    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Physical Arrangement

    Sh.

    52

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    2/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    NEMA SG-6 Withdrawn, but still used by many

    BIL Based

    Provides

    Bus spacings Horn Gap Spacings

    Side Break Switch Spacings

    Minimum Metal-to-Metal

    Minimum Phase-to-Ground

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    3/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    4/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    IEEE 1427-2006 Guide for Electrical Clearances &Insulation Levels in Air Insulated Electrical PowerSubstations

    BIL/BSL Based

    Rec. Phase-to-Phase Min. Metal-to-Metal

    Min. Phase to Ground

    Rec. Bus Spacings including Horn Gap

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    5/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013Spacing & Clearances

    IEEE 1427SG-6

    50

    52.5

    63

    Min Ph-Gnd

    Rec. Ph-Gnd

    Min Ph-Ph

    49

    N/A

    54

    650 kV BIL Ex:

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    6/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    BIL/Voltage Ratio

    Table 8 shows the comparison between various maximum system voltages andBILs associated with these voltages. The comparison is intended ONLY toillustrate the ratio has decreased with use of higher system voltages.

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    7/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    IEEE 1427-2006 What It DoesntAddress Uprating (Discussion Only)

    Wildlife Conservation Shielding Effects Contamination Hardware & Corona Arcing During Switch Operation Mechanical Stress Due to Fault Currents Safety

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    8/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    NESC (ANSI/IEEE C2) Safety Based

    Standard Installation and Maintenance Requirements

    Stations

    Aerial Lines

    Underground Circuits

    Grounding Methods

    NFPA 70E

    Safe Working Clearances for Low and Medium-Voltage

    Equipment

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    9/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Spacing & Clearances

    NESC FenceSafetyClearance

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    10/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013Spacing & Clearances

    IEEE C37.32

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    11/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013

    Typical 138 kV Substation Four (4) Breaker Ring Bus w/ Oil Circuit Breakers

  • 7/25/2019 SubDesign_Spacing Clerances Copia Parcial

    12/12

    HV Substation Design: Applications and Considerations IEEE CED Houston Chapter 2012-2013Spacing & Clearances