sso.hydro.mb.ca · web viewthe ultimate objective of this assessment is to identify eso’s that...

49
Multi-Zone AHU As-Found Audit information System Description: Building Name: Building Address: Building Description: Name of Auditor: Date of Audit:

Upload: others

Post on 18-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

Multi-Zone AHU

As-Found Audit information

System Description:

Building Name:

Building Address:

Building Description:

Name of Auditor:

Date of Audit:

Page 2: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 1 of 30

Current System General Assessment

This Template is a suggested approach to standardize the information collected from a Multi-Zone Air Handling System. This tool has been designed for use on a Windows based PC or tablet using Microsoft Office Word 2007 or newer. Through the use of screen captures and pull-down menu options this tool will assist in summarizing the As-Found details and operational sequences for this equipment.

Template Guide

a) Screen-Shot: Where screen shots are indicated, a short instructional image is provided with a step-by-step procedure designed to assist a novice Windows user in the capturing of a specific view from a PC screen and placement within this document. The approach described is one of many variants possible which is intended to provide a general description to provide the results being sought. (See example below…)

b) Text Prompts: Where specific information is required, blank text boxes and prompts have been provided for data entry. To enter data in these fields, simply click on the grey box and start typing in relevant information to correspond with the category heading. The box size will adjust to accommodate the amount of text entered into the field. (See example below…)

Page 3: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 2 of 30

c) Pull-Down Menus: Throughout the document pull-down menus have been provided with a list of options available to select from. Obviously not all possible choices for each category could be anticipated for each category – in these cases a blank field has been made available to record specific details for each category. Where blank fields have been provided, the pull-down menus have been provided as a convenience and should not be considered as the only options from which to select from for each category. Where a pull-down menu is used to confirm whether a line item has been reviewed or not, select a suitable response to complete the form. (See examples below…)

d) Additional Remarks (column): This field has been provided as another area to add any additional comments deemed relevant by the system assessor for each category. Information included in this column is entirely optional and at the discretion of the system assessor. (See example below…)

e) Check-boxes: The use of check-boxes provides a quick means of documenting large amounts of repetitive information in a clean and organized fashion. To open up the Check Box Field Options window, double-click on the grey box to be checked and select the Checked option under the Default value – then select OK. (See example below…)

Page 4: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 3 of 30

f) System equipment selection check-boxes: The use of check-boxes provides an easy and efficient way of identifying the equipment and features of a particular system. To identify equipment as part of the system, select the check-box next to the equipment title, double-click on the grey box and select the Checked option under the Default value – then select OK. Once the check-box is checked, the equipment section may be filled in. If equipment listed in the template is not part of the system, check the check-box next to “Not Applicable” by following the same procedure as described above. If the equipment is checked as “Not Applicable”, the section contents can be deleted leaving only the section title to clearly show that it is not relevant to the particular system. (See example below…)

g) Y or N: Another quick means of documenting large amounts of repetitive information in a clean and organized fashion, similar to check-boxes, is the Y (for Yes) and N (for No) entry fields. These fields provide a positive or negative response to the topic listed at the top of the column. Simply enter a Y or N in the grey field provided. (See example below…)

h) General Editing and Document Maintenance: Beyond all the special features of the template, it is essentially a word document when completed. Where excess screen-shot categories, text-prompts, unused pull-down menus or redundant rows remain after entering all relevant information pertaining to the AHU, the user should tidy-up the document by deleting any unused or redundant template clutter to complete the process and produce a clean informative document representative of the effort put into completing it. The Template Guide Section (shown in blue) instructions and diagrams should also be deleted once the document is complete.

Page 5: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 4 of 30

i) Alternate Formats: In circumstances where alternate documents are used in place of this template, Manitoba Hydro will require all categories indicated in this template will be included and suitable description will be provided.

Energy Saving Opportunities (ESO’s)

The ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements for this particular system. In support of this objective, a list of Common Energy Saving Opportunities (ESO’s) has been provided in Table MZa of this Template (Review All Line Items on Table MZa – Current System | Common AHU Energy Saving Opportunities …on the next page). Table MZb has been included for any other ESO’s that can be identified (See MZb – Current System | PBC Purposed AHU Energy Saving Opportunities) . The far right column of Table 4a – Current System | AHU Sequences of Operation Assessment has been included to document all ESO recommendations for this system (See example below…).

Page 6: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 5 of 30

Table MZa – Current System | Common AHU Energy Saving Opportunities (ESO’s):Air Handling Unit (AHU) Considerations

ESO Reviewed (select √ or Not Applicable)1. Revise control sequence:

1.1. [select] Modify AHU Optimum Start to maintain the mixed air dampers in full return air mode for maximum reasonable time after the Occupied Start time.

1.2. [select] Implement a Pre-Occupied Purge Mode.1.3. [select] Apply PID loop-tuning to mixed air damper control to improve control stability.1.4. [select] Seasonally reset hot and cold deck supply air temperature control to meet space heating and

cooling demands.1.5. [select] Reset hot and cold deck supply air temperature control to actively meet space heating and cooling

demands.1.6. [select] Reset humidity set-point to the outdoor air temperature based on a reset schedule designed to

include the heat loss through the window to prevent condensation on the windows.2. Optimize Equipment Run-Time:

2.1. [select] Revise heat pump compressor stages sequencing for optimal energy use (consider equal run-time as part of control sequence revisions).

2.2. [select] Implement Run-Time totalization to track equipment use for Persistence Monitoring use later in the EBOP program.

3. Optimize AHU control schedule:3.1. [select] Based on current building occupant use, adjust AHU Occupied start and stop times3.2. [select] Confirm AHU control schedule includes unoccupied programming for all statutory holidays, etc.

4. Coordinate HVAC air flow balance and control air flow measurement:4.1. [select] Confirm with the qualified TAB agency that the space static pressure control is effectively being

managed at three separate seasons: Summer, Shoulder Season & Winter.5. Control Device Adjustment:

5.1. [select] Adjust linkage and actuator for positive closure of motorized damper on outdoor wall.5.2. [select] Adjust control valve travel and stops for positive closure (or full-bypass) of valve – replace valve if

seat is worn or adjustment is not possible.5.3. [select] Adjust proving device for positive indication of equipment operation.5.4. [select] Adjust temperature control for accurate operation.5.5. [select] Adjust humidity control for accurate operation.5.6. [select] Adjust pressure control for accurate operation.5.7. [select] Adjust hot and cold deck damper linkage and actuator for accurate zone temperature control and

to mitigate potential simultaneous heating and cooling.6. Control sensor calibration:

6.1. [select] Validate all control sensors are indicating values within reasonable tolerance of the product range of accuracy (or control industry standards).

6.2. [select] Where reliable sensor calibration cannot be accomplished across a reasonable range of measured values, arrange for the sensor to be replaced.

6.3. [select] Where a sensor is being adversely influenced by placement in sunlight, close proximity to a heat-source, or other similar, arrange for the sensor to be relocated.

7. Additional measures:7.1. [select]      7.2. [select]      7.3. [select]      7.4. [select]      7.5. [select]      

Page 7: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 6 of 30

1. CURRENT SYSTEM DESCRIPTION

Figure 1a: Graphic Screen-Shot of Current System, (as available from BAS)

Page 8: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 7 of 30

Figure 1b: Graphic Screen-Shot of Current System, (as available from BAS)

Page 9: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 8 of 30

Figure 1c: Graphic Screen-Shot of Current System, (as available from BAS)

Page 10: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 9 of 30

1.1 Role and Placement of this HVAC system within the Building:

     

Page 11: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 10 of 30

Table 1a – Current System | AHU Description:

Air Handling Unit (AHU) Ventilation Components per AHU SystemAdditional Remarks

1. Fan Assemblies: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Supply Fan:      Location:      

Quantity:            CFM (total max AF)

Motor Power:       Units [Choose an item] [Actual/Estimated]Motor Efficiency:      % [Actual/Estimated]Motor Load:       Units [Choose an item] [Actual/Estimated]

     

b. Fan Configuration [Choose an item]      Fan Control Options [Choose an item]      Location:      

Quantity:            CFM (total max AF)

Motor Power:       Units [Choose an item] [Actual/Estimated]Motor Efficiency:      % [Actual/Estimated]Motor Load:       Units [Choose an item] [Actual/Estimated]

     

c. Fan Configuration [Choose an item]      Fan Control Options [Choose an item]      Location:      

Quantity:            CFM (total max AF)

Motor Power:       Units [Choose an item] [Actual/Estimated]Motor Efficiency:      % [Actual/Estimated]Motor Load:       Units [Choose an item] [Actual/Estimated]

     

d. Fan Configuration [Choose an item]      Fan Control Options [Choose an item]      Location:      

Quantity:            CFM (total max AF)

Motor Power:       Units [Choose an item] [Actual/Estimated]Motor Efficiency:      % [Actual/Estimated]Motor Load:       Units [Choose an item] [Actual/Estimated]

     

e. Fan Configuration [Choose an item]      Fan Control Options [Choose an item]      Location:      

Quantity:            CFM (total max AF)

Motor Power:       Units [Choose an item] [Actual/Estimated]

     

Page 12: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 11 of 30

Motor Efficiency:      % [Actual/Estimated]Motor Load:       Units [Choose an item] [Actual/Estimated]

2. Motorized Damper Control: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Common Control Signal [Choose an item] Common Damper Selection [Choose an item]b. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]c. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]d. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]e. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]f. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]g. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]h. Dedicated Control Signal [Choose an item] Dedicated Damper Selection [Choose an item]

Additional Remarks:      3. Coil Assemblies:

Not Applicable (Check this box and erase details below if this system does not exist in the building)a. Coil Placement [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Primary Control [Choose an item]      Primary Configuration [Choose an item]      Primary Coil Energy Transfer to Air:       Units [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Secondary Control [Choose an item]      Secondary Configuration [Choose an item]      Secondary Coil Energy Transfer to Air:       Units [Choose an item]

Additional Remarks:      

     

b. Coil Placement [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Primary Control [Choose an item]      Primary Configuration [Choose an item]      Primary Coil Energy Transfer to Air:       Units [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Secondary Control [Choose an item]      Secondary Configuration [Choose an item]      Secondary Coil Energy Transfer to Air:       Units [Choose an item]

Additional Remarks:      

     

c. Coil Placement [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Primary Control [Choose an item]      Primary Configuration [Choose an item]      Primary Coil Energy Transfer to Air:       Units [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Secondary Control [Choose an item]      Secondary Configuration [Choose an item]      Secondary Coil Energy Transfer to Air:       Units [Choose an item]

     

Page 13: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 12 of 30

Additional Remarks:      d. Coil Placement [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Primary Control [Choose an item]      Primary Configuration [Choose an item]      Primary Coil Energy Transfer to Air:       Units [Choose an item]

Heating-Cooling Medium/Source [Choose an item]      Secondary Control [Choose an item]      Secondary Configuration [Choose an item]      Secondary Coil Energy Transfer to Air:       Units [Choose an item]

Additional Remarks:      

     

4. Heat Recovery Assemblies: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Heat Recovery Type [Choose an item]Auxiliary Load [Choose an item]       Units [Choose an item]Type of Recovery [Choose an item]      Heat Recovery Classification [Choose an item]      Heat Recovery Standard [Choose an item]      

Additional Remarks:      

     

b. Heat Recovery Type [Choose an item]Auxiliary Load [Choose an item]       Units [Choose an item]Type of Recovery [Choose an item]      Heat Recovery Classification [Choose an item]      Heat Recovery Standard [Choose an item]      

Additional Remarks:      

     

5. Multi-Zone AHU Air Distribution: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Number of Zones:      Actuator Control [Choose an item]

Additional Remarks:      

     

6. HVAC Controls: Primary Equipment:a. Controller Type [Choose an item]      

Man-To-Machine Interface [Choose an item]      Historic Data Collection [Choose an item]      Historic Data Available Memory Capacity [Choose an item]      Remote Access [Choose an item]      Additional Remarks:      

Page 14: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 13 of 30

Table 1b – Current System | Terminal Unit Air Distribution Description:Air Distribution (Terminal Unit) Ventilation Components per AHU System Additional Remarks1. Unit Heater (UH):

Not Applicable (Check this box and erase details below if this system does not exist in the building)a. Unit Heater Style [Choose an item]      

Unit Heater Control [Choose an item]      Quantity:      

     

b. Unit Heater Style [Choose an item]      Unit Heater Control [Choose an item]      Quantity:      

     

c. Unit Heater Style [Choose an item]      Unit Heater Control [Choose an item]      Quantity:      

     

d. Unit Heater Style [Choose an item]      Unit Heater Control [Choose an item]      Quantity:      

     

e. Unit Heater Style [Choose an item]      Unit Heater Control [Choose an item]      Quantity:      

     

2. Fan Coils: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Fan Coil Style [Choose an item]      Fan Coil Control [Choose an item]      Quantity:      

     

b. Fan Coil Style [Choose an item]      Fan Coil Control [Choose an item]      Quantity:      

     

c. Fan Coil Style [Choose an item]      Fan Coil Control [Choose an item]      Quantity:      

     

d. Fan Coil Style [Choose an item]      Fan Coil Control [Choose an item]      Quantity:      

     

3. Radiant Heating (Separate from TU Zone Control): Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Heating Type [Choose an item]      Effective Length [Choose an item]       Units [Choose an item]Surface Area Heated:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

b. Heating Type [Choose an item]      Effective Length [Choose an item]       Units [Choose an item]Surface Area Heated:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

c. Heating Type [Choose an item]      

Page 15: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 14 of 30

Effective Length [Choose an item]       Units [Choose an item]Surface Area Heated:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

4. Overhead Cooling: Not Applicable (Check this box and erase details below if this system does not exist in the building)

a. Cooling Type [Choose an item]      Effective Length [Choose an item]       Units [Choose an item]Surface Area Cooled:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

b. Cooling Type [Choose an item]      Effective Length [Choose an item]       Units [Choose an item]Surface Area Cooled:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

c. Cooling Type [Choose an item]      Effective Length [Choose an item]       Units [Choose an item]Surface Area Cooled:       Units [Choose an item]Control [Choose an item]      Quantity:      Zone Names:      

     

5. HVAC Controls: Terminal Unit (TU) Controllera. Controller Type [Choose an item]      

Man-To-Machine Interface [Choose an item]      Historic Data Collection [Choose an item]      Historic Data Available Memory Capacity [Choose an item]      Remote Access [Choose an item]      Additional Remarks:      

Page 16: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 15 of 30

2. CURRENT CONTROL POINTS

Table 2a – Current System | AHU Control Points:Air Handling Unit (AHU) Ventilation ComponentsControl Outputs

Control Points per AHU System

Bin

ary

Ana

log

Ope

ratio

nal

Tre

nd-R

eady Additional Remarks

1. Damper Control:Mixed Air Control Signal [Choose an item]Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]     

     

2. Fan Control:MCC: Supply fanReturn Fan [Choose an item]Relief Fan [Choose an item]Exhaust Fan [Choose an item]Injection Fan [Choose an item]     

     

3. Heat Recovery:Heat Recovery Control [Choose an item]     

     

4. Pre-Heat:Pre-Heat Control [Choose an item]     

     

5. Pre-Heat Coil Circ. Pump:Pre-Heat Coil Circ. Pump [Choose an item]     

     

6. Main Heat:Heating Control [Choose an item]     

     

7. Heating Coil Circ. Pump:Pre-Heat Coil Circ Pump [Choose an item]     

     

8. Cooling:Cooling Control [Choose an item]     

     

9. Humidification:Humidification Control [Choose an item]     

     

10. Multi-Zone AHU Air Distribution:Damper Control Signal [Choose an item]Damper Control Signal [Choose an item]     

     

11.      :

Page 17: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 16 of 30

          

     

Table 2a (continued) – Current System | AHU Control Points:Air Handling Unit (AHU) Ventilation ComponentsControl Inputs

Control Points per AHU System

Bin

ary

Ana

log

Acc

urat

e

Tre

nd-R

eady Set-Point

(where applicable)Fixed-or-resetA1 resetA2 resetB1 resetB2 1

1. BAS Input [Choose an item]2. BAS Input [Choose an item]3. BAS Input [Choose an item]4. BAS Input [Choose an item]5. BAS Input [Choose an item]6. BAS Input [Choose an item]7. BAS Input [Choose an item]8. BAS Input [Choose an item]9. BAS Input [Choose an item]10. BAS Input [Choose an item]11. BAS Input [Choose an item]12. BAS Input [Choose an item]13. BAS Input [Choose an item]14. BAS Input [Choose an item]15. BAS Input [Choose an item]16. BAS Input [Choose an item]17. BAS Input [Choose an item]18. BAS Input [Choose an item]19. BAS Input [Choose an item]20. BAS Input [Choose an item]21. BAS Input [Choose an item]22. BAS Input [Choose an item]23. BAS Input [Choose an item]24. BAS Input [Choose an item]25. BAS Input [Choose an item]26. BAS Input [Choose an item]27. BAS Input [Choose an item]28. BAS Input [Choose an item]29. BAS Input [Choose an item]30. BAS Input [Choose an item]31. BAS Input [Choose an item]32. BAS Input [Choose an item]33. BAS Input [Choose an item]34. BAS Input [Choose an item]35. BAS Input [Choose an item]36. BAS Input [Choose an item]37.      

:                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       :                       

Table 2b – Current System | Terminal Unit Control Points:Air Distribution (Terminal Unit) Ventilation Components1 resetA1 & resetA2: upper and lower reference values used for resetB1 & resetB2, (i.e. for example Boiler Reset: resetA1: OAT5°C, resetA2: OAT-35°C, resetB1: 60°C, reset B2: 90°C)

Page 18: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 17 of 30

Control Values

Control Points per AHU System

Bin

ary

Ana

log

Ope

ratio

nal

Tre

nd-R

eady Set-Point

(where applicable)Fixed-or-resetA1 resetA2 resetB1 resetB2 2

1. Unit HeaterTU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]     

:                       :                       :                       :                       :                       

2. Fan CoilTU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]     

:                       :                       :                       :                       :                       

3. Radiant Heater (Separate from TU Zone Control)TU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]     

:                       :                       :                       :                       :                       

4. Overhead CoolingTU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]TU Control Signal [Choose an item]     

:                       :                       :                       :                       :                       

5.                               

:                       :                       :                       :                       :                       

6.                               

:                       :                       :                       :                       :                       

2 resetA1 & resetA2: upper and lower reference values used for resetB1 & resetB2, (i.e. for example Boiler Reset: resetA1: OAT5C, resetA2: OAT-35C, resetB1: 60C, reset B2: 90C)

Page 19: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 18 of 30

3. CURRENT OPERATION

Table 3a – Current System | AHU Modes of Operation | AHU Sequences of Operation:Air Handling Unit (AHU) Ventilation Components1. Unoccupied Shut-Down Mode:Damper Control [Choose an item]       AHU Fan Control [Choose an item]       Fan Control [Choose an item]      AHU Hot Deck Temperature Control [Choose an item]       AHU Cold Deck Temperature Control [Choose an item]       Zone Temperature Control [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]      

Fail-Safe Humidification [Choose an item]      

2. Start-Up Mode No Cold-Weather Start-Up:AHU Fan Start [Choose an item]       Fan Start [Choose an item]      

Damper Control [Choose an item]       AHU Hot Deck Temperature Control [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]       Building Pressure Control [Choose an item]      

3. Pre-Occupied Warm-Up Mode:AHU System Warm-Up Operation [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]      

4. Pre-Occupied Cool-Down Mode:AHU System Pre-Cool Operation [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]      

5. Pre-Occupied Purge Mode:AHU System Pre-Purge Operation [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]      

6. Occupied Normal Mode:AHU Fan Control [Choose an item]       AHU Return Fan Air Flow Control [Choose an item]       Building Pressure Control [Choose an item]       Fresh Air to Building Control [Choose an item]      

Economizer Switch Point [Choose an item]       Units [Choose an item]      

Heat Recovery Control [Choose an item]       Cooling Recovery Control [Choose an item]      

AHU Mixed Air Control [Choose an item]       AHU Heating Control [Choose an item]       AHU Cooling Control [Choose an item]       AHU Hot Deck Heating Control [Choose an item]       AHU Cold Deck Cooling Control [Choose an item]       Zone Temperature Control [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]      

AHU Humidity Control [Choose an item]      

Emergency Shut-Down Control [Choose an item]       Emergency Shut-Down Control [Choose an item]      

7. Fail-Safe Shut-Down Mode: Fan Fails to Prove Normal Op’n. Low Temperature Detection Smoke Detection Fire Alarm      

Fail-Safe Dampers [Choose an item]       Fail-Safe Fans [Choose an item]       Fail-Safe Heating [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]       Fail-Safe Cooling [Choose an item]       Fail-Safe Humidification [Choose an item]       Fail-Safe Multi-Zone Dampers [Choose an item]      

Page 20: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 19 of 30

8. Emergency Fan Over-Ride Mode: Automated Smoke Evacuation Mode Fire Panel Manual Fan Control

Fail-Safe Dampers [Choose an item]       Fail-Safe Fans [Choose an item]       Fail-Safe Heating [Choose an item]       Heating Coil Circ. Pump Control [Choose an item]       Fail-Safe Cooling [Choose an item]       Fail-Safe Humidification [Choose an item]      

9.      Mode:     

10.      Mode:     

11.      Mode:     

12.      Mode:     

13.      Mode:     

Page 21: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 20 of 30

Table 3b – Current System | Terminal Unit Modes of Operation:Air Distribution (Terminal Unit) Ventilation ComponentsModes Additional Remarks

1. Unoccupied Mode:i. No TU participation in unoccupied modes

ii. Set-back temperature set-pointiii. TU damper open to full flowiv. TU damper closes to low flowv. TU fan(s) on continuous

vi. TU fan(s) off continuousvii. TU fan(s) cycle for temporary heating mode

viii. TU fan(s) cycle for temporary cooling modeix.      

     

2. Start-Up Mode:i. No TU participation in start-up

ii. TU fan speed ramp-upiii. Staggered TU fan start-upiv. All TU fans start-up simultaneouslyv.      

     

3. Warm-Up, Cold Weather:i. No TU participation in warm-up

ii. TU fan speed ramp-upiii. Staggered TU fan start-upiv. TU damper open to full flowv. All TU fans start-up simultaneously

vi.      

     

4. Cool-Down, Hot Weather:i. No TU participation in cool-down

ii. TU damper open to full flowiii.      

     

5. Pre-Occupied Purge Mode:i. No TU participation in purge

ii. TU supports purgeiii. TU damper open to full flowiv. TU damper open to       % higher flowv.      

     

6. Occupied Normal Mode:i. No TU occupied normal mode

ii. Normal TU operationiii.      

     

7. Emergency Fan Over-Ride Mode:i. No TU participation in emergency modes

ii. TU supports emergency modesiii.      

     

8. Fail-Safe Shut-Down Mode:i. No TU participation in fail-safe modes

ii. TU supports fail-safe modesiii.      

     

Page 22: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 21 of 30

Table 4a – Current System | AHU Sequences of Operation Assessment:Air Handling Unit (AHU) Ventilation Components

Prior to any in-depth functional test, it is recommended during the ESO Investigation phase to verify proper system operation under normal operating conditions over time. Commonly, operational issues may not be apparent when a system is “forced” into a particular operational state via over-riding sensors or changing set-points. Utilizing existing BAS Trending capabilities or Stand-Alone Data-Loggers is recommended to capture and verify actual system operation under normal operating conditions. Trend measurement sample rates between 1 & 5 minutes or based Change-Of-Value (COV) are recommended over a time period of 2 weeks to include at least one Monday morning following recovery after a weekend. Select a minimum group of trended points to meet the analysis requirements of this template.

Refer to recommended actions for ESO’s listed in Table MZa and MZb ->

Tabl

e M

Za &

MZb

ESO

#

Obs

erve

d to

be

oper

ation

al:

Y or

N

Ener

gy S

avin

g O

ppor

tuni

ty:

Y or

N

1. Unoccupied Mode:1.1. Confirm:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d) Operational Sequence Checks [Choose an item]e) Operational Sequence Checks [Choose an item]f) Operational Sequence Checks [Choose an item]g) Operational Sequence Checks [Choose an item]h) Operational Sequence Checks [Choose an item]i) Operational Sequence Checks [Choose an item]j) Operational Sequence Checks [Choose an item]k) Operational Sequence Checks [Choose an item]l) Operational Sequence Checks [Choose an item]m) Operational Sequence Checks [Choose an item]n)      o)      p)      

1.2. Confirm when OAT ≥ 5°C:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c)      

1.3. Confirm when OAT < 4°C:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c)      

                                                                                

               

               

                                                                                

               

               

2. Start-Up Mode:2.1. Confirm thru changing BAS system clock to test Start-Up programming:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d) Operational Sequence Checks [Choose an item]e) Operational Sequence Checks [Choose an item]f) Operational Sequence Checks [Choose an item]g) Operational Sequence Checks [Choose an item]h) Operational Sequence Checks [Choose an item]i)      

                                             

                                             

Page 23: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 22 of 30

Table 4a (continued) – Current System | AHU Sequences of Operation Assessment:Air Handling Unit (AHU) Ventilation ComponentsPrior to any in-depth functional test, it is recommended during the ESO Investigation phase to verify proper system operation under normal operating conditions over time. Commonly, operational issues may not be apparent when a system is “forced” into a particular operational state via over-riding sensors or changing set-points. Utilizing existing BAS Trending capabilities or Stand-Alone Data-Loggers is recommended to capture and verify actual system operation under normal operating conditions. Trend measurement sample rates between 1 & 5 minutes or based Change-Of-Value (COV) are recommended over a time period of 2 weeks to include at least one Monday morning following recovery after a weekend. Select a minimum group of trended points to meet the analysis requirements of this template.

Refer to recommended actions for ESO’s listed in Table MZa and MZb ->

Tabl

e M

Za &

MZb

ESO

#

Obs

erve

d to

be

oper

ation

al:

Y or

N

Ener

gy S

avin

g O

ppor

tuni

ty:

Y or

N

3. Pre-Occupied Warm-Up Mode:3.1. Confirm thru changing BAS system clock to test start-up programming:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d) Operational Sequence Checks [Choose an item]e)      

                         

                         

4. Pre-Occupied Cool-Down Mode:4.1. Confirm thru changing BAS system clock to test start-up programming:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d)      

                    

                    

5. Pre-Occupied Purge Mode:5.1. Confirm thru changing BAS system clock to test start-up programming:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d)      

                    

                    

Page 24: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 23 of 30

Table 4a (continued) – Current System | AHU Sequences of Operation Assessment:Air Handling Unit (AHU) Ventilation ComponentsPrior to any in-depth functional test, it is recommended during the ESO Investigation phase to verify proper system operation under normal operating conditions over time. Commonly, operational issues may not be apparent when a system is “forced” into a particular operational state via over-riding sensors or changing set-points. Utilizing existing BAS Trending capabilities or Stand-Alone Data-Loggers is recommended to capture and verify actual system operation under normal operating conditions. Trend measurement sample rates between 1 & 5 minutes or based Change-Of-Value (COV) are recommended over a time period of 2 weeks to include at least one Monday morning following recovery after a weekend. Select a minimum group of trended points to meet the analysis requirements of this template.

Refer to recommended actions for ESO’s listed in Table MZa and MZb ->

Tabl

e M

Za &

MZb

ESO

#

Obs

erve

d to

be

oper

ation

al:

Y or

N

Ener

gy S

avin

g O

ppor

tuni

ty:

Y or

N

6. Occupied Normal Mode:6.1. Confirm thru Trend Data, Trend Graphs and supervised over-ride testing:a) Operational Sequence Checks [Choose an item]b) Operational Sequence Checks [Choose an item]c) Operational Sequence Checks [Choose an item]d) Operational Sequence Checks [Choose an item]e) Operational Sequence Checks [Choose an item]f) Operational Sequence Checks [Choose an item]g) Operational Sequence Checks [Choose an item]h) Operational Sequence Checks [Choose an item]i) Operational Sequence Checks [Choose an item]j) Operational Sequence Checks [Choose an item]k) Operational Sequence Checks [Choose an item]l) Operational Sequence Checks [Choose an item]m) Operational Sequence Checks [Choose an item]n) Operational Sequence Checks [Choose an item]o) Operational Sequence Checks [Choose an item]p) Operational Sequence Checks [Choose an item]q) Operational Sequence Checks [Choose an item]r) Operational Sequence Checks [Choose an item]s) Operational Sequence Checks [Choose an item]t) Operational Sequence Checks [Choose an item]u) Operational Sequence Checks [Choose an item]v) Operational Sequence Checks [Choose an item]w) Operational Sequence Checks [Choose an item]x) Operational Sequence Checks [Choose an item]y) Operational Sequence Checks [Choose an item]z) Operational Sequence Checks [Choose an item]aa) Operational Sequence Checks [Choose an item]bb) Operational Sequence Checks [Choose an item]cc)      dd)      

                                                                                                                                                      

                                                                                                                                                      

Page 25: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 24 of 30

Current Trend Graph Screen-Shot, reference EBOP ESO:      

Page 26: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 25 of 30

Current Trend Graph Screen-Shot, reference EBOP ESO:      

Page 27: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 26 of 30

Current Trend Graph Screen-Shot, reference EBOP ESO:      

Page 28: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 27 of 30

Current Trend Graph Screen-Shot, reference EBOP ESO:      

Page 29: sso.hydro.mb.ca · Web viewThe ultimate objective of this assessment is to identify ESO’s that can be considered for Energy Conservation Measures within the Program requirements

As Found System Template: Multi-Zone AHU Page 28 of 30

Current Trend Graph Screen-Shot, reference EBOP ESO:      

Available in accessible formats upon request.