relay setting chart _ crp panel_shambhu_revb

Upload: mahesh

Post on 04-Jun-2018

259 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    1/21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    2/21

    1

    Differential

    Protection

    (Restrained)

    ABB - RET

    67087T>

    Stage 1 (T2D1 )

    2

    Differential

    Protection

    (Unrestrained),Stage 2

    ABB - RET

    670 87T>>

    3

    Earth faultABB - RET

    67064R LV

    ow

    RECOMMEND

    SI. No. Type ofProtection

    Relay Make/ No.

    PROTECTION ANSICODE

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    3/21

    64R HV

    es r c e

    Earth faultABB - RET

    67064R LV

    g

    Im edence

    64R HV

    4

    Stand -by

    Earth fault

    Protection

    HV Side

    ABB - RET

    67051s-EFR HV

    ( 4th-Stage- OFF)

    RET-670 , TIME CO-ORDINATED SETTINGS OF Stan-by-

    EFR ( HV & LV )

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    4/21

    Stand -by Earth fault

    Protection (LV Side)

    ABB - RET

    67051s-EFR LV

    I_base

    I1>

    t1>

    I2>

    t2>

    I3>

    t3>

    I4>

    t4>

    Stand -by Earth fault

    Protection (HV Side)

    ABB - RET

    67051s-EFR HV

    I_base

    I1>

    t1>

    I2>

    t2>

    I3>

    t3>

    I4>

    t4>

    STAGE-3

    STAGE-4

    STAGE-1

    STAGE-3

    STAGE-4

    STAGE-1

    STAGE-2

    STAGE-2

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    5/21

    Parameter Description

    150/1A (132KV side) Operation on

    2000/1A (11 kV Side) IdMinSetting of minimum

    differential operating current

    %Z = 12.5% ( TAKE

    FROM Name plate of

    trafo. )End section 1 Cross-Over point b/w slope1

    & Slope-2

    Vector group = YNyn0 Slope section 2Setting of slope 2

    stabilisation, (Slope 1 has

    fixed stabilization)

    End section 2Cross-Over point b/w slope2

    & Slope-3

    Slope section 3Setting of slope 3

    stabilisation,

    150/1A (132KV side)

    2000/1A (11 kV Side) Idunre

    Differential current, High set

    (Unrestrained)

    Cross blocking logic OpCrossBlock = on

    Id2f / Id1f> (%) 2nd Harmonic restraint

    Id5f/ Id1f> (%) 5th Harmonic restraint

    Set the operation of

    Negative sequence

    differential protection

    OpNegSeqDiff = = on

    IMinNegSeq =

    Setting of minimum negative

    sequence differential currentlevel

    NegSeqROA Relay operate angle

    2000/1A (11 kV Side) Idmin (%)

    ROA Relay operate angle

    D RELAY SETTING CHART FOR 132/11.5kV, 20/25 MV

    CT Ratio / PT Ratio/OTHER

    Relay

    Available setting range

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    6/21

    150/1A (132KV side) Idmin (%)

    ROA Relay operate angle

    2000/1A (11 kV Side) U alarm Operate voltage

    t Alarm Operate time

    U trip Operate voltage

    t trip Operate time

    Rs Series Resistor

    150/1A (132KV side) U alarm Operate voltage

    t Alarm Operate time

    U trip Operate voltage

    t trip Operate time

    Rs Series Resistor

    150/1A (132KV side) IN1>/ Ib Base Current Setting

    Dir mode

    Ibase

    1st-stage t11> DT setting

    NA k11> TMS

    IN2>/ Ib Base Current Setting

    Dir mode

    2nd-stage t1 2> DT setting

    NA k1 2> TMS

    IN3>/ Ib Base Current Setting

    Dir mode

    3rd-stage t1 3> DT setting

    NA k1 3> TMS

    NEW SETTINGS OLD SETTINGS. Remarks

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    7/21

    100% 80%

    80% of Ibase 80% of Ibase

    0.96 sec 0.0 sec

    50% of Ibase 50% of Ibase

    1.2 sec 0.40 sec

    40% of Ibase 40% of Ibase

    1.4sec 0.80 sec

    30% of Ibase 30% of Ibase

    1.6sec 1.20 sec

    100% 80%

    80% of Ibase 80% of Ibase

    1.26 sec 0.3 sec

    100% of Ibase 100% of Ibase

    1.46 sec 0.15 sec

    off off

    OFF OFF

    off off

    OFF OFF

    t= 0.96 sec. is the Normal-

    EFR ( in incomer of 11KV-

    rex-521 ) Relay's time

    setting. So, the same has

    been maintained as trip-

    time to SB-EFR-LV.

    Assuming a time

    descripation of 0.3 sec.

    b/w 11KV & 132KV -trip

    time , t1= 0.96 + 0.3sec. =

    1.26 SEC.

    600/1A (132KV side)

    150/1A (132KV side)

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    8/21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    9/21

    4.0 -100.0 30% Inst

    60 - 90 Degrees 60

    ( 2 -500 ) V N / A

    0 - 60 sec N / A 5.0 sec.

    ( 5 -900 ) V 109.5 V

    ----- ---- Inst

    10 -20000 Ohms. 396 ohms.

    ( 2 -500 ) V N / A

    0 - 60 sec N / A 5.0 sec.

    ( 5 -900 ) V 63 V

    ----- ---- Inst

    10 -20000 Ohms. 250 ohms.

    1.0 -2500.0 %

    Ibase20% * Ibase

    ----- Non directional

    0 - 60 Secs ---- 1.0 sec.

    0.05 - 999 0.15 Secs NI 0.15 Secs

    1.0 -2500.0 %

    Ibase 15% * Ibase

    ----- Non directional

    0 - 60 Secs ---- 1.5 sec.

    0.05 - 999 0.15 Secs NI 0.15 Secs

    1.0 -2500.0 %

    Ibase10% * Ibase

    ----- Non directional

    0 - 60 Secs ---- 2.0 sec.

    0.05 - 999 0.15 Secs NI 0.15 Secs

    a op e g - mpe ence

    based REFR-Protection.

    see ANNEXURE-01

    see ANNEXURE-01

    see ANNEXURE-01 ---

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    10/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    1Differential Protection

    (Restrained)

    ABB - RET

    67087T> 150/1A (132KV side) Operation on ---- ---- ----

    Stage 1 (T2D1 ) 2000/1A (11 kV Side) IdMinSetting of minimum

    differential operating

    current

    0.10-0.60 0.25 * Ibase. Inst

    %Z = 12.5% ( TAKE

    FROM Name plate of

    trafo. )

    End section 1Cross-Over point b/w

    slope1 & Slope-20.2 - 1.5 1.25 * Ibase.

    Vector group = YNyn0 Slope section 2Setting of slope 2

    stabilisation, (Slope 1

    has fixed stabilization)

    10.0 -50.0 % 40 * Ibias

    End section 2 Cross-Over point b/wslope2 & Slope-3

    1.0 -10 3 * Ibase.

    Slope section 3Setting of slope 3

    stabilisation,30.0 -100.0 % 80 * Ibias

    2Differential Protection

    (Unrestrained) ,Stage 2

    ABB - RET

    67087T>>

    150/1A (132KV side)

    2000/1A (11 kV Side)Idunre

    Differential current,

    High set (Unrestrained)

    100- 5000 % of

    Ibase10 * Ibase. Inst

    Cross blocking logic OpCrossBlock = on ----- -----

    Id2f / Id1f> (%) 2nd Harmonic restraint 5-100 % of fn 15%

    Id5f/ Id1f> (%) 5th Harmonic restraint 5-100 % of fn 25%

    Set the operation of

    Negative sequence

    differential protection

    OpNegSeqDiff = = on ----- -----

    IMinNegSeq =

    Setting of minimum

    negative sequence

    differential current level

    (0.01 - 0.10 )* Iopr. 0.04 * Iopr.

    NegSeqROA Relay operate angle 60 - 90 Degrees 60

    3Restricted Earth fault

    Protection

    ABB - RET

    67064R LV 2000/1A (11 kV Side) Idmin (%) 4.0 -100.0 30% Inst

    ( Low impedance bsed.) ROA Relay operate angle 60 - 90 Degrees 60

    64R HV 150/1A (132KV side) Idmin (%) 4.0 -100.0 30% Inst

    ROA Relay operate angle 60 - 90 Degrees 60

    Restricted Earth fault

    Protection

    ABB - RET

    67064R LV 2000/1A (11 kV Side) U alarm Operate voltage ( 2 -500 ) V N / A

    (High Impedence based.) t Alarm Operate time 0 - 60 sec N / A 5.0 sec.U trip Operate voltage ( 5 -900 ) V 109.5 V

    t trip Operate time ----- ---- Inst

    Rs Series Resistor 10 -20000 Ohms. 396 ohms.

    64R HV 150/1A (132KV side) U alarm Operate voltage ( 2 -500 ) V N / A

    t Alarm Operate time 0 - 60 sec N / A 5.0 sec.

    U trip Operate voltage ( 5 -900 ) V 63 V

    t trip Operate time ----- ---- Inst

    Rs Series Resistor 10 -20000 Ohms. 250 ohms.

    see ANNEXURE-01

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    This settings may not

    be applicable - while

    we have adopted High -

    Impedence based

    REFR-Protection.

    see ANNEXURE-01

    Available setting range

    see ANNEXURE-01

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.

    Type of ProtectionRelay Make /

    No.

    PROTECTION

    ANSI CODE

    Page 10 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    11/21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    12/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    Available setting range

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.

    Type of ProtectionRelay Make /

    No.

    PROTECTION

    ANSI CODE

    5Stand -by Earth fault

    Protection (LV Side)

    ABB - RET

    67051s-EFR LV 600/1A ( in NGR ) IN1>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 15% * Ibase

    ( 4th-Stage-

    OFF)Dir mode ----- Non directional

    1st-stage t11> DT setting 0 - 60 Secs ---- 2.0 sec.

    NA k11> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs

    IN2>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 25% * Ibase

    Dir mode ----- Non directional

    2nd-stage t1 2> DT setting 0 - 60 Secs ---- 1.5 sec.

    NA k1 2> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs

    IN3>/ Ib Base Current Setting 1.0 -2500.0 % Ibase 30% * Ibase

    Dir mode ----- Non directional

    3rd-stage t1 3> DT setting 0 - 60 Secs ---- 1.0 sec.

    NA k1 3> TMS 0.05 - 999 0.15 Secs NI 0.15 Secs

    6Under Frequency .

    Protection.

    ABB - RET

    67081.U 132KV / 110 Volts. Operation mode on /Off on.

    Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV

    f < Start Freq.Freq setting / start

    value.35 -75 Hz. 48.8 Hz.

    Int_Bloc_Level Internal_Blocking_Level in % Of Ubase

    0 -100 % Of UB 50%

    Time delay operate 0 -60 sec. 0.2 sec.

    Time delay Reset 0 -60 sec. 0.0 sec.

    Time delay Restore 0 -60 sec. 0.0 sec.

    Restore freq. 45 - 65 Hz. 50.10 Hz.

    Timer Operation DT/ Voltage based DT ----

    Unom 50 -150 % Ub 100 N / A

    Umin 50 -150 % Ub 90 N / A

    Exponent . 0.0 - 5.0 1 N / A

    Tmax. 0.01 -60 sec. 1 N / A

    Tmin 0.01 -60 sec. 1 N / A

    6 Over Frequency . Protection.ABB - RET

    67081.O 132KV / 110 Volts. Operation mode on /Off off

    Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV

    f > Start Freq.Freq setting / start

    value.35 -75 Hz. 51.20 Hz.

    Int_Bloc_LevelInternal_Blocking

    _Level in % Of Ubase0 -100 % Of UB 50%

    Time delay operate 0 -60 sec. 0.0 sec.

    Time delay Reset 0 -60 sec. 0.0 sec.

    see ANNEXURE-01

    see ANNEXURE-01

    see ANNEXURE-01

    Page 12 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    13/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    Available setting range

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.Type of Protection

    Relay Make /

    No.

    PROTECTION

    ANSI CODE

    6Rate of change of

    Frequency . Protection.

    ABB - RET

    670Df /dt 132KV / 110 Volts. Operation mode on /Off off

    Ubase (KV) Base voltage setting 0.05 - 2000 volts. 132 KV

    f > Start Freq. Gradient. Freq .Gradient. -10 - 10 Hz/sec.. 0.5 Hz /sec.

    Int_Bloc_LevelInternal_Blocking

    _Level in % Of Ubase0 -100 % Of UB 50%

    Operate Time ( tTrip ) 0 -60 sec. 0.2 sec.

    Time delay Reset 0 -60 sec. 0.0 sec.

    Time delay Restore 0 -60 sec. 0.0 sec.

    Restore freq. 45 - 65 Hz. 49.90 Hz.

    6Over Fluxing (Over

    excitation)

    ABB - RET

    67099 (24) 220KV / 110 Volts. V/Hz> Voltage / Freq. 100 - 180% x U/f 110% x U/f

    t alarm oprtng. Time 0-9000 sec. ---- 5sec.

    T-alarm_level Alarm operate level 50 -120% 100%

    V/Hz>> Voltage / Freq. 100 - 200% x U/f 140% x U/f

    tmax.max. trip delay for I -

    curves0 - 9000 sec. 1500 1800

    tminmin. trip delay for I -

    curves0 - 60 secs 4 sec 7

    tr-pulse length of Pulse for trip 0 - 60 secs 0.1 0.1

    X-leakageLeaakage reactance of

    trafo. Winding.0.00-200 ohms. 0

    t-coolingcooling time constant

    for Trao.0.1 -9000 sec 1200 1200 sec.

    CurveType curve selection.INVERSE/ IEEE /

    TAILOR MADE.IEEE

    see ANNEXURE-01

    see ANNEXURE-01

    Page 13 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    14/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    Available setting range

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.

    Type of ProtectionRelay Make /

    No.

    PROTECTION

    ANSI CODE

    7 Local Breaker Back-upABB - RET

    67050 LBB

    150 / 1A

    (132KV side)Operating mode backup trip mode

    1 out of 4/ 2 out of 4

    / 1 out of 31 out of 3

    Retrip-mode re-trip -Off

    IP >Operate Ph. Current in

    % of Ibase5-200% 10%

    IN >Operate Residual.

    Current in % of Ibase2-200% 10%

    t1 > time delay of re-trip 0-60sec. 0 sec. 0 sec.

    8Residual -Over voltage

    Voltage Protection Protn.

    ABB - RET

    67059N 132KV/3 / 110V/3 Operation Mode ---- 0n , STAGE-1

    UB = Open-delta Voltage CurveType DT/C-A/C-B/C-C DT

    U1 > START VOLTAGE 1- 200 % UB 30 % UB

    t1 > Definite Time Delay 0 - 6000 sec. 5 sec. 5 sec.

    t1 min >Operating Time for I -

    curves0 - 60 sec. 5 sec. NA

    k1 > TMS 0.05 - 1.10 0.05 NA

    HystAbs1Absolute Hysteresis

    in% of Ubase.0 -100 % UB 0.5 % UB

    Operation Mode ---- 0n , STAGE-2

    CurveType DT/C-A/C-B/C-C DT

    U2 > START VOLTAGE 1- 100 % UB 45 % UB

    t2 > Definite Time Delay 0 - 6000 sec. 5 sec. 5 sec.

    t2 min >Operating Time for I -

    curves0 - 60 sec. 5 sec. NA

    k2 > TMS 0.05 - 1.10 0.05 NA

    HystAbs2Absolute Hysteresis

    in% of Ubase.0 -100 % UB 0.5 % UB

    9

    Back-up Overcurrent/ Earth

    fualt protection ( Non-dir /

    Dir )

    REX 52151 / 50 / 51N / 67

    / 67N150/1A (132KV side) Operation Mode

    Not in use / DT/ NI/VI /

    c-2 ETC. ( 1 to 15 )DT =01 31>

    H-02 NOC3Low (51) 31> Current setting (I/ In) 0.10 - 5.00 xIn. 0.7

    Operate time ( in DT) 0.05 - 300 Secs 0.05

    time Multiplier ' K '( in

    IDMT -mode )0.05 - 1.00 0.05 IDMT

    IEEE- time DAIL in

    IDMT -mode 0.5 - 15 0.5

    NOC3High ( 50 / 51 ) Operation Mode Not in use / DT / inst.. Inst. = 02 31>>

    31>> Current setting (I/ In) 0.10 - 40 xIn. 2

    Operate time ( in DT -

    Mode)0.05 - 300 Secs 0.05

    DT- 0.05

    SECS.

    see ANNEXURE-01

    see ANNEXURE-02

    Page 14 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    15/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    Available setting range

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.

    Type of ProtectionRelay Make /

    No.

    PROTECTION

    ANSI CODE

    REX 521 DEF2Low ( 67N / 51N ) Operation ModeNot in use / DT/ NI/VI /

    c-2 ETC.DT =01 Io >->

    Operation Criteria 67N,51N etc.., (1 to 05)4 = Non-directional

    Io>-----

    Operation direction forward / Reverse forward=0 N/A

    Operation

    Charecteristics.

    IoSin(phi) / IoCos(phi)

    ( 0,1)0 N/A

    Basic Angle -90 deg to 60 deg. -90 deg N/A

    Io > Current setting (Io/ In) 0.01 - 5.00 xIn. 0.075

    Uo> Start voltage 2.0 - 100 % of Un. 75% N/A

    Operate time ( in DT) 0.10 - 300 Secs 0.1

    REX 521 DEF2High ( 67N ) Operation ModeNot in use / DT/ NI/VI /

    c-2 ETC.DT =01 Io >>->

    Operation Criteria 67N, etc.., (1 to 05)0 = Basic angle &

    Uo-----

    Operation direction forward / Reverse forward=0 ---

    Operation

    Charecteristics.

    IoSin(phi) / IoCos(phi)

    ( 0,1)

    0=Io*sin(phi) ----

    Basic Angle -90 deg to 60 deg. -90 deg -----

    Io > Current setting (Io/ In) 0.01 - 5.00 xIn. 0.075

    Uo> Start voltage 2.0 - 100 % of Un. 5%

    Operate time ( in DT) 0.1 - 300 Secs 0.1

    intermittent EFR Active / Not-active (0,1) 0 ---

    REX 521 DOC6Low ( 67 ) Operation ModeNot in use / DT/ NI/VI /

    c-2 ETC.DT =01 3I >_> 3I >>_>

    Operation direction forward / Reverse forward=0 ---

    Operation

    Charecteristics.

    IoSin(phi) / IoCos(phi)

    ( 0,1)0=Io*sin(phi) ---

    Basic Angle 0 deg to 90 deg. 60 deg ---

    Io > Current setting (Io/ In) 0.05 - 40 xIn. 0.75

    time Multiplier ' K '( in

    IDMT -mode )0.05 - 1.00 0.05 IDMT

    Operate time ( in DT) 0.05 - 300 Secs 0.05

    see ANNEXURE-02

    Page 15 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    16/21

    PACP Recomended Relay Settings

    Parameter Description Available range PSMTMS/DMT

    (sec)

    CT Ratio / PT Ratio/

    OTHER

    Relay Setting

    Available setting range

    RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER

    Recommended setting RemarksSI.

    No.Type of Protection

    Relay Make /

    No.

    PROTECTION

    ANSI CODE

    intermittent EFR -

    protectionDisabled / Enabled(0,1) 0 ---

    REX 521 DOC6High ( 67 ) Operation Mode Not in use / DT/ Inst. Inst. = 02 3I >>_> 3I >>_>

    Operation direction forward / Reverse forward=0 ---

    Operation

    Charecteristics.

    IoSin(phi) / IoCos(phi)

    ( 0,1)0=Io*sin(phi) ---

    Basic Angle 0 deg to 90 deg. 60 deg ---

    Io > Current setting (Io/ In) 0.05 - 40 xIn. 0.05

    Non directional

    Operation

    when the dir. Cannot be

    determined ( 0, 1 )0 ----

    Operate time ( in DT) 0.05 - 300 Secs 0.05

    intermittent EFR -

    protectionDisabled / Enabled(0,1) 0 ---

    10 Under-Voltage Relay. RXEG 21 27 132000V/3 / 110V/3 Operation ModeDT -ALARM / trip

    stageU< -

    U< Alarm Under voltage setting. 40 -120 V 85 volts.

    t > alarm time setting.(DT) 0 - 99 hrs. 3.0 sec.

    U< Trip Under voltage setting. 40 -120 V 77 volts.

    t > Trip time setting.(DT) 0 - 99 hrs. 1.0 sec.

    11 Over-Voltage Relay. RXEG 21 59 132000V/3 / 110V/3 Operation Mode DT -ALARM / TRIPstage

    U> -

    U> Alarm Under voltage setting. 60 -160 V 115 volts.

    t > alarm time setting.(DT) 0 - 99 hrs. 3.0 sec.

    U> Trip Under voltage setting. 40 -120 V 121 volts.

    t > Trip time setting.(DT) 0 - 99 hrs. 1.0 sec.

    see ANNEXURE-01

    Page 16 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    17/21

    APPM-MDP

    1)

    a) Initial setting:( Idmin) ; ---This setting covers the un-balance created in the differential operating current by the

    +10% to -15% , and hence the mean tap value : [ 10 +(-15) ] / 2 = - 2.5% and so, the Hv -amps @ mean tap value

    2.56% variation in the HV-currents when mean value is considered. Also,in practice typically the initial minimum dif

    30% - 40% . However, RET-670 is in-built with OLTC compensation factor and it is possible to set the Id(min) to m

    preferred to se the Idmin = 0.25 of Ibase.

    b) Endsection-1 setting: ; ---This is the most sensitive part of the charecteristic.Uncompensated OLTC currents a

    so, the slope in this section is always zero.The end lit of this section is set at 1.25 after ensuring the risk of higher fa

    set in the RET-670.

    c) Slopesection-2 , End section-2 ,Slopesection-3 ; --- These settings are typically adopted to form the Differntia

    for various applications as per the Technical -reference manual-rev-b (p-116) .Also, the basis for these settings are a

    d) Unrestrain -high set ,Idunre ; ---This setting by defualt set at 10.This setting ensures the operation instantaneo

    only due to internal fualts. Also, this by-passes the harmonic test in its operation and so, called unstabilised operatio

    2)

    It is a common known fact that ( compared to Low impedence based REFR protection) , High impedence based

    high impedence based protections are current / voltage based , and hence makes use of METROSIL & STABILIZI

    The settings for Metrosil and Stablising resistor are as under : CTR -HV = 150 / 1A . R nct = ( as per the field tes

    RET-670 & REX-521 RELAY - DETAILED DESCRIPT

    87T -TRAFO. DIFFERENTIAL PROTECTION: The charecteristic for this protection function as adopted i

    64R-HV & 64R-LV -TRAFO.HIGH IMPEDENCE BASED RESTRICTED EARTH FUALT PROTECTION :

    Page 17 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    18/21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    19/21

    APPM-MDP

    Calculat ions for REFR -HV :

    Rnct = 2.0 ohms , Rlead = 2.0 ohms. & Rct(ph) = 4.0 ohms. ( for calculations Rct(ph) sha

    Nct -Ratio = 150 /1A

    Uk -Nct = 150 Volts. ( as phase CT's are designed for Uk> 400volts,Hence the chances g

    Excitation current for NCT < 30 mA @ Vk /2 ( considering the worst case ).

    IfL -HV = 109.35A , CTR= 150

    If = ( %Z ) x IfL = 12.5 x 109.35 = 1367 A ( Max. expected through fault current expected.

    Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (1367 / 150) [4 +2 ] = 109.36

    As Uk is >>> than 150 V as per the Trafo. Name plate data for NCT.The operation of pro

    Us =Uk /2 = 54.68 volts.=55 V (approx.)

    Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.

    Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.

    The setting to adopted is = 115% of Us> = 1.15 x 55 = 63 (Approx.) volts.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }Ir = Current through the Relay @ voltage Us> = 63/250 = 252 mA .

    Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.

    nxIe = no. of CT's and their average Excitation currents. = (0.0504+3x0.0252) = 126mA.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 150{ 252+5+126 } = 5

    This is well below the value minimum fualt current, and only constitute 38.3 % of Rated C

    Also,

    As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 2 ) = 0.12 A

    so, the setting is safe.

    Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.

    Calculat ions fo r REFR -LV :

    Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) sh

    IfL -LV = 1255.15A , CTR= 2000/1A

    Nct -Ratio = 2000 /1A

    Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chanExcitation current for NCT < 30 mA @ Vk / 4.

    If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expecte

    Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 18

    As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of pro

    Us =Uk /2 = 94.14 volts.=95 V (approx.)

    Hence, the Stabilizing Resistor , Rs= Us/Ir. = 95 / 0.24 =395.83 = 396 Ohms (approx.)

    Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.

    The setting to adopted is = 115% of Us> = 1.15 x 95 = 109.5 (Approx.) volts.

    Calculation of Stabilizing Resistor :As per manuals of RET ,

    This can be directly selected to a value Rs=396 ohms .

    Now , this value of resistor should satisfy the below eqn.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }

    Ir = Current through the Relay @ voltage Us> = 109.5/396 = 276.5 mA .

    Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.

    nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 2000{ 276.5+5+218 }

    This is well below the value minimum fualt current, and only constitute 49.95 % of Rated

    Also,

    As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A

    so, the setting is safe.

    Hence, the Stabilizing Resistor , Rs= 396 ohms. & Us>= 109.5 volts.

    Page 19 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    20/21

    APPM-MDP

    3) 51Ns -HV & LV :

    The stand by earth-fualt protection , is mainly to Protect the NGR from over heating due to

    .So, the settings adopted have to be set in Definite time mode depending upon it's therma

    is 600A for 30 secs. And hence , the settings should be planned such that the HV - S/b E

    compeletely isolating the Transformer from the circuit. However , as discussed in the prio

    in the System , then it's setting should be minimised to the value of Lower -rating NGR or

    for your reference. Hence, the setting should be adopted for

    HV S/B EFR :

    CTR= 150 /1A ,

    Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A ,Else 8

    Time setting: definite time , and should be with in the Rated duty of NGR i.e 3.0 secs.

    LV S/B EFR :

    CTR= 600 /1A ,

    Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A .)

    4) 99 (24) : Over fluxing Protection.

    Actual set limits for this protection should be in accordance with the data submitted by the

    of as in the relay , suits for most of the applications. These default settings programmed a

    applications. As pe the TRAFo. " Permissible Over-excitation Curve " ( attached with mail

    Some Important Factors / Notes for Over fluxing Protection:

    1) Over excitaion occurs from the excessive applied voltage, possibly in combination with b

    Transformers are directly connected to the Generators.

    2) Bmax is directly proportional to the Induced voltage., as E = 4.44 x f x n x Bmax . A

    3) The calculation of the relative ( M ) ,is based on the V/Hz ratio..

    4) As per IEC 60076-1 , All transformers shall be capable of operating continuously at 10%

    the User does not know what exactly to be set , then th e standard IEC-60076 -1 section-

    5) As long as the E/f or V/F did not cross the relative value (M) set of the relay, the Trafo.

    Over excitaion = M - V/Hz >6) Operatin Time of the Overexcitation Protection :

    The most famous Law ,so called IEEE Law approximates a square Law

    over excitation capability charecteristics. They can match a well a transformer core capabil

    t op = 0.18 x k [ M - V/Hz>)2 .= 0.18 x k / ( Overexcitaton ) .

    Where: M -- is the , Mean value in the interval from t=0 to t=top .

    V/Hz > ---- is the Max. continously allowed voltage at no -Load and rated Freque

    K ----- is the time multiplier setting for the inverse time functions as usual & sele

    Since , from - " Trfo. Data curves " over Excitation of beyond 110% is not allowed so, fo

    Also, the Alarm setting in the relay is in-built and is 2% less than the set value , with a defin

    chart. We have attached a " over -Excitation Protection basis for your reference along wit

    Page 20 of 21

  • 8/13/2019 Relay Setting Chart _ CRP Panel_Shambhu_REVB

    21/21

    APPM-MDP

    5) 81.O & 81.U - or df/dt Protection. : ( RET-670 )

    The basis for this settings when derived from the over excitation limits ( V/Hz - ratio lim

    found to be extremely high or extremely low , such as ( f > becomes 55 Hz. & f < becomes

    Regulatory Rules bound to that region. We request M/s Customer to do this setting at site

    6) 27 & 59 - Protection. : ( REXEG-21 )

    These settings are based on the common practice adopted at most of the installations. Als

    India. The values adopted are --- 110% of the 110V = 121 volts. ( PT -secondary Rated-

    ---- 70% of the 110V = 77 Volts ( PT -secondary Rated-val

    7) 50/51, 50N/51N, 67 & 67N - Protection. : ( Rex-521)

    These settings are based on the relay co-ordination study , and direction is also based on

    relay cordination timings , then the Directional - OCR shall be graded fastly to look towards

    time delay. Also, the current settings for these Relays are the full-load current of the Equip

    TMS , needs a DETAILED STUDY.

    Calculat ions for REFR -LV :

    Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) sh

    IfL -LV = 15690 A , CTR= 2000/1 A

    Nct -Ratio = 2000 /1A

    Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chan

    Excitation current for NCT < 30 mA @ Vk / 4.

    If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expecte

    Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 18

    As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of pro

    Us =Uk /2 = 95 volts.=95 V (approx.)

    Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.

    The setting to adopted is = 115% of Us> = 1.15 x 101 = 117 (Approx.) volts.

    Calculation of Stabilizing Resistor :As per manuals of RET ,

    This can be directly selected to a value Rs=450 ohms .

    Now , this value of resistor should satisfy the below eqn.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }

    Ir = Current through the Relay @ voltage Us> = 117/450 = 260 mA .

    Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.

    nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.

    Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 3000{ 260+5+218 } =

    This is well below the value minimum fualt current, and only constitute 48.3 % of Rated C

    Also,

    As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A

    so, the setting is safe.

    Hence, the Stabilizing Resistor , Rs= 450 ohms. & Us>= 117 volts.