structural plan review wall bracing continued lesson 7 · structural plan review wall bracing...
TRANSCRIPT
Structural Plan Review
Wall Bracing Continued
Lesson 7
Updated: March 2017
2 of 66
Braced Wall Connections
In order to be effective, braced wall panels must connect the roof diaphragm to
the foundation system. The provisions in R602.10.6 give minimum prescriptive
criteria for the connection of the BWPs to the double top plate and to the
foundation system.
R602.10.6 Braced wall panel connections. Braced wall panels shall
be connected to floor framing or foundations as follows:
1. Where joists are perpendicular to a braced wall panel above or
below, a rim joist, band joist or blocking shall be provided along the
entire length of the braced wall panel in accordance with Figure
R602.10.6(1). Fastening of top and bottom wall plates to framing, rim
joist, band joist and/or blocking shall be in accordance with Table
R602.3(1).
3 of 66
Braced Wall Connections Cont.
of 66 4
Braced wall connections cont. 2. Where joists are parallel to a braced wall panel above or below, a rim joist, end joist
or other parallel framing member shall be provided directly above and below the braced
wall panel in accordance with Figure R602.10.6(2). Where a parallel framing member is
not located directly above and below the panel, full-depth blocking at 16 inch (406 mm)
spacing shall be provided between the parallel framing members to each side of the
braced wall panel in accordance with Figure R602.10.6(2). Fastening of blocking and
wall plates shall be in accordance with Table R602.3(1) and Figure R602.10.6(2).
5
of 66
Braced wall connections cont.
6 of 66
Braced wall connections cont.
3. Connections of braced wall panels to concrete or masonry shall be in accordance
with Section R403.1.8.
R403.1.8 Foundation anchorage. Sill plates and walls supported directly on continuous
foundations shall be anchored to the foundation in accordance with this section. Wood
sole plates at all exterior walls on monolithic slabs, wood sole plates of braced wall
panels at building interiors on monolithic slabs and all wood sill plates shall be anchored
to the foundation with anchor bolts spaced a maximum of 6 feet (1829 mm) on center.
Bolts shall be at least ½ inch (12.7 mm) in diameter and shall extend a minimum of 7
inches (178 mm) into concrete or grouted cells of concrete masonry units. A nut and
washer shall be tightened on each anchor bolt. There shall be a minimum of two bolts per
plate section with one bolt located not more than 12 inches (305 mm) or less than seven
bolt diameters from each end of the plate section. Interior bearing wall sole plates on
monolithic slab foundation that are not part of a braced wall panel shall be positively
anchored with approved fasteners. Sill plates and sole plates shall be protected against
decay and termites where required by Sections R317 and R318. Cold-formed steel
framing systems shall be fastened to wood sill plates or anchored directly to the
foundation as required in Section R505.3.1 or R603.3.1.
7
of 66
Braced wall connections cont.
7” 7
”
To prevent walls and floors from shifting
under lateral loads, the code requires
anchorage to the supporting foundation.
Anchor bolts installed as specified in this
section supply the minimum required
capacity. Figure R403.1.6 illustrates
anchorage of wood sill plates. The 1/2-
inch bolts must extend into concrete or
grouted cells of concrete masonry units.
This anchorage applies at exterior walls
in any seismic design category.
8 of 66
Braced wall connections cont.
R403.1.8.1 Foundation anchorage in Seismic Design Categories C,D1 andD2.
In addition to the requirements of Section R403.1.6, the following requirements shall
apply to wood light-frame structures in Seismic Design Categories D1 and D2 and wood
light-frame townhouses in Seismic Design Category C.
1. Plate washers conforming to Section R602.11.1 shall be provided for all anchor bolts
over the full length of required braced wall lines. Properly sized cut washers shall be
permitted for anchor bolts in wall lines not containing braced wall panels.
2. Not shown
3. Not shown
4. In Seismic Design Category D2, the
maximum anchor bolt spacing shall be
4 feet (1219 mm)for buildings over two
stories in height.
5. Not shown
6. Not shown
9
of 66
Braced wall connections cont.
R602.11 Wall anchorage. Braced wall line sills shall be anchored to concrete or masonry
foundations in accordance with Sections R403.1.6 and R602.11.1.
602.11.1 Wall anchorage for all buildings in Seismic Design Categories D1 and D2 and
townhouses in Seismic Design Category C. Plate washers, a minimum of 0.229 inch by 3
inches by 3 inches (5.8 mm by 76 mm by 76 mm) in size, shall be provided between the
foundation sill plate and the nut except where approved anchor straps are used. The hole in
the plate washer is permitted to be diagonally slotted with a width of up to 3/16 inch (5 mm)
larger than the bolt diameter and a slot length not to exceed 13/4 inches (44 mm), provided a
standard cut washer is placed between the plate washer and the nut.
of 66 10
11 of 66
Braced wall connections cont.
R602.10.6.1 Braced wall panel connections for Seismic Design Categories D1 and D2.
Braced wall panels shall be fastened to required foundations in accordance with Section
R602.11.1, and top plate lap splices shall be face-nailed with at least eight 16d nails on
each side of the splice.
12 of 66
Braced wall connections cont.
R602.10.6.2 Connections to roof framing. Exterior braced wall panels shall be
connected to roof framing as follows.
1. Parallel rafters or roof trusses shall be attached to the top plates of braced wall panels in
accordance with Table R602.3(1).
13 of 66
Braced wall connections cont.
2. For SDC A, B and C and wind speeds less than 100 miles per hour (45 m/s), where
the distance from the top of the rafters or roof trusses and perpendicular
top plates is 91/4 inches (235 mm) or less, the rafters or roof trusses shall be connected
to the top plates of braced wall lines in accordance with Table R602.3(1) and blocking
need not be installed. Where the distance from the top of the rafters and perpendicular
top plates is between 91/4 inches (235 mm) and 151/4 inches (387 mm) the rafters shall be
connected to the top plates of braced wall panels with blocking in accordance with
Figure R602.10.6.2(1) and attached in accordance with Table R602.3(1). Where the
distance from the top of the roof trusses and perpendicular top plates is between 91/4
inches (235 mm) and 151/4 inches (387 mm) the roof trusses shall be connected to the top
plates of braced wall panels with blocking in accordance with Table R602.3(1).
The following connection details represent a simple principle: braced wall
lines extend from diaphragm to diaphragm and must be connected at both top
and bottom.
14 of 66
Braced wall connections cont.
15 of 66
Braced wall connections cont.
16 of 66
Braced wall connections cont.
17 of 66
Braced wall connections cont.
R602.10.1.2.1 Braced wall panel uplift load path. Braced wall panels located at
exterior walls that support roof rafters or trusses (including stories below top story) shall
have the framing members connected in accordance with one of the following:
1. Fastening in accordance with Table R602.3(1)
where:
1.1. The basic wind speed does not exceed 90 mph (40 m/s), the wind
exposure category is B, the roof pitch is 5:12 or greater, and the roof span is
32 feet (9754 mm) or less, or
1.2. The net uplift value at the top of a wall does not exceed 100 plf. The net
uplift value shall be determined in accordance with Section R802.11 and shall
be permitted to be reduced by 60 plf (86 N/mm) for each full wall above.
2. Where the net uplift value at the top of a wall exceeds 100 plf (146 N/mm), installing
approved uplift framing connectors to provide a continuous load path from the top of the
wall to the foundation. The net uplift value shall be as determined in Item 1.2 above.
3. Bracing and fasteners designed in accordance with accepted engineering practice to
resist combined uplift and shear forces.
of 66 18
Braced wall connections cont.
R802.11.1 Uplift resistance. Roof assemblies which are subject to wind uplift pressures
of 20 pounds per square foot (960 Pa) or greater as established in Table R301.2(2) shall
have rafter or truss ties provided at bearing locations in accordance with Table R802.11.
A continuous load path shall be designed to transmit the uplift forces from the rafter or
truss ties to the foundation.
19 of 66
Braced wall connections cont.
Braced wall panel uplift load path
From Section R602.10.1.2.1, Item 1.1, it can be inferred that the Table R602.3(1),
Item 5, prescriptive nailing requirements provide 100 pounds of net uplift (plf)
resistance to properly attached roofs. No additional attachment is required until the
uplift loads specified in Table R802.11 exceed this amount. In addition, Section
R602.10.1.2.1, Item 1.2, provides the effective weight of each full wall above the
wall-to-floor connection in question as 60 plf . This amount can be subtracted from
the uplift amount, as the uplift requirement for each lower floor is calculated (see
Example 1.2). Given this information, the user is able to use the truss or rafter
connection uplift force provided in Table R802.11 and its notes to compute the net
uplift requirement for a structure at a given location. Note that the notes of Table
R802.11 are important and must be considered.
20 of 66
Braced wall connections cont.
Uplift @ Brace Wall Panels
21 of 66
Braced wall connections cont.
R602.10.7 Braced wall panel support. Braced wall panel support shall be provided
as follows:
1. Cantilevered floor joists, supporting braced wall lines, shall comply with
Section R502.3.3. Cantilevered floor joists complying with Section R502.3.3
shall be permitted to support braced wall panels. In all structures in Seismic
Design Category D1 and D2 and in townhouses in Seismic Design Category C,
cantilevered floor joists supporting braced wall panels shall comply with the
requirements of Section R301.2.2.2.5, item 1. Solid blocking shall be provided
at the nearest bearing wall location. In Seismic Design Categories A, B and C,
where the cantilever is not more than 24 inches (610 mm), a full height rim joist
instead of solid blocking shall be provided.
2. Elevated post or pier foundations supporting braced wall panels shall be
designed in accordance with accepted engineering practice.
The above two items have been covered earlier in this module. Next we see
the provisions for when masonry stem walls are used as the base for brace
wall panels.
22 of 66
Braced wall connections cont.
3. Masonry stem walls with a length of 48 inches (1220 mm) or less supporting braced
wall panels shall be reinforced in accordance with Figure R602.10.7. Masonry stem
walls with a length greater than 48 inches (1220 mm) supporting braced wall panels
shall be constructed in accordance with Section R403.1. Braced wall panels constructed
in accordance with Sections R602.10.3.2 and R602.10.3.3 shall not be attached to
masonry stem walls (Portal Frames).
4. Concrete stem walls with a length of 48 inches (1219mm) or less, greater than 12
inches (305 mm) tall and less than 6 inches (152 mm) thick shall have reinforcement
sized and located in accordance with Figure R602.10.7.
5. In all structures in Seismic Design Category D1 and D2 and in townhouses in
Seismic Design Category C, the end of a braced wall panel over an opening in the wall
below are subject shall comply with the requirements of Section R301.2.2.2.5, item 3.
23 of 66
Braced wall connections cont.
R602.10.7 Braced wall panel support cont.
Figure R602.10.7
Masonry Stem Walls Supporting Braced Wall Panels
24 of 66
Braced wall connections cont.
R602.10.7 Braced wall panel support cont.
Figure R602.10.7
Masonry Stem Walls Supporting Braced Wall Panels
25 of 66
Brace wall line spacing
Determining BWL spacing using Section 602.10.1.4 The provisions for brace wall line spacing between brace wall lines is covered
in the code Section 602.10.1.4 which states that the spacing shall be located in
accordance with Figure R602.10.1.4(1).
The braced wall spacing used in Tables 602.10.1.2(1 &2) is referring to the
spacing between lines A & B and the spacing
between lines B & C. If you are looking at the
table spacing for wall line A you would take
the distance between lines
A & B. If you are looking for
the table spacing for line B
then you would take the
greater distance
between lines A & B or
lines B & C.
26 of 66
Brace wall line spacing cont.
Determining BWL spacing using Section 602.10.1.4 cont.
An example of the spacing for the box shaped building below would be:
Wall line A, L = 30’
Wall line B, L = 30’
Wall line 1, L = 60’
Wall line 2, L = 60’
27 of 66
Brace wall line spacing cont.
Determining BWL spacing using Section 602.10.1.4 cont.
28 of 66
Brace wall line spacing cont.
Determining BWL spacing using Section 602.10.1.4 cont.
As seen in the example
on the right, Line A is
4’ perpendicular from each
wall that is parallel with
the wall line so the brace
wall line can use the gray
shaded walls for the wall
line bracing.
29 of 66
Brace wall line spacing cont.
The walls of the house are permitted to offset from the BWL:
• < or = 4’ on either side
of the BWL
• BWL is not required to
align with the actual wall(s)
30 of 66
Brace wall spacing cont. The 12.5 foot end-distance provision is in place to prevent the elimination of a braced wall
panel in a wall line. For example, if the 12.5-foot rule is applied at each end of a 29-foot long
wall line, only a single panel is required in the wall line: one braced panel positioned 12.5 feet
from each end of the wall line12.5 feet + 4 feet + 12.5 feet = 29 feet. The provision eliminates
the possibility of such an interpretation. The bracing provisions require bracing at each end and
every 25 feet on center. A single panel in a braced wall line violates the intent of the provision to
have a minimum of two braced panels, and may not provide sufficient stability to the roof or
floor diaphragm above.
31 of 66
Brace wall panel length along BWL
Once the wall line locations have been determined and that there are the
appropriate conforming panel configurations available then it must be verified
that the brace wall line has the minimum overall total length. In order to verify
this you move into the tables for the wind provisions (remember, we will look
at the seismic provisions and multi-story applications once we have the basic
understanding of the brace wall concept).
Table R602.10.1.2(1) is the table that establishes the basic minimum length for
brace wall panels based on brace wall type and spacing between wall lines.
Once the minimum length per the table is established then there are several
other tables that need to be referenced which have multipliers dependent
upon the variables of the particular building configuration. There are multipliers
for such things as exposure related to stories, roof ridge height, number of
braced wall lines and brace wall types.
Bracing requirements per the wind speed tables
32 of 66
Brace wall panel length along BWL cont.
33 of 66
Brace wall panel length along BWL cont. Determining BWP length using Table R602.10.1.2(1)
An example of the BW length for the box shaped building below would be:
Wall line A, spacing L = 60’
Per table using method WSP
(Wood Structural Panel)
Exposure B
Single story, 10 ft, wall height
Eave to ridge height = 15 ft.
No interior drywall
34 of 66
Brace wall panel length along BWL cont.
35 of 66
Brace wall panel length along BWL cont.
The base wall line length for Wall Line A is 9.5 lineal feet of brace wall using
plywood structural panels. Now we need to check the multiplier tables:
This is a single story exposure B structure so the multiplier is 1.0
36 of 66
Brace wall panel length along BWL cont.
The eave to ridge
height is 15 ft. for this
structure and the wall
height is 10 feet which
does not require a
multiplier per footnote “d”
but a 1.3 multiplier must
be used for the ridge
height. This multiplier
takes into account the
taller “sail” area.
37 of 66
Brace wall panel length along BWL cont.
The building only has two resisting BWLs so an adjustment factor is not required.
Using the WSP method of bracing will require the BW length to be adjusted by
the 1.4 factor.
If the owner/designer chooses to install hold down devices per footnote ‘i’
then an adjustment factor of 0.8 can be used to reduce the BW length.
38 of 66
Brace wall panel length along BWL cont.
Total required brace panel length @ Wall Line A:
Assuming the use of hold down devices @ panel ends
LA = (9.5)(1.0)(1.3)(1.4)(0.8) = 13.83’, use 14’
So using two panels, the length of each panel is 7’ within the 30’ long wall
Note: Due to the symmetry of the box configuration the same brace wall
configuration can be used for Line B.
39 of 66
Brace wall panel length along BWL cont.
Brace wall length at Wall Lines 1 & 2:
For wall lines 1 & 2 we will assume that this is the gable end of the building
And as such there is the triangular portion of the roof structure facing the wind.
Wall lines 1 & 2, spacing L = 30’
Per table using method WSP (Wood Structural Panel)
Exposure B
Single story 10 ft., wall height
Eave to ridge height = 15 ft.
40 of 66
Brace wall panel length along BWL cont.
The base wall line length for Wall Lines 1 & 2 for a 30 ft. BWL spacing is 5
lineal feet of brace wall using plywood structural panels. Again, we need to
check the multiplier tables:
This is a single story exposure B structure so the multiplier is 1.0
Using the WSP method of bracing will again require the BW length to be
adjusted by the 1.4 factor. This time we will not use the hold down provisions
from footnote ‘i’.
L1 & 2 = (9.5)(1.0)(1.3)(1.4) = 17.29’, use 20’
So using five panels, the length of each panel is 4’ within the 60’ long wall but
this exceeds the 25’ o.c. spacing would still be 5 – 4’ panels.
41 of 66
Interpolation ORSC allows interpolation in many tables
No extrapolation
42 of 66
Interpolation
43 of 66
Interpolation cont.
44 of 66
Interpolation cont.
45 of 66
Interpolation cont.
Box Method
46 of 66
47 of 66
Brace wall length analysis
8’
10’
6’-4”
9’
9’
Front Elevation
Left Side Elevation Roof Plan
Elevation and roof plan
for the example residence
48 of 66
Brace wall line spacing cont.
45’
15’
Determining brace wall lines at complex structures When looking at structures that do not have easily defined wall lines such as a
simple box it is helpful to consider the structure in a series of smaller boxes. By
approaching the structure in this fashion it will be easier to isolate individual brace
wall lines. As an example, wall line B is influenced by the box made up of wall
Lines 1 & 2 with wall lines A & B, also
the boxes made up of wall lines B & C
with wall lines 1 & 4 and Lines 3 & 4.
In regions controlled by wind and not
within Seismic Design Categories D1
& D2 the 45’ long spacing would be
allowed otherwise the maximum
spacing between wall lines is 25’ for
typical applications. Wall line 4 is
discontinuous but is influenced by
the boxes made up of wall lines B & C
with wall lines 1 & 4 and Lines 3 & 4
8’
49 of 66
More brace wall length analysis cont.
50 of 66
Wall Covering – Exterior
Key points:
• Section R703 outlines the requirements for exterior wall coverings.
• A general rule of thumb is that exterior wall coverings are installed in
accordance with the manufacturer’s installation instructions.
• Exterior walls of buildings must be protected against damage caused by
precipitation, wind and other weather conditions. This section also requires that
flashing be installed in the exterior wall at penetrations and terminations of the
exterior wall covering.
• R703.1.1 is the Oregon amendment of the “drainage plane” requirement.
• R703.2 is the water-resistive barrier (WRB) requirement.
51 of 66
Wall Covering – Exterior
“The Drainage Plane”
R703.1.1 Exterior wall envelope.
• The exterior wall envelope shall be installed in a manner that water that enters
the assembly can drain to the exterior.
• The envelope shall consist of an exterior veneer, a water-resistive barrier as
required in Section R703.2, a minimum 1/8 inch (3 mm) space between the
water- resistive barrier and the exterior veneer, and integrated flashings as
required in Section R703.8.
• The required space shall be formed by the use of any non-corrodible furring
strip, drainage mat or drainage board.
• The envelope shall provide proper integration of flashings with the water-
resistive barrier, the space provided and the exterior veneer. These
components, in conjunction, shall provide a means of draining water that enters
the assembly to the exterior.
52 of 66
Wall Covering – Exterior “The Drainage Plane”
R703.1.1 Exterior wall envelope. (Exceptions)
1. A space is not required where the exterior veneer is installed over a water-
resistive barrier complying with Section R703.2 that is manufactured in a
manner to enhance drainage and meets the 75-percent drainage efficiency
requirement of ASTM E2273 or other recognized national standards.
2. A space is not required where window sills are equipped with pan flashings that
drain to the exterior surface of the veneer in a through wall fashion. All pan
flashings shall be detailed within the construction documents and shall be of
either a self-adhering membrane complying with AAMA 711-07 or of an
approved corrosion-resistant material or a combination thereof. Self-adhering
membranes extending to the exterior surface of the veneer shall be concealed
with trims or other measures to protect from sunlight.
3. A space is not required for detached accessory structures.
53 of 66
Wall Covering – Exterior “The Drainage Plane”
R703.1.1 Exterior wall envelope. (Exceptions continued)
4. A space is not required for additions, alterations or repairs where the new
exterior veneer is;
4.1. Matching the existing exterior veneer; and
4.2. Installed in the same plane as the existing veneer without a change
in direction or use of a control joint; and
4.3. Installed over a water-resistive barrier complying with Section
R703.2.
5. The requirements of Section R703.1 shall not be required over concrete or
masonry walls designed in accordance with Chapter 6 and flashed according
to Section R703.7 or R703.8.
6. Tested Exterior Envelope – See Section for details
54 of 66
Wall Covering – Exterior “The Drainage Plane”
R703.2 Water-resistive barrier. One layer of No. 15 asphalt felt, free from holes
and breaks, complying with ASTMD226 for Type 1 felt or other approved water-
resistive barrier shall be applied over studs or sheathing of all exterior walls. Such
felt or material shall be applied horizontally, with the upper layer lapped over the
lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped
not less than 6 inches (152 mm). The felt or other approved material shall be
continuous to the top of walls and terminated at penetrations and building
appendages in a manner to meet the requirements of the exterior wall envelope as
described in Section R703.1.
Exception: Omission of the water-resistive barrier is permitted in the following
situations:
1. In detached accessory buildings.
2. Under exterior wall finish materials as permitted in Table R703.4.
3. Under paperbacked stucco lath when the paper backing is an approved water-
resistive barrier.
55 of 66
Wall Covering – Exterior
“The Drainage Plane”
Part 1:
Drainage Plane R703.1.1
• 1/8” non-corrodible furring strips
• Drainage mat / wrap / board
+
Part 2:
Water Resistive Barrier
R703.2
• No. 15 ASTM D 226 Felt
• Other approved WRB
There are two parts that must be addressed to satisfy the
prescriptive requirements of ORSC Section R703.1 & R703.2:
Note: Application of certain exceptions from R703.1.1 essentially combine
parts 1 & 2 into a single step path.
56 of 66
Wall Covering – Exterior “The Drainage Plane”
On the left, a section detail including non-corrodible furring strips
with No. 15 felt. On the right, a section detail satisfying both
R703.1.1 and R703.2 in a single step through the use of
Exception 1.
57 of 66
Wall Covering – Exterior “The Drainage Plane”
58 of 66
Wall Covering – Exterior
R703.3 Wood, hardboard and wood structural panel siding.
R703.3.1 Panel siding. Joints in wood, hardboard or wood structural panel siding
shall be made as follows unless otherwise approved. Vertical joints in panel siding
shall occur over framing members, unless wood or wood structural panel
sheathing is used, and shall be ship lapped or covered with a batten. Horizontal
joints in panel siding shall be lapped a minimum of 1 inch (25 mm) or shall be ship
lapped or shall be flashed with Z-flashing and occur over solid blocking, wood or
wood structural panel sheathing.
R703.3.2 Horizontal siding. Horizontal lap siding shall be installed in accordance
with the manufacturer’s recommendations. Where there are no recommendations
the siding shall be lapped a minimum of 1 inch (25 mm), or ½ inch (13 mm) if
rabbeted, and shall have the ends caulked, covered with a batten or sealed and
installed over a strip of flashing.
59 of 66
Wall Covering – Exterior
Table R703.4 & Section R703.4
R703.4 Attachments. Unless specified otherwise, all wall coverings shall be
securely fastened in accordance with Table R703.4 or with other approved
aluminum, stainless steel, zinc-coated or other approved corrosion-resistive
fasteners. Where the basic wind speed per Figure R301.2(4) is 110 miles per hour
(49 m/s) or higher, the attachment of wall coverings shall be designed to resist the
component and cladding loads specified in Table R301.2(2).
• Table R703.4 covers all prescriptive exterior weather-resistant siding
attachment.
• The requirements are broken down by siding material in the left column.
• The table also identifies attachment based on support for each material.
• Pay particular attention to the footnotes as applicable (a through z).
60 of 66
Wall Covering – Exterior Table R703.4 & Section R703.4
61 of 66
Wall Covering – Exterior Other specific requirements for exterior wall covering:
R703.5 – Wood shakes and shingles
R703.6 – Exterior plaster
R703.7 – Stone and masonry veneer
R703.9 – Exterior insulation and finish systems (EIFS)
R703.10 – Fiber cement siding
R703.11 – Vinyl siding
R703.12 – Adhered masonry veneer
62 of 66
Wall Covering – Exterior
R703.8 Flashing. Approved corrosion-resistant flashing shall be applied shingle-
fashion in a manner to prevent entry of water into the wall cavity or penetration of
water to the building structural framing components and redirect it to the exterior.
Self-adhered membranes used as flashing shall comply with AAMA 711. The
flashing shall extend to the surface of the exterior wall finish. Approved corrosion-
resistant flashings shall be installed at all of the following locations:
1. Exterior window and door openings. Flashing at exterior window and door
openings shall extend to the surface of the exterior wall finish or to the water-
resistive barrier for subsequent drainage.
63 of 66
Wall Covering – Exterior Flashing requirements for exterior walls (continued)
R703.8 Flashing…
Approved corrosion-resistant flashings shall be installed at all of the following
locations:
2. At the intersection of chimneys or other masonry construction with frame or
stucco walls, with projecting lips on both sides under stucco copings.
3. Under and at the ends of masonry, wood or metal copings and sills.
64 of 66
Wall Covering – Exterior Flashing requirements for exterior walls (continued)
R703.8 Flashing…
Approved corrosion-resistant flashings shall be installed at all of the following
locations:
4. Continuously above all projecting wood trim.
Includes:
Windows
& Doors
65 of 66
Wall Covering – Exterior Flashing requirements for exterior walls (continued)
R703.8 Flashing…
Approved corrosion-resistant flashings shall be installed at all of the following
locations:
5. Where exterior porches, decks or stairs attach to a wall or floor assembly of
wood-frame construction.
66 of 66
Wall Covering – Exterior Flashing requirements for exterior walls (continued)
R703.8 Flashing…
Approved corrosion-resistant flashings shall be installed at all of the following
locations:
6. At wall and roof intersections. Kick-out flashings shall be installed at all wall and
roof intersections, such as where a lower roofline terminates against a vertical wall
[see Figure R703.8(1)].
7. At built-in gutters.