trip curve values for micrologic® trip units
DESCRIPTION
Micro logic trip valuesTRANSCRIPT
Instruction BulletinS1A1576900 (Rev01)
09/2009Cedar Rapids, IA, USA
Replaces S1A1576900 08/2009
Trip Curve Values for Micrologic® Trip UnitsBasic, A, P and H Types
Retain for future use.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
© 2009 Schneider Electric All Rights Reserved
Schneider Electric3700 Sixth St. SWCedar Rapids, IA 52404 USA1-888-SquareD (1-888-778-2733)www.schneider-electric.us
Micrologic Trip Curve Values These values apply for Basic, A, P and H type Micrologic trip units, for all protections levels (2.0, 3.0, 5.0 and 6.0).
Table 1: Micrologic Trip Unit Long-Time Delay Values
SettingLong-Time Delay in Seconds
0.5 1 2 4 8 12 16 20 24
tr at 1.35 x IrMinimum 11.94 23.89 47.77 95.54 191.09 286.64 382.19 477.74 573.28
Maximum 19.12 38.24 76.49 152.98 305.96 458.94 611.92 764.9 917.88
tr at 1.5 x IrMinimum 8.66 17.32 34.64 69.27 138.55 207.82 277.1 346.37 415.65
Maximum 12.51 25.03 50.05 100.11 200.22 300.32 400.43 500.54 600.65
tr at 2 x IrMinimum 4.15 8.29 16.59 33.17 66.35 99.52 132.69 165.87 199.04
Maximum 5.47 10.93 21.87 43.73 87.46 131.91 174.92 218.65 262.38
tr at 3 x IrMinimum 1.68 3.36 6.72 13.44 26.89 40.33 53.78 67.22 80.67
Maximum 2.14 4.27 8.54 17.08 34.17 51.25 68.34 85.42 102.51
tr at 5 x IrMinimum 0.58 1.16 2.32 4.64 9.28 13.92 18.56 23.2 27.84
Maximum 0.73 1.45 2.91 5.81 11.63 17.44 23.25 29.07 34.88
tr at 6 x IrMinimum 0.4 0.8 1.6 3.2 6.4 9.6 12.8 16 19.2
Maximum 0.5 1 2 4 8 12 16 20 24
tr at 7.2 x IrMinimum 0.35 0.55 1.11 2.21 4.42 6.63 8.85 11.06 13.27
Maximum 0.5 0.69 1.38 2.76 5.52 8.28 11.04 13.8 16.56
Table 2: Micrologic Trip Unit Short-Time Delay Values
SettingShort-Time Delay
0 0.1 0.2 0.3 0.4
I2t off (Isd at 10 Ir) (seconds) 0 0.1 0.2 0.3 0.4
I2t on (Isd at 10 Ir) (seconds) — 0.1 0.2 0.3 0.4
tsd (min. trip) (milliseconds) 20 80 140 230 350
tsd (max. trip) (milliseconds) 80 140 200 320 500
Table 3: Micrologic Trip Unit Ground-Fault Delay Values
SettingGround-Fault Delay
0 0.1 0.2 0.3 0.4
I2t off (at 1 In) (seconds) 0 0.1 0.2 0.3 0.4
I2t on (at 1 In) (seconds) — 0.1 0.2 0.3 0.4
tsd (min. trip) (milliseconds) 20 80 140 230 350
tsd (max. trip) (milliseconds) 80 140 200 320 500