relay setting chart _ crp panel_shambhu_revb
TRANSCRIPT
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
1/21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
2/21
1
Differential
Protection
(Restrained)
ABB - RET
67087T>
Stage 1 (T2D1 )
2
Differential
Protection
(Unrestrained),Stage 2
ABB - RET
670 87T>>
3
Earth faultABB - RET
67064R LV
ow
RECOMMEND
SI. No. Type ofProtection
Relay Make/ No.
PROTECTION ANSICODE
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
3/21
64R HV
es r c e
Earth faultABB - RET
67064R LV
g
Im edence
64R HV
4
Stand -by
Earth fault
Protection
HV Side
ABB - RET
67051s-EFR HV
( 4th-Stage- OFF)
RET-670 , TIME CO-ORDINATED SETTINGS OF Stan-by-
EFR ( HV & LV )
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
4/21
Stand -by Earth fault
Protection (LV Side)
ABB - RET
67051s-EFR LV
I_base
I1>
t1>
I2>
t2>
I3>
t3>
I4>
t4>
Stand -by Earth fault
Protection (HV Side)
ABB - RET
67051s-EFR HV
I_base
I1>
t1>
I2>
t2>
I3>
t3>
I4>
t4>
STAGE-3
STAGE-4
STAGE-1
STAGE-3
STAGE-4
STAGE-1
STAGE-2
STAGE-2
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
5/21
Parameter Description
150/1A (132KV side) Operation on
2000/1A (11 kV Side) IdMinSetting of minimum
differential operating current
%Z = 12.5% ( TAKE
FROM Name plate of
trafo. )End section 1 Cross-Over point b/w slope1
& Slope-2
Vector group = YNyn0 Slope section 2Setting of slope 2
stabilisation, (Slope 1 has
fixed stabilization)
End section 2Cross-Over point b/w slope2
& Slope-3
Slope section 3Setting of slope 3
stabilisation,
150/1A (132KV side)
2000/1A (11 kV Side) Idunre
Differential current, High set
(Unrestrained)
Cross blocking logic OpCrossBlock = on
Id2f / Id1f> (%) 2nd Harmonic restraint
Id5f/ Id1f> (%) 5th Harmonic restraint
Set the operation of
Negative sequence
differential protection
OpNegSeqDiff = = on
IMinNegSeq =
Setting of minimum negative
sequence differential currentlevel
NegSeqROA Relay operate angle
2000/1A (11 kV Side) Idmin (%)
ROA Relay operate angle
D RELAY SETTING CHART FOR 132/11.5kV, 20/25 MV
CT Ratio / PT Ratio/OTHER
Relay
Available setting range
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
6/21
150/1A (132KV side) Idmin (%)
ROA Relay operate angle
2000/1A (11 kV Side) U alarm Operate voltage
t Alarm Operate time
U trip Operate voltage
t trip Operate time
Rs Series Resistor
150/1A (132KV side) U alarm Operate voltage
t Alarm Operate time
U trip Operate voltage
t trip Operate time
Rs Series Resistor
150/1A (132KV side) IN1>/ Ib Base Current Setting
Dir mode
Ibase
1st-stage t11> DT setting
NA k11> TMS
IN2>/ Ib Base Current Setting
Dir mode
2nd-stage t1 2> DT setting
NA k1 2> TMS
IN3>/ Ib Base Current Setting
Dir mode
3rd-stage t1 3> DT setting
NA k1 3> TMS
NEW SETTINGS OLD SETTINGS. Remarks
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
7/21
100% 80%
80% of Ibase 80% of Ibase
0.96 sec 0.0 sec
50% of Ibase 50% of Ibase
1.2 sec 0.40 sec
40% of Ibase 40% of Ibase
1.4sec 0.80 sec
30% of Ibase 30% of Ibase
1.6sec 1.20 sec
100% 80%
80% of Ibase 80% of Ibase
1.26 sec 0.3 sec
100% of Ibase 100% of Ibase
1.46 sec 0.15 sec
off off
OFF OFF
off off
OFF OFF
t= 0.96 sec. is the Normal-
EFR ( in incomer of 11KV-
rex-521 ) Relay's time
setting. So, the same has
been maintained as trip-
time to SB-EFR-LV.
Assuming a time
descripation of 0.3 sec.
b/w 11KV & 132KV -trip
time , t1= 0.96 + 0.3sec. =
1.26 SEC.
600/1A (132KV side)
150/1A (132KV side)
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
8/21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
9/21
4.0 -100.0 30% Inst
60 - 90 Degrees 60
( 2 -500 ) V N / A
0 - 60 sec N / A 5.0 sec.
( 5 -900 ) V 109.5 V
----- ---- Inst
10 -20000 Ohms. 396 ohms.
( 2 -500 ) V N / A
0 - 60 sec N / A 5.0 sec.
( 5 -900 ) V 63 V
----- ---- Inst
10 -20000 Ohms. 250 ohms.
1.0 -2500.0 %
Ibase20% * Ibase
----- Non directional
0 - 60 Secs ---- 1.0 sec.
0.05 - 999 0.15 Secs NI 0.15 Secs
1.0 -2500.0 %
Ibase 15% * Ibase
----- Non directional
0 - 60 Secs ---- 1.5 sec.
0.05 - 999 0.15 Secs NI 0.15 Secs
1.0 -2500.0 %
Ibase10% * Ibase
----- Non directional
0 - 60 Secs ---- 2.0 sec.
0.05 - 999 0.15 Secs NI 0.15 Secs
a op e g - mpe ence
based REFR-Protection.
see ANNEXURE-01
see ANNEXURE-01
see ANNEXURE-01 ---
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
10/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
1Differential Protection
(Restrained)
ABB - RET
67087T> 150/1A (132KV side) Operation on ---- ---- ----
Stage 1 (T2D1 ) 2000/1A (11 kV Side) IdMinSetting of minimum
differential operating
current
0.10-0.60 0.25 * Ibase. Inst
%Z = 12.5% ( TAKE
FROM Name plate of
trafo. )
End section 1Cross-Over point b/w
slope1 & Slope-20.2 - 1.5 1.25 * Ibase.
Vector group = YNyn0 Slope section 2Setting of slope 2
stabilisation, (Slope 1
has fixed stabilization)
10.0 -50.0 % 40 * Ibias
End section 2 Cross-Over point b/wslope2 & Slope-3
1.0 -10 3 * Ibase.
Slope section 3Setting of slope 3
stabilisation,30.0 -100.0 % 80 * Ibias
2Differential Protection
(Unrestrained) ,Stage 2
ABB - RET
67087T>>
150/1A (132KV side)
2000/1A (11 kV Side)Idunre
Differential current,
High set (Unrestrained)
100- 5000 % of
Ibase10 * Ibase. Inst
Cross blocking logic OpCrossBlock = on ----- -----
Id2f / Id1f> (%) 2nd Harmonic restraint 5-100 % of fn 15%
Id5f/ Id1f> (%) 5th Harmonic restraint 5-100 % of fn 25%
Set the operation of
Negative sequence
differential protection
OpNegSeqDiff = = on ----- -----
IMinNegSeq =
Setting of minimum
negative sequence
differential current level
(0.01 - 0.10 )* Iopr. 0.04 * Iopr.
NegSeqROA Relay operate angle 60 - 90 Degrees 60
3Restricted Earth fault
Protection
ABB - RET
67064R LV 2000/1A (11 kV Side) Idmin (%) 4.0 -100.0 30% Inst
( Low impedance bsed.) ROA Relay operate angle 60 - 90 Degrees 60
64R HV 150/1A (132KV side) Idmin (%) 4.0 -100.0 30% Inst
ROA Relay operate angle 60 - 90 Degrees 60
Restricted Earth fault
Protection
ABB - RET
67064R LV 2000/1A (11 kV Side) U alarm Operate voltage ( 2 -500 ) V N / A
(High Impedence based.) t Alarm Operate time 0 - 60 sec N / A 5.0 sec.U trip Operate voltage ( 5 -900 ) V 109.5 V
t trip Operate time ----- ---- Inst
Rs Series Resistor 10 -20000 Ohms. 396 ohms.
64R HV 150/1A (132KV side) U alarm Operate voltage ( 2 -500 ) V N / A
t Alarm Operate time 0 - 60 sec N / A 5.0 sec.
U trip Operate voltage ( 5 -900 ) V 63 V
t trip Operate time ----- ---- Inst
Rs Series Resistor 10 -20000 Ohms. 250 ohms.
see ANNEXURE-01
CT Ratio / PT Ratio/
OTHER
Relay Setting
This settings may not
be applicable - while
we have adopted High -
Impedence based
REFR-Protection.
see ANNEXURE-01
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.
Type of ProtectionRelay Make /
No.
PROTECTION
ANSI CODE
Page 10 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
11/21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
12/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.
Type of ProtectionRelay Make /
No.
PROTECTION
ANSI CODE
5Stand -by Earth fault
Protection (LV Side)
ABB - RET
67051s-EFR LV 600/1A ( in NGR ) IN1>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 15% * Ibase
( 4th-Stage-
OFF)Dir mode ----- Non directional
1st-stage t11> DT setting 0 - 60 Secs ---- 2.0 sec.
NA k11> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs
IN2>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 25% * Ibase
Dir mode ----- Non directional
2nd-stage t1 2> DT setting 0 - 60 Secs ---- 1.5 sec.
NA k1 2> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs
IN3>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 30% * Ibase
Dir mode ----- Non directional
3rd-stage t1 3> DT setting 0 - 60 Secs ---- 1.0 sec.
NA k1 3> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs
6Under Frequency .
Protection.
ABB - RET
67081.U 132KV / 110 Volts. Operation mode on /Off on.
Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV
f < Start Freq.Freq setting / start
value.35 -75 Hz. 48.8 Hz.
Int_Bloc_Level Internal_Blocking_Level in % Of Ubase
0 -100 % Of UB 50%
Time delay operate 0 -60 sec. 0.2 sec.
Time delay Reset 0 -60 sec. 0.0 sec.
Time delay Restore 0 -60 sec. 0.0 sec.
Restore freq. 45 - 65 Hz. 50.10 Hz.
Timer Operation DT/ Voltage based DT ----
Unom 50 -150 % Ub 100 N / A
Umin 50 -150 % Ub 90 N / A
Exponent . 0.0 - 5.0 1 N / A
Tmax. 0.01 -60 sec. 1 N / A
Tmin 0.01 -60 sec. 1 N / A
6 Over Frequency . Protection.ABB - RET
67081.O 132KV / 110 Volts. Operation mode on /Off off
Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV
f > Start Freq.Freq setting / start
value.35 -75 Hz. 51.20 Hz.
Int_Bloc_LevelInternal_Blocking
_Level in % Of Ubase0 -100 % Of UB 50%
Time delay operate 0 -60 sec. 0.0 sec.
Time delay Reset 0 -60 sec. 0.0 sec.
see ANNEXURE-01
see ANNEXURE-01
see ANNEXURE-01
Page 12 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
13/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
6Rate of change of
Frequency . Protection.
ABB - RET
670Df /dt 132KV / 110 Volts. Operation mode on /Off off
Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV
f > Start Freq. Gradient. Freq .Gradient. -10 - 10 Hz/sec.. 0.5 Hz /sec.
Int_Bloc_LevelInternal_Blocking
_Level in % Of Ubase0 -100 % Of UB 50%
Operate Time ( tTrip ) 0 -60 sec. 0.2 sec.
Time delay Reset 0 -60 sec. 0.0 sec.
Time delay Restore 0 -60 sec. 0.0 sec.
Restore freq. 45 - 65 Hz. 49.90 Hz.
6Over Fluxing (Over
excitation)
ABB - RET
67099 (24) 220KV / 110 Volts. V/Hz> Voltage / Freq. 100 - 180% x U/f 110% x U/f
t alarm oprtng. Time 0-9000 sec. ---- 5sec.
T-alarm_level Alarm operate level 50 -120% 100%
V/Hz>> Voltage / Freq. 100 - 200% x U/f 140% x U/f
tmax.max. trip delay for I -
curves0 - 9000 sec. 1500 1800
tminmin. trip delay for I -
curves0 - 60 secs 4 sec 7
tr-pulse length of Pulse for trip 0 - 60 secs 0.1 0.1
X-leakageLeaakage reactance of
trafo. Winding.0.00-200 ohms. 0
t-coolingcooling time constant
for Trao.0.1 -9000 sec 1200 1200 sec.
CurveType curve selection.INVERSE/ IEEE /
TAILOR MADE.IEEE
see ANNEXURE-01
see ANNEXURE-01
Page 13 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
14/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.
Type of ProtectionRelay Make /
No.
PROTECTION
ANSI CODE
7 Local Breaker Back-upABB - RET
67050 LBB
150 / 1A
(132KV side)Operating mode backup trip mode
1 out of 4/ 2 out of 4
/ 1 out of 31 out of 3
Retrip-mode re-trip -Off
IP >Operate Ph. Current in
% of Ibase5-200% 10%
IN >Operate Residual.
Current in % of Ibase2-200% 10%
t1 > time delay of re-trip 0-60sec. 0 sec. 0 sec.
8Residual -Over voltage
Voltage Protection Protn.
ABB - RET
67059N 132KV/3 / 110V/3 Operation Mode ---- 0n , STAGE-1
UB = Open-delta Voltage CurveType DT/C-A/C-B/C-C DT
U1 > START VOLTAGE 1- 200 % UB 30 % UB
t1 > Definite Time Delay 0 - 6000 sec. 5 sec. 5 sec.
t1 min >Operating Time for I -
curves0 - 60 sec. 5 sec. NA
k1 > TMS 0.05 - 1.10 0.05 NA
HystAbs1Absolute Hysteresis
in% of Ubase.0 -100 % UB 0.5 % UB
Operation Mode ---- 0n , STAGE-2
CurveType DT/C-A/C-B/C-C DT
U2 > START VOLTAGE 1- 100 % UB 45 % UB
t2 > Definite Time Delay 0 - 6000 sec. 5 sec. 5 sec.
t2 min >Operating Time for I -
curves0 - 60 sec. 5 sec. NA
k2 > TMS 0.05 - 1.10 0.05 NA
HystAbs2Absolute Hysteresis
in% of Ubase.0 -100 % UB 0.5 % UB
9
Back-up Overcurrent/ Earth
fualt protection ( Non-dir /
Dir )
REX 52151 / 50 / 51N / 67
/ 67N150/1A (132KV side) Operation Mode
Not in use / DT/ NI/VI /
c-2 ETC. ( 1 to 15 )DT =01 31>
H-02 NOC3Low (51) 31> Current setting (I/ In) 0.10 - 5.00 xIn. 0.7
Operate time ( in DT) 0.05 - 300 Secs 0.05
time Multiplier ' K '( in
IDMT -mode )0.05 - 1.00 0.05 IDMT
IEEE- time DAIL in
IDMT -mode 0.5 - 15 0.5
NOC3High ( 50 / 51 ) Operation Mode Not in use / DT / inst.. Inst. = 02 31>>
31>> Current setting (I/ In) 0.10 - 40 xIn. 2
Operate time ( in DT -
Mode)0.05 - 300 Secs 0.05
DT- 0.05
SECS.
see ANNEXURE-01
see ANNEXURE-02
Page 14 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
15/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.
Type of ProtectionRelay Make /
No.
PROTECTION
ANSI CODE
REX 521 DEF2Low ( 67N / 51N ) Operation ModeNot in use / DT/ NI/VI /
c-2 ETC.DT =01 Io >->
Operation Criteria 67N,51N etc.., (1 to 05)4 = Non-directional
Io>-----
Operation direction forward / Reverse forward=0 N/A
Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)0 N/A
Basic Angle -90 deg to 60 deg. -90 deg N/A
Io > Current setting (Io/ In) 0.01 - 5.00 xIn. 0.075
Uo> Start voltage 2.0 - 100 % of Un. 75% N/A
Operate time ( in DT) 0.10 - 300 Secs 0.1
REX 521 DEF2High ( 67N ) Operation ModeNot in use / DT/ NI/VI /
c-2 ETC.DT =01 Io >>->
Operation Criteria 67N, etc.., (1 to 05)0 = Basic angle &
Uo-----
Operation direction forward / Reverse forward=0 ---
Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)
0=Io*sin(phi) ----
Basic Angle -90 deg to 60 deg. -90 deg -----
Io > Current setting (Io/ In) 0.01 - 5.00 xIn. 0.075
Uo> Start voltage 2.0 - 100 % of Un. 5%
Operate time ( in DT) 0.1 - 300 Secs 0.1
intermittent EFR Active / Not-active (0,1) 0 ---
REX 521 DOC6Low ( 67 ) Operation ModeNot in use / DT/ NI/VI /
c-2 ETC.DT =01 3I >_> 3I >>_>
Operation direction forward / Reverse forward=0 ---
Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)0=Io*sin(phi) ---
Basic Angle 0 deg to 90 deg. 60 deg ---
Io > Current setting (Io/ In) 0.05 - 40 xIn. 0.75
time Multiplier ' K '( in
IDMT -mode )0.05 - 1.00 0.05 IDMT
Operate time ( in DT) 0.05 - 300 Secs 0.05
see ANNEXURE-02
Page 15 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
16/21
PACP Recomended Relay Settings
Parameter Description Available range PSMTMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting RemarksSI.
No.Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
intermittent EFR -
protectionDisabled / Enabled(0,1) 0 ---
REX 521 DOC6High ( 67 ) Operation Mode Not in use / DT/ Inst. Inst. = 02 3I >>_> 3I >>_>
Operation direction forward / Reverse forward=0 ---
Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)0=Io*sin(phi) ---
Basic Angle 0 deg to 90 deg. 60 deg ---
Io > Current setting (Io/ In) 0.05 - 40 xIn. 0.05
Non directional
Operation
when the dir. Cannot be
determined ( 0, 1 )0 ----
Operate time ( in DT) 0.05 - 300 Secs 0.05
intermittent EFR -
protectionDisabled / Enabled(0,1) 0 ---
10 Under-Voltage Relay. RXEG 21 27 132000V/3 / 110V/3 Operation ModeDT -ALARM / trip
stageU< -
U< Alarm Under voltage setting. 40 -120 V 85 volts.
t > alarm time setting.(DT) 0 - 99 hrs. 3.0 sec.
U< Trip Under voltage setting. 40 -120 V 77 volts.
t > Trip time setting.(DT) 0 - 99 hrs. 1.0 sec.
11 Over-Voltage Relay. RXEG 21 59 132000V/3 / 110V/3 Operation Mode DT -ALARM / TRIPstage
U> -
U> Alarm Under voltage setting. 60 -160 V 115 volts.
t > alarm time setting.(DT) 0 - 99 hrs. 3.0 sec.
U> Trip Under voltage setting. 40 -120 V 121 volts.
t > Trip time setting.(DT) 0 - 99 hrs. 1.0 sec.
see ANNEXURE-01
Page 16 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
17/21
APPM-MDP
1)
a) Initial setting:( Idmin) ; ---This setting covers the un-balance created in the differential operating current by the
+10% to -15% , and hence the mean tap value : [ 10 +(-15) ] / 2 = - 2.5% and so, the Hv -amps @ mean tap value
2.56% variation in the HV-currents when mean value is considered. Also,in practice typically the initial minimum dif
30% - 40% . However, RET-670 is in-built with OLTC compensation factor and it is possible to set the Id(min) to m
preferred to se the Idmin = 0.25 of Ibase.
b) Endsection-1 setting: ; ---This is the most sensitive part of the charecteristic.Uncompensated OLTC currents a
so, the slope in this section is always zero.The end lit of this section is set at 1.25 after ensuring the risk of higher fa
set in the RET-670.
c) Slopesection-2 , End section-2 ,Slopesection-3 ; --- These settings are typically adopted to form the Differntia
for various applications as per the Technical -reference manual-rev-b (p-116) .Also, the basis for these settings are a
d) Unrestrain -high set ,Idunre ; ---This setting by defualt set at 10.This setting ensures the operation instantaneo
only due to internal fualts. Also, this by-passes the harmonic test in its operation and so, called unstabilised operatio
2)
It is a common known fact that ( compared to Low impedence based REFR protection) , High impedence based
high impedence based protections are current / voltage based , and hence makes use of METROSIL & STABILIZI
The settings for Metrosil and Stablising resistor are as under : CTR -HV = 150 / 1A . R nct = ( as per the field tes
RET-670 & REX-521 RELAY - DETAILED DESCRIPT
87T -TRAFO. DIFFERENTIAL PROTECTION: The charecteristic for this protection function as adopted i
64R-HV & 64R-LV -TRAFO.HIGH IMPEDENCE BASED RESTRICTED EARTH FUALT PROTECTION :
Page 17 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
18/21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
19/21
APPM-MDP
Calculat ions for REFR -HV :
Rnct = 2.0 ohms , Rlead = 2.0 ohms. & Rct(ph) = 4.0 ohms. ( for calculations Rct(ph) sha
Nct -Ratio = 150 /1A
Uk -Nct = 150 Volts. ( as phase CT's are designed for Uk> 400volts,Hence the chances g
Excitation current for NCT < 30 mA @ Vk /2 ( considering the worst case ).
IfL -HV = 109.35A , CTR= 150
If = ( %Z ) x IfL = 12.5 x 109.35 = 1367 A ( Max. expected through fault current expected.
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (1367 / 150) [4 +2 ] = 109.36
As Uk is >>> than 150 V as per the Trafo. Name plate data for NCT.The operation of pro
Us =Uk /2 = 54.68 volts.=55 V (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.
Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.
The setting to adopted is = 115% of Us> = 1.15 x 55 = 63 (Approx.) volts.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }Ir = Current through the Relay @ voltage Us> = 63/250 = 252 mA .
Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0504+3x0.0252) = 126mA.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 150{ 252+5+126 } = 5
This is well below the value minimum fualt current, and only constitute 38.3 % of Rated C
Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 2 ) = 0.12 A
so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.
Calculat ions fo r REFR -LV :
Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) sh
IfL -LV = 1255.15A , CTR= 2000/1A
Nct -Ratio = 2000 /1A
Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chanExcitation current for NCT < 30 mA @ Vk / 4.
If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expecte
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 18
As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of pro
Us =Uk /2 = 94.14 volts.=95 V (approx.)
Hence, the Stabilizing Resistor , Rs= Us/Ir. = 95 / 0.24 =395.83 = 396 Ohms (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.
The setting to adopted is = 115% of Us> = 1.15 x 95 = 109.5 (Approx.) volts.
Calculation of Stabilizing Resistor :As per manuals of RET ,
This can be directly selected to a value Rs=396 ohms .
Now , this value of resistor should satisfy the below eqn.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }
Ir = Current through the Relay @ voltage Us> = 109.5/396 = 276.5 mA .
Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 2000{ 276.5+5+218 }
This is well below the value minimum fualt current, and only constitute 49.95 % of Rated
Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A
so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 396 ohms. & Us>= 109.5 volts.
Page 19 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
20/21
APPM-MDP
3) 51Ns -HV & LV :
The stand by earth-fualt protection , is mainly to Protect the NGR from over heating due to
.So, the settings adopted have to be set in Definite time mode depending upon it's therma
is 600A for 30 secs. And hence , the settings should be planned such that the HV - S/b E
compeletely isolating the Transformer from the circuit. However , as discussed in the prio
in the System , then it's setting should be minimised to the value of Lower -rating NGR or
for your reference. Hence, the setting should be adopted for
HV S/B EFR :
CTR= 150 /1A ,
Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A ,Else 8
Time setting: definite time , and should be with in the Rated duty of NGR i.e 3.0 secs.
LV S/B EFR :
CTR= 600 /1A ,
Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A .)
4) 99 (24) : Over fluxing Protection.
Actual set limits for this protection should be in accordance with the data submitted by the
of as in the relay , suits for most of the applications. These default settings programmed a
applications. As pe the TRAFo. " Permissible Over-excitation Curve " ( attached with mail
Some Important Factors / Notes for Over fluxing Protection:
1) Over excitaion occurs from the excessive applied voltage, possibly in combination with b
Transformers are directly connected to the Generators.
2) Bmax is directly proportional to the Induced voltage., as E = 4.44 x f x n x Bmax . A
3) The calculation of the relative ( M ) ,is based on the V/Hz ratio..
4) As per IEC 60076-1 , All transformers shall be capable of operating continuously at 10%
the User does not know what exactly to be set , then th e standard IEC-60076 -1 section-
5) As long as the E/f or V/F did not cross the relative value (M) set of the relay, the Trafo.
Over excitaion = M - V/Hz >6) Operatin Time of the Overexcitation Protection :
The most famous Law ,so called IEEE Law approximates a square Law
over excitation capability charecteristics. They can match a well a transformer core capabil
t op = 0.18 x k [ M - V/Hz>)2 .= 0.18 x k / ( Overexcitaton ) .
Where: M -- is the , Mean value in the interval from t=0 to t=top .
V/Hz > ---- is the Max. continously allowed voltage at no -Load and rated Freque
K ----- is the time multiplier setting for the inverse time functions as usual & sele
Since , from - " Trfo. Data curves " over Excitation of beyond 110% is not allowed so, fo
Also, the Alarm setting in the relay is in-built and is 2% less than the set value , with a defin
chart. We have attached a " over -Excitation Protection basis for your reference along wit
Page 20 of 21
-
8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB
21/21
APPM-MDP
5) 81.O & 81.U - or df/dt Protection. : ( RET-670 )
The basis for this settings when derived from the over excitation limits ( V/Hz - ratio lim
found to be extremely high or extremely low , such as ( f > becomes 55 Hz. & f < becomes
Regulatory Rules bound to that region. We request M/s Customer to do this setting at site
6) 27 & 59 - Protection. : ( REXEG-21 )
These settings are based on the common practice adopted at most of the installations. Als
India. The values adopted are --- 110% of the 110V = 121 volts. ( PT -secondary Rated-
---- 70% of the 110V = 77 Volts ( PT -secondary Rated-val
7) 50/51, 50N/51N, 67 & 67N - Protection. : ( Rex-521)
These settings are based on the relay co-ordination study , and direction is also based on
relay cordination timings , then the Directional - OCR shall be graded fastly to look towards
time delay. Also, the current settings for these Relays are the full-load current of the Equip
TMS , needs a DETAILED STUDY.
Calculat ions for REFR -LV :
Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) sh
IfL -LV = 15690 A , CTR= 2000/1 A
Nct -Ratio = 2000 /1A
Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chan
Excitation current for NCT < 30 mA @ Vk / 4.
If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expecte
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 18
As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of pro
Us =Uk /2 = 95 volts.=95 V (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.
The setting to adopted is = 115% of Us> = 1.15 x 101 = 117 (Approx.) volts.
Calculation of Stabilizing Resistor :As per manuals of RET ,
This can be directly selected to a value Rs=450 ohms .
Now , this value of resistor should satisfy the below eqn.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }
Ir = Current through the Relay @ voltage Us> = 117/450 = 260 mA .
Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 3000{ 260+5+218 } =
This is well below the value minimum fualt current, and only constitute 48.3 % of Rated C
Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A
so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 450 ohms. & Us>= 117 volts.