relay setting chart

15
CLIENT M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP PROJECT 1x18 MW CO-GEN POWER PLANT DOCUMENT TITLE RELAY SETTING CHART FOR 33KV SWITCHYARD DOCUMENT NO. IKE-ISGEC-KWL61-DOC-233 REVISION 00 DATE 11.10.2013 NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY ARD KBD ABH EPC ELECTRICAL CONTRACTOR IKE ELECTRIC PVT. LTD. 601 - 602, MARIEGOLD NECO GARDENS, VIMAN NAGAR, PUNE - 411 014 MAHARASHTRA INDIA PHONE - 020 - 66290300 / 301 TELEFAX - 020 - 66290302 **Sheets (Including Title Sheet)

Upload: erkamlakar2234

Post on 25-Oct-2015

247 views

Category:

Documents


8 download

DESCRIPTION

Relay Setting Chart

TRANSCRIPT

Page 1: Relay Setting Chart

CLIENT M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

DOCUMENT TITLE RELAY SETTING CHART FOR 33KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-233

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

ARD KBD ABH

EPC ELECTRICAL CONTRACTOR IKE ELECTRIC PVT. LTD.

601 - 602, MARIEGOLD NECO GARDENS,VIMAN NAGAR,PUNE - 411 014MAHARASHTRAINDIAPHONE - 020 - 66290300 / 301TELEFAX - 020 - 66290302

**Sheets (Including Title Sheet)

Page 2: Relay Setting Chart

PREPARED BY: ARD1 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 33KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks

I 33KV Transformer Control and Relay Panel

1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)

Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 500/1A

Idiff>=2.5-30 Iref HV: CTR: 200/1 A

Idiff>>>=2.5-30 Iref NCTR: *** A

m1: 0.15-1.5 m1: 0.2

m2: 0.15-1.5 m2: 0.7

IR,m2 (1.5-10.0 Iref) 4

Op.del, trip signal:0-100S

Restricted earthfault protection(64R)

Effective setting: 10% 10%In

High Impedance relay NCTR: *** A

Stabilising resistor

(0-1000) Ohm Rst: 200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT 50N/51N Interconnection In: 0.08-4In 0.75*In characterictics67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 sec 3 Sec Curve78, 27Z, 59, 8160, 81R, 99, 27 Inst. Overcurrent protection (50)

In: 0.08-32In 6*In CTR: 200/1AT: 0-100 sec 0 sec (Inst) PTR: 33KV/110V

Earth fault protection (51N) IDMT Ie: 0.08-4In 0.2*In charactericticsT: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N) Ie: 0.08-4In 0.3*InT: 0-100 sec 0.5 sec

Page 3: Relay Setting Chart

PREPARED BY: ARD2 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 33KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksDir. Overcurrent protection (67)In: 0.08-32In 0.75*In RCA: 30 degT: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)Ie: 0.08-32In 0.1*In RCA: 45 degT: 0-100 sec 0.35 sec

Under volatge protection (27)U<: 10-120V 80 VT: 0-100 sec 2 sec

Over voltage protection (59)U>: 60-185V 121 VT: 0-100 sec 3 sec

Under frequency protection (81U)f<: 45-65Hz 47.7 Hz PTR: 33KV/110VT: 0-100 sec 2 sec

Over frequency protection (81O)f>: 45-65Hz 52 HzT: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)In: 0.4-4*In 1*In CTR: 200/1ATime delay 0.3 sec

df/dt protection (81R)df/dt: 0.1-10Hz/sec 4 Hz/ secT: 0-100 sec Inst Inst

Page 4: Relay Setting Chart

PREPARED BY: ARD3 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 33KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksDead band lower frequency45-65Hz 49 Hz

Dead band upper frequency45-65Hz 51 Hz

Voltage Balance Relay (60)******

Overfluxing Protection Relay (99)******

Vector surge protection (78)dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G) Ie: 0.08-4In 0.3 * In CTR: 200/1 AT: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)

50N/51N protection relay In: 0.08-4In 0.9 * In

(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)In: 0.08-32In 6 * In CTR: 500 / 1 AT: 0-100 sec 0 Sec PTR: 11kV / 110 V

Page 5: Relay Setting Chart

PREPARED BY: ARD4 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 33KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksIDMT Earth fault protection (51N)Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N) Ie: 0.08-4In 0.3 * InT: 0-100 sec 0.3 Sec

4 27, 59 Numerical MICOM P921 Under voltage protection (27)59D protection relay U<: 10-120V 0.8

T: 0-100 sec 0.5 sec

Over voltage protection (59)U>: 60-185V 1.1T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)V: 5.4 -20V 5.4 VTMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.

b) All the other functions which are not mentioned in this chart shall be disabled.

Page 6: Relay Setting Chart

CLIENT M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

DOCUMENT TITLE RELAY SETTING CHART FOR 132KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-133

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

ARD KBD ABH

EPC ELECTRICAL CONTRACTOR IKE ELECTRIC PVT. LTD.

601 - 602, MARIEGOLD NECO GARDENS,VIMAN NAGAR,PUNE - 411 014MAHARASHTRAINDIAPHONE - 020 - 66290300 / 301TELEFAX - 020 - 66290302

**Sheets (Including Title Sheet)

Page 7: Relay Setting Chart

PREPARED BY: ARD1 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 132KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks

I 132KV Transformer Control and Relay Panel

1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)

Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 1500/1A

Idiff>=2.5-30 Iref HV: CTR: 150/1 A

Idiff>>>=2.5-30 Iref NCTR: *** A

m1: 0.15-1.5 m1: 0.2

m2: 0.15-1.5 m2: 0.7

IR, m2 (1.5-10.0 Iref) 4

Op.del, trip signal:0-100S

Restricted earthfault protection(64R)

Effective setting: 10% 10%In

High Impedance relay NCTR: *** A

Stabilising resistor

(0-1000) Ohm Rst:200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT 50N/51N Interconnection In: 0.08-4In 0.75*In characterictics67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 3 Sec Curve78, 27Z, 59, 8160, 81R, 99, 27 Inst. Overcurrent protection (50)

In: 0.08-32In 6*In CTR: 150/1AT: 0-100 sec 0 sec (Inst) PTR: 132KV/110V

Earth fault protection (51N) IDMT Ie: 0.08-4In 0.2*In charactericticsT: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N) Ie: 0.08-4In 0.3*InT: 0-100 sec 0.5 sec

Page 8: Relay Setting Chart

PREPARED BY: ARD2 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 132KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksDir. Overcurrent protection (67)In: 0.08-32In 0.75*In RCA: 30 degT: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)Ie: 0.08-32In 0.1*In RCA: 45 degT: 0-100 sec 0.35 sec

Under volatge protection (27)U<: 10-120V 80 VT: 0-100 sec 2 sec

Over voltage protection (59)U>: 60-185V 121 VT: 0-100 sec 3 sec

Under frequency protection (81U)f<: 45-65Hz 47.7 Hz PTR: 132KV/110VT: 0-100 sec 2 sec

Over frequency protection (81O)f>: 45-65Hz 52 HzT: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)In: 0.4-4*In 1*In CTR: 150/1ATime delay 0.3 sec

df/dt protection (81R)df/dt: 0.1-10Hz/sec 4 Hz/ secT: 0-100 sec Inst

Page 9: Relay Setting Chart

PREPARED BY: ARD3 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 132KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksDead band lower frequency45-65Hz 49 Hz

Dead band upper frequency45-65Hz 51 Hz

Voltage Balance Relay (60)******

Overfluxing Protection Relay (99)******

Vector surge protection (78)dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G) Ie: 0.08-4In 0.3 * In CTR: 150/1 AT: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)

50N/51N protection relay In: 0.08-4In 0.7 * In

(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)In: 0.08-32In 6 * In CTR: 1500 / 1 AT: 0-100 sec 0 Sec PTR: 11kV / 110 V

Page 10: Relay Setting Chart

PREPARED BY: ARD4 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 132KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting RemarksIDMT Earth fault protection (51N)Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N) Ie: 0.08-4In 0.3 * InT: 0-100 sec 0.3 Sec

4 50/51 Numerical MICOM P127 IDMT overcurrent protection (51)

50N/51N protection relay In: 0.08-4In 0.7 * In

(HV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)In: 0.08-32In 6 * In CTR: 1500 / 1 AT: 0-100 sec 0 Sec PTR: 132kV / 110 V

IDMT Earth fault protection (51N)Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N) Ie: 0.08-4In 0.3 * InT: 0-100 sec 0.3 Sec

5 27, 59 Numerical MICOM P921 Under voltage protection (27)59D protection relay U<: 10-120V 0.8

T: 0-100 sec 0.5 sec

Over voltage protection (59)U>: 60-185V 1.1T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)V: 5.4 -20V 5.4 VTMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.

Page 11: Relay Setting Chart

PREPARED BY: ARD5 of 11

CHECKED BY: KBDAPPROVED BY: ABH

RELAY SETTING CHART- 132KV SWITCHYARD RELAY

Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks

b) All the other functions which are not mentioned in this chart shall be disabled.