testing. permanent link definition –horizontal cabling extending from the wall plate to the cross...

47
Testing

Upload: rosalind-chambers

Post on 15-Jan-2016

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Testing

Page 2: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Permanent Link

• Definition– Horizontal cabling extending from the wall plate to the cross

connect

WORK AREA

TELECOMMUNICATIONS CLOSET

Horizontal

Cross-connect

Wall Outlet

Maximum Length - 90 Meters

Page 3: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Channel

• Definition

– The end-to-end transmission path connecting any two points at

which application specific equipment is connected. Equipment

and work area cables are included in the channel

Page 4: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Channel

WORK AREA

TELECOMMUNICATIONS CLOSET

Horizontal Cross-connect

Wall Outlet

ConcentrationPoint

EquipmentCable

PatchCable

Maximum Length 100 Meters

Page 5: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Permanent Link Test

• Configuration

Horizontal Cross-connect

WORK AREA

TELECOMMUNICATIONS CLOSET

Wall Outlet

Test Set

Test Set

Test Set Connection Cable (2 meters)

Maximum Length 94 meters

Page 6: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Channel Test

• Configuration

TELECOMMUNICATIONS CLOSET

Horizontal

ConcentrationPoint

PatchCable

Maximum Length 100

Meters

WORK AREA

Cross-connect

Wall Outlet

EquipmentCable

Test Set

Test Set

Page 7: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Twisted Pair

• Before we look at each of the basic tests we need to review the

– Physical– Electrical characteristics of a wire pair

Page 8: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Anatomy of a Wire Pair

• What we think of when we envision a wire pair.

Page 9: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Anatomy of a Wire Pair

• However, to a signal it looks like:– Resistors– Capacitors– Inductors

• The cable is not made up of discrete components but has the characteristics of these components

– Resistance– Capacitance– Inductance

Page 10: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• The characteristics are changed when a cable is:– Stretched (pulling / laying)– Kinked (handling / storage / tight corners)– Distorted (cable ties / stood upon / Heavy cable

bundles)

Damaging the cable

Page 11: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Physical Layer TestsTest Parameter TIA-568-B ISO 11801:2002

Wiremap Pass/Fail Pass/Fail

Propagation Delay Pass/Fail Pass/Fail

Delay Skew Pass/Fail Pass/Fail

Cable Length Pass/Fail Information only

Insertion Loss (IL) Pass/Fail Pass/Fail

Return Loss (RL) Pass/Fail (except Cat3)

Pass/Fail

Near-End Crosstalk (NEXT) Pass/Fail Pass/Fail

Power Sum NEXT (PSNEXT) Pass/Fail Pass/Fail

Equal-Level Far-End Crosstalk (ELFEXT)

Pass/Fail Pass/Fail

Power Sum ELFEXT (PSELFEXT) Pass/Fail Pass/Fail

Attenuation-to-Crosstalk Ratio (ACR) Information only Pass/Fail (except Class C)

Power sum ACR (PSACR) Information only Pass/Fail (except Class C)

DC Loop Resistance Pass/Fail

Page 12: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Wire Map

• Verification of the physical connection at each end of the cable

• Checks for– Opens

– Shorts

– Crosses

– Reverses and any other misfiring

– Splits• Difficult to identify with a DC wire map tester• Must use an advanced tester• Will fail on crosstalk

Page 13: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Length

• Physical– Calculated based on the length markings on the cable

• Maximum physical length of a permanent link is 90 meters

• Maximum physical length of a channel is 100 meters

Page 14: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Length

• Electrical– Based on the propagation delay of a signal over the

cable pair• Accomplished using a TDR (Time Domain Reflectometer)

• Calculation base on the Nominal Velocity of Propagation (NVP) of the signal over the pair being tested

Page 15: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• An analogy is friction

• Some of the signal is lost over distance

• Energy is dissipated in the form of heat

• Message may become to weak to be understood

DATA DATA DATA DATA DATA DATA DATA DATA DATA

Attenuation

Page 16: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Decibels dB’s

• Before we go any further we must talk a little about decibels (dB’s)

Page 17: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 17

• The deciBel is a convenient means of expressing the ratio of two values

– it is commonly used for example to express the Gain or Attenuation of a signal path:

Signal Path

Electrical/ Optical Signal

Input

Electrical/ Optical Signal

Output

Gain or Attenuation = Output Signal ÷ Input Signal

Decibels dB’s

Page 18: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 18

• deciBel expressions for the power and voltage level of a signal are slightly different:

– Voltage Gain/Attenuation =

– Power Gain/Attenuation =

Note: For Optical Fibre only the Power expression is relevant

IN

OUT

V

VLog1020

IN

OUT

P

PLog1010

Decibels dB’s

Page 19: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 19

A NEXT reading is -40 dB for Pair 1 to Pair2. What percentage of the Pair 1 input voltage appears at the input of Pair 2 ?

ANSWER

This result says that 1% of whatever is injected into Pair 1 will appear at the input of Pair 2

dBV

VLog

IN

NEXT 40201,

2,10

220

40

1,

2,10

IN

NEXT

V

VLog

%101.010 2

1,

2, orV

V

IN

NEXT

Example 1

Page 20: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 20

A FEXT reading is -50 dB from Pair 3 to Pair2. What percentage of the Pair 3 input voltage appears at the output of Pair 2 ?

ANSWER

This result says that 0.3% of whatever is injected into Pair 3 will appear at the output of Pair 2

dBV

VLog

IN

FEXT 50203,

2,10

5.220

50

3,

2,10

IN

FEXT

V

VLog

%3.0003.010 5.2

3,

2, orV

V

IN

FEXT

Example 2

Page 21: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 21

Pair 4 has an Attenuation reading of 20 dB. What percentage of the Pair 4 input voltage appears at the output of Pair 4 ?

ANSWER

This result says that 10% of whatever is injected into Pair 4 will appear at the output of Pair 4

dBV

VLog

IN

OUT 20204,

4,10

120

20

4,

4,10

IN

OUT

V

VLog

%101.010 1

4,

4, orV

V

IN

OUT

Example 3

Page 22: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• The loss of signal strength over the cable pair,

measured in dB

– Increases as the carrier frequency increases

– Pass/fail based on the worst case attenuation of all

pairs

Back To Attenuation

Page 23: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Attenuation

Page 24: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Crosstalk

• Defined as the induction of a portion of the signal from one pair into the adjacent pairs

– Measured in dB

Page 25: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

– NEXT• NEAR END CROSS TALK

– ELFEXT• EQUAL LEVEL FAR END CROSS TALK

– PSNEXT • POWER SUM NEAR END CROSS TALK

– PSELFEXT • POWER SUM EQUAL LEVEL FAR END CROSS TALK

Cross Talk Types

Page 26: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

NEXT and ELFEXT

• A final point is that ELFEXT depends greatly on the length of cable being examined, whereas the NEXT is much less dependent

Page 27: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Crosstalk Components

• Inductive and Capacitive Relationships:

Page 28: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• SPILL OVER

• ELECTRONS ARE LOST TO THE ADJACENT CABLE PAIRS

• THE MESSAGE IS CORRUPTED

Cross Talk

DATA DATA ATA DATA DATA DATA DAA DATA DATA

DATA DATA DDATA DATA DATA DATTA DATA DATA

Page 29: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• NEXT MEASURES THE CROSSTALK EFFECT ONE PAIR HAS UPON THE OTHER WITH RESPECT TO THE NEAR END OF THE CABLE

NEXT

Page 30: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Near-End Crosstalk (NEXT)

Page 31: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Power Sum

• Use of the TIA Algorithm for Calculating Power Sum– Calculation is derived from the conventional NEXT measurement.– Only one pair is energized at a time; formula “sums” the crosstalk

effect of three energized pairs on the remaining fourth pair.

Page 32: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• POWER SUM NEXT IS THE COMPUTED EFFECT OF THREE PAIRS UPON THE FOURTH WITH RESPECT TO THE NEAR END OF THE CABLE

PSNEXT

Page 33: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• ELFEXT MEASURES THE CROSSTALK EFFECT ONE PAIR HAS UPON THE OTHER WITH RESPECT TO THE FAR END OF THE CABLE

ELFEXT

Page 34: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• POWER SUM ELFEXT IS THE COMPUTED EFFECT OF THREE PAIRS UPON THE FOURTH WITH RESPECT TO THE FAR END OF THE CABLE

PSELFEXT

Page 35: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• NEXT and ELFEXT (and crosstalk in general) depend very much on the frequency at which they are measured

– they increase as the frequency increases– on average they may be described as follows:

NEXT and ELFEXT

23

frequencyNEXT 2frequencyFEXT

Page 36: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

NEXT and ELFEXT

• In practise this means as the Cat6 specification includes frequencies up to 250 MHz, that both the NEXT and ELFEXT measurements will increase dramatically

– For example the NEXT at 250 MHz should be about 4 times higher than the NEXT at 100MHz for any given combination of pairs

– Even worse the ELFEXT at 250 MHz should be over 6 times higher than the value at 100 MHz for any given combination of pairs

– For these reasons (and more) cable that passes Cat 5/5e quite easily may still fail the Cat 6 standard

Page 37: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Copyright of the Applied Optoelectronics Centre DIT 19/08/99 Photocopying strictly prohibited 37

CAT 5 to CAT 7 NEXT values at 100 MHz

NEXT dB Calculations

SPECIFICATION NEXT Percentage

CATEGORY 5 32 dB 2.5%

CATEGORY 5e 35 dB 1.8%

CATEGORY 6 43 dB 0.7%

CATEGORY 7 71 dB 0.03%

Page 38: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Attenuation to Crosstalk Ratio

• Definition:– A ratio comparing the received signal with the near-end crosstalk on a

cable

• It is not a direct test– It is a comparison of the attenuation test and NEXT test– Used to give an indication of how problem-free the cable line will be

Attenuation-to-Crosstalk ratio (ACR) is the difference between the signal attenuation produced and NEXT and is measured in decibels (dB). The ACR indicates how much stronger the attenuated signal is than the crosstalk at the destination (receiving) end of a communications circuit. The ACR figure must be at least several decibels for proper performance. If the ACR is not large enough, errors will be frequent. In many cases, even a small improvement in ACR can cause a dramatic reduction in the bit error rate. Sometimes it may be necessary to switch from un-shielded twisted pair (UTP) cable to shielded twisted pair (STP) in order to increase the ACR.

Page 39: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Attenuation to Crosstalk Ratio (ACR)

Page 40: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Propagation Delay

• Propagation Delay– The time needed for the signal to travel from the transmitter to

the receiver over a 100 Ohm 4-pair cable.

Page 41: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• THE TRANSMISSION TIME

T1 T2

Delay

Page 42: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• THE DIFFERENCE IN TIME BETWEEN THE FASTEST AND SLOWEST PAIR

T2

T1 T3Delay Skew = Difference between T2 and T3

Delay Skew

Page 43: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

• DELAY – THE TRANSMISSION TIME

• DELAY SKEW (X)– THE DIFFERENCE IN TIME BETWEEN THE FASTEST AND

SLOWEST PAIR

Delay / Delay skew

X

Page 44: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Propagation Delay

Page 45: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

DC Loop Resistance

• DC Loop Resistance measures the total resistance through one wire pair looped at one end of the connection. This will increase with the length of the cable. DC resistance usually has less effect on a signal than insertion loss, but plays a major role if you require power over Ethernet. Also measured in ohms is the characteristic impedance of the cable, which is independent of the cable length

Page 46: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Return Loss

• It measures the difference between test signal’s amplitude and the amplitude of signal reflections returned by the cable.

• Information Provided:– Indicates how well the cable’s characteristic impedance matches its

rated impedance

Return Loss is the measurement (in dB) of the amount of signal that is reflected back toward the transmitter. The reflection of the signal is caused by the variations of impedance in the connectors and cable and is usually attributed to a poorly terminated wire. The greater the variation in impedance, the greater the return loss reading. If 3 pairs of wire pass by a substantial amount, but the 4 pair barely passes, it usually is an indication of a bad crimp or bad connection at the RJ45 plug.

Page 47: Testing. Permanent Link Definition –Horizontal cabling extending from the wall plate to the cross connect WORK AREA TELECOMMUNICATIONS CLOSET Horizontal

Return Loss