CONFIDENTIAL REQUEST FOR QUOTATION UPGRADE OF KITCHEN EXHAUST SYSTEM AT BURSA MALAYSIA FOOD COURT, ANNEXE BUILDING Prepared By: Administration, Corporate Services This document is the intellectual property of Bursa Malaysia. No part of the document is to be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording or any information storage and retrieval system, without permission in writing from Bursa Malaysia.

Upload: vudieu

Post on 13-Mar-2018

220 views

Category:

Documents


4 download

TRANSCRIPT

CONFIDENTIAL

RREEQQUUEESSTT FFOORR QQUUOOTTAATTIIOONN

UUPPGGRRAADDEE OOFF KKIITTCCHHEENN EEXXHHAAUUSSTT SSYYSSTTEEMM AT BURSA MALAYSIA

FOOD COURT, ANNEXE BUILDING

Prepared By: Administration, Corporate Services

This document is the intellectual property of Bursa Malaysia. No part of the document is to be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording or any information storage and retrieval system, without permission in writing from Bursa Malaysia.

Table of Contents

1.0 INTRODUCTION ........................................................................................................2

2.0 STANDARDS AND INSTRUCTIONS 2.1 INSTRUCTIONS TO PROSPECTIVE BIDDERS ....................................................................................... 2 2.2 CONTACT PERSONS..................................................................................................................... 3 2.3 TIME FRAME ............................................................................................................................. 3

3.0 COMPANY PROFILE ……………………………………………………………………………..3

4.0 SITE BRIEFING .........................................................................................................3

5.0 SCHEDULE OF PRICES ..............................................................................................4

6.0 SCOPE OF WORKS ....................................................................................................4

7.0 FORM OF QUOTATION ............................................................................................4

8.0 BACKGROUND OF EXISTING KITCHEN EXHAUST SYSTEM .....................................5

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

2

1.0 INTRODUCTION

This document sets out the requirements of Bursa Malaysia Berhad (“Bursa”) to look for a qualified

ventilation contractor to upgrade the existing kitchen exhaust system in the Food Court at Annexe

Building for the purpose of eliminating the unpleasant cooking oil and smoke. Bidders are required to

address all the requirements stated in this Request For Quotation (“RFQ”) document and its

appendices.

The RFQ belongs to Bursa and bidders are required to hold such proprietary and confidential

information in the strictest form. It is not to be duplicated, distributed or disclosed to any third parties

without written consent from Bursa.

2.0 STANDARDS AND INSTRUCTIONS

This section covers the standards and instructions that should be followed by the bidders in response to

this RFQ. Please read this RFQ specification carefully. Bidders are advised to read the whole of this

document.

2.1 Instructions to Prospective Bidders

2.1.1 The proposal must be enclosed in a SEALED envelope and must be addressed to:-

Head, Administration, Corporate Services

Bursa Malaysia Berhad

1st Floor, Business Centre, Exchange Square

Bukit Kewangan

50200 Kuala Lumpur

2.1.2 The proposal must reach Bursa Malaysia not later than 5.00pm, Friday April 5, 2013. Late

responses will not be entertained.

2.1.3 The top left-hand corner of the envelope must be marked “RFQ For Upgrade of Kitchen

Exhaust System”. This is also required for any subsequent written correspondence.

2.1.4 Quote must be signed by an official who is authorised to act on behalf of the organisation

submitting this proposal.

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

3

2.1.5 Any suggestions for additional work which the bidder reckons need to be included in the RFQ

must be stated in Appendix I.

2.1.6 Prices must be quoted in Ringgit Malaysia (RM) on a per item basis as per Specifications /

Schedule of Prices (Appendix I).

2.1.7 Bursa reserves the right to accept or reject any proposal submitted.

2.2 Contact Persons

All questions regarding this RFQ must be submitted in writing or via e-mail to the parties listed below:-

Contact Person Mohamad Noor Ahmad Shaharuddin

Address 13th Floor, Exchange Square, Bukit Kewangan 50200

Kuala Lumpur

E-Mail Address [email protected]

Contact Number 013-269 2966

Contact Person Leong Shee Sim

Address 13th Floor, Exchange Square, Bukit Kewangan 50200

Kuala Lumpur

E-Mail Address [email protected]

Contact Number 019-354 7066

2.3 Time Frame

Date Action

22/3/2013 Tender Notice 26/3/2013 Briefing to participating bidders : Q&A session 5/4/2013 Submission of proposal by bidders

3.0 COMPANY PROFILE

Bidders must provide the following information:

3.1 Bidder’s profile (by completing the form in Appendix II).

3.2 Previous experience in dealing with similar requirements.

3.3 Reference sites.

4.0 SITE BRIEFING

A site briefing will be conducted on March 26, 2013 at 3.00 pm. Bidders are requested to assemble at

Lower Ground Floor, Exchange Square before 2.30 pm. If you require further information please

contact our Mr Leong Shee Sim at telephone no. 019-354 7066.

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

4

5.0 SCHEDULE OF PRICES

5.1 Bidders are to submit their schedule of prices in Appendix I.

6.0 SCOPE OF WORKS

6.1 Upgrade of Existing Exhaust Fan System 6.1.1 To supply and install two (2) additional booster exhaust fans at existing main exhaust

ducting for increasing the static pressure during heavy cooking periods. 6.1.2 To supply and install two (2) nos. of Fresh Air Fan i.e. 1 No of 10,400 CFM and 1 no of

9,975 CFM at Static Pressure of 1.6” WG. 6.1.3 To supply and replace existing fifteen (15) individual exhaust fans which are currently

installed at the kitchen hoods with larger capacity exhaust fans (1,500 cfm). 6.1.4 To supply and install one lot of new fresh air ducting system, complete with fire

alarm tripping signal integration to existing fire alarm system at Annexe Building (to comply to Bomba requirements) for the purpose of increasing the exhaust rate to 1500 CFM per exhaust food for achievement of 90% of fresh air make-up rate.

6.1.5 To supply and install one new stainless steel kitchen hood at Stall No.16. For your

information this stall is not provided with kitchen hood previously.

6.2 Repair of Existing Exhaust Ducting

6.2.1 To repair all existing ducting joints to prevent oil leaking. 6.2.2 To install oil dripping pan at each of the stall kitchen for collecting oil leaking from the

ducting joints.

6.2 Mechanical and Electrical Works

6.2.1 To engage competent technician and wireman to install the electrical work. 6.2.2 To terminate all unused existing power cabling in a safe manner. This is to prevent

electrical hazard.

7.0 FORM OF QUOTATION

7.1 Bidders are to submit their Form of Quotation in Appendix III.

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

5

8.0 BACKGROUND OF EXISTING VENTILATION FAN SYSTEM

No. Description Quantity Remarks

1. BOOSTER EXHAUST FAN AT INDIVIDUAL

KITCHEN HOOD

§ Brand : Kruger

§ Model : 450

§ Voltage : 240 Vac

§ Horse Power : 1 HP

§ Fan Speed : 1440 RPM

§ Air Volume : 1300 CFM

§ Static Pressure : 2” WG

§ Noise : 70 db

§

14

2. MAIN EXHAUST FAN AT MAIN DUCTING

(LOCATED AT THE RUBBISH COMPACTOR

ROOM)

§ Brand : Kruger

§ Model : 710

§ Voltage : 415 Vac

§ Horse Power : 7.5 HP

§ Fan Speed : 1420 RPM

§ Air Volume : CFM

§ Static Pressure : 2” WG

§ Noise : 70 db

§

1

3. EXISTING EXHAUST DUCT LAYOUT PLAN

Refer to the attached drawing ref : BM/3/2013-

001, BM/3/2013-002 and BM/3/2013-003

3 drawings

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

6

SPECIFICATIONS / SCHEDULE OF PRICES Appendix I No Description Quantity Unit Price

(RM) Amount

(RM) 1. PRELIMINARIES

1.1

1.2

1.3

1.4

1.5

Provision of insurance coverage of RM500,000 for workman compensation and third party liability. Provision of a full-time site engineer to supervise the work during construction period. Provision of shop-drawings for approval prior to implementation of construction work. Provision of site temporary hoarding during construction. Diversion and relocation of existing mechanical and electrical services to make way for new ducting/grilles installation.

1 lot

1 lot

1 lot

1 lot

1 lot

2. INSTALLATION OF NEW KITCHEN EXHAUST FANS 2.1

EXHAUST FAN ( KEF-1) To supply and install centrifugal type kitchen exhaust fan KEF-1 at existing main exhaust duct ( Zone A), complete with isolation springs, duct silencer and modification of existing ducting. Specifications :

• Brand : Kruger • Model : BSB-D 710 • Fan Type : SISW Cent ( centrifugal) • Fan Diameter : 710mm • Capacity : 10,500 CFM • Static Pressure : 3” WG • Motor Power : 15KW • Horse Power : 20 HP • Motor Pole : 4 • Motor Class : F • Voltage/Frequency : 415V/50Hz • Fan Speed : 1450 RPM • Lw dB(A) : 95 dB • Lp dB (A) : 74 dB

1 lot

2.2 EXHAUST FAN ( KEF-2) To supply and install centrifugal type kitchen exhaust fan KEF-2 at existing main exhaust duct

1 lot

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

7

( Zone B), complete with isolation springs, duct silencer and modification of existing ducting. Specifications :

• Brand : Kruger • Model : BSB-D 710 • Fan Type : SISW Cent ( centrifugal) • Fan Diameter : 710mm • Capacity : 13,500 CFM • Static Pressure : 3” WG • Motor Power : 15KW • Horse Power : 20HP • Motor Pole : 4 • Motor Class : F • Voltage/Frequency : 415V/50Hz • Fan Speed : 1450 RPM • Lw dB(A) : 97 dB • Lp dB (A) : 76 dB

2.3

2.3.1

2.3.2

Electrical work To supply and install 3-phase 50 Ampere sub-main cable and control starter board for the new kitchen exhaust fan KEF-1 , complete with 10mm2 PVC cables, wall-hung starter panel, timers, MCCBs, MCBs, ELR, relays, Phase indicators, selector switch , overload relay, fire alarm tripping signal cable and cable and trunking. To supply and install 3-phase 50 Ampere sub-main cable and control starter board for the new kitchen exhaust fan KEF-2 , complete with 10mm2 PVC cables, wall-hung starter panel, timers, MCCBs, MCBs, ELR, relays, Phase indicators, selector switch, overload relay, fire alarm tripping signal cable and trunking.

1 lot

1 lot

3. INSTALLATION OF NEW FRESH AIR DUCTING AND FAN MOTORS

3.1

3.1.1

3.1.2

NEW FRESH AIR DUCTING To supply and install G.I (TDC and slit/cleat type) fresh air ducting for Zone A and Zone B as per Drawing Ref : BM12/3/2013-002, complete with brackets, painting and all necessary accessories. To supply labour and necessary tools to diamond-core existing concrete slab (roof level) for two (2) openings (size : 1000mm x 400mm and 1200mm x 400mm), complete with construction of 2 feet

1 lot

1 lot

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

8

height brick wall plastering with both sides, waterproofing treatment and aluminium louver.

3.2

3.2.1

KITCHEN FRESH AIR FAN ( KFF-CAFE-1) To supply and install axial type kitchen fresh air fan KFF-CAFÉ-1 at existing main exhaust duct ( Zone A), complete with isolation springs, duct silencer and modification of existing ducting. Specifications :

• Brand : Kruger • Model No. TDA800 • Fan Type : Axial Fan • Capacity : 10,500 CFM • Static Pressure : 1.6” WG • Motor Power : 5.5KW • Horse Power : 7.5HP • Motor Pole : 4 pole • Motor Class : F • Voltage/Frequency : 415V/50Hz • Fan Speed : 1450 RPM • Lw dB(A) : 97 dB • Lp dB (A) : 76 dB

Note : Complying with Bomba requirements – the fresh air fan need to be integrated with existing fire alarm system at Annexe Building to stop the fan running during fire mode.

1 lot

4.

4.1

KITCHEN FRESH AIR FAN ( KFF-CAFE-2) To supply and install axial type kitchen fresh air fan KFF-CAFE-2 at existing main exhaust duct (Zone B), complete with isolation springs, duct silencer and modification of existing ducting. Specifications :

• Brand : Kruger • Model No. TDA800 • Fan Type : Axial Fan • Capacity : 9,975 CFM • Static Pressure : 1.6” WG • Motor Power : 5.5KW • Horse Power : 7.5HP • Motor Pole : 4 pole

1 lot

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

9

• Motor Class : F • Voltage/Frequency : 415V/50Hz • Fan Speed : 1450 RPM • Lw dB(A) : 97 dB • Lp dB (A) : 76 dB

Note : Complying with Bomba Requirements – the fresh air fan need to be integrated with existing fire alarm system at Annexe Building to stop the fan running during fire mode.

4.1

4.1.1

4.1.2

Electrical work To supply and install 3-phase 50 Ampere sub-main cable and control starter board for the new fresh air fan KFF-CAFE-1 , complete with 10mm2 PVC cables, wall-hung starter panel, timers, MCCBs, MCBs, ELR, relays, Phase indicators, selector switch , overload relay, fire alarm tripping signal cable and cable and trunking. To supply and install 3-phase 50 Ampere sub-main cable and control starter board for the new fresh air fan KFF-CAFE-2, complete with 10mm2 PVC cables, wall-hung starter panel, timers, MCCBs, MCBs, ELR, relays, Phase indicators, selector switch, overload relay, fire alarm tripping signal cable and trunking.

1 lot

1 lot

5. INSTALLATION OF ADDITIONAL INLET LOUVERS FOR EXISTING EXHAUST DUCT

5.1 To supply and install additional inlet louver to the existing main exhaust duct at the back lane of kitchen for reducing stuffiness during heavy cooking.

12

6. INSTALLATION OF NEW KITCHEN AT STALL NO.9 6.1 To supply and install stainless steel exhaust hood

(size : 1500 [W] x 750 [D] x 600 [H]) at Stall No.9 , complete with :

• Grease drawer • Grease filter • Power supply • Modification of existing kitchen duct

1 lot

7. INSTALLATION OF OIL DRAIN PAN AT INDIVIDUAL KITCHEN AND OTHER ENHANCEMENT ACESSORIES

7.1 To supply and install stainless steel oil drain pan 15

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

10

7.2

7.3

7.4

under the existing exhaust fan and duct at the kitchen for collecting the unresolved dripping oil, complete with grease drawer and necessary materials. To supply and install additional NRD, VCD to all existing kitchen exhaust hood connection, complete with necessary accessories. To supply and install necessary fire damper, complete with access manhole for ducting for wall and slab penetration. To supply labour and necessary material to modify existing main exhaust duct’s discharge outlet at the Rubbish Disposal Centre with proper G.I nozzle, complete with dismantling existing G.I. louver.

1 lot

1 lot

1 lot

8. REPLACEMENT OF EXISTING BOOSTER EXHAUST AT INDIVIDUAL KITCHEN HOOD

8.1 To supply and replace existing axial type kitchen exhaust fan at existing kitchen hood, complete with isolation springs, duct silencer and modification of existing ducting. Specifications :

• Brand : Kruger • Model No. : TDA 450 • Fan Type : Axial Fan • Capacity : 1,500 CFM • Static Pressure : 0.65 WG • Motor Power : 5.5KW • Horse Power : 0.75HP • Motor Pole : 4pole • Motor Class : F • Voltage/Frequency : 240V/50Hz • Fan Speed : 1450 RPM • Lw dB(A) : 83 dB • Lp dB (A) : 62 dB

15 nos

9.

9.1

OTHER WORKS : Any other works which bidder reckons need to be included in this quote. ………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

11

……………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………… …………………………………………………………………………………………………………………………………………………………………………………………………………………………………………..… ………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………………

TOTAL CARRIED TO FORM OF QUOTATION

Requirements :

o Completion Period : …………………. Days o Validity : 3 months o Warranty Period : Two (2) years

QUOTATION BRIEFING

§ A site briefing will be conducted on March 26, 2013 at 3.00pm. Bidders are requested to assemble at Lower Ground Floor, Exchange Square before 2.45pm. If you require further information please contact our Mr Leong Shee Sim at telephone no. 019-354 7066

Signature : …………………………..…………………………… Authorised Person Name: ………………………………. Company Chop : Date : …………………… Contact Person Name : ………………………………………….. Contact No. ……………………………………………………………. Email Address : ……………………………………………………… Your Reference No. ………………………( Bidder must fill in the quote reference no.)

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

12

PARTICULAR OF PROSPECTIVE BIDDER

1. Particular of the Company

Name : ………………………………………………………………………………….. Address : ………………………………………………………………………………..

……………………………………………………………………………….. …………………………………………………..…………………………..

2. Date First Registered : …………………………………………………………… 3. Paid-up Capital : …………………………………………………………………….

4. Authorised Capital : ………………………………………………………………..

5. Ownership :

Major Shareholder % Specify (B) – Bumiputra

(NB) – Non-Bumiputra

6. We declare that the abovementioned company is :

a related Public Listing Company (PLC) with Bursa Malaysia. a related subsidiary and associate company of PLC. a non-related company to PLC

7. Financial Performance

Last Three years’ Turnover

Year Turnover ( RM’000) 2012 2011 2010

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

13

Note : You are also required to submit your last three years’ audit profit and lost account statement.

8. Staffing

Last Three Years’ Staff Strength Year Number of Staff at December 31 2012 2011 2010

9 Job Reference

Client Name Scope of Work Project Sum (RM)

Year

I believe that the information given above, to the best of my knowledge is correct. …………………………………………………. Signature Name : …………………………………………………. Designation : …………………………………………. Date : ……………………………………………………

RFQ FOR UPGRADE OF VENTILATION SYSTEM AT FOOD COURT , ANNEXE BUILDING 1/3/2013

14

Appendix III

FORM OF QUOTATION

BURSA MALAYSIA BERHAD CORPORATE SERVICES 13th Floor, Exchange Square Bukit Kewangan 50200 Kuala Lumpur RREEQQUUEESSTT FFOORR QQUUOOTTAATTIIOONN FFOORR UUPPGGRRAADDEE OOFF KKIITTCCHHEENN EEXXHHAAUUSSTT SSYYSSTTEEMM AT BURSA MALAYSIA FOOD COURT, ANNEXE BUILDING CLOSING DATE : APRIL 5, 2013 TIME : 5.00 PM Herewith, we transmit our bid which is based on the Quotation Documents we received from you:- (a) Schedule of Prices (Template) (b) Proposed Drawings We confirm that our Quote fully complies with your specifications and with your scope of work as contained in the Quotation Documents. We offer to carry out the work for the Lump Sum of Ringgit Malaysia …………………………………….……………… (RM…………………..), being valid up to June 30, 2013. We undertake to complete the work within ………………………….. days upon confirmation of order. We understand that you are not bound to accept the lowest or any offer you may receive and that you reserve the right to award the contract separately for itemised quotes. Yours faithfully, …………………………………… Signature Name : …………………………………………………….. Bidder’s Stamp : Date : ………………………………..