and address used in program to connect I/O point to the slave module, which is composed in SyCon with PLC program.
5 Click Online > Write Parameter (Standard Settings, HS Link, P2P) or click
.
It starts writing High-speed Link parameter to Pnet remote I/F Module.
6 Click Online > Enable Link (HS Link, P2P) or click .
It enables Pnet remote I/F module’s communication.
High-speed Link communication status flag information
The following table indicates the communication flag list corresponding to High-speed Link Number.
Table 13 – Communication flag list
No. Keyword Type Contents Description
L000000 _HS1_RLINK Bit All stations of High-speed Link No.1 are normal.
It indicates normal status of all stations, which operate according to parameter set in the High-speed Link.
If the following condition are met, it would be turned ON.
a) All stations set in parameter are RUN mode and there is no Error.
b) All data blocks set in parameter operate properly.
5. Communication Programming 5.1. How to set master module
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 49 September 2010 Honeywell
No. Keyword Type Contents Description
c) When parameter of each station in parameter communicates normally, after Run_Link is ON, Run_Link maintains ON continuously unless disabled.
L000001 _HS1_LTRBL Bit
Indicates abnormal After _HS1RLINK ON
When _HSmRLINK Flag is ON, if station set in parameter and communication status is same as the following, this flag is turned ON.
a) Station set in parameter is not RUN mode.
b) Station set in parameter has Error.
c) Communication status of data block set in parameter is not proper.
If above condition is met, Link_Troble set ON.
If condition is normal, Link_Troble set OFF.
L000020 ~ L00009F
_HS1_STATE[k]
(k=000~127)
Bit Array
Indicates High-speed Parameter No.1 Kth Block’s total status
It indicates total status about each data block set in parameter.
HS1STATE[k]=HS1MOD[k]&_HS1TRX[k]&(~_HSmERR[k])
L000100 ~L00017F
_HS1_MOD[k]
(k=000~127)
Bit Array
Run Mode of High-speed Parameter No.1 Kth Block
It indicates operation mode of station set in Kth block of parameter.
L000180 ~
L00025F
_HS1_TRX[k]
(k=000~127)
Bit Array
Indicates normal Communication status with High-speed Parameter No.1 Kth Block
It indicates whether communication status of parameter’s Kth data block operates normally or not according to setting.
L000260 ~ L00033F
_HS1_ERR[k]
(k=000~127)
Bit Array
Error Mode of High-speed Parameter No.1 Kth Block
It indicates whether communication status of parameter’s Kth data block has error or not.
L000340 ~ L00041F
_HS1_SETBLOCK[k]
Bit Array
Indicates setting of High-speed Parameter No.1 Kth Block
It indicates whether Kth data block of parameter is set or not.
Note: In case of Pnet, Kth block indicates slave’s station number.
5. Communication Programming 5.2. How to register Profibus-DP remote module
50 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
ATTENTION
High-speed Link
Number
L Region Address Number
Reference
2 L000500~L00099F
In the above table, when High-speed Link is 1, other Flag address number is as follows according to simple calculation.
Calculation: L region address number = L000000 + 500 X (High-speed Link Number-1)
In the case of using the High-speed Link Flag for the program and monitoring, use Flag Map registered in the SoftMaster.
3 L001000~L00149F
4 L001500~L00199F
5 L002000~L00249F
6 L002500~L00299F
7 L003000~L00349F
8 L003500~L00399F
9 L004000~L00449F
10 L004500~L00499F
11 L005000~L00549F
K indicates information about 128 Blocks from Block No.000 to 127 through 8 word (Each word consist of 16 block).
For example, mode information (_HS1MOD) has information about block 0 ~15 in the L00010. (16~31, 3 2~47,48~63, 64~79, 80~95, 96~111, 112~127 in the L00011, L00012, L00013, L00014, L00015, L00016, L00017). So block no. 55’s mode information in the L000137.
5. Communication Programming 5.2. How to register Profibus-DP remote module
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 51 September 2010 Honeywell
5.2 How to register Profibus-DP remote module In order to use Profibus-DP remote module, you have to register an extended module parameter by using Extended Adapter.
Creating a new project
To create a new project, perform the following steps.
Step Action
1 In the SoftMaster-NA, click File > New File.
The New project dialog box appears.
2 From the Adapter type list, select 2MLL-PSRA and click OK.
After connecting USB cable to Profibus-DP remote module, turn on the power.
3 Click Online > Connection Settings.
The Online Settings dialog box appears.
5. Communication Programming 5.2. How to register Profibus-DP remote module
52 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
4 Select the Type as USB and Depth as Local.
5 Click Connect. The connection is established.
Setting I/O parameter
If I/O parameter is different from the actual system configuration in main base, Profibus-DP remote module indicates Module type mismatch error. At this time, STATUS LED is OFF.
Figure 18 – Error log
5. Communication Programming 5.2. How to register Profibus-DP remote module
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 53 September 2010 Honeywell
To set I/O parameter, perform the following steps.
Step Action
1 In the SoftMaster-NA, click Online > I/O Information.
The I/O information dialog box appears.
Verify whether the I/O information matches with the actual system configuration.
The following figure shows the I/O information.
2 If the I/O information matches with the actual module configuration, click the I/O Sync. button and match the I/O information.
After synchronization, the following message appears.
3 If module mismatch error appears, verify whether ERR LED is off or not.
Check whether all the modules are registered at project window.
5. Communication Programming 5.2. How to register Profibus-DP remote module
54 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
4 Analog module parameter setting: To set a detail parameter on the module, double-click the module at project window.
The parameter window, which appears when you double click 2MLF DC4A, is given below.
For detail on the each parameter, refer to the product’s manual.
After completing the parameter setting, download the parameter through Online > Write Parameter.
5 Digital I/O module parameter setting: If you double-click the digital I/O module, emergency output setting window appears for the output module, and input filter setting window appears for input module. In case of remote
5. Communication Programming 5.2. How to register Profibus-DP remote module
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 55 September 2010 Honeywell
Step Action
error, emergency output sets the output status for output module.
If emergency output is Clear, output becomes ‘0’ in case of error. If emergency output is Hold, output holds the last output data.
6 Before downloading, save the project and write the parameter.
After completing the parameter setting, click Online > Write Parameter to download parameter.
After download is complete, the following message appears.
5. Communication Programming 5.2. How to register Profibus-DP remote module
56 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
ATTENTION
Parameter is saved in flash memory permanently.
Emergency parameter is applied when communication with master is not normal.
Emergency output data is not maintained when power is off. If the power is turned OFF and ON when the emergency output is set as HOLD, it leads to an error, and the emergency output data is not saved.
Communication may stop if you download parameter, read I/O, and synchronize I/O during communication.
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 57 September 2010 Honeywell
6. Profibus-DP Communication
6.1 Overview Profibus is an open type field bus that the manufacturer selects independently (Vendor-independence). In addition, it is used widely for processing automation. Profibus-DP is the most frequently used Communication profile and the network suitable for FA environment of Field Level and it is suitable for master-slave communication between the master automation machine and the distribution slave I/O machine. It is designed to install with low cost and is the most suitable item to replace the existing system such as Hart system together with 24V parallel signal transmission to the production automation system.
6.2 Communication Specification The following table provides information about the Profibus-DP classification.
Table 14 – Profibus-DP classification
Classification Profibus-DP
Module type Pnet remote I/F module
Network type Profibus-DP
Slave protocol DP-V0
Standard EN 50170 / DIN 19245
Media access Logical Token Ring
Communication method
RS-485 (Electric)
Topology Bus
Modulation method NRZ (Non Return to Zero)
MAX (media access method)
Local token ring
Communication distance and transfer speed
Distance (m) Transfer speed (bps)
1,200 9.6k/19.2k/93.7k/187.5k
400 500k
6. Profibus-DP Communication 6.3. Basic Performance
58 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Classification Profibus-DP
200 1.5M
100 3M/6M/12M
Maximum Node/network
126 Stations
Maximum Node/segment
32 Stations
Cable Electric twisted shielded pair cable
Maximum I/O data/slave
244 byte
Maximum I/O module installation count
12
Installation position CPU slot
6.3 Basic Performance
Overview
Profibus-DP Master module sets the following functions.
1. Supports only High-speed Link communication.
2. Uses parameter setting in SoftMaster-NM and Configuration Tool (Honeywell provided tool: SyCon).
3. Sets only sending/receiving area from SoftMaster-NM High-speed Link parameter setting.
4. Sending/receiving data is saved continuously from the setting area and sent. (this is similar to the continued MAP of MASTER-K.)
5. Uses SyCon to set sending/receiving number and slave area per slave station and uses Configuration Port to download the master module.
6. Sending/receiving number is available up to 512bytes/3,584bytes respectively according to the type of Daughter board.
7. Sending/receiving number per slave station is set as byte unit (set in SyCon). Communication begins through SoftMaster-NM High-speed Link enable set.
6. Profibus-DP Communication 6.3. Basic Performance
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 59 September 2010 Honeywell
Operation by High-speed Link
If Master module is the product of Honeywell (2MLL-PMEA), it configures Profibus Network using SyCon.
1. Download Profibus Network Configuration to master module.
2. Set High-speed Link parameter of master in 2MLL-PMEA and download it.
3. Enable High-speed Link.
4. If using third party’s product as Master, configure Profibus Network using Configuration Tool of the corresponding product.
How to establish Pnet communication
Master communicates with Pnet expansion I/O module based on the downloaded setting information.
1. After writing parameter and checking, I/O data communication starts.
2. If it fails when processing each step, diagnosis is executed.
3. Initial sequence operation to establish communication is as follows.
6. Profibus-DP Communication 6.3. Basic Performance
60 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Figure 19 – Sequence operation to establish communication
6. Profibus-DP Communication 6.3. Basic Performance
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 61 September 2010 Honeywell
I/O data Communication
1. Expansion I/O modules are communicating with master by using backplane bus.
2. Maximum TRX data is 244 byte.
Figure 20 – I/O data Communication through backplane bus
3. For expansion I/O module, write parameter through local USB connection.
6. Profibus-DP Communication 6.4. Tool for Communication Setting
62 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Figure 21 – I/O data Communication through local USB
6.4 Tool for Communication Setting
Communication setting by SyCon
If using master module provided by Honeywell (2MLL-PMEA), configure Profibus network using SyCon and download the information to the corresponding master module. As Profibus Network Configuration Tool is different for each master module, and if you are using Honeywell master module (2MLL-PMEA), use only SyCon.
For communication setting, perform the following steps.
Step Action
1 Start the SyCon tool.
2 Click Insert > Master or select from the top left tool bar to insert Master module.
The Insert Master dialog box appears.
6. Profibus-DP Communication 6.4. Tool for Communication Setting
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 63 September 2010 Honeywell
Step Action
3 If using master module is 2MLL-PMEA, select COM-C-DPM and click the Add button.
Confirm Station address, and change Description if necessary.
4 Click OK and master module is inserted as below:
6. Profibus-DP Communication 6.4. Tool for Communication Setting
64 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
5 Master module setting: If you right-click the inserted master module and select Master Settings... from the context menu, the following dialog box appears.
Perform the following steps in order.
a) Click Controlled release of the communication by the application program under Parameter to user interface.
b) Click Little Endian (LSB-MSB) under Storage format (word module).
c) Click Buffered, host controlled under Handshake of the process data.
d) Click OK.
6 Click Insert > Slave or select from top left toolbar and click master to insert slave.
The Insert Slave dialog box appears.
6. Profibus-DP Communication 6.4. Tool for Communication Setting
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 65 September 2010 Honeywell
Step Action
7 In the Available slaves list, select 2MLL-PSRA and click the Add button if you are using 2MLL-PSRA. If there are several masters, select one from the Master and confirm Station address and Description, and then click OK.
ATTENTION
If there is no slave to use in the Available slaves list of Insert Slave dialog box, copy GSD file which is supplied by the module manufacturer, from the directory as shown below. Then, try SyCon again and insert slave.
8 Slave Configuration: Right-click the inserted slave icon and select Slave configuration from context menu or double-click the slave icon.
6. Profibus-DP Communication 6.4. Tool for Communication Setting
66 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
From the list of available modules, select the module having the necessary point and click Append Module. Insert the input module first and then insert output module.
9 Bus Parameter Setting: Bus parameter setting is the setting about Profibus-DP network. Click Settings > Bus Parameter.
The Bus Parameter dialog box appears. Optimize field contains standard and user definition setting. Speed setting (Baud rate) contains 9.6kbps ~12Mbps setting.
Normally, Baud rate is set as 1.5Mbps and Optimize is set as standard.
6. Profibus-DP Communication 6.4. Tool for Communication Setting
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 67 September 2010 Honeywell
Step Action
ATTENTION
Communication speed is related to transmission distance.
When you select Baud rate as 12Mbps, you should use the connector only for 12Mbps exclusive cable.
When using 12Mbps cable, distance between stations should be more than 1m.
When using 12Mbps cable, if the communication is cut off (especially, the station far from master), search for the proper end resistance value and set it random.
10 Device Allocation: It is required to download the prepared configuration to the master module. Click Setting > Device Assignment.
11 Select driver from the Driver select dialog box and click OK.
ATTENTION
Driver to be provided by 2MLL-PMEA type master module is only RS-232C port. Thus, CIF TCP/IP Driver, CIF Device Driver is not available.
Driver Selection of CIF Serial Driver:
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
68 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
Connect PC serial port and Configuration Port of Profibus-DP master module and apply the power of master module. Click Connect COM1 or other button according to PC serial port and confirm if the corresponding module is selected. As in the figure, Version and Date may have different value. If there is no error, select the check box and click the OK button.
ATTENTION
When you click the Connect COM1 button, if the module information does not appear normally and the error occurs, verify the connection of cable for configuration and the cable condition.
12 Configuration Download: Click Online > Download. It starts downloading, all LED status is OFF and only READY LED blinks. After downloading, all LED shows its function.
During the download, the following warning message appears.
After confirming if there is a problem in communication, click Yes to download.
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 69 September 2010 Honeywell
6.5 High-speed Link setting in SoftMaster-NM The following table lists the operation sequence of High-speed Link.
Table 15 – Operation sequence of High-speed Link
No. Software
used Operation Action
1
SyCon
Execute dedicated configuration tool
For 2MLL-PMEA, start SyCon.
2 Set network configuration
Refer to section 6.4 for SyCon Setting setting.
3 Connect to communication port
Refer to section 6.4 for SyCon setting.
4 Download network Configuration
Refer to section 6.4 for SyCon setting.
5
SoftMaster-NM
Execute SoftMaster-NM
On the SoftMaster window, click Tools > Network Manager.
6 Create new file On the SoftMaster-NM window, click File > New File. Type project name and select the PLC series.
7 Set SoftMaster-NM connection
Select applicable connection driver through SoftMaster-NM using Online > Connect menu.
8 Connect to SoftMaster-NM
On the SoftMaster-NM window, click Online > Connect.
9 IO Information ReadOn the SoftMaster-NM window, click Online > Read IO Information.
10 Define High-speed Link project
Select High-speed Link from the SoftMaster-NM window.
11
Set communication module and communication period
Select one among High-speed Link 1~ 12 and double-click it to specify module type, base number, slot number and period type.
12 Upload SyCon Double-click the created Block and click Online > SyCon Upload on
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
70 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
No. Software
used Operation Action
the High-speed Link window.
13 High-speed Link Block Setting
Double-click the cell on the High-speed Link window.
For Send : specify Read area (CPU area)
For Receive : specify Save area (CPU area)
14 High-speed Link Parameters Write
Click Online > Write Parameter and verify the applicable High-speed Link.
15 High-speed Link Enable
Click Online > Enable Link to enable the applicable High-speed Link.
Perform the High-speed Link parameter setting as follows.
Step Action
1 On the SoftMaster window, click Tools > Network Manager.
The SoftMaster-NM window appears.
2 Click File > New File.
The New NM Project dialog box appears.
3 Type the NM Project Name and select the PLC series.
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 71 September 2010 Honeywell
Step Action
4 Connect SoftMaster-NM and PLC on which the communication module is installed.
Click Online > Connection Settings.
The Online Settings dialog box appears. It indicates the way SoftMaster-NM is connected to the CPU.
The following table lists the items and description of Online Settings dialog box.
Items Description
Connection settings
Connection method RS-232C, USB, Ethernet, Modem, Extended base USB.
Connection steps
Local/Remote connection setting
Local: Connection from PC to CPU.
Remote: Connection from PC to CPU through communication module.
Common
Timeout interval when communication failure
1~9 seconds
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
72 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
Retrial number when communication failure
1~9 times
5 Click Online > Read IO Information to read the modules installed on the base.
6 Select High-speed Link tab on the SoftMaster-NM.
7 Select the communication module and double-click the High-speed Link.
The Communication Module Settings dialog box appears.
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 73 September 2010 Honeywell
Step Action
The following table describes the communication settings.
Classification Description
Communication module settings
Module type Select Pnet.
Base number
Select base number on which the module is installed.
Range of setting: 0 ~ 7
Slot number
Select slot number on which the module is installed.
Range of setting: 0 ~ 11
Communication period settings
Period type
Set the data transmission period
Range of setting: 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s, 10s
(default is 20ms)
Communication period is applied to all of the Send/Receive blocks.
Output data setup in case of emergency
CPU error Data is latched or cleared when CPU is on Error.
CPU stop Data is latched or cleared when CPU is Stop.
6. Profibus-DP Communication 6.5. High-speed Link setting in SoftMaster-NM
74 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Step Action
8 Click OK in the Communication Module Settings dialog box.
The following window appears.
9 Click Online > SyCon Upload to upload the SyCon’s configuration file.
10 Double-click the applicable index number of uploaded Configuration file and it indicates the Read area and Write area of Sending/Receiving data.
The following table describes the block settings.
Classification
Description
Master Station #
Display the Master station number.
Station # *1
Setting range for the slave : 0 ~ 126
If identical station No. is set, communication may not be normal.
Mode *1
Sending: Data transmission from master module to slave module.
Receiving: Data transmission from slave module to master module.
6. Profibus-DP Communication 6.6. How to set and download GSD
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 75 September 2010 Honeywell
Step Action
Read area (Master module → Slave module)
2MLR
Read area to set the start address of device used for sending.
Refer to ML200R User’s Guide for memory address.
2MLI
Read area to set the start address of device used for Sending.
Setting device : A, M, I, Q, R, W, F, K, L, N, U
Write area (Slave module → Master module)
2MLR
Write area to set the start address of device used for receiving.
Refer to ML200R User’s Guide for memory address.
2MLI
Write area to set the start address of device used for receiving.
Setting device : A, M, I, Q, R, W, F, K, L, N, U
Sending/ Receiving data (Byte)
Display input/output points of slave module (in bytes).
In case of I/O module of 8 bits or less, set 1 byte.
Note: *1 – Read/Write area is not able to set.
11 Click Online > Write Parameter. The Write parameter dialog box appears.
12 Select the applicable High-speed Link and click OK.
13 Click Online > Enable Link. The Link Enable(HS Link,P2P) dialog box appears.
14 Select the applicable High-speed Link and click Write. If the High-speed Link is enabled, then High-speed LED is ON.
6. Profibus-DP Communication 6.6. How to set and download GSD
76 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
6.6 How to set and download GSD The following procedure explains how to set and download GSD.
1. Download the expansion I/O module and the Pnet remote I/F module information through GSD file.
2. Read the GSD file where information of digital or analog I/O module is described through the configuration tool supporting Pnet configuration.
3. Modify the parameter through configuration tool.
4. After completing the setting, download information to Pnet master module.
5. Master establishes the communication with Pnet remote I/F module and verifies the information of expansion I/O modules based on the downloaded information.
Figure 22 – Downloading configuration information through GSD file
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 77 September 2010 Honeywell
7. Maintenance and Repair
7.1 I/O module maintenance The routine inspections are recommended to maintain the module in good condition.
The I/O module mainly consists of semiconductor elements. Hence, the life of PLC depends upon the condition of its semiconductor parts. Regular checks must be carried out as errors in the elements may occur due to the effect of the surrounding environment.
Refer to the following table for the items to be checked, once or twice in every 6 months.
Checklist Judgment Basis Actions
Environment
Temperature
0 ~ + 55°C Adjust the temperature and humidity conditions properly.
Humidity 5 ~ 95%RH
Vibration None Use vibration-preventive rubber or other measures.
Loose terminal screw Screws should not be loose.
Tighten the loosened screw.
Input voltage change rate
Within -15%+10% Maintain the change rate within the allowable range.
Spare parts
Check whether the amount and conditions of spare parts are proper.
Replenish insufficient parts and improve the storage condition.
Power supply
Voltage measure between terminals.
DC 20.4 ~ 28.8V
Adjust the power within the allowable voltage variance range.
7. Maintenance and Repair 7.2. Routine inspection
78 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
7.2 Routine inspection The following items must be routinely inspected for Profibus-DP module.
Checklist Check Point Judgment Basis Actions
I/O module connection status
Check whether the screws are firmly tightened.
Check whether the module cover is intact or separated.
Must be firmly tightened.
Tighten the module screw.
Cable connection status
Check the cable connection if it is loosened.
Cable must be tightened.
Tighten the cable.
Display LED
RUN LED
Check whether the LED is ON in RUN state.
LED On (off or blinking is error).
Refer to section System Configuration
P-N LED Check whether the LED is ON.
Power and communication normal.
STATUS LED
Check whether the LED is ON.
Expansion I/O module information match.
ERR LED
Check whether the LED is ON.
Module detached, invalid module installed, Out of I/O data range, I/O parameter error.
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 79 September 2010 Honeywell
8. Troubleshooting
8.1 Introduction This chapter describes various potential errors that occur while operating the system, causes of errors, ways to detect them, and corrective measures.
8.2 Basic troubleshooting procedure If there is any problem in the system, identifying the cause for the problem and taking immediate corrective actions would improve the reliability of the system. To troubleshoot the system, ensure that the cautions and procedures given below are followed.
Check the following manually.
Operation status (Stop and Run).
Power ON/OFF status.
I/O device status.
Wiring status (I/O wiring, extension, and communication cable).
The status of each displays (RUN, ERR, P-RUN, STATUS LED, I/O LED, and so on), connection to peripherals, and verify the operation condition.
Check for any abnormality. Observe how an error can be detected:
Move the key switch to STOP and turn it ON/OFF.
Restricting range. Identify the reason for the fault.
Is it from the PLC or external factor?
I/O module or others?
PLC program?
8. Troubleshooting 8.3. Troubleshooting methods
80 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
8.3 Troubleshooting methods The following procedure describes the detection methods, description for error codes, and corrective measures.
8. Troubleshooting 8.3. Troubleshooting methods
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 81 September 2010 Honeywell
Action method when RUN LED is OFF
This section describes the sequence of steps to be taken, if the RUN LED is OFF.
8. Troubleshooting 8.3. Troubleshooting methods
82 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Action method when ERR LED is ON
This section describes the sequence of steps to be taken, if the ERR LED is ON.
8. Troubleshooting 8.3. Troubleshooting methods
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 83 September 2010 Honeywell
Action method when Program Write does not work
This section describes the sequence of steps to be taken, if the Program Write does not work.
8. Troubleshooting 8.3. Troubleshooting methods
84 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
SyCon connection error
This section describes the sequence of steps to be taken, if the SyCon connection error occurs.
8. Troubleshooting 8.3. Troubleshooting methods
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 85 September 2010 Honeywell
SoftMaster-NM connection error
This section describes the sequence of steps to be taken, if the SoftMaster-NM connection error occurs.
8. Troubleshooting 8.3. Troubleshooting methods
86 Pnet Remote I/F Module 2MLL-PSRA User's Guide R200 Honeywell September 2010
Communication error with slave
This section describes the sequence of steps to be taken, if the communication error occurs with slave.
8. Troubleshooting 8.3. Troubleshooting methods
R200 Pnet Remote I/F Module 2MLL-PSRA User's Guide 87 September 2010 Honeywell