![Page 1: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/1.jpg)
Simulation Models for Single Phase Compressor Motors
Bernie Lesieutre (UW-Madison, LBNL)
NERC FIDVR and Dynamic Load Modeling Workshop, September 30, 2015. Support from CERTS and PSERC
1
![Page 2: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/2.jpg)
Simulation Models for Compressor Load Models
Option 1: Detailed motor models, and single-phase network models. Useful for research, hopefully not needed for grid-scale simulations.Option 2: Adapt models for grid simulations
- static performance model, current modelsimplistic, somewhat pessimistic.
- dynamic phasor model, complicated, doesn’tcapture subcycle influences (yet).
2
![Page 3: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/3.jpg)
Single-Phase Motor Models for Grid
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-15
-10
-5
0
5
10
15
time
aux.
winding
current
“Dynamic Phasor” Model
“Performance” Model
![Page 4: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/4.jpg)
Important Questions about Grid Simulations
• To what extent do single-phase, point-on-wave effects matter? Examine with single-phase motor simulations and tests.
• To what extent can impacts be aggregated?Do all motors stall during a FIDVR event?
4
![Page 5: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/5.jpg)
Single Phase Compressor Simulation Model
Tmech
Tave
0 0.25 0.5 0.751.0
mechanical revolution
Reciprocating Compressor Mechanical Load
5
![Page 6: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/6.jpg)
Point-on-Wave EffectsSimulations of Single-Phase Compressor Motor
Applied voltage. The disturbance occurs at different points along the sinusoid: peak, zero crossing, in between.
Instantaneous drop to 62% nominal for 3 cycles.
Speed for the different applied voltages. Worst case: zero crossing disturbance.
6
![Page 7: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/7.jpg)
Point-on-Wave EffectsStall Voltage vs fault duration, and point-on-wave variation.
Instantaneous voltage drop
7
![Page 8: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/8.jpg)
Point-on-Wave Effects
• Ramp Voltage Instead:
Point-on-wave effect is greatly reduced for even a very short ramp.
Performance Model Characteristic for reference
8
![Page 9: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/9.jpg)
Point-on-Wave Effects
• These results suggest a reason why FIDVR events don’t cascade beyond an event feeder.
• Locally, A/C motors stall in response to event.
Point-on-wave effect is greatly reduced for even a very short ramp.
Performance Model Characteristic for reference
Further away, the filtered voltage may exceed threshold.
9
![Page 10: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/10.jpg)
Laboratory Tests• Air Conditioner Tests at BPA Facility• Test Point-on-Wave Response, with and
without ramp.• Scroll Compressor
Voltage dip to 48, 45, 40, 35 and 30% nominalRecovery voltage at 90% nominal.
Find fault duration to result in a change in operating characteristic (not stall)
10
![Page 11: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/11.jpg)
Fault Regions, Instantaneous Voltage Dip
Zero Crossing
45°
Peak
11
![Page 12: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/12.jpg)
Fault Region: 1 Cycle Ramp in Voltage Dip
Peak
Zero Crossing45°
12
![Page 13: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/13.jpg)
Do All Motors Stall?
Grid VoltageV
25 Buses, 13 loads, tree distribution network, single connection to the grid.
Loads denoted by arrows.
Is it possible for a fraction of motors to stall in this network without stalling them all?
![Page 14: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/14.jpg)
Do All Motors Stall?
Grid VoltageV
Loads denoted by arrows.
100% Compressor Load: They all stall.50% Compressor, 50% Impedance, some may stall.(up to 5 maximum in this example)
![Page 15: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/15.jpg)
Conclusions
A dynamic phasor models may be suitable for grid-scale simulations because- point-on-wave effects may be naturally
mitigated by smoothing in disturbance away from the event location.
- allow aggregation of stall effects.
15
![Page 16: Simulation Models for Single Phase Compressor Motors · Simulation Models for Compressor Load Models Option 1: Detailed motor models, and single-phase network models. Useful for research,](https://reader036.vdocuments.us/reader036/viewer/2022081400/5f85c4f09c5e1a17ce3285da/html5/thumbnails/16.jpg)
Dynamic Phasor Model16