Electrical Inspection using Infrared Thermography, 111 Something Dr. TJ
[SAMPLE REPORT 111 SOMETHING DR.] Dmitry Starikov, Level 3 Thermographer, ME, CET
Infrared Imaging Solutions Inc 1-877-526-IRIS
1
INTRODUCTION
The purpose of this inspection was to identify any thermal patterns and temperatures that may indicate
electrical wear or failure. This inspection was completed utilizing the “FLIR” S660 handheld thermal
imaging system.
Infrared inspections are used to locate areas in need of maintenance. These anomalies can be located with
infrared imaging systems because of their increased or decreased temperature. The temperature rise of a
detected anomaly is measured and then the I.R. and the digital reference images are taken for
documentation. The report may contain references to demonstrate the appropriate working condition of
some equipment. Any anomalies are labeled as faults within the report.
The report is limited to the size and extent of inspection at the time it was conducted and as such is not
meant to be a warranty nor guarantee. It does not relieve concerned parties from their obligations.
Factors such as environmental and consumption fluctuations make it impossible to accurately predict
when an anomaly will result in a system failure. We suggest preventative maintenance to ensure
uninterrupted functioning of all electrical apparatus and motors at the above location.
PRIORITY Chart
HIGH Repair Immediately
MEDIUM Repair within 30 Days
LOW Repair within 6 months
REFERENCE For reference only
NOTE Visual anomalies, Electrical code violations
ACTION ITEMS SUMMARY
Designation Fault Action Pg.
Splitter #4 Misaligned B phase contacts Clean, lube, exercise, torque 2
P-1 Faulty Fuse Replace all 3 fuses, service fds 3
DS-A Loose connection on fuse clips Clean, lube, torque 4
LP-3B Misaligned B phase contacts Clean, exercise, lube, torque 5
Transformer ITA Misaligned C phase contacts Clean, exercise, lube, torque 6
Note Debris in lower level Mech Rm. Keep Electrical Rooms clean 7
Infrared Imaging Solutions Inc 1-877-526-IRIS
2
FAULT #1
PRIORITY LOCATION EQUIPMENT
Medium Main Electrical Room 100 A FUSED DISCONNECT SWITCH
A r1
32.9
50.1 °C
35
40
45
50
PARAMETERS ANALYSIS AND RECOMMENDATION
Date 06/06/2013
Filename IR_2648.jpg
Max Temperature 57.0 °C
Min Temperature 29.1 °C
Ar1 Max. Temperature 57.0 °C
Atmospheric
Temperature
21.2 °C
Object Distance 1.6 m
Image Camera Type ThermaCam SC660
Wes
Emissivity 0.91
Equipment: ITE, V7E-3633 100 A FUSED DISCONNECT SWITCH 120/208 VAC 3ph. 60 Hz
Designation: Splitter #4
Loads A:34a B:35a C:33a
Fault Analysis: Thermal variance detected across B phase line side on main contacts migrating to switch mechanism, fuse clip and conductor.
Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean Lubricate, exercise, torque as required and rescan.
Infrared Imaging Solutions Inc 1-877-526-IRIS
3
FAULT #2
PRIORITY LOCATION EQUIPMENT
LOW Lower level mechanical room 30A FUSED DISCONNECT SWITCH
A r1
35.0
86.0 °C
40
60
80
PARAMETERS ANALYSIS AND RECOMMENDATION
Date 06/06/2013
Filename IR_2650.jpg
Max Temperature 90.1 °C
Min Temperature 24.2 °C
Ar1 Max. Temperature 90.1 °C
Atmospheric
Temperature
21.2 °C
Object Distance 1.6 m
Image Camera Type ThermaCam SC660
Wes
Emissivity 0.91
Equipment: Siemens ID361 30 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz
Designation: P-1
Loads A:13 a B:14 a C:15 a
Fault Analysis: Thermal variance detected across B Phase fuse barrel.
Recommendation: Service 30 Amp FUSED DISCONNECT SWITCH and replace fuses.
Infrared Imaging Solutions Inc 1-877-526-IRIS
4
FAULT #3
PRIORITY LOCATION EQUIPMENT
Low Library Server Room 100A FUSED DISCONNECT SWITCH
A r1
29.9
57.9 °C
40
50
PARAMETERS ANALYSIS AND RECOMMENDATION
Date 06/06/2013
Filename IR_2657.jpg
Max Temperature 64.2 °C
Min Temperature 25.8 °C
Ar1 Max. Temperature 64.2 °C
Atmospheric
Temperature
21.2 °C
Object Distance 1.6 m
Image Camera Type ThermaCam SC660
Wes
Emissivity 0.91
Equipment: FPE-1136SN 100 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz
Designation: DS-A
Loads A:19a B:24a C:35a
Fault Analysis: Thermal variance detected across phases A and C line side on fuse clips migrating to main contacts
Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean, lubricate, exercise n torque. All 3 fuses should be uniform. Rescan.
Infrared Imaging Solutions Inc 1-877-526-IRIS
5
FAULT #4
PRIORITY LOCATION EQUIPMENT
Low 2nd
Floor Electrical room 100A FUSED DISCONNECT SWITCH
A r1
29.3
38.5 °C
30
35
PARAMETERS ANALYSIS AND RECOMMENDATION
Date 06/06/2013
Filename IR_2659.jpg
Max Temperature 39.8 °C
Min Temperature 25.3 °C
Ar1 Max.
Temperature
39.8 °C
Atmospheric
Temperature
21.2 °C
Object Distance 1.6 m
Image Camera Type ThermaCam SC660
Wes
Emissivity 0.91
Equipment: CEB, A3036A 100 amp FUSED DISCONNECT SWITCH, 600 VAC , 3ph., 60 Hz
Designation: LP-3B
Loads A:20a B:17a C:25a
Fault Analysis: Thermal variance detected across phase B line side on main contacts migrating to switch mechanism, fuse barrel and conductor
Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean, lubricate, exercise and torque. Rescan.
Infrared Imaging Solutions Inc 1-877-526-IRIS
6
FAULT #5
PRIORITY LOCATION EQUIPMENT
Medium 1st
Floor A, Music Room 118 100 A FUSED DISCONNECT SWITCH
A r1
27.0
60.5 °C
30
40
50
60
PARAMETERS ANALYSIS AND RECOMMENDATION
Date 06/06/2013
Filename IR_2662.jpg
Max Temperature 63.8 °C
Min Temperature 23.7 °C
Ar1 Max.
Temperature
63.8 °C
Atmospheric
Temperature
21.2 °C
Object Distance 1.6 m
Image Camera Type ThermaCam SC660
Wes
Emissivity 0.91
Equipment: CEB,A3036A 100 amp FUSED DISCONNECT SWITCH, 600 VAC 3ph. 60 Hz
Designation: Transformer ITA
Loads A:8a B:9a C:8a
Fault Analysis: Thermal variance detected across C phase line side on main contacts, migrating to switch mechanism, fuse barrel and conductor
Recommendation: Service 100 Amp FUSED DISCONNECT SWITCH. Clean lubricate, exercise and torque. Rescan
Infrared Imaging Solutions Inc 1-877-526-IRIS
7
Notes
Note #1
Main Electrical Room, Main Switchboard
600 amp FUSED DISCONNECT SWITCH Designation: Office Building Riser
Rug and brush were left inside switch enclosure IRIS Tech removed debris. (no action required)
Note #2
Lower level Mechanical Room
Refer to:
Ontario Electrical Safety Code Rule 2-316
Working Space around Electrical Equipment
Ontario Electrical Safety Code Rule 2-316 Flammable Material near electrical equipment
Action Required: Remove all debris from electrical room.
Infrared Imaging Solutions Inc 1-877-526-IRIS
8
Equipment List
Location Units Equipment Inspected Condition Priority Level
Image #
1 floor main electrical room
1 1600 A
air circuit breaker
Yes Satisfactory
1 switch board consisting of:
Yes Satisfactory
3 600 A fused disconnect switch
Yes note 1 None DC 2647
3 400 A fused disconnect switch
Yes Satisfactory
8 200 A fused disconnect switch
Yes Satisfactory
6 100 A
fused disconnect switch
Yes Fault #1 Medium IR 2648, DC 2649
1 300 A transfer switch Yes Satisfactory
1 25 KVA
dry type transformer
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
9
1 30 KVA
dry type transformer
Yes Satisfactory
1 300 KVA
dry type transformer
Yes Satisfactory
3 splitter Yes Satisfactory
2 contactor Yes Satisfactory
3 distribution panel
Yes Satisfactory
4 200 A fused disconnect switch
Yes Satisfactory
1 100 fused disconnect switch
Yes Satisfactory
5 30 A fused disconnect switch
Yes Satisfactory
1 floor mechanical room
5 splitter Yes note 2 None DC 2652, 2653, 2654
2 chillers Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
10
2 400 A fused disconnect switch
Yes Satisfactory
1 100 A fused disconnect switch
Yes Satisfactory
3 60 A fused disconnect switch
Yes Satisfactory
12 30 A fused disconnect switch
Yes Fault #2 Low IR 2650, DC 2651
2 control panel Yes Satisfactory
1 combo motor control
Yes Satisfactory
2 1.5 HP
motor Yes Satisfactory
1 7.5 HP
motor Yes Satisfactory
6 15 HP
motor Yes Satisfactory
penthouse elevator room
2 control panel Yes Satisfactory
1 splitter Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
11
2 100 A fused disconnect switch
Yes Satisfactory
3 30 A fused disconnect switch
Yes Satisfactory
penthouse mechanical room
1 10 KVA
dry type transformer
Yes Satisfactory
1 splitter Yes Satisfactory
2 control panel Yes Satisfactory
2 combo motor control
Yes Satisfactory
1 distribution panel
Yes Satisfactory
1 100 A fused disconnect switch
Yes Satisfactory
1 30 A fused disconnect switch
Yes Satisfactory
penthouse mechanical room
10 combo motor control
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
12
1 60 A fused disconnect switch
Yes Satisfactory
3 7.5 HP
motor Yes Satisfactory
1 5 HP motor Yes Satisfactory
1 0.33 HP
motor Yes Satisfactory
3 2 HP motor Yes Satisfactory
penthouse MUA P-12 room
2 splitter Yes Satisfactory
5 combo motor control
Yes Satisfactory
penthouse cooling tower
1 60 A fused disconnect switch
Yes Satisfactory
penthouse MUA room
1 5 KVA
dry type transformer
Yes Satisfactory
1 15 KVA
dry type transformer
Yes Satisfactory
4 distribution panel
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
13
3 splitter Yes Satisfactory
10 combo motor control
Yes Satisfactory
1 starters Yes Satisfactory
lower level B elevator lobby
1 distribution panel
Yes Satisfactory
lower level B by mechanical room
3 distribution panel
Yes Satisfactory
lower level B east entrance
1 distribution panel
Yes Satisfactory
1 floor B elevator lobby
1 distribution panel
Yes Satisfactory
1 floor B by 106 1 distribution panel
Yes Satisfactory
1 floor B by telephone room
1 distribution panel
Yes Satisfactory
1 floor B main lobby
1 distribution panel
Yes Satisfactory
1 floor B by theatre office
1 distribution panel
Yes Satisfactory
1 floor A by janitor 1 distribution panel
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
14
3 floor A by stairwell
1 distribution panel
Yes Satisfactory
2 floor B elevator lobby
1 distribution panel
Yes Satisfactory
3 floor B elevator lobby
2 distribution panel
Yes Satisfactory
3 floor B by 303 1 distribution panel
Yes Satisfactory
lower level B theatre
1 distribution panel
Yes Satisfactory
lower level B library
2 distribution panel
Yes Satisfactory
lower 1 floor B library
2 distribution panel
Yes Satisfactory
lower 2 floor B library
2 distribution panel
Yes Satisfactory
lower 1 floor B library server room
1 splitter Yes Satisfactory
2 distribution panel
Yes Satisfactory
1 100 A
fused disconnect switch
Yes Fault #3 Low IR 2657, DC 2658
Infrared Imaging Solutions Inc 1-877-526-IRIS
15
4 30 A fused disconnect switch
Yes Satisfactory
1 motor control Yes Satisfactory
1 floor B theatre electrical room
1 150 KVA
dry type transformer
Yes Satisfactory
2 splitter Yes Satisfactory
1 400 A fused disconnect switch
Yes Satisfactory
1 200 A fused disconnect switch
Yes Satisfactory
1 100 A fused disconnect switch
Yes Satisfactory
3 30 A fused disconnect switch
Yes Satisfactory
1 floor B electrical room
3 200 A fused disconnect switch
Yes Satisfactory
3 100 A fused disconnect switch
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
16
1 60 A fused disconnect switch
Yes Satisfactory
2 splitter Yes Satisfactory
1 75 KVA
dry type transformer
Yes Satisfactory
1 floor child care 2 distribution panel
Yes Satisfactory
3 floor B electrical room
1 15 KVA
dry type transformer
Yes Satisfactory
1 30 A fused disconnect switch
Yes Satisfactory
2 floor B electrical room
1 75 KVA
dry type transformer
Yes Satisfactory
1 30 KVA
fused disconnect switch
Yes Satisfactory
1 9 KVA
fused disconnect switch
Yes Satisfactory
2 splitter Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
17
3 distribution panel
Yes Satisfactory
2 200 A fused disconnect switch
Yes Satisfactory
4 100 A
fused disconnect switch
Yes Fault #4 Low IR 2659, DC 2660
2 60 A fused disconnect switch
Yes Satisfactory
1 30 A fused disconnect switch
Yes Satisfactory
2 floor City hallway 2 distribution panel
Yes Satisfactory
3 floor B IT room 1 30 A fused disconnect switch
Yes Satisfactory
lower level B elevator room
1 100 A fused disconnect switch
Yes Satisfactory
1 30 A fused disconnect switch
Yes Satisfactory
lower level A 019 electrical room
1 100 A fused disconnect
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
18
switch
1 30 A fused disconnect switch
Yes Satisfactory
3 60 A fused disconnect switch
Yes Satisfactory
1 15 KVA
dry type transformer
Yes Satisfactory
1 75 KVA
dry type transformer
Yes Satisfactory
1 splitter Yes Satisfactory
1 distribution panel
Yes Satisfactory
lower level A 019 electrical room
1 distribution panel
Yes Satisfactory
lower level B air duct room
4 combo motor control
Yes Satisfactory
lower level A elevator room
2 100 A fused disconnect switch
Yes Satisfactory
2 30 A fused disconnect switch
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
19
1 splitter Yes Satisfactory
lower level A 021 room
1 splitter Yes Satisfactory
2 60 A fused disconnect switch
Yes Satisfactory
6 30 A fused disconnect switch
Yes Satisfactory
1 contactor Yes Satisfactory
1 floor A 118 musical room
2 splitters Yes Satisfactory
2 distribution panel
Yes Satisfactory
1 75 KVA
dry type transformer
Yes Satisfactory
1 200 A fused disconnect switch
Yes Satisfactory
4 100 A
fused disconnect switch
Yes Fault #5 Medium IR 2662, DC 2663
Infrared Imaging Solutions Inc 1-877-526-IRIS
20
3 60 A fused disconnect switch
Yes Satisfactory
2 floor A 210 room hallway
1 distribution panel
Yes Satisfactory
2 floor A 210 room electrical room
1 75 KVA
dry type transformer
Yes Satisfactory
1 distribution panel
Yes Satisfactory
1 splitter Yes Satisfactory
1 200 A fused disconnect switch
Yes Satisfactory
2 100 A fused disconnect switch
Yes Satisfactory
5 60 A fused disconnect switch
Yes Satisfactory
3 floor A 310 room electrical closet
1 splitter Yes Satisfactory
1 distribution panel
Yes Satisfactory
2 100 A fused disconnect switch
Yes Satisfactory
Infrared Imaging Solutions Inc 1-877-526-IRIS
21
3 60 A fused disconnect switch
Yes Satisfactory
Lower level tractor room
1 60 A fused disconnect switch
Yes Satisfactory
Lower level compressor room
1 15 KVA
dry type transformer
Yes Satisfactory
1 distribution panel
Yes Satisfactory
1 splitter Yes Satisfactory
1 control panel Yes Satisfactory
3 30 A fused disconnect switch
Yes Satisfactory
Lower level sump pump room
1 100 A fused disconnect switch
Yes Satisfactory
1 distribution panel
Yes Satisfactory