micrologic p
TRANSCRIPT
Micrologic control units5.0 P, 6.0 P and 7.0 PLow Voltage Products
User manual
Firmware version P Logic-2002 AA
E60
439A
We do more with electricity.
Micrologic P Schneider Electric1
Discovering Micrologic P 4Identification 4Presentation 5Setting procedure 6Setting Micrologic 5.0 P using the dials 8Setting Micrologic 6.0 P using the dials 9Setting Micrologic 7.0 P using the dials 10Selecting the type of neutral protection 11Main menus 12Metering 14History, maintenance and setup 16Protection 18
Overview of functions 20Current protection 20Voltage protection 26Other protection 27Load shedding and reconnection 28Measurements 29Alarms 31Optional M2C and M6C contacts 32Event histories 33LEDs and display screens 34COM communications option 36
Setup 38Setting up the optional M2C / M6C contacts 38Setting up the Micrologic control unit 40Setting up the metering functions 43Setting up the COM communications option 46
Protection settings 48Fine adjustment of the long-time I2t, short-time andinstantaneous settings using the keypad 48Fine adjustment of the long-time Idmtl, short-time andinstantaneous settings using the keypad 49Fine adjustment of the ground-fault and earth-leakageprotection setting using the keypad 50Setting the neutral protection 51Setting the It, I unbal, max, U min, U max, U unbal, rP max,F min, F max and phase-rotation protection functionsusing the keypad 52Setting load shedding / reconnection 54
Metering 56Current measurements 56Voltage measurements 59Power measurements 61Energy measurements 63Frequency measurements 64
Maintenance 66Resetting fault indications 66Viewing the event histories 67Operation counter and contact-wear indicator 68Checking/replacing the battery 69Tests 70
Micrologic control units5.0 P, 6.0 P and 7.0 P
I
Micrologic P Schneider Electric2
Tripping curves 72Voltage measurements 74Zone selective interlocking (ZSI) 76Power supply 77Changing the long-time rating plug 79Thermal memory 80Data available via the COM communications option 81Threshold and time-delay settings 82Other settings 85Measurement setting ranges and accuracy 86Power-factor sign conventions 87
Index 88
Technical appendix 72
Micrologic P Schneider Electric3
Micrologic P Schneider Electric4
Discovering Micrologic P
E60
230A
E60
483A
All Masterpact NT and NW circuit breakersare equipped with a Micrologic control unitthat can be changed on site.Control units are designed to protectpower circuits and connected loads.They offer current, voltage, frequency,power and energy measurements.The functions provided by Micrologic 5.0 P,6.0 P and 7.0 P control units optimisecontinuity of service and powermanagement in your installation.
Identification
E60
231A
X: type of protectionc 2 for basic protectionc 5 for selective protection
Micrologic P Schneider Electric5
1 top fastener2 terminal block for external connections3 housing for battery4 screw for long-time rating plug5 long-time rating plug6 cover opening point7 protective cover8 lead-seal fixture for protective cover9 infrared link with communications interfaces10 connection with circuit breaker11 bottom fastener
Indications
12 LED indicating long-time tripping13 LED indicating short-time or
instantaneous tripping14 LED indicating ground-fault or
earth-leakage tripping15 LED indicating additional-protection or
auto-protection tripping16 graphics display17 button for reset of fault-trip LED reset
and battery test
Navigation
18 access button to the "Metering" menu (*)19 access button to the "History, maintenance
and setup" menu (*)20 access button to the "Protection" menu (*)21 button used to scroll down or reduce
the displayed value22 button used to scroll up or increase
the displayed value23 button used to select or confirm a choice
Adjustment dials
24 long-time current setting Ir25 long-time tripping delay tr26 short-time pickup Isd27 short-time tripping delay tsd28 instantaneous pickup Ii29 ground-fault pickup Ig30 ground-fault tripping delay tg31 earth-leakage pickup I∆n32 earth-leakage tripping delay ∆t33 LED indicating an overload34 test button for ground-fault and
earth-leakage protection35 test connector
(*) These buttons include a LED indicating the active menu.
Presentation
E60
235B
E60
236A
E60
237A
Micrologic 5.0 P control unit Micrologic 6.0 P control unit
E60
238A
E60
239A
E60
240A
10
9
18 19 20
21 22 23
Micrologic 5.0 P
4260AN 1 2 3
100
50
0
12
13
14
15
16
17
delaysettingx Ir
22.5
34 5
68
10
Isd
1.5
.4.5.6
.7.8
.9.95.98
1
short timeI itsd
(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
instantaneous
long timealarmIr
x In .512
48
121620
tr(s)
@ 6 Ir24
x In2
410
3
6 8
1215
off
24
25
26
27
33
28
35
.4.5.6
.7.8
.9.95.98
1
delay
short timeI itsd
(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
instantaneous
long timealarmIr
x In
ground fault
BC
DE F
GH
J
Ig tg(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
A
settingx Ir
22.5
34 5
68
10
Isd
1.5
.512
48
121620
tr(s)
@ 6 Ir24
x In
test
2
410
3
6 8
1215
off
35
33
34
28
24
25
26
27
29
30
Micrologic 7.0 P control unit
E60
241B
.4.5.6
.7.8
.9.95.98
1
delay
short timeI itsd
(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
instantaneous
long timealarmIr
x In
Micrologic P Schneider Electric6
Discovering Micrologic P
Settings using the dials
E60
250B
Setting procedure
c open the protectivecover.
Micrologic 5.0
Dialsc dials are used to set Micrologic Pprotection thresholds and tripping delaysfor overloads, short-circuits, ground faultsand earth leakage.c if the set thresholds are overrun, theseprotection functions systematically tripthe circuit breaker.
Buttonsc buttons on the keypad are used for fineadjustments of the protection thresholds andtripping delays for overloads, short-circuits,ground faults and earth leakage. The valuepreviously set using a dial automaticallybecomes the maximum value for the keypadsettings.c they may also be used to activate otherfactory-disabled protection functionsavailable on Micrologic P. These otherprotection functions are not accessiblevia the dials.
With the protective cover open, make allthe necessary settings for your control unit.
All fine adjustments are permanently storedin memory, unless the setting is modifiedusing the adjustment dial.
For remote settings using thecommunications option,see the "Remote settings" section inthe "Com setup" menu under "History,maintenance and setup".
E60
251B
Micrologic 5.0
c make the necessary settings using the dialsc the screen automatically displays the relevant curvec check the set value on the screen, in absolute valuein amperes (A) and in seconds (s).
Settings using the keypad
È60
252B
Micrologic 5.0
c the and buttons under the screen may beused for fine adjustments of the settings made usingthe dials.c all the settings not available via the dials are madein the same manner, using the keypad.
Caution!A new overload (long-time) or short-circuit(short-time and instantaneous) protection settingmade using one of the dials:ccccc deletes all the fine adjustments previouslymade using the keypad for the overload(long-time) and short-circuit (short-time andinstantaneous) protectionccccc does not affect the fine adjustments madeusing the keypad for ground-fault andearth-leakage protectionccccc does not affect any other settings made usingthe keypad.
Similarly, a new ground-fault or earth-leakageprotection setting made using one of the dials:ccccc deletes all the fine adjustments previouslymade using the keypad for the ground-fault andearth-leakage protectionccccc does not affect the fine adjustments madeusing the keypad for the overload (long-time) andshort-circuit (short-time and instantaneous)protectionccccc does not affect any other settings made usingthe keypad.
Micrologic P Schneider Electric7
With the protective cover closed,it is not possible to set the protectionfunctions. However, it is possible to setmetering functions and alarms, as well asview all measurements, settings andhistories.
Caution!If you notice that the tab on the back of the protectivecover has been broken off, contact the Schneiderafter-sales support department to replace the cover.
View the settings and measurements
E60
253B
Micrologic 5.0
E60
254B
Micrologic 5.0
c close the protectivecover for the dialsc access to the dials isblocked and it is nolonger possible to makefine adjustments usingthe keypad
c if necessary, install alead seal to protect thesettingsc settings may be viewedat any time using thekeypad.
E60
490B
Micrologic 5.0
Micrologic P Schneider Electric8
Setting Micrologic 5.0 Pusing the dials
Consider a 2000 A circuit breaker.
E60
325A
E60
445A
1
In = 2000 A
In = 2000 A
See pages 22 and 24 for selection of thesetting ranges.
Set the thresholds
settingx Ir
22.5
34 5
68
10
Isd
1.5
.4.5.6
.7.8
.9.95.98
1
short timeI i
instantaneous
long timeIr
x In
In = 2000 A
Ir = 0.5 x 2000 = 1000 A
Ii = 2 x 2000 = 4000 A
Isd = 2 x 1000 = 2000 A
x In2
410
3
6 8
1215
off
Set the time delays
E60
326A
delay
short timetsd(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
long time
.512
48
121620
tr(s)
@ 6 Ir24
tr = 1 s
tsd = 0.2 s
Discovering Micrologic P
E51
375A
E51
376A
tr
tsd
0 I
t
tr
tsd
0 I
t
I2t ON curve I2t OFF curve
time delays
tr: LT tripping delaytsd: ST tripping delay
E51
372A
E51
373A
Ir
Isd
Ii
0 I
tIr
Isd
Ii
0 I
t
I2t ON curve I2t OFF curve
thresholds
Ir: LT thresholdIsd: ST pickupIi: Instantaneous pickup
Micrologic P Schneider Electric9
Setting Micrologic 6.0 Pusing the dials
Set the thresholds
Set the time delays
E60
329A
E60
330A
Consider a 2000 A circuit breaker.
E60
445A
1
In = 2000 A
In = 2000 A
.4.5.6
.7.8
.9.95.98
1
short timeI i
instantaneous
long timeIr
x In
ground fault
BC
DE F
GH
J
Ig
A
settingx Ir
22.5
34 5
68
10
Isd
1.5x In
2
410
3
6 8
1215
off
In = 2000 A
Ir = 0.5 x 2000 = 1000 A
Ii = 2 x 2000 = 4000 A
Isd = 2 x 1000 = 2000 A
B Ig = 640 A
delay
short timetsd(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
long time
ground fault
tg(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
.512
48
121620
tr(s)
@ 6 Ir24
tr = 1 s
tg = 0.2 s
tsd = 0.2 s
See pages 22 to 26 for selectionof the setting ranges.
E51
415A
E51
416A
0 I
t
Ig
0 I
t
Ig
E51
419A
E51
418A
0 I
t
tg
0 I
t
tg
E51
376A
E51
375A
tr
tsd
0 I
t
tr
tsd
0 I
t
time delays
I2t ON curve I2t OFF curve
E51
373A
E51
372A
Ir
Isd
Ii
0 I
tIr
Isd
Ii
0 I
t
I2t ON curve I2t OFF curve
thresholds
Ig: ground-fault pickup
Ir: LT thresholdIsd: ST pickupIi: Instantaneous pickup
tr: LT tripping delaytsd: ST tripping delay
tg: ground-fault tripping delay
Micrologic P Schneider Electric10
Setting Micrologic 7.0 Pusing the dials
Set the thresholds
E60
445A
E60
333B
Consider a 2000 A circuit breaker.
See pages 22 to 26 for selection ofthe setting ranges.
Set the time delays
E60
334B
1
In = 2000 A
In = 2000 A
.4.5.6
.7.8
.9.95.98
1
short timeI i
instantaneous
long timeIr
x In
settingx Ir
22.5
34 5
68
10
Isd
1.5
earth leakage
12
35 7
1020
30.5
I∆n(A)
x In2
410
3
6 8
1215
off
In = 2000 A
Ir = 0.5 x 2000 = 1000 A
Ii = 2 x 2000 = 4000 A
Isd = 2 x 1000 = 2000 A
I∆n = 1 A
delay
short timetsd(s)
on I2t
.2
.3.4 .4
.1
.2.3
.10off
long time
.512
48
121620
tr(s)
@ 6 Ir24
800
earth leakage
∆t(ms)
60
140
230 350
tr = 1 s
∆t = 140 ms
tsd = 0.2 s
Discovering Micrologic P
I2t OFF curve
E51
376A
E51
375A
tr
tsd
0 I
t
tr
tsd
0 I
t
E51
423A
time delays
I2t ON curve
0 I
t
∆t
E51
373A
E51
372A
Ir
Isd
Ii
0 I
tIr
Isd
Ii
0 I
t
I2t ON curve I2t OFF curve
E51
421A
thresholds
0 I
t
I∆n
Ir: LT thresholdIsd: ST pickupIi: Instantaneous pickup
tr: LT tripping delaytsd: ST tripping delay
I∆n: earth-leakage pickup ∆t: earth-leakage trippingdelay
E60
153A
Micrologic P Schneider Electric11
Selection dial on four-pole circuit breakers
On four-pole circuit breakers, it is possible to select the type of neutral protectionfor the fourth pole using the three-position dial on the circuit breaker:c no neutral protection 4P 3Dc half neutral protection 3D + N/2c full neutral protection 4P 4D
The factory default setting is 3D + N/ 2.
Selecting the type of neutralprotection
E51
383A
4P 3D
3D+N/2
4P 4D
Caution!With the 4P 3D setting, the current in the neutral mustnot exceed the rated current of the circuit breaker.
Micrologic P Schneider Electric12
Discovering Micrologic P Main menus
The Micrologic P control unit offers access to the main screen and three menus:c the main screen displaying the continuous measurement of the phase currents(I1, I2, I3) and the neutral current (IN), if it existsc the "Metering" menuc the "History, maintenance and setup" menuc the "Protection" menu.
Main screen
E60
101A
4260A1 2 3
100
50
0
"Metering", "History, maintenance and setup" and"Protection" menus
E60
102A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
v press the or button to return to the mainscreen
v press the button to return to the previousscreenv whatever the screen displayed, if no further action istaken, the system returns to the main screen after afew minutesv the LED goes OFF on exiting the menu.
As long as no functions are activated, Micrologic Pcontrol units display in real time the current on themost heavily loaded phase.The number for that phase is presented in a square.
The current in the neutral is displayed if the neutral CTis set as internal or external (see "Ineutral (A)"settings in the "Current protection" menu).
When a menu button is pressed, apresentation screen is displayed and thegreen LED on the button goes ON.
c "Metering" menu
Micrologic P Schneider Electric13
E71
657A
c saving settings
E71
711A
E71
712A
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
c "History, maintenance and setup" menu
v press the or button to return to the mainscreen
v press the button to return to the previousscreenv whatever the screen displayed, if no further action istaken, the system returns to the main screen after afew minutesv the LED goes OFF on exiting the menu.
c "Protection" menu
v press the or button to return to the mainscreen
v press the button to return to the previousscreenv whatever the screen displayed, if no further action istaken, the system returns to the main screen after afew minutesv the LED goes OFF on exiting the menu.
When a setting is made in any of the three menus, thescreen used to save the modification(s) may beaccessed by pressing one of the three buttons
, or .
v select yes to save the modificationsv select no to cancel and maintain the previoussettingsv this screen remains displayed until yes or no areselected.
Do you wantto save newsettings?
no
yes
Micrologic P Schneider Electric14
Discovering Micrologic P Metering
Press the button to select the "Metering" menu.
move the cursor down the screen or decrement a value.
move the cursor up the screen or increment a value.
select an option in a list, confirm a selection or the value of a setting.
indicates that the operator is in the "Metering" menu and returnsto the previous screen.
return to the main screen.
Current measurements
E60
105A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
E60
391A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
I (A)access to the following sections:
Instant.
I1, I2, I3, INI1, I2, I3, IN currents(depending on the type ofsystem)
MaxStoring and reset ofthe maximum instantaneouscurrents.
Demand
I1, I2, I3, INDemand current on thephases 1, 2, 3 and on N(depending on the type ofsystem)
MaxStoring and reset ofthe maximum demandcurrents.
Voltage measurements
I I I
U (V)access to the following sections:
Instant.Instantaneous phase-to-phase U12, U23, U31 andphase-to-neutral V1N, V2N, V3N voltages(depending on the type of system)
Average 3 ΦAverage voltage U average of the phase-to-phasevoltages.
Unbal 3 ΦUnbalance voltage U unbal. of the phase-to-phasevoltages.
I
Phaserotation
Phase sequence.
Micrologic P Schneider Electric15
E60
392A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
E60
393A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
Power measurements
P (kW)access to the following sections:
Instant.
P, Q, S,Total active power PTotal reactive power QTotal apparent power S
Powerfactor
Power factor PF
Demand
P, Q, S
Max
Demand values for the:c total active power Pc total reactive power Qc total apparent power S
Storing and reset ofthe maximum demand powervalues
Energy measurements
E (kWh)access to the following sections:
E total
E in
Total active energy E.PTotal reactive energy E.QTotal apparent energy E.S
Positive component of:c the total active energy E.Pc the total reactive energy E.Q
E outNegative component of:c the total active energy E.Pc the total reactive energy E.Q
ResetEnergy
Reset all the energy values to zero
Frequency measurement
F (Hz)access to the frequency measurement
E60
394A
I
U (V)
(kW)
(A)
E (kWh)
P
F (Hz)
Micrologic P Schneider Electric16
Discovering Micrologic P History, maintenanceand setup
Press the button to select the "History, maintenance and setup" menu.
move the cursor down the screen or decrement a value.
move the cursor up the screen or increment a value.
select an option in a list, confirm a selection or the value of a setting.
indicates that the operator is in the "History, maintenance and setup" menuand returns to the previous screen.
return to the main screen.
E71
711A
E71
713A
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
Event history
access to the following sections:
Triphistory
The last ten alarms recorded
Number of operations (opening or closing)
Contactwear
M2C / M6C Contacts
Eventhistory
The last ten faults recorded
Alarmhistory
Operationcounter
Wear of the circuit-breaker main contacts
access to the following sections:ContactsM2C / M6C
Assignment of a protection alarm to an M2C or anM6C contact
SetupLatching mode for each M2C or M6C contact
ResetReset of the M2C or M6C contacts
Alarmtype
Micrologic P Schneider Electric17
Micrologic setup
E71
714A
E71
715A
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
access to the following sections:
Language
Setting of the date and time
Indication of the circuit-breaker type
Metering setup
Micrologicsetup
Selection of the display language
Date / time
Breakerselection
Select of the primary and secondary voltages onthe instrument transformerVT ratio
Indication of the rated system frequencySystemfrequency
access to the following sections:Meteringsetup
c 3 phases, 3 wires, 3 CTs: method usingtwo wattmetersc 3 phases, 4 wires, 3 CTs: method usingthree wattmetersc 3 phases, 4 wires, 4 CTs: method usingthree wattmeters with measurementof the neutral current.
Currentdemand
Selection of the calculation method and settingof the time interval for the calculation
Selection of the calculation method and settingof the parameters for the calculation
Systemtype
Powerdemand
Setting of the sign convention for the power factorand reactive power, i.e. IEEE, IEEE alternate or IEC(see page 87 to determine the sign convention)
Signconvention
Setting the power signPowersign
E71
716A
Eventhistory
setupMetering
ContactsM2C / M6C
Micrologicsetup
setupCom.
COM communications-option setup
access to the following sections:
Com.parameter
Authorisation of access to settings viathe COM communications option.
Authorisation of access to the circuit-breaker ONand OFF commands via the COM communicationsoption.
Com.setup
Setting of parameters for the COM communicationsoption (address, baud rate, parity)
Remotesettings
Remotecontrol
Micrologic P Schneider Electric18
Discovering Micrologic P
Press the button to select the "Protection" menu.
move the cursor down the screen or decrement a value
move the cursor up the screen or increment a value
select an option in a list, confirm a selection or the value of a setting
indicates that the operator is in the "Protection" menu and returnsto the previous screen
return to the main screen
E71
712A
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
I (A)
access to the following sections:Currentprotection
Fine settings of the long-time I2t, short-time andinstantaneous protection functions
Protection
Idmtl (A)Fine settings of the long-time Idmtl,short-time and instantaneous protection functions
I (A)Fine settings of the:c ground-fault (Micrologic 6.0 P)c earth-leakage (Micrologic 7.0 P) protection functions
Ineutral (A)Selection of the type of neutralsensor and type of neutral protection
I AlarmSetting of the I alarm
Iunbal (%)Setting of the current-unbalance protection I unbal
Setting of the maximum-current protection 1 max
I1 max (A)
I2 max (A)Setting of the maximum-current protection 2 max
I3 max (A)Setting of the maximum-current protection 3 max
Current protection
I
I
I
IN max (A)Setting of the maximum-current protection N maxI
Micrologic P Schneider Electric19
E71
719A
E71
720A
Voltage protection
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
E71
721A
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
E71
722A
I
P
Currentprotection
Voltageprotection
Otherprotection
Loadshedding
Loadshedding
access to the following sections:
Setting of the maximum-voltage protection U max.
Setting of the voltage-unbalance protection U unbal.
Other protection
Voltageprotection
Setting of the minimum-voltage protection U min.
Umin (V)
Umax (V)
Uunbal (%)
access to the following sections:Otherprotection
Setting of the reverse-power protection rP max
rPmax (W)
Setting of the minimum-frequency protection F min
Fmin (Hz)
Setting of the maximum-frequency protection F max
Fmax (Hz)
Setting of the phase-rotation protectionPhaserotation
Load shedding depending on current
Access to load shedding and reconnectiondepending on current
Loadshedding I
Load shedding depending on power
Access to load shedding and reconnectiondepending on power
Loadshedding P
Micrologic P Schneider Electric20
Overview of functions Current protectionI2t long-time protection
For the default values, the setting ranges,increment steps and setting accuracies,see the technical appendix.
The long-time protection function protects cables against overloads. This function isbased on true rms measurements.It is possible to select either I2t long-time protection or Idmtl long-time protection.
I2t long-time protectionLong-time current setting Ir and standard tripping delay tr
Micrologic control unit Accuracy 5.0 P, 6.0 P and 7.0 Pcurrent setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1tripping betweeen 1.05 and 1.20 Ir other ranges or disable by changing rating plug
time setting 0,5 1 2 4 8 12 16 20 24time delay (s) tr at 1.5 x Ir 0 to - 30% 12.5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0 to - 20% 0.7 (1) 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
(*) In: circuit breaker rating(1) 0 to - 40%(2) 0 to - 60%
c it is possible to enhance the Ir setting accuracy (reduced range) or disable thelong-time protection function by using a different long-time rating plug.See the technical appendix "Changing the long-time rating plug".
Thermal memoryc the thermal memory continuously accounts for the amount of heat in the cables,both before and after tripping, whatever the value of the current (presence of anoverload or not). The thermal memory optimises the long-time protection function ofthe circuit breaker by taking into account the temperature rise in the cables.c the thermal memory assumes a cable cooling time of approximately 15 minutes.
Micrologic P Schneider Electric21
Idmtl long-time protection
Idmtl ProtectionLong-time current setting Ir and Idmtl tripping delay tr
Micrologic control unit Accuracy 5.0 P, 6.0 P and 7.0 Pcurrent setting Ir = In (*) x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1tripping between 1.05 and 1.20 Ir other ranges or disable by changing rating plug
time setting 0,5 1 2 4 8 12 16 20 24
DTtime delay (s) tr at 1.5 x Ir 0 to - 20% 0.53 1 2 4 8 12 16 20 24
tr at 6 x Ir 0 to - 20% 0.53 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.53 1 2 4 8 12 16 20 24tr at 10 x Ir 0 to - 20% 0.53 1 2 4 8 12 16 20 24
SITtime delay (s) tr at 1.5 x Ir 0 to - 30% 1.9 3.8 7.6 15.2 30.4 45.5 60.7 75.8 91
tr at 6 x Ir 0 to - 20% 0.5 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (1) 0.88 1.77 3.54 7.08 10.6 14.16 17.7 21.2tr at 10 x Ir 0 to - 20% 0.7 (2) 0.8 1.43 2.86 5.73 8.59 11.46 14.33 17.19
VITtime delay (s) tr at 1.5 x Ir 0 to - 30% 3.6 7.2 14.4 28.8 57.7 86.5 115.4 144.2 173.1
tr at 6 x Ir 0 to - 20% 0.5 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (1) 0.81 1.63 3.26 6.52 9.8 13.1 16.34 19.61tr at 10 x Ir 0 to - 20% 0.7 (2) 0.75 1.14 2.28 4.57 6.86 9.13 11.42 13.70
EITtime delay (s) tr at 1.5 x Ir 0 to - 30% 12.5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0 to - 20% 0.7 (1) 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6tr at 10 x Ir 0 to - 20% 0.7 (2) 0.7 (1) 0.7 (1) 1.41 2.82 4.24 5.45 7.06 8.48
HVFtime delay (s) tr at 1.5 x Ir 0 to - 30% 164.5 329 658 1316 2632 3950 5265 6581 7900
tr at 6 x Ir 0 to - 20% 0.7 (1) 1 2 4 8 12 16 20 24tr at 7.2 x Ir 0 to - 20% 0.7 (2) 0.7 (1) 1.1 (1) 1.42 3.85 5.78 7.71 9.64 11.57tr at 10 x Ir 0 to - 20% 0.7 (2) 0.7 (2) 0.7 (1) 0.7 (1) 1.02 1.53 2.04 2.56 3.07
(*) In: circuit breaker rating(1) 0 to - 40%(2) 0 to - 60%
c these curves with different slopes are used to improve:v discrimination with fuses positioned upstream (HV) and/or downstreamv protection for certain types of loads
c five types of curves are available:v DT: definite time curvev SIT: standard inverse time curve (I0.5t)v VIT: very inverse time curve (It)v EIT: extremely inverse time curve (I2t)v HVF: compatible with high-voltage fuses (I4t).
c neutral protectionOverload protection (long time) for the neutral is disabled if the Idmtl protectionfunction is selected. However, the short-circuit protection (short time andinstantaneous) remains operational.
c intermittent overloadsAs long as the Micrologic P control unit remains supplied with power, the effects ofintermittent overloads on cables are calculated. If power is cut, temperature rise incables is not calculated.
c circuit-breaker thermal limitFor certain settings, the Idmtl curves may be limited by the I2t curve when thetripping delay tr is set to 24 seconds or by its thermal memory. The maximum I2tcurve remains active for the phases and the neutral even when the Idmtl curves areactivated.
Micrologic P Schneider Electric22
Overview of functions Current protectionShort-time and instantaneousprotection
For the default values, the setting ranges,increment steps and setting accuracies,see the technical appendix.
Short-time protectionc the short-time protection function protects the distribution system againstimpedant short-circuitsc the short-time tripping delay and the I2t ON and I2t OFF options can be used toensure discrimination with a downstream circuit breakerc this function carries out true rms measurements.
c use of I2t curves with short-time protection:v I2t OFF selected: the protection function implements a constant time curvev I2t ON selected: the protection function implements an I2t inverse-time curve up to10 Ir. Above 10 Ir, the time curve is constant.
c zone selective interlocking (ZSI)The short-time and ground-fault protection functions enable time discrimination bydelaying the upstream devices to provide the downstream devices the timerequired to clear the fault. Zone selective interlocking can be used to obtain totaldiscrimination between circuit breakers using external wiring.
c intermittent faults are taken into account by Micrologic P and may lead to shortertripping times than those set.
Short-time pickup Isd and tripping delay tsd
Micrologic control unit 5.0 P, 6.0 P and 7.0 Ppickup Isd = Ir x ... accuracy ± 10 % 1.5 2 2.5 3 4 5 6 8 10time delay (ms) setting I2t Off 0 0.1 0.2 0.3 0.4at 10 Ir I2t On 0.1 0.2 0.3 0.4I2t On or tsd (max resettable time) 20 80 140 230 350I2t Off tsd (max break time) 80 140 200 320 500
For the characteristics and external wiringof the zone selective interlocking function,see the technical appendix on "Zoneselective interlocking".
Instantaneous protection
c the instantaneous-protection function protects the distribution system againstsolid short-circuits. Contrary to the short-time protection function, the tripping delayfor instantaneous protection is not adjustable. The tripping order is sent to thecircuit breaker as soon as current exceeds the set value, with a fixed time delay of20 milliseconds.c this function carries out true rms measurements.
Instantaneous pickup Ii
Micrologic control unit 5.0 P, 6.0 P and 7.0 Ppickup Ii = In (*) x ... accuracy ± 10 % 2 3 4 6 8 10 12 15 OFF
(*) In: circuit-breaker rating
c circuit breakers have two types of instantaneous protection:v adjustable instantaneous protection Iiv self-protection.Depending on the circuit breaker, the OFF position corresponds tothe self-protection pickup.
If the "without long-time protection" plug is used and the long-time protectionfunction is disabled, the short-time pickup Isd is automatically multiplied by Ininstead of Ir as is the standard case.
Micrologic P Schneider Electric23
Three-pole circuit breakersProtection of the neutral is possible on a three-pole circuit breaker by connectingan external sensor.
Settings are made using the and buttons on the control unit.
For the default values, the setting ranges,increment steps and setting accuracies,see the technical appendix.
Neutral protection
Micrologic control unit 5.0 P, 6.0 P and 7.0 PSetting OFF N/2 N 1.6xN
Type of neutral DescriptionNo neutral protection The distribution system does not require protection
of the neutral conductor.Half neutral protection The cross-sectional area of the neutral conductor is half that
of the phase conductors.c the long-time current setting Ir for the neutral is equal tohalf the setting valuec the short-time pickup Isd for the neutral is equal to halfthe setting valuec the instantaneous pickup Ii for the neutral is equal tothe setting valuec for ground-fault protection (Micrologic 6.0 P), pickup Ig forthe neutral is equal to the setting value.
Full neutral protection The cross-sectional area of the neutral conductor is equal tothat of the phase conductors.c the long-time current setting Ir for the neutral is equal tothe setting valuec the short-time pickup Isd for the neutral is equal to thesetting valuec the instantaneous pickup Ii for the neutral is equal to thesetting valuec for ground-fault protection (Micrologic 6.0 P), pickup Ig forthe neutral is equal to the setting value.
Oversized neutral protection In installations with a high level of third-order harmoniccurrents (or multiples thereof), the current in the neutralconductor may exceed that of the phase currents understeady-state conditionsc the long-time current setting Ir for the neutral is 1.6 timesthat of the setting valuec the short-time pickup Isd for the neutral is 1.6 times that ofthe setting value, but may not exceed 10 In to limittransients and self-protect the installationc the instantaneous pickup Ii for the neutral is equal tothe setting valuec for ground-fault protection (Micrologic 6.0 P), pickup Ig forthe neutral is equal to the setting value.
Micrologic control unit 5.0 P, 6.0 P and 7.0 PSetting OFF N/2 N
Type of neutral DescriptionNo neutral protection The distribution system does not require protection of the
neutral conductor.Half neutral protection The cross-sectional area of the neutral conductor is half that
of the phase conductors.c the long-time current setting Ir for the neutral is equal tohalf the setting valuec the short-time pickup Isd for the neutral is equal to halfthe setting valuec the instantaneous pickup Ii for the neutral is equal to thesetting value
Full neutral protection The cross-sectional area of the neutral conductor is equalto that of the phase conductors.c the long-time current setting Ir for the neutral is equal tothe setting valuec the short-time pickup Isd for the neutral is equal to thesetting valuec the instantaneous pickup Ii for the neutral is equal tothe setting value.
Four-pole circuit breakersThe initial protection setting is made using the dial on the neutral pole of the circuitbreaker.
The and buttons on the control unit may then be used for a more precisesetting. The dial setting constitutes the upper limit for adjustments using the keypad.
Micrologic P Schneider Electric24
Current protectionGround-fault and earth-leakageprotection
Ground-fault protection on Micrologic 6.0 Pc an ground fault in the protection conductors can provoke local temperature rise atthe site of the fault or in the conductors. The purpose of the ground-fault protectionfunction is to eliminate this type of fault.c there are two types of ground-fault protection.
For the default values, the setting ranges,increment steps and setting accuracies,see the technical appendix.
Type DescriptionResidual c the function determines the zero-phase sequence
current, i.e. the vector sum of the phase and neutralcurrents (depending on the type of installation).
Source Ground Return c using a special external sensor, this function directlymeasures the fault current returning to the transformervia the earth cablec it detects faults both upstream and downstream ofthe circuit breakerc the maximum distance between the sensor and thecircuit breaker is ten metres.
c ground-fault and neutral protection are independent and can therefore becombined.
Ground-fault pickup Ig and tripping delay tgThe pickup and tripping-delay values can be set independently and are identical forboth the residual and "source ground return" ground-fault protection functions.
Micrologic control unit 6.0 Ppickup Ig = In (*) x ... accuracy ± 10 % A B C D E F G H J
In ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1400 A < In ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In > 1200 A 500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A
time delay (ms) settings I2t Off 0 0.1 0.2 0.3 0.4at In or 1200 A I2t On 0.1 0.2 0.3 0.4I2t On or tg (max resettable time) 20 80 140 230 350I2t Off tg (max. break time) 80 140 200 320 500
Earth-leakage protection on sur Micrologic 7.0 P
c the earth-leakage protection function primarily protects people against indirectcontact because an earth-leakage current can provoke an increase in the potentialof the exposed conductive parts. The earth-leakage pickup value I∆n is displayeddirectly in amperes and the tripping delay follows a constant-time curve.c an external rectangular sensor is required for this functionc this function is inoperative if the long-time rating plug is not installedv d Protected against nuisance trippingv k DC-component withstand class A up to 10 A.c if the optional external voltage-measurement input is used, a 24 V DC externalpower supply must be connected to Micrologic P (terminals F1-, F2+).
Pickup value I∆n and tripping delay ∆t
Micrologic control unit 7.0 Ppickup (A) I∆n accuracy 0 to - 20 % 0.5 1 2 3 5 7 10 20 30time delay (ms)settings ∆t (max resettable time) 60 140 230 350 800
∆t (max. break time) 140 200 320 500 1000
Overview of functions
(*) In: circuit-breaker rating
Micrologic P Schneider Electric25
I t Alarm, current unbalance,maximum current
Operating principleprotection tripped by a maximum value
E71
740A
For the pickup and dropout thresholds andtime delays, see the technical appendix.
1: pickup threshold2: pickup time delay3: dropout threshold4: dropout time delay
c for protection tripped by a maximum value, it is possible to set:v a pickup threshold (1) that activates an alarm, a contact and/or trippingv a pickup time delay (2) that steps in when the pickup threshold (1) is reachedv a dropout threshold (3) corresponding to deactivation of the alarm and/or contactv a dropout time delay (4) that steps in when the dropout threshold (3) is reachedc the dropout threshold is always less than or equal to the pickup threshold.
I ttttt Alarmc the alarm function is tripped by the rms value of an earth-leakage currentc this alarm signals an earth-leakage current under the pickup value and does notproduce circuit-breaker tripping.
Current-unbalance protection I unbalc this protection is activated by an adjustable level of unbalance between the RMSvalues of the three phase currents.
E71
749A c from:v I avg is the average value of the rms currents of thethree phases
I avg =I1 + I2 + I3
3
I unbal =
v E max is the maximum difference between thecurrent of each phase and I avgc Micrologic P uses the two values above to calculatethe current unbalance:
I
I
1
0 I t Alarm, I unbal,I max
t
3
24
0
I
I1 I2 I3
I avgE max
Maximum-current protection per phase maxc protection values may be set for each of the following currents:v 1 max: maximum current on phase 1v 2 max: maximum current on phase 2v 3 max: maximum current on phase 3v N max: maximum current in the neutral
c this function calculates the rms demand value of the current for the given phase( 1, 2, 3) or the neutral ( N), over a sliding time interval.
The time interval is the same as that for the calculation of the demand currents inthe "Metering" menu.
Settings are made in the "Metering setup" menu.
Note:IN max protection does not take into account the neutral-protection setting (N, N/2, 1.6xN, OFF).
IIII
I I I
E maxI avg
Micrologic P Schneider Electric26
Voltage protectionMinimum voltage, maximum voltage,voltage unbalance
For the pickup and dropout thresholds andtime delays, see the technical appendix.
Operating principleprotection trippedby a minimum value
1: pickup threshold2: pickup time delay3: dropout threshold4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:v a pickup threshold (1) that activates an alarm, a contact and/or trippingv a pickup time delay (2) that steps in when the pickup threshold (1) is reachedv a dropout threshold (3) corresponding to deactivation of the alarm and/or contactv a dropout time delay (4) that steps in when the dropout threshold (3) is reachedc for protection tripped by a minimum value, the dropout threshold is always greaterthan or equal to the pickup thresholdc for protection tripped by a maximum value, the dropout threshold is always lessthan or equal to the pickup thresholdc if both the minimum and maximum protection functions are activated at the sametime, the minimum threshold is automatically limited to the value of the maximumand vice versa.
Minimum-voltage protection U minc this function calculates the minimum rms value of the three phase-to-phasevoltagesc protection is activated when at least one of the three phase-to-phase voltages(U12, U23, U31) is below the threshold set by the userc this protection function does not detect phase failure.
Maximum-voltage protection U maxc this function calculates the maximum rms value of the three phase-to-phasevoltagesc protection is activated when the three phase-to-phase voltages (U12, U23, U31)are simultaneously above the threshold set by the user.
Voltage-unbalance protection U unbalThis protection is activated by an adjustable level of unbalance between the rmsvalues of the three phase-to-phase voltages.This function calculates the rms value of the unbalance between the three phase-to-phase voltages.
E71
742A c from:
v U avg is the average value of the rms voltages of thethree phases
v E max: is the maximum difference between thevoltage of each phase and U avgc Micrologic P uses the two values above to calculatethe voltage unbalance:
U unbal =
U avg =U12 + U23 + U31
3
Overview of functions
E60
489A
1
0 U min
t
3
24
protection trippedby a maximum value
E71
741A
1
0 U maxU unbal.
t
3
24
0
U
U12 U23 U31
U avgE max
E maxU avg
If the voltage protection functions areactivated and the voltage measurementinputs are still energised, it is impossible toreset and close the circuit breaker.
Micrologic P Schneider Electric27
1
0 F min
t
3
24
Other protectionReverse power, min. frequency,max. frequency, phase rotation
For the pickup and dropout thresholds andtime delays, see the technical appendix.
Operating principleprotection trippedby a minimum value
E60
487A
1: pickup threshold2: pickup time delay3: dropout threshold4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:v a pickup threshold (1) that activates an alarm, a contact and/or trippingv a pickup time delay (2) that steps in when the pickup threshold (1) is reachedv a dropout threshold (3) corresponding to deactivation of the alarm and/or contactv a dropout time delay (4) that steps in when the dropout threshold (3) is reachedc for protection tripped by a minimum value, the dropout threshold is always greaterthan or equal to the pickup thresholdc for protection tripped by a maximum value, the dropout threshold is always lessthan or equal to the pickup thresholdc if both the minimum and maximum protection functions are activated at the sametime, the minimum threshold is automatically limited to the value of the maximumand vice versa.
Reverse-power protection rP maxc this function calculates the value of the total active power on the three phasesc the function is activated when the total active power of the three phases flows inthe direction opposite that set by the user is greater than the pickup threshold (1)for a time greater than the time delay (2).
Note:The direction of flow is set by the user in the "Power sign" section of the "Micrologic setup"menu under "History, maintenance and settings".c + corresponds to the normal direction of flow, i.e. from the top terminals on the circuit breakerto the bottom terminalsc - is the opposite.
Minimum and maximum-frequency protection F min.and F maxThese functions monitor the value of the frequency on the distribution system.
Phase-rotation alarmThis alarm is activated if two of the three phases are inverted.
Note:The alarm is activated following a fixed 300-millisecond time delay. If one of the phases isabsent, the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot beactivated.
E60
486A
1
0 F maxrP max
t
3
24
protection trippedby a maximum value
If the voltage protection functions areactivated and the voltage measurementinputs are still energised, it is impossible toreset and close the circuit breaker.
Micrologic P Schneider Electric28
Overview of functions Load sheddingand reconnection
For the pickup and dropout thresholds andtime delays, see the technical appendix.
Load shedding and reconnection depending on currentThe pickup curve for load shedding and reconnection depending on current isparallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plugis installed, the load shedding/reconnection function based on current cannot beactivated.
c I2t protection: the neutral is taken into accountc Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarmlinked to an M2C or M6C contact (disconnection and reconnection of non-priorityloads).
The load-shedding and reconnection function is determined by thresholds and timedelays.
1: pickup threshold2: pickup time delay3: dropout threshold4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
Load shedding and reconnection depending on powerLoad shedding and reconnection depending on power calculates the total activepower on the three phases. This function does not trip the circuit breaker, but canbe used to set off an alarm linked to an M2C or M6C contact (disconnection andreconnection of non-priority loads).The load-shedding and reconnection function is determined by thresholds and timedelays.
E60
249B
1: pickup threshold2: pickup time delay3: dropout threshold4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
E71
754A
3
0 I
t
1
4
2
Long-timeprotectioncurve
3
0 P
t
1
42
Micrologic P Schneider Electric29
MeasurementsCurrent and voltage
For the setting ranges and measurementaccuracies, see the technical appendix.
To display the phase-to-neutral voltages,select the "3Φ 4w 4CT" option in "Systemtype" in the "Metering setup" menu under"History, maintenance and setup".
Instantaneous currentMicrologic P control units offer two, non-exclusive measurement possibilities.
c on the bargraph display on the main screen
The instantaneous current of the most heavily loaded phase is automaticallydisplayed in amperes for phases 1, 2, 3 and the neutral (depending on the neutralprotection settings). The bargraph indicates the percent load of thethree phases.
c in the I inst. section of the instantaneous currentsv display in amperes of the instantaneous currents I (rms) on phases I1, I2 and I3and the neutral current IN, the ground-fault current Ig (Micrologic 6.0 P), theearth-leakage current I∆n (Micrologic 7.0 P)v the maximum instantaneous currents are displayed and stored in memoryv the stored maximums can be reset at any time.
Demand currentc display of the demand current on phases 1, 2, 3 and the neutral N(depending on the type of distribution system)c selection of the demand calculation methodc display of the interval over which the value is calculatedc the maximum demand values are displayed and stored in memoryc the stored maximums can be reset at any time.
Note:The calculation method, the type of calculation window (fixed or sliding) and its durationmay be set in the "Metering setup" menu under "History, maintenance and setup".
Phase-to-neutral and phase-to-phase voltagesMicrologic P offers different voltage measurements:c phase-to-phase voltages (rms) between phases U12, U23 and U31,displayed in volts
c phase-to-neutral voltages (rms) between the phases and the neutral V1N, V2Nand V3N, displayed in volts.
Average voltageAverage Uavg of the instantaneous voltages between phases U12, U23 and U31.
Phase rotationDisplays the phase sequence.
Voltage unbalanceDisplay of the unbalance Uunbal between the three phase-to-phase voltages,displayed as a percentage.
c from:v U avg is the average value of the rms voltages of thethree phases
v E max is the maximum difference between thevoltage of each phase and U avgc Micrologic P uses the two values above to calculatethe voltage unbalance
U unbal =
U avg =U12 + U23 + U31
3
E71
742A
0
U
U12 U23 U31
U avgE max
E maxU avg
I I II
Micrologic P Schneider Electric30
MeasurementsPower, energy and frequency
For the setting ranges and measurementaccuracies, see the technical appendix.
Instantaneous power and power factorMicrologic P offers a number of different measurements.
c total power measurements:v instantaneous active power P in kWv instantaneous reactive power Q in kvarv instantaneous apparent power S in kVA
c measurement of the power factor PF.
Demand powerc display of the demand values for the active power P, reactive power Q andapparent power Sc selection of the demand calculation methodc display of the interval over which the value is calculatedc the maximum demand values are displayed and stored in memoryc the stored maximums can be reset at at any time.
Note:c the calculation method, the type of calculation window (fixed or sliding) and its duration maybe set in the "Metering setup" menu under "History, maintenance and setup".c the synchronisation function (Synchro.Com) is available only with the COM communicationoption; with this function, the demand power is determined on the basis of a signalsynchronised by the communication module.c these settings apply to all demand powers (active power P, reactive power Q and apparentpower S). If the settings are modified, the demand values are systematically recalculated.
EnergyMicrologic P offers a number of different measurements:
c total energy:v total active energy E.P in kWhv total reactive energy E.Q in kvarhv total apparent energy E.S in kVAh
c energy consumed (Energy in), positively incremented:v active energy E.P in kWhv reactive energy E.Q in kvarh
c energy supplied (Energy out), negatively incremented:v active energy E.P in kWhv reactive energy E.Q in kvarh
c energy values can be reset.
Note:c the Energy in and Energy out values are incremented according to the power sign setin the "Metering setup" menu under "History, maintenance and setup".c as standard, the total calculated energy values are "absolute total values".They represent the sum of the energy in and out values:v EP = Σ EP in + Σ EP outv EQ = Σ EQ in + Σ EQ outc as an option (access exclusively via the COM communications option), energy can becalculated algebraically:v EP = Σ EP in - Σ EP outv EQ = Σ EQ in - Σ EQ outThese values are called "signed" energies.
FrequencyThe frequency of the distribution system is displayed in Hz.
Overview of functions
Micrologic P Schneider Electric31
For information on the communicationsoption and the portable test kit, see therespective user guides.
Alarms
c an alarm may be viewed using:v the "Alarm history" menuv the COM communications optionv the portable test kit.
c the commands in the "Protection" menu are used to attribute a specific operatingmode to each of the protection functions:v OFF: protection disabledv Alarm: the function issues an alarm, but does not trip the circuit breakerv Trip + Alarm: the function issues an alarm and trips the circuit breaker.
c the protection functions against overloads (long time), short circuits (short timeand instantaneous) and ground faults (ground-fault and earth-leakage currents)automatically result in tripping and cannot be deactivated (Trip mode only).
c the "I t Alarm" and phase rotation alarms can be set exclusively to OFF or Alarmmode.
c the other protection functions for current, voltage, power and frequency may beset to any of the three modes, OFF, Alarm or Trip + Alarm.
c the load shedding and reconnection function may be set to ON or OFF.
c the resettable alarms linked to device tripping are activated when the Ir, Isd/Iior I t thresholds are overrun.
The Ir alarm is reset one second after tripping. The Isd/Ii and t alarms are reset bypressing the button.
Current protection Off Alarm Trip + AlarmIr cIsd / li cI t c
c delayed alarms are activated when the pickup and dropout thresholds areoverrun and the corresponding time delays have expired.
c history loggingv Alarm mode: as soon as a given protection threshold is overrun, an alarm isrecorded in the "Alarm history"v Trip mode: as soon as a given protection threshold is overrun, the circuit breakertrips and the fault is recorded in the "Trip history".
c the "Protection setup" menu under "History, maintenance and setup" is used toenable or disable the Trip mode that is displayed in the protection-setting screens.On leaving the factory, the protection functions are set to Alarm mode.
c the "M2C / M6C contacts" menu under "History, maintenance and setup" is usedto link an M2C or M6C contact to an alarm. M2C and M6C contacts may not beused together. They require a 24 V external power supply.
c the COM communications module can be used to transmit alarms to asupervisor.
Current protection Off Alarm Trip + AlarmI t Alarm c cI unbal c c c 1 max c c c 2 max c c c 3 max c c c N max c c cVoltage protection Off Alarm Trip + Alarm
U min c c cU max c c cU unbal c c cOther protection Off Alarm Trip + Alarm
rP max c c cF min c c cF max c c cPhase rotation c cShedding/reconnection Off On
current I c cpower P c c
E71
744B
E71
745B
Different pickup and dropout thresholds
Identical pickup and dropout thresholds
IIII
Dropout
Other alarms
T1
T2
Pickup
Ir, Isd, Ii, I alarms
Pickup /Dropout
Other alarms
T1 T2
Ir, Isd, Ii, I alarms
Micrologic P Schneider Electric32
An alarm is issued if the Alarm or theTrip + Alarm mode was set for the givenprotection function.
Caution!The M2C and M6C contacts require anauxiliary power supply. See the "Powersupply" section in the technical appendix.
Optional M2C and M6C contactsE
6049
2AE
6049
1C
c current protection:v Irv Isdv Iiv I tv I t Alarmv I unbalv 1 maxv 2 maxv 3 maxv N max.
c voltage protection:v U minv U maxv U unbal.
c other protection:v F minv F maxv rP maxv phase rotation.
c available types of contacts:v M2C: up to two contacts maximum, S1 and S2v M6C: up to six contacts maximum, S1 to S6.
c load shedding and reconnection:v current Iv power P.c latching settings:v non-latching contact: the contact remains activated as long as the fault thatcaused the alarm has not been clearedv latching contact: the contact remains activated until it is reset ("Reset menu")v time-delay contact: the contact remains activated for the duration of an adjustabletime delay or until it is reset ("Reset menu").v locked to 1: the contact is forced to 1 for an automation testv locked to 0: the contact is forced to 0 for an automation test.
c contact operating diagram for long-time protection
471
S1
474
484
S2
474
Wiring diagram for M2C contacts.
Wiring diagram for M6C contacts
IIII
E71
914A
E60
494B
c contact operating diagram for short-time, instantaneous and ground-faultprotection
delay 1 to 360 s
Isd, Ii or Ig pickup
Press
Internal alarm
Non-latching contact
only after pressingReset possibleend of delayReset possible before
contactLatchingcontactTime-delay
Isd, Ii or Ig LED
tsd or tg delay
c contact operating diagram for the other protection functions
Pickup
Dropout
Internal alarm
Non-latching contact
only after T2Reset possibleend of delayReset possible before
contactLatchingcontactTime-delay
delay 1 to 360 s
E60
493B
Press
Internal alarm
t
T1
Non-latching contact
only after T2 = 1 sReset possibleLatching
contact
Time-delaycontact
T2 = 1 sec
delay 1 to 360 s
Ir LED
Ir threshold tr delay
end of delayReset possible before
S1
31 5
42 6
S3
S2
97 11
108 12
S4
24V 0V
1917 21 23 25
S5
14 16 18
S6
20 22 24
ComQ1 Q2 Q3
Overview of functions
Micrologic P Schneider Electric33
Trip historyc the trip history is the means to display at any time the parameters measuredduring the last ten trips.c for each trip, the following parameters are recorded:v tripping causev trip thresholdv interrupted currents in amperes (only if an external power supply is present) for Ir,Isd/Ii, Ig or I∆n tripsv datev time (hours, minutes and seconds).
Alarm historyc the alarm history is the means to display at any time the parameters measuredduring the last ten alarms.c for each alarm, the following parameters are recorded:v alarm causev alarm thresholdv datev time (hours, minutes and seconds).
Operation counterThis function is available only via the COM communications option.
c Micrologic P:v stores and displays the total number of operations (incremented each time thecircuit breaker opens) since the initial installation of the circuit breakerv stores and displays the total number of operations since the last reset.
Contact wear indicationThis function can be used to:
c determine the condition of the most worn contact in the circuit breaker. A counteris displayed on the screen. The contacts must be inspected each time the counterreaches a hundred mark. The message "Not available or circuit breaker type notdefined" is displayed if the type of circuit breaker has not been defined. In this case,see "Breaker selection" in the "Micrologic setup" menu under "History, maintenanceand setup".
c reset the indicator after changing the main contacts. Reset is also carried out via"Breaker selection" in the "Micrologic setup" menu.
Note:If the control unit is changed, the circuit breaker must be defined again. In this case, see"Breaker selection" in the "Micrologic setup" menu under "History, maintenance andsetup".
Event histories
The interrupted currents are indicated interms of their peak values.
Micrologic P Schneider Electric34
Overview of functions
LED indicator
LEDs and display screens
Signals overrun of thelong-time current setting(1.125 x Ir).
Signals the load level oneach phase as apercentage of Ir.
E60
444A
Overload bargraph onthe main screen
off
Alarm
E60
495A
Micrologic 5.0 P
4260AN 1 2 3
100
50
0
Fault-trip indicationsc control-unit statusThe circuit breaker has tripped.The control unit may or may not have an external power supply.The voltage measurement inputs may be connected upstream or downstream.
The procedure required to reclose thecircuit-breaker following a fault trip ispresented in the circuit-breaker user guide.
Concerning the presence or absence of anexternal power supply, see the "Powersupply" section in the technical appendix.
Caution!The battery maintains the trip indications.If no indications are displayed, check thebattery.
v control unit without anexternal power supplyand with voltagemeasurement inputconnected downstream
v control unit with anexternal power supplyand with voltagemeasurement inputconnected upstream
E60
298A
Micrologic 5.0 P
E71
600B
Micrologic 5.0 P
Trip
02:04:0422/11/1999
Umin 100V
Resetby test/resetbutton
A LED signals the type offault (Ir, Isd, Ii, Ig, I∆n orAp).
The type of fault issignalled by a LED andon the graphic display.
Micrologic P Schneider Electric35
The self-protection function (excessivetemperature, fault detected in ASIC powersupply or instantaneous self-protection builtinto the device) trips the circuit breaker andturns the Ap LED on.
A number of simultaneous causes mayresult in tripping. For example, a short-circuit and a distribution-system voltageunder a set value.The LED signalling the last faultchronologically is the only one to remainON. E.g., the Ap LED may signal a voltagedrop under a set value where the voltagedrop was caused by a short-circuit.
c fault-trip LEDsc the LEDs indicate the type of fault that tripped the circuit breakerc the LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n andAp LEDs)c when activated, a LED remains ON until it is locally reset.
E60
337B
E60
338B
Signals tripping followingoverrun of the long-timecurrent setting Ir.
Signals tripping followingoverrun of the short-timepickup Isd or theinstantaneous pickup Ii.
c Ir LED c Isd, Ii LED
c Ig, I∆n LED c Ap LED
E60
339B
E60
340B
Signals tripping followingoverrun of the ground-fault pickup Ig or theearth-leakage pickup I∆n.
Signals tripping due to:c self-protection function:v temperaturev ASIC power supplyv instantaneous pickup for circuit-breaker selfprotectionc protection functions:v current unbalance I unbalv maximum current 1 max, 2 max, 3 max, N max;v voltage unbalance U unbalv maximum voltage U maxv minimum voltage U minv reverse power rP maxv maximum frequency F maxv minimum frequency F min.
I I II
c LEDs on buttons to access the menusThe activated LED indicates the menu for which the screen is displayed:v "Metering"v "History, maintenance and setup"v "Protection".
E60
485A
Micrologic 5.0 P Micrologic 5.0 P
Micrologic 5.0 P Micrologic 5.0 P
LEDs and display screens
Micrologic P Schneider Electric36
Micrologic 5.0 P
COM module onchassis (optional)
COM module on circuit breaker
(Infra Red)
Micrologic Pcontrol unit
Circuit breaker
Chassis
COM communications optionE
7174
8A Communication optionsDigipact and ModBus are the indispensable elements when integrating Micrologic Pin the Digivision and SMS Powerlogic installation-management systems whichcommunicate via the BatiBus and ModBus protocols.External gateways are available for communication over other networks, includingProfiBus, Ethernet, etc.
The communications option makes possible the following remote functions:c device identification:v addressv device typev control-unit typev type of long-time rating plug
c settings:v reading of the dial settingsv fine adjustments within the range determined by the dialv protection and alarm settingsv setup of the M2C / M6C contacts.
Operating and maintenance aidsc protection and alarm values:v standardv set.
c measurement values:v currentsv voltages, frequencies, power, etc.
c fault values:v fault typev interrupted current.
c histories and logs:v trip historyv alarm historyv event history.
c indicators:v contact wear, counters, etc.v maintenance register.
Overview of functions
Micrologic P Schneider Electric37
Micrologic P Schneider Electric38
Setup
Select an alarm
Note:An alarm may be selected if the "Alarm" or "Trip + Alarm" mode was selected during setup ofthe given protection function, in the "Protection" menu.
Set up each contactc select the latching mode
Select the command
Setting up the optionalM2C / M6C contacts
Select the command
E71
601A
S1S2
Alarmtype
E60
146A
S2
Ir
E60
226A
S2
IrE
7160
2A
E71
603A
E71
604A
S1S2
SetupM2C / M6C S2
latchingcontact
Mode
S2Mode
latchingcontact
ContactsM2C / M6C
Alarmtype
ContactsM2C / M6C
Setup
then then
Select a contact. Select an alarm. Confirm.
then thenSelect a contact. Select a latching mode:
c non-latchingc latchingc time-delayc locked to 1c locked to 0.
Confirm.
Micrologic P Schneider Electric39
c set the time delay for time-delay latching
Reset the contacts to 0
E71
605A
360s
time delay
S2Mode
Delay
E71
606A
350s
time delay
S2Mode
Delay
E71
607A
350s
time delay
S2Mode
DelayE
6044
2A
E60
389A
S1 0
M2C / M6C
Reset (- / +)
S2 0S1 1
M2C / M6C
Reset (- / +)
S2 1
Reset the contacts to 0… or cancel the reset,then confirm.
Select the command
M2C / M6CContacts
Reset
then
Select the time delay. Adjust. Confirm.
then
Micrologic P Schneider Electric40
Setup
Set the date and timec enter the date and time for time-stamping purposes in the trip and alarmhistories.
Setting up the Micrologiccontrol unit
E71
608A
Language
Deutsch
English US
English UK
Espanol
FrançaisE
7193
8B
English UK
Espanol
Français
Italiano
LanguageE
7161
0B
E71
611B
E71
612B
Time
Date
01 / 01 / 2000
18 : 30 : 03
Time
Date
01 / 01 / 2000
18 : 30 : 03
Time
Date
01 / 01 / 2000
18 : 30 : 03
Select the date. Enter the day. Enter the month.
If the time is set via a communicationsmodule, any previous manual setting isautomatically erased.
Prior to setting up the protection functions or carrying out measurements,the following operations are required:c selection of the display languagec entry of the date and timec entry of the circuit-breaker typec entry the power signc selection of the transformation ratio between the primary and secondarywindings if an auxiliary voltage transformer is installedc entry of the rated frequency.
Select the display languageSelect the command
Micrologicsetup
Language
Select the command
Micrologicsetup
Date / time
then then then
c the resolution of the time setting is 20 ms.
Select.
1. Return to the mainscreen by pressing anyof the three buttons
or press the button
followed by any of thethree buttons
Confirm.
2. Select the "History,maintenance and setup"menu by pressing
3. Select the "Micrologicsetup" menu by movingthe cursor up on the firstmenu. Move the cursordown on the third menuand confirmby pressing
4. Select the "Language"menu by moving thecursor up on the firstmenu.Confirm by pressing
To return to English
Micrologic P Schneider Electric41
NT08N
Circuit breaker
Standard
0 3 E 7
type
Breakerselection
Masterpact
UL
P Logicxxxxxx
E89
321A
E89
322A
E89
323A
The circuit-breaker code is required toidentify the device and activate the contact-wear counter.
Note this code if the control unitmust be changed (example 03E7).
Enter this code when setting up a newcontrol unit on the circuit breaker.For a new device, the code is set to zero.
When the main circuit-breaker contacts arereplaced, this code must be reset to zero.
Circuit-breaker selection
E89
324A
E89
325A
E89
326A
Choose and confirm. Select the type. Choose and confirm.
E71
613B
E71
614B
Enter the year. Set the time in the samemanner.
Time
Date
01 / 01 / 2000
18 : 30 : 03
Time
Date
01 / 01 / 2000
18 : 30 : 03
Select the command
Micrologicsetup
Breakerselection
then then then
then then then
then then
Select the standard. Choose and confirm. Select the circuit breaker.
NT H1
selection
Circuit breaker
Standard
0 3 E 7
type
Breaker
Masterpact
IEC
P Logicxxxxxx
NT H1
Circuit breaker
Standard
0 3 E 7
type
Breakerselection
Masterpact
IEC
P Logicxxxxxx
630b
Circuit breaker
Standard
0 3 E 7
type
P Logicxxxxxx
Breakerselection
Compact NS
IEC
630b
Circuit breaker
Standard
0 3 E 7
type
P Logicxxxxxx
Breakerselection
Compact NS
IEC
800
Circuit breaker
Standard
0 3 E 7
type
P Logicxxxxxx
Breakerselection
Compact NS
IEC
Date and time are backed up by battery.
If time is not synchronised bythe supervisor via the communicationmodule, a drift of up to one hour per yearmay be observed.
Micrologic P Schneider Electric42
Setup Setting up the Micrologiccontrol unit
If the supply voltage for the control unitexceeds 690 V, an external voltagetransformer must be installed.
To display the true voltage values, enter thetransformation ratio between the primaryand secondary voltages of the transformer.
Note that if Digipact display modules areused, the rated distribution-system voltagemust be entered.
Enter the voltage-transformation ratio
E71
624A
E71
625A
E71
626A
Secondary
Primary
VT ratio
690V
690VSecondary
Primary
VT ratio
690V
690VSecondary
Primary
VT ratio
690V
690V
Select either the:c primary voltagec secondary voltage.
Enter the voltage. Go on to the next setting.
Enter the rated frequency
E71
627A
E71
628A
E71
629ASystem
frequency
400Hz
Systemfrequency
50 - 60Hz
Systemfrequency
50 - 60Hz
Select the command
Micrologicsetup
VT ratio
Select the command
Micrologicsetup
Systemfrequency
If the phase-rotation protection function isactivated, the 400 Hz frequency may not beselected. If the 400 Hz frequency isselected, the phase-rotation protectionfunction is disabled.
Select. Choose. Confirm.
then then
By default, Micrologic P uses P+ for thepower flowing from top to bottom terminals.The selected direction of flow is valid for:c measurement of power and the powerfactorc measurement of energyc load shedding and reconnectiondepending on power.
Select the sign of the power
E71
642B
E71
643B
E71
644B
Select. Choose. Confirm.
Powersign
P-
Powersign
P+
Powersign
P+
Select the commandMicrologicsetupPowersign
Micrologic P Schneider Electric43
Caution!The neutral current IN cannot be measuredwith the "3-phase, 3-wire, 3-CT" and"3-phase, 4-wire, 3-CT" types.
For a 3-pole device, the neutral,if distributed, must be connected toterminal VN of the Micrologic P control unit.
See the "Overview of functions" section forinformation on the available types ofmeasurements.
Setting up the metering functions
Prior to setting up the protection functions or carrying out measurements,the following operations are required:c entry of the system typec selection of the calculation mode for the demand currentc selection of the calculation mode for the demand powerc select the power signc select the sign convention for the power factor measurement.
Select the system typeThe Micrologic P control unit offers three measurement options:c 3 phases, 3 wires, 3 CTs (method using two wattmeters)The currents on phases I1, I2 and I3 are displayed.The current on the neutral IN is not displayed.The phase-to-phase voltages U12, U23 and U31 are displayed.The phase-to-neutral voltages V1N, V2N and V3N are not displayed.c 3 phases, 4 wires, 3 CTs (method using three wattmeters)The currents on phases I1, I2 and I3 are displayed.The current on the neutral IN is not displayed.The phase-to-phase voltages U12, U23 and U31 are displayed.The phase-to-neutral voltages V1N, V2N and V3N are displayed.c 3 phases, 4 wires, 4 CTs (method using three wattmeters)The currents on phases I1, I2 and I3 are displayed.The current on the neutral IN is displayed.The phase-to-phase voltages U12, U23 and U31 are displayed.The phase-to-neutral voltages V1N, V2N and V3N are displayed.Note:It is advised not to use the "3-phase, 4-wire, 4-CT" type of measurement unless the neutral iseffectively connected to the control unit (four-pole circuit breaker with an external voltage-measurement input).
E71
630A
E71
631A
E71
632A
Select. Choose. Confirm.
3Φ 4w3CT
Systemtype
3Φ 3w3CT
Systemtype
3Φ 3w3CT
Systemtype
Select the calculation method for demand current
E71
945C
E89
200C
E89
201C
Select. Adjust. Confirm.
15 min
blockinterval
Calculationmethod
Currentdemand
Window type sliding
thermal
Interval15 min
Calculationmethod
Currentdemand
Window type sliding
blockinterval
Interval15 min
Calculationmethod
Currentdemand
Window type sliding
blockinterval
Interval
Select the command
MeteringsetupSystemtype
Select the commandMeteringsetupCurrentdemand
Thermal method based in I2t calculation.
Micrologic P Schneider Electric44
Setup Setting up the metering functions
E89
213C
E89
214C
E89
215C
Select. Adjust. Confirm.
Calculationmethod
Currentdemand
15 min
blockinterval
Interval
Window type sliding
Calculationmethod
Currentdemand
blockinterval
Interval
Window type sliding
20 min 20 min
Calculationmethod
Currentdemand
blockinterval
Interval
Window type sliding
Select the calculation method for demand power
E89
216C
E89
217C
E89
218C
Select. Choose between:c thermalc block intervalc sync. to comms
Confirm.
Calculationmethod
Powerdemand
Window type sliding
thermal
Interval15 min 15 min
Calculationmethod
Powerdemand
Window type sliding
blockinterval
Interval15 min
Calculationmethod
Powerdemand
Window type sliding
blockinterval
Interval
E89
219C
E89
220C
E89
221C
Select. Choose between fixed orsliding.
Confirm.
15 min
Calculationmethod
Powerdemand
Window type sliding
blockinterval
Interval15 min
Calculationmethod
Powerdemand
blockinterval
Interval
Window type fixed
15 min
Calculationmethod
Powerdemand
blockinterval
Interval
Window type fixed
Select the commandMeteringsetupPowerdemand
The synchronisation function"Synchro.Com" is available only with theCOM communication option. With thisfunction, the demand power is determinedon the basis of a signal synchronised bythe communication module.
Thermal method based on I2t calculation.
Sliding window:power demand is refreshedevery 15 secondes.
Fixed window:power demand is refreshedat the end of the time interval.
Micrologic P Schneider Electric45
Set up the power-factor calculation
E89
226B
E89
227B
Select. Choose between IEEE,IEEE alternate and IEC.
Confirm.
IEEE
Signconvention
E89
225B
Signconvention
IEEE alt.
Select the command
MeteringsetupSignconvention
Signconvention
IEEE alt.
E89
222C
E89
223C
Select. Adjust. Confirm.
E98
320A
15 min
Calculationmethod
Powerdemand
blockinterval
Interval
Window type fixed
20 min
Calculationmethod
Powerdemand
blockinterval
Interval
Window type fixed
20 min
Calculationmethod
Powerdemand
blockinterval
Interval
Window type fixed
See page 87 for the description of powerfactor sign conventions.
Micrologic P Schneider Electric46
Setup
As soon as the Digipact or ModBuscommunications option is connected, thecontrol unit recognises it and displays thetype of module on the graphic screen.Automatic time updates are possible onlywith the ModBus system.
Setting up the COMcommunications option
When a COM communications option is used, it is necessary to:c set up the COM communications optionc authorise remote setting of the Micrologic control unitc authorise remote control of the circuit breaker.
View and set up the communications option
E71
723A
E71
724A
E71
725A
Select an existingparameter.
Adjust. Confirm.
47Baud-rate
Parity
9600
None
ModbusCom
Address
ModbusCom
Parity
9600
None
45Baud-rate
Address
Parity
9600
None
ModbusCom
Address
45Baud-rate
Adjust all the other parameters for the communications option in the same manner.
DIGIPACT MODBUS(read only) (read and set up)
Address 1 - 255 1 - 47Baud rate 9 600 bauds
19 200 baudsParity Even
None
Authorise remote setup of Micrologic
E71
726A
E71
727A
E71
728A
Select existing setting. Choose. Confirm.
No
Accesscode
0 0 0 0
Remotesettings
Accesspermit
Accesscode
Remotesettings
Accesspermit
Yes
0 0 0 0
Accesscode
Remotesettings
Accesspermit
Yes
0 0 0 0
Select the commandCom.setupCom.parameter
then
Select the commandCom.setupRemotesettings
then
The access code is a password that mustbe provided by the supervisor prior toaccessing the Micrologic settings.
Micrologic P Schneider Electric47
It is possible to set circuit-breaker control tolocal only ("Manual") or to local and remote("Auto").
E71
729A
E71
730A
E71
731A
Select the existingaccess code setting.
Enter the first digit. Confirm and proceed inthe same manner for theother digits.
Authorise remote control of the circuit breaker
E71
732A
E71
733A
E71
734A
Press enter. Select Auto or Manual. Confirm.
Accesscode
Remotesettings
Accesspermit
Yes
0 0 0 0
Accesscode
Remotesettings
Accesspermit
Yes
1 0 0 0
Accesscode
Remotesettings
Accesspermit
Yes
1 0 0 0
Manual
Remotecontrol
Auto
Remotecontrol
Auto
Remotecontrol
Select the command
Com.setupRemotecontrol
If the operator does not enter a specificaccess code, the default access code is0000 and is requested by the supervisor.
Micrologic P Schneider Electric48
Fine adjustment of the long-timeI2t, short-time and instantaneoussettings using the keypad
E71
738A
E60
275A
E60
149A
E60
276A
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
998 A
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
998 A
Select a setting. Adjust the value. Confirm.
E60
277A
Adjust the other settingsand confirm.
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
998 A
Select the command.Currentprotection
then
I (A)
E71
657A
No
Yes
Do you wantto save newsettings?
then
Protection settings
When all the settings have been adjusted,quit the screen by pressing one of themenu-access buttons. This saves the newvalues.
Confirm.
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A long-time current setting Ir
long-time tripping delay tr
short-time tripping delay tsdinstantaneous pickup Ii
short-time pickup Isd
E60
277A
I(A)Trip
2000 A
0.2 s
4000 A
1.0 s
998 A
Quit the setting screen.
Micrologic P Schneider Electric49
Fine adjustment of the long-timeIdmtl, short-time andinstantaneous settings usingthe keypad
E71
739A
E71
718A
E60
278A
E60
151A
Yes
Idmtl (A)
No
Change I(A)settings withIdmtl(A)?
Idmtl (A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A
EIT
Idmtl (A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A
VIT
Select yes. Select a setting. Change the setting.
E60
279A
E60
280A
E71
657A
Confirm. Adjust the other settings. Confirm.
Idmtl (A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A
VIT
Idmtl (A)Trip
2000 A
0.2 s
4000 A
1.0 s1000 A
VIT
No
Yes
Do you wantto save newsettings?
Select the commandCurrentprotection
Idmtl (A)
then then
puis
long-time current setting Irlong-time tripping delay tr
short-time tripping delay tsdinstantaneous pickup Ii
short-time pickup Isd
Idmtl protection:DT, SIT, VIT, EIT, HVF
Idmtl (A)Trip
2000 A
0.2 s
4000 A
1.0 s
1000 A
EIT
Micrologic P Schneider Electric50
Protection settings Fine adjustment of the ground-fault and earth-leakage protectionsetting using the keypad
E89
230A
I (A)Trip
0.5s
1200A threshold
time delay
E89
231A
I (A)Trip
0.5s
1200A
E89
232A
E89
234A
E89
233A
I (A)Trip
0.5s
1198A
I (A)Trip
0.5s
1198A
I (A)Trip
0.5s
1198A
E89
235A
E89
236A
I (A)Trip
0.4s
1198A
I (A)Trip
0.4s
1198A
Select the command
When all the settings have been adjusted,quit the screen by pressing one of themenu-access buttons. This saves the newvalues.
E89
236A
I (A)Trip
0.4s
1198A
Currentprotection
I (A)
Select a setting.
Adjust the value. Confirm. Go to the next setting.
Adjust the value. Confirm. Quit the setting screen.
then
then
Micrologic P Schneider Electric51
I
E89
237B
E89
238B
E89
239B
E89
241B
E89
240B
Using the keypad on the control unit
Note:On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dialsetting.
E89
242B
Confirm.Quit the setting screen.
Choose between:c internalc externalc none.
Confirm.
Choose. Confirm.
E71
657A
Do you wantto save newsettings?
no
yes
E89
242B
Select the command
neutral
Currentprotection
(A)
Setting the neutral protection
Type of Possibles choices circuit breakerfour-pole OFF: no neutral protection
N / 2: half neutral protectionN: full neutral protection
three-pole OFF: no neutral protectionN / 2: half neutral protectionN: full neutral protection1.6 x N: oversized neutral protection
Caution!Selection of the CT type determines the"Ineutral" protection in the "Protection"menu.c "none" disables the neutral protection.c "Internal" for a four-pole circuit breakerprovides access to the N/2, N and OFFprotection functions.c "External" for a three-pole circuit breakerprovides access to the N/2, N, 1.6xN andOFF protection functions. Select.
then
Select.
then
Ineutral (A)
OFF
Protection
Neutral CT
Internal
Ineutral (A)
Neutral CT
OFF
Protection
External
Ineutral (A)
OFF
Protection
Neutral CT
External
Ineutral (A)
OFF
Protection
Neutral CT
External
Ineutral (A)
N/2
Protection
Neutral CT
External
N/2
Protection
Ineutral (A)
Neutral CT
External
N/2
Protection
Ineutral (A)
Neutral CT
External
Micrologic P Schneider Electric52
Protection settings
Specific case for It alarmc only the following choices are available:v On: activation of the alarm without fault tripping by the circuit breakerv Off: alarm disabled.
Setting the I , I unbal, max, U min,U max, U unbal, rP max, F min,F max, and phase-rotation protectionfunctions using the keypad
E71
661BSelect the corresponding menu
Currentprotection
Voltageprotection
Otherprotection
I Alarm
I unbal (%)
I1 max (A)
I2 max (A)
IN max (A)
I3 max (A)
Umin (V)
Umax (V)
Uunbal (%)
rPmax (W)
Fmin (Hz)
Fmax (Hz)
Phaserotation
Pick up
Drop out
operating mode(Off, Alarm or Trip)
pickup threshold
pickup time delay
dropout threshold
dropout time delay
type of protection
I
I
Example: Maximum voltage setting (U max)c select Alarm mode
E60
292B
E60
171B
E60
293B
690V
5.00s
690V
0.50s
Umax (V)Off
Pick up
Drop out
Umax (V)
690V
5.00s
690V
0.50s
Alarm
Pick up
Drop out
Umax (V)
690V
5.00s
690V
0.50s
Alarm
Pick up
Drop out
Select the first setting. Choose Off or Alarm. Confirm.
then
E60
292B
E89
294B
690V
5.00s
690V
0.50s
Umax (V)Off
Pick up
Drop out
Umax (V)
690V
Trip
5.00s
Pick up
Select the first setting. Choose Trip.
then
In trip mode, the dropout threshold is equalto the pickup threshold.The dropout time delay is fixed and equalto 1 second.
Micrologic P Schneider Electric53
E89
293B
Umax (V)
690V
Trip
5.00s
Pick up
E89
295B
Umax (V)
Do you wantto set theprotection toTrip mode?
no
yes
Confirm.
then
For protection tripped by a maximum value,the dropout threshold is always less than orequal to the pickup threshold.
For protection tripped by a minimum value,the dropout threshold is always greaterthan or equal to the pickup threshold.
If both the minimum and maximumprotection values are activated, theminimum threshold is automatically limitedto the value of the maximum and viceversa.
E71
665A
E71
666A
E71
667A
Select the existing Adjust. Confirm.dropout threshold setting
Alarm
Umax (V)
690V
Pick up
Drop out
5.00s
690V0.50s
Umax (V)
690V
5.00s
685V0.50s
Pick up
Drop out
Alarm
Umax (V)
690V
5.00s
685V0.50s
Pick up
Drop out
Alarm
E71
668A
E71
657A
Set the other parameters.
Umax (V)
690V
5.00s
685V
0.50s
Pick up
Drop out
Alarm
No
Yes
Do you wantto save newsettings?
then
then
When all the settings have been made,quit the screen by pressing one of themenu-access buttons.This saves the new values.
Confirm
E71
668A
Quit the setting screen.
Umax (V)
690V
5.00s
685V
0.50s
Pick up
Drop out
Alarm
c set the pickup and dropout thresholds and time delays
Micrologic P Schneider Electric54
Setting loadshedding / reconnection
Select the commandLoadshedding I
Loadshedding P
E71
673B
Protection settings
Pick up
Drop out
Loadshedding type of shedding (I or P)
operating mode (On, Off)
pickup time delay
dropout threshold
pickup threshold
dropout time delay
Micrologic P Schneider Electric55
E71
670A
E71
671A
Select the first setting. Select:c Off: load sheddingdisabledc On: load sheddingenabled.
E71
672A
Example: Take load shedding / reconnection depending on power.
Confirm.
E71
674A
E71
675A
E71
676A
Select the existingdropout threshold.
Adjust. Confirm.
E71
677A
E71
657A
Set the other parameters. Confim.
P
1000kW
Off
Pick up
Drop out
3600s
1000kW10s
Loadshedding
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
1000kW10s
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
1000kW10s
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
980kW10s
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
985kW10s
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
985kW10s
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
985kW
10s
No
Yes
Do you wantto save newsettings?
then
then
When all the settings have been made,quit the screen by pressing one of themenu-access buttons.This saves the new values.
E71
677A
Quit the setting screen.
Pick up
Drop out
Loadshedding P
1000kW
On
3600s
985kW
10s
then
Micrologic P Schneider Electric56
Metering Current measurements
Continuous current measurementThe bargraph displays the value in amperes of the most heavily loaded phase.
E60
184A
E60
185A
E60
187A
Measure an instantaneous-current valuec measure the instantaneous currents
E60
188A
E60
189A
Select. View.
Only the measurements for the phase(1, 2, 3) and neutral currents are displayedon the main screen.
The neutral current is displayed if theneutral CT is set to internal or external(see "Ineutral (A)" settings in the "Currentprotection" menu).
4260A1 2 3
100
50
0
3850A1 2 3
100
50
0
3410A1 2 3
100
50
0
The and buttons may be used to display the currents on the threephases. If the operator no longer uses the buttons for a few seconds, the bargraphreturns to the display of the most heavily loaded phase.
Max
I1, I2, I3, IN
inst.I
I3 = 3850 A
I2 = 4260 A
I1 = 3410 A
inst.I
= 13 AI
IN = 200 A
c check the instantaneous-current maximeter
E60
190A
E60
191A
Max
I1, I2, I3, IN
inst.I
I3 =
I2 =
I1 =
instant.Imax
=I
Reset ( - / + )
4700 A
4800 A
5600 A
28 A
IN = 800 A
Select. View.
Select the command
I (A)
then
then
Instant.
Micrologic P Schneider Electric57
c reset the maximeter
E60
192A
E60
191A
Measure a demand-current valuec measure the demand currents
E71
678A
E71
679A
Select. View.
I3 =
I2 =
I1 =
instant.Imax
=I
Reset ( - / + )
0 A
0 A
0 A
0 A
IN = 0 A
Reset the maximeter or... cancel the reset.
I3 =
I2 =
I1 =
instant.Imax
=I
Reset ( - / + )
4700 A
4800 A
5600 A
28 A
IN = 800 A
I1, I2, I3, IN
Max
Demand Demand
I1 = 3950 A
I2 = 4270 A
13min
I3 = 3890 A
IN = 340 A
then
Select the command
I (A)
Demand.
E60
191A
Micrologic P Schneider Electric58
Metering Current measurements
E71
680A
E71
681A
E71
682A
E71
683A
Reset the maximeter or... cancel the reset.
c check the demand-current maximeter
I1, I2, I3, IN
Demand
MaxI1 =
I2 =
I3 =
ImaxDemand
Reset ( - / +)
4020 A
4450 A
4300 A
15min
IN = 600 A
Select. View.
c reset the maximeter
I1 =
I2 =
I3 =
ImaxDemand
Reset ( - / +)
0 A
0 A
0 A
15min
IN = 0 A
I1 =
I2 =
I3 =
ImaxDemand
Reset ( - / +)
4020 A
4450 A
4300 A
15min
IN = 600 A
then
Micrologic P Schneider Electric59
Voltage measurements
E89
257B
E60
193A
Select. View.
Measure the voltage unbalance U unbal
E89
259B
E71
689A
Select. View.
Measure an instantaneous-voltage value (U or V)
U12 =U23 =U31 =
inst.U
400 V404 V401 V
U1N =U2N =U3N =
230 V229 V233 V
Measure the average voltage U avgE
7168
7A
Select. View.
E89
258B
U (V)
Average 3Φ
Instant.
Unbal 3Φ
Phaserotation
402 V
3ΦUavg.
U (V)
Average 3Φ
Instant.
Unbal 3Φ
Phaserotation
1 %
3ΦUunbal
then
then
Select the command
U (V)
then
The phase-to-neutral voltages aredisplayed if the selected system type is3-phase, 4-wire (see page 43).
U (V)
Average 3Φ
Instant.
Unbal 3Φ
Phaserotation
Micrologic P Schneider Electric60
E89
260A
E89
261A
Determine the phase sequence
U (V)
Average 3Φ
Instant.
Unbal 3Φ
Phaserotation
∆Φ : 1, 2, 3
Phaserotation
Select. View.
then
Metering Voltage measurements
Micrologic P Schneider Electric61
Power measurements
To ensure reliable power and power-factormeasurements, the "Power sign" and "Signconvention" parameters must be set.
E71
690A
E60
199B
Select. View.
Measure a demand-power valuec display the demand power
E71
693A
E71
694B
Select. View.
Measure an instantaneous-power value
Measure the power factorE
7169
2A
Select. View.
E71
691A
Pinst.P, Q, S
Powerfactor
Pinst.
(kW)
(kvar)
(kVA)
2180
-650
2280
P
Q
S
Pinst.P, Q, S
Powerfactor
Powerfactor
1.00
P, Q, S
Demand
Max
Demand
(kW)
(kvar)
(kVA)
2350
-820
2640
P
Q
S
Select the command
then
Select the command
P (kW)
then
then
P (kW)
Instant.
Demand
Micrologic P Schneider Electric62
c check the demand-power maximeter
E71
695A
E71
696B
P, Q, S
Demand
Max
PmaxDemand
Reset (- / +)
(kW)
(kvar)
(kVA)
2450
-800
2700
P
Q
S
Select. View.
c reset the maximeter
E71
697B
E71
698B
Reset the maximeter or... cancel the reset.
PmaxDemand
Reset (- / +)
(kW)
(kvar)
(kVA)
0
0
0
P
Q
S
PmaxDemand
Reset (- / +)
(kW)
(kvar)
(kVA)
2450
-800
2700
P
Q
S
then
Metering
Micrologic P Schneider Electric63
Energy measurements
To ensure reliable energy measurements,the "Power sign" and "Sign convention"parameters must be set.
Measure the energy values
E71
699A
Select.
EE total
energyReset
E in
E out
(kWh)Select the energy value to be measured:c total energyc energy in (positive component in the total energy)c energy out (negative component in the total energy).
Select the command
E (kWh)
then
E71
700B
View the total energyvalues.
E total(kWh)
(kvarh)
(kVAh)
20168
-2733
22926
E.P
E.Q
E.S
E71
701B
E in(kWh)
(kvarh)
+21320
-2770
E.P
E.Q
E71
702B
(kWh)
(kvarh)
168
33
E.P
E.Q
E out
Reset the energy values
E71
703A
Select. Select yes or no. If yes, confirm.
E71
704A
E71
705A
EE total
EnergyReset
E in
E out
(kWh) ResetEnergy
No
Yes
Are yousure ?
To resetenergypressenter
then then
View the energyin values.
View the energyout values.
Micrologic P Schneider Electric64
Frequency measurements
E60
110A
F (Hz)
60.0
View.
Select the command
F (Hz)
Metering
Micrologic P Schneider Electric65
Micrologic P Schneider Electric66
Maintenance Resetting fault indications
E60
306B
Caution!If the circuit breaker remains closed andthe Ap LED remains ON after the reset,open the circuit breaker and contact theafter-sales support department.
The fault indication is maintained until it is reset on the control panel.Press the reset button.
Micrologic 7.0 P
02:04:0422/11/1999
Umin 100V
Resetby test/resetbutton
Fault
Micrologic P Schneider Electric67
Viewing the event histories
E71
706A
E71
707A
Select a fault. View.
E71
708A
E71
709A
Select an alarm. View.
Trip history
Triphistory
27/01/1999U min
27/06/1998Ir
18/02/1998Ir
Trip
02:04:0422/11/1999
Umin 160V
Alarm history
23/03/1998
Alarmhistory
U max
I2 max
In max
27/01/1999
12/02/1998
Alarm
13:06:0927/01/1999
I2 max 3400A
Select the commandEventhistory
Triphistory
Select the commandEventhistory
Alarmhistory
then
then
Micrologic P Schneider Electric68
Maintenance Operation counter andcontact-wear indicator
View and/or reset the operation counter
Check the wear of the contacts
E71
710C
Select the commandEventhistory
Operationcounter
Select the commandEventhistory
Contactwear
E71
736A
Reset… … or cancel the reset,then confirm.
Operationssince lastreset
operationsNumber of
17824Total
0
Reset ( - / + )
E71
737A
Operationssince lastreset
operationsNumber of
17824Total
6923
Reset ( - / + )
then
Operationssince lastreset
17824Total
operationsNumber of
6923
Reset ( - / + )
E71
735A
Contact wear is indicated from 0 to 900.The contacts should be inspected everytime the counter reaches a multiple of 100. 59
Contactwear
Micrologic P Schneider Electric69
If the battery must be replaced, use a newbattery with the Schneider part number33593 (technical characteristics availableon the battery-slot cover).Check its condition regularly by pressingand holding down the test button on thecontrol unit for several seconds.
Checking/replacing the battery
E60
307A
Check the control-unit battery
Micrologic 7.0 P
1 2 3
Press and hold down the test button on the control unit to check the LEDs and thebattery. The battery information is displayed if the control unit is equipped with anexternal power supply or if the circuit breaker is ON.
Replacing the control-unit battery
E71
751A
1. remove 2. remove the batterythe battery cover
E60
308A
E51
443A
E60
473A
E60
481A
3. insert a new battery. 4. put the cover backCheck the polarity. in place. Press the
battery-test button tocheck the new battery.
+
Battery fully charged
Battery half charged
No battery or must be replaced
Micrologic P Schneider Electric70
Maintenance
Test the ground-fault (Micrologic 6.0 P) and earth-leakage(Micrologic 7.0 P) protection functionsThe circuit breaker must be supplied with power and closed for the test.
Press the TEST button. The circuit breaker should trip.
Refer to the manual that comes with thetest kits.
Tests
E60
309A
E60
310A
E60
311A
Micrologic 5.0 P
If the circuit breaker does not trip, contact the after-sales support department.
Mini test kit and portable test kitThe test connector is used to connect the mini or the portable test kit to check thatthe control unit is operating correctly.
Micrologic 5.0 P
1
Micrologic 5.0 P
2
Micrologic P Schneider Electric71
Micrologic P Schneider Electric72
Technical appendix Tripping curves
Long-time I2t, short-time and instantaneous protectionMicrologic 5.0 P, 6.0 P, 7.0 P
E71
753A
E47
587A
0
0.40.3
0.20.1
t(s)
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
10 0005 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1.05
.02
.01
.005
.002
.001
x In
tr = 0.5…24 s
Isd = 1.5…10 x Ir
Ir = 0.4…1 x In
Ii = 2…15 x In . OFF
I2t OFF
x Ir
0.40.3
0.20.1
I2t ON
0
Long-time Idmtl, short-time and instantaneous protectionMicrologic 5.0 P, 6.0 P, 7.0 P
DT
VIT
EIT
HVF
SIT
.5 .7 1 2 3 4 5 7 10 20
I / Ir
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
100 000
t(s)
Micrologic P Schneider Electric73
Ground-fault protection - Micrologic 6.0 P
E46
266A
Ig = A…J x In (1) 1200 A max.
t(s)
I / In
10 0005 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1.05
.02
.01
.005
.002
.001.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I2t OFF
0.4
0.30.20.1
I2t ON
0.4
0.30.20.1
0 0
Micrologic P Schneider Electric74
Technical appendix Voltage measurements
Micrologic P is equipped with a three-phase voltage power supply that, with respectto the distribution system, may be considered a delta load. The three-phase powersupply reinjects voltage on an open phase.The voltage-protection functions react as indicated below.
Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unitreinjects voltage on the failed phase and measures a phase-to-phase voltagehigher than the actual voltage.The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurementindicates zero as well.
By limiting the pickup threshold of the minimum-voltage protection to the 80% -100% range of the rated distribution-system voltage, the differences between thereal voltages and the measured values are not significant and Micrologic willoperate under all circumstances in the expected manner.
Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unitreinjects voltage on the failed phase and measures a phase-to-phase voltagehigher than the actual voltage.The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurementindicates zero as well.
By limiting the pickup threshold of the voltage-unbalance protection to the 0% -20% range, the differences between the real voltages and the measured values arenot significant and Micrologic will operate under all circumstances in the expectedmanner.
Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage andvoltage-unbalance protection functions.The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for thethree phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).
Micrologic P Schneider Electric75
c diagram 1
c diagram 2
Fuses
Open
Contactor
Motor
Fuses
Open
Contactor
Motor
c diagram 3
FusesOpen
Contactor
Motor
c diagram 4
Fuses
Load
Othermeasurementand protectionsystems
E71
916A
E71
917A
E71
918A
E71
919A
Micrologic P Schneider Electric76
Caution!lf the protection function is not used oncircuit breakers equipped for ZSIprotection, a jumper must be installed toshort terminals Z3, Z4 and Z5. If the jumperis not installed, the short-time and ground-fault tripping delays are set to zero,whatever the position of the adjustmentdial.
Zone selective interlocking (ZSI)
Operating principlec a fault occurs at point ADownstream device no. 2 clears the fault and sends a signal to upstream device no.1, which maintains the short-time tripping delay tsd or the ground-fault trippingdelay tg to which it is set.c a fault occurs at point BUpstream device no. 1 detects the fault. In the absence of a signal from adownstream device, the set time delay is not taken into account and the devicetrips according to the zero setting. If it is connected to a device further upstream, itsends a signal to that device, which delays tripping according to its tsd or tg setting.
Note:On device no. 1, the tsd and tg tripping delays must not be set to zero because thiswould make discrimination impossible.
Connections between control unitsA logic signal (0 or 5 volts) can be used for zone selective interlocking between theupstream and downstream circuit breakers.c Micrologic 5.0 A, 6.0 A, 7.0 Ac Micrologic 5.0 P, 6.0 P, 7.0 Pc Micrologic 5.0 H, 6.0 H, 7.0 H.An interface is available for connection to previous generations of trip units.
Wiringc maximum impedance: 2.7 Ω / 300 metresc capacity of connectors: 0.4 to 2.5 mm2
c wires: single or multicorec maximum length: 3000 metresc limits to device interconnection:v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected toa maximum of ten inputsv a maximum of 100 devices may be connected to the common ZSI - IN (Z3) andto an input ZSI - IN CR (Z4) or GF (Z5).
E60
450B
E71
912ATerminals Z1 to Z5 correspond to the
identical indications on the circuit-breakerterminal blocks.
Technical appendix
Z1Z2Z3Z4Z5
1
Z1Z2Z3Z4Z5
Z1Z2Z3Z4Z5
Z1Z2Z3Z4Z5
2
downstreamcircuit-breaker
point B
point A
upstreamcircuit-breaker tsd = 0.3
tsd = 0. 2
Test
The portable test kit may be used to check the wiring and operation of the zoneselective interlocking between a number of circuit breakers.
A
B1
2
Micrologic P Schneider Electric77
Power supply
AD power-supply moduleThe AD power-supply module provides auxiliary 24 V DC power for the control-unitfunctions listed below:c graphic display:v device OFF or not suppliedv the long-time, short-time, instantaneous and ground-fault protection functionsoperate under all circumstances on their own powerc activation of an M2C programmable contactThe AD power-supply module is required to assign an M2C programmable contactto an alarm.
The AD power-supply module can supply the following voltages:c 110 V ACc 220 V ACc 380 V ACc 24 / 30 V DCc 48 / 60 V DCc 125 V DC.
Battery moduleUse of a BAT battery module, mounted in series with the AD power-supply module,ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.
Wiring diagramsv reliable or backed-up auxiliary system
v auxiliary system without back-up
c supply with the MC6 module
L3
L4
G1G2+
–
Input
220VAC
Output
24VDCAD 220V
F1-
F2+
L3
L4
G1G2+
–
Input
220VAC
Output
24VDCAD 220V
H3
H4
H2H1-
+
Input
24VDC
Output
24VDCBAT 24V
F1-
F2+
+-
E60
449A
E60
448A
E60
447A
L3
L4
G1G2+
–
Input
220VAC
Output
24VDCAD 220V
M6C
17
25
19 21 23
Q1 Q2 Q3
Caution!It is advised to use the AD power-supplymodule rather than an off-the-shelf 24 Vpower supply to ensure Class II insulationon the front panel of the Micrologic Pcontrol unit.
The power supply must have the followingcharacteristics:c output voltage 24 V DCc DC ripple less than 5%c power rating 5 W / 5 VAc Dielectric withstand (input/output):3 kV rms
Micrologic P Schneider Electric78
Using the AD power-supply module
circuit breaker closed open openAC power present for Micrologic P yes yes no
M2C, M6C programmable-contacts option yes yes yesdisplay function no no yestime-stamping function no no nocircuit-breaker status indications and control no no novia communications busidentification, settings, operation and maintenance aids no no yesvia communications bus
The 24 V DC external power-supply (AD module) is required for certain operatingconfigurations as indicated in the table below:c yes means the power supply is requiredc no means it is not required.
c if the 24 V DC external power supply (AD module) is used, the maximum cablelength between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed10 metres.c the communications bus requires its own 24 V DC power source (E1, E2).This source is not the same as the 24 V DC external power-supply module(F1-, F2+).
Selection of the voltage-measurement inputs
The voltage-measurement inputs are standard equipment on the downstreamconnectors of the circuit breaker.
It is possible to measure distribution-system voltage externally using the PTEexternal voltage-measurement input option.
With this option, the internal voltage-measurement inputs are disconnected.The PTE option is required for voltages greater than 690 V (in which case a voltagetransformer is required).
When the PTE option is implemented, the supply circuit of the voltage-measurement input must be protected against short-circuits. Installed as closeas possible to the busbars, this protection function is ensured by a P25M circuitbreaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
The supply circuit of the voltage-measurement input is reserved exclusivelyfor the control unit and must never be used to supply other circuits.
Technical appendix Power supply
Micrologic P Schneider Electric79
Caution!Following any modifications to the long-time rating plug, all control-unit protectionparameters must be checked.
Changing the long-timerating plug
Select the long-time rating plug
A number of long-time rating plugs are available for Micrologic P control units.
Part number Setting range for the Ir value33542 standard 0.4 to 1 x Ir33543 low setting 0.4 to 0.8 x Ir33544 high setting 0.8 to 1 x Ir33545 without long-time protection
c Ir = In for the short-time protection settingc frequency protection not availablec load shedding / reconnection based on current not available
Change the long-time rating plugProceed in the following manner.
2. open the protectivecover of the control unit
3. completely removethe long-time rating plug screw
E89
252A
E89
253A
4. snap out the ratingplug
5. clip in the new rating plug
E89
254A
E89
255A
6. refit the screw for thelong-time rating plug
7. check and/or modify thecontrol-unit settings
Caution!If no long-time rating plug is installed, thecontrol unit continues to operate under thefollowing downgraded conditions:c the long-time current setting Ir is 0.4c the long-time tripping delay trcorresponds to the value indicated by theadjustment dialc the earth-leakage protection function isdisabledc the voltage-measurement inputs aredisconnected.
Micrologic 5.0 H
Micrologic 5.0 H
.4.5.6
.7.8 .9
.95
.98
1
long time
alarm
Ir
x In
.512
48 12
16
20
tr(s)
@ 6 Ir24
Micrologic 5.0 H
.4.5.6
.7.8 .9
.95
.98
1
long time
alarm
Ir
x In
.512
48 12
16
20
tr(s)
@ 6 Ir24
1. open the circuit breaker
Micrologic 5.0 H
Micrologic P Schneider Electric80
Technical appendix Thermal memory
Thermal memoryThe thermal memory is the means to take into account temperature rise andcooling caused by changes in the flow of current in the conductors.
These changes may be caused by:c repetitive motor startingc loads fluctuating near the long-time protection settingsc repeated circuit-breaker closing on a fault.
Control units with a thermal memory record the temperature rise caused by eachoverload, even very short ones. This information stored in the thermal memoryreduces the tripping time.
Micrologic control units and thermal memoryAll Micrologic control units are equipped as standard with a thermal memory.
c for all protection functions, prior to tripping, the temperature-rise and cooling timeconstants are equal and depend depend on the tr tripping delay:v if the tripping delay is short, the time constant is lowv if the tripping delay is long, the time constant is high.
c for long-time protection, following tripping, the cooling curve is simulated by thecontrol unit. Closing of the circuit breaker prior to the end of the time constant(approximately 15 minutes) reduces the tripping time indicated in the trippingcurves.
Short-time protection and intermittent faultsFor the short-time protection function, intermittent currents that do no provoketripping are stored in the Micrologic P memory.This information is equivalent to the long-time thermal memory and reduces thetripping delay for the short-time protection.
Following a trip, the short-time tsd tripping delay is reduced to the value of theminimum setting for 20 seconds.
Ground-fault protection and intermittent faultsThe ground-fault protection implements the same function as the short-timeprotection (see above).
Micrologic P Schneider Electric81
Data available via the COMcommunications option
Measurementsc currentsv instantaneous currentsv maximum and minimum instantaneous currentsv average instantaneous currentsv instantaneous-current unbalance per phasev maximum and minimum instantaneous-current unbalance per phasec demand currentv demand current per phasev maximum and minimum demand current per phase since last resetv prediction of demand current per phasev time-stamping of demand-current maximums and minimumsc voltagesv phase-to-neutral and phase-to-phase voltagesv average phase-to-neutral and phase-to-phase voltagesv phase-to-neutral and phase-to-phase voltage unbalancev maximum and minimum phase-to-neutral and phase-to-phase voltage unbalancec active, reactive and apparent power per phasec demand powerv demand power per phasev maximum and minimum demand power per phase since last resetv maximum and minimum recommended demand power per phasev time-stamping of demand-power maximums and minimumsc energyv total active and reactive energyv positively incremented energyv negatively incremented energyc system frequencyc power factorc reset date of demand currents, demand power and energy.
Setup / Maintenancec setting of the control-unit date and timec password for the measurement modulec control-unit ID codec control-unit ID namec selection of the measurement calculation algorithmc sign convention for the active powerc total-energy measurement modec interval for the demand-current calculation windowc power quality indicationc demand-power calculation modec interval for the demand-power calculation windowc battery-charge indicationc trip and alarm historiesc operation counter and contact-wear indicatorc assignment and setup of programmable contactsc event log and maintenance register.
Protectionc circuit-breaker rated currentc type of neutral protectionc long-time I2t protection settingsc long-time Idmtl protection settingsc short-time protection settingsc instantaneous-protection settingsc ground-fault protection settingsc earth-leakage protection settingsc current-unbalance, It alarm and maximum-current protection settingsc voltage-protection settingsc setting for other protection functions.
The COM communications option can beused to remotely access the Micrologic Pmeasurement, setting, maintenance andprotection values.
Micrologic P Schneider Electric82
Technical appendix
Long-time I2t and Idmtl protection
Threshold and time-delay settings
Type Range Factory setting Step AccuracyIr current setting 0.4 to In maximum 1 A 1.05 to 1.20 Irtr tripping delay 0.5 to 24 s maximum 0.5 s - 20 %, + 0 %
Short-time protection
Type Range Factory setting Step AccuracyIsd pickup 1.5 to 10 Ir maximum 10 A ± 10 %tsd tripping delay 0 - 0.1 - 0.2 - 0.3 - 0.4 s maximum 0.1 s
Instantaneous protection
Type Range Factory setting Step AccuracyIi pickup 2 to 15 In or off maximum 10 A ± 10 %
Ground-fault protection on Micrologic 6.0 P
Type Range Factory setting Step AccuracyIg pickup depends on rating maximum 1 A ± 10 %tg tripping delay 0 - 0.1 - 0.2 - 0.3 - 0.4 s maximum 0.1 s
Earth-leakage protection on Micrologic 7.0 P
Type Range Factory setting Step AccuracyI∆n pickup maximum 0.1 A - 20 %, + 0 %∆t tripping delay 60 -140 - 230 - 350 - 800 ms maximum 1 setting
Neutral protection
Type Range Factory settingthree-pole device Off, N/2, N, 1.6xN offfour-pole device Off, N/2, N N/2
Micrologic P Schneider Electric83
Type Range Factory setting Step Accuracycurrent unbalance I unbal
Pickup threshold 5% to 60% 60 % 1 % -10 %, +0 %Dropout threshold 5% of pickup threshold pickup threshold 1 % -10 %, +0 %Pickup time delay 1 s to 40 s 40 s 1 s -20 %, +0 %Dropout time delay 10 s to 360 s 10 s 1 s -20 %, +0 %
ground-fault I ttttt alarmPickup threshold 20 A to 1200 A 120 A 1 A +/- 15 %Dropout threshold 20 A to pickup threshold pickup threshold 1 A +/- 15 %Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %Dropout time delay 1 s to 10 s 1 s 0.1 s -20 %, +0 %
earth-leakage I ttttt alarmPickup threshold 0.5 A to 30 A 30 A 0.1 A -20 %, +0 %Dropout threshold 0.5 A to pickup threshold pickup threshold 0.1 A -20 %, +0 %Pickup time delay 1 s to 10 s 10 s 0.1 s -20 %, +0 %Dropout time delay 1 s to 10 s 1 s 0.1 s -20 %, +0 %
maximum current 1 max, 2 max, 3 max, N maxPickup threshold 0.2 In to In In 1 A ± 6.6%Dropout threshold 0.2 In to pickup threshold pickup threshold 1 A ± 6.6%Pickup time delay 15 s to 1500 s 1500 s 1 s -20 %, +0 %Dropout time delay 15 s to 3000 s 15 s 1 s -20 %, +0 %
Current protection
Voltage protection
I I I I
Type Range Factory setting Step Accuracyminimum voltage U min
Pickup threshold 100 V to U max pickup threshold 100 V 5 V -5 %, +0 %Dropout threshold pickup threshold to U max pickup threshold 5 V -5 %, +0 %
pickup thresholdPickup time delay 1.2 s to 5 s 5 s 0.1 s -0 %, +20 %Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
maximum voltage U maxPickup threshold U min pickup threshold to 1200 V 725 V 5 V -0 %, +5 %Dropout threshold 100 V to pickup threshold pickup threshold 5 V -0 %, +5 %Pickup time delay 1.2 s to 5 s 5 s 0.1 s -0 %, +20 %Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 %
voltage unbalance U unbalPickup threshold 2% to 30% 30 % 1 % -20 %, +0 %Dropout threshold 2% to pickup threshold pickup threshold 1 % -20 %, +0 %Pickup time delay 1 s to 40 s 40 s 1 s -20 %, +0 %Dropout time delay 10 s to 360 s 10 s 1 s -20 %, +0 %
Micrologic P Schneider Electric84
Technical appendix
Other protection
Load shedding and reconnection
Threshold and time-delay settings
Type Range Factory setting Step Accuracyreverse power rP max
Pickup threshold 5 to 500 kW 500 kW 5 kW ± 2.5%Dropout threshold 5 kW to pickup threshold pickup threshold 5 kW ± 2.5%Pickup time delay 0.2 s to 20 s 20 s 0.1 s -0 %, +20 % (1)
Dropout time delay 1 s to 360 s 1 s 0.1 s -0 %, +20 %
maximum frequency F maxPickup threshold F min pickup threshold to 440 Hz 65 Hz 0.5 Hz ± 0.5 HzDropout threshold 45 Hz to pickup threshold pickup threshold 0.5 Hz ± 0.5 HzPickup time delay 1.2 s to 5 s 5 s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
minimum frequency F minPickup threshold 45 Hz to F max pickup threshold 45 Hz 0.5 Hz ± 0.5 HzDropout threshold pickup threshold to F max pickup threshold 0.5 Hz ± 0.5 Hz
pickup thresholdPickup time delay 1.2 s to 5 s 5 s 0.1 s -0 %, +20 % (2)
Dropout time delay 1.2 s to 36 s 1.2 s 0.1 s -0 %, +20 % (2)
phase rotationPickup threshold Ph1, Ph2, Ph3 or Ph1, Ph3, Ph2 Ph1, Ph2, Ph3 none noneDropout threshold pickup threshold pickup threshold none nonePickup time delay 0.3 s 0.3 s none - 0 %, + 50 %Dropout time delay 0.3 s 0.3 s none - 0 %, + 50 %
Type Range Factory setting Step Accuracycurrent I
Pickup threshold 50 % to 100% Ir 100 % Ir 1 % ± 6 %Dropout threshold 30 % Ir to shedding threshold shedding threshold 1 % ± 6 %Pickup time delay 20 % to 80% tr 80 % tr 1 % -20 %, +0 %Dropout time delay 10 s to 600 s 10 s 1 s -20 %, +0 %
power PPickup threshold 200 kW to 10 000 kW 10 000 kW 50 kW ± 2.5 %Dropout threshold 100 kW to shedding threshold shedding threshold 50 kW ± 2.5 %Pickup time delay 10 s to 3600 s 3600 s 10 s -20 %, +0 %Dropout time delay 10 s to 3600 s 10 s 10 s -20 %, +0 %
(1) + 30 % on dial 0.2 s
(2) + 30 % up to 1.5 s
Micrologic P Schneider Electric85
Other settings
M2C / M6C contacts
Type Range Factory setting Steptime-delay 1 - 360 s 360 s 1 slatchingtime delay
Micrologic setup
Type Range Factory setting Steplanguage German English UK
English USEnglish UKItalianFrenchSpanishChinese
date / time 1 scircuit-breaker "no def"selectionneutral TC no TCVT ratioprimary voltage min. 100 V, max. 1150 V 690 V 1 Vsecondary voltage min. 100 V, max. 690 V 690 V 1 Vsystem 50/60 Hz 50/60 Hzfrequency or
400 Hz
Measurement setup
Type Range Factory setting Stepsystem type 3 Φ, 3 w, 3 CT 3 Φ, 4 w, 4 CT
3 Φ, 4 w, 3 CT3 Φ, 4 w, 4 CT
demand-currentcalculation method thermal or block interval
block intervaltype of window fixed or sliding slidingcalculation interval 5 to 60 minutes 15 minutes 1 minutedemand-powercalculation method thermal or block interval
block interval orsync. to comms
type of window fixed or sliding slidingcalculation interval 5 to 60 minutes 15 minutes 1 minutepower sign P+ P+
P- (flow from top tobottom)
sign convention IEEE IEEEIEEE alternateIEC
Type Range Factory settingcom parameter MODBUSaddress 1-47 47baud rate 9600 to 19 200 bauds 19 200 baudsparity even even
noneremote settingsaccess authorisation yes / no yesaccess code 0000 to 9999 0000remote manual automaticcontrol automatic
Type Range Factory settingcurrent protection alarm / trip / OFF OFFvoltage protectionother protection
Communication setup
Protection setup
Micrologic P Schneider Electric86
Measurement setting ranges and accuracy
Type Range Accuracy at 25 °Cinstantaneous current
I1, I2, I3 0.005 x In to 20 x In ± 1.5 %IN 0.005 x In to 20 x In ± 1.5 %I t ground 0.005 x In to In ± 10 %I t earth leakage 0 to 30 A ± 1.5 %I1 max, I2 max, I3 max 0.005 x In to 20 x In ± 1.5 %IN max 0.005 x In to 20 x In ± 1.5 %I t max ground 0.005 x In to In ± 10 %I t max earth leakage 0 to 30 A ± 1.5 %
demand current1, 2, 3 0.005 x In to 20 x In ± 1.5 %N 0.005 x In to 20 x In ± 1.5 %1 max, 2 max, 3 max 0.005 x In to 20 x In ± 1.5 %N max 0.005 x In to 20 x In ± 1.5 %
phase-to-phase voltagesU12 170 to 1150 V ± 0.5 %U23 170 to 1150 V ± 0.5 %U31 170 to 1150 V ± 0.5 %
phase-to-neutral voltagesV1N 100 to 1150 V ± 0.5 %V2N 100 to 1150 V ± 0.5 %V3N 100 to 1150 V ± 0.5 %
average voltageU avg 170 to 1150 V ± 0.5 %
voltage unbalanceU unbal 0 to 100 % ± 0.5 %
instantaneous powerP 0.015 to 184 MW ± 2 %Q 0.015 to 184 Mvar ± 2 %S 0.015 to 184 MVA ± 2 %
power factorPF -1 to +1 ± 2 %
demand powerP 0.015 to 184 MW ± 2 %Q 0.015 to 184 Mvar ± 2 %S 0.015 to 184 MVA ± 2 %P max 0.015 to 184 MW ± 2 %Q max 0.015 to 184 Mvar ± 2 %S max 0.015 to 184 MVA ± 2 %
total energyE.P -1010 GWh to +1010 GWh ± 2 %E.Q -1010 Gvarh to +1010 Gvarh ± 2 %E.S -1010 GVAh to +1010 GVAh ± 2 %
total energy inE.P -1010 GWh to +1010 GWh ± 2 %E.Q -1010 Gvarh to +1010 Gvarh ± 2 %
total energy outE.P -1010 GWh to +1010 GWh ± 2 %E.Q -1010 Gvarh to +1010 Gvarh ± 2 %
frequencyF 45 Hz to 440 Hz ± 0.1 %
Measurement setting rangesand accuracy
Technical appendix
c The accuracy of the currentmeasurements depends on both the valuedisplayed (or transmitted) and the circuit-breaker rating, where:Accuracy = 0.5% In + 1.5% reading
Example:For a circuit breaker with a 4000 A ratingand a current displayed on Micrologicof 49 A, the accuracy is:0.5% x 4000 + 1.5% x 49 = ± 21 A
II
III
II
I
Micrologic P Schneider Electric87
Power factor sign conventions
E71
920B
P
QFlow of active andreactive power
P from loadQ to load
P to loadQ to load
P from loadQ from load
P to loadQ from load
E71
921B
IEC
P = -Q = +pf = -
P = +Q = +pf = +
P = -Q = -pf = -
P = +Q = -pf = +
P
Q
E71
922B
IEEE
P = -Q = +pf = + (leading)
P = +Q = +pf = - (lagging)
P = -Q = -pf = - (lagging)
P = +Q = -pf = + (leading)
P
Q
E71
923B
IEEE Alt
P = -Q = -pf = + (leading)
P = +Q = -pf = - (lagging)
P = -Q = +pf = - (lagging)
P = +Q = +pf = + (leading)
P
Q
Micrologic P Schneider Electric88
AActivation 25, 26, 27, 28, 31Active, reactive, apparent energy 30, 63Active, reactive, apparent power 30AD power-supply module 77Address 36Alarm 31Alarm history 33, 67
BBaud rate 46Buttons 5, 6
CCircuit-breaker selection 41COM communication option 36, 46, 81Contact 32, 38Contact wear 68Control unit identification 4Control-unit battery 5, 69Current demand calculation 29, 43
DDate and time 40Demand current 29, 57Demand power 30, 61Digipact 46Dropout 25, 26, 27, 28, 31DT 21, 49
EEarth-leakage protection 24Earth-leakage protection tripping delay ∆ 24EIT 21, 49
FF max 30, 52F min 30, 52Fault 66Frequency 30, 64Full neutral protection 23, 51Graphic display 5Ground-fault / Earth-leakage fault protection test 70Ground-fault protection 24
HHalf neutral protection 23, 51History, setup and maintenance menu 13, 16HVF 21, 49
II t 50I t Alarm 25, 52I avg 25I max 25, 52I unbal 25, 52I∆n pickup 24I2t 20, 48Idmtl 21, 49Ig pickup 24Ii pickup 22Infrared link 5Instantaneous current 29, 56Instantaneous protection 22Ir current setting 20, 21Isd pickup 22
LLanguage 40Latching 32Lead seal for cover 5LEDs 5, 34, 69Load shedding / reconnection 28, 54Long-time I2t protection 20Long-time Idmtl protection 21Long-time plug 5, 79
Index
Micrologic P Schneider Electric89
MM2C / M6C 32, 38Main screen 12, 56Maximum demand current 29, 58Maximum demand power 30, 62Maximum instantaneous current 29, 56Metering menu 13, 14ModBus 46
NNegatively incremented energy 30, 63Neutral CT 51Neutral protection 11, 23Neutral protection setting 11, 51No neutral protection 23, 51
OOperation counter 68Oversized neutral protection 23, 51
PParity 46Phase rotation 27, 52Phase sequence 27Phase-to-neutral and phase-to-phase voltage 29, 59Portable test kit 70Positively incremented energy 30, 63Power demand calculation 30, 44Power factor 61Power sign 42Power supply 77Protection menu 13, 18
RRemote control 47Remote settings 46Resetting the alarms and fault indications 66Resetting the contacts 32, 38Resetting the energy values 63Resetting the maximum demand current values 58Resetting the maximum demand power values 62Resetting the maximum instantaneous current values 57Resetting the operation counter 68rP max 27, 52
SSelf-protection 35Setting dials 5, 6Short-time protection 22Sign convention 87SIT 21, 49System frequency 42System type 43
TTab 7Temperature 35Test connector 5, 70tg tripping delay 24Thermal memory 20, 80tr tripping delay 20, 21Transformation ratio 42Trip 4Trip history 33, 67Tripping curves 72tsd tripping delay 22
Micrologic P Schneider Electric90
Index
UU max 26, 52U min 26, 52U unbal 26, 52, 59
VVIT 21, 49Voltage U avg 26, 29, 59
ZZone selective interlocking 76
Schneider Electric Industries SA
Postal address5, rue Nadar92506 Rueil-Malmaison CedexFranceTel: +33 (0)1 41 29 82 00Fax:+33 (0)1 47 51 80 20
http://www.schneider-electric.com
04443726AA-D 05-02
Layout by: HeadLinesPrinted by:
As standards, specifications and design change from time to time, always ask for confirmationof the information given in this publication.
This document has been printed on ecological paper