1TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
DATAMINING FOR DECISION SUPPORT OF CBM OF POWER
CABLES
E. GULSKI(1), F.J. WESTER(1), B. QUAK(1), J.J. SMIT(1), F.de VRIES(2), M.B. MAYORAL(3)
(1) Delft University of Technology – The Netherlands (2) Nuon InfraCore – The Netherlands
(3) Universidad Politecnica de Madrid – Spain
2TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
FailureProbability
Asset Aging Over-voltageProbability
ConditionAssessment
Type of DefectLocation of
Defect
Different categories of technical information to support AM decisions
3TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
Positioning of diagnostics and condition assessment in the AM processing of
technical information on component level Equipment Inventory
Failure cases
Spare parts and equipment
Diagnostics
Maintenance
Ageing Models
Reliability evaluation
Maintenance rules
1:Maintenance and diagnostic evaluation, scenario search and evaluation of usability
Replace
Run to Failure
Refurbish
CBM/ TBM/ CM
M/ D modification
As Before
Monitoring
Scenarios
4TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
AM Decision Support System:power cables
Cable construction effects: insulation types, defect types
Operational effects:electrical, thermal, mechanical stresses
DIAGNOSTICS
detection of insulation & construction
defects
DATABASES & DATAMINING
service based knowledge rules
AM Decision Support System
CONDITION ASSESMENT
Cable construction effects: insulation types, defect types
Operational effects:electrical, thermal, mechanical stresses
DIAGNOSTICS
detection of insulation & construction
defects
DATABASES & DATAMINING
service based knowledge rules
AM Decision Support System
CONDITION ASSESMENT
5TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
Evaluation of different PD diagnostics for distribution power cables
0
1
2
3
4
51
2
3
4
5
6AC 50/60 Hz
AC 15-300 Hz
VLF 0.1 Hz
DAC 50-500 Hz
Voltage type
Non-destructiveness
IEC 60270 conformity
SensitivityAnalysis
Efficiency
6TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
Oscillating Wave Test System in the field
HV supply / computer
Coil / HV Switch / PD detection circuit
7TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003Partial discharge occurrence during DAC voltages
8TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
PD mapping and database protocol made
automatically after the 3 phase of the distribution
power cable are tested
9TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
61%
29%
2%8%
16%
33%
51%
0%
20%
40%
60%
80%
100%
PD presence PD location
PD activiy PILC
PD at U0 PD at 1.3*U0 PD at Higher VoltagesUnknown Results PD Source in Cable Insulation PD Source in TerminationPD Source in Joint
4 years experiences
10TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
45%
18%
27%
9%
83%
17%
0%
20%
40%
60%
80%
100%
PD presence PD location
PD activiy XLPE
PD free PD at U0 PD at 1.3*U0
PD at Higher Voltages PD Source in Termination PD Source in Joint
2 years experiences
11TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
Datamining; four characteristics
Is based on an earlier stages of data
selection, data transformation,
stages of validation
and interpretation
Is based on finding intelligible patterns
which are not predicted by
established theory
It formats the output data in a visual form that
human intelligence can interpret easily
It is an alternative to the traditional
scientific method, where data analysis is
largely directed by hypothesis and theory
I II
III IV
12TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
data-mining process for condition-based maintenance of HV assets, e.g. power cables
Data-mining
approach
Componentdata
Failuredata
Conditiondata
ConditionBasedMaintenanceActivities
Knowledgerules
Norms &criteria
Data
sourc
es
(A)
(B)
(C)
13TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
diagnostics database
Norms
Cable Data
Measurement Types
Definition of Measurement
Types
MeasurementData
Input of Measurement
Data
Analysis of Measurement
and Cable Data / Norms
Definition of Cable Structure
14TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
15TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
PILC database population of two different type of cable
splices( a )
( b )
16TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
17TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003 Remaining Life-time
Cable Insulation degradation
0
5
10
15
20
25
30
35
0 5 10 15 20 25 30Time [years]
Rem
aini
ng li
fetim
e
Defect
Normal
Future load
Tota
l A
s set
Con
dit
ion
Asset Service Life
18TUD_Gulski_A1_The Netherlands_author_ALPHA6_Block 3
Barcelona 12-15 May 2003
Condition assessment is an important element of Asset Management maintenance approach and means combination of advanced diagnostics and technical information of the actual network situation
With regard to distribution power cables, PD detection is a good method to get insight into discharging insulation defects. Selecting proper advanced PD diagnosis e.g. at DAC voltages needs evaluation of technical and economical aspects.
To use diagnostic information for AM decision support standardized database protocols are necessary. Database support in combination with datamining is important elements in obtaining relevant information for condition assessment of assets e.g. powers cables.
Based on this information, decisions can be made about levels for updating or maintenance. When these levels are applied on the database as norm levels, components are easily selected for inspection, maintenance or replacement actions.
Conclusions