single-phase-lab-report

5
Single Phase Inverter 1.1 Introduction An inverter is a DC to AC converter that converts a DC voltage into an AC of variable voltage and variable frequency. They are also referred as Voltage Source Inverters. In inverter circuits power semi conductor devices such as thyristors, MOSFETs, IGBTs, BJTs and GTOs can be used. If a thyristor is used, forced commutation circuits are required to turn it OFF. A MOSFET and IGBT are fully controlled devices. If they are used, a very high switching frequency can be implemented. 1.2 Pulse-width modulation (PWM) It is a technique used to control the power supplied to electrical devices, especially to loads. The average value of voltage fed to the load is controlled by turning the switch on and off at a fast rate.The longer the switch is on the higher the total power supplied to the load. The PWM switching frequency has to be much higher so the resultant waveform must be as smooth as possible. The frequencies at which the power supply must switch depend on load and application. The term duty cycle describes the proportion of 'on' time to the regular interval or 'period' of time. = Where D is the duty cycle, Ts is the total period ton is the a time for which the switch is ON. A low duty cycle corresponds to low power, because the power is off for most of the time. Duty cycle is expressed in percent, 100% being fully on. The main advantage of PWM is that power loss in the switching devices is very low. When a switch is off there is practically no current, and when it is on and power is being transferred to the load, there is almost no voltage drop across the switch. Power loss, being the product of voltage and current, is thus in both cases close to zero. PWM also works well with digital controls, which, because of their ON/OFF nature, can easily set the needed duty cycle.

Upload: malik-zaid

Post on 06-Jan-2017

118 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: single-phase-lab-report

Single Phase Inverter

1.1 Introduction

An inverter is a DC to AC converter that converts a DC voltage into an AC of

variable voltage and variable frequency. They are also referred as Voltage

Source Inverters. In inverter circuits power semi conductor devices such as

thyristors, MOSFETs, IGBTs, BJTs and GTOs can be used. If a thyristor is used,

forced commutation circuits are required to turn it OFF. A MOSFET and IGBT are

fully controlled devices. If they are used, a very high switching frequency can be

implemented.

1.2 Pulse-width modulation (PWM)

It is a technique used to control the power supplied to electrical devices,

especially to loads. The average value of voltage fed to the load is controlled by

turning the switch on and off at a fast rate.The longer the switch is on the higher

the total power supplied to the load. The PWM switching frequency has to be

much higher so the resultant waveform must be as smooth as possible. The

frequencies at which the power supply must switch depend on load and

application. The term duty cycle describes the proportion of 'on' time to the

regular interval or 'period' of time.

𝑡𝑜𝑛 = 𝐷𝑇𝑠

Where D is the duty cycle,

Ts is the total period

ton is the a time for which the switch is ON.

A low duty cycle corresponds to low power, because the power is off for most of

the time. Duty cycle is expressed in percent, 100% being fully on.

The main advantage of PWM is that power loss in the switching devices is very

low. When a switch is off there is practically no current, and when it is on and

power is being transferred to the load, there is almost no voltage drop across the

switch. Power loss, being the product of voltage and current, is thus in both

cases close to zero. PWM also works well with digital controls, which, because of

their ON/OFF nature, can easily set the needed duty cycle.

Page 2: single-phase-lab-report

Here we discuss some techniques of pulse width modulation.

1.2.1 Single Pulse Width Modulation

In single pulse width modulation control, there is only one pulse per half cycle

and the output rms voltage is changed by varying the width of the pulse. The

gating signals are generated by comparing the rectangular control signal of

amplitude with triangular carrier signal. The frequency of the control signal

determines the fundamental frequency of output voltage.

1.3 Single Phase Half Bridge Inverter

1.3.1 Introduction

It is known as basic building blocks for full bridge, three phase inverters. There

are 2 switches, dividing the dc source voltage into two parts with the capacitors.

Each capacitor has the same value and has voltage Vdc / 2. The top (S1) and

bottom (S2) switch must be complementary to each other. When S1 is closed, S2

must be opened and vice versa. Feedback (freewheeling) diodes are required to

provide continuity of current for inductive loads but for resistive loads they have

no role. It provides current to flow even switches are opened. Using a diode in

parallel with a unidirectional device is common practice. Should the device be

subjected to a reverse-polarity voltage, a dangerous situation might occur. If the

voltage is high enough, an electric arc might destroy the device. With a diode,

however, applying a reverse voltage will result in current owing through the

diode. This may only destroy the diode, which can be easily and inexpensively

replaced.

Page 3: single-phase-lab-report

For Resistive load

As our output is square wave it is also known as square wave inverter.

For inductive load

1.4 Full Bridge single phase inverter

1.4.1 Introduction

Single phase full bridge inverter consists of four SCRs and four diodes. For Full

bridge inverter when T1, T2 conduct, load voltage is Vs and T3, T4 conduct load

voltage is –Vs. Frequency of output voltage can be controlled by varying the

periodic time T. During inverter operation it should be ensured that two thyristors

in the same branch should not conduct simultaneously as this would lead to a

direct short circuit of the source. For inductive load, load voltage and load current

Page 4: single-phase-lab-report

will not be in phase with each other. In this case diodes D1, D2, D3 and D4

connected in anti-parallel will thyristors will allow the current to flow when main

thyristors are turned off. As the energy is fed back to the dc source when these

diodes conduct, these are called feedback diodes. Operation of series R-L-C

load can be explained for R-L-C under damped and over damped load. R-L-C

Over Damped Load: Before t = 0, thyristors T3 and T4 are conducting and load

current i0 is flowing from B to A, i.e. in reverse direction. This current is at t =0.

After T3 and T4 are turned off at t = 0, current cannot change its direction

immediately because if the nature of load. As a result diodes D1 and D2 starts

conducting after t = 0 and allow i0 to flow against the supply voltage Vs. A soon

as D1 and D2 begin to conduct, the load is subjected to Vs. Though T1 and T2

are gated at t = 0, these SCRs will not turn on as these are reverse biased by the

voltage drop across the diodes D1 and D2. When Load current through D1 and

D2 falls to zero, T1 and T2 becomes forward biased by source voltage Vs. Now

T1 and T2 get turned on as these are gated for the period of T/2 seconds. Now

load current flows in the positive direction from A to B. At t = T/2; T1 and T2 are

turned off by forced commutation and as load current cannot reverse

immediately, diodes D3 and D4 come into conduction to allow the flow of current

i0 after T/2. Thyristor T3 and T4 though gated will not turn on as these are

reverse biased by the voltage drop in diodes D3 and D4. When the current in

diodes D3 and D4 drops to zero; T3 and T4 are turned on as these are already

gated R-L-C Over Damped Load: For R-L-C under damped load after t = 0,

thyristor T1 and T2 are carrying load current . As i0 through T1 and T2 reduces

to zero at t1, these SCRs are turned off before T3 and T4 are gated. As T1 and

T2 stops conducting, current through the load reverses and now is carried by

diodes D1 and D2 as T3 and T4 are not yet gated. The diodes D1 and D2 are

connected in anti-parallel to T1 and T2; the voltage drop in these diodes appears

as a reverse bias across T1 and T2. If the duration of reverse bias is more than

the SCR turn off time; T1 and T2 will get commutated naturally and therefore no

commutation circuitry is needed. This method of commutation is known as load

commutation.

Page 5: single-phase-lab-report

For Resistive load

For inductive load